Read this document carefully before using this device. The guarantee will be expired by
damaging of the device if you don't attend to the directions in the user manual. Also we don't
ENDA EC762F UP/DOWN COUNTER
Thank you for choosing ENDA EC762F COUNTER.
* 72x72mm sized.
* 2x6 digits display.
* Easy to use by front panel keypad.
* Counting up and down with a 2 channel inputs having 90° phase shift.
* Input frequency can be selectable.
* Prescaler factor can be adjusted between 0.001 and 99.9999.
* 6 digits Batch Counter.
* 6 digits Total Counter.
* Preset1 may depend on Preset2.
* Decimal point can be adjusted between 1. and 5. digits.
* Sensor type can be selected as PNP, NPN or Encoder.
* Double set-points control is made by 2 relays outputs.
* Output can be energized continuously or just for a time interval of 0.01
to 999.9 seconds.
* Selectable functional reset input.
* Input offset feature.
* Parameter access protection on 3 levels.
* Easy connection by removable screw terminal.
EC762F
OUT1
SET
* Having CE mark according to European Norms.
PRESET
Order Code : EC762F-
1
1 - Supply Voltage
230VAC...230V AC
24VAC.....24V AC
SM...........9-30V DC / 7-24V AC
ENDA
TOTAL
RESET
PRESET UP/DOWN COUNTER
TECHNICAL SPECIFICATIONS
ENVIRONMENTAL CONDITIONS
Ambient/storage temperature 0 ... +50°C/-25 ... +70°C (with no icing)
80% up to 31°C decreasing linearly 50% at 40°C.
Max. relative humidity
According to EN 60529
Front panel : IP65
Rated pollution degree
Rare panel : IP20
Height
Max. 2000m
Do not use the device in locations subject to corrosive and flammable gases.
up to date: 23082010, modification reserved and can be change any time previous notice !
ELECTRICAL CHARACTERISTICS
Supply
Power consumption
Wiring
Date retention
EMC
Safety requirements
230VAC +10%/-20%, 50/60Hz, 24VAC±10%,50/60Hz or 24Vac/dc (9-30Vdc or 7-24Vac)
Max. 7VA
2.5mm² screw-terminal connections
EEPROM (Min. 10 years)
EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B for the EMC standard)
EN 61010-1: 2001 (pollution degree 2, overvoltage category II)
INPUTS
Count inputs (CP1, CP2)
Frequency (Hz)
Minimum On ans Off times
for pulses
Reset input
2 channels (Max. 7500Hz, 5V to 30V pulse)
25, 500, 1000, 2000, 5000, 7500Hz (selectable by programming)
20ms for f=25Hz
1ms for f=500Hz
500ms for f=1kHz
250ms for f=2kHz
100ms for f=5kHz
67ms for f=7,5kHz
PNP: Positive reset (5V to 30V pulse with adjustable pulse time between 2ms and 50ms)
NPN: GND terminal is connected to the RESET IN terminal.
OUTPUTS
Relay : 250V AC, 2A (for resistive load), NO+NC
Open collector output (S.S. OUT1): Max. 30V DC, 100mA.
Relay : 250V AC, 2A (for resistive load), NO+NC
Control output (OUT2)
Open collector output (S.S. OUT2): Max. 30V DC, 100mA.
12V DC, Max. 50mA (without regulation)
Auxiliary power supply
Mechanical 30.000.000 operation; Electrical 300.000 operation.
Life expectancy for relays
Note : Relay and S.S.OUT outputs are in synchronization . When OUT1 relay is energized S.S. OUT1 transistor goes into saturation.
Similarly, when OUT2 relay is energized S.S. OUT2 transistor goes into saturation.
Control output (OUT1)
HOUSING
Housing type
Dimensions
Weight
Enclosure material
Suitable for flush-panel mounting according to DIN 43 700.
W72xH72xD97mm
Approx. 405g (after packing)
Self extinguishing plastics
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
1/5
1./5
EC762F-E
TERMS
EC762F
(1) The value of the parameter selected by disp. parameter during run mode.
config
Parameter name during programming mode.
(2) The value of the parameter selected by disp. parameter during run mode.
config
Parameter value during programming mode.
(3) State indicators shows the state of the counter.
(4) To see the total result press this key in the run mode.
Increment or parameter selection key during programming mode.
(5) Reset key in the run mode.
Decrement or parameter selection key during programming mode
(6) Used for selecting preset value in the run mode.
Used for selecting oPtion. s or parameter to be changed in the programming mode.
(7) Used for selecting run or programming modes or for adjusting parameters.
OUT
SET
PRESET
ENDA
TOTAL
RESET
PRESET UP/DOWN COUNTER
( 1 ) Digital display
( 2 ) Digital display
6 digits, seven segment red LED
6 digits, seven segment yellow LED
Digital display (1) : 9.1mm
Digital display (2) : 7.1mm
4 red LEDs
Character height
( 3 ) State indicators
( 4 ),( 5 ),( 6 ),( 7 ) Keypad
Micro switch
Depth
DIMENSIONS
Panel cut-out
97mm
2
75mm
+0.7
mm
+0.7
mm
68
68
OUT
SET
PRESET
ENDA
TOTAL
RESET
84mm
78mm
72mm
EC762F
PRESET UP/DOWN COUNTER
Connection
cables
For removing mounting clamps:
- Push up the flush-mounting
clamp in direction 1 as
shown in the figure above.
- Then, pull out the clamp in
direction 2.
1
1
2
Note 1) While panel mounting, additional distance required for
connection cables should be considered.
2) Panel thickness should be maximum 10mm.
3) If there is no 90mm free space at back side of the device,
it would be difficult to remove it from the panel.
Flush mounting
clamp
Panel
Rubber packing
CONNECTION DIAGRAM
ENDA EC762F is intended for installation in control panels. Make sure that the device is used only for intended
purpose. The shielding must be grounded on the instrument side. During an installation, all of the cables that are
connected to the device must be free of energy. The device must be protected against inadmissible humidity,
vibrations, severe soiling and make sure that the operation temperature is not exceeded. All input and output
lines that are not connected to the supply network must be laid out as shielded and twisted cables. These cables
should not be close to the power cables or components. The installation and electrical connections must be
11
230V AC +10% -20%
50/60Hz 7VA
11
24V AC ±10%
50/60Hz 7VA
12
13
4 RESET IN
OUT1
AC 250V 2A
RESISTIVE
LOAD
13
14
4 RESET IN
OUT1
AC 250V 2A
RESISTIVE
LOAD
15
5 S.S. OUT2
10 +12V 50mA
14
184-253V AC 11
50/60Hz 7VA 12
Switch
Line
Neutral
230V AC Supply
Fuse should
be connected.
Cable size: 1,5mm²
5 S.S. OUT2
OUT2
AC 250V 2A
RESISTIVE
7 CP2 INPUT LOAD
9 GND
Fuse
F 100 mA
250V AC
15
16
6 S.S. OUT1
8 CP1 INPUT
NOTE :
12
17
18
ENDA
INDUSTRIAL
ELECTRONICS
EC762F
SN: XXXXXXXXX
16
6 S.S. OUT1 OUT2
AC 250V 2A
RESISTIVE
7 CP2 INPUT LOAD
8 CP1 INPUT
9 GND
10 +12V 50mA
17
18
Note : 1) Mains supply cords shall meet the requirements of IEC 60227
or IEC 60245.
2) In accordance with the safety regulations, the power supply
switch shall bring the identification of the relevant instrument
ENDA
INDUSTRIAL
ELECTRONICS
EC762F-24AC
SN: XXXXXXXXX
Holding screw 0.4-0.5Nm
Equipment is protected throughout
by DOUBLE INSULATION.
2./5
EC762F-E
SET
SET
Equ.
PrSEt1.
RESET
conFýG.
tot.Cr.
RESET
tý.
out2
RESET
tý.
out1
RESET
typE
outPut.
RESET
1.00000
SET
1.00000
NOTE 3 To change the position of the decimal point press and hold both
key and use
PRESET
SET
= Totalizer counts out2 .
RESET
out
dýsP.
RESET
dAtA
oFFSEt
CAL.
dýsP.
RESET
Poýnt
dEcý.
RESET
oPtýon.
See NOTE 2 for modification.
Pr2.Sub. = The difference between PrSEt2 and PrSEt1 becomes the new
Pr1.
value of PrSEt1'. It means PrSEt1 (new) = PrSEt2 - PrSEt1(old)
Now, output is energized when counter reaches PrSEt1(new) value.
SET
keys for 0.6 sec.
SET
1.01000
and
SET
RESET
RESET
1.00000
keys together.
key, the value of the selected parameter can be changed by
key. And then, press both
1.00000
SET
PRESET
PRESET
and
conFiG.
5
0.050
second
5000
Hert.
UP
Ph-4
dýsP.
PrSEt1 = Output is energized when counter reaches PrSEt1 value.
See NOTE 2 for modification.
inPut
out2
= Totalizer counts out1 .
inPut = Counter input is selected as Totalizer counter input.
Countr.
diSAb. = Totalizer counter parameter becomes active.
999.9 seconds.
If it is made 0.0, output is energized continuously when
counter reaches PrSEt2 value.
See NOTE 1 for modification.
See NOTE 3 for changing the position of the decimal point.
Out2 energizing time can be adjusted between 000.0 and
inPut
out1
keys.
SET
RESET
SET
PRESET
inPut
out2
conFiG.
4
0.020
second
2000
Hert.
CP2.dir.
CP1-UP
999.9 seconds.
If it is made 000.0 output is energized continuously when
counter reaches PrSEt1 value.
See NOTE 1 for modification.
See NOTE 3 for changing the position of the decimal point.
keys. In order to reset all the digits, first press and hold
SET
inPut
out1
inPut
Countr.
Out1 energizing time can be adjusted between 000.0 and
key the value of the selected parameter is seen on the display. While holding
RESET
diSAb.
tot.Cr.
conFiG.
999.9
999.9
conFiG.
3
0.010
second
Encod.
1000
Hert.
CP2-Gt.
CP1-UP
.............
............
conFiG.
2
0.005
second
PnP
500
Hert.
oPPoS.
Pr2.Sub.
PrSEt1.
Pr1.
000.0
out2
ti.
PrSEt1.
Equ.
000.0
conFiG.
1
outPut
typE
out1
ti.
0.002
second
rESEt
PuLS
nPn
25
Hert.
SEnSor
tyPE
dirEct
CP2-UP
CP2-dn
inPut
Frq.
CP1-UP
CP1-UP
Countr.
dir.
inPut
typE
There are eleven different output types. A schematic
diagram of output types is at the next page.
See NOTE 2 for modification.
key, the
PARAMETER MODIFICATION DIAGRAM
The minimum pulse duration of the
external RESET input can be selected.
See NOTE 2 for modification.
Sensor type can be selected.
See NOTE 2 for modification.
Input frequency can be selected.
See NOTE 2 for modification.
Counting direction can be selected
dirEct. or oPPos. A schematic
diagram of counting directions
according to the selected input types
is at the next page.
There are seven different
input types. A schematic diagram of
counting modes according to the input
types is at the next page.
See NOTE 2 for modification.
NOTE 2 To modify non-mumerical parameters, hold
Selected
numerical
parameter
PRESET
using
NOTE 1 Holding
Puls
Reset
RESET
tyPE
SEnSor
RESET
Frq.
ýnPut
RESET
dýr.
Countr.
RESET
typE
ýnPut
RESET
OutPut
PRESET
programming mode is entered.
PRESET
key is pressed while holding
oPtýon.
PRG
if
Second preset value.
See NOTE 1 for modification.
First preset value.
See NOTE 1 for modification.
ýnPut
SET
150000
PrSEt2
100000
PrSEt1
The value of the parameter selected by disP..
config
parameter is on the display.
oPtýon.
PRESET
99999
100000
INPuT oPTIoN.
OuTPuT oPTIoN.
Run mode
conFiG.
8
PRESET
conFiG.
9
conFiG.
10
conFiG.
bAtch
nonE
nonE
SECUr.
codE
inP.opt
SECUR.
out.opt.
SECUR.
dEFAuL.
SEt.
bAtch
rESEt
totAL.
rESEt
3./5
EC762F-E
= Upper display shows maximum totAL counter
value,
lower display minimum totAL counter value.
totAL.h
totAL.L
See NOT 2 for modification.
= Upper display shows PrSEt1 value,
lower display shows bAtch value.
= Upper display shows bAtch value,
lower display shows PrSEt2 value.
= Upper display shows counting value,
lower display shows bAtch value.
= Upper display shows counting value,
lower display shows PrSEt2 value.
= Upper display shows counting value,
lower display shows PrSEt1 value.
PrSET1
bAtch
bAtch
PrSEt2
Countr.
bAtch
Countr.
PrSEt2
Countr.
PrSEt1
offset value can be adjusted between 0 and 500000.
It means counter starts counting from the offset value
when it is reset.
See NOTE 1 for modification.
..............
Set.
dEfaul.
RESET
rESEt
bAtch
RESET
rESEt
totAL
RESET
rESEt
Count.
RESET
SECUR.
dýs.opt.
RESET
SECUR.
out.opt.
RESET
SECUR.
ýnP.opt.
PRESET
reset
both
bAtch
PrSEt2
0.00000
PrSEt1
bAtch
totAL.h
totAL.L
Prog.
no
Prog.
yES
nonE
Prog.
yES
Prog.
no
nonE
Prog.
yES
Prog.
no
nonE
no
key.
= totAL counter can be reset by
= batch counter can be reset by
While leaving the programming mode,
See NOTE 2. for modification.
no
= All the modifications are saved.
Yes = Default values are set to parameters.
RESET
= batch counter can not be reset.
RESET
= totAL counter can not be reset.
key.
key.
= Both RESET input and the
key can
RESET
be used for resetting.
See NOTE 2. for modification.
PAnEL
rESEt
RESET
= Counter can be reset by the RESET input.
See NOTE 2. for modification.
PAnEL
rESEt
no
reset
both
reSEt
inPut.
= Counter can be reset by
= Counter can not be reset.
= Menu is seen and programming is possible.
See NOT 2. for modification.
= No menu is seen.
= Menu is seen but can not be programmed.
= Menu is seen and programming is possible.
See NOT 2. for modification.
= No menu is seen.
= Menu is seen but can not be programmed.
= Menu is seen and programming is possible.
See NOT 2. for modification.
= No menu is seen.
= Menu is seen but can not be programmed.
Access code for entering security option menu.
This parameter should be 1111.
See NOTE 2 for modification.
no
PAnE.
reSEt
yES
PAnEL
rESEt
PAnEL
rESEt
rESEt
inPut
Prog.
no
PAnEL
rESEt
Prog.
yES
Prog.
yES
Prog.
yES
Countr.
bAtch
500000
99.9999
.............
Prog.
no
Prog.
no
Countr.
PrSEt2
RESET
codE
SECUr.
RESET
oPtýon.
SECUr.
no
no
no
no
nonE
1111
diSP.
config
diS.opt.
SECUR.
Count.
rESEt
0
Countr.
PrSEt1
oFFSEt
dAtA
0.00001 .............
diSP.
CAL.
0.0
0
dEci.
Point
Calibration (Prescaler) value can be adjusted between
0.00001 and 99.9999. Counter multiplies the number of
pulses by the prescaler value and the result is displayed
on the screen.
See NOTE 1 for modification.
See NOTE 3 for changing the position of the decimal point.
Decimal point can be adjusted between 1. and 5. digits.
If desired, decimal point is not included.
See NOTE 2 for modification.
conFiG.
6
conFiG.
7
Ph-2
7500
Hert.
UP-dn
Ph-1
PARAMETER TABLE
UP-dn
DisP. oPTIoN.
SECUr. oPTIoN.
H
L
H
L
H
L
H
L
H
L
H
L
H
L
H
L
H
L
H
L
n
n
n
n
n
n
n
n+1
n+1
n+1
n+1
n+1
n+1
n+1
n+2
n+2
n+2
n+2
n+2
n+2
n+3
n+2
n+3
n+3
n+3
n+3
n+3
n+3
n+2
n+3
H
L
H
L
DISPLAY
C o u n t
input CP1
C o u n t
input CP2
n
n-1
n-2
n-3
n+6
DISPLAY
H
L
H
L
n
n-1
n-2
n-3
n+5
n+3
n+6
n+2
n+7
n+3
n+8
H
L
H
L
H
L
H
L
DISPLAY
C o u n t
input CP1
C o u n t
input CP2
DISPLAY
C o u n t
input CP1
dirction
input CP2
DISPLAY
H
L
H
L
n
n
n
n-1
n-1
n-1
n-2
n-2
n-2
n-3
n-3
n-3
n+5
n+4
n+2
n+3
n+2
n+1
DISPLAY
C o u n t
input CP2
C o u n t
input CP1
H
L
H
L
DISPLAY
H
L
H
L
n
n
n-1
n-1
n-2
n-3
n-2
Note: The maximum value of the input frequency can be
2/3 of the selected value (inPut. Frq.)
n+4
n+3
C o u n t
input CP1
C o u n t
input CP2
Note: The maximum value of the input frequency can be
1/3 of the selected value (inPut. Frq.)
n+4
n+4
n+4
C o u n t
input CP1
G a t e
input CP2
Note: The maximum value of the input frequency can be
one half of the selected value (inPut. Frq.)
n+5
n+7
C o u n t
input CP1
C o u n t
input CP2
n-4
n-4
n-4
n-5
n-4
oPPoS.
Note: The maximum value of the input frequency can be
one half of the selected value (inPut. Frq.)
n+4
dirEct.
For NPN sensor counter is triggered at the falling edge of the pulses.
For PNP sensor, counter is triggered at the rising edge of the pulses.
DISPLAY
H
L
H
L
DISPLAY
C o u n t
input CP1
C o u n t
input CP2
DISPLAY
C o u n t
input CP1
C o u n t
input CP2
DISPLAY
C o u n t H
input CP1 L
direction H
input CP2 L
DISPLAY
C o u n t
input CP1
G a t e
input CP2
DISPLAY
C o u n t
input CP1
C o u n t
input CP2
DISPLAY
C o u n t
input CP1
C o u n t
input CP2
C o u n t
input CP1
C o u n t
input CP2
NOTE :
UP-dn
Ph-2
UP-dn
Ph-1
UP
Ph-4
CP1-UP
CP2.dýr
CP1-UP
CP2-Gt
CP1-UP
CP2-UP
CP1-UP
CP2-dn
inPut
tyPE
Countr.
dir.
INPUT TYPES
n-5
n-3
n-5
n-3
n-6
n-3
n-4
n-2
n-6
n-2
n-2
n-3
n-7
n-4
n-7
n-2
n-1
n-8
999,999
Reset
Countr.
= dirEct
dir.
Out2
Out1
0
Preset1
Preset2
Config 999,999
7
Reset
Out2
Out1
0
Preset1
Preset2
Config 999,999
6
Reset
Out2
Out1
0
Preset1
Preset2
Config 999,999
5
Reset
Out2
Out1
0
Preset1
Preset2
Config 999,999
4
Reset
Out2
Out1
0
Preset1
Config Preset2
3
999,999
Reset
Out2
Out1
0
Preset1
Config Preset2
2
999,999
Reset
Out2
Out1
0
Preset1
inPut CP1-UP CP1-UP UP
=
,
,
typE
CP2-UP CP2-Gt. Ph-4
Countr.
= oppos.
dir.
DOWN COUNTER
OUTPUT TYPES
Input frequency should not exceed the values indicated
n-3
UP COUNTER
CP1-UP
CP1-UP
inPut
= CP2-UP , CP2-Gt. , UP
typE
Ph-4
Config Preset2
1
(HOLD)
(Autoreset)
(Delayed
Autoreset)
(Delayed
Autoreset
and HOLD)
(Autoreset and
Display hold)
inPut CP1-UP CP1-UP UP-dn UP-dn
typE = CP2-dn , CP2.dir. , Ph-1 , Ph-2
UP / DOWN COUNTER
Config
bAtch
Config
bAtch
Out2
Out1
-99,999
Reset
999,999
Preset2
Preset1
0
Out2
Out1
-99,999
0
999,999
Preset2
Preset1
Reset
Out2
Out1
-99,999
999,999
Preset2
Preset1
0
Out2
Preset2
Batch
Counter 0
Out1
0
Reset
999,999
Preset1
Countr.
= oPPos.
dir.
Out2
Preset2
Batch
Counter 0
Out1
0
Reset
999,999
Preset1
Countr.
= dýrEct.
dir.
ti.
ti.
ti.
4./5
EC762F-E
Adjusting out1 or out2 to 0.0, a continuous output is obtained.
a pulse output is obtained.
ti.
While counting value
is greater or equal to
the Preset1 and
Preset2 values,
OUT1 and OUT2
becomes active
While counting value
is lower or equal to
the Preset1 and
Preset2 values,
OUT1 and OUT2
becomes active
While counter is
equal to Preset1
and Preset2 values,
OUT1 and OUT2
becomes active
Adjusting out1 or out2 to a value between 0.01 and 999.9 seconds,
While Batch counter mode is selected, decimal point is not seen.
Because, Prset2 and batch counting values are integer.
Config
10
Config
9
Config
8
Reset
inPut CP1-UP CP1-UP UP-dn UP-dn
typE = CP2-dn , CP2.dir. , Ph-1 , Ph-2
OUTPUT TYPES
TERMINAL CONNECTIONS
Terminal descriptions
11
230V AC +10% -20%
50/60Hz 7VA
4 : Reset input.
5 : Solid state out2 (Max 30V 100mA open collector NPN)
6 : Solid state out1 (Max 30V 100mA open collector NPN)
7 : Input for clock pulse 2 (Max 30V 7.5kHz)
8 : Input for clock pulse 1 (Max 30V 7.5kHz)
9 : GND
10 : +12V 50mA auxiliary power supply for sensors.
11,12 : SUPPLY inputs.
13,14,15 : 1. relay output (Max 2A 250V AC)
16,17,18 : 2. relay output (Max 2A 250V AC)
12
13
4 RESET IN
OUT1
AC 250V 2A
RESISTIVE
LOAD
14
15
5 S.S. OUT2
16
6 S.S. OUT1
OUT2
AC 250V 2A
RESISTIVE
7 CP2 INPUT LOAD
18
8 CP1 INPUT
ENDA
INDUSTRIAL
ELECTRONICS
EC762F
9 GND
10 +12V 50mA
17
SN: XXXXXXXXX
TYPICAL SENSOR CONNECTIONS
Fuse
F 100 mA
250V AC
Switch
11
230V AC +10% -20%
50/60Hz 7VA
230V AC Supply
12
Cable size: 1,5mm²
13
4 RESET IN
OUT1
AC 250V 2A
RESISTIVE
LOAD
14
15
5 S.S. OUT2
PNP PROXIMITY SWITCH
16
6 S.S. OUT1 OUT2
AC 250V 2A
RESISTIVE
7 CP2 INPUT LOAD
OUT
8 CP1 INPUT
GND
9 GND
+ 12V
17
18
ENDA
INDUSTRIAL
ELECTRONICS
EC762F
10 +12V 50mA
SN: XXXXXXXXX
Fuse
F 100 mA
250V AC
Switch
11
230V AC +10% -20%
50/60Hz 7VA
230V AC Supply
12
Cable size: 1,5mm²
13
4 RESET IN
OUT1
AC 250V 2A
RESISTIVE
LOAD
14
15
5 S.S. OUT2
PNP PROXIMITY SWITCH
16
6 S.S. OUT1 OUT2
AC 250V 2A
RESISTIVE
7 CP2 INPUT LOAD
OUT
OUT
GND
PNP PROXIMITY SWITCH
GND
ENDA
INDUSTRIAL
ELECTRONICS
EC762F
9 GND
+ 12V
17
18
8 CP1 INPUT
10 +12V 50mA
SN: XXXXXXXXX
+ 12V
Fuse
F 100 mA
250V AC
Switch
11
230V AC +10% -20%
50/60Hz 7VA
12
13
4 RESET IN
OUT1
AC 250V 2A
RESISTIVE
LOAD
230V AC Supply
Cable size: 1,5mm²
14
15
5 S.S. OUT2
ENCODER
16
B OUT
A OUT
GND
6 S.S. OUT1 OUT2
AC 250V 2A
RESISTIVE
7 CP2 INPUT LOAD
8 CP1 INPUT
17
18
ENDA
INDUSTRIAL
ELECTRONICS
EC762F
9 GND
+ 12V
10 +12V 50mA
SN: XXXXXXXXX
NOTE: NPN PROXIMITY SWITCH connection is the same as PNP PROXIMITY SWITCH connection.
SURAN Industrieelektronik
Dettinger Str. 9 / D-72160 Horb a.N
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
E-mail : [email protected]
Internet : www.suran-elektronik.de
5./5
EC762F-E