Eaton S225-10-10 McGraw-Edison VR-32 Regulator and CL-5 Servies Control Instructions
Advertisement
Advertisement
Voltage Regulators
McGraw-Edison
®
VR-32 Regulator and CL-5 Series
Control Installation, Operation and Maintenance
Instructions and Parts Replacement Information
Service Information
S225-10-10
Contents
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Receiving, Installation and Maintenance . . . . . . . 1-1
Control Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Control Function Codes . . . . . . . . . . . . . . . . . . . . . 3-1
Control Advanced Features . . . . . . . . . . . . . . . . . . 4-1
Tap Changer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . 6-1
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Spare Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
General
McGraw-Edison ® VR-32 voltage regulators are regulating auto-transformers. They regulate rated voltage from 10% raise (boost) to 10% lower (buck) in 32 approximately 5 /
8 percent steps.
McGraw-Edison regulators are supplied with the following standard features:
• Dual-rated 55/65°C rise
• ADD-AMP™ capability
• Unit construction
• Sealed-tank construction
• Pressure relief device
• 17” minimum creep bushings with clamp-type connectors
• MOV-type external series arrester
• Shunt arrester mounting bosses
• Two laser-etched nameplates
• Oil sight gauge
• Upper filter press connection
• Drain valve and oil-sampling device
• CE mark compliant control
• Control cable quick disconnect
The 65°C rise insulation system and the sealed-tank construction allow for a bonus capacity 12% above the
55°C nominal rating without loss of normal insulation life. The bonus capacity is stated on the nameplate
(such as 167/187 kVA for a nominal 167 kVA regulator).
All McGraw-Edison regulators are manufactured and tested to ANSI standard C57.15.
Unit construction, which suspends the internal assembly from the cover, allows for ease of inspection and maintenance.
There are three types of step-voltage regulators: sourceside series winding (Type B), load-side series winding
(Type A), and series transformer. McGraw-Edison regulators are usually equipped with an equalizer winding. The nameplates located on the tank and control box define the power circuit.
Figure 1.
VR-32 Voltage Regulator with CL-5 Series Control
These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide directions for meeting every possible contingency during installation, operation or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user’s purpose, please contact your Cooper Power Systems representative.
October 2001 • Supersedes 12/00 • © 2001 Cooper Power Systems, Inc.
Printed in U.S.A.
McGraw-Edison VR-32 Regulator and CL-5 Series Control
2
SAFETY FOR LIFE
Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture, marketing, and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment and support our “Safety For Life” mission.
SAFETY INFORMATION
The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it.
A competent technician has these qualifications:
• Is thoroughly familiar with these instructions.
• Is trained in industry-accepted high-and low-voltage safe operating practices and procedures.
• Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment.
• Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc.
Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings.
Safety Instructions
Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual.
DANGER: Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high voltage lines and equipment.
WARNING: Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual.
Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage.
Hazard Statement Definitions
This manual may contain these four types of hazard statements:
DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only.
WARNING: This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury and equipment damage.
WARNING: Power distribution equipment must be selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain this equipment can result in death, severe personal injury, and equipment damage.
MOV-TYPE SERIES
ARRESTER
JUNCTION BOX
HANDHOLE COVER
COVER
POSITION INDICATOR
AUTOMATIC
PRESSURE RELIEF
DEVICE
CONTROL CABLE WITH
DISCONNECT PLUG
POLE MOUNTING
BRACKETS
LOCKABLE CONTROL
ENCLOSURE
CONTROL
BOLT-DOWN PROVISIONS (4)
Figure 2.
External Features of the VR-32 Voltage Regulator
S225-10-10
CLAMP-TYPE CONNECTORS
THREADED-STUD
BUSHING TERMINALS
BUSHINGS
INTERNAL ASSEMBLY
LIFTING EYES
UPPER FILTER PRESS
CONNECTION
REGULATOR LIFTING LUGS
SHUNT ARRESTER
MOUNTING BOSSES
(3 PER BUSHING)
BALL-TYPE OIL
SIGHT GAUGE
LASER-ETCHED
NAMEPLATES (2)
(SECOND ON CONTROL
ENCLOSURE DOOR)
PANEL-TYPE RADIATORS
CONDUCTOR
STABILIZING BOSS
GROUND BOSSES (2)
DRAIN VALVE & OIL
SAMPLING DEVICE
3
McGraw-Edison VR-32 Regulator and CL-5 Series Control
Receiving, Installation and Maintenance
Receiving
Inspection
Prior to shipment, the regulator is thoroughly tested and inspected at the factory. Immediately upon receipt of the regulator shipment, before unloading, a thorough inspection should be made for damage, evidence of rough handling or shortages. The position indicator, junction box, arrester, radiators and bushings should all be inspected for evidence of damage. Should this initial inspection reveal evidence of rough handling, damage, or shortages, it should be noted on the bill of lading and a claim should immediately be made with the carrier. Also, notify Cooper Power Systems,
2300 Badger Drive, Waukesha, Wisconsin 53188, attention Service Manager.
Unloading
When an overhead crane is used for unloading, the regulator must be lifted by means of a sling and
spreader bar utilizing the tank-mounted lifting lugs which are shown in Figure 2. Do not lift the entire
unit with the lifting eyes on the cover. The lifting eyes are only to be used to untank the internal assembly which is attached to the cover.
CAUTION: Do not subject tap changer to temperatures above 150°F (66°C). To do so may cause damage to the contact panels, resulting in misalignment of the contacts.
regulator and filter oil before putting unit in service.
See Table 1-5, page 1-12, for values that oil should meet. Be sure to properly replace handhole cover.
4. Check position indicator for damage. When cleaning the faceplate, do NOT use solvent or fuel.
5. If regulator has been stored for some time, test dielectric strength of oil according to
Table 1-5, page 1-12.
6. Regulator may be energized at rated voltage (with caution) and an operational check (see page 1-10) can be performed. (This procedure is optional.)
7. A high-potential test may be done to ensure adequate electrical clearances to ground. (This procedure is optional.)
WARNING: The cover may fracture if the cover-mounted lifting eyes are used to lift the entire unit. Lift the entire unit only with tank-mounted lifting lugs.
BYPASS SWITCH
Ø
N
DISCONNECTS
L
S
SHUNT
ARRESTERS
SL
SERIES
ARRESTER
Storing
If the regulator is not to be placed into immediate use, it can be stored with minimal precautions. Store the unit where the possibility of mechanical damage is minimized.
Installation
Pre-Installation Inspection
Before connecting the regulator to the line, make the following inspection:
1. Check oil sight gauge. Look for visible signs of oil leakage.
2. Examine series arrester for damage. If damaged, install a new arrester of same voltage rating.
3. Inspect porcelain bushings for damage or leaking seals. If there is a suspicion that moisture has entered unit, remove handhole cover and inspect for evidence of moisture such as rust or water tracks in oil. If moisture has entered that tank, dry
Figure 1-1.
Regulating a single-phase circuit
A
B
C
N
DISCONNECTS
BYPASS SWITCH
L
SHUNT
ARRESTERS
S
SL
SERIES
ARRESTER
Figure 1-2.
1-1
S225-10-10
WARNING: Connect the “S” bushing to the source, the “L” bushing to the load, and the
“SL” bushing to neutral. To do otherwise may cause excessively high or low voltage on the load side of the regulator or cause severe damage to the regulator.
Systems Connections
A regulator can regulate a single-phase circuit, or one phase of a three-phase wye (star) or delta circuit.
Two regulators connected phase-to-phase in open-delta, or three regulators connected phase-to-phase in closeddelta, can regulate a three-phase, three-wire circuit.
When connected in wye, three regulators can regulate a three-phase, four-wire multi-grounded wye circuit. Three regulators should not be connected directly in wye on three-phase, three-wire circuits because of the probability of neutral shift, unless the neutral is connected to the neutral of a wye-connected bank of distribution transformers or to the substation transformer secondary neutral. Typical connection diagrams are illustrated in Figures 1-1 through 1-5.
A
B
C
DISCONNECTS
BYPASS SWITCH
L
SL
SHUNT
ARRESTER
S
1
SERIES
ARRESTER
S
2
L
SL
Figure 1-3.
Regulating a three-phase, three-wire circuit with two regulators
A
B
C
N
DISCONNECTS
BYPASS SWITCH
BYPASS SWITCH
BYPASS SWITCH
L
L L
S S S
SHUNT
ARRESTER
SL SL SL
1 2
SERIES
ARRESTER
3
Figure 1-4.
Regulating a three-phase, four-wire, multi-grounded wye (star) circuit with three regulators
A
B
C
BYPASS SWITCH
BYPASS SWITCH
BYPASS SWITCH
DISCONNECTS
L
L L
S
SHUNT
ARRESTER
SERIES
ARRESTER
1
SL
S
2
SL S
3
SL
Figure 1-5.
Regulating a three-phase, three-wire circuit with three regulators
NOTE: Individual switches are shown for the bypass and disconnect functions. However, a regulator-bypass-disconnect switch can be used in each phase to perform the bypassing and disconnecting operations in sequence. Each of these switches replaces one bypass and two disconnect switches shown in the diagrams.
1-2
McGraw-Edison VR-32 Regulator and CL-5 Series Control
Mounting
A regulator can be mounted on a pole, crossarm platform or elevating structure. Regulators are normally provided with either pole mounting brackets or a substation base according to the rating. An elevating structure can be provided to simplify substation installation of regulators requiring a specific live part-toground clearance.
The regulator control can be mounted on the regulator tank, or at a point remote from the unit. Rubber-covered cable is available in 5 foot (1.52 m) incremental lengths from 15 feet (4.57 m) to 45 feet (13.7 m) for interconnection between the control and the regulator.
Placing a Regulator in Service
Regulators can be placed in service without interrupting load continuity once bypass and disconnect switches are installed.
WARNING: Closing the bypass switch with the tap changer in any position other than neutral will short-circuit part of the series winding.
Before closing the bypass switch, the regulator must be in neutral, the control switch set to OFF and the motor circuit fuse removed.
Procedure A should be followed when one bypass switch and two disconnect switches are used. Procedure
B should be followed when a regulator bypass-disconnect switch is used.
A ground pad tapped for 1/2 inch 13 NC thread is provided on the side of the control cabinet.
WARNING: For the protection of personnel from surges while operating the control, the following control enclosure grounding procedures should be followed:
If the enclosure is attached to the regulator tank or is remote from the tank but only accessible with a ladder, then the enclosure should be connected to the regulator-to-ground rod conductor.
If the enclosure is accessible by personnel standing on the ground, then the enclosure should be directly connected to a ground mat and ground rod.
When energizing the control from an external source, use only a 120 V ac source, unless the control is set up for 240 volts, indicated by a decal adjacent to the terminals.
KNIFE
SWITCHES
Figure 1-6.
Back panel
RCT
CAUTION: Only an ac power supply is to be used to energize the control externally; direct current (dc) to alternating current (ac) inverters are not to be used due to excessive harmonics that can be generated, resulting in damage to the front panel.
CAUTION: Be mindful of polarity when using an external source. Polarity reversal may result in control damage.
1-3
S225-10-10
Procedure A: One Bypass Switch and
Two Disconnect Switches
1. Verify from regulator nameplate that control circuit is connected for proper regulated system voltage.
2. Set power switch to OFF and control switch to OFF.
3. Knife switches on back panel should be set with V
1
(potential switch) (and V
6 if present) closed (pushed in), and C (CT shorting switch) open (pulled out).
See Figure 1-6.
4. Close source-load (SL) disconnect switch if available.
5. Close source (S) disconnect switch.
6. Set power switch to INTERNAL and control switch to MANUAL.
7. Lift raise-lower switch to operate tap changer two or three steps, then depress raise-lower switch to return tap changer to the neutral position.
(These steps verify that the mechanism is functional.) When on neutral, neutral light will glow continuously and position indicator will point to zero.
8. With regulator in neutral position, set control switch to OFF, set power switch to OFF, open V switch (and V
6
1 knife if present), and remove 6 A motor fuse.
9. Close load (L) disconnect switch.
10. Open bypass switch. The regulator is now energized.
11. Replace 6 A motor fuse, close V
1 set power switch to INTERNAL.
knife switch and
12. Go to Setting the Control for Service, following.
Procedure B: Regulator Bypass-
Disconnect Switch
1. Verify from regulator nameplate that control circuit is connected for proper regulated system voltage.
2. Set control switch to MANUAL and power switch to
EXTERNAL.
3. Knife switches on back panel should be set with V
1
(potential switch) (and V
6 if present) open (pulled out), and C (CT shorting switch) closed (pushed in).
See Figure 1-6.
4. Apply 120 V (or other voltage as indicated by the decal) to external source terminals, if available. If not, proceed to Step 7, below.
5. Lift raise-lower switch to operate tap changer two or three steps, then depress raise-lower switch to return tap changer to neutral position. (These steps verify that the mechanism is functional.) When on neutral, neutral light will glow continuously and position indicator will point to zero.
6. Remove the voltage from external source terminals.
7. With regulator in the neutral position, set control switch to OFF, set power switch to OFF, and remove 6 A motor fuse.
8. Close source-load (SL) disconnect switch. (Delta applications only.)
9. Close regulator bypass-disconnect switch. The regulator is now energized.
10. Replace 6 A motor fuse, close V
1 knife switch (and
V
6 if present), open C knife switch, and set power switch to INTERNAL.
11. Go to Setting the Control for Service, following.
Setting the Control for Service
There are more than 50 parameters on the control which are user-selectable. Many of these values pertain to the operation of the advanced features that are not needed for normal regulator operations. A full detailed description of each of the features is given in the Control
Advanced Features section, along with set-up instructions.
The control must be energized to perform the programming. This can be accomplished by applying
120 V (or other voltage as indicated by the decal) to the external source terminals and placing the power switch in the external position. Alternately, the regulator may be energized at line potential, and the power switch placed in the internal position. When power is applied to the control, all segments of the display will light, followed by a PASS indication. If the FAIL message is encountered, see Diagnostics, on page 2-5.
Accessing the Control
Before gaining access to change the control settings, the proper security level must be activated. This is accomplished by entering a security code at the
Function Code 99 location. Depress the following keys on the keypad:
FUNCTION, 99, ENTER
12121, ENTER
The proper level of security to change operational settings has now been activated.
All programming of the control is done through the keypad or communication ports.
For quick set-up of Cooper Power Systems regulators, see Table 1-1, page 1-5. For complete set-up, see
Table1-2, page 1-6 for a detailed checklist for control programming. The only two parameters this checklist does not address are voltage and current calibration,
Function Codes 47 and 48.
1-4
McGraw-Edison VR-32 Regulator and CL-5 Series Control
TABLE 1-1
Setting the Controls for Basic Operation
Security System
Keys to Depress
FUNCTION, 99, ENTER
12121, ENTER
F.C
99
Func
Display
_ _ _ _ _
_ _
Description
The security system is now activated for changing operational settings
Set Voltage
Range: 100.0 - 135.0 (Factory Setting: 120.0)
Keys to Depress F.C
1
Change
01
01
1220, ENTER 01
Display
120.0
_ _ _._c
122.0
Description
This is the set voltage as shipped from the factory
Enter the desired value. Example: 122.0
The set voltage is now 122.0 volts.
Bandwith
Range: 1.0 - 6.0 (Factory Setting: 2.0)
Keys to Depress F.C.
2
Change
30, ENTER
02
02
02
Time Delay
Range: 5 - 180 (Factory Setting: 30)
Keys to Depress F.C.
3
Change
03
03
45, ENTER 03
Display
2.0
_._c
3.0
Display
30
_ _ _c
45
Description
This is the bandwith as shipped from the factory
Enter the desired value. Example: 3.0
The bandwidth is now 3.0 volts
Description
This is the time delay as shipped from the factory
Enter the desired value. Example: 45
The time delay is now 45 seconds
Line Drop Compensation, Resistance
Range: -96.0 - +96.0 (Factory Setting: 0.0)
Keys to Depress F.C.
4
Change
50, ENTER
04
04
04
Line Drop Compensation, Reactance
Range: -96.0 - +96.0 (Factory Setting: 0.0)
Keys to Depress
5
Change
30, ENTER
F.C.
05
05
05
Display
0.0
_ _._c
5.0
Display
0.0
_ _._c
3.0
Regulator Configuration
Range: 0 - 2 (Factory Setting: 0 [Wye or Star])
Keys to Depress F.C.
Display
FUNCTION, 41, ENTER
Change
1, ENTER
41
41
41
0
_c
1
Description
This is the resistive compensation as shipped from the factory
Enter the desired value. Example: 5.0
The resistive compensation is now 5.0 volts
Description
This is the reactive compensation as shipped from the factory
Enter the desired value. Example: 3.0
The reactive compensation is now 3.0 volts
Control Operating Modes
Range: 0 - 2 (Factory Setting: 0 [Sequential])
Keys to Depress F.C.
FUNCTION, 42, ENTER
Change
42
42
1, ENTER 42
Display
0
_c
1
System Line Voltage
Range: 1200 - 36000 (Factory Setting: Regulator Rated Voltage)
Keys to Depress
FUNCTION, 43, ENTER
Change
7200, ENTER
F.C.
43
43
43
Display
7620
_ _ _ _ _c
1
Description
This is the control operating mode as shipped from the factory
Enter the desired value. Example: 1
The control operating mode is now Time Integrating
Description
This is the system line voltage for a 7620 volt regulator as shipped from the factory
Enter the desired value. Example: 7200
The system line voltage is now 7200 volts
Overall Potential Transformer Ratio
Range: 10 - 300 (Factory Setting: PT ratio for Regulator Rated Voltage)
Keys to Depress F.C.
Display Description
FUNCTION, 44, ENTER
Change
44
44
63.5
_ _ _._c
This is the overall PT ratio for a 7620 volt regulator as shipped from the factory
Enter the desired value. Example: 60.0
600, ENTER 44 60.0
The system line voltage is now 7200 volts
Calendar Clock
Range: 10 - 300 (Factory Default Setting XX)
Keys to Depress F.C.
FUNCTION, 50, ENTER
Scroll up
Scroll up
Change
50
50
50
50
00, ENTER
Scroll up
Change
10, ENTER
Scroll up
Change
24, ENTER
Scroll up
50
50
50
50
50
50
50
50
Change
14, ENTER
Scroll up
Change
30, ENTER
Scroll up
Change
45, ENTER
50
50
50
50
50
50
50
50
Display
1.01
x.xx
1d 90
1 _ _c
1 0
2 1
2 _ _c
2 10
3 1
3 _ _c
3 24
4 xx
4 _ _c
4 14
5 xx
5 _ _c
5 30
6 xx
6 _ _c
6 45
Description
This is the regulator configuration as shipped from the factory
Enter the desired value. Example: 1
The regulator configuration is now Delta Lag
Description
This is the default value for the date.
This is the present time (hour/minute).
This is the default value for the year, 1990.
Enter the desired value for Year. Example: 2000
The Year is now 2000.
This is the default value for the month, January.
Enter the desired value for Month. Example: October
The month is now October.
This is the default value for the Day 1.
Enter the desired value for the Day. Example 24.
The Day is now 24.
This is the present value for the Hour, xx.
Enter the desired value for Hour. Example: 2:00 P.M.
The Hour is now 14. Military Time.
This is the present value for the Minutes. Example: xx.
Enter the desired value for Minutes. Example: 30.
The Minutes is now 30.
This is the present value for the Seconds, xx.
Enter the desired value for Seconds. Example 45.
The Seconds is now 45.
1-5
S225-10-10
TABLE 1-2
CL-5 Series Control Programming Checklist
Step Activity/Question
A
B
Power up control or run Self Test (FC 91).
Access Security Level 3.
C
Set Voltage
Bandwidth
Time Delay Set the Forward Power Flow Control Settings --
LDC Resistance
LDC Reactance
Verify position indicator is in sync with tap changer by stepping D through the neutral position.
E Is the Control Tap Position in sync with the position indicator?
F Set the Control Tap Position.
G Is Source Side Voltage Calculation required?
H
I
Activate Source Side Calculation.
Set Type of Regulator. (A and Series Transformer =1; B=2)
J Change Control I.D.?
K Set Control I.D.
L Is regulator bank configuration closed or open delta?
M Refer to Determination of Leading or Lagging, page 1-7.
N Set Regulator Configuration.
O Change Operating Mode? (Factory set for sequential)
P Set Operating Mode.
Q Set System Line Voltage.
R Set Overall P.T. Ratio. (from Nameplate)
S Verify C.T. Primary Rating. (from Nameplate)
T Change Demand Time Interval?
U Set Demand Time Interval.
V Change Tap Changer selection?
W Set Tap Changer selection.
X Are date and time correct?
Year
Month
Y Set the required date and time by way of subfunctions- Day
Hour
Minute
Z
AA Verify Reverse Sensing Mode is set on Locked Forward (0).
Second
Should control be set up to react to a reverse power flow condition?
AB Verify the baud rate of Local Channel #1 (Data Reader) is set for 4800.
AC Set up Remote Communications Channel #2?
AD Set Remote Communications Function Codes as desired.
AE Verify the Blocking Status is normal.
AF Is Voltage Reduction required?
AG Set Voltage Reduction Function Codes as desired.
AH Is Soft Add-Amp required?
AI Activate Soft Add-Amp.
Set Add-Amp Raise Limit.
Set Add-Amp Lower Limit.
AJ Is Voltage Limiter required?
AK Set Voltage Limiter Function Codes as desired.
AL Set Profile Recorder Parameters.
AM Is Security Override required?
AN Set Security Override.
AO Change Security Codes?
AP Set Security Codes as desired.
AQ Reset Metering & Tap Position.
AR Take Data Reader reading (optional).
AS Press DISPLAY OFF key to return to Base Security Level.
AT CONTROL IS NOW FULLY PROGRAMMED.
Function
Code
99
1
2
3
4
5
Factory
Set
32123
120
2
30
0
0
Owner
Set
12P
12P
39
39
39-1
40
40
0
Control Serial No.
1
Nameplate value
76
77
79*
79*
79-1*
79-2*
80
80
64
65
66
67
68-1
68-2
69
70
70
72
73
74
75
81
82
85*
85-1
85-2
85-3
85-4
85-5*
92
92
96
97
98
38
50
50-1
50-2
50-3
50-4
50-5
50-6
44
45
46
46
41
42
42
43
49
49
56
60
0
0
Rated Voltage
Rated P.T.Ratio
Rated C.T. Primary
15
Nameplate value
0
4
0
0
0
0
0
1234
12121
32123
Nameplate value
1
1
Check
Next
Step
Pass = B; Fail = Refer to page 2-5
C
D
E
No = F; Yes = G
G
No = J; Yes = H
I
J
No = L; Yes = K
L
No = O; Yes = M
N
O
No = Q; Yes = P
Q
R
S
T
No = V; Yes = U
V
No = X; Yes = W
X
No = Y; Yes = Z
Z
No = AA; Yes = BA (Table 1-3)
AB
AC
No = AE; Yes = AD
AE
AF
No = AH; Yes = AG
AH
No = AJ; Yes = AI
AJ
No = AL; Yes = AK
AL
AM
No = AO; Yes = AN
AO
No = AQ; Yes = AP
AQ
AR
AS
AT
1-6
McGraw-Edison VR-32 Regulator and CL-5 Series Control
TABLE 1-3
CL-5 Series Control Programming Checklist for Reverse Power Flow Detection and Operation
Function Factory
Code Set
Owner
Set
BD
BE
BN
BO
BP
BQ
BR
BF
BG
BH
BI
BJ
BK
BL
Step
BA
BB
BC
BM
Activity/Question
Is voltage regulation required on the source and load side of regulator?
Is dispersed generation available on load side of regulator?
Is voltage regulation required on the source side of regulator during a reversal of power flow?
Is the load side of regulator dedicated to a Co-generation facility?
Is Tap to Neutral required for excursions below a reverse power threshold?
Set Reverse Sensing Mode to Reverse Idle.
Is source side metering required during a reversal of power flow?
Set Reverse Sensing Mode to Bi-directional.
Set Reverse Sensing Mode to Reactive Bi-directional
Set Reverse Sensing Mode to Lock Reverse.
Set Reverse Sensing Mode to Co-Generation.
Set Reverse Sensing Mode to Neutral Idle.
Set the Reverse Power Flow Control Settings -
Set Voltage
Bandwidth
Time Delay
LDC Resistance
LDC Reactance
Set Reverse Power Threshold (%)
Does regulator have an internal or external source side sensing voltage?
Activate Source Side Calculation.
Set Type of Regulator. (A and Series Transformer =1; B=2)
REQUIRED REVERSE MODE IS PROGRAMMED.
56
56
56
51
52
53
54
55
57
56
56
56
39
39-1
120
2
30
0
0
2
2
3
6
1
5
4
1
Nameplate value
Check
Delta-connected (Line-to-line)
Regulators
Determination of Leading or Lagging
For a regulator to operate properly when connected phase to phase, it is necessary for the control to be programmed with the correct regulator configuration in
Function Code 41. It must be determined whether it is connected “leading” or “lagging”. The control aids the operator in making this determination.
1. Regulator must be installed.
2. Power switch must be set to Internal.
3. V
1 knife switch (and V
6
, if present) must be closed.
4. Knife switch C must be open. Current must be flowing.
5. Control (Auto/Remote-Off-Manual) switch may be in any position.
6. For regulator #1, set Function Code 41 to 1 (Delta
Lag) and record the Power Factor, Function
Code 13.
7. For the same regulator set Function Code 41 to 2
(Delta Lead) and record the Power Factor.
8. Repeat steps 6 and 7 for each regulator in the bank.
For each regulator, one of the two power factor values will be reasonable and the other will be unreasonable.
Next
Step
No = BC; Yes = BB
No = BH; Yes = BI
No = BD; Yes = BJ
No = BE; Yes = BK
No = BF; Yes = BL
BG
No = BQ; Yes = BN
BM, BN & BO
BM, BN & BO
BM & BO
BM, BN & BO
BM & BO
BR
BR
No = BP; Yes = BR
BQ
BR
See Table 1.2 - AB
Set the Regulator Configuration (FC 41) to the value which produced the reasonable power factor.
For one regulator: Set Function Code 41 to the value which produced the reasonable power factor.
For two regulators in open delta: See the example in
Table 1-4. In an open delta connection one of the regulators will always be leading and the other lagging.
The reasonable power factor for each regulator should be very close to the typical power factor of the system. In this example, regulator #1 is the lagging unit and regulator #2 is the leading unit.
For three regulators in closed delta: In closed delta, all three regulators are either leading or lagging, depending on how they are connected relative to generator phase rotation.
TABLE 1-4
Sample Power Factor Values for Regulators Connected in
Open Delta Configuration
Configuration Recorded Power Factor (FC 13)
(FC 41)
Set to This
Value
Reg. #1 Reg. #2
1
(Delta Lag) 0.94* -0.77
2
(Delta Lead) 0.17
*Reasonable power factor values.
0.93*
1-7
S225-10-10
Figure 1-7.
Nameplate of a 60 hertz regulator with an internal series winding P.T.
1-8
McGraw-Edison VR-32 Regulator and CL-5 Series Control
Cooper Power Systems
Figure 1-8.
Nameplate of a 50 hertz regulator indicating metric weights and volumes
1-9
S225-10-10
Operational Check
Pre-Installation Operational Check
The CL-5 Series Control has the facilities for either manual or automatic operation of the tap changer, using either the internal source of power (the regulator), or an external source. To perform an operational check of the control before installing the regulator, follow these steps:
1. Open V
1
(and V
6
, if present) knife switch(es) located on control backpanel.
2. Place POWER switch in OFF position, and
CONTROL switch in OFF position.
3. Connect a variable 120-volt 50/60 Hz source to
EXTERNAL SOURCE terminals. Grounded side of external source must connect to ground (white) terminal on control.
4. Place POWER switch in EXTERNAL position.
5. Move CONTROL switch to MANUAL, and depress and hold RAISE-LOWER momentary toggle switch. Allow tap changer to operate to 8L, the 5% buck position.
6. Hold up on RAISE-LOWER momentary toggle switch. Allow tap changer to operate to 8R, the 5% boost position.
7. Now place Control switch in the AUTO/REMOTE position.
8. Increase variable voltage source so applied voltage is out of band. Note that “HIGH” band annunciator in display will come on. After time delay period, control will issue “LOWER” tap change signals. Check to ensure that operations counter is registering tap changes by pressing “0” key on keypad.
9. Decrease variable voltage source so applied voltage is out of band. Note that “LOW” band annunciator in display will come on. After time delay period, control will issue “RAISE” tap change signals. Check to ensure that operations counter is registering tap changes.
10. Place CONTROL switch in MANUAL position and manually return tap changer to NEUTRAL. When on NEUTRAL, NEUTRAL LAMP will light continuously and position indicator will point to zero.
11. Place CONTROL switch in OFF position.
12. Press down on momentary toggle switch labeled
DRAG HAND RESET, and position indicator drag hands will reset around indicating hand.
13. Turn POWER switch to OFF and disconnect power supply from EXTERNAL SOURCE terminals.
In-Service Operational Check
With the control now set for basic operation, an operational check of manual and automatic operation should be performed as follows:
1. Depress “8” key to display compensated voltage.
2. Place control switch in MANUAL position.
3. Lift up on Raise/Lower switch to activate a raise operation.
4. Allow tap changer to operate for enough steps to take voltage out of band.
5. Place control switch in the AUTO position. After time delay period, the control should cause the regulator to step down to the top band edge.
(EXAMPLE: 120 V and a 2 V B.W. = 121 V top band edge.) This should be shown in the display.
6. After voltage is brought in-band and tap changing has stopped, move control switch to the MANUAL position.
7. Press down on Raise/Lower switch to activate a lower operation.
8. Allow tap changer to operate for enough steps to take voltage out of band.
9. Place control switch in the AUTO position. After time delay period, the control should cause the regulator to step up to the lower band edge.
(EXAMPLE: 120 V and a 2 V B.W. = 119 V lower band edge.) This should be shown in the display.
Field Calibration Check
If the operator also desires to check the calibration of the control, perform the steps listed below.
NOTE: Field calibration checks are only an indication of calibration, and are not nearly as precise as the laboratory procedure described in the Troubleshooting
Guide section of this manual.
1. Connect an accurate true-RMS responding voltmeter to the voltmeter terminals.
2. The easiest and most direct way to perform a calibration check is to compare the voltage that the control “sees” to the voltage measured at the test terminals. This is accomplished by accessing the keypad and keying:
FUNCTION, 47, ENTER.
3. Under ideal conditions, the displayed voltage of the control will match the voltage of the voltmeter.
Realistically, the voltages may be slightly different because:
1-10
McGraw-Edison VR-32 Regulator and CL-5 Series Control a. The metering and operation is based upon the
RMS value of the fundamental power line frequency. Thus, the metered values exclude the influences of harmonic voltages which are probably present on the line. A true-RMS meter however, will include these harmonic voltages in its calculations of the RMS voltage. This does not present a problem with either metering device, since each device uses a different approach to metering.
b. The calibration of the voltmeter being used for measurement is probably not exact. Even a very good meter with a basic accuracy of 0.5% could be in error by as much as 0.6 V (out of
120 V), and still be considered to be “incalibration.” The control is calibrated using a conditioned power supply and reference voltmeters which are periodically calibrationchecked, traceable to the National Bureau of Standards.
NOTE: The control is designed to perform ratio correction in software. Through the use of the ratio correcting transformer (RCT) located on the back panel, the voltage brought to the front panel is usually already corrected to the 120 V base voltage. However, there are some ratings in which this voltage is not fully corrected by the RCT. Column 6 in Table 1-10 or 1-11, page 1-21 gives a general indication of these voltages, however, always refer to the nameplate which provides the specific information for the particular regulator.
Whatever voltage results from dividing the nominal system voltage, FC43, by the overall P.T. ratio, FC44, is considered by the control to be the nominal voltage.
Therefore, when that voltage appears at the input of the control, 120 volts will be reported as the output voltage,
FC6 (whether the nominal is actually 120 or not).
Likewise, the compensated voltage, FC8, and input voltage, FC7, will be scaled accordingly. If the regulator is equipped and programmed for reverse power operation, the voltage displayed at Function Code 8 will be correct even during reverse power conditions.
The load voltage, FC10, source voltage, FC11, and calculated parameters such as the kVA, kW and kvar are not scaled similar to FCs 6 and 8. Instead, they reflect the true value of line voltage.
NOTE: The voltage measured at the test terminals during reverse power flow is the new source voltage at the L bushing of the regulator.
Removal From Service
Determining Neutral Position
WARNING: In order to prevent possible damage to equipment and injury to personnel, prior to bypass switching being attempted, the following must be accomplished: 1) The regulator must be placed in the neutral position; 2) action must be taken to prevent tap changer operation while the bypassing is being performed.
If the regulator is in any position other than neutral, part of the series winding will be shorted if bypass switch is closed. This results in high circulating current which can severely damage the regulator. If catastrophic failure occurs, it could pose a threat of injury or death to operating personnel.
Return the regulator to neutral. The regulator can be safely removed from service without interrupting load continuity only in the neutral position. It is recommended to use more than one method to determine whether a regulator is on neutral.
To Return the Regulator to Neutral
1. Use Raise/Lower switch to bring regulator to neutral position.
WARNING: A regulator should be bypassed with the line energized only if both the position indicator and the neutral light indicate neutral. If both do not indicate neutral, the line should be de-energized to avoid shorting part of the series winding.
WARNING: Always use the control switch
(labeled AUTO/REMOTE-OFF-MANUAL) to operate the regulator, not the power switch. Failure to do so may result in the tap changer stepping off of neutral immediately upon being energized.
2. When in neutral, neutral light will light continuously and position indicator will point to zero.
WARNING: To stop the regulator on the neutral position, the control switch should be turned to OFF during the switching operation from positions “1” or “-1” to position zero. Switching to
OFF prior to reaching the neutral position prevents overshoot.
1-11
S225-10-10
3. To increase safety, we recommend verifying that the regulator is in the neutral position using the following three methods: a. Verify that the neutral indicator light on the control is indicating the neutral position. Neutral is indicated only when the light is continuously illuminated.
b. Verify that position indicator is in the neutral position.
c. Using an acceptable method, verify that there is no voltage difference between the source and load bushings.
4. When the regulator has been placed in the neutral position, and prior to bypassing, additional safety action must be taken to ensure that the tap changer will not inadvertently switch to an off-neutral position. This can be accomplished by doing the following: a. Place the control (Auto/Remote-Off-Manual) switch in OFF position.
b. Remove motor fuse.
c. Place control power switch in OFF position.
d. Open V
1 knife switch (and V on control back panel.
6 if present) located
If the precautions listed above are taken, the likelihood of damaging a regulator or injuring personnel is eliminated.
De-energizing the Regulator
Once it has been established that the regulator is on neutral, immediately proceed with the following steps:
1. Place control (Auto/Remote-Off-Manual) switch in
OFF position.
2. Place power switch in OFF position.
3. Open V
1 knife switch (and V
6 if present) on back panel (see Figure 1-7, page 1-8).
4. Remove the 6 A motor fuse.
5. Close bypass switch.
6. Open load (L) disconnect switch.
7. Open source (S) disconnect switch.
8. Open source-load (SL) disconnect switch, if available.
NOTE: If a regulator bypass disconnect is used in place of three separate switches, steps 5, 6 and 7 are carried out in one operation.
Maintenance Program
Periodic Inspections
Step-type voltage regulators are designed to provide many years of trouble-free operation. Proper operation of the regulator can be checked without removing the unit from service. Using the manual mode of operation, run the regulator several steps in the raise direction, and then switch the control back to auto. After the time delay, FC3, expires, the regulator should return to band edge. When this has been completed, use the manual mode of operation to run the regulator several steps in the lower direction, and then switch the control back to auto. After the time delay, the regulator should return to band edge.
If the regulator will not operate properly, a substitute control can be tried before removing the unit from service. Refer to the following sections for proper procedures on removing and replacing the control.
Since the usable life of a regulator is affected by its application, it may be desirable to periodically remove the regulator from service and untank the unit to verify contact wear, oil dielectric, etc. The time for this will vary, depending on a specific user’s past experience.
The oil should be checked (a) prior to energization, if the regulator has not been energized for a long time period, or (b) at normal maintenance intervals. Table 1-5 shows the characteristics that the oil should meet.
TABLE 1-5
Oil Characteristics*
New Used
Dielectric Strength
(kV minimum)
ASTM D1816-84
0.08 inch gap
ASTM D877-87
Interfacial Tension
ASTM D971-91
(mN/m)
Water
ASTM D1533-88
(ppm maximum)
40
30
35
25
34
26
24
35
*Per C57.106.
1-12
McGraw-Edison VR-32 Regulator and CL-5 Series Control
Removal of Control Front Panel
The front panel may be removed from the regulator with the regulator energized.
To open the front panel, unscrew the captive knurled knobs on the left side of the panel. This allows the control to swing open on its hinges. With the control open, the back panel is readily accessible. The design of the control enclosure, back panel and front panel enable easy replacement of the front panel, leaving the back panel, control enclosure, and cable intact. To remove the front panel, proceed as follows:
WARNING: Push the C shorting switch closed before attempting to remove the fanning strip. Failure to do so may open the regulator
CT circuit, producing a flashover in the control.
1. Push closed the current shorting switch, C. This shorts out the secondary of the regulator CT.
NOTE: Regulators shipped with a quick disconnect cable contain a solid-state CT shorting board in the junction box. This device automatically places a burden on the CT anytime the CT circuit is opened. For consistency, it is recommended that the CT shorting switch be used whenever it is present on the back panel.
2. Pull open disconnect switch, V
1
, (and V
6 if present).
This de-energizes terminal board TB
2
.
3. Loosen screws on terminal board TB
2 at the bottom of back panel.
4. Pull fanning strip (a series of terminals, wired to front panel) free from terminal strip.
5. Disconnect front panel ground lead from back panel.
The front panel can now be lifted off its hinges. Care should be taken to prevent damage to a control front panel while in transit and/or storage.
Replacement of Control Front Panel
To replace a front panel in the control enclosure, follow the procedure outlined below:
1. Engage the front panel on enclosure hinges.
2. Connect front panel ground lead to back panel.
3. Insert fanning strip from front panel wiring harness under TB
2 terminal board screws.
4. Tighten screws on interconnecting terminal board.
5. Push closed the disconnect switch, V
1
, (and V
6 if present).
6. Pull open the current shorting switch, C.
7. Close panel and tighten panel locking screws.
WARNING: Do not pull open the current shorting switch, C, until the screws have been tightened on the interconnecting terminal block.
Failure to do so could open the regulator CT secondary causing a flashover in the control.
Untanking the Regulator
WARNING: When the internal assembly is lifted for inspection or maintenance, blocking should be placed between the cover and the top of the tank to keep the assembly from falling should the lifting apparatus fail.
CAUTION: Before untanking a regulator that contains a thermometer, (1) lower the oil level below the thermometer, then (2) remove the thermometer well. Failure to do so will result in damage to the thermometer well and/or spillage of oil when the internal assembly is lifted.
CAUTION: Do not suspend the control box using the control cable.
1. Manually run tap changer to neutral, if possible. If not, record position indicator reading before proceeding to untank.
2. Disconnect control cable from bottom of junction box (Figure 1-9).
3. Remove series arrester. Release internal pressure using pressure relief device on side of regulator.
4. Free cover by removing clamping ring or cover bolts.
5. Attach sling or hooks with spreader bar (Figure
1-10) to lifting eyes and raise the cover, with the attached core-and-coil assembly, until the top of the coil is approximately one inch under oil.
As a safety precaution, blocking between the cover and tank lip should be used until inspection of the tap changer or other maintenance is complete. A service cable assembly is available for operating an untanked regulator from the mounted control cabinet, if connection cable is not long enough.
Contact customer service for availability.
1-13
Figure 1-9.
Quick Disconnect Cable
SPREADER
BAR
BLOCKING
MEMBERS
Figure 1-10.
Untanking
S225-10-10
Retanking the Regulator
Retank the regulator as follows:
1. Be sure position indicator shows present position of the tap changer. If not, remove indicator cable in junction box from position indicator shaft after loosening set screw. Rotate indicator shaft until proper position is reached, then tighten set screw. Verify coordination of position indicator with tap changer in the neutral position
(control neutral light on). Refer to page 6-3 for position indicator replacement.
2. Check gasket seat surfaces on cover and tank and wipe clean. Wipe gasket and position it on tank lip. Loosen horizontal side channel bolts to ensure proper seating of regulator in tank and proper cover seal.
3. Raise cover assembly and attached components over tank. Make certain of proper orientation.
4. Lower unit, rotating channels counter-clockwise into tank guides.
5. Seat unit in tank. Tighten cover clamps or bolts.
NOTE: Tap cover with a rubber hammer around edge to properly seal gasket while tightening cover band.
6. Check and retighten horizontal side channel bolts through handhole, if required.
7. Properly reseal handhole cover, being careful not to damage cover or insulation on the handhole cover bolt.
8. Connect control cable to connector at bottom of junction box.
Maintenance
The following is the recommended maintenance program for a regulator that has been untanked:
1. Check all connections for tightness.
2. Check all contacts for wear (refer to S225-10-2).
3. Avoid removing main core-and-coil assembly from oil, except when a winding failure occurs.
Blocking between cover and tank lip should be used to suspend core-and-coil assembly within oil until inspection of tap changer or other maintenance is complete.
If it is necessary to remove main core-and-coil assembly from oil, the following steps should be followed. a. Tap changer must not be subjected to temperatures above 150°F (66°C). It must be removed if the unit is baked at higher temperatures.
1-14
McGraw-Edison VR-32 Regulator and CL-5 Series Control b. If unit is out of oil more than four hours, it must be rebaked for a minimum of 24 hours at 100°C (212°F). The maximum number of times a unit should be rebaked is twice over its life.
c. Within four hours after bake, the unit should be retanked and filled with oil.
d. It is recommended that a vacuum be pulled on the unit for at least one hour (2 mm of vacuum or better) after the unit is completely refilled with oil. If vacuum processing is not available, allow entire internal assembly to soak in oil for at least five days before energizing.
Construction
Surge Protection
Series Arrester
All VR-32 Regulators are equipped with a bypass arrester connected across the series winding between the source (S) and load (L) bushings. This arrester limits the voltage developed across the series winding during lightning strikes, switching surges and line faults. The series surge arrester can be seen in Figure 2, page 3. A heavy-duty MOV-type series surge arrester of 3 kV offers series winding protection on all regulators except those rated 22,000 V and greater, which have a 6 kV
MOV-type series surge arrester.
Shunt Arresters
A shunt arrester is a recommended accessory on the
VR-32 regulator for protection of the shunt winding. The shunt arrester is a direct-connected arrester mounted on the tank and connected between the bushing and ground (earth). It is recommended that arresters be applied to all non-grounded bushings.
For best results, locate these arresters on the mounting pads provided on the tank near the bushing. Connect the arrester and the regulator tank to the same ground connection using the shortest cable possible. Shunt arrester application data is listed in Table 1-6.
TABLE 1-6
Shunt Arrester Application Data
Regulator
Voltage
Rating
2500
5000
6600
7620
8660
11000
13800
Recommended
MOV Shunt
Arrester
Ratings
(kV)
3
6
9
10
12
15
18
Regulator
Voltage
Rating
14400
15000
19920
22000
33000
34500
Recommended
MOV Shunt
Arrester
Ratings
(kV)
18
21
27
27
36
36
Position Indicator & ADD-AMP
Capability
The position indicator (Figure 1-11) is mounted on a junction box on the cover of the regulator and is directly connected to the tap changer by a flexible drive shaft passing through the junction box and terminal board via a sealing gland.
The indicator face is graduated in steps. Drag hands indicate the maximum and minimum positions attained during raise and lower operations. The drag hands are automatically reset around to the main hand position by operating the drag hand reset switch on the control front panel.
During forward power flow the main hand of the position indicator will be to the right of the neutral position when the regulator is boosting. During reverse power flow the main hand will be to the left of the neutral position when the regulator is boosting.
The ADD-AMP feature of VR-32 regulators allows increased current capacity by reducing the regulation range. This is accomplished by either setting limit switches in the position indicator or enabling function code 79 (soft ADD-AMP) to prevent the tap changer from traveling beyond a set position in either raise or lower directions.
The limit switches have scales graduated in percent regulation, and are adjustable to specific values of 5,
6 1 ⁄
4
, 7 1 ⁄
2
, 8 3 ⁄
4
, and 10% regulation to alter the regulation range. These percentages translate to tap position limitations of 8, 10, 12, 14, or 16 raise or lower. The five possible load current ratings associated with the reduced regulation ranges are summarized in Tables 1-7 and 1-8.
Higher regulation ranges are realized in closed delta application. When using the limit switches, a detent stop at each setting provides positive adjustment. Settings other than those stops are not recommended. The raise and lower limits need not be the same value unless reverse power is possible. The regulator will stay within the ADD-AMP limits set forth by the control or the position indicator, whichever limit is of a lower regulation percentage.
NOTE: If the ADD-AMP limits have been programmed into the control (soft ADD-AMP) and the limit switches have not been set, it is possible to manually step the tap changer beyond the ADD-AMP limit. If the unit is switched back to automatic mode, the control will step the regulator back to within the ADD-AMP limits set in the control.
See also page 6-3 for position indicator replacement and calibration.
1-15
S225-10-10
MAIN HAND
Figure 1-11.
Position Indicator
BEZEL
COVER
LIMIT SWITCH TABS
DRAG HANDS
Setting the Manual (Hard) Limit
Switches
Before setting the manual limit switches, be sure the new settings will not conflict with the present tap changer position. Do not set the switches below the indicated tap changer position. For example, if the main hand is at step 12 and the change to be made is from plus or minus 10% (step 16) to plus or minus 5% (step 8), run the tap changer back to step 7 or less, manually. Then set the limit switches for plus or minus 5% regulation.
Limit switches should be set in anticipation of the maximum deviation of primary voltage. For example, on a circuit where 7200 V is to be maintained, plus or minus
10% will permit voltages between 6480 V and 7920 V to be regulated effectively. For voltages outside this range, the regulator will not be able to return the voltage to the preselected level (7200 V). Five percent regulation would accommodate circuit voltages between 6840 and
7560 V, maintaining 7200 V for all voltages in this range.
To set the limit switches, follow this two-step procedure:
1. Loosen the captive bezel securing screws and swing the bezel open.
2. Lift the limit switch adjustment lever free of the detent and slide it to the new setting allowing the lever to snap into the detent stop.
Internal Construction & Wiring
Diagrams
The main core-and-coil assemblies are of the shell-form configuration. The series winding on the input (source) side of the regulator (Figure 1-12) allows all windings
(control, shunt and series) to be located in one coil assembly. The load voltage is monitored by the control winding.
Regulators that have the series winding on the output (load) side (Figure 1-13) have a separate potential transformer installed on the load side in lieu of a control winding.
The control winding or separate potential transformer supplies a voltage for the tap changer motor and the control sensing circuit. Additional taps are available on them for line voltages lower than rated voltage.
Most regulators, depending upon the rating, have an equalizer winding. This winding improves contact life for high-current applications.
Figure 1-14 shows a typical regulator power circuit with a series transformer. This design is utilized when the load current rating exceeds the tap changer rating. In this type of design, the series transformer winding losses are a function of the load alone and are independent of the tap position. Because of this, limiting the range of voltage regulation does not reduce losses and therefore, the ADD-AMP feature is not applicable.
The bridging reactor is a core-form design, consisting of a coil on each leg of one core. The inside half of one coil is connected to the outside half of the other coil and vice versa, providing equal current in each half of the reactor winding. This interlacing of the two coils reduces the interwinding leakage reactance to a very low value. The reactor is completely isolated from ground by stand-off insulators since the reactor coil is at line voltage above ground. The reactor core, core clamps and other associated parts approach this level.
The current transformer is a toroid, through which the load current passes. It furnishes a current proportional to load current for the line-drop compensator and metering features.
The tap changer enables the regulator to provide regulation in smooth, accurately proportioned steps at a controlled speed that minimizes arcing and extends contact life. Figures 6-3 and 6-4 in the Troubleshooting section illustrate typical internal wiring schemes of the various types of regulator constructions. Most of the wiring is on the tap changer itself. Application, troubleshooting and operation of the tap changer and related components are covered extensively in Service
Manual S225-10-2.
The terminal board inside the junction box on the cover connects the internal tank wiring to the position indicator and control. The junction box wiring is shown in Figure
6-1, page 6-5.
1-16
McGraw-Edison VR-32 Regulator and CL-5 Series Control
TABLE 1-7
ADD-AMP Capabilities of 60 Hz Ratings
†Load Current Ratings (amperes)
Regulation Range (Wye and Open Delta)
Rated Rated
Volts kVA ±10% ± 8.75% ±7.5% ±6.25% ±5%
Regulation Range (Closed Delta)
25
±15% ± 13.1% ±11.3% ±9.4%
100
50
75
100
2500 125
200
300
400
500
167
250
668
1000
333 1332
416.3
1665
110
220
330
440
550
668
1000
1332
1665
120
240
360
480
600
668
1000
1332
1665
135
270
405
540
668
668
1000
1332
1665
±7.5%
160
320
480
640
668
668
1000
1332
1665
72
144
288
333
416
14400 432
500
576
667
720
833
50
100
200
19920 333
400
500
667
833
1000
25
50
100
125
5000 167
250
333
416.3
50
100
200
250
334
500
668
833
55
110
220
275
367
550
668
833
60
120
240
300
401
600
668
833
68
135
270
338
451
668
668
833
80
160
320
400
534
668
668
833
38.1
57.2
76.2
114.3
50
75
100
150
55
83
110
165
60
90
120
180
68
101
135
203
80
120
160
240
167* 219/232 241/255 263/278 296/313 350/370
7620 250* 328/347 361/382 394/417 443/469 525/556
333* 438/464 482/510 526/557 591/625
416.3* 548/580 603/638 658/668 668
668
668
500* 656/668 668 668 668 668
667* 875/926 875/926 875/926 875/926 875/926
833* 1093/1157 1093/1157 1093/1157 1093/1157 1093/1157
69
138
207
276
13800 414
500
552
667
833
50
100
150
200
300
362
400
483
604
55
110
165
220
330
398
440
531
664
60
120
180
240
360
434
480
580
668
68
135
203
270
405
489
540
652
668
80
160
240
320
480
579
640
668
668
50
100
200
231
289
300
347
400
463
500
578
25.1
50.2
100.4
167
200.8
250
335
418
502
55
110
220
254
318
330
382
440
509
550
636
28
55
110
184
220
275
369
460
552
60
120
240
277
347
360
416
480
556
600
668
30
60
120
200
240
300
402
502
602
68
135
270
312
390
405
468
540
625
668
668
34
68
135
225
270
338
452
564
668
† 55/65°C rise rating on VR-32 regulators gives an additional 12% increase in capacity if the tap changer’s maximum current rating has not been exceeded. For loading in excess of the above values please refer to customer service.
* Regulators are capable of carrying current corresponding to rated kVA when operated at 7200 Volts.
80
160
320
370
462
480
555
640
668
668
668
40
80
160
267
320
400
536
668
668
1-17
110
220
330
440
660
165
330
495
660
75
150
225
300
450
600
750
55
110
165
220
330
440
550
660
33
66
99
132
198
264
330
396
TABLE 1-8
ADD-AMP Capabilities of 50 Hz Ratings
Rated Rated
Volts kVA
6600
11000
15000
22000
33000
†Load Current Ratings (amperes)
Regulation Range (Wye and Open Delta)
±10% ± 8.75% ±7.5% ±6.25% ±5%
Regulation Range (Closed Delta)
±15%
50
100
150
200
300
400
500
600
± 13.1% ±11.3%
55
110
165
220
330
440
550
660
60
120
180
240
360
480
600
668
±9.4%
68
135
203
270
405
540
668
668
±7.5%
80
160
240
320
480
640
668
668
55
110
165
220
330
440
550
55
110
165
220
330
440
550
660
55
110
165
220
330
55
110
165
220
50
100
150
200
300
400
500
50
100
150
200
300
400
500
600
50
100
150
200
300
50
100
150
200
60
120
180
240
360
480
600
668
60
120
180
240
360
480
600
60
120
180
240
360
60
120
180
240
68
135
203
270
405
540
668
68
135
203
270
405
540
668
668
68
135
203
270
405
68
135
203
270
80
160
240
320
480
640
668
80
160
240
320
480
640
668
668
80
160
240
320
480
80
160
240
320
† 55/65°C rise rating on VR-32 regulators gives an additional 12% increase in capacity if the tap changer’s maximum current rating has not been exceeded. For loading in excess of the above values please refer to customer service.
TABLE 1-9
Current Transformer Applications (50 & 60 Hz)
Regulator Current
Ratings
25
50
75
100
150
167, 200
219, 231, 250
289, 300
328, 334, 347, 400
418, 438, 463, 500
548, 578, 656, 668
833, 875, 1000, 1093
1332, 1665
C.T.
Primary Current
25
50
75
100
150
200
250
300
400
500
600
1000
1600
SOURCE
BUSHING
S
VL
REVERSING
SWITCH
VR
SERIES WINDING
1 2 3 4 5 6 7 8
N
POLARITY
MARKER
CURRENT
TRANSFORMER
LOAD BUSHING
L
REACTOR
EQUALIZER WINDING LOAD
SOURCE
SHUNT
WINDING
SOURCE-LOAD
BUSHING
E
3
E
2
E
1
G
JBB-S
2
JBB-G
JBB-C
2
C
2
V
G
1
R
O
L
C
O
N
T
JBB-C
1
C
1
CONTROL WINDING
SL
Figure 1-12.
Power circuit — series winding located on the source-side (ANSI Type B)
SOURCE
BUSHING
S
N
VR VL
REVERSING
SWITCH
POLARITY
MARKER
SERIES WINDING
1 2 3 4 5 6 7 8
REACTOR
EQUALIZER WINDING
SOURCE SHUNT
WINDING
SOURCE-LOAD
BUSHING
LOAD
POTENTIAL
TRANSFORMER
CURRENT
TRANSFORMER
LOAD BUSHING
L
JBB-C
2
C
2
JBB-C
1
C
1 E
3
E
2
E
1
G
JBB-S
2
JBB-G
V
1
G
CONTROL
LOAD
SL
Figure 1-13.
Power circuit — series winding located on the load-side (ANSI Type A)
S225-10-10
1-18
McGraw-Edison VR-32 Regulator and CL-5 Series Control
SOURCE
BUSHING
SHUNT
TRANSFORMER
SOURCE
VL
VR
8
7
6
5
4
3
2
1
SL
REVERSING
SWITCH
N
SOURCE-LOAD
BUSHING
Figure 1-14.
Power circuit — series transformer
Voltage Circuits
All McGraw-Edison VR-32 regulators have provisions for operation at system voltages lower than the nameplate rating, as illustrated in Tables 1-10 and 1-11. This is accomplished by providing taps on the control winding or
P.T. The taps are brought to a terminal board located on top of the tap changer assembly, under oil and are marked E
1
, E
2
, etc. (See Figure 1-15.) The connections are made with push-on terminals and are easily accessed through the handhole.
Regulators built prior to 1995 will have all the voltage terminal connections mounted on the top of the tap changer. Since the middle of 1995, the voltage connections will be as shown in figure 1-15.
P TAPS
Figure 1-15.
Internal tap terminals
S
E TAPS
JBB-C
1
L
LOAD BUSHING
CURRENT TRANSFORMER
JBB-C
2
POLARITY
MARKER
LOAD
POTENTIAL
TRANSFORMER
SERIES
TRANSFORMER
EQUALIZER WINDING
REACTOR
E
3
E
2
E
1
G
JBB-S
2
JBB-G
V
C
2
R
O
L
C
O
N
T
G
1
C
1
LOAD
The tapped potential winding cannot always provide adjustment of the voltage fine enough for control or motor use. A tapped autotransformer is therefore used for fine voltage adjustment. This transformer, the Ratio
Correcting Transformer (RCT
1
), has input taps at 104,
110, 115, 120, 127, and 133 V. The output tap to the control and motor is set as 120 V. RCT
1 is located on the control back panel (see Figure 1-7, page 1-3). To operate a regulator on a system other than its rating, the appropriate selection must be made for the internal tap and RCT
1 tap, and the control must be programmed properly at Function Code 43 (System Line Voltage) and
Function Code 44 (Overall P.T. Ratio). The nameplate provides these values for common system voltages (see
Figure 1-8 on page 1-9).
This voltage supply is then brought from the tap changer terminal board to the junction box terminal board through the control cable, into the enclosure, terminating at the knife switch labeled V
1
. Opening this knife switch provides a visible means of removing all power to the control and motor circuits. From the knife switch, the voltage is ratio corrected by RCT
1 as previously described. The motor circuit is routed directly to the control front panel and the sensing potential is brought back to the top terminal strip through a series of removable jumpers, and then to the front panel. This scheme allows for the complete interchangeability with all the prior CL-series controls and accompanying accessories.
If a regulator is purchased with the intent of using it in an area where reverse power flow is likely, the unit may
1-19
S225-10-10 have a second voltage source installed internal to the regulator to develop the source-side voltage supply. (For the CL-5C and subsequent controls, reverse power flow may instead be handled using the source voltage calculator. See page 4-3, Reverse Power Operation.) A series winding (differential) P.T. is utilized for measuring the voltage across the series winding, which is then used, along with the existing control winding or separate control windings, to develop the source-side voltage.
The series winding P.T. will have taps similar to the load side supplies. These high-voltage taps (see Figure 1-15) are located on the series winding P.T. and are marked
P
1
, P
2
, etc. The secondary voltage of the series winding
P.T. is brought directly to the knife switch labeled V
6
, and then passes through RCT
2 for ratio correction
(similar to that performed for V
1
). The differential V
6 voltage, once corrected by RCT
2
, is labeled V
7 and is then routed to the control front panel.
On the front panel, the three potentials (V s
, sensing voltage; V
7
, differential voltage; V m
, motor voltage) are all brought directly to the power switch. Without a source side supply, the V
7 terminal is connected to the V s terminal on the control back panel, and the control software then recognizes that the V
7 voltage is not present.)
The power switch has three positions: internal, off, and external. The internal position powers the control and motor from the regulator sensing winding, and the external position permits an external supply for the same purpose. When the power switch is in the external position, the internal supply is disconnected to prevent accidentally energizing the high voltage winding and bushings. The external source terminals are prominently located adjacent to the voltmeter test terminals.
The voltmeter terminals allow the monitoring of the voltage that is applied to the circuit board. This is the voltage output from RCT
1 and the voltage displayed at
Function Code 47. During forward power flow, the voltage at these terminals is the output voltage. During reverse power flow the voltage at these terminals is the source voltage.
The three voltage circuits are routed from the power switch to the respective 6 A motor fuse, 2 A panel fuse, and 2 A differential voltage fuse. The differential voltage fuse is provided to protect the front panel if an external source P.T. is used. From the 6 A fuse, the motor potential provides power to the auto/manual selector switch, the drag hand reset solenoid, the neutral light, and the holding switch (alternate motor source) circuits.
The sensing voltage and differential voltage are connected directly to their respective circuit board input terminals.
2500
5000
7620
13800 13800
13200
12470
12000
7970
7620
7200
6930
8000
7970
7620
7200
6930
4800
4160
2400
2500
2400
5000
4800
4160
2400
14400 14400
13800
13200
12000
7970
7620
7200
6930
19920 19920
17200
16000
15242
14400
7970
7620
7200
TABLE 1-10
VR-32 Tap Connections and Voltage Levels (60 Hz)
Nominal
Regulator Single Ratio Adjusting Data
Voltage Phase
Rating Voltage Internal PT RCT
1 2
Tap*
3
Ratio
4
Tap
5
Test Overall
Terminal Potential
Voltage
**
Ratio
**
6 7
—
—
20:1
20:1
E 1 /P 1
E 1 /P 1
E 2 /P 2
E 2 /P 2
E 2 /P 2
E 3 /P 3
E 3 /P 3
E 3 /P 3
E 1 /P 1
E 1 /P 1
E 1 /P 1
E 2 /P 2
E 1 /P 1
E 1 /P 1
E 1 /P 1
E 1 /P 1
E 1 /P 1
E 2 /P 2
E 2 /P 2
E 3 /P 3
40:1
40:1
40:1
20:1
E 1 /P 1
E 1 /P 1
E 1 /P 1
E 1 /P 1
E 2 /P 2
E 2 /P 2
E 2 /P 2
E 2 /P 2
E 1 /P 1
E 1 /P 1
E 1 /P 1
E 1 /P 1
115:1
115:1
115:1
115:1
E 2 /P 2 57.5:1
E 2 /P 2 57.5:1
E 2 /P 2 57.5:1
E 2 /P 2 57.5:1
120:1
120:1
120:1
120:1
60:1
60:1
60:1
60:1
166:1
166:1
120:1
120:1
120:1
60:1
60:1
60:1
60:1
60:1
60:1
60:1
60:1
40:1
40:1
20:1
120
115
104
104
133
133
120
120
133
133
127
120
115
120
104
120
120
120
120
120
104
120
120
104
133
127
120
133
127
120
120
115
110
104
133
127
120
115
120
120
125
120
125
120
125
120.5
120.5
120
120
120
120.5
120
120
120
125
120
125
120
120
120
120
120
120
115.5
120
120
120
120.5
120:1
115:1
110:1
104:1
66.5:1
63.5:1
60:1
57.5:1
120 166:1
119.5
143.9:1
120.5
120
133:1
127:1
120
120
120
120
120:1
66.5:1
63.5:1
60:1
20:1
20:1
40:1
40:1
34.7:1
20:1
66.5:1
66.5:1
63.5:1
60:1
57.5:1
40:1
34.7:1
20:1
115:1
110.2:1
99.7:1
99.7:1
63.7:1
63.7:1
57.5:1
57.5:1
* P taps are used with E taps only on regulators where an internal potential transformer is used in conjunction with the control winding to provide voltage supplies to the control. See nameplate for verification of this type of control supply.
** Test terminal voltage and overall potential ratio may vary slightly from one regulator to another. See the regulator nameplate for determining the exact values.
1-20
McGraw-Edison VR-32 Regulator and CL-5 Series Control
6600 6930
6600
6350
6000
5500
11000 11600
11000
10000
6930
6600
6350
6000
5500
15000 15000
14400
13800
13200
12000
11000
10000
8660
22000 23000
22000
20000
19100
15000
12700
11000
10000
33000 34500
33000
30000
22000
20000
11600
11000
10000
TABLE 1-11
VR-32 Tap Connections and Voltage Levels (50 Hz)
Nominal
Regulator Single Ratio Adjusting Data
Voltage Phase
Rating Voltage Internal PT RCT
1 2
Tap*
3
Ratio
4
Tap
5
Test Overall
Terminal Potential
Voltage
**
Ratio
**
6 7
—
—
—
—
—
55:1
55:1
55:1
55:1
55:1
E 1 /P 1
E 1 /P 1
E 1 /P 1
E 1 /P 1
E 1 /P 1
E 2 /P 2
E 2 /P 2
E 3 /P 3
E 1 /P 1
E 1 /P 1
E 1 /P 1
E 2 /P 2
E 2 /P 2
E 2 /P 2
E 2 /P 2
E 2 /P 2
91.7:1
91.7:1
91.7:1
55:1
55:1
55:1
55:1
55:1
120:1
120:1
120:1
120:1
120:1
92.3:1
92.3:1
72.9:1
E 1 /P 1 183.3:1
E 1 /P 1 183.3:1
E 1 /P 1 183.3:1
E 1 /P 1 183.3:1
E 2 /P 2 119.8:1
E 2 /P 2 119.8:1
E 3 /P 3 91.6:1
E 3 /P 3 91.6:1
E 1 /P 1
E 1 /P 1
275:1
275:1
E 1 /P 1 275:1
E 2 /P 2 183.3:1
E 2 /P 2 183.3:1
E 3 /P 3 91.7:1
E 3 /P 3
E 3 /P 3
91.7:1
91.7:1
120
120
110
104
120
104
120
110
120
120
115
110
104
120
110
120
127
120
110
120
110
127
120
110
127
120
110
127
120
115
110
104
127
120
115
110
104
118
120
119
120
119
119.5
120
119
119
120
120.5
119
115.5
119.5
120
119
119
120
120
119
115.5
125
120
120
120
115.5
119
118
119
120:1
120:1
115:1
110:1
104:1
92.3:1
84.6:1
72.9:1
125.5
183.3:1
120
119
183.3:1
168:1
120 159.2:1
125.5
119.8:1
122.5
103.9:1
120 91.6:1
119 84:1
58.2:1
55:1
52.7:1
50.4:1
47.7:1
97:1
91.7:1
84.1:1
58.2:1
55:1
52.7:1
50.4:1
47.7:1
291:1
275:1
252.1:1
183.3:1
168:1
97:1
91.7:1
84:1
* P taps are used with E taps only on regulators where an internal potential transformer is used in conjunction with the control winding to provide voltage supplies to the control. See nameplate for verification of this type of control supply.
** Test terminal voltage and overall potential ratio may vary slightly from one regulator to another. See the regulator nameplate for determining the exact values.
TABLE 1-12
RCT Ratios
RCT Input Tap RCT Ratio
133
127
120
115
110
104
1.108
1.058
1.000
0.958
0.917
0.867
Allowable System Voltages
Calculation of Overall P.T. Ratio
If the system voltage is other than those listed on the nameplate, it can be determined whether there is sufficient ratio correction available from the control winding (internal P.T.) taps and the Ratio Correction
Transformer (RCT) taps to allow the CL-5 Series control and motor to function properly. The general guideline is that the overall P.T. ratio is sufficient if the voltage delivered to the control for the nominal voltage conditions is in the range of 115-125 V.
To determine the voltage delivered to the control, use the following procedure:
1. Of the P.T. ratios shown on the nameplate choose the one which provides a voltage closest to 120V at the output of the internal P.T. (The output of the internal P.T. is the input to the RCT).
2. Calculate the voltage at the output of the internal
P.T., and compare that to the RCT input taps of
133, 127, 120, 115, 110 and 104.
3. Choose the RCT tap closest to the RCT input voltage.
4. Given the RCT input tap use Table 1-12 to determine the RCT ratio.
5. Use the formula below to calculate the control input voltage.
6. Use the formula below to calculate the overall
P.T. Ratio.
Control Input V = Internal P.T. Output V (RCT Ratio)
Overall P.T. Ratio = Internal P.T. Ratio x (RCT Ratio)
EXAMPLE: If a 60Hz, 14400 V regulator is to be used on a system with a nominal voltage of 12700, the following is determined:
1. 12700V / 120V=105.8. Choose 120:1 Control
Winding Tap
2. Internal P.T. output voltage = 12700V / 120=105.8V
3. Best RCT input tap is 104
4. RCT ratio is 0.867
5. Control input V = 105.8/0.876 = 122V. This is within allowable range.
6. Overall P.T. ratio = 120 x .867 = 104:1
1-21
S225-10-10
Changing System Voltage
WARNING: Remove regulator from service before performing internal lead connection changes.
To utilize a regulator at a system voltage other than the nominal voltage designated on the nameplate,
1. If required, change control winding tap (E1-E3) on the terminal strip (accessible through the handhole,) to the value indicated on the nameplate.
2. If the regulator contains an internal differential
P.T., and if a change to the P.T. settings is required, make the changes on the P.T. (through the handhole.)
3. Move the Control Function switch to OFF.
4. Move the Power switch to OFF.
5. Remove the 6 amp motor fuse.
6. Open the V
1
(and V
6 if present) knife switches, on the control back panel.
7. If required, change the Ratio Correction
Transformer tap (on the control back panel) to the value indicated on the nameplate.
8. Close The V
1
( and V
6 if present) knife switches, on the control back panel.
9. Replace the 6 amp motor fuse.
10. Move the Power switch to External or Internal, depending on how regulator control is energized.
11. Change Function Code 44 to the new overall P.T.
Ratio.
12. Change Function Code 43 to new system voltage.
13. Move the Control Function switch to AUTO/
REMOTE.
Current Circuit
All VR-32 regulators are designed with an internal current transformer to provide a current source for the line drop compensation calculations and for metering functions. Table 1-9, page 1-17 provides the application information for the various C.T.s used on the McGraw-
Edison regulators. These C.T.s provide 200 mA output for the rated C.T. primary current.
The current developed by the C.T. is brought to the terminal board inside the junction box, through the control cable, into the enclosure, terminating at the knife switch labeled C. Closing the knife switch provides a
visible means of shorting the C.T., thus allowing the operator to work safely on the current circuitry. (For additional safety measures, the V
1 and V
6 knife switches should also be opened.) For all regulators with quick disconnect, connector (Figure 1-9), an automatic solidstate C.T. shorting device is located in the junction box.
This solid-state device automatically will short the C.T.
when the cable is disconnected.
Figure 1-16.
Internal bushing mounted current transformer
At this knife switch, one side of the C.T. is connected to the equipment ground, and is also routed to the front panel for termination on the circuit board. The “high” side of the current circuit is brought to the top terminal board through two removable jumpers and then to the front panel for connection to the circuit board. Once this current signal is delivered to the circuit board, it is transformed into a voltage signal and converted into a digital format for processing.
Motor Circuit
The motor circuit power is brought from the 6 A fuse to the circuit board through a set of back-to-back diodes to the control (auto/manual) switch. When this switch is set for automatic operation, motor power is applied to the relays. An appropriate relay closure then applies this power to the tap changer motor, after first passing through the limit switch contacts in the position indicator. When the switch is set for manual operation, the power is transferred to the momentary toggle switch labeled raise-lower. By actuating this switch in one direction or the other, power is applied through the limit switch contacts, directly to the tap changer motor, completely bypassing the circuit board.
1-22
McGraw-Edison VR-32 Regulator and CL-5 Series Control
Also included as a part of the motor circuit is an alternate feed to the motor called the holding switch circuit. Located on the tap changer is a switch or switches, which operate off of the tap changing mechanism. Motor rotation causes switch closure (one direction or the other) and establishes a complete circuit for motor current until the rotation is complete and the cam drops out. During the time the holding switch is closed, motor current is drawn through an input on the circuit board which permits the control to detect that a tap change is in process. The microprocessor uses this information in its decision making process, as described under Control Operating Modes, page 2-8.
Two other unassociated circuits which share the 6 A motor source are the drag hand reset and neutral light circuits. The drag hand reset function is accomplished simply by operating a momentary toggle switch which applies power to the reset solenoid in the position indicator. The neutral light is energized from a neutral light switch (located on the tap changer) when in the neutral tap position.
1-23
S225-10-10
Control Basics
Introduction
The CL-5 Series Control
The McGraw-Edison CL-5 series control is a full-featured control which incorporates digital logic and microprocessor technology. A keypad is used to simplify the setup of the basic control and its many built-in accessory features. An LCD (liquid crystal display) screen displays the control settings, accessory settings, metering values and annunciator words.
Standard features of the control are:
• Line Drop Compensation
• Voltage Limiting
• Voltage Reduction (Local and Remote)
• Reverse Power Flow Operation
• Metering
• Data Port
• CE Mark Compliant
Advanced features of the control are:
• Source Voltage Calculation (CL-5C and later only)
• Calendar/Clock
• Time-Tagged Min/Max Demand Metering
• Metering Profile Recorder
• Total Harmonic Distortion and odd harmonic voltages and currents up to the 13th
• Tap Position Indication
• Pulse Voltage Reduction Mode
• Security Override
• Supervisory On/Off Switch
• Resident Communications Protocol (DATA 2179)
• Tap to Neutral*
• Enhanced Operation Counter*
• SOFT ADD-AMP Limits*
* CL-5E only
The demand metering values and control settings are stored in EEPROM memory to prevent their loss during a power outage. Information stored in the EEPROM will be retained indefinitely, with or without power applied.
To fully capitalize on the microprocessor capabilities, a
12-bit analog-to-digital converter is used in the front end of the design to convert the analog voltage and current waveforms into digital signals. A digital signal processing
TABLE 2-1
Control Specifications
B.
C.
D.
A.
E.
Physical Size
Weight
17 1 /
2
” H 10 1 /
4
” W 2 1 /
2
” D
(44.5 cm 26.0 cm 6.35 cm)
11 1 /
2 lbs. (5.2 kg)
Burden @ 120 V 4 VA
Operating
Temperature
Range
-40° C to +85° C
Control System
Accuracy
±1%
F.
Metering Accuracy
Voltage Inputs (2)
Output Voltage and Differential/Source Voltage
80-137 V ac, 45 to 65 Hz with error not to exceed
0.5%*† of the reading under all conditions.
The control will withstand up to 137 V without damage or loss of calibration.
Current Input
0-0.400 A ac 45 to 65 Hz with error not to exceed
0.6% (0.0012 A)* of the nominal full load current
(0.200 A), under all conditions. The control will withstand the short-circuit rating of the regulator without damage or loss of calibration.
Calculated Values - kVA, kW, kvar
0-9999, with error not to exceed 1%* under all conditions.
Harmonic Analysis - Current and Voltage Harmonics
3, 5, 7, 9, 11, 13th harmonic frequencies and THD, with error not to exceed 5%* under all conditions.
*Basic accuracy of the device, excluding P.T. and C.T. errors
†0.5% on 120 volt base; (0.5%) (120)=0.6 volts technique, called Discrete Fourier Analysis, is then performed on this data. This permits extremely accurate resolution of both the voltage and current input signals. It is this technique which enables the control to do harmonic analysis (to the 13th harmonic frequency), as well as measurements for metering and control.
All control setting values, instantaneous and demand metering values, tap position values and diagnostic values can be displayed on the LCD screen. (Some reverse power flow operation modes and metering require source side voltage, from either an optional differential potential transformer or the source voltage calculator in the control [CL5C and later.])
The entire control data base (all Function Codes) may be copied through the control Data Port to an optional
McGraw-Edison Data Reader for transfer to a personal computer, or be copied directly to a personal computer.
The control can communicate digitally with a SCADA system.
2-1
McGraw-Edison VR-32 Regulator and CL-5 Series Control
NEUTRAL
INDICATING LIGHT
DRAG HAND
RESET SWITCH
CONTROL SWITCH
(AUTO/REMOTE-OFF-
MANUAL)
MANUAL RAISE/
LOWER SWITCH
SUPERVISORY
ON/OFF SWITCH
MOTOR FUSE
DIFFERENTIAL
VOLTAGE FUSE
PANEL FUSE
Figure 2-1.
CL-5 series control front panel
2-2
LCD DISPLAY
KEYPAD
DATA PORT
POWER SWITCH
(INTERNAL-OFF-
EXTERNAL)
VOLTMETER
TERMINALS
EXTERNAL POWER
TERMINALS
S225-10-10
Front Panel Components
Lower Section - Grey
The lower section of the control contains components which are similar to the other controls in the McGraw-
Edison CL series.
Power Switch
In the external position, the control and tap changer motor are powered from an external 120 V ac source connected to the external source terminals. In the internal position, the control and motor get power from the regulator. In the off position, no power is delivered to either the control or the motor.
External Power Terminals
Providing 120 V ac to these terminals powers the control and tap changer motor. See page 1-3 for cautionary note. Controls wired for an external source of 220-240 V ac have a “240” decal at the terminals.
Control Switch
In the auto/remote position, the tap changer motor can be controlled by either the front panel (auto) or remotely by SCADA. In the off and manual positions, automatic operation and analog-type remote motor control are inhibited. In the manual position, automatic operation and analog-type remote motor control are inhibited and the tap changer may be raised or lowered locally by momentarily depressing the raise/lower switch.
Manual (Raise/Lower) Switch
This switch allows the operator to manually raise or lower the tap changer motor.
Supervisory Switch
This switch is used for digital communications only.
When in the on position, SCADA has full capabilities.
When in the off position, SCADA may only read the control database. See DIGITAL SCADA, page 4-11.
Draghand Reset Switch
This switch operates a solenoid in the Position Indicator to move the draghands to the present position of the main hand.
Neutral Light
This is the primary indication that the tap changer is in the neutral position. See Determining Neutral Position, page 1-11.
Figure 2-2.
Keypad
Voltmeter Terminals
These allow the connection of a voltmeter so that the potential sensed by the control (between the load (L) bushing and SL bushing of the regulator) can be measured.
Fuses
The motor fuse is a 6.25 A slow-blow fuse. The 2 A panel fuse protects the control panel circuit. The 2 A differential voltage fuse protects the circuit from miswiring of an external PT.
Data Port
This was first introduced on the CL-4 control. It allows the temporary connection of a McGraw-Edison Data
Reader or personal computer. See Data Retrieval and
Settings Uploading, page 4-12.
Upper Section - Black
The man-machine interface chosen for the CL-5 Series control is a 16-key touchpad and a liquid crystal display
(LCD).
The keypad, with a layout similar to a touch-tone telephone, has a snap-action response. (See Figure 2-2.)
The special, low-temperature LCD was chosen to be easily visible in direct sunlight. (See Figure 2-3 for a diagram of the LCD with all of the segments on.)
SET
VOLTAGE
1
BAND
WIDTH
2
LINE DROP
RESISTIVE
4
LINE DROP
REACTIVE
5
TIME
DELAY
3
OUTPUT
VOLTAGE
6
FUNCTION
INPUT
VOLTAGE
7
–
COMP.
VOLTAGE
8
OPERATION
COUNTER
0
LOAD
CURRENT
9
+
DISPLAY
OFF
CHANGE
RESET
ENTER
2-3
McGraw-Edison VR-32 Regulator and CL-5 Series Control
FUNCTION-CODE
FIELD
HOUR, MINUTE
LOW
LOW
V. RED.
HIGH
HIGH
REV. PWR.
MONTH, DAY
Figure 2-3.
Display fields
Control Operation
In the automatic mode of operation, the power switch will be set on internal, and the control switch will be placed on auto. The regulator is assumed energized from the primary circuit. If the sequential mode of operation is selected (the standard mode), the control response is as follows:
1. As the primary voltage moves to a level which represents an out-of-band condition, the sensing voltage will correspondingly reflect the same results on the 120 V base. Assuming the voltage dropped low, a lower than nominal signal will appear at the printed circuit board input, terminals P
5
-4 to P
5
-3.
2. The signal is transformed and converted into a digital format for use by the microprocessor.
3. The microprocessor, recognizing the voltage condition as low and out-of-band, issues an output which activates the LOW band indicator in the display, and starts an internal timer which is equivalent to the time delay setting.
4. During the time-out period, the voltage is continually sensed and sampled. Should the voltage momentarily move into band, the low band indicator is deactivated and the timer is reset.
5. At the end of the time delay period, the microprocessor issues an output which causes the
RAISE relay coil to be energized.
6. The tap changer motor begins to turn as a result of the relay closure, and a cam on the tap changer closes the RAISE holding switch. This now provides an alternate source for the motor current, which passes through the input terminals P
4
-9 and
P
4
-11 on the circuit board.
7. The microprocessor now recognizes that current is flowing in the holding switch circuit; the operations counter and tap position indication are incremented, and the RAISE relay is de-energized, thus opening its contacts.
8. As a result of the relay contacts opening, the motor current is now carried solely by the holding switch circuit. When the motor rotation is complete, the holding switch opens as a result of the cam action, and the motor stops.
9. The microprocessor recognizes that the tap change is now complete by detecting that motor current is no longer flowing through input terminals
P
4
-9 and P
4
-11. A 2-second pause then occurs, allowing the sensing voltage to stabilize from the motor operation.
10. At the end of this pause, if the voltage is still out-of-band, another output is issued to close the RAISE relay, thus starting another tap change sequence (step 6). If the voltage is in-band, the
LOW band indicator is turned off, and the time delay timer is reset. At all times, the microprocessor is sampling the sensing voltage for a change of conditions.
This sequence is altered slightly if the voltage averaging or time integrating mode of operation is selected. These characteristics are described in Control Operating
Modes, starting on page 2-8.
Manual Operation
In the manual mode of operation, the power switch can be set on either internal or external and the control switch will be placed on manual. If the external position is chosen, an external source must be applied through the terminals on the front panel. This should be a nominal 120 V ac source (or other ac voltage as indicated by a decal) and should not be a direct current
(dc) to alternating current (ac) inverter.
Operation of the momentary toggle raise-lower switch applies power through the position indicator limit switch contacts directly to the tap changer motor. As the tap changer motor cam rotates, the holding switch is closed, as described in the preceding section, step 6. This holding switch current is sensed by the circuit board, and the operations counter and tap position indicator are appropriately incremented (Function Code 0).
Tap changes will continue to occur as long as the raiselower switch is closed and the ADD-AMP limit switch is not opened.
System Protection
All control inputs (15) are protected with metal oxide varistors (MOVs) and capacitors to prevent damage from line surges and high-frequency transients. This protection concept has proven very effective in the surge tests conducted by Cooper Power Systems. Provisions
2-4
S225-10-10 have also been made in the design to further enhance the control operation under adverse conditions. Orderly operation is ensured by MERTOS4, an operating system developed by Cooper Power Systems for microprocessor-based systems. There are four error detection firmware activities, overseen by MERTOS4, which are an inherent part of the normal operation:
1. The microprocessor architecture includes a COP
(Computer Operating Properly) watchdog system to protect against firmware failures. A watchdog reset sequence is executed on a periodic basis so that the watchdog timer is never allowed to time out. Should the firmware malfunction, the reset sequence will not be generated, and the
COP will time out, causing the system to enter a diagnostic routine.
2. MERTOS4 continually polls the various firmware tasks to ensure that they are performing correctly.
If an abnormality is encountered, MERTOS4 will cause the system to enter a diagnostic routine.
3. Throughout the unused memory space, commands are embedded which generate a system reset if executed. Should an event occur which causes the processor to run errantly into unused memory space, the system will immediately be directed to a diagnostic routine.
4. Settings programmed into the control are stored in non-volatile memory in triplicate. A voting scheme is used as each parameter is accessed.
If one of the three values does not match, the
“different” value will be corrected to agree with the other two. This will also be counted as an
EEPROM correction and the “Number of EEPROM
Corrections” (Function Code 93) will be increased by 1.
If all three values are different, a “default” value
(one that is chosen as a representative value programmed into ROM), will be used for that particular parameter. If a setting parameter defaults, the “Number of Defaults” (Function
Code 90) will be increased by 1. Additionally, when interrogated, the parameter(s) that defaulted will display a “d” preceding the value to indicate it is a default. The control will continue to operate using the default value(s).
Three parameters cannot default to a predetermined value because no logical choice is possible. The three parameters, regulator configuration (Function Code 41), system line voltage (Function Code 43), and overall P.T.
ratio (Function Code 44) will revert to an invalid status and will display dashes preceded by a “d”. Anything dependent upon these values will cease to function, and
Function 95 will display a “6” to represent invalid critical parameters.
Diagnostics
There are three events which force the control into the self-diagnostic routines: 1) The power is first turned on; 2) operator entry of the self-test mode (Function
Code 91); or 3) MERTOS4 detects a firmware problem.
Once the diagnostic routines are entered, the first action taken by the control is to light all segments of the LCD display for approximately six seconds. This provides the operator an opportunity to observe the display for defective segments. Activities are performed as follows:
1. Non-volatile memory is checked to ensure all locations can be written to and erased;
2. The frequency detection circuitry is checked to verify a signal frequency between 45 and 65 Hz is being sampled;
3. The interrupt line to the processor is checked to verify that it is functional;
4. The multiplexor and analog-to-digital converter are checked to verify operation;
5. Critical parameters are checked to ensure validity;
6. The input/differential voltage channel is checked for the presence of a signal;
7. The output voltage channel is checked for the presence of a signal.
The duration of this test sequence is approximately three seconds. At completion, the display will indicate PASS or
FAIL, depending upon the test results. The PASS message will remain in the display until the operator makes an entry through the keypad, or 30 minutes if no keypad entry is made. After 30 minutes, the display will automatically be turned off. The PASS message will be preceded by dashes (----) if the internal calendar/clock requires resetting. If, after 30 minutes, no keys have been pressed, the display will be formatted showing four dashes (----) only if the calendar/clock requires resetting.
The clock will maintain timekeeping for 24 hours after loss of ac power to control. The backup power source requires 65 hours operation on ac power to become fully charged.
“Soft” failures are those listed under Function Code 95,
System Status Code. Keypad entry is allowed, but automatic operation is inhibited for the following System
Status Codes: 3, 4, 5, 6 and 8. Automatic operation is resumed as soon as the problem condition is removed. If status code is 10, see tap position indication, page 4-3.
For a “hard” failure, such as a RAM malfunction, the control will not operate. For hard failures the FAIL message remains in the display for approximately 15 minutes, then the diagnostic routines are executed again. The control will attempt to overcome the problem
2-5
McGraw-Edison VR-32 Regulator and CL-5 Series Control
TABLE 2-2
Security Codes
Security Level
0
1
Accessible at
Function Code
No Code Required
Factory Programmed
Code
No Code Required
User Definable
Range
No Code Required
96 1234 1-9999
2
3
97
98
12121
32123
10000-19999
20000-32766
Functions Available at the Active Code
Read all parameters except security
(Function Codes 96, 97, & 98).
Read all parameters as described above, and reset all demand metering and tap position maximum and minimum values and date/times.
Read all parameters as described above, reset all demand meter and tap position maximum and minimum values and date/times, and change any operational or setup parameter.
Read, reset or change any parameter.
that disabled it by going through this process continually until it receives operator attention. Keypad entry is denied during a hard failure.
NOTE: The word ERROR on the LCD indicates a key entry error, not a diagnostic failure. See Table 9-2, page 9-2 for a listing of the error codes.
Security System
The security (password) system implemented on the control is structured into four (4) levels. This permits selective access to the various parameters as dictated by the active security level. Most Function Codes may be read (accessed) at level 0, the base (unsecured) level. The security level required to change or reset each parameter is listed in Table 3-1, page 3-1. The security access codes for levels 1, 2 and 3 have been programmed into the control at the factory. These codes may be changed by the user according to Table 2-2.
Access into the system is accomplished by entering the appropriate security code at Function Code 99.
The user has the option of overriding (inhibiting) one or more levels of security by choosing the appropriate
Security Override Code at Function Code 92. Choices at Function 92 are 0 = standard security mode (no override); 1 = override level 1; 2 = override levels 2 and 1, and 3 = override levels 3, 2 and 1.
The values of the three security codes, Function Codes
96, 97 and 98, may be read only at level 3. If the level 3 code has been changed and forgotten, it may be retrieved with the McGraw-Edison Data Reader or with a personal computer using the Cooper Control
Interface (CCI) CL-4/CL-5 Interface program.
Working with the Control
Function Codes
All of the parameters of the control — settings, metering values, etc., have been assigned a number. This number is called the Function Code of the parameter. To read the value of a parameter — that is, to display the parameter on the LCD — the operator accesses the appropriate Function Code. The value appears on the
LCD, right-justified, with decimal point shown as necessary. See Table 3-1, page 3-1 for a list of the
Function Codes grouped by subject.
Accessing Function Codes
All parameters, except for the Profiler data, can be read at the LCD by accessing its Function Code by one of the following methods:
One-touch Method
Access Function Codes 0-9 directly by pressing keys
0-9. The parameter printed on these keys is the same as the Function Code number. EXAMPLE: Function
Code 1 = Set Voltage. Via the one-touch method, the operator may quickly read the Operations Counter (0), the five basic control settings (1-5), and the four most important instantaneous metering values (6-9).
Scroll Method
Use the scrolls keys — the upward- and downwardpointing arrows — to scroll up or down through the
Functions Codes. In addition to the main Function
Codes, there are Function Code Extensions. For
2-6
S225-10-10 instance, the extensions of Function Code 18, are 3, 5,
7, 9, 11 and 13. When Function Code 18 is accessed the
Total Harmonic Distortion (THD) is displayed. When one scrolls up from THD, the extension number 3 is displayed just to the right of the Function Code 18, denoting that the value displayed to the far right is the
3rd harmonic. Function code extensions may only be accessed by scrolling.
Function Key Method
One may scroll to Function Codes numbered higher than
9, but a more convenient method is to do the following:
Press the FUNCTION key, key in the Function Code number, and press the ENTER key. EXAMPLE: To access Function Code 18: Press FUNCTION, 1, 8,
ENTER. The Function Code and its value will be displayed.
For security, certain parameters may only be accessed by the function key method. They are as follows:
• 38 - Master Metering & Tap Position Reset
• 47 - Voltage Calibration
• 48 - Current Calibration
• 89 - Software Version Number
• 91 - Self Test
• 99 - Enter Security Code
LCD Annunciator
The left third of the LCD is the Annunciator field. The operator is advised of the present status of operations by words which appear in this field. While Function Codes and their values are dropped from the LCD 30 minutes after the last keypad activity, the annunciator field is always active.
On the band indicator line, LOW or HIGH indicate an out-of-band condition. (See Control Operating Modes, page 2-8 for details.) On the voltage limiter line LOW or
HIGH indicate that the voltage limiter is operating. (See page 4-8.) On the accessory active line V. RED.
indicates that voltage reduction is active. (See page
4-9.) Also on that line, REV. PWR. indicates that the regulator is currently experiencing a reverse power condition, except when Function Code 56 is set to zero,
Locked Forward. (See Reverse Power Flow Operation, page 4-3)
To display all of the segments of the LCD; if the control is off, turn on; or if the control is on, access Self Test,
Function Code 91.
Basic Control Operations
Set Voltage
The set voltage is the voltage level to which the control will regulate, on the 120 V base. Since the control performs ratio correction in software, this value will normally be set for 120.0 V unless it is desired to operate at a voltage level higher or lower than nominal.
For proper operation, the ratio correcting transformer located on the control back panel must also be set for the correct tap as shown by the regulator nameplate.
Bandwidth
The bandwidth is defined as that total voltage range, around the voltage setting, which the control will consider as a satisfied condition. As an example, a 2 V bandwidth on a 120 V setting means the operational timer will not activate until the voltage is below 119 V or above 121 V. When the voltage is in-band, the band edge indicators are off, and the timer (time delay) is off, so no relay closure can occur. Selection of a small bandwidth will cause more tap changes to occur, but will provide a more “tightly” regulated line. Conversely, a larger bandwidth results in fewer tap changes, but at the expense of better regulation. Selection of the bandwidth and time delay settings should be made recognizing the interdependence of these two parameters.
Time Delay
The time delay is the period of time (in seconds) that the control waits, from the time when the voltage first goes out-of-band, to the time when relay closure occurs. If a rapid response is required, a smaller setting should be used. If several devices on the same line are to be coordinated (cascaded), different time delay settings will be required to allow the proper devices to operate in the desired sequence. Proceeding from the source, each device should have a longer time delay than the preceding device. We recommend a minimum 15 second difference between regulators located on the same phase on the same feeder. The delay allows the upstream device to perform its operations prior to the downstream device reacting. The time delay setting of a voltageminimizing activated capacitor control should be set the same as a regulator control. Alternate time delays are available with the voltage limiting feature, page 4-8.
Line Compensation, Resistance and
Reactance Settings
Quite often regulators are installed some distance from the theoretical load center (the location at which the voltage is to be regulated). This means the load will not be served at the desired voltage level due to the losses
(voltage drop) on the line between the regulator and the load. Furthermore, as the load increases, line losses also increase, causing the lowest voltage condition to occur during the time of heaviest loading.
To provide the regulator with the capability to regulate at a “projected” load center, manufacturers incorporate line drop compensation elements in the controls. This circuitry usually consists of a current source (C.T.) which
2-7
McGraw-Edison VR-32 Regulator and CL-5 Series Control produces a current proportional to the load current, and resistive (R) and reactive (X) elements through which this current flows. As the load increases, the resulting
C.T. current flowing through these elements produces voltage drops which simulate the voltage drops on the primary line.
For the control, the input current is sampled and is used in a computer algorithm which calculates the respective resistive and reactive voltage drops based upon the line drop compensation values, programmed into the control at Function Codes 4 and 5 (or Function Codes 54 and
55 for reverse power flow conditions). This is by far a more accurate and economical means of developing the compensated voltage.
To select the proper R and X values, the user must know several factors about the line being regulated.
See reference document R225-10-1 for assistance in this determination.
Regulator Configuration
The control is designed to operate on wye (star) connected and delta-connected regulators. Regulators connected line-to-ground (wye) develop potentials and currents suitable for direct implementation in the control.
Regulators connected line-to-line (delta) develop a potential-to-current phase shift which is dependent upon whether the regulator is defined as leading or lagging.
The phase shift must be known by the control to permit accurate calculations for correct operation. This is accomplished by entering the proper code: 0 = Wye, 1 =
Delta Lagging, 2 = Delta Leading.
See page 1-7 for an explanation of how to determine whether the regulator is leading or lagging.
Control Operating Modes
Cooper Power Systems is the only manufacturer that offers a selection of three modes in which the control responds to out-of-band conditions. This permits the user to select the mode that best fits the application.
These modes and their corresponding codes are:
0 = Sequential, 1 = Time Integrating, 2 = Voltage
Averaging.
Sequential
This is the standard mode of response, incorporated on all McGraw-Edison CL-5 Series regulator controls.
When the load voltage goes out-of-band, the time delay circuit is activated. At the end of the time-out, a tap change is initiated. After each tap change, a 2-second pause occurs to permit the control to sample the voltage again. This sequence continues until the voltage is brought into band, at which time the timing circuit is reset. Any time the voltage goes in-band, the timer is reset.
Time Integrating
When the load voltage goes out-of-band, the time delay circuit is activated. At the end of the time-out, a tap change is initiated. After each tap change, a 2-second pause occurs to permit the control to sample the voltage again. If the voltage is still out-of-band, another tap change is performed. This sequence continues until the voltage is brought into band. When the voltage goes inband, the timer is decremented at the rate of 1.1
seconds for every second elapsed, until it reaches zero.
Voltage Averaging
When the load voltage goes out-of-band, the time delay circuit is activated. During this time delay period, the microprocessor monitors and averages the instantaneous load voltage. It then computes the number of tap changes required to bring the average voltage back to the set voltage level. When the time delay period is complete, the computed number of tap changes are performed without any delay between them, up to a maximum of 5 consecutive tap changes, to avoid an accumulative error. The timer is not reset on voltage excursions in-band unless the voltage stays in-band for at least 10 continuous seconds. An error-averaging characteristic is inherent with the voltage averaging mode.
NOTE: To permit sufficient time for the microprocessor to average the voltage, the time delay period must be 30 seconds or longer. If the time delay is set for less than
30 seconds, the control ignores the setting and uses 30 seconds.
System Line Voltage
The control performs ratio correction in software, and, consequently, the primary voltage must be entered for the control to perform this calculation. This value is simply the nominal single phase voltage supplied across the L and SL terminals. Regulators shipped from the factory are set for the voltage indicated by the pin on the nameplate, and this value is programmed into the control. If the regulator is installed on any other system voltage, this system voltage must be entered for proper operation. See page 1-19, Voltage Circuits, for other changes required.
Potential Transformer Ratio
Since the control performs ratio correction in software, the P.T. ratio for the voltage sensing supply must be entered for the control to perform this calculation. The ratio to be programmed in the control is the OVERALL
P.T. RATIO, as shown on the regulator nameplate for every applicable system voltage for the particular regulator. The P.T. ratio which corresponds to the regulator rated voltage is set by the factory. If the
2-8
S225-10-10 regulator is installed on any other system voltage, the corresponding P.T. ratio must also be entered for proper operation. This value includes the correction performed by the ratio correcting transformer (RCT) on the control back panel. The voltage from the RCT is normally corrected to 120 V. However, in the instance in which this voltage is other than 120 V, the control will define the particular input voltage as the 120 V base voltage, and 120 V will be displayed at Function Code 6. The voltage test terminals will continue to show the voltage as applied to the control from the RCT.
Current Transformer Primary Rating
The control is designed for 200 mA (full scale) as the rated C.T. current, and will meter to 400 mA (200% load) with no loss of accuracy. Ratio correction is performed by the software, and consequently, the C.T. primary rating must be entered. The C.T. primary rating is available on the regulator nameplate. EXAMPLE: If a
C.T. ratio of 400/0.2 is indicated on the nameplate, then
400 must be entered at Function Code 45. (See Table 1-
9, page 1-17 for standard ratings.)
Delta-connected (Line-to-lineconnected) Regulators
When a regulator is connected line-to-line, the phase angle of the line current is 30° displaced from the voltage impressed across the regulator. By setting the
Regulator Configuration, FC 41, correctly, the correct relationship between the voltage and current is established. (See page 1-7.) By setting the Regulator
Configuration to the incorrect delta value (lagging instead of leading, or vice versa), the phase angle will be in error 60°. Below are considerations concerning delta-connected regulators:
1. The basic decision-making of the control when line drop compensation is not used is not affected by the phase angle, therefore operation will be correct even if FC 41 is set to either of the two incorrect values. This is true for forward and reverse operation.
2. If line drop compensation is used, the scaling of the R and X values and the positive/negative sign of these values is controlled by FC 41, therefore, it is important to correctly set FC 41.
3. The following metering parameters will be correct only if the Regulator Configuration is correctly set: power factor, kVA, kW, kvar, demand kVA, demand kW and demand kvar.
4. Note that the kVA, kW, kvar, demand kVA, demand kW and demand kvar use the line-to-line voltage, therefore they display the value at the regulator, not on one feeder. To determine the total three-phase value of any one of these parameters, each regulator value must be divided by 1.732 before adding the three together.
2-9
McGraw-Edison VR-32 Regulator and CL-5 Series Control
Control Function Codes
TABLE 3-1
CL-5 Series Regulator Control Function Codes
Function
Code
Function
Security
Level
Change/Reset
FORWARD CONTROL SETTINGS
0 Operation Counter (Q, R_, R
_
, 1, 2, 3, 4, 5, 6)* 3*
2
3
4
5
Bandwidth, volts
Time Delay, seconds
Line Compensation Resistance, volts
Line Compensation Reactance, volts
2
2
2
2
2
INSTANTANEOUS METERING
6 Load Voltage, Secondary
7
8
Source Voltage, Secondary
Compensated Voltage, Secondary
9
10
11
12
Load Current, Primary, amperes
Load Voltage, Primary, kV
Source Voltage, Primary, kV
Tap Position & Percent Regulation (TP, %)
13
14
15
16
17
18
19
Power Factor kVA Load kW Load kvar Load
Line Frequency
3
Voltage Harmonics (THD, 3, 5, 7, 9, 11, 13), percent
Current Harmonics (THD, 3, 5, 7, 9, 11, 13), percent
FORWARD DEMAND METERING
20 Load Voltage (H-D, T; L-D, T; P)
21
22
Compensated Voltage (H-D, T; L-D, T, P)
Load Current (H-D, T; L-D, T; P), amperes
23H
23L
Power Factor @ Max kVA Demand
Power Factor @ Min kVA Demand
24
25
26
27
28
29 kVA Load (H-D, T; L-D, T; P) kW Load (H-D, T; L-D, T; P) kvar Load (H-D, T; L-D, T; P)
Max Tap Pos & Max % Boost (TP-D, T; %)
Min Tap Pos & Max % Buck (TP-D, T; %)
Source Voltage **(H-D, T; L-D, T; P)
1
1
1
REVERSE DEMAND METERING
30 Load Voltage (H-D, T; L-D, T; P)
31
32
Compensated Voltage (H-D, T; L-D, T; P)
Load Current (H-D, T; L-D, T; P), amperes
33H
33L
34
Power Factor @ Max kVA Demand
Power Factor @ Min kVA Demand kVA Load (H-D, T; L-D, T; P)
35
36
37 kW Load (H-D, T; L-D, T; P) kvar Load (H-D, T; L-D, T; P)
Source Voltage**(H-D, T; L-D, T; P)
CONFIGURATION
39 Source Voltage Calculation
0 = Off, 1 = On;
1 = Type A, 2 = Type B
40
41
Regulator Identification
Regulator Configuration
0 = Wye, 1 = Delta Lag, 2 = Delta Lead
42
43
44
45
Control Operating Modes
0 = Sequential, 1 = Time Integrating,
2 = Voltage Averaging
System Line Voltage, volts
Overall P.T. Ratio
C.T. Primary Rating, amps
1
1
1
1
1
1
MASTER METERING & TAP POSITION INDICATION RESET
38 Reset 1
2
2
2
2
2
2
2
1
1
1
1
1
Notes:
H-D, T = Highest (maximum) value since last reset, date & time
L-D, T = Lowest (minimum) value since last reset, date & time
P = Present value
THD = Total Harmonic Distortion
TPI = Tap position indication
Function
Code
Function
46
49
Demand Time Interval, minutes
Tap Changer Selection
0 = Quik Drive, 1 = Spring/Direct Drive
CALIBRATION
47
48
Voltage Calibration, volts
Current Calibration, amps
CALENDAR/CLOCK
50 Date & Time Set (D, T, 1, 2, 3, 4, 5, 6)
1 = Year, 2 = Month, 3 = Day,
4 = Hour, 5 = Minute, 6 = Second
REVERSE CONTROL SETTINGS
51 Set Voltage, volts
52
53
54
55
56
Bandwidth, volts
Time Delay, seconds
Line Compensation, Resistance, volts
Line Compensation, Reactance, volts
Reverse Sensing Mode
0 = Locked Forward, 1 = Locked Reverse
2 = Reverse Idle, 3 = Bi-Directional
4 = Neutral Idle, 5 = Co-Generation
57
6 = Reactive Bi-directional
Reverse Threshold %
COMMUNICATIONS
60 Channel 1 (Data Port) Baud Rate
61 Control Communication Protocol
62
63
64
65
66
67
68
69
XX.03 = Data 2179
Channel 1 (Data Port) Status
Channel 2 (Comm Port) Status
Control Communications Address
Channel 2 (Comm Port) Baud Rate
Comm Port Handshake Mode
Comm Port Resynch Time Chars.
Comm Port Transmit Enable Delay (On, Off)
Blocking Status
0 = Normal, 1 = Blocked
75
76
77
79
71
72
73
74
VOLTAGE REDUCTION
70 Voltage Reduction Mode
0 = Off, 1=Local/Digital Remote,
2 = Analog Remote (Latching), 3 = Pulse
10 = Off, 11 = Local/Digital Remote,
12 = Analog Remote (Latching), 13 = Pulse
(Utilizing 10-13 activates tap to neutral)**
% Voltage Reduction In Effect (Read Only)
Local Reduction %
Remote #1 %
Remote #2 %
Remote #3 %
# of Pulse Reduction Steps
% of Voltage Reduction Per Pulse Step
Soft ADD-AMP limits**
0 = Off, 1 = On;
High limit; Low limit;
VOLTAGE LIMITER
80 Voltage Limiting Mode
0 = Off, 1 = High Limit Only
2 = High and Low Limits
81
82
High Voltage Limit, volts
Low Voltage Limit, volts
Security
Level
Change/Reset
2
3
3
3
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Q = Quantity of operations since last change
R = Time of last counter change
* Change/Reset and Sub-function codes only on CL-5E control
** CL-5E only
See next page for more function codes
3-1 3
S225-10-10
2
Function
Code
Function
METERING PROFILE RECORDER
85 Profile Period
(5, 10, 15, 30, 60, 90, 120 min.)**
1 = Parameter 1, 2 = Parameter 2,
3 = Parameter 3, 4 = Parameter 4,
5 = Data Retrieval Mode (0 = Off, 1 = On)
WATCHDOG DIAGNOSTICS
89
90
Firmware Version #
Number of Defaults
91
93
94
95
Self Test
Number of EEPROM Corrections
Number of Resets
System Status Code (Read Only)
0 All Systems Good
1 EEPROM Write Failure
** CL-5E control only.
TABLE 3-2
Function Codes
Security
Level
Change/Reset
1
3
3
Function
Code
00
00*
Function
Code
Function
2 EEPROM Erase Failure
3 Frequency Detection Failure
4 No Sampling Interrupt-Failure
5 Analog-To-Digital Converter-Failure
6 Invalid Critical Parameters-Failure
7 No Input Voltage Detected-Warning
8 No Output Voltage Detected-Failure
9 No Input & Output V Detected-Failure
10 TPT No Neutral Sync Signal-Warning
SECURITY ACCESS
92
96
Security Override (1 = Override 1, etc.)
Level 1 Security Code
97
98
99
Level 2 Security Code
Level 3 Security Code
ENTER SECURITY CODE
Security
Level
Change/Reset
3
3
3
3
Function
Code
Extension
Parameter
Unit of
Measure
To
Read
Security Level
To To
Change Reset
Default
Value
Key Entry
Limit
Low High
—
Q,R_,R
_
,1
2, 3, 4, 5 ,6
Operation Counter
• The operation counter is activated by detecting tap changer motor operation which is determined by sensing current flow in the holding switch circuit.
• The operations count is written into non-volatile memory after every ten (10) counts.
• In the event of a power outage, the count will round back to the nearest ten (10), and then add five (5) to obtain the restored count when power recovers. EXAMPLE: Count 218; After Power Loss/Recovery = 215
Operation Counter
—
—
0
0
NA
3
NA
3
NA
NA
NA
NA
NA
NA
• The operation counter is activated by detecting tap changer motor operation which is determined by sensing current flow in the holding switch circuit.
• The main operations count is written into non-volatile memory after every ten (10) counts. The subfunction counts are written to non-volatile memory hourly, or daily, as specified below.
• In the event of a power outage, the main operations count will round back to the nearest ten (10), and then add five (5) to obtain the restored count when the power recovers. EXAMPLE: Count 218; After Power Loss/Recovery = 215. Applicable subfunction codes
(1, 2, & 3) shall reset to zero in the event of a power outage.
01 date, R for time of the last counter change. This counter may be set to a specific value.
• 1-6 are subfunctions of function code 00. They are all resettable. They are defined as follows:
• 1 = Operations in the last 24 hours (updated hourly)
• 2 = Operations in the last 30 days (updated daily)
• 3 = Operations since the beginning of current month (updated daily, and reset if clock’s month is changed.)
• 4 = Operations last calendar month (if reset, this field will remain zero until the first of the next month.)
• 5 = Operations since January 1st of current year (updated daily, and reset if clock’s year is changed.)
• 6 = Operations in last calendar year (if reset, this field will remain zero until the first of the next year.)
— Set Voltage (Forward) V 0 2 NA 120.0
100.0
135.0
02
• The set voltage is the voltage level to which the control will regulate, on the 120 V base, during forward power flow.
— Bandwidth (Forward) V 0 2 NA 2.0
1.0
6.0
03
• The bandwidth is defined as the total voltage range, around the set voltage, which the control will consider as a satisfied
(in-band) condition, during forward power flow. EXAMPLE: A bandwidth of 2.0 V and a set voltage of 120 V will establish a low limit of 119.0 V and a high limit of 121.0 V.
— Time Delay (Forward) sec.
0 2 NA 30 5 180
• The time delay is the period of time that the control waits, from when the voltage first goes out-of-band to when a tap change is initiated, during forward power flow.
• See Function Code 42, Control Operating Mode.
* CL-5E control only.
3-2
McGraw-Edison VR-32 Regulator and CL-5 Series Control
Function
Code
04
05
06
07
08
09
10
11
12
Function
Code
Extension
Parameter
Unit of
Measure
Security Level
To To To
Read Change Reset
Default
Value
Key Entry
Limit
Low High
—
Line Compensation,
Resistance (Forward)
V 0 2 NA 0.0
–96.0
96.0
• The resistive line drop compensation value is used to model the resistive line voltage drop between the regulator and the theoretical load center.
• The control uses this parameter, in conjunction with the regulator configuration (Function Code 41) and the load current, to calculate and regulate to the compensated voltage (displayed at Function Code 8) during forward power flow.
—
Line Compensation,
Reactance (Forward)
V 0 2 NA 0.0
–96.0
96.0
• The reactive line drop compensation value is used to model the reactive line voltage drop between the regulator and the theoretical load center.
• The control uses this parameter, in conjunction with the regulator configuration (Function Code 41) and the load current, to calculate and regulate to the compensated voltage (displayed at Function Code 8) during forward power flow.
— Load Voltage, Secondary V 0 NA NA NA NA NA
• This is the fundamental RMS voltage, referred to the secondary, which appears at the output (load) terminals of the regulator.
• Since ratio correction is performed by the firmware, this parameter is scaled according to the inputs at Function Code 43
(System Line Voltage) and Function Code 44 (overall PT Ratio).
— Source Voltage, Secondary V 0 NA NA NA NA NA
• This is the fundamental RMS voltage, referred to the secondary, which appears at the input (source) terminals of the regulator.
• Since ratio correction is performed by the firmware, this parameter is scaled according to the inputs at Function Code 43
(System Line Voltage) and Function Code 44 (overall PT Ratio).
• The control requires source voltage from a differential or source potential transformer or from the source voltage calculator to obtain this parameter. Lack of this voltage will result in the parameter displaying dashes. Refer to page 4-1.
— Compensated Voltage, Secondary V 0 NA NA NA NA NA
• This is the calculated voltage at the load center, referred to the secondary.
• This is based upon the resistive compensation setting (Function Codes 4 or 54), reactive compensation setting (Function
Codes 5 or 55), and the load current.
• This is the voltage that the regulator is regulating during either forward or reverse power flow.
— Load Current, Primary A 0 NA NA NA NA
• This is the fundamental RMS current flowing in the primary circuit.
• This parameter is scaled according to the CT primary rating which is entered at Function Code 45.
— Load Voltage, Primary kV kV 0 NA NA NA NA
NA
NA
• This is the fundamental RMS voltage, referred to the primary, which appears at the output (load) terminals of the regulator.
• Since ratio correction is performed by the firmware, this parameter is scaled according to the inputs at Function Code 43
(System Line Voltage) and Function Code 44 (overall PT ratio).
— Source Voltage, Primary kV kV 0 NA NA NA NA NA
• This is the fundamental RMS voltage, referred to the primary, which appears at the input (source) terminals of the regulator.
• Since ratio correction is performed by the firmware, this parameter is scaled according to the inputs at Function Code 43
(System Line Voltage) and Function Code 44 (overall PT ratio).
• The control requires an input voltage from a differential or source potential transformer to obtain this parameter. Lack of this voltage will result in the parameter displaying dashes. Refer to page 4-1.
P Tap Position Indication Tap 0 3 NA NA –16 16
• This is the present position of the tap changer.
• The tap position indication is reset when in the neutral position, as indicated by the neutral light circuit. Tap positions are displayed from – 16 to 16 corresponding to 16 Lower (regulator bucking) to 16 Raise (regulator boosting), respectively.
• Function Code 12P may be changed via the keypad by accessing security level 3.
• This is the actual percentage that the regulator is actively boosting (raising) or bucking (lowering) the input (source) voltage.
• This parameter is displayed after pressing the scroll-up key after entering function Code 12.
• This is calculated as follows: Percent Regulation = ([Output/Input] -1) x 100
3-3 3
2
S225-10-10
Function
Code
12 (Cont.)
13
Function
Code
Extension
Parameter
Unit of
Measure
To
Read
Security Level
To To
Change Reset
Default
Value
Key Entry
Limit
Low High
NA — Percent Regulation % 0 NA NA NA NA
• When the regulator output voltage is greater than the input voltage (regulator boosting), the sign is implied (+). When the output voltage is lower than the input voltage.
• The control requires an input voltage to obtain this parameter.
Lack of this voltage will result in the parameter displaying dashes. Refer to page 4-1.
— Power Factor — 0 NA NA NA NA NA
• This is the power factor of the primary circuit, as represented by the phase difference between the line current and voltage.
• Lagging current, or inductive loads, are designated by an implied (+) sign, and leading current, or capacitive loads, are designated by a (-) sign
REVERSE POWER
I
UNITY
LAGGING
(+)
I
2
2
2
I
LEADING
(-)
E
FORWARD POWER
I
I
I
LEADING
(-)
E
UNITY
I
LAGGING
(+)
Figure 3-1.
Reverse power vector diagram.
Figure 3-2.
Forward power vector diagram.
14
15
16 kVA 0 NA NA NA NA NA
• This is the total kilovolt-amperes drawn by the load, as calculated by the product of the primary kV (Function Code 10) times the primary load current (Function Code 9). See Figure 3-3.
— kW Load kW 0 NA NA NA NA NA
• This is the total kilowatts (true power) consumed by the load.
• This is calculated by the product of the power factor (Function Code 13) times the kVA load (Function Code 14). See Figure 3-3.
— kvar Load kvar 0 NA NA NA NA NA
• This is the total kilovolt-amperes reactive (reactive power) drawn by the load.
• It is this reactive power which adds to losses on the line, yet does not do any work. See Figure 3-3.
kVA kvar
POWER FACTOR = kW
kVA kW = kVA cos kvar = kVA sin kW
Figure 3-3.
Power Triangle
3-4
McGraw-Edison VR-32 Regulator and CL-5 Series Control
Function
Code
17
18
19
20
21
22
23
Function
Code
Extension
Parameter
Unit of
Measure
Security Level
To To To
Read Change Reset
Default
Value
— Line Frequency Hz 0 NA NA NA
• This is the frequency of the power line, as measured by the control.
• The control is capable of operating on systems from 45 to 65 Hz with no loss of accuracy in its measurements.
Key Entry
Limit
Low High
NA NA
—
3, 5, 7, 9, 11, 13
Voltage THD
Voltage Harmonics
%
%
0
0
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
• The total harmonic distortion (THD) is displayed after entering Function Code 18. The harmonic contents at the 3rd, 5th, 7th, 9th,
11th and 13th harmonic frequencies are displayed by pressing the scroll-up key. “3, 5, 7, 9, 11, and 13” are displayed as a
Function Code extension to identify the individual harmonic values.
• The total harmonic distortion is computed as the RSS (square root of the sum of the squares) of the six individual odd harmonic values.
• The value displayed is a percentage of the fundamental RMS voltage. Example: 120.0 V of 60 Hz fundamental (power line frequency), with a reading of 0.5 at the 7th harmonic (420 Hz), is 0.6 V RMS.
—
3, 5, 7, 9, 11, 13
Current THD
Current Harmonics
%
%
0
0
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
• The total harmonic distortion (THD) is displayed after entering Function Code 19. The harmonic contents at the 3rd, 5th, 7th, 9th,
11th and 13th harmonic frequencies are displayed by pressing the scroll-up key. “3, 5, 7, 9, 11, and 13” are displayed as a
Function Code extension to identify the individual harmonic values.
• The total harmonic distortion is computed as the RSS (square root of the sum of the squares) of the six individual odd harmonic values.
• This is displayed as a percentage of the fundamental RMS voltage. Example: 200 A of 60 Hz fundamental (power line frequency), with a reading of 1.9 at the 5th harmonic (300 Hz), is 3.8 A RMS.
H, H_, H
_
,
L, L_, L
_
, P
Load Voltage Demand (Forward) V 0 NA 0 Reset** NA NA
• This is the secondary output voltage of the regulator, as a demand value, according to the demand time interval at Function
Code 46.
_ for time the maximum value occurred. Continue to scroll up to L, the lowest value since reset, L_ for date, and L occurred. Continue to scroll up to P for present value.
H, H_, H
L, L_, L
_
,
, P
Compensated Voltage Demand
(Forward)
V 0 NA 1 for time the lowest value
Reset** NA NA
• This is the calculated secondary voltage at the load center, as a demand value, according to the demand time interval at Function
Code 46.
• The line compensation settings for resistance and reactance (Function Codes 4 and 5) are used in this calculation.
_
_ the maximum value occurred. Continue to scroll up to L, the lowest value since reset, L_ for date, and L for time for time the lowest value occurred. Continue to scroll up to P for present value.
H, H_, H
L, L_, L
_
,
, P
Load Current Demand (Forward) A 0 NA 1 Reset** NA NA
• This is the load current, as a demand value, according to the demand time interval at Function Code 46.
_
_ maximum value occurred. Continue to scroll up to L, the lowest value since reset, L_ for date, and L for time the for time the lowest value occurred. Continue to scroll up to P for present value.
H
Power Factor at Maximum kVA Demand (Forward)
— 0 NA [A]
“----”
(invalid)
NA NA
• This is the instantaneous power factor of the load at the first time when the maximum kVA demand occurred, since last reset.
• (A) This parameter is associated with the maximum kVA demand and, therefore, cannot be reset independent of that parameter.
3-5
* CL-5E Control only.
**A default value of “Reset” indicates that the parameter is reset to the present value.
3
S225-10-10
2
Function
Code
23
24
25
26
27
Function
Code
Extension
Parameter
Unit of
Measure To
Read
Security Level
To To
Change Reset
Default
Value
Key Entry
Low
Limit
High
L
Power Factor at Minimum kVA Demand (Forward)
— 0 NA [A]
“----”
(invalid)
NA NA
• This is the instantaneous power factor of the load at the first time when the minimum kVA demand occurred, since last reset.
• The power factor at maximum kVA demand “H” is displayed when entering Function Code 23, scroll up to the power factor at minimum kVA demand “L” value.
• (A) This parameter is associated with the minimum kVA demand and, therefore, cannot be reset independent of that parameter.
H, H_, H
L, L_, L
_
,
, P kVA Load Demand (Forward) kVA 0 NA 1 Reset** NA NA
• This is the load kVA, as a demand value, according to the demand time interval at Function Code 46.
• H, the highest value since last reset, is displayed after entering this Function Code. Scroll up to H_, to obtain date, and H
_ the maximum value occurred. Continue to scroll up to L, the lowest value since reset, L_ for date, and L
_ for time for time the lowest value occurred. Continue to scroll up to P for present value.
H, H_, H
_
,
L, L_, L
_
, P kW Load Demand (Forward) kW 0 NA 1 Reset** NA NA
• This is the load kW, as a demand value, according to the demand time interval at Function Code 46.
• H, the highest value since last reset, is displayed after entering this Function Code. Scroll up to H_ to obtain date, and H
_ maximum value occurred. Continue to scroll up to L, the lowest value since reset, L_ for date, and L
_ for time the for time the lowest value occurred. Continue to scroll up to P for present value.
H, H_, H
L, L_, L
_
,
, P kvar Load Demand (Forward) kvar 0 NA 1 Reset** NA NA
• This is the load kvar, as a demand value, according to the demand time interval at Function Code 46.
• H, the highest value since last reset, is displayed after entering this Function Code. Scroll up to H_ to obtain date, and H
_ the maximum value occurred. Continue to scroll up to L, the lowest value since reset, L_ for date, and L
_ for time for time the lowest value occurred. Continue to scroll up to P for present value.
H, H_, H
_
Maximum Tap Position Tap 0 NA 1 Reset** NA NA
• This is the highest tap position that the regulator has reached since last reset.
• H, the highest position since last reset, is displayed after entering this Function Code. Scroll up to H_ for date, and H
_ highest position occurred.
for time the
• The maximum position and associated date and time can be reset via the reset key or via master reset. Function Code 38. This parameter is not reset by the draghand reset switch.
—
__
Maximum % Boost
(Minimum % Buck)
% 0 NA 1 Reset** NA NA
28
• Scroll up from 27 H to read this parameter.
• This parameter is the upper draghand value for the present percent regulation, Function Code 12.
• The control requires an input voltage from a differential or source potential transformer to obtain this parameter. Lack of this voltage will result in the parameter displaying dashes. Refer to page 4-1.
L, L_, L
_
Minimum Tap Position Tap 0 NA 1 Reset** NA NA
• This is the lowest tap position that the regulator has reached since last reset.
• L, the lowest position since last reset, is displayed after entering this Function Code. Scroll up to L_, for date, and L
_ for time the lowest position occurred.
• The minimum position and associated date and time can be reset via the reset key of via master reset, Function Code 38. This parameter is not reset by the draghand reset switch.
—
Maximum % Buck
(Minimum % Boost)
% 0 NA 1 Reset** NA NA
• Scroll up from 28 L to read this parameter.
• This parameter is the lower draghand value for the present percent regulation, Function Code 12.
• The control requires an input voltage from a differential or source potential transformer to obtain this parameter. Lack of this voltage will result in the parameter displaying dashes. Refer to page 4-1.
* CL-5E control only.
**A default value of “Reset” indicates that the parameter is reset to the present value.
3-6
McGraw-Edison VR-32 Regulator and CL-5 Series Control
Function
Code
29*
Function
Code
Extension
H, H_, H
L, L_, ,L
_
,
, P
30
31
32
Parameter
Source Voltage Demand
(Forward)
Unit of
Measure
V
Security Level
To To To
Read Change Reset
0 NA NA
Default
Value
NA
Key Entry
Limit
Low High
NA NA
• H, the maximum source voltage seen, is displayed after this function code is entered. Scroll up to H_ for date, and H maximum source voltage occurred. Continue scrolling up to see L, the lowest source voltage seen, followed by the L_ and L
_
, the date and time of its occurrence. Continue to scroll up to P to see the present value.
H, H_, H
L, L_, L
_
,
, P
Load Voltage Demand
(Reverse)
V 0 NA 1 Reset** NA NA
• This is the secondary output voltage of the regulator during reverse power flow, as a demand value, according to the demand time interval at Function Code 46.
• H, the highest value since last reset, is displayed after entering this Function Code. Scroll up to H_ to obtain date, and H
_ the maximum value occurred. Continue to scroll up to L, the lowest value since reset, L_ for date, and L
_ for time for time the lowest value occurred. Continue to scroll up to P for present value.
• The control requires an input voltage from a differential or source potential transformer to obtain this parameter. Lack of this voltage will result in this parameter displaying dashes. Refer to page 4-1.
H, H_, H
L, L_, L
_
,
, P
Compensated Voltage Demand
(Reverse)
V 0 NA 1 Reset** NA NA
• This is the calculated secondary voltage at the load center during reverse power flow, as a demand value, according to the demand time interval at Function Code 46.
• The line compensation setting for resistance and reactance (Function Codes 54 and 55) are used in this calculation.
• H, the highest value since last reset, is displayed after entering this Function Code. Scroll up to H_ to obtain date, and H
_ the maximum value occurred. Continue to scroll up to L, the lowest value since reset, L_ for date, and L
_ for time for time the lowest value occurred. Continue to scroll up to P for present value.
• The control requires an input voltage from a differential or source potential transformer to obtain this parameter. Lack of this voltage will result in this parameter displaying dashes. Refer to page 4-1.
H, H_, H
L, L_, L
_
,
, P
Load Current Demand
(Reverse)
A 0 NA 1 Reset** NA NA
33
33 the maximum value occurred. Continue to scroll up to L, the lowest value since reset, L_ for date, and L occurred. Continue to scroll up to P for present value.
for time for time the lowest value
• The control requires an input voltage from a differential or source potential transformer to obtain this parameter. Lack of this voltage will result in this parameter displaying dashes. Refer to page 4-1.
H
Power Factor at Maximum kVA Demand (Reverse)
— 0 NA [A]
“----”
(invalid)
NA NA
• This is the instantaneous power factor of the load at the first time the maximum kVA demand occurred during reverse power flow since last reset.
• The control requires an input voltage from a differential or source potential transformer to obtain this parameter. Lack of this voltage will result in this parameter displaying dashes. Refer to page 4-1.
• (A) This parameter is associated with the maximum kVA demand and, therefore, cannot be reset independent of that parameter.
L
Power Factor at Minimum kVA Demand (Reverse)
— 0 NA [A]
“----”
(invalid)
NA NA
• This is the instantaneous power factor of the load at the first time the minimum kVA demand occurred during reverse power flow since last reset.
• The power factor at maximum kVA demand “H” is displayed after entering Function Code 33, scroll up to the power factor at minimum kVA demand “L” value.
• The control requires an input voltage from a differential or source potential transformer to obtain this parameter. Lack of this voltage will result in this parameter displaying dashes. Refer to page 4-1.
• (A) This parameter is associated with the minimum kVA demand and, therefore, cannot be reset independent of that parameter.
* CL-5E control only.
** A default value of “Reset” indicates that the parameter is reset to the present value.
3-7 3
S225-10-10
2
Function
Code
34
Function
Code
Extension
H, H_, H
L, L_, L
_
,
, P
35
Parameter kVA Load Demand (Reverse)
Unit of
Measure kVA
Security Level
To To To
Read Change Reset
0 NA 1
Default
Value
Reset**
Key Entry
Limit
Low High
NA NA the maximum value occurred. Continue to scroll up to L, the lowest value since reset, L_ for date, and L occurred. Continue to scroll up to P for present value.
• The control requires an input voltage from a differential or source potential transformer to obtain this parameter. Lack of this voltage will result in this parameter displaying dashes. Refer to page 4-1.
for time for time the lowest value
H, H_, H
L, L_, L
_
,
, P kW Load Demand (Reverse) kW 0 NA 1 Reset** NA NA
36 the maximum value occurred. Continue to scroll up to L, the lowest value since reset, L_ for date, and L occurred. Continue to scroll up to P for present value.
• The control requires an input voltage from a differential or source potential transformer to obtain this parameter. Lack of this voltage will result in this parameter displaying dashes. Refer to page 4-1.
for time for time the lowest value
H, H_, H
L, L_, L
_
,
, P kvar Load Demand (Reverse) kvar 0 NA 1 Reset** NA NA
37*
38
39 the maximum value occurred. Continue to scroll up to L, the lowest value since reset, L_ for date, and L for time for time the lowest value occurred. Continue to scroll up to P for present value.
• The control requires an input voltage from a differential or source potential transformer to obtain this parameter. Lack of this voltage will result in this parameter displaying dashes. Refer to page 4-1.
H, H_, H
L, L_, L
_
,
, P
Source Voltage Demand
(Reverse)
V 0 NA NA NA NA NA
• This is the primary input voltage of the regulator during reverse power flow, as a demand value, according to the demand time interval at Function Code 46.
• H, the maximum source voltage seen, is displayed after this function code is entered. Scroll up to H_ for date, and H
_ maximum source voltage occurred. Continue scrolling up to see L, the lowest source voltage seen, followed by the L_ and L
_
, the date and time of its occurrence. Continue to scroll up to P to see the present value.
— Master Demand Reset &
Tap Position Indication Reset
— NA NA 1 NA NA NA
• All demand metering and tap position maximum (H) and minimum (L) values will be reset to their corresponding present (P) values when this function code is accessed. Successful master reset is indicated by the word “done” appearing on the display.
• All dates and times associated with demand metering and tap position maximum and minimum values will be reset to the present date and time.
• If the present demand value or tap position is in an invalid state (dashes), the maximum and minimum values will also become invalid (displaying dashes).
• Individual H and L values and their date/time may be reset to the present value by first accessing the appropriate H or L value, or its date or time, and then pressing the reset key.
• Scrolling to this parameter is not allowed.
1
Source Voltage Calculation
(CL-5C and later only)
— 0 2 NA 0 0 1
• The source side voltage is calculated based on tap position and the regulator type of A or B (for series transformer, use type A):
0 = source voltage calculator off 1 = source voltage calculator on
• Subfunction 1 defines to the control, the regulator type, as defined by ANSI.
Regulator type is defined on the nameplate.
1 = A
• The calculated method provides accuracy to ±1.5% maximum error.
2 = B
• When the calculated values are used, a small “c” is shown on the display following the function code. If the tap position becomes invalid, the calculated values become invalid and if the regulator uses the calculated values, it will idle until conditions are established to valid values for the decision process.
* Available on CL-5E control when available.
**A default value of “Reset” indicates that the parameter is reset to the present value.
3-8
McGraw-Edison VR-32 Regulator and CL-5 Series Control
Function
Code
40
41
42
43
44
45
46
47
Function
Code
Extension
Parameter
Unit of
Measure
Security Level
Default
Value
Key Entry
Limit
To To To
Read Change Reset
0 2 NA
Low High
1 32766 — Regulator Identification — 12345
• Provision is made for entry of a number to uniquely identify each control.
• The serial number of the control (as shown on the decal on the back of the front panel) was entered at Function Code 40 at the factory. However, any other number within the limits defined above may be chosen instead.
• This permits easy identification when data is collected via the Data Reader or other means.
— Regulator Configuration –– 0 2 NA
“----”
(invalid)
0 2
• The control is designed to operate on wye-connected or delta-connected three-phase systems.
• Regulators connected line-to-ground (wye or star) develop potentials and currents suitable for direct implementation in the control.
• Regulators connected line-to-line (delta) develop a potential-to-current phase shift which is dependent upon whether the regulator is defined as leading or lagging. This phase shift must be known by the control to permit accurate calculations for correct operation. This is accomplished by entering the proper code: 0 = Wye (or Star); 1 = Delta Lagging; or 2 = Delta Leading.
• See Reference Bulletin R225-10-1 for a discussion of delta connections. See page 1-7 for use of the control to determine whether the regulator is leading or lagging.
— Control Operating Mode — 0 2 2 0 0 2
• The manner in which the control responds to out-of-band conditions is selectable by the user. The appropriate mode is selected by entering one of the corresponding codes:
0 = Sequential (Standard) 1 = Time Integrating 2 = Voltage Averaging
• For detailed information, see Control Operating Modes, page 2-8.
— System Line Voltage V 0 2 NA
“----”
(invalid)
2400 36000
• The control is designed to operate on primary system voltages from 2400 V to 36000 V.
• Ratio correction is performed by the firmware, and consequently, the primary voltage must be entered for this calculation.
EXAMPLES: A regulator installed on a 7200 V system (line-to-neutral) would have 7200 entered at Function Code 43. A regulator installed open or closed delta on an 11000 V system (line-to-line) would have 11000 entered at Function Code 43.
— Overall Potential Transformer Ratio — 0 2 NA
“----”
(invalid)
20.0
300.0
• The control is designed to operate on primary system voltages from 2400 V to 36000 V.
• Ratio correction is performed by the firmware, and consequently, the overall potential transformer (P.T.) ratio must be entered for this calculation. The overall P.T. ratio is available on the regulator nameplate, and is summarized in Tables 1-10 and 1-11 on page 1-20 and 1-21 for most regulator ratings. EXAMPLE: A 13800 V regulator, installed on a 7970 V system, would have 7970 entered at Function Code 43, and 63.7 entered at Function Code 44. The control will then define the 125.1 V (output from the back panel ratio correction transformer) as the 120-base voltage, and 120 V is displayed at Function Code 6.
— Current Transformer Primary Rating A 0 2 NA 100 25 2000
• The control is designed for 200 mA as the rated current transformer (C.T.) output current, and will meter to 400 mA (200% load) with no loss of accuracy.
• Ratio correction is performed by the firmware, and consequently the C.T. primary rating must be entered. The C.T. primary rating is available on the regulator nameplate, and is summarized in Table 1-9 on page 1-17 for most regulator ratings. EXAMPLE:
A 7620 V, 328 A regulator (250 kVA) would have a C.T. primary rating of 400 A, and therefore, 400 is entered at Function Code 45.
— Demand Time Interval min.
0 2 NA 15.0
3.0
60.0
• This is the time period during which the demand integral is performed for all demand readings, Function Codes 20 through 36.
• Demand readings are useful because they represent the values which produce actual heating effects in electrical equipment, and they do not respond to the continuous fluctuations which occur on the line.
— Voltage Calibration V 0 3 NA [B] 110.0
130.0
• The voltage which the control actually measures is displayed at Function Code 47. In the example given in Function Code 44 description, Function Code 47 would indicate 125.1 V when Function Code 6 indicated 120 V.
• Calibration is performed by the factory, and should not be necessary in the field.
• To calibrate, this value is compared to a reference voltmeter and, if different, is changed to display the correct value.
• Scrolling to this parameter is not allowed.
• See Control Calibration, page 6-4.
[B] Representative calibration “factors” are programmed into ROM for use in the event the working memory experiences a default condition.
3-9 3
S225-10-10
2
Function
Code
48
49
50
51
52
53
54
55
Function
Code
Extension
Parameter
Unit of
Measure
Security Level
To To To
Read Change Reset
0 3 NA
Default
Value
Key Entry
Limit
Low High
100.0
400.0
— Current Calibration mA [B]
• The current which the control actually measures, in milli-amps, is displayed at Function Code 48.
• The control is designed for 200 mA as the rated C.T. output current, and will meter to 400 mA (200% load) with no loss of accuracy.
• Calibration is performed by the factory and should not be necessary in the field.
• To calibrate, this value is compared to a reference ammeter and, if different, is changed to display the correct value.
• Scrolling to this parameter is not allowed.
• See Control Calibration, page 6-4.
—
Tap Changer Selection
(CL-5D and Later)
NA 0 2 NA
As
Manuf.
0 1
• This function code identifies the tap changer type (See Chapter 5.) This function code is pre-set at the factory. Changing this function code changes the control’s sampling rate.
• 0 = Quik Drive 1 = Spring/Direct Drive
[C]
1, 2, 3, 4, 5, 6
Calendar/Clock
Year, Month, Day, Hour,
—
—
0
0
NA
3
NA
NA
“----”
(invalid)
—
“----” —
(invalid)
—
—
• [C] A segment bar after the Function Code 50 in the LCD moves from bottom of display indicating month.day to the top of LCD display to indicate hour.minute.
• The date (month.day) is displayed after entering Function Code 50. The time (hour.minute) is displayed after pressing the scroll up key. These are read-only parameters.
• Continued depressions of the scroll-up key display function extensions: 1 = year; 2 = month; 3 = day; 4 = hour; 5 = minute;
6 = seconds. These values may be changed if necessary.
• If power is restored after internal backup power is exhausted, the Calendar/Clock starts at January 1, 1990; 00:00:00.
• Refer to page 4-1.
— Set Voltage (Reverse) V 0 2 NA 120.0
100.0
• The set voltage is the voltage level to which the control will regulate, on the 120 V base, during reverse power flow.
• See Reverse Power Operation, page 4-3.
135.0
— Bandwidth (Reverse) V 0 2 NA 2.0
1.0
6.0
• The bandwidth is defined as that total voltage range, around the set voltage, which the control will consider as a satisfied
(in-band) condition, during reverse power flow. EXAMPLE: A bandwidth of 3 V and a set voltage of 120 V will establish a low limit of 118.5 V and a high limit of 121.5 V.
• See Reverse Power Operation, page 4-3.
— Time Delay (Reverse) sec.
0 2 NA 30 5 180
• The time delay is the period of time (in seconds) that the control waits, from the time when the voltage first goes out-of-band, to the time when the relay closure occurs, during reverse power flow.
• See Reverse Power Operation, page 4-3.
—
Line Compensation,
Resistance (Reverse)
V 0 2 NA 0.0
–96.0
96.0
• The resistive line drop compensation value is used to model the resistive line losses between the regulator and the theoretical load center.
• The control uses this parameter, in conjunction with the regular configuration (Function Code 41) and the load current flow, to calculate the compensated voltage (displayed at Function Code 8) during the reverse power flow.
• See Reverse Power Operation, page 4-3.
—
Line Compensation,
Reactance (Reverse)
V 0 2 NA 0.0
–96.0
96.0
• The reactive line drop compensation value is used to model the reactive line losses between the regulator and the theoretical load center.
• The control uses this parameter, in conjunction with the regular configuration (Function Code 41) and the load current flow, to calculate the compensated voltage (displayed at Function Code 8) during the reverse power flow.
• See Reverse Power Operation, page 4-3.
[B] Representative calibration “factors” are programmed into ROM for use in the event the working memory experiences a default condition.
3-10
McGraw-Edison VR-32 Regulator and CL-5 Series Control
Function
Code
56
57
Function
Code
Extension
Parameter
Unit of
Measure
Security Level
To To To
Read Change Reset
Default
Value
Key Entry
Limit
Low High
— Reverse Sensing Mode –– 0 2 NA 0 0 6
• The control offers six different response characteristics for reverse power flow operation, selectable by the user. The six modes, and their corresponding codes are:
0 = Locked Forward
1 = Locked Reverse [D]
2 = Reverse Idle
3 = Bi-directional [D]
4 = Neutral Idle [D]
5 = Co-generation [D]
6 = Reactive bi-directional [D]
• See Reverse Power Operation, page 4-3.
— Reverse Threshold % 0 2 NA 2 1 5
60
61
62
63
• This is the current threshold at which the control switches operation, either from forward to reverse, or reverse to forward.
• This threshold is programmable as a percentage of the rated C.T. primary rating. EXAMPLE: A 328 A regulator utilizing a C.T. with a 400 A primary rating, and with a 3% threshold value, would have a threshold of 12 A.
• The metering of the control switches on a fixed 1% threshold, completely independent from Function Code 57.
• See Reverse Power Operation, page 4-3.
— Data Port (Channel #1) Baud Rate — 0 2 NA 4 1 4
• The control microprocessor has two communications channels, each with selectable baud rates.
• Channel #1 is dedicated to the 9-pin Data Port located on the control front panel. The available baud rates for Channel #1 are:
1 = 300 Baud; 2 = 1200 Baud; 3 = 2400 Baud; and 4 = 4800 Baud.
• To permit communications with the McGraw-Edison Data Reader (data gathering device), the Channel #1 baud rate has been factory set to 4800; i.e., Function Code 60 = 4.
— Communications Protocol — 0 NA NA NA NA NA
• Communications Channel #2 is dedicated to the real-time digital communications interface. Function 61 indicates the type of protocol installed and its revision. The readout is RR.PP (read only). RR is an internal revision number from 1-99. PP is the protocol: 03 = Cooper Power Systems DATA 2179.
• CL-5 Series Controls are supplied with DATA 2179 protocol installed.
• See Digital SCADA, page 4-11.
— Data Port (Channel #1) Status — 0 NA NA NA NA NA
• The control microprocessor monitors the communications channels and reports the status of communication channel #1 Data Port sessions at Function 62.
• This is for information only.
• Status codes are listed with Function Code 63.
• The control microprocessor monitors the communications channels and reports the status of channel #2 sessions at Function 63.
—
Communications Port
(Channel #2) Status
— 0 NA NA NA NA NA
• This is for information use only.
• Status codes for both Function Codes 62 and 63 are listed as follows:
0 = Valid message received 6 = Check sum error in the received message
1 = Control in local mode
2 = Framing error in the received message
3 = Overrun error in the received message
4 = Noise error in the received message
5 = Parity error in the received message
7 = Invalid point type requested
8 = Invalid command received
9 = Invalid point number specified
“----” = Channel inactive
[D] Source-side voltage is required for these modes to be active.
3-11
3
2
S225-10-10
Function
Code
64
65
66
67
Function
Code
Extension
—
Parameter
Control Communications Address
(Protocol 2179)
Unit of
Measure
—
Security Level
To To To
Read Change Reset
Default
Value
0 2 NA
“----”
(invalid)
0
Key Entry
Limit
Low High
2046
• Cooper Power Systems has developed advanced controls for various products utilizing common protocol communications.
• Each control on the system can be uniquely addressed by the SCADA RTU or other communications device.
• The control SCADA address is entered at Function 64 with a factory preset address of 5.
• For protocol DATA-2179, the device addresses and responses are as follows:
0-2046 = Unique device address range. Controls with addresses in this range uniquely respond when the particular address is sent.
2047 = Broadcast address. All controls on the system listen and change as commanded, with no response if a message is sent to address 2047.
—
Communications Port
(Channel #2) Baud Rate
— 0 2 NA
“----”
(invalid)
1 5
• The user may select the baud rate to which the control system interfaces to the SCADA system. The available baud rates are:
1 = 300 Baud; 2 = 1200 Baud; 3 = 2400 Baud; 4 = 4800 Baud; 5 = 9600 Baud.
• The control is factory set for 4800 Baud.
—
Communications Port
Handshake Mode
— 0 2 NA
“----”
(invalid)
0 2
• The user can select the appropriate method for control-to-SCADA message interaction (handshake mode).
• The transmit/receive handshaking mode allows adaptability to different types of communication system interfaces with the CL-5C control. When using mode 2, the handshake out signal is used as the transmit enable. The handshaking input signal is ignored.
• The available modes are:
0 = No handshaking. This mode is used for direct communication between the control and a personal computer. It may also be used with an RTU for point-to-point communications.
1 = Not applicable. For C.P.S. use only.
2 = Handshaking is active. This mode is used where a transmit enable signal (push-to-talk) is required as part of the handshaking. Transmit enable is also required when the control is connected in a fiber-optic ring.
• See Function Code 68 for the programming of Transmit Enable Delay On and Transmit Enable Delay Off (transmit disable).
—
Communications Port
Number of Line Sync Characters
Char.
0 2 NA
“----”
(invalid)
0 10
• Defines the period of time the receive must idle to assume the start of a request message. Dead-line sync is used to determine the start of the request message. When used on a ring-configured or broadcast communication system, the control “hears” messages for devices at other nodes on the received data line. By reading the address, the control determines if the message is intended for it and ignores the remaining bytes if it is not. A period of time during which the received data line is inactive, defines the end of the previous message. This inactive time is the dead-line sync period. The control is now synchronized so that the next byte received is considered the beginning of a new message.The value programmed is the equivalent number of characters that the receive line must remain inactive, to be considered the end of a message. The control determines the actual time delay internally, taking into account baud rate and the number of bits in the character.
For example: Baud = 4800; Dead-line sync character = 5 characters
Dead time = 5 characters x 10 bits/character* = 50 bits
50 bits @ 4800 bits/second = 10.4 mS dead-line sync time
*10 bits/character applies to protocol 2179, 8 data bits, 1 start bit, 1 stop bit.
• See Figures 3-4 and 3-5.
DEAD-LINE SYNC TIME
R
X
D RECEIVE
DATA MESSAGE
T
X
D TRANSMIT
DATA
MESSAGE
Figure 3-4.
Message received at CL-5 Series control; message is for the CL-5 Series control
R
X
D RECEIVE
DATA
MESSAGE
DEAD-LINE SYNC TIME
MESSAGE
Figure 3-5.
Message received at CL-5 Series control; message is not for the CL-5 Series control
3-12
McGraw-Edison VR-32 Regulator and CL-5 Series Control
Function
Code
68
Function
Code
Extension
Parameter
Unit of
Measure
Security Level
To To To
Read Change Reset
Default
Value
Key Entry
Limit
Low High
1
Communications Port
Transmit Enable Delay - On msec.
0 2 NA
“----”
(invalid)
0 425
• When the control is set for transmit control handshaking (Function Code 66 = 2), the user may require a delay to occur between the time when the transmit enable is enabled to when data is transmitted. As an example, if the transmit enable were used as a keying device for a transmitter or modem, a “warm-up” period may be necessary before data can be transmitted.
• The delay period can be entered at this function code extension and is normally set to 0 for the presently supported communications system. See Figure 3-6.
2
Communications Port
Transmit Enable Delay - Off msec.
0 2 NA
“----”
(invalid)
0 250
• When the control is set for transmit control handshaking (Function Code 66 = 2), the user may require a delay to occur between the time when the data transmission is terminated and when the transmit enable signal is disabled.
• The delay period can be entered at this function code extension and is normally set to 0 for the presently supported communications system. See Figure 3-6.
69
70
TRANSMIT
ENABLE ON
TRANSMIT
ENABLE OFF
DATA
MESSAGE
FC 68-1
TRANSMIT
ENABLE
DELAY ON
FC 68-2
TRANSMIT
ENABLE
DELAY OFF
Figure 3-6.
Data transmission from the CL-5 Series control to the communication system for handshaking applications
— Regulation Blocking Status — 0 2 NA NA 0 1
•The control with communications options allows the user to completely control the regulator through the SCADA system. The
SCADA system may place the regulator in a “blocked” state, thus inhibiting any further tap changer operation initiated by the control. A practical example might be to perform a certain amount of voltage reduction, and then disable the tap changer (inhibit additional operations) for an indefinite time period.
• Statuses are as follows:
0 = Normal (normal automatic operation)
1 = Blocked (automatic operation is inhibited)
• The operator may change the state of this code by entering the level 2 security at the control and pressing the
CHANGE/RESET key. If SCADA has the control blocked, the operator may override the SCADA system by changing
Function Code 69 from 1 to 0, or if the operator chooses to block automatic operation, Function Code 69 can be changed from 0 to 1.
• Additional information concerning the SCADA interaction with the control is on page 4-9.
— Voltage Reduction Mode — 0 2 NA 0 0
• The control has three voltage reduction modes available for user selection. The appropriate mode is activated by entering the corresponding code:
0 = Off
1 = Local/Digital Remote
2 = Analog Remote - Latching
3 = Remote - Pulse
• See Voltage Reduction, page 4-8.
3
3-13 3
S225-10-10
Function
Code
70*
71
72
73
74
75
76
77
Function
Code
Extension
Parameter
Unit of
Measure
Security Level
To To To
Read Change Reset
— 0 2 NA
Default
Value
0
Key Entry
Limit
Low High
0 13 —
Voltage Reduction Mode/
Tap to Neutral
• The control has three voltage reduction modes available for user selection. The appropriate mode is activated by entering the corresponding code:
0 = Off 10 = Off, Tap to Neutral Enabled
1 = Local/Digital Remote 11 = Local/Digital Remote, Tap to Neutral Enabled
2 = Analog Remote (Latching) 12 = Analog Remote ( Latching,) Tap to Neutral Enabled
3 = Pulse 13 = Pulse, Tap to Neutral Enabled
• If enabled, tap-to-neutral is activated by energizing contacts 1 and 2 on TB-2. It is not possible to employ voltage reduction
Remote #3 (Function Code 75) if tap-to-neutral is active.
• See Voltage Reduction, page 4-8.
— Percent Voltage Reduction in Effect % 0 NA NA NA NA NA
• This is the actual percentage of voltage reduction presently active.
• See Voltage Reduction, page 4-8.
—
Local/Digital Remote
Voltage Reduction %
% 0 2 NA 0.0
0.0
10.0
• The percentage of local voltage reduction to be performed, is entered here. Example: If the regulator is set for
125 V voltage setting and 3.6% voltage reduction is required, 3.6% is entered here (first set Function Code 70 = 1), and the regulator will tap down 4.5 V (3.6% of 125 V) immediately following the time delay period.
• When activating voltage reduction via digital SCADA, this is the parameter which is changed to the percent desired.
• See Voltage Reduction, page 4-8.
— Analog Remote Reduction Setting #1 % 0 2 NA 0.0
0.0
10.0
• Three levels of remotely activated latching voltage reduction are available.
• The percentage of voltage reduction to be performed at Removal Level 1 is programmed at the Function Code 73. Remote activation is then accomplished by applying a signal to the appropriate input terminal, when Function Code 70 = 2.
• See Remote (Latching) Mode, page 4-9.
— Analog Remote Reduction Setting #2 % 0 2 NA 0.0
0.0
10.0
• Three levels of remotely activated latching voltage reduction are available.
• The percentage of voltage reduction to be performed at Removal Level 2 is programmed at the Function Code 74. Remote activation is then accomplished by applying a signal to the appropriate input terminal, when Function Code 70 = 2.
• See Remote (Latching) Mode, page 4-9.
— Analog Remote Reduction Setting #3 % 0 2 NA 0.0
0.0
10.0
• Three levels of remotely activated latching voltage reduction are available.
• The percentage of voltage reduction to be performed at Removal Level 3 is programmed at the Function Code 75. Remote activation is then accomplished by applying a signal to two appropriate input terminals, when Function Code 70 = 2.
• See Remote (Latching) Mode, page 4-9.
—
Analog Pulsed Voltage Reduction
Number of Steps
— 0 2 NA 0 0 10
• Up to ten steps of voltage reduction are available when pulsed voltage reduction mode is selected. (Function Code 70 = 3.)
• Function 76 defines the number of steps selected for pulsed reduction operation. The percentage of voltage reduction of each step is defined at Function Code 77.
• See Pulse Mode, page 4-9.
—
Analog Pulsed Voltage Reduction
Voltage Reduction Per Step
% 0 2 NA 0.0
0.0
10.0
• Function Code 77 defines the percentage of voltage reduction which will be applied for each step of pulsed voltage reduction selected at Function Code 76
• See Pulse Mode, page 4-9.
2
* CL-5E control only.
3-14
McGraw-Edison VR-32 Regulator and CL-5 Series Control
Function
Code
79*
80
81
82
85
85*
89
90
Function
Code
Extension
1, 2
Parameter
Soft Add-Amp Limits
Unit of
Measure
NA
Security Level
To To To
Read Change Reset
0 2 2
Default
Value
0
Key Entry
Limit
Low High
NA NA
• The control has soft add-amp capabilities.
0 = Off, 1 = On (Default is off)
• Subfunction 1 defines the high soft add amp setting. The allowable values are 16, 14, 12, 10, or 8. Default is 16.
• Subfunction 2 defines the low soft add amp setting. The allowable values are -16, -14, -12, -10, or -8. Default is -16.
• See Add Amp, Page 1-15 and 4-10.
— Voltage Limiting Mode — 0 2 NA 0 0
• The control has voltage limiting capabilities for both high-voltage and low-voltage conditions.
• The appropriate mode is activated by entering the corresponding code:
0 = Off
1 = High limit active only
2 = High and low limits active
• See Voltage Limiting, page 4-8.
— High Voltage Limit V 0 2 NA 130.0
120.0
2
135.0
• The high-voltage limit is programmed here.
• When the voltage limiting function is activated (Function Code 80 = 1 or 2), the control will prevent the output voltage of the regulator from exceeding this value.
• See Voltage Limiting, page 4-8.
— Low Voltage Limit V 0 2 NA 105.0
105.0
120.0
• The low-voltage limit is programmed here.
• When the voltage limiting function is activated (Function Code 80 = 2), the control will prevent the output voltage of the regulator from dropping below this value.
• See Voltage Limiting, page 4-8.
1, 2, 3, 4 Profile Recorder NA 0 1 NA 9,14,15,16 6 19
• Function Code 85, with its four extensions, is used to select the parameters to be included in the profile recorder data table.
• The profile recorder samples any four instantaneous metering functions (Function Codes 6 thru 19). The sample interval is every
15 minutes for a 30-hour period (120 values).
• See Profile Recorder, page 4-2.
1, 2, 3, 4, 5, Profile Recorder NA 0 1 NA
1
9,14,15,16
1
6
7
19
• Function Code 85 is used to profile any four instantaneous metering functions (Functions Codes 6 through 22, or demand values
24-26, 29-32, or 34-37) and to set a time interval for profiling data collection.
• The sample period (time interval) is defined by function code 85, where 1 = 5 minutes, 2 = 10 minutes, 3 = 15 minutes, 4 = 30 minutes, 5 = 60 minutes, 6 = 90 minutes, 7 = 120 minutes. The last 120 values for each function shall be stored in volatile control memory.
• The first four subfunctions of function code 85 define the four instantaneous metering functions (Functions Codes 6 through 22, or demand values 24-26, 29-32, or 34-37) to be profiled.
• The fifth subfunction of function code 85 reflects the “on/off” state of the profiler feature related to the 2179 protocol, that determines whether the parameters returned in response to a request message are all the values, or only the “new” values since the last read.
— Device Firmware Version — 0 NA NA NA NA NA
• This parameter takes the form RR.DD, where RR is the revision number and DD is the device number. The control is device 06.
• Scrolling to this parameter is not allowed.
— Number of Defaults — 0 NA NA NA NA NA
• This is a counter for the number of parameters in the control operating system which have defaulted.
• During normal operation this will be zero.
• If any number other than zero is encountered, all of the control settings must be examined to determine which has defaulted.
Then the setting(s) must be changed to the correct value(s).
• Defaulted functions will be identified with the letter “d” after the function code number in the LCD display.
* CL-5E control only.
3-15 3
S225-10-10
Function
Code
91
92
93
94
95
96
Function
Code
Extension
Parameter
Unit of
Measure
Security Level
To To To
Read Change Reset
NA NA NA
Default
Value
Key Entry
Limit
Low High
NA NA — Self Test — NA
• The control will execute a self-diagnostic routine by entry of Function Code 91.
• This causes the system to re-boot, or initialize itself, and in so doing to check the various components for failures.
• The test initiates by lighting all segments in the display for 3 seconds, and then displays PASS or FAIL, depending upon the test results.
• “----” (dashes) preceding the PASS indicates that the clock needs to be set.
• Performing the self test will appear as a power interruption to the control demand task, and accordingly, it will cause the present demands to go invalid (dashes) and the max/min demands to cease tracking for one demand interval.
• Self test does not set all profiler values to zero.
• Scrolling to this parameter is not allowed.
— Security Override — 0 3 NA 0 0 3
• Function Code 92 is the control security override parameter.
• Entering the level 3 security code at Function Code 99 will permit the security parameters to be modified,
0 = standard security mode
1 = override security level 1
2 = override security levels 2 and 1;
3 = override security levels 3, 2 and 1;
• EXAMPLE: With Function Code 92 = 1, metering and tap position resetting may be done without entering security level 1.
• See Tap Position Indication, page 4-3.
— Number of EEPROM Corrections — 0 NA 3 0 NA NA
• This is a counter for the number of times the control has detected an incorrect value in its non-volatile memory (EEPROM), and has changed it to the correct value.
• This is for information only.
— Number of Resets — 0 NA 3 0 NA NA
• This is a counter for the number of times the control has experienced a transient condition (such as a lightning stroke) which caused it to reset.
• The control will recover after a transient condition and will resume normal operations.
— System Status Code — 0 NA NA NA NA NA
• The control is continually checking itself, and the results of this self-diagnosis are displayed at Function Code 95 via a system status code as follows:
0 = All Systems Good
1 = EEPROM Write Failure
2 = EEPROM Erase Failure
3 = Frequency Detection Failure
4 = No Sampling Interrupt - Failure
5 = Analog-to-Digital Converter Failure
6 = Invalid Critical Parameters - Failure
7 = No Source Voltage Detected - Warning
8 = No Output Voltage Detected - Failure
9 = No Source and Output Voltage Detected - Failure
10=TPI. No Neutral Sync Signal - Warning
• If the word ERROR appears on the display this indicates a key entry error, not the system status code. See Table 9-2.
• See System Protection, page 2-4 and Diagnostics, page 2-5.
— Level 1 Security Code — 3 3 NA 1234 1
• The number to be used as the level 1 security code is entered here.
• The level 1 code assigned at the factory is 1234.
• Entry of this number at Function Code 99 permits the user to change/reset only the parameters marked as level 1 security
(demand and tap position readings).
• Scrolling to this parameter is not allowed.
• See Security System, page 2-6.
9999
2
* CL-5E control only.
3-16
McGraw-Edison VR-32 Regulator and CL-5 Series Control
Function
Code
97
98
99
Function
Code
Extension
—
Parameter
Level 2 Security Code
Unit of
Measure
—
Security Level
To To To
Read Change Reset
3 3 NA
Default
Value
12121
Key Entry
Limit
Low High
10000 19999
• The number to be used as the level 2 security code is entered here.
• The level 2 code assigned at the factory is 12121.
• Entry of this number at Function Code 99 permits the user to change/reset only the parameters marked as level 2 security
(control settings, configuration and clock) and level 1 security.
• Scrolling to this parameter is not allowed.
• See Security System, page 2-6.
• The number to be used as the level 3 security code is entered here.
— Level 3 Security Code — 3 3 NA 32123 20000 32766
• The level 3 code assigned at the factory is 32123.
• Entry of this number at Function Code 99 permits the user to change/reset any parameter.
• NOTE: If the level 3 code is changed by the user, the new value should be recorded and kept in a safe place. If lost, the security codes cannot be displayed or changed, diagnostic codes cannot be displayed or change, and calibration cannot be performed unless the present code is identified by using the Data Reader and Data Reader software or Communication
Interface software available from Cooper Power Systems.
• Scrolling to this parameter is not allowed.
• See Security System, page 2-6.
— Enter Security Code — NA 0 NA
• This is the function code location where the security codes are entered for access to the system.
• Scrolling to this parameter is not allowed.
• See Security System, page 2-6.
NA 1 32766
3-17 3
S225-10-10
Control Advanced Features
Differential Voltage
Unless specifically ordered, or required as a part of the specified operation, most regulator designs will be without the internal source-load differential P.T. Units with the CL-5C or newer controls have source voltage calculation available (FC 39). Without a source voltage input, several functions cannot be obtained, and will indicate dashes when displayed (see Table 4-1). Also,
Function Code 95 will display a “7” to indicate no input voltage.
TABLE 4-1
Function Code Dependent Upon Differential Voltage
Function Code Description
7
11
12
27
28
30-36
Source Voltage, Secondary
Source Voltage, Primary
Percent Regulation
Maximum % Boost/Minimum % Buck
Maximum % Buck/Minimum % Boost
All Reverse Metered Demand Values
If the parameters listed in Table 4-1 are desired and the regulator is not able to determine the source voltage, an external source side potential transformer may be connected to the control. (See Reverse Power
Operation, page 4-3.)
Calendar/Clock
Integral to several functions of the control is an internal calendar/clock. The digital clock maintains the year, month, day, hour, minute and seconds, and has resolution of 1 second. Hours are in 24-hour (military) time, that is, 3:15 p.m. is shown as 15:15. The clock does not adjust for Daylight Savings Time. It is powered by ac (60 or 50 Hz) and operates under normal power when the control is powered up. When ac power is off, the clock uses a crystal as a reference and a capacitor as the power source. The back-up power will sustain the clock for a minimum of 24 hours. Sixty-five hours on ac power are required to fully charge the capacitor.
Upon powering up the control, if the clock is invalid due to lack of power, four (4) dashes will appear in the display to the left of the word PASS. In this situation the clock will restart at 1/1/90 00:00:00. Until the clock is reset, four dashes will appear on the right of the display whenever the display would normally be blank.
Metering
The control has extensive metering capabilities, which we categorize as Instantaneous, Demand and Profile.
Instantaneous Metering
Instantaneous metering values are stored in RAM, and are refreshed once per second. They may be read at
Function Codes 6 through 19. See the detailed description of these parameters starting on page 3-2.
Demand Metering
The control provides demand metering values for six or eight parameters: load voltage, source voltage* (forward and reverse), compensated voltage, load current, kVA load, kW load, and kvar load. For each of these parameters the present “P” value, the maximum “H” value since last reset, and the minimum “L” value since last reset are recorded, as well as the earliest time and date that the maximum and minimum values occurred.
Additionally, the power factor at maximum kVA demand and minimum kVA demand are recorded. All of these values are stored in non-volatile memory separately for forward and reverse power conditions.
Demand values may be read at Function Codes 20 through 37. See the detailed description of these parameters starting on page 3-5, and the discussion concerning metering during reverse power flow, starting on page 4-3.
Demand Task Operation
The demand metering function is based upon a sliding window concept, or moving integral. The algorithm implemented simulates the response of a thermal demand meter which will reach 90% of its final value after one demand interval in response to a step function input. (See Figure 4-1.)
100%
90%
0 1T 2T 3T 4T
DEMAND TIME INTERVAL
5T 6T
Figure 4-1.
Demand time interval response
* Source voltage: CL-5E only.
t
4-1
McGraw-Edison VR-32 Regulator and CL-5 Series Control
The task works like this:
1. For 3 minutes after a power outage or power reversal, no demands are calculated. This allows the utility system to stabilize from the event which created the outage or power reversal.
2. At 3 minutes, the present demands (for the appropriate power direction) are set to their corresponding instantaneous value, and the integration algorithm begins according to the programmed demand interval at Function
Code 46.
3. At 15 minutes or at the demand time interval
(whichever is longer), the max/min demand values begin to track the present demand, similar to drag hands. All demand values are calculated continuously in the working memory (RAM), and the max/min demands are also stored in the nonvolatile memory (EEPROM) every 15 minutes, if a change has occurred. This prevents loss of data during a power interruption or outage.
Notice that the provisions are made to reset any demand value by itself via the change/reset key, or all demands can be reset simultaneously by entering Function Code
38. Maximum (H) and minimum (L) values will be set to their corresponding present (P) demand value and the H and L dates and times will be set to the present date/time. If the present demand is in an invalid state
(dashes), the maximum and minimum values will also become invalid, displaying dashes.
Two conditions can cause the present demands to be invalid: The power has just been applied (within the 3 minute freeze period) or the power flow has changed direction. If the control is metering in the forward direction, the reverse present demands will be invalid; and if metering in the reverse direction, the forward present demands will be invalid.
Profile Recorder
Function Code 85.
The CL-5D control has a Profile Recorder (Profiler) function which records any four (4) metering values every 15 minutes for 30 hours (120 time slots). On the
CL-5E and newer controls, the time interval is variable, from 5-120 minutes. See Function Code 85 description.
To set the Profiler, access security level 1, then enter the parameters of choice at the Function Code extensions 1,
2, 3 and 4. The selectable CL-5D parameters are:
• 6 - Load Voltage, Secondary
• 7 - Source Voltage, Secondary*
• 8 - Compensated Voltage, Secondary
• 9 - Load Current, Primary
• 10 - Load Voltage, Primary
• 11 - Source Voltage, Primary*
• 12 - Present Tap Position
• 13 - Power Factor
• 14 - kVA Load
• 15 - kW Load
• 16 - kvar Load
• 17 - Line Frequency
• 18 - Voltage Total Harmonic Distortion
• 19 - Current Total Harmonic Distortion
*Source voltage required
For the CL-5E, the following parameters are also available for Profiler data collection.
• 20 Forward Load Voltage
• 21 Forward Compensated Voltage
• 22 Forward Load Current
• 24 Forward kVA Load
• 25 Forward kW Load
• 26 Forward kVAR Load
• 29 Forward Source Voltage
• 30 Reverse Load Voltage
• 31 Reverse Compensated Voltage
• 32 Reverse Load Current
• 34 Reverse kVA Load
• 35 Reverse kW Load
• 36 Reverse kVAR Load
• 37 Reverse Source Voltage
TABLE 4-2
Default Values for Profiler Parameters
F.C.
85
85
85
85
Extension
1
2
3
4
Value
9
14
15
16
Parameter
Load Current, Primary kVA Load kW Load kvar Load
EXAMPLE: To record the tap position (FC 12) instead of the load current, do the following:
1. Access security level 2.
2. Press FUNCTION, 8, 5, ENTER.
3. The display will read “85 1 9”, or, if the CL-5E or newer control is installed, the display will read, “85
15”.
4. If the control is a CL-5E or newer, scroll up one value.
The control will now read, “85 1 9”.
5. Press CHANGE, 1, 2 ENTER.
The profiler data is stored in working memory (RAM), therefore, if power is lost, all profiler values are lost.
Upon return of power, if the clock is still operating on backup power, the profiler will start at the next time interval. If due to lack of power the clock starts with the default hour: minute values of 00:00, the first values will be recorded at 00:15 or at the first time interval, if the
CL-5E control is in use.
If a parameter at one of the extensions of Function Code
85 is changed, the entire profiler database will be reset,
4-2
S225-10-10 that is, all values for all four parameters will be set to 0.
To reset all profiler values to 0 either turn the power off, or change one of the Function Code 85 extension values.
If the clock is reset, prior values and times in the profiler will be retained, and the newest value will be recorded at the next time interval. It should be noted that the hour and minute are stored on the profiler, not the month and day.
After all 120 time slots are filled, the oldest set of values is deleted when the newest set of values is recorded.
The time-stamped profiler values are not accessible through the keypad and display. To retrieve the values, download the control database through the Data Port with a McGraw-Edison Data Reader or with a PC using
CCI CL-4/CL-5 Interface Program or extract the data through the communications channel.
Tap Position Indication
The control has the ability to track the position of the tap changer. The tap position indication (TPI) function senses the status of the motor and neutral light circuits and does not require source (input) voltage. The present tap position is stored at Function Code 12. EXAMPLES:
“8” at Function Code 12 indicates 8 raise and “-7” indicates 7 lower.
The TPI function is synchronized to the position of the tap changer by running the regulator to the neutral position. When the tap changer cannot be returned to neutral due to the voltage support which is necessary, the value of the present tap position may be changed to the position shown by the position indicator main hand by doing the following: Access security level 3; access
FC 12; use the CHANGE key to change to the desired value.
The maximum tap position since last reset (upper draghand value of the present tap position) and its date and time are stored at Function Code 27. The minimum tap position since last reset (lower draghand value of the present tap position) and its date and time are stored at
Function Code 28. The TPI draghand values and dates/times are reset to the present values by the master reset, Function Code 38, or by resetting each of the values individually. The draghand reset switch resets the draghands of the position indicator only, not TPI.
All TPI values are stored in a non-volatile memory. The present tap position value will go to invalid “----” if the following condition is detected. The present tap position is “O” (neutral) but no neutral signal is detected. This condition will occur if a replacement control with present tap position set to “O” is installed on a regulator which is not in the neutral position. If the TPI function detects a successful upward tap and the prior value of FC 12 was
“16”, or a successful downward tap is detected and the prior value of FC 12 was “–16” the prior value will be maintained. These conditions could occur if the present tap position was manually set incorrectly.
The following relates the action of the diagnostics routine with regard to the Tap Position Indication function only.
See page 2-5 for the list of other reasons which would cause diagnostics to report FAIL.
The display will show FAIL upon power-up under these circumstances: 1) the present tap position value prior to power-up is “---” (invalid) and the regulator is not in neutral position. 2) The present tap position prior to power-up is 0 and the regulator is not in the neutral position. This condition will cause the present tap position value to go to invalid (“----”). 3) During automatic or manual operation the present tap position changes to
0, but a neutral signal is not received. In all of these cases, the value at Function Code 95, Systems Status, is set to “10”, “TPI - NO NEUTRAL SYNC - WARNING”.
The display will show PASS upon power-up under the following circumstances: 1) The present tap position is not 0 and the regulator is not in neutral. 2) The regulator is in neutral.
Reverse Power Operation
Most voltage regulators are installed in circuits with welldefined power flow from source to load. However, some circuits have interconnection or loops in which the direction of power flow through the regulator may change. For optimum utility system performance, a regulator installed on such a circuit should have the capability of detecting reverse power flow, and of sensing and controlling the voltage, regardless of the power flow direction.
The control has full reverse power capabilities, but for fully automatic reverse operation the source voltage or source-to-load differential voltage must be supplied to the control in addition to the load voltage. Regulators may be ordered direct from the factory with an internal
(source-to-load) series winding P.T., or an external source-side P.T. may be installed in the field. In either case, a second Ratio Correcting Transformer (RCT) on the control back panel is required for proper correction of the source voltage if the external source side P.T. has a voltage other than 120V. Regulators with factory installed series winding P.T.s also have the second RCT installed at the factory.
Some field installations may require that a source voltage P.T. be used instead of the series winding P.T.
which is the standard technique used on the McGraw-
Edison voltage regulator. The control is designed such that it can be configured for this application also. This reconfiguration is accomplished by removing the back shield and moving a soldered jumper from one set of terminal posts marked V diff to another set of terminals
4-3
McGraw-Edison VR-32 Regulator and CL-5 Series Control marked V in.
The software of the control then recognizes this differential/source voltage as a source voltage, and will function accordingly.
The CL-5C and later generation controls have the ability to calculate the source side voltage without a series winding P.T.. When this feature is turned on, the control will use the load voltage from the main P.T., the regulator type (either straight, also known as ANSI type
A, or inverted, also known as ANSI type B), the tap position and the internal impedance of the regulator to calculate the source side voltage. This source voltage is with ±1.5% of actual. With the source voltage P.T. the accuracy improves to ±1%. Only the regulator type needs to be programmed into the control. The other values are already available to the control.
The control offers seven different response characteristics for reverse power detection and operation. These characteristics are user selectable by programming
Function Code 56. The seven modes, and their corresponding codes are:
0 = Locked Forward, 1 = Locked Reverse
2 = Reverse Idle, 3 = Bi-directional
4 = Neutral Idle, 5 = Co-generation
6 = Reactive Bi-directional
This section will separately explain each mode of operation. Since the control retains the reverse metered demand values separate from the forward metered values, the metering will also be explained for each mode.
In determining power direction, the control senses the real component of the current (except in reactive bidirectional mode), and then determines the current direction and magnitude in that direction. When the conditions indicate the power is flowing in reverse, the following parameters assume new values and the control operation is affected accordingly:
Load Voltage - Now sensed from what was previously the source voltage supply.
Source Voltage - Now sensed from what was previously the load voltage supply.
Load Current - In the forward direction, the current is used directly as measured. In the reverse direction, the current is scaled to reflect the ratio difference between the source and load side of the regulator, according to this formula:
Forward
Load
Reverse Current
Load =
Source
Voltage
Supply
Supply where source voltage supply and load voltage supply are in the reverse direction.
kVA, kW, kvar, and % buck/boost are now calculated based upon the new metered reverse values.
Locked Forward Mode
Function Code 56 = 0. No source voltage is required.
This mode is not intended to be used in applications where reverse power flow is possible.
METERING: Always operates in the forward direction, regardless of power flow direction. If reverse power occurs, the metering functions remain on the normal load side of the regulator—no reverse demand readings will occur.
OPERATION: (Figure 4-2) Always operates in the forward direction. This allows operation down to zero current conditions since there is no forward threshold involved. A safeguard has been built into the control to prevent misoperation in the event reverse power flow does occur. If more than 2% (.004 A C.T. secondary) reverse current occurs, the control idles on the last tap position held, and the band edge indicators will turn off.
As the current flow returns to a level above this reverse threshold, normal forward operation resumes.
BAND EDGE INDICATORS ARE
TURNED OFF AND TAP CHANGING
IS INHIBITED WHEN REAL
COMPONENT OF CURRENT IS
GREATER THAN 2% REVERSE
Figure 4-2.
Locked forward mode operation
FORWARD
OPERATION
Locked Reverse Mode
Function Code 56 = 1. Source voltage is required. This mode is not intended to be used in applications where forward power flow is possible.
4-4
S225-10-10
METERING: Always operates in the reverse direction, regardless of power flow direction. If forward power occurs, the metering functions remain on the source
(S bushing) side of the regulator — no forward demand readings will occur.
OPERATION: (Figure 4-3.) Always operates in the reverse direction using the reverse settings at Function
Codes 51, 52, 53, 54 and 55. This allows operation down to zero current conditions since there is no reverse threshold involved. A safeguard has been built into the control to prevent misoperation in the event forward power flow does occur. If more than 2% (.004 A
C.T. secondary) forward current occurs, the control idles on the last tap position held, and the band edge indicators will turn off. As the current flow returns to a level above this forward threshold, normal reverse operation resumes. (See Figure 4-3.)
BAND EDGE INDICATORS
ARE TURNED OFF AND TAP
CHANGING IS INHIBITED
WHEN REAL COMPONENT
OF CURRENT IS GREATER
THAN 2% FORWARD
NORMAL FORWARD
METERING
"REV PWR" OFF
FORWARD METERING
FORWARD SCALING
"REV PWR" ON
1% 0 1%
CURRENT LEVEL
Figure 4-4.
Reverse idle metering without source voltage
OPERATION: (Figure 4-5.) The threshold for which the control switches operation is programmable at Function
Code 57 over the range 1 to 5% of the rated C.T.
current. When the real component of the current is above this threshold, the control operates in the normal forward direction. When current falls below this threshold, all tap changing is inhibited. The control idles on the last tap position held before the threshold was crossed. The operational timer (time delay) is reset on any excursion below this threshold, and the band edge indicators turn off.
TAP CHANGING IS INHIBITED
WHEN REAL COMPONENT OF
CURRENT IS AT OR BELOW
THE OPERATION THRESHOLD,
FC57
REVERSE
OPERATION
Figure 4-3.
Locked reverse mode operation
Reverse Idle Mode
Function Code 56 = 2. Source voltage required for metering only. This mode is recommended for installation where reverse power flow may occur, but a source voltage is not available.
METERING: (Figure 4-4.) A threshold level of 1% (.002
A) of the full load C.T. secondary current (.200 A) is used in setting the power direction. The metering will be forward until the current exceeds the 1% threshold in the reverse direction. At this time, the various parameters use the reverse settings, and the REV PWR annunciator turns on. The control continues metering in reverse until the current exceeds the 1% threshold in the forward direction, and then the parameter scaling reverts back to normal and the REV PWR annunciator turns off. If the source or differential P.T. is not installed, reverse metering will not be available, but all other metering operations remain the same. If the P.T. is installed, metering will be per Figure 4-6.
OPERATION
Figure 4-5.
Reverse idle mode operation
*Tap changing is inhibited and band edge indicators are turned off.
Bi-directional Mode
Function Code 56 = 3. Source voltage is required. This mode is recommended for all installations where reverse power flow may occur except where the source of reverse power is a co-generation facility or independent power producer.
METERING: (Figure 4-6.) A threshold level of 1% (.002
A) of the full load C.T. secondary current (.200 A) is used in setting the power direction. The metering will be
4-5
McGraw-Edison VR-32 Regulator and CL-5 Series Control forward until the current exceeds the 1% threshold in the reverse direction. At this time the various parameters use the reverse settings, and the REV PWR annunciator turns on. The control continues metering in reverse until the current exceeds the 1% threshold in the forward direction, and then the parameter scaling reverts back to normal and the REV PWR annunciator turns off.
NORMAL FORWARD
METERING
"REV PWR" OFF
REVERSE METERING
REVERSE SCALING
"REV PWR" ON
1% 0 1%
CURRENT LEVEL
Figure 4-6.
Bi-directional, Neutral Idle and Reactive Bi-directional
Metering
OPERATION: (Figure 4-7.)The control operates in the forward direction whenever the real component of the current is above the operator defined forward threshold
(Function Code 57). The control operates in the reverse direction, using the reverse settings at Function Codes
51, 52, 53, 54 and 55, whenever the current is above the operator defined reverse threshold (Function Code 57).
When the current is in the region between the two thresholds, the control idles on the last tap position held before the current fell below the threshold. The operational timer (time delay) is reset on any excursion below the threshold in either direction, and the band edge indicators turn off.
Neutral Idle Mode
Function Code 56 = 4. Source voltage is required.
METERING: (Figure 4-6.) A threshold level of 1% (.002
A) of the full load C.T. secondary current (.200 A) is used in setting the power direction. The metering will be forward until the current exceeds the 1% threshold in the reverse direction. At this time, the various parameters use the reverse settings, and the REV PWR annunciator turns on. The control continues metering in reverse until the current exceeds the 1% threshold in the forward direction, and then the parameter scaling reverts back to normal and the REV PWR annunciator turns off.
OPERATION: (Figure 4-8.) The control operates in the forward direction whenever the real component of the current is above the operation defined forward threshold
(Function Code 57). When the current exceeds the operator defined reverse threshold (Function Code 57), and is held for 10 continuous seconds, the control will tap to neutral. Neutral position is determined as when the percent buck/boost is within ±.3% of 0. When the current is in the region between the two thresholds, the control idles on the last tap position held before the forward threshold was crossed. While tapping to the neutral position, if the current falls below the reverse threshold, the control continues to tap until neutral position is reached. The operational timer (time delay) is reset on any excursion below the forward threshold and the band edge indicators turn off.
BAND EDGE INDICATORS ARE
TURNED OFF AND TAP CHANGING IS
INHIBITED WHEN REAL COMPONENT
OF CURRENT IS AT OR BELOW THE
OPERATION THRESHOLD, FC57, IN
EITHER DIRECTION
TAP CHANGING
INHIBITED AND
BAND EDGE
INDICATORS ARE
TURNED OFF
= REVERSE
OPERATION
Figure 4-7.
Bi-directional mode operation
FORWARD =
OPERATION
4-6
= TAP TO
NEUTRAL
OT=Operating Threshold
** (F.C. 57), 1-5%
Figure 4-8.
Neutral idle mode operation
** Band edge indicators are turned off.
FORWARD =
OPERATION
S225-10-10
Co-generation Mode
Function Code 56 = 5. Source voltage is required.
In recent years, there have been a growing number of voltage regulator applications involving co-generation by the utilities’ customers. The co-generation mode was developed for the McGraw-Edison control to satisfy the specialized needs of these applications. Normally, the desired operation of a regulator installed on a feeder involving co-generation is to regulate the voltage at the customer substation during times of power flow into the customer site, and to regulate the voltage at the regulator (on the same output side) during power flow into the utility grid. This is accomplished by simply not reversing the control sensing input voltage when reverse power is detected, and by altering the line drop compensation settings to account for this change in power flow direction. (See Figure 4-9.)
LINE DROP
COMPENSATION
DIFFERENCE
STIFF
BUS
UTILITY
SUBSTATION
REGULATED
VOLTAGE DURING
REVERSE POWER FLOW
CUSTOMER
SUBSTATION
CO-GENERATION
SITE
REGULATED
VOLTAGE DURING
FORWARD POWER FLOW
Figure 4-9.
Co-generation regulation points used when the current exceeds the fixed 1% forward metering threshold. The demand values acquired during reverse power flow are stored as reverse metered data but the values are not scaled (to reflect the other side of the regulator) since the operating direction of the regulator never truly reverses.
OPERATION: (Figure 4-11.) The control always operates in the forward direction. The control will operate in the forward direction, but will use the reverse settings for line drop compensation when the real component of the current is above the fixed 1% reverse metering threshold. The control will continue to use the reverse line drop compensation settings until the real component of the current is above the fixed 1% forward metering threshold. The operational timer (time delay) is not reset on any transitions between the application of forward and reserve line drop compensation settings.
Co-Generation Mode Operation
REVERSE LDC @-1%
FORWARD OPERATIONS
WITH REVERSE LDC
FORWARD OPERATIONS
WITH FORWARD LDC
FORWARD LDC @+1%
METERING: (Figure 4-10.) Always operates in the forward direction except that load center voltage is calculated based upon the reverse line drop compensation settings (Function Codes 54 and 55), when the fixed 1% reverse metering threshold is exceeded. The REV PWR annunciator turns on when this reverse threshold is crossed. The forward line drop compensation settings (Function Codes 4 and 5) are
REVERSE FORWARD
NORMAL FORWARD
METERING
"REV PWR" OFF
FORWARD METERING
WITH REVERSE LDC
"REV PWR" ON
Figure 4-10.
Co-generation metering
1% 0 1%
CURRENT LEVEL
-5 -4 -3 -2 -1 0 1 2
PERCENT OF C.T. RATING
3 4 5
Figure 4-11.
Co-generation mode operation
Reactive Bi-Directional Mode
Function Code 56 = 6. Source voltage is required.
This mode is recommended for installations where reverse power flow may occur and the real component of the current is below the operator defined threshold
(Function Code 57), except where the source of reverse power is a co-generation facility or independent power producer.
METERING: (Figure 4-6.) A threshold level of 1% (0.002
A) of the full load C.T. secondary current (0.200 A) is used in setting the power direction. The metering will be forward until the current exceeds the 1% threshold in the reverse direction. At this time, the various parameters use the reverse settings, and the REV PWR annunciator turns on. The control continues metering in reverse until the current exceeds the 1% threshold in the forward direction, and then the parameter scaling reverts back to the normal and REV PWR annunciator turns off.
4-7
McGraw-Edison VR-32 Regulator and CL-5 Series Control
OPERATION: (Figure 4-12.) The control determines which settings (forward/reverse) to use by sensing the real and reactive components of the current. The control operates in the forward direction whenever the magnitude of the reactive component of the current exceeds the operator defined threshold (Function Code
57) in the negative direction. The control also operates in the forward direction if the magnitude of the real component of the current exceeds the operator defined threshold (Function Code 57) in the positive direction while the magnitude of the reactive component of the current is between the operator-defined thresholds
(Function Code 57). The control operates in the reverse direction using the reverse settings at Function Codes
51, 52, 53, 54, and 55, whenever the magnitude of the reactive component of the current exceeds the operator defined threshold (Function Code 57) in the positive direction. The control also operates in the reverse direction if the magnitude of the real component of the
= REVERSE
OPERATION
FORWARD =
OPERATION
Figure 4-12.
Reactive bi-directional mode operation current exceeds the operator defined threshold (Function
Code 57) in the negative direction while the magnitude of the reactive component of the current is between the operator defined thresholds (Function Code 57).
Voltage Limiting
The voltage limiting accessory is used to place both a high and low limit on the output voltage of the regulator.
When enabled, it operates in either the forward or reverse directions, and has the highest priority of all operating functions. Voltage limiting is overridden only by the operator taking local control, or by an interconnected SCADA system. The purpose of the voltage limiter is to protect the consumer from abnormally high or low voltages resulting from:
• Large, rapid changes in transmission voltage
• Abnormal loading of the feeder
• Inaccurate regulator control settings (voltage level, bandwidth, and line drop compensation)
• Heavy loading by the first customer while there is a leading power factor on the feeder
• Light loading at the first customer with heavy loading on the feeder at the same time
The appropriate high and low limits for the output voltage can be programmed into the control at Function Codes
81 and 82, respectively. The accessory is then activated by accessing Function Code 80 and entering the appropriate code for the desired operation: 0 = off; 1 = high-voltage limiting only; 2 = both high and low limiting.
If low-voltage limiting only is desired, Function Code 80 should be set to 2 to enable this limit, and the value programmed into Function Code 81 for the high limit can be set to some extreme number (such as 135) to prevent the high limit from activating.
The control has two response sensitivities. If the output voltage exceeds either the high or low limit by
3 V or more, the control samples the voltage for two seconds and then taps immediately to bring the voltage to the limit value. If the output voltage exceeds either the high or low limit by less than 3 V, the control samples the voltage for 10 seconds then taps to bring the voltage to the limit value. The 10 second delay is used to prevent false responses to transient conditions. The control uses the sequential method of tapping, a two second pause between taps for voltage sampling, when bringing the voltage back to the limit value. HIGH and LOW annunciators in the display indicate when either limit is active.
To avoid potential cycling of the regulator, set the highand low-voltage limits at least two volts above and below the upper and lower bandwidth limits. This will establish a “grey zone” between the high-and low-voltage limits and the upper and lower bandwidth limits. When the output voltage is within this “grey zone,” the control will not perform any tap changes that would take the output voltage closer to the limit. If the voltage is directly on the inner edge of the grey zone, the control will allow one tap change to permit the voltage to enter the grey zone by as much as 0.7 V.
4-8
S225-10-10
NORMAL
RANGE OF
OPERATION
127 V HIGH-VOLTAGE LIMIT (F.C. 81)
125 V EDGE OF HIGH GREY ZONE
VOLTAGE SETTING (F.C. 1 OR 51)
Figure 4-13.
Voltage limiting grey zones
116 V EDGE OF LOW GREY ZONE
114 V LOW-VOLTAGE LIMIT (F.C. 82)
Voltage Reduction
An ideal application for system load management is at the distribution voltage regulator. Voltage reduction capabilities within the regulator control permit it to trigger the regulator to reduce voltage during situations where power demands surpass the available capacity, and where there are extraordinary peak loads. The control offers three modes of voltage reduction: local/digital remote, analog remote, and pulse. All modes operate for forward or reverse power flow conditions.
For the CL-5E control, a tap-to-neutral option has been added to the Voltage Reduction function. This feature may be employed regardless of the voltage reduction mode selected. To activate this feature, it must be enabled via Function Code 70, and 120 V ac must be applied to Terminals 1 and 2 of TB
2
. When tap-to-neutral is enabled, the third voltage reduction level of Analog
Remote (Latching), (Function Code 75), is disabled. If tap-to-neutral is not used, then Function codes 73, 74, and 75 all work as normal. All voltage reduction modes of the control work by calculating an effective set voltage as follows:
Effective Set Voltage = Set Voltage x (1- (percent reduction))
EXAMPLE: If the set voltage = 123 V and voltage reduction of 4.6% is active, the regulator will regulate the compensated voltage to 117.3 V, that is, tap down 5.7 V.
When any mode of voltage reduction is in effect, the
V. RED. annunciator segment is turned on. Voltage reduction occurs after timeout, as established by the time delay, Function Code 3 or 53, and the Control
Operating Mode, Function Code 42. The percent reduction in effect is displayed at Function Code 71.
Local/Digital Remote Mode
Function Code 70 = 1 (or 11 for CL-5E).
Voltage reduction can be performed by selecting the
Local/Digital Remote mode of operation (Function Code
70 = 1), and then entering into Function Code 72 the amount of reduction required as a percentage of the set voltage. To turn voltage reduction off set function Code
70 to 0.
Remote (Latching) and Pulse Mode
The remote latching and pulse mode of voltage reduction will be discussed in Analog SCADA.
Supervisory Control and Data
Acquisition (SCADA)
With its tap changer, potential transformer and current transformer, the regulator is a likely candidate for a
Supervisory Control and Data Acquisition system where the utility needs to have centralized voltage control for peak shaving, energy conservation or other purposes.
For many years regulators have been connected to analog SCADA systems where the regulator is controlled by contact closure and the feedback is via a voltage transducer connected to the voltage sensing circuit of the regulator control. Regulators are still being installed where the link between the regulator control and the remote terminal unit (RTU) is analog.
The control has a number of features which allow it to function well on these types of systems. For details, see
Analog SCADA, following.
With the advent of microprocessor-based controls such as the McGraw-Edison 4 and 5 Series controls, two-way real-time digital communication with the regulator control is now possible. The CL-5C and subsequent controls are specifically designed for this type of system. For details, see Digital SCADA, page 4-11.
The control is also well suited to the user who does not have a SCADA system, but does have a need for detailed information about the bus or feeder loading. See
Data Retrieval and Settings Upload, page 4-12.
Analog SCADA
Built-in Voltage Reduction
This is a continuation of the Voltage Reduction discussion. During voltage reduction the control remains in the Automatic mode. See Figure 4-14 which shows the left-most section of TB
2
, the bottom terminal board on the back panel. For either of the two modes described next, Remote Latching and Pulse, a nominal
125 V ac needs to be supplied to either or both terminals, 1 and 2. If the user supplies dry contacts, the voltage should be obtained from terminal V
9
. V
9 voltage is only available when the control switch is in the auto/remote position. If the user supplies wet contacts, the connections should be as shown in Figure 4-15.
Note that J is connected at the factory to the control ground.
Analog Remote (Latching) Mode
Function Code 70 = 2 (or 12 for CL-5E).
Up to three independent values of voltage reduction
(VR) are possible. Levels 1, 2 and 3 are programmed at
4-9
McGraw-Edison VR-32 Regulator and CL-5 Series Control
Function Codes 73, 74 and 75 respectively. As shown in
Table 4-3, latching contact 1 activates the VR programmed at Function Code 73, latching contact 2 activates the VR programmed at Function Code 74, and latching both contacts activates the VR programmed at
Function Code 75. Each of these function codes may be set from 0.1 to 10.0%.
TABLE 4-3
Voltage Regulator Latching Contacts
Latch Closed at These Contacts
Function Code
To Activate Voltage Reduction
1
2
1 & 2*
73
74
75
* Automatic Tap to Neutral for CL-5E, if FC70 is set to values 10, 11,
12 or 13
Pulse Mode
Function Code 70 = 3 (or 13 for CL-5E)
The same terminals and contacts are used for this mode as shown in Figures 4-14 and 4-15, but the contacts are pulsed (momentarily closed) rather than latched closed.
Each closure and waiting period between closures is expected to be at least 0.25 seconds in duration.
The number of steps of pulsed reduction, up to 10, is programmed at Function Code 76. The percent reduction per step is programmed at Function Code 77.
Starting at zero percent reduction, every time the contact 1 is pulsed, one step of reduction is added to the accumulated total. EXAMPLE: If the number of steps is
3, and the percent per step is 1.5%, four successive pulses of contact 1 will cause the following percentages of reduction: 1.5, 3.0, 4.5, 0. Pulsing to one step higher
TB
2
4 3 2 1 J V
9
V
7
BR G
2
1
USER – PROVIDED
CONTACTS (DRY)
Figure 4-14.
Dry contact connections for Remote Latching and Pulse
Modes
FACTORY-INSTALLED
JUMPER
TB
2 4 3
2
2
1
1 J V
9
V
7
BR G
125 VAC
USER – PROVIDED
CONTACTS (WET)
AND VOLTAGE
WETTING VOLTAGE
Figure 4-15.
Wet contact connections for Remote Latching and Pulse
Modes than the programmed number returns the reduction to zero. Also, any time contact 2 is pulsed the reduction returns to zero.
SOFT ADD-AMP
This feature (Function Code 79) allows the user to set the regulator for ADD-AMP locally at the control as well as remotely through SCADA. The SOFT ADD-AMP limits can be overridden by a local operator running the tap changer in manual mode of operation. This is not the case for the “hard” ADD-AMP limit switches on the position indicator face.
Remote Motor Control & Auto Inhibit
Terminal board TB
8
, located below RCT
1 on the control back panel, is supplied for user connections for Auto
Inhibit (blocking) and Motor Control. See Figure 4-16.
When the motor is controlled remotely, it is necessary to inhibit automatic operation. To control Auto Inhibit remotely, remove the jumper between terminals 4 and 5 and connect normally-closed contacts. Latching open those contacts inhibits automatic operation.
To remotely raise or lower the tap changer, the appropriate set of contacts is momentarily closed. An optional SCADA relay (current relay) is recommended if there is any chance that the raise and lower contacts may be closed simultaneously. If user-provided interposing relays are used, such that raise and lower contact closure cannot occur simultaneously, then the
SCADA relay is not required. If the SCADA relay is not used, then the operator should make a permanent connection from TB
2
-V
9 to TB
8
-2.
4-10
S225-10-10
USER-PROVIDED
REMOTE VOLTAGE
REDUCTION MODULE G HS R1 L1 NL DHR VS V5 G TB1
REMOVE JUMPER
FOR AUTO INHIBIT
TB3
CR1
CR2
HS2
HS1
C
M
TB8
1 2 3 4 5 6 7
AUTO
INHIBIT
RAISE LOWER
4 3 2 1 J V9 V7 BR G VS VM C1 C3 HS R3 L3 NL DHR TB2
REAR PANEL
NOTE: Connect M to HS
to HS
2
1
1
for spring drive tap changers.
Figure 4-16.
Auto inhibit and remote motor control connections
Transducer Connections
Refer to Figure 6-5, page 6-11 . To monitor the load voltage (forward direction), a transducer, nominal 120 V ac input, may be connected as follows: Connect the transducer hot lead to terminal V
4 on TB
1 and its ground lead to G on TB
1
. A current transducer, 200 mA input, may be connected as follows: Close knife switch C.
Remove the jumper between C
2 and C
4 on TB
1
.
Connect the transducer hot lead to C
2 and its ground lead to C
4
. Open knife switch C.
Fooler Voltage Scheme
Using this method, the voltage sensed by the control is raised, thereby “fooling” the control into reducing the voltage during its normal automatic operation. This method can be used with all CL-5 Series controls. A VR module, as shown in Figure 4-17, is usually supplied by the Remote Terminal Unit manufacturer. The VR module is usually a tapped auto-transformer with a pulseactivated indexing relay. When connected to the control back panel as shown, the voltage sensed by the control is raised as the module is pulsed to higher taps.
Since this method keeps the control in automatic operation, Auto Inhibiting is not used. An advantage of this method is that it can be applied to many different models of controls from many manufacturers. A disadvantage of this method is that while VR is activated, the measured load voltage is incorrect, as are all other calculated metering values which use the load voltage. To avoid the effects of metering inaccuracy, we recommend that the CL-5 Series Pulse Mode of VR be used.
COMMON V(IN)
REMOVE JUMPER
RELAY
K
V(OUT)
TB
1
G HS R
1
L
1
NL DHR V
S
V
5
Figure 4-17.
Typical user provided “Fooler Voltage” module
Digital Scada
Communication Protocols
The standard communications protocol used by the CL-
5 Series control is C.P.S. DATA 2179. This protocol is resident in the control, therefore a DATA 2179 protocol conversion board is not required by the CL-5 Series control.
Physical Interface
The Communications Channel #2 physical connections are made to an interface board, which is mounted to the control back panel. The interface board can be factory installed or field installed. The board mounts to predrilled holes in the back panel provided on C.P.S. regulator controls since 1989 for the installation of this or other devices. A communications cable connects the interface board to the CL-5 Series communications port.
For connection to an RTU, where the distance between the control and the RTU is typically long, a fiber-optic interface board is recommended for surge isolation. For installations where the interface board is close-coupled to another device, such as a telephone modem or radio, interface boards other than fiber-optic type will be made available.
4-11
McGraw-Edison VR-32 Regulator and CL-5 Series Control
Local Operator Security
Through the communications channel, the SCADA master may read the CL-5 Series data points, write to certain data points, or reset certain data points. The technique of writing to a data point is used for performing operations such as changing settings like Set
Voltage or Reverse Power Mode, or inhibiting automatic operation or controlling the tap changer motor, etc.
Following is a discussion of the levels of security used to protect the local operator.
Fiber-optic/RS232 and
Fiber-optic/Modem Interface Boards
2197 interface boards can be ordered either 1) equipped for Fiber-optic/RS232 capabilities or 2) equipped for
Fiber-optic/Modem capabilities. The interface boards are equipped with provisions for a 3.6 volt lithium cell battery for back-up power. To maximize battery life, no battery is supplied with the unit. If a back-up battery is not installed, loss of power to the interface board will inhibit all SCADA activity with the specific control, and with other controls connected in a loop.
Fiber-optic/RS232 interface boards can communicate via SCADA. The fiber-optic option can be used in a loop or star application. The RS232 option can only be used in a star application.
Fiber-optic/modem interface boards can also communicate via SCADA. The modem option can be used in both loop and star applications. The fiber-optic option is meant to be used only to loop controls.
Supervisory Switch
The CL-5 Series controls are equipped with a
Supervisory on/off switch. When this switch is in the on position, SCADA may perform the normal read, write and reset activity. When the switch is in the off position,
SCADA may only read the database. This affords protection to the local operator at the front panel, while allowing the system operator to maintain surveillance.
Control Switch
If the local operator switches the control switch
(auto/remote-off-manual) to either off or manual, the control internal circuitry prohibits SCADA from controlling the tap changer motor. Resets and other writes are allowed.
Active Control Security Level
If the local operator changes the control active security level to level 1 or above, or security override is set to override 1 or higher, this does not inhibit any SCADA activity. To inhibit SCADA writes and resets the local operator should turn the Supervisory switch to off.
NOTE: A local operator wishing to check automatic operation should check to make sure that the Blocking
Status, Function Code 69, is set to normal (0).
NOTE: Changes to any of the communications parameters, Function Codes 60-68 take effect immediately, as compared to the CL-4C which required that the power be turned off, then on, to reset those parameters on the separate protocol communications board.
Data Retrieval and Settings Uploading
The communications #1 channel of the CL-5 Series control is dedicated to the 9-pin D-subminiature connector located on the control front panel, labeled
Data Port. The Data Port is designed to interface with the McGraw-Edison Data Reader, a handheld, batteryoperated data gathering device. See page 7-1 for details on the Data Reader Kit. With the Data Reader the entire control data base may be downloaded for transfer to a personal computer. Analysis of the “reading” from the control, using the Data Reader Program (included in the
Data Reader Kit) allows the user to verify the control settings and analyze the conditions of the feeder as follows:
1) at the moment of the downloading (instantaneous metering), 2) maximum and minimum demand values since last reset (time-tagged demand metering), and
3) the profile of salient parameters (profile recorder).
The Channel #1 baud rate is selectable at 300, 1200,
2400 and 4800 Baud. However, to permit communications with the McGraw-Edison Data Reader, the Channel 1 baud rate is set at the factory to 4800 Baud.
Temporary connection to the Data Port may also be made with an IBM-compatible personal computer. A PCbased program, the CL-5 Interface Program, allows the local operator to 1) download the control data in a similar fashion as the Data Reader, 2) reset all metering and tap position maximum and minimum values, and upload settings which are specific to the control I.D.
number. For CL-4 and CL-5 Series control readings which were obtained with the Data Reader or the
Interface Program, the Interface Program also allows the user to view the data and to print custom reports.
4-12
Tap Changer
Tap Changer Operation
Spring- and Direct-drive Tap Changers
Regulators for low-current applications use stored energy spring-drive tap changers, most commonly on ratings 219 A and below. The tap changer for a specific rating is shown on the rating plate. Figures 5-1 (95 kV
BIL and below) and 5-2 (150 kV BIL) illustrate typical spring-drive mechanisms.
Voltage regulators used in medium- and high-current applications employ direct or Quik-drive tap changers.
Direct-drive tap changers are commonly applied above
219 A. The model 770B (Figure 5-3), 660C (Figure 5-4), and T875 (Figure 5-5) are rated 150 kV BIL.
Motor
The motor for the spring-drive and direct-drive tap changer is a capacitor-start, reversing gear-motor suitable for operation at 120 V ac, single-phase, at 50/60
Hz. An integral braking mechanism controls motor coast.
The motor for the Quik-drive tap changers is a capacitorstart, high-torque, reversing, gear-motor rated 120 V ac, single-phase, at 50/60 Hz, with a spring-loaded disc brake mechanism located on the tap changer.
All components are compatible with hot transformer oil and the windings are oil cooled. The motor will carry locked-rotor current for at least 720 hours.
Reversing Switch
The reversing switch function changes the polarity of the tapped winding. When the spring-drive tap changer is in the neutral position, the reversing switch is open. When the direct-drive tap changer is in the neutral position, the reversing movable contact assembly is in contact with the lower reversing stationary contact (V
L
).
The load current on all types is carried by the source bushing, the reactor, slip rings, main movable contacts, neutral stationary contact and the load bushing.
The reversing switch motion on the spring-drive tap changer occurs as the main movable contacts enter or leave the neutral position. A pin in the contact drive sprocket assembly engages a slot in the reversing segment when the main switch is in the neutral position.
The first tap step in either direction rotates the segment and the reversing switch engages the appropriate reversing stationary.
The drive sprocket pin and reversing segment provide a mechanical stop located approximately 320° on either side of neutral. When the pin engages the end of the
Figure 5-1.
928D Spring-drive Tap Changer
Figure 5-2.
170C Spring-drive Tap Changer
S225-10-10
5-1
McGraw-Edison ® VR-32 Regulator and CL-5C Control segment, the spring-drive mechanism will be loaded and the segment is locked to prevent any further motion in that direction.
The reversing switch motion on the direct-drive tap changers occurs as the main movable contact goes from neutral to the first raise position. On the Model 770B tap changer, a roller on the back side of the rear roller plate engages a slot in the reversing segment on the reversing insulating arm. On the Model 660C tap changer, a pinion, mounted on the same shaft as the rear roller plate, engages a slot in the reversing segment on the reversing insulating arm. As the rear roller plate rotates, the reversing movable contacts are driven from the VL reversing stationary contact to the VR contact.
Spring-drive Mechanism
Two steel extension springs are arranged in a triangular configuration to provide positive spring-over-center action to move the switch contacts. The mechanism is adjusted for smooth make-and-break contact action.
Direct-drive Mechanism
The 770B and 660C tap changers employ drive mechanisms based upon the same design principle, and many components are interchangeable. The motor turns a geneva pinion three complete revolutions per tap change. The motion of the geneva pinion turns a sixtooth geneva gear, a main drive shaft, and a scroll cam
180° per tap change. Each 180° movement of the scroll cam operates one of two roller plates and moves the corresponding main movable contacts 40°. The combination of geneva gearing and scroll cam characteristics results in a three-step, wipe/transfer/wipe contact action.
Attached to the main (geneva gear) drive shaft is a planetary gear-type mechanical stop which prevents contact motion beyond the maximum raise and lower positions.
Quik-drive Mechanism
The T875 tap changer is also a direct drive type. Once a tap change is initiated a holding switch energizes the motor through a separate circuit until the indexing motion is completed. The indexing occurs very fast. The total elapsed time to complete the action is 250 milliseconds from the time the indexing signal is started by the control. The motor turns a geneva gear pinion through a chain drive. Each full turn of the pinion rotates the geneva gear 20 degrees. The moving contacts are mounted on an insulating board that is rotationally attached to the geneva gear. This direct connection achieves accurate indexing of the contacts.
A friction brake arrests the inertia of the system once the tap change is completed. The brake is disengaged
Figure 5-3.
770B Direct-drive Tap Changer
Figure 5-4.
660C Direct-drive Tap Changer
5-2
S225-10-10
Figure 5-5.
T875 Quik-drive Tap Changer during the indexing motion. A mechanical stop prevents rotation of the geneva beyond the maximum position.
Contacts
Several connection conditions are satisfied by the variety of contact structures. They are divided into arcing and non-arcing.
The non-arcing contacts consist of front and rear slip rings which serve as the connection point for opposite ends of the reactor windings and one end of the two main movable contacts. All contact surfaces are
Electrical Tough Pitch (ETP) copper and all joints are riveted, bolted, or brazed to maintain a high-conductivity current path. Contact pressure between moving points is maintained by steel leaf springs (in the spring-drive tap changers) or by opposing steel compression springs (in the direct-drive and Quick-drive tap changers). The main movable contact is split to make contact on both surfaces of the slip ring and to resist separation in the event of high-current surges.
There are several types of arcing contacts on a regulator tap changer. They can be divided into two categories, stationary and movable.
1. The main stationary contacts are connected to the series-winding taps. The main movable contacts connect the slip rings to the main stationary contacts.
2. The reversing stationary contacts are connected to opposite ends of the series winding. The reversing movable contacts connect the neutral stationary contacts and load bushing to the reversing stationary contact.
NOTE: The neutral stationary contact in the directdrive tap changer has both arcing and non-arcing contact conditions.
All stationary contact bodies are made of ETP copper.
Copper-tungsten inserts are brazed to the edges of the stationary contacts since those contacts are subject to damage from impact or arcing duty. The main movable contacts are constructed of a copper-tungsten. The movable contacts are split to make connection on both sides of the stationary contacts. This split resists separation in the event of high-current surges.
The tap changer stationary contact body is copper. The reversing movable contacts are the same construction as the main movable contact.
Silver tungsten is used for movable contacts in highcurrent applications.
Contact erosion is a function of many variables such as system parameters voltage, load current, power factor, reactor design and main winding design.
Stationary contacts should be replaced before the arcing inserts erode to the point where there may be burning on the copper. Movable contacts should be replaced when approximately 1/8 inch of smooth surface remains.
Refer to S225-10-2 for complete information and typical erosion patterns for the various stages of contact life.
Spring-drive Operating Sequence
When the spring-drive switch is in the neutral position and the control calls for a tap change, the following events occur:
1. Motor brake releases and motor starts.
2. Motor holding switch closes, assuring that one tap change will be completed.
3. The up-slope of sprocket cam engages a lip of the spool. This lifts the pin in the pin cam and frees it from the hole in the actuator.
4. A projection on the sprocket cam contacts a leg on the pin cam, and both turn.
5. Drive shaft, which is attached to the pin cam, begins to turn the crank arm and the springs begin to extend.
6. Pin comes free from the lip on the spool and a spring pushes it against the surface actuator.
7. Down-slope of sprocket cam returns the spool to the start position.
5-3
McGraw-Edison ® VR-32 Regulator and CL-5C Control
8. Pin drops into the hole in the actuator 180° from the start position.
9. At this point, the crank arm is at top dead-center and the springs are fully loaded. Drive shaft and crank arm, sprocket cam, pin cam and actuator are locked together and connected through the chain to the motor.
10. Motor drives all parts beyond top dead center.
11. Spring unloads, instantaneously pulling pin cam and actuator through 180° at high speed. Pins on the actuator cause the contact drive sprocket to index one tap position.
12. As the contact drive sprocket moves, it imparts motion to the reversing switch segment and main movable contacts. This action closes the reversing movable and reversing stationary contacts and drives the main movable contact onto the adjacent main stationary contact. Also, the neutral light switch opens.
13. Motor continues to turn the sprocket cam until the motor holding switch opens. The gear motor output shaft has completed one revolution.
Should more than one tap change be required, the proceeding sequence will be repeated (except reversing switch portion) until the control is satisfied or the limit switch in the position indicator is reached.
Direct-drive Operating Sequence
When the switch is in neutral and the control calls for a tap change in the raise direction, the following events occur:
1. Motor brake releases and motor starts.
2. Geneva pinion rotates counter-clockwise to engage the geneva gear.
3. Geneva pinion drives the geneva gear, main drive shaft, and scroll cam through 60° and produces initial wipe action at the front main movable contact and reversing movable contacts.
4. Motor holding switch closes, assuring that one tap change will be completed.
5. Geneva pinion completes first revolution and continues to rotate.
6. Geneva pinion drives the geneva gear through 60° and the scroll cam and roller plates transfer the front main movable contacts from the neutral stationary contact N to the stationary contact No. 1.
Simultaneously, the reversing movable contact is transferred from the reversing stationary contact
(VL) to the stationary contact (VR).
7. Neutral light switch opens.
8. Geneva pinion completes second revolution and continues to rotate.
9. Geneva pinion drives the geneva gear, main drive shaft, and scroll cam through 60° and produces final wipe action at the front main movable and reversing movable contacts.
10. Motor holding switch opens.
11. Motor brake engages.
12. Motor stops.
A tap change from No. 1 raise position to neutral will be accomplished as described, except the geneva pinion will rotate clockwise. The reversing movable contact will be transferred from the reversing stationary contact (VR) to the stationary contact (VL).
Quik-drive Operating Sequence
When the tap changer is in the neutral position and the control calls for a tap change the following events occur:
1. The motor is energized and begins to turn.
2. The motor sprocket drives the main sprocket through the chain drive.
3. The geneva pinion on the main sprocket enters the geneva slot and begins to index the geneva.
4. The holding switch closes to insure the tap change will go to completion. The control opens the initial circuit. The motor is energized only through the holding switch.
5. The reversing switch pin on the geneva begins to drive the reversing switch indexing arm.
6. One of the two main interrupting movable contacts slides out of engagement with the neutral stationary contact and interrupts the circuit through that branch.
7. The reversing switch arm rotates, driving the reversing switch contacts to pivot, and bridge the neutral contact to a stationary contact connected to one end of the series winding is thus established.
No arcing occurs across the reversing switch contacts.
8. The main interrupting contacts slides over and onto the number one stationary contact, making a bridging position from contact N to contact 1 through the reactor.
9. The geneva pinion exits the geneva slot. The geneva stops moving and is rotationally locked.
10. The holding switch opens and de-energizes the motor.
5-4
11. The brake engages a disk in the main sprocket and brings it to a stop at mid travel.
12. The motor shaft has completed a 360 degree turn.
The elapsed time from step 1 to step 13 is 250 milliseconds.
13. If the control issues another signal to index in the same direction, the same sequence is repeated except the reversing switch is not actuated. The reversing switch does not move until the tap changer is reversed and stepped the opposite direction back to neutral.
S225-10-10
5-5
McGraw-Edison ® VR-32 Regulator and CL-5 Series Control
Cooper Power Systems
Service Information
Troubleshooting Guide
Complete Regulator in Service
WARNING: When troubleshooting energized equipment, protective gear must be worn to avoid personal contact with energized parts. Failure to do so may cause serious injury or death.
External Check
When service personnel arrive at what appears to be a malfunctioning regulator, it is advisable to examine the power connections first. For example, verify that the source lead is connected to the source bushing; that the load lead is connected to the load source bushing; and that the source-load lead is connected to the source-load bushing. Check for other potential problems, such as an open ground connection.
Defining the Problem
Refer to Figure 6-2, page 6-7 while diagnosing the problem.
After the external power connections have been checked, check the voltage-disconnect knife switch
(V
1 and V
6 if present) and the current shorting knife switch (C) of the rear panel signal circuit in the control box. Close the voltage disconnects if open. Open the shorting switch, if closed.
Check for loose connections or burnt wiring. Make sure the ratio-correcting transformer RCT
1 is on the correct tap for the regulated voltage shown on the nameplate on the control box door.
Remove the motor and panel fuses from the control and check for continuity across each fuse. Spare fuses are shipped with each control and located in the control box.
NOTE: Use only 350 V ac, slow-blow ceramic fuses of the proper current rating. Failure to do so may cause unnecessary fuse operation or insufficient protection of the regulator and control.
If the above checks do not identify the problem, determine which of the following three categories best describes the malfunction, and follow the corresponding diagnostic steps:
The Regulator Will Not Operate
Manually or Automatically
Diagnosing Trouble:
1. Connect a voltmeter between TB
TB
1
1
-R
1 and
-G. Set the control function switch on
MANUAL.
2. Toggle the raise switch and measure the voltage between terminals R
1
TB
1 the set voltage setting. and G on terminal board
. The voltage reading should be approximately
3. Place the voltmeter hot lead on TB
1
-L
1 toggle the lower switch.
and then
4. Measure the voltage between terminals L
1 and G on terminal board TB
1
. The voltage reading should be approximately the set voltage value.
5. If correct voltage readings are obtained in steps
2 and 4, the trouble may be in the position indicator, junction box or control cable. Refer to the junction box troubleshooting section on page 6-3.
6. If there is no voltage measurement in either step 2 or 4, make a corresponding measurement (R and L
3 to G) on lower terminal board TB
2
.
3 to G
7. If the voltages measured in Step 6 are approximately the set voltage value, then the fault is likely a loose connection or a faulty terminal between TB
1 and TB
2
.
8. If steps 2, 4, and 6 do not provide voltage readings, measure the voltage between V
M and
G on terminal board TB
2
. The reading should be approximately the set voltage value.
9. If Step 8 measures correctly, the trouble could be an open motor fuse, power switch or control.
10. If Step 8 does not yield a voltage measurement check the voltage between PD
1
1 (V
1
) and ground
(G) at the voltage disconnect knife switch.
a. If the set voltage value is approximately obtained, the V
1 disconnect or the ratio correcting transformer (RCT
1
) of the rear panel signal circuit is probably faulty.
b. If voltage is not obtained, the trouble is in the control cable, junction box, or regulator tank.
Refer to the junction box troubleshooting section on page 6-3. If the junction box checks are satisfactory, the trouble is in the regulator tank.
See S225-10-2 for the troubleshooting method.
The Regulator Will Operate
Manually But Not Automatically
Diagnosing Trouble:
1. If the control will not operate automatically, verify that the band edge indicators are functioning.
(These are the HIGH and LOW indicators located on the display.) If they are not functioning, check
6-1
Printed in U.S.A.
1
2
S225-10-10
Function Code 56, Reverse Sensing Mode. Set it to 0, if it is not there already. Retry the automatic mode of operation.
2. Verify that Function Code 69 (Auto Blocking) is set to 0 (Off). Retry the automatic mode of operation.
3. Measure the voltage from V
S board TB
2
.
to G on lower terminal a. A measurement of approximately the set voltage value at V
S to G indicates that the problem is in the control.
b. If there is no voltage present at V
S trouble is in the V
1 to G, the disconnect or ratio correcting transformer of the rear signal circuit. Replace them.
4. If check “a” indicates that the trouble is in the control, refer to Control Troubleshooting.
5. Check the hold switch circuit.
a. The tap changer will complete a tap change by placing the control function switch to MANUAL and toggling and holding the raise/lower switch in the desired direction for 2 seconds.
b. If the raise/lower switch must be held in the
RAISE or LOWER position to complete a tap change, the problem is in the “hold switch” circuit.
c. Check for voltage between TB and TB
TB
1
1
-HS and G. If voltage is present at
-HS and not on TB
2
2
-HS and G,
-HS, the problem is in the back panel wiring harness. Replace the orange HS lead from TB
1 voltage is present at TB
1
-HS to TB
2
-HS. If no
-HS, the problem is in the control cable, junction box cover or the hold switch (located inside the regulator) itself.
Check cable continuity up to the junction box. If it appears normal, the problem is the hold switch. Adjust or replace it (See S225-10-2). If all appears to be in order, the problem is not in the hold switch, but most likely in the control.
The Regulator Operates Manually but Operates Incorrectly
When Set On Automatic
Diagnosing Trouble:
Run the regulator to the neutral position with the control switch. Check for voltage between V
4 and G on TB
1
.
This is the sensing circuit supplying voltage from the output of RCT
1 on the rear panel. If this voltage is more than 10% above or below the programmed voltage level setting of the control, then the source is beyond the range of the regulator. An absence of voltage would indicate a wiring problem such as an open somewhere in the control power supply. If these checks are correct, then the malfunction is probably in the control. Refer to
Control Troubleshooting, following.
Control Troubleshooting
At this point, the problem has been determined to be in the control, so the front panel should be taken out of the control cabinet to a service bench for troubleshooting.
Figure 6-2, page 6-7 can be used to aid the troubleshooting process. The panel components are checked by using an external voltage of approximately 120 V ac,
60/50 Hz, applied to the external source terminals of the control.
To gain access to the front panel components, first remove the back shield. This is accomplished by removing the cable clamp attached to the shield side, and then removing the four nuts which secure the shield to the front panel.
1. Check the motor and panel fuses to ensure they have not blown.
2. Connect the power source to the external source terminals, observing the proper polarity.
WARNING: Correct polarity must be administered to the control. Failure to do so will cause a short circuit of the users’ voltage supply and possible damage to the control.
Place the power switch on the EXTERNAL position.
3. The control display should light. If the display does not light, measure the voltage on the printed circuit board from terminals P
5
-4 to P measure approximately 120 V ac.
5
-3, expecting to
4. If the display does not light and no voltage is measured from terminals P
5
-4 to P
5
-3, then the problem is in the power switch. The power
(Internal-Off-External) switch can be checked by measuring the voltage from switch terminal PS
2 ground, switch terminal PS
5 terminal PS
8 to to ground, and switch to ground. These measurements should equal the external voltage applied. If not, the power switch is defective.
5. If the display does not light and voltage is measured from terminals P
5
-4 to P
5
-3, then the circuit board is defective and must be returned to the factory for repair.
6. If the display does light, but reports the FAIL message, then the internal diagnostics have detected a problem. When the word FAIL appears, it does not necessarily indicate the control is malfunctioning.
Display Function Code 95.
6-2
McGraw-Edison ® VR-32 Regulator and CL-5 Series Control
Compare the display number with the System
Status Code, page 3-16. If any number other than
0, 6, 7 or 10 is displayed, the control has failed, and in need of repair. Contact Cooper Power
Systems for return authorization information. If 10 is displayed, it means there is no neutral light signal and the control has Function Code 12P set to 0
(neutral). Change FC 12P from 0 to 1, then reboot the control. It will now PASS.
The front panel circuits for the drag-hand reset solenoid
(DHR) and neutral light (NL) can be checked as follows:
1. Connect the ac voltmeter from G to DHR on fanning strip TB
2
(identified as white wire [G] and white/orange tracer [DHR]).
2. Depress the drag-hand reset toggle switch and observe approximately 120 V on the voltmeter. If no voltage is measured, the switch is probably defective.
3. Connect a 120 V ac source to the fanning strip TB
2
-
NL (identified as white/red) and fanning strip TB
2
-G and TB
2
-NL ground (identified as white). The neutral light on the control panel should light. If not, the bulb may be bad.
Junction Box Troubleshooting
This section is used if the regulator will not operate manually. (Problem was isolated to junction box or regulator tank after checking out control, on page 6-1).
The junction box is composed of a terminal board, the position indicator, and the control box interconnections.
Refer to Figure 6-1, page 6-5, when the following steps are made:
1. Remove the regulator from service, as stated on page 1-10.
2. Ground the three high-voltage bushings.
3. Open V
1
, disconnect switch on rear panel of control cabinet.
4. Remove junction box lid.
5. Check the wiring on the junction box terminal board for loose connections, burnt wiring or bad swage joints.
6. Set the power switch to EXTERNAL.
7. Apply a 60/50 Hz, 120 V ac nominal variable source to the external source terminals. Make certain to maintain correct polarity.
8. Set the control function switch on MANUAL.
9. Toggle the raise switch. Measure the voltage between terminals R and G on terminal board. The voltage reading should be approximately 120 V ac.
10. Move the voltmeter leads to L and G. Toggle the lower switch.
11. Measure the voltage between terminals L and G on terminal board. The voltage reading should be approximately 120 V ac.
12. If correct voltage readings are obtained in steps 9 and 11 above, the trouble is in the regulator tank.
Refer to troubleshooting section of S225-10-2.
13. If there is no voltage measurement in either step 9 or 11, the problem is in the limit switches inside the position indicator or in the control cable.
14. Check the continuity of the raise and lower limit switches. The switches should be closed on all tap changer positions except for the set limit switch positions of the indicator dial. To check the continuity: a. Remove position indicator green-black lead from splice terminals.
b. Place the meter lead on the disconnected lead and the other lead on terminal L of the junction box terminal board. Then check continuity.
c. If a continuity problem occurs, refer to Position
Indicator Replacement below.
d. Remove the position indicator blue lead from the splice terminal.
e. Place the meter lead on the disconnected lead and the other lead on terminal R of the junction box terminal board. Check continuity.
f. If a continuity problem occurs, refer to Position
Indicator Replacement below.
15. Check the reset solenoid of position indicator.
Depress the drag-hand reset switch while measuring the voltage between DHR and G on the terminal board. The voltage reading should be approximately 120 V ac and drag hands will reset.
16. If 120 V is read and drag hand will not reset, refer to Position Indicator Replacement, below.
17. If 120 V is not read, refer to Control Troubleshooting, page 6-2.
Position Indicator Replacement
The following instructions apply only to the junction box mounted position indicator construction that was initiated in April, 1980.
To replace a defective position indicator, the unit must be removed from service as outlined in Removal from
Service, page 1-11.
6-3
3
2
S225-10-10
WARNING: This procedure must only be performed on a regulator that is out of service.
1. A defect in the position indicator may have caused loss of synchronization between the tap changer and the indicator hand. Verify that the tap changer is in neutral via the neutral light of the control and visual inspection of the tap changer. If the position indicator does not also show neutral, refer to instructions in S225-10-2, Regulator Tap Changer
Operation and Maintenance.
2. Remove the junction box cover.
3. Note the location of the indicating hand for future alignment and disengage the flexible shaft from the position indicator shaft. In early 1989 this joint was changed to a setscrew type coupling. Older equipment employed a cotter pin coupling.
4. Disconnect the four leads from the junction box terminal board and open the two splice terminals to the control cable. Refer to Figure 6-1.
5. Remove the three bolts holding the indicator to the junction box and slide the indicator free.
6. Remove the gasket from the groove on the back of the indicator body.
7. Clean the gasket surface of the junction box and the gasket and groove on the new indicator.
8. Place the gasket in the groove and insert the leads through the junction box wall, align the holes and install the three bolts finger tight.
9. Wrench-tighten the bolts to evenly compress the gasket and bring the indicator body tight against the junction box.
10. Connect the six leads to the terminal board and control cables leads per Figure 6-1 and secure all connections.
11. Turn the indicator drive shaft to place the hands at the previously noted position.
12. Slide the flexible shaft coupling into the indicator coupling and secure the allen screws.
13. Position the wires to prevent snagging on the couplings and secure the wires with tie wraps.
14. Connect a 120 V ac external power supply to the external banana jack on the front of the control panel.
15. Run the tap changer manually to verify the alignment of the position indicator hand and the neutral light. The neutral light should be ON with the yellow pointer hand on zero.
16. The following steps are instructions for setting the proper alignment to ensure rotational calibration
on a new "Cooper " position indicator.
a. Align the black scribe line on the position indicator (PI) coupling to the center of the operating band notches on the PI housing (The notches are located on the back hub of the PI
housing). Note that the new Cooper PI has a one-piece input shaft/coupling and a raised mark at the 12 o'clock position on the PI housing hub.
Also, note the counterclockwise (ccw) and clockwise (cw) band indicator notches located on the sides of the 12 o'clock mark. Each band indicator notch is 15 degrees in bandwidth.
b. Directly align the scribe line on the coupling and the 12 o'clock housing marks and insert the external flex end into the receiver hole of the coupling and tighten the 2 set screws to 16 inlbs.
c. Apply power to the control, set the control to manual mode, and proceed to check the proper movement and alignment of the PI as follows: d. Index the PI to the 2-R position, the scribe line on the coupling should be located ccw of the 12 o'clock mark. If the scribe line is outside of the ccw band notch of the PI back hub, loosen the brass coupling set screws and rotate the coupling (while holding the flex shaft) until the scribe line is one line-width inside the band notch. Retighten the setscrews and proceed to step e. If the scribe line is inside the notch, proceed to e.
e. Index the PI to neutral (0) position. The scribe line should be located cw of the 12 o'clock mark.
If the scribe line is outside the cw band notch, loosen the screws and rotate the coupling until the scribe line is one line-width inside the band notch and retighten the setscrews to 16 in-lbs. f. Index the PI to 2-R and 2-L position several times and each time, the scribe line should stop inside the notched area of the PI housing then proceed to steps 17. If at any time that the scribe line falls outside of the notch area after each indexing, try to recalibrate per this procedure one more time or contact the Cooper
Service Department for assistance.
17. Replace the junction box cover.
Control Calibration
All controls are factory calibrated and should not need to be recalibrated by the user. However, calibration can be
6-4
McGraw-Edison ® VR-32 Regulator and CL-5 Series Control performed for both the voltage and current circuits with the following steps:
WARNING: It must be verified that both the neutral light and the position indicator hand indicate neutral when the tap changer is physically in the neutral position. Lack of synchronization will cause an indefinite indication of NEUTRAL. Without both indications of neutral, bypassing of the regulator at a later time will not be possible, and the line must be de-energized to avoid shorting part of the series winding.
Voltage Calibration
1. Connect an accurate true-RMS-responding voltmeter to the voltmeter terminals. This voltmeter should have a base accuracy of at least 0.1% with calibration traceable to the National Bureau of
Standards.
2. Connect a stable 50/60 Hz voltage source (with less than 5% harmonic content) to the external source terminals.
3. Place the power switch on EXTERNAL.
4. Adjust the voltage source to provide 120.0 V to the control, as read on the reference voltmeter.
5. Before calibration can be performed, security level 3 must be activated. This is accomplished by entering the proper security code at Function
Code 99. Depress the following keys on the keypad:
FUNCTION, 99, ENTER; 32123, ENTER
The proper level of security is now activated.
6. Access Function Code 47 by keying FUNCTION,
47, ENTER.
7. The display will show the voltage applied to the control. This should correspond to the reading on the reference voltmeter. If the control reading is significantly different (see Table 2-1 for allowable tolerances), the calibration can be altered by keying
CHANGE, and then entering the correct voltage as displayed on the reference meter, followed by
ENTER. The voltage circuit is now calibrated.
RS (ORG-BLK)
CC (ORG-BLK)
CC (RED)
CC (BLK)
RLS (BLU)
POSITION INDICATOR
LOWER LIMIT
SWITCH (LLS)
RAISE LIMIT
SWITCH (RLS)
POS. IND.
RESET
SOLENOIDS
(RS)
AVAILABLE
LEAD FOR
ACCESSORIES
1 2
JBB-L (GRN-BLK)
CC (GRN-BLK)
1 2
JBB-R (BLU)
CC (BLU)
JBB-G (WH)
JBB-DHR (ORG-BLK)
CC (WHT-BLK)
LLS (GRN-BLK)
CC (ORG)
CC (RED-BLK)
CC (GRN)
CC (WH)
RS (WH)
10 CONDUCTOR
CABLE (CC)
S
4
R
S
HS
L
NL
C
2
M
2
2
C
1
G
DHR
JUNCTION
BOX
TERMINAL
BOARD
(JBB)
TB2
TB1
CT PROTECTION
CIRCUIT
GROUND
STUD
GROUND
STUD
TO CONTROL
Figure 6-1.
Junction Box Wiring Diagram
6-5
3
2
S225-10-10
Current Calibration
1. Connect an accurate true-RMS-responding ammeter in series with the current source.
2. Connect a stable 60/50 Hz current source (with less than 5% harmonic content) to the reference ammeter and to the current input terminals C
C
3 on fanning strip TB
2 wire, and C
3
(C
1 is identified as the green wire).
1 and is identified by a red
3. To power the control, connect a 120 V ac voltage source to the external source terminals.
4. Place the power switch on EXTERNAL.
5. Adjust the current source to provide 0.200 A to the control, as read on the reference ammeter.
6. Before calibration can be performed, security level 3 must be activated. This is accomplished by entering the proper security code at Function
Code 99. Depress the following keys on the keypad:
FUNCTION, 99, ENTER; 32123, ENTER
The proper level is now activated.
7. Access Function Code 48 by keying FUNCTION,
48, ENTER.
8. The display will show the current applied to the control. This should correspond to the reading on the reference ammeter. If the control reading is significantly different (greater than 0.6 milliamperes error), the calibration can be altered by keying
CHANGE, and then entering the correct current as displayed on the reference meter, followed by
ENTER. The current circuit is now calibrated.
6-6
McGraw-Edison ® VR-32 Regulator and CL-5 Series Control
CIRCUIT BOARD CONNECTORS
CONNECTOR P4
11 ORANGE
10 VIOLET
9 WHITE
8 BROWN
7 YELLOW
6 WHITE/PURPLE
5 (BLANK)
4 WHITE/RED
3 RED/WHITE
2 WHITE/ORANGE
1 WHITE/BLUE
CONNECTOR P5
9 WHITE/GREEN
8 RED/BLACK
7 BLUE
6 (BLANK)
5 WHITE/BROWN
4 BLACK
3 WHITE
2 GREEN
1 RED
SOURCE
BUSHING
S
SERIES
WINDING
REMOVABLE
JUMPERS FOR
ACCESSORIES
TAPS LOCATED
ON TAP CHANGER
TERMINAL BOARD
UNDER OIL
CURRENT TRANSFORMER
(TOROIDAL COIL)
L
LOAD
BUSHING
CTP
JBB-C
2
1
SD
1
JBB-C
1
2
(C)
TB
1
-C
2
TB
1
-C
4
TB
1
-C
3
REMOVABLE GROUND
Located on back panel plate inside control box.
TB
2
-C
1
TB
2
-C
3
P
4
P
3 P
2
P
1
X
2
X
1
DIFFERENTIAL
POTENTIAL
TRANSFORMER
CTP - CURRENT TRANSFORMER
PROTECTOR CIRCUIT
DF - DIFFERENTIAL VOLTAGE FUSE
DHR - DRAG HAND RESET
EST - EXTERNAL SOURCE TERMINALS
HSL - HOLDING SWITCH LOWER
HSR - HOLDING SWITCH RAISE
IRS - INDICATOR RESET SOLENOID
(POSITION INDICATOR)
JB - JUNCTION BOX ON
REGULATOR COVER
JBB - JUNCTION BOX TERMINAL
BOARD ON THE COVER
LLS - LOWER LIMIT SWITCH
(POSITION INDICATOR)
MC - MOTOR CAPACITOR
MF - MOTOR FUSE
MOV - METAL OXIDE VARISTOR
NL - NEUTRAL LIGHT
NLC - NEUTRAL LIGHT CAPACITOR
NLS - NEUTRAL LIGHT SWITCH
PD - POTENTIAL DISCONNECT DEVICE
PF - PANEL FUSE
PS - POWER SWITCH
RCT - RATIO CORRECTION
TRANSFORMER
RLS - RAISE LIMIT SWITCH
(POSITION INDICATOR)
SD - CURRENT SHORTING DEVICE
TB - CONTROL TERMINAL BOARD
TCB - TAP CHANGER TERMINAL BOARD
VDIFF - DIFFERENTIAL VOLTAGE
VM - MOTOR VOLTAGE
VS - SENSING VOLTAGE
VTT - VOLTAGE TEST TERMINALS
SHUNT
WINDING
CONTROL
WINDING
SL
SOURCE
LOAD
BUSHING
E
3
E
2
E
1
G
REMOVABLE
GROUND
ON BACK
PANEL
JBB-G
TB
1
-G
JBB-S
4
JBB-S
2
Figure 6-2.
Wiring diagram for Type B VR-32 Regulator and control with differential potential transformer
1
PD1
2
(V
1
)
1
PD2
2
(V
6
)
133
127
120
115
110
104
COM
RCT1
TB
7
-V
6
TB
7
TB
7
-V
-G
1
133
127
120
115
110
104
COM RCT2
6-7
3
S225-10-10
VR
2
COUPLER
TB
2
-2
TB
2
-1
TB
2
-J
P
4
-7
P
4
-8
P
4
-10
P
5
-2
P
5
-1
I
REMOTE
VOLTAGE
REDUCTION
VR
1
COUPLER
SUPERVISORY
SWITCH
COUPLER
AUTO
ENABLE
COUPLER
CL5 CIRCUIT BOARD
NEUTRAL
LAMP
SENSE
COUPLER
DHR
MOV
P
4
-2
V
IN
RELAYS
LOWER SOURCE RAISE
MOTOR
CURRENT SENSE
COUPLER
P
5
-5
P
5
-4
MOVABLE
SOLDERED
JUMPER
2 A
PF
6 A
MF
7
EXTERNAL
SOURCE
8
9
INTERNAL
SOURCE
6
4 1
5
OFF
2
3
2 A
DF
PS
TB
1
-V
4
TB
1
-V
5
TB
1
-V s
TB
2
-V s
TB
2
-V
M
REMOVABLE JUMPERS
FOR ACCESSORIES
TB
2
-V
7
V
IN
V
DIFF
P
5
-3
V
OUT
P
4
-3 P
4
-1 P
5
-9 P
5
-8
P
5
-7 P
4
-11 P
4
-9 P
4
-6 P
4
-4
1
EST
2
TB
2
-G
OFF
ON
SUPERVISORY
1
VTT
2
TB
2
-BR
TB
8
-5
TB
8
-4
AUTO
OFF
MANUAL
RAISE
OFF
LOWER
TB
2
-V9
REMOVABLE
JUMPER FOR
BLOCKING
RELAY
PROVISION
TB
2
-L3
TB
1
-L
1
TB
8
-3
TB
2
-R
3 TB
2
-HS
TB
1
-HS
TB
8
-1
MOTOR
1
2
TCB-5
LLS
JBB-L
T
3
JB
2
MC
1
RLS
TB
1
1
-R
1
2
JBB-R
T
2
JBB-HS
TCB-4
NO NC
TCB-1
NLS
C
T
1
3 1
HSL
TCB-G
1 2
HSR
JBB-G
JBB-NL
TB
1
-NL
TB
2
-NL
NLC
1
NL
2
TB
2
-G TB
2
-G TB
1
-G
INTERNAL REMOVABLE GROUND
IN JUNCTION BOX
DRAG
HAND
RESET
OFF
RESET
TB
2
-DHR
TB
1
-DHR
JBB-DHR
1
2
IRS
2
Note: Portions of schematic shown in dotted enclosure (----) are located in regulator tank.
Portions of schematic shown in dashed enclosure (– – – –) are located on the circuit board.
Portions of schematic shown in short-long dashed enclosure ( — - —) are located in the junction box near the tank cover.
Portion of schematic shown in short-short-long dashed enclosure (— - - —) is the power switch on the front panel.
6-8
McGraw-Edison ® VR-32 Regulator and CL-5 Series Control
S4
R
C1
S2
DHR
L
NL
HS
C2
M2
G
JUNCTION BOX TERMINAL
BOARD (JBB)
TO CONTROL
TERMINAL BOARD AND
POSITION INDICATOR
JBB-C1
JBB-C2
1
2
TAP CHANGER
TERMINAL BOARD (TCB)
JBB-NL
JBB-L
JBB-R
JBB-HS
JBB-G
7
6
5
4
1
G
NL-NC
NL-C
MC-2
HS-3
MC-1
HS-2
HS-1
NL-NO
M-1
T-S1
CURRENT
TRANSFORMER (C)
TCB-E3
TCB-E2
TCB-E1
TCB-G
S1 E1 E2 F1
CONTROL WINDING
(T)
TCB-7
TCB-6
TCB-1
NC
C
NO
NEUTRAL LIGHT
SWITCH (NL) RAISE
TAP CHANGER
MOTOR (M)
LOWER
1 2 3
HOLDING SWITCH (HS)
2 TCB-4
1 TCB-1
3 TCB-5
T-E1 E JBB-S2
TCB-G
T-E2
E1
P3
E3
P2
E2
T-F1
MC-1
MC-2
M-2
TCB-4
M-3
TCB-5
1 2
MOTOR CAPACITOR (MC)
HS-1 — BLACK
HS-2 — BLUE
HS-3 — RED
JBB-C
1
JBB-C
2
— WHITE
— BLACK
JBB-G — WHITE
JBB-HS — ORANGE
JBB-L — GRN/BLK
JBB-NL — RED/BLK
JBB-R — BLUE
JBB-S
2
— WHITE
M-1 — WHITE
M-2 — BLUE
M-3 — RED
MC-1 — BLUE
MC-2 — RED
NL-C — WHITE
NL-NC — GREEN
NL-NO — ORANGE
T-F
1
T-E
1
— WHITE
— WHITE
Figure 6-3.
Typical internal wiring of regulator with spring and direct drive tap changer
T-E
2
T-S
1
— WHITE
— WHITE
TCB-1(HS) — BLACK
TCB-1(NL) — ORANGE
TCB-4 — BLUE
TCB-5 — RED
TCB-6 — WHITE
TCB-7 — GREEN
TCB-E
1
TCB-E
2
— WHITE
— WHITE
TCB-E
3
— WHITE
TCB-G — WHITE
6-9
3
S225-10-10
S4
S2
R
C1
DHR
L
NL
HS
C2
M2
G
JUNCTION BOX TERMINAL
BOARD (JBB)
TO CONTROL
TERMINAL BOARD AND
POSITION INDICATOR
JBB-NL
JBB-L
JBB-R
JBB-HS
JBB-G
T-E1
JBB-C1
JBB-C2
7
6
5
4
1
G
1
2
TAP CHANGER
TERMINAL BOARD (TCB)
E1
E3
NL-NC
NL-C
MC-2
LHS-NO
MC-1
RHS-NO
LHS-C
RHS-L
NL-NO
M-1
E JBB-S2
T-E3
CURRENT
TRANSFORMER (C)
TCB-7
TCB-6
TCB-1
NC
C
NO
NEUTRAL LIGHT
SWITCH (NL)
TCB-G
TCB-E3
TCB-E2
TCB-E1
JBB-S4
S1 E1 E2 E3
TRANSFORMER
CONTROL WINDING
(T)
TAP CHANGER
MOTOR (M)
LOWER RAISE
LOWER
HOLDING SWITCH (LHS)
NO TCB-5
C TCB-1
NC
1 2 3 CAM
NC
C TCB-1
NO TCB-4
MC-2
RAISE HOLDING SWITCH (RHS)
MC-1
M-2
TCB-4 TCB-5
M-3
T-E2 E2
1 2
MOTOR CAPACITOR (MC)
2
JBB-S 4 (SWPT-Y
1
) —
BLACK
SWPT-X
1
SWPT-X
2
— BLACK
— WHITE
LHS-NO — BLACK
RHS-NO — BLUE
LHS-C — RED
JBB-C
1
— WHITE
JBB-C
2
— BLACK
RHS-C — BLACK
JBB-G — WHITE
JBB-HS — ORANGE
JBB-L — GRN/BLK
JBB-NL — RED/BLK
JBB-R — BLUE
JBB-S
2
— WHITE
JBB-S
4
(T-S 1 )— WHITE
M-1 — WHITE
M-2 — BLUE
M-3 — RED
MC-1 — BLUE
MC-2 — RED
NL-C — WHITE
NL-NC — GREEN
Figure 6-4.
Typical internal wiring of regulator with Quik-drive tap changer
NL-NO — ORANGE
T-E
T-E
T-E
1
2
3
— WHITE
— WHITE
— WHITE
TCB-1(HS) — BLACK
TCB-1(NL) — ORANGE
TCB-4 — BLUE
TCB-5 — RED
TCB-6 — WHITE
TCB-7 — GREEN
TCB-E
1
TCB-E
2
— WHITE
— WHITE
TCB-E
3
— WHITE
TCB-G — WHITE
6-10
McGraw-Edison ® VR-32 Regulator and CL-5 Series Control
JBB-G — WHITE
JBB-HS — ORANGE
RLS-1 — BLUE
LLS-1 — GRN/BLK
JBB-NL — RED/BLK
JBB-DHR — ORG/BLK
JBB-S
2
JBB-C
2
JBB-C
1
TB
TB
TB
TB
TB
— BLACK
— GREEN
— RED
2
-HS — ORANGE
8
-1 — BLUE
2
-R
3
2
-L
— BLUE
8
3
— WHT/GRN
-3 — WHT/GRN
TB
TB
TB
2
-NL — WHT/RED
2
-DHR — WHT/ORG
2
-V
RCT
1 s
— BLACK
-120 — BLACK
-1 — VIOLET SD
1
TB
2
-C
RCT
2
3
— GREEN
— WHT/BRN
— BLACK RCT
1
TB
TB
7
7
-V
-V
6
— WHT/BRN
PD
2
PD
1
1
— BLACK
-2 (V
6
) — WHT/BRN
-2 (V
1
) — BLACK
-COM — WHITE RCT
2
TB
TB
1
2
-C
-C
2
— VIOLET
RCT
1
TB
1
— RED
-COM — WHITE
TB
TB
TB
7
-G — WHITE
1
8
-V
4
— BLACK
-4 — WHITE
— BLUE
TB
TB
1
-R
1
1
-L
2
1
— WHT/GRN
-G — WHITE
TB
TB
2
-BR — WHT/BLUE
8
-5 — WHT/BLUE
TB
SD
1
TB
1
-V
S
— BLACK
-2 — RED
TB
TB
TB
TB
1
1
-C
3
— GREEN
-HS — ORANGE
1
-NL — WHT/RED
1
-DHR — WHT/ORG
7
-G — WHITE
-120 — WHT/BRN RCT
2
JBB-S
4
TB
2
-V
7
— WHT/BLK
— WHT/BRN
REMOVABLE
GROUND
JBB-G
G HS
KNIFE
SWITCHES
VOLTAGE
SUPPLY
JBB-HS
RLS-1
R
1
LLS-1
(V
6
)
PD
2
L
1
JBB S
4
JBB S
2 JBB C
2
TB
7
-V
1
(V
1
)
PD
1
REMOVABLE JUMPERS
FOR ACCESSORIES
JBB-DHR
JBB-NL
NL DHR V
S
TB
2
-HS
TB
8
-1
TB
2
-
TB
2
R
3
-L
3
TB
8
-3
TB
2
TB
2
-DHR
NL
TB
2
-V
S
RCT
2
TB
7
-V
6
1
2
RTC
1
1
2
(C)
1
SD
1
2
JBB-C
1
V
5
V
4
RCT
1
-120
V
7
TB
1
-C
2
CURRENT
SUPPLY
TB
2
-C
1
VOLTAGE RATIO
ADJUSTMENT LEAD
WITH FORK TONGUE
TERMINAL
G
TB
7
-G
R
2
JBB
L
2
TO POSITION INDICATOR
AND REGULATOR TANK
SPARE
WHITE/BLACK
WIRE
R
4
VR
2
VR
1
COM
V
6
TB
2
-V7
PD
2
-2
TB
7
RCT
1
-G
-COM
TB
1
-V
4
PD
1
-2
L
4
C
2
SD
1
-1
PD
2
-2 PD
1
-2 RCT
2
-COM
133
127
120
115
110
104
COM
133
127
120
115
110
REMOVABLE JUMPERS
FOR ACCESSORIES
C
4
V
1
RCT
2
RCT
1
G
C
3
TB
2
-C
3
104
RCT
2
-COM
TB
8
-4
TB
1
-R
1
COM
TB
1
-L
1
TB
2
RCT
1
-G
-COM
TB
2
-BR
TB
1
TB
7
1 2 3 4 5 6 7 TB
8
NOTES:
TB
2
-V
7 to TB
2
-V s jumper only applies to nonreverse power flow back panel assemblies supplied without RCT
2
.
TB 2 -V
7 is connected to
RCT
2
-120 on back panel assemblies set up for reverse power flow supplied with RCT 2 .
4 3 2 1 J V
9
RCT
2
-120
TB
8
-5
TB
8
-4
TB
1
-V
S
V
7
BR G V
S
V
M
SD
1
-2
C
1
TB
1
-HS
TB
1
-C
3
C
3
HS
TB
1
-L
1
TB
1
-R
1
R
3
L
3
TB
1
-DHR
TB
1
-NL
NL DHR TB
2
CONTROL
Figure 6-5.
Back panel signal circuit
6-11
3
S225-10-10
Accessories
Heater Assembly
The thermostatically-controlled heater assembly is best used in high-humidity areas.
The thermostat in the heater assembly will turn the heater on when the temperature falls below 85°F (29°C) and off when the temperature exceeds 100°F (38°C).
For full details refer to S225-10-1 Supplement 2.
Data Reader
The optional hand-held Data Reader allows the operator to copy all of the function code parameters from the control for transfer to a personal computer. Operation of the control is not affected by the Data Reader.
The Data Reader can store 100 Meter Pac readings, 100
CL-4B/C control readings, 25 CL-5 Series control readings and 20 F4C control readings before the memory must be purged.
Data Reader and Software Kit
The Data Reader and Software Kit includes the Data
Reader, the Data Reader-to-control cable, the Data
Reader-to-PC cable, the Data Reader windows software and documentation. The non-copy protected software operates on an IBM-compatible personal computer with
Windows 3.1 or higher. The software allows the operator to perform the following functions:
1. Upload the data from the Data Reader to the soft ware database.
2. Erase the Data Reader memory.
3. Scan the data on the monitor.
4. Print reports.
5. Transfer data to another database.
Data Reader Assembly
The Data Reader Assembly consists of the Data Reader and the Data Reader-to-control cable.
Cooper Control Interface Software
The Cooper Control Interface (CCI) is a Windows-based configuration software package for use with the regulator
CL-4C and CL-5 Series controls. The CCI allows the users to:
• Create Control Settings
• Upload Settings to the Control
• Download Readings from the Control
Figure 7-1.
Fiber / RS-232 Board
Figure 7-2.
Fiber / Modem Board
• Provide Output of Settings and Readings
• Manage Settings and Readings Effective
This program is fully compatible with Windows 95,
Windows 98, Windows 2000, and Windows NT4.0
operating systems. The CCI applications use Dynamic
Data Exchange (DDE) technology to connect from hardware to software easily and trouble free.
Both readings and settings are stored as non-proprietary data base formats (.xls) to allow use of the data by other applications without awkward conversions.
Its Graphic User Interface is easy to use and understand. Online help and a complete User Manual make the program easy to learn and generous toolbars make working within the program efficient.
The CCI is designed for front panel configuration with the regulator or recloser control. It also has 2179 protocol for verification with the communication port.
The program includes a file conversion routine to update all of your old files, both settings and readings, to the
7-1
McGraw-Edison ® VR-32 Regulator and CL-5 Series Control new file format. This conversion facilitates the transition from the old DOS-based applications to the new applications.
PC to Data Port Cable
For direct connection of a PC to the Data Port of the
CL-4 or CL-5 (and also the Form 4C recloser control) a special cable is required. This special cable connects from the computer’s RS-232 port to the TTL Data Port.
The cable provides the proper voltage and pin configuration.
The Data Port is intended for connection with either the
Data Reader black coil cord or the above PC to Data
Port cable. A standard RS-232 cable will not work for interfacing from a PC to the Data Port on the CL-4 or
CL-5 series controls. Use of a RS-232 may cause damage to the Data Port on the control and future connections to the Data Port may not work properly.
Digital Communications
This feature includes full remote metering and realtime operation capability. Using this feature, all metering and changing of parameters, including all of the options, can be controlled remotely. Additional remote capabilities include the ability to tap up or down a specified number of taps and the ability to determine the status of local activity. Digital communications requires the addition of one interface board to the back panel.
Digital Communication Interface
Board
For connection of the CL-5 Series controls to a digital communication system, several interface boards are available.
One option is a board that provides either fiber optic or
RS-232 interface with DATA 2179 communication output. A pair of standard ST type fiber optic connectors and an RS-232 port are mounted on the interface board to provide the customer connection to digital SCADA via multi-mode fiber optic cables or a standard 9-pin DB-9
RS-232 cable. Communication settings are easily changed with the use of dip switches. (See Figure 7-1.)
A second option is a board that provides modem/fiber optic interface with DATA 2179 communication output.
The modem connection is just like a computer modem at 2400 baud, and is addressed simply by dialing into it via telephone. The modem connection on the board is a standard RJ-11 phone line connection. All communications to and from the digital SCADA system to the regulators utilize the modem connection. A pair of standard ST type fiber optic connectors is mounted on the interface board to provide the customer connection from regulator to regulator in a loop. Therefore, in this
Figure 7-3.
DNP 3.0 Board application, only one modem interface board is required for the loop of regulators. The standard fiber optic/RS232 boards would be supplied for additional regulators in the loop. (See Figure 7-2.)
Another option is a board that provides either fiber optic or RS-232 interface with DNP 3.0 communication output.
This two-layer board consists of a protocol converter interface board (from DATA 2179 to DNP 3.0) and a power supply board. A pair of standard ST type fiber optic connectors and an RS-232 port are mounted on the interface board to provide the customer connection to digital SCADA via fiber optic cables or a standard 9pin DB-9 RS-232 cable. Communication settings are easily changed with the use of dip switches and rotary switches on the board. (See Figure 7-3.)
7-2
S225-10-10
The boards are self-powered from the internal regulator potential transformer. A connection from the interface board is made to a port located on the inside of the CL-5 swing panel. The boards can be factory installed or easily installed at the customer's site.
SCADA Relay and Terminal Block
For analog SCADA operation (remote tap changer control), as shown in Figure 4-16, page 4-10, an optional
SCADA relay and terminal block assembly is available.
(See Figure 7-4.)
Remote Mounting Control Cable
For remote mounting of the control cabinet, extended cable lengths are available in 5 foot (1.5 m) increments from 15 feet (4.6 m) to 45 feet (13.8m).
Fan Cooling Accessory
Voltage regulators 250 kVA and larger can be equipped with fan cooling. Fan cooling increases the load capacity of the regulator by 33%. Special requirements are necessary on regulators using fan cooling. Therefore, the regulator must be ordered with fan cooling or with provisions for adding fan cooling. Mounting cooling fans flush to the plate-type radiator is accomplished by using T-bolts that secure the cooling fan to the bank of radiators.
The automatic operation of the fan is controlled by a thermometer having a thermal switch that will cycle the fan on or off when the top-oil temperature reaches predetermined temperature limits. The thermal switch has an upper limit adjustable from 80°C to 110°C. The differential from make to break is 6°C to 10°C. The thermal switch, when temperature-activated or deactivated, signals a relay which turns the fan on or off.
Figure 7-4.
SCADA relay and terminal block
7-3
McGraw-Edison ® VR-32 Regulator and CL-5 Series Control
Spare Parts
Ordering Information
When ordering replacement parts or field-installation accessories for your McGraw Edison VR-32 step-voltage regulator, provide the following information:
1. Regulator serial number (found on nameplate).
2. Regulator catalog number (found on nameplate).
3. Part number (from Parts Manual*).
4. Description of each part.
5. Quantity of each part required.
*A complete list of replacement parts is available. The parts replacement list is most conveniently accessed through the EPIC CD-ROM that requires only a catalog or serial number. This CD-ROM covers parts for VR-32 and Auto-booster regulators built since 1981. Consult your Cooper Power Systems sales representative for information on receiving a CD.
TANK COVER
Figure 8-1.
High-voltage bushing
Cooper Power Systems
Service Information
TERMINAL CAP
TERMINAL CAP GASKET
COMPLETE BUSHING
ASSEMBLY W/HARDWARE
BUSHING (PORCELAIN)
BUSHING GASKET
CLAMP RING
BOLT
SPRING
WASHER
CONICAL SPRING WASHER
ROD ASSEMBLY
HEX JAM NUT
MAIN
MOVABLE
CONTACT (LH)
HOLDING
SWITCH FOR
ALL TAP
CHANGER
MODELS
MOTOR KIT
REVERSING
STATIONARY
CONTACT (RH)
REVERSING
STATIONARY
CONTACT (LH)
Figure 8-2.
Replacement parts for spring-drive tap changers 928D and 170C
8-1
Printed in U.S.A.
MAIN
STATIONARY
CONTACT
MAIN
MOVABLE
CONTACT (RH)
1
S225-10-10
REVERSING
NEUTRAL
STATIONARY
CONTACT
ASSEMBLY
REVERSING
STATIONARY
CONTACT
Figure 8-3.
Replacement parts for direct drive tap changer 770B
SHIELD
MAIN MOVABLE
CONTACT
STATIONARY
ARCING
CONTACT
ASSEMBLY
REVERSING
NEUTRAL
STATIONARY
CONTACT
ASSEMBLY
MOTOR KIT FOR BOTH
770B AND 660C
REVERSING
MOVABLE
CONTACT
REVERSING
STATIONARY
CONTACT
2
Figure 8-4.
Replacement parts for direct drive tap changer 660C
REVERSING
MOVABLE
CONTACT
ASSEMBLY
MAIN MOVABLE
CONTACT
ASSEMBLY
8-2
McGraw-Edison ® VR-32 Regulator and CL-5 Series Control
QUIK-DRIVE
HOLDING
SWITCH
ASSEMBLY
MOTOR CAPACITOR
50 uF 440 VOLTS 100°C
CHAIN
RIGHT HAND
REVERSING
STATIONARY
CONTACT
MOTOR
MAIN
REVERSING
STATIONARY
MAIN STATIONARY
CONTACT
LEFT HAND REVERSING
STATIONARY CONTACT
BRAKE ASSEMBLY
LEFT HAND MAIN
MOVABLE CONTACT
RIGHT HAND MAIN
MOVABLE CONTACT
REVERSING MOVABLE
CONTACTS CONTACT
Figure 8-5.
Replacement parts for Quik-drive tap changer T875
8-3
3
S225-10-10
Index
Section-Page Number
Accessing ....................................................................1-4, 2-6
ADD-AMP Feature ...........................................................1-15
Hard ............................................................................4-10
Soft..............................................................................3-15
Address, Communications ...............................................3-12
ANSI Type A.....................................................................1-18
ANSI Type B.....................................................................1-18
Arresters
Series ..........................................................................1-15
Shunt...........................................................................1-15
Auto Inhibit .......................................................................4-10
Automatic Operation...........................................................2-4
Back Panel
Photo.............................................................................1-3
Schematic ...................................................................6-11
Band (In-Band, Out-of-Band) .............................................2-4
Baud Rate
Comm. Channel ..........................................................3-12
Data Port .....................................................................3-11
Bandwidth ..........................................................2-7, 3-2, 3-10
Bi-directional Mode ..................................................4-5 to 4-6
Blocking Status.................................................................3-13
Bypassing.................................................................1-3 to 1-4
Cable
Control .................................................................1-13, 7-3
Calendar....................................................................3-10, 4-1
Calibration ............................1-9 to 1-10, 3-9, 3-10, 6-4 to 6-5
Circuits
Current ........................................................................1-22
Motor ...........................................................................1-22
Power..............................................................1-18 to 1-19
Voltage ........................................................................1-19
Clock .........................................................................3-10, 4-1
Co-generation Mode...........................................................4-7
Communications ..................................................3-11 to 3-13
Channels.........................................................3-11 to 3-13
Port .................................................................3-11 to 3-13
Protocol...........................................................3-11 to 3-12
Communications, Digital ...........................................4-11, 7-2
Compensated Voltage ........................................................3-3
Configuration ...............................................................2-8, 3-9
Contacts .............................................................................5-3
Control
Accuracy .......................................................................2-1
Basic Operation .....................................................2-1, 2-7
Burden ..........................................................................2-1
Cable ...................................................................1-13, 7-3
Design ...........................................................................2-1
Features..............................................................2-1 to 2-3
Operating Modes ...................................................2-8, 3-9
Operation ......................................................................2-4
Programming ......................................................1-4 to 1-7
Removal ......................................................................1-11
Replacement ...............................................................1-11
Set-up .................................................................1-4 to 1-7
Specifications ................................................................2-1
Counter...............................................................................3-2
Current .....................................................................3-3 to 3-6
Current Circuit .............................................................1-22
Current Transformer .....................................1-17, 2-9, 3-9
Current Calibration ....................................................3-10, 6-5
Data Acquisition ........................................See Data Retrieval
Data Port ..........................................................2-3, 3-11, 4-12
Data Reader ..............................................................4-12, 7-1
Program ...............................................................4-12, 7-1
Data Retrieval...................................................................4-12
Data ...................................................................See Calendar
De-energizing ...................................................................1-12
Delta Connection.........................................................1-7, 2-8
Section-Page Number
Demand Time Interval ........................................................3-9
Diagnostics................................................................2-5, 3-16
Differential P.T....................................................................4-1
Digital Communications ................................4-11 to 4-12, 7-2
Elevating Structure .............................................................1-3
Error Codes .................................................................2-5, 9-2
External Features, VR-32 ......................................................2
External Source...........................................................1-3, 2-3
FAIL.............................................................................2-5, 4-3
Failure.......................................................................See FAIL
Fan Cooling ........................................................................7-3
Features, VR-32 Regulator....................................................1
Field Calibration ...............................................................1-10
Firmware Version .............................................................3-15
Fooler Voltage Scheme (VR) ...........................................4-11
Frequency ..........................................................................3-5
Front Panel
Features..............................................................2-2 to 2-3
Removal ......................................................................1-13
Replacement ...............................................................1-13
Function Codes
Descriptions ......................................................3-2 to 3-17
List .........................................................................3-1, 9-3
Function Key Method .........................................................2-6
Fuses ........................................................................1-20, 2-3
Handshaking ....................................................................3-12
Harmonics ..........................................................................3-5
Heater.................................................................................7-1
Holding Switch ..........................................................1-23, 2-4
I.D., Regulator ....................................................................3-9
Inspection
Periodic .......................................................................1-12
Pre-installation ..............................................................1-1
Receiving ......................................................................1-1
Installation ..........................................................................1-1
Interface
Physical.......................................................................4-11
Board ...................................................................4-12, 7-2
Interface Program .....................................................4-12, 7-2
Internal Construction ........................................................1-16
Internal Differential P.T.......................................................4-1
Internal Tap Terminals .....................................................1-20
Junction Box ...................................................................3, 6-3
Keypad ...............................................................................2-3 kVA ...................................................................3-4 to 3-5, 3-7 kW .....................................................................3-4 to 3-5, 3-7 kvar ..........................................................................3-4 to 3-6
LCD Annunciator ................................................................2-4
Limit Switches ...........................................................1-16, 6-4
Line Drop Compensation .....................................2-7, 3-3, 3-9
Line Sync Characters .......................................................3-10
Local Mode (VR) ................................................................4-9
Locked Forward Mode........................................................4-4
Locked Reverse Mode .......................................................4-5
Maintenance .....................................................................1-12
Manual Operation ...............................................................2-4
Master Reset ......................................................................3-8
Metering
Instantaneous ..............................................3-2 to 3-4, 4-1
Demand Metering ........................................3-5 to 3-7, 4-1
Profile Recorder ............................................................4-2
Metering Reset ...................................................................3-8
Motor ..................................................................................5-1
Motor Circuit .....................................................................1-22
Nameplate ...................................................................1-8, 1-9
Neutral Idle Mode ...............................................................4-6
Neutral Light .....................................................................1-11
Neutral Position ................................................................1-11
9-1
McGraw-Edison ® VR-32 Regulator and CL-5 Series Control
Section-Page Number
Oil
Characteristics ............................................................1-12
Maintenance .................................................................1-1
One-touch Method..............................................................2-6
Operation
Automatic ......................................................................2-4
Manual ..........................................................................2-4
Operational Check (Control & Regulator)...........................1-9
Overall P.T. Ratio...............................................1-21, 2-8, 3-9
Parameters .............................................See Function Codes
Password ...................................................See Security Code
Placing Into Service............................................................1-3
Position Indicator ..........................................1-15 to 1-16, 6-4
Potential Transformer Ratio .................See Overall P.T. Ratio
Power
Reverse Flow .....................................See Reverse Power
Power Circuit ........................................................1-18 to 1-19
Power Factor........................................................3-4, 3-5, 3-7
Profile Recorder ..............................................3-15, 4-2 to 4-3
Protection, System ...................................................2-4 to 2-5
Protocol ...................................................................3-11, 4-11
P.T. Ratio .............................................See Overall P.T. Ratio
Pulse Mode (VR) ..............................................................4-10
Ratings .............................................................................1-17
Ratio Correction
Transformer.................1-3, 1-18 to 1-20, 2-8, 4-3, 6-1 to 6-2
Reactive Bi-directional Mode..............................................4-7
Receiving............................................................................1-1
Regulation, Percent.....................................................3-4, 3-6
Regulator Configuration ..............................................2-8, 3-9
Remote (Latching) Mode (VR) ...........................................4-9
Removal from Service ......................................................1-11
Replacement Parts...................................................8-1 to 8-3
Reset ..................................................................................3-8
Retanking .........................................................................1-14
Reverse Idle Mode .............................................................4-5
Reverse Modes
Bi-directional .................................................................4-5
Co-generation Mode .....................................................4-7
Locked Forward ............................................................4-4
Reactive Bi-Directional..................................................4-7
Locked Reverse ............................................................4-5
Neutral Idle Mode..........................................................4-6
Reverse Idle Mode ........................................................4-5
Reverse Power ........................................1-7, 3-9 to 3-10, 4-3
Reversing Switch .....................................................5-1 to 5-2
SCADA ...................................................................4-9 to 4-12
Analog.............................................................4-11 to 4-12
Digital ..............................................................4-11 to 4-12
Relay ...........................................................................4-10
Schematics.............................................................6-7 to 6-11
Scroll Method .....................................................................2-6
Security
Codes ......................................................2-6, 3-16 to 3-17
Levels............................................................................3-1
Local Operator ............................................................4-12
Override ...............................................................2-6, 3-16
System ................................................................ 2-6, 4-12
Sequential Mode ................................................................2-8
Series Transformer Regulator ..........................................1-19
Service Parts ............................................................8-1 to 8-3
Settings Upload ................................................................4-12
Set Voltage .......................................................2-7, 3-2, 3-10
Source Voltage Calculator ..........................................3-8, 4-1
Spare Parts ..............................................................8-1 to 8-3
Storing ................................................................................1-1
Supervisory Control .............................................See SCADA
Surge Protection...............................................................1-15
Switches
Control (Auto/Remote-Off-Manual) ...............................2-3
Draghand Reset ............................................................2-3
Holding.................................................................1-23, 2-4
Limit .....................................................................1-16, 6-4
Manual Raise/Lower .....................................................2-3
Power (Internal-Off-External) ........................................2-3
Section-Page Number
Reversing ......................................................................5-1
Supervisory ..........................................................2-3, 4-12
System Connections ..........................................................1-2
System Line Voltage ..........................................1-21, 2-8, 3-9
System Protection ....................................................2-4 to 2-5
System Status Codes .......................................................3-16
Tap Changer ............................................................5-1 to 5-5
Contacts ........................................................................5-3
Direct-drive ............................................................5-2, 5-4
Drive Mechanisms ........................................................5-2
Motor .............................................................................5-1
Operation ............................................................5-1 to 5-5
Quik Drive ..............................................................5-2, 5-4
Reversing Switch ..........................................................5-1
Spring-drive...................................................................5-3
Tap Changing Inhibiting...........................See Reverse Power
Tap Connections ..............................................................1-21
Tap Position Indication.........................................3-3, 3-6, 4-3
Reset.............................................................................3-8
Temperature Range, Control..............................................2-1
Temperature Rise...............................................................1-1
Terminals
External Power..............................................................2-3
Voltmeter.......................................................................2-3
Threshold, Reverse ..........................................................3-11
Time ........................................................................See Clock
Time Delay .........................................................2-7, 3-2, 3-10
Time Integrating Mode .......................................................2-8
Transducer Connections ..................................................4-11
Transmit Enable Delay .....................................................3-13
Troubleshooting .....................................................6-1 to 6-11
Control ................................................................6-2 to 6-3
Junction Box .......................................................6-3 to 6-5
Position Indicator ..........................................................6-3
Regulator ............................................................6-1 to 6-3
Unloading ...........................................................................1-1
Untanking .........................................................................1-13
Voltage
Averaging Mode ............................................................2-8
Circuits ........................................................................1-19
Compensated................................................................3-3
Differential .....................................................................4-1
Limiting ................................................................3-15, 4-8
Load ................................................................... 3-5 to 3-7
Reduction ................................................3-13 to 3-14, 4-9
Set .........................................................................2-7, 3-2
Source...........................................................................3-3
System Line .................................................1-21, 2-8, 3-9
Voltage Calibration.............................................1-10, 3-9, 6-5
Watchdog Diagnostics ...................................See Diagnostics
Wiring Diagrams ...............................4-10 to 4-11, 6-5 to 6-11
TABLE 9-1
Security Codes
Security Level
2
3
0
1
Factory-set Security Code
No Code Required
1234
12121
32123
TABLE 9-2
Error Codes
Error Code Error Message
XX ERROR 1
XX ERROR 2
XX ERROR 3
XX ERROR 4
Input Value too Low
Input Value too High
Improper Security to Change
Invalid Security Code
Note: XX is the Function Code at which the error was made.
9-2
TABLE 9-3
CL-5 Series Regulator Control Function Codes
Function
Code
Function
Security
Level
Change/Reset
FORWARD CONTROL SETTINGS
0 Operation Counter (Q, R_, R
_
, 1, 2, 3, 4, 5, 6)* 3*
2 Bandwidth, volts
2
2
3
4
5
Time Delay, seconds
Line Compensation Resistance, volts
Line Compensation Reactance, volts
2
2
2
INSTANTANEOUS METERING
6 Load Voltage, Secondary
11
12
13
14
9
10
7
8
15
16
17
18
19
Source Voltage, Secondary
Compensated Voltage, Secondary
Load Current, Primary, amperes
Load Voltage, Primary, kV
Source Voltage, Primary, kV
Tap Position & Percent Regulation (TP, %)
Power Factor kVA Load kW Load kvar Load
Line Frequency
3
Voltage Harmonics (THD, 3, 5, 7, 9, 11, 13), percent
Current Harmonics (THD, 3, 5, 7, 9, 11, 13), percent
FORWARD DEMAND METERING
20 Load Voltage (H-D, T; L-D, T; P)
21
22
Compensated Voltage (H-D, T; L-D, T, P)
Load Current (H-D, T; L-D, T; P), amperes
23H
23L
24
25
Power Factor @ Max kVA Demand
Power Factor @ Min kVA Demand kVA Load (H-D, T; L-D, T; P) kW Load (H-D, T; L-D, T; P)
26
27
28
29 kvar Load (H-D, T; L-D, T; P)
Max Tap Pos & Max % Boost (TP-D, T; %)
Min Tap Pos & Max % Buck (TP-D, T; %)
Source Voltage **(H-D, T; L-D, T; P)
1
1
1
REVERSE DEMAND METERING
30
31
32
33H
33L
34
35
36
37
Load Voltage (H-D, T; L-D, T; P)
Compensated Voltage (H-D, T; L-D, T; P)
Load Current (H-D, T; L-D, T; P), amperes
Power Factor @ Max kVA Demand
Power Factor @ Min kVA Demand kVA Load (H-D, T; L-D, T; P) kW Load (H-D, T; L-D, T; P) kvar Load (H-D, T; L-D, T; P)
Source Voltage**(H-D, T; L-D, T; P)
CONFIGURATION
39 Source Voltage Calculation
0 = Off, 1 = On;
1 = Type A, 2 = Type B
40
41
42
Regulator Identification
Regulator Configuration
0 = Wye, 1 = Delta Lag, 2 = Delta Lead
Control Operating Modes
0 = Sequential, 1 = Time Integrating,
2 = Voltage Averaging
43
44
45
System Line Voltage, volts
Overall P.T. Ratio
C.T. Primary Rating, amps
1
1
1
1
1
1
MASTER METERING & TAP POSITION INDICATION RESET
38 Reset 1
2
2
2
2
2
2
2
1
1
1
1
1
Notes:
H-D, T = Highest (maximum) value since last reset, date & time
L-D, T = Lowest (minimum) value since last reset, date & time
P = Present value
THD = Total Harmonic Distortion
TPI = Tap position indication
Function
Code
Function
46
49
Demand Time Interval, minutes
Tap Changer Selection
0 = Quik Drive, 1 = Spring/Direct Drive
CALIBRATION
47 Voltage Calibration, volts
48 Current Calibration, amps
CALENDAR/CLOCK
50 Date & Time Set (D, T, 1, 2, 3, 4, 5, 6)
1 = Year, 2 = Month, 3 = Day,
4 = Hour, 5 = Minute, 6 = Second
REVERSE CONTROL SETTINGS
51 Set Voltage, volts
52
53
54
Bandwidth, volts
Time Delay, seconds
Line Compensation, Resistance, volts
55
56
57
Line Compensation, Reactance, volts
Reverse Sensing Mode
0 = Locked Forward, 1 = Locked Reverse
2 = Reverse Idle, 3 = Bi-Directional
4 = Neutral Idle, 5 = Co-Generation
6 = Reactive Bi-directional
Reverse Threshold %
COMMUNICATIONS
60 Channel 1 (Data Port) Baud Rate
61 Control Communication Protocol
XX.03 = Data 2179
62
63
Channel 1 (Data Port) Status
Channel 2 (Comm Port) Status
64
65
66
67
68
69
Control Communications Address
Channel 2 (Comm Port) Baud Rate
Comm Port Handshake Mode
Comm Port Resynch Time Chars.
Comm Port Transmit Enable Delay (On, Off)
Blocking Status
0 = Normal, 1 = Blocked
71
72
73
74
75
76
77
79
VOLTAGE REDUCTION
70 Voltage Reduction Mode
0 = Off, 1=Local/Digital Remote,
2 = Analog Remote (Latching), 3 = Pulse
10 = Off, 11 = Local/Digital Remote,
12 = Analog Remote (Latching), 13 = Pulse
(Utilizing 10-13 activates tap to neutral)**
% Voltage Reduction In Effect (Read Only)
Local Reduction %
Remote #1 %
Remote #2 %
Remote #3 %
# of Pulse Reduction Steps
% of Voltage Reduction Per Pulse Step
Soft ADD-AMP limits**
0 = Off, 1 = On;
High limit; Low limit;
VOLTAGE LIMITER
80 Voltage Limiting Mode
81
82
0 = Off, 1 = High Limit Only
2 = High and Low Limits
High Voltage Limit, volts
Low Voltage Limit, volts
Security
Level
Change/Reset
2
3
3
3
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Q = Quantity of operations since last change
R = Time of last counter change
* Change/Reset and Sub-function codes only on CL-5E control
** CL-5E only
See next page for more function codes
9-3
McGraw-Edison ® VR-32 Regulator and CL-5 Series Control
TABLE 9-3, Continued
CL-5 Series Regulator Control Function Codes
Function
Code
Function
METERING PROFILE RECORDER
85 Profile Period
(5, 10, 15, 30, 60, 90, 120 min.)**
1 = Parameter 1, 2 = Parameter 2,
3 = Parameter 3, 4 = Parameter 4,
5 = Data Retrieval Mode (0 = Off, 1 = On)
WATCHDOG DIAGNOSTICS
89
90
Firmware Version #
Number of Defaults
91
93
94
95
Self Test
Number of EEPROM Corrections
Number of Resets
System Status Code (Read Only)
0 All Systems Good
1 EEPROM Write Failure
Security
Level
Change/Reset
1
3
3
** CL-5E control only.
Function
Code
Function
2 EEPROM Erase Failure
3 Frequency Detection Failure
4 No Sampling Interrupt-Failure
5 Analog-To-Digital Converter-Failure
6 Invalid Critical Parameters-Failure
7 No Input Voltage Detected-Warning
8 No Output Voltage Detected-Failure
9 No Input & Output V Detected-Failure
10 TPT No Neutral Sync Signal-Warning
SECURITY ACCESS
92
96
Security Override (1 = Override 1, etc.)
Level 1 Security Code
97
98
99
Level 2 Security Code
Level 3 Security Code
ENTER SECURITY CODE
Security
Level
Change/Reset
3
3
3
3
9-4
McGraw-Edison ® VR-32 Regulator and CL-5 Series Control
For additional information, contact:
COOPER POWER SYSTEMS
DISTRIBUTION TRANSFORMERS
1900 EAST NORTH STREET
WAUKESHA, WI 53188-3899
(262) 547-1251
For service-related inquiries, e-mail us at: [email protected]
©2001 Cooper Industries, Inc.
ADD-AMP ™ is a registered trademark of Cooper Industries, Inc.
McGraw-Edison ® is a trademark of Cooper Industries, Inc.
P.O. Box 1640
Waukesha, WI 53187 http://www.cooperpower.com
ø