MODEL: TC10NM Temperature Controller TC10 Series RELATED PRODUCTS TEMPERATURE CONTROLLER

MODEL: TC10NM Temperature Controller TC10 Series RELATED PRODUCTS TEMPERATURE CONTROLLER
MODEL: TC10NM
Temperature Controller TC10 Series
TEMPERATURE CONTROLLER
(Modbus, size 48 x 96 mm)
Functions & Features
• One PID controller
• Universal input x 1 point, control output x 4 points,
discrete input x 2 points, clamp-on current sensor input x 1
point
• Universal input configurable to T/C, RTD, DC current or
voltage independently
• Discrete inputs usable to switch PID bank or operation
mode
• Control outputs configurable to MV, PV or alarm
• Clamp-on current sensor input enables to detect heater
wire break or over current
• Auto tuning function
48(1.89)
96(3.8)
108(4.25)
mm (inch)
MODEL: TC10NM–[1]–M2
ORDERING INFORMATION
• Code number: TC10NM-[1]-M2
Specify a code from below for [1].
(e.g. TC10NM-A-M2)
[1] CONTROL OUTPUT 1
A: 0 – 20 mA DC (Load resistance 500 Ω max.)
V: 0 – 10 V DC (Load resistance 2 kΩ max.)
P: 12 V pulse (Load resistance 600 Ω max.)
POWER INPUT
AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
http://www.m-system.co.jp/
RELATED PRODUCTS
• PC configurator software (model: TC10CFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
• Clamp-on current sensor (model: CLSE)
(Used for detecting the heater wire break)
GENERAL SPECIFICATIONS
Construction: Panel flush mounting
Degree of protection: IP65; applicable to the front panel of
the unit with single mounting according to the specified
panel cutout
Configuration jack: 2.5 dia. miniature jack connector;
RS-232-C level (bottom of the unit)
Connection: M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal: Refer to the drawing at the end of the
section.
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size: 0.25 to 1.65 mm2 (AWG 22 to 16)
Screw terminal: Nickel-plated steel
Isolation: Pv1 to CT1 to Di1 or Di2 to MV1 to MV2 to Do1 or
Do2 to Modbus to power
CT Input waveform
RMS sensing: Up to 15 % of 3rd harmonic content
Control mode: Standard PID, heating and cooling control
(ON/OFF, PID)
Proportional band (P): 0.1 to 3200.0 (temperature unit)
Integral time (I): 0 to 3999 sec.
Derivative time (D): 0.0 to 999.9 sec.
Auto-tuning: Limit cycle method
Alarm: Deviation high & low, absolute high & low, etc.
Sampling cycle: 100 msec.
Control cycle: 1.0 to 99.9 sec.
(100 msec. fixed for MV output 0 - 20 mA DC
and 0 - 10 V DC)
MV output range: -5 - +105 % for output scale
Parameters: Stored in non-volatile memory; write/erase
cycle endurance: less than 1 000 000
Parameter setting: With front panel operation buttons or PC
configurator software (model: TC10CFG)
• Universal input
• Burnout on/off
• Control output
• Bank
• Event input
• CT input
• Auto-tuning
TC10NM SPECIFICATIONS
ES-9582 Rev.0 Page 1/7
MODEL: TC10NM
Refer to the instruction manual for detail.
■Recommended solderless terminal
INPUT SPECIFICATIONS
6 (.24) max
3.3 (.13) max
mm (inch)
MODBUS COMMUNICATION
Communication: Half-duplex, asynchronous, no procedure
Standard: Conforms to RS-485
Transmission distance: 500 meters max.
Transmission media: Shielded twisted-pair cable
(CPEV-S 0.9 dia.)
Node adress: 1 to 247
Data mode: RTU (Binary)
Parity: None, even or odd
Baud rate: 4800, 9600, 19.2 k, 38.4 k, 57.6 k (bps)
Stop bit: 1 or 2
Node adress, parity, baud rate setting: With front panel
operation buttons or PC configurator software (model:
TC10CFG)
Terminating resistor: Built-in (Enable by shorting between
pin 3 and 4)
DISPLAY
PV display: 5 digits 7-segment green LED, 10.2 mm (.40”)
height
SP display: 5 digits 7-segment red LED, 8.2 mm (.32”)
height, switchable to MV display
Display range: -32000 to 32000
Decimal point position: 10–1 to 10–4 or none
Zero indication: Higher-digit zeros are suppressed.
Loop status indicators
Bank1: Green LED turns on when bank 1 chosen
Bank2: Green LED turns on when bank 2 chosen
Bank3: Green LED turns on when bank 3 chosen
Bank4: Green LED turns on when bank 4 chosen
Alarm1: Red LED turns on at alarm 1
Alarm2: Red LED turns on at alarm 2
Alarm3: Red LED turns on at alarm 3
Alarm4: Red LED turns on while setting is saving to the
non-volatile memory.
Run: Green LED turns on while loop is in operation.
Man: Green LED turns on during manual mode
Local: Unused, off
At: Green LED turns on during auto-tuning
Out1: Green LED turns on when MV1 output
Out2: Green LED turns on when MV2 output
http://www.m-system.co.jp/
■ Universal input (Pv1)
For type and range configuration, refer to the instruction
manual.
DC Current:
Input range: 0 - 20 mA DC
Input resistance: 49.9 Ω resistor incorporated
• DC voltage input
Input resistance: ≥ 10 kΩ (-1000 to +1000 mV DC)
Input resistance: ≥ 1 MΩ (-10 to + 10 V DC)
• Thermocouple
Input resistance: ≥ 10 kΩ
Burnout sensing: ≤ 4 μA
• RTD (2-wire or 3-wire)
Excitation: ≤ 0.33 mA
Allowable leadwire resistance: 20 Ω per wire
• Resistor (2-wire or 3-wire)
Excitation: ≤ 0.33 mA
Allowable leadwire resistance: 20 Ω per wire
• Potentiometer
Excitation: ≤ 0.33 mA
Input range: 0 to 4000 Ω
Allowable leadwire resistance: 20 Ω per wire
■ Clamp-on current sensor (CT1)
(Sensor model No.: AC input)
CLSE-R5: 0 – 5 A
CLSE-05: 0 – 50 A
CLSE-10: 0 – 100 A
CLSE-20: 0 – 200 A
CLSE-40: 0 – 400 A
CLSE-60: 0 – 600 A
Frequency: 50 / 60 Hz
Operational range: 0 – 120 % of rating
Overload capacity:
CLSE-R5: 10 A continuous
CLSE-05: 60 A continuous
CLSE-10: 120 A continuous
CLSE-20: 240 A continuous
CLSE-40: 480 A continuous
CLSE-60: 720 A continuous
Be sure that the input voltage is of 480 V or less.
■ Discrete Input (Di1, Di2)
Contact rating: 3.3 V @ 0.33 mA
Detection levels:
≤ 1.6 kΩ / 0.5 V at close
≥ 30 kΩ / 2.5 V at open
OUTPUT SPECIFICATIONS
Four control outputs are configurable to Mv, Ao or Do.
■ Control Output (Mv1, Mv2)
Specify the type of output with the code number.
■ DC Current: 0 – 20 mA DC
TC10NM SPECIFICATIONS
ES-9582 Rev.0 Page 2/7
MODEL: TC10NM
Operational range: 0 – 23 mA DC
Load resistance: ≤ 500 Ω
■ DC Voltage: 0 – 10 V DC
Operational range: 0 - +11.5 V DC
Load resistance: ≥ 2 kΩ
■ Voltage Pulse
Maximum frequency: 1 Hz
Minimum pulse width: 1 msec.
Hi level: 12 V ±15 %
Lo level: ≤ 0.5 V
Load resistance: 600 Ω min.
■ Control Output (Do1, Do2)
• Open collector
Maximum frequency: 1 Hz
Minimum pulse width: 1 msec.
Output rating: 50 V DC 100 mA (resistive load)
Saturation voltage: 0.5 V DC
STANDARDS & APPROVALS
CE conformity:
EMC Directive (2004/108/EC)
EMI EN 61000-6-4: 2007/A1: 2011
EMS EN 61000-6-2: 2005
Low Voltage Directive (2006/95/EC)
EN 61010-1: 2010
Installation Category II
Pollution Degree 2
Input or output or Modbus to power – Reinforced insulation
(300 V)
Input to output to Modbus – Basic insulation (300 V)
INSTALLATION
Power Consumption
•AC:
Approx. 6 VA at 100 V
Approx. 7 VA at 200 V
Approx. 8 VA at 240 V
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 5 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Panel flush mounting
Weight: 450 g (0.99 lb)
PERFORMANCE in percentage of span
Accuracy
• Pv1: Refer to "Input type, range & conversion accuracy"
section.
• CT1: ±2 % (sensor error margin not included)
• MV1 or MV2: ±0.5 % (added to the input accuracy)
Cold junction compensation error (thermocouple input):
±2.0°C at -10 – 55°C (±3.6°F at 14 – 131°F)
CJC sensor is adjacently attached to the input terminals.
Temp. coefficient
• Pv1: ±0.03 %/°C (± 0.02 %/°F)
• CT1: ±0.03 %/°C (± 0.02 %/°F)
Response time
• CT1: ≤ 2 sec. (0 – 90 %)
• Mv1 or Mv2: ≤ 1 sec. (0 – 90 %, DC output)
Burnout response (thermocouple, RTD, resistor,
potentiometer input): ≤ 10 s
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (Pv1 to CT1 to Di1
or Di2 to MV1 to MV2 to Do1 or Do2 to Modbus to power to
ground)
http://www.m-system.co.jp/
TC10NM SPECIFICATIONS
ES-9582 Rev.0 Page 3/7
MODEL: TC10NM
INPUT TYPE, RANGE & CONVERSION ACCURACY
INPUT TYPE
INPUT RANGE
0 to 20mA DC
-1000 to +1000mV DC
ACCURACY
±20μA
When max. range*2 is ≥60mV ±20μV
When max. range*2 is ≤120mV ±30μV
When max. range*2 is ≥120mV ±200μV
-10 to +10V DC
±10mV ±0.1%
POTENTIOMETER
Total resistance up to 4000Ω*3
±0.1Ω or ±0.1%, whichever is greater
RESISTOR
0 to 4000Ω
±0.1Ω or ±0.1%, whichever is greater
°C
゜F
Thermocouple
INPUT RANGE ACCURACY*1 CONFORMANCE RANGE INPUT RANGE ACCURACY*1 CONFORMANCE RANGE
(PR)
0 to 1760
±1.80
0 to 1760
32 to 3200
±3.24
32 to 3200
K (CA)
-270 to +1370
±0.40
-150 to +1370
-454 to +2498
±0.72
-238 to +2498
E (CRC)
-270 to +1000
±0.60
-170 to +1000
-454 to +1832
±1.08
-274 to +1832
J (IC)
-210 to +1200
±0.70
-180 to +1200
-346 to +2192
±1.26
-292 to +2192
T (CC)
-270 to +400
±0.50
-170 to +400
-454 to +752
±0.90
-274 to +752
B (RH)
100 to 1820
±2.00
400 to 1760
212 to 3308
±3.60
752 to 3200
R
-50 to +1760
±1.00
200 to 1760
-58 to +3200
±1.80
392 to 3200
S
-50 to +1760
±1.00
0 to 1760
-58 to +3200
±1.80
32 to 3200
C (WRe 5-26)
0 to 2315
±1.00
0 to 2315
32 to 4199
±1.80
32 to 4199
N
-270 to +1300
±0.50
-130 to +1300
-454 to +2372
±0.90
-202 to +2372
U
-200 to +600
±0.50
-200 to +600
-328 to +1112
±0.90
-328 to +1112
L
-200 to +900
±0.30
-200 to +900
-328 to +1652
±0.54
-328 to +1652
P (Platinel ll)
0 to 1395
±0.30
0 to 1395
32 to 2543
±0.54
32 to 2543
°C
F
゜
RTD
INPUT RANGE
ACCURACY
INPUT RANGE
ACCURACY
Pt 100 (JIS ’97, IEC)
-200 to +850
±0.40
-328 to +1562
±0.72
Pt 500
-200 to +850
±0.40
-328 to +1562
±0.72
Pt 1000
-200 to +850
±0.40
-328 to +1562
±0.72
Pt 50Ω (JIS‘81)
-200 to +649
±0.60
-328 to +1200
±1.08
JPt 100 (JIS’89)
-200 to +510
±0.40
-328 to +950
±0.72
Ni 508.4Ω
-50 to +200
±0.60
-58 to +392
±1.08
Cu 10 (25℃)
-50 to +250
±2.00
-58 to +482
±3.60
*1.Thermocouple: Add 2.0°C of cold-junction-compensation error.
*2. Max. range: absolute range (greater of 0% and 100% range values), whichever is greater.
*3. Refer to the operating manual for details.
DC CURRENT
DC VOLTAGE
EXTERNAL VIEW
■ FRONT VIEW
■ BOTTOM VIEW
Loop
status indicators
PV Display
SP/MV
DisplayJack
Configuration
SP/MV
Esc
Configuration Jack
Operation Buttons
http://www.m-system.co.jp/
TC10NM SPECIFICATIONS
ES-9582 Rev.0 Page 4/7
MODEL: TC10NM
CONNECTION DIAGRAMS
■ MASTER CONNECTION
TERMINATOR
TC10NM
DA
DB
HOST PC
TX+/RX+
TX–/RX–
SG
RX+
RX–
TC10NM
DA
DB
*1
NO.
ID
FUNCTION
4
5
DA
DB
DA
DB
*1. For using internal terminator, short-accross terminals 3 and 4.
DIMENSIONS unit: mm (inch)
4 – M3 Screw
20 – M3 Terminal Screw
Terminal Cover
1
11
2
12
3
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
92 (3.62)
Mounting Bracket
96 (3.78)
103(4.06)
Watertight Sealing
2 (.08)
48(1.89)
8 (.31)
98 (3.86)
45(1.77)
100 (3.93)
■ PANEL CUTOUT unit: mm (inch)
Pitch ≥147 (5.79)
92
+0.8
−0
45 +0.8
−0
Pitch ≥75 (2.95)
Mounting bracket: 0.5 – 10 (0.02 to 0.39)
http://www.m-system.co.jp/
TC10NM SPECIFICATIONS
ES-9582 Rev.0 Page 5/7
MODEL: TC10NM
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Indicator LEDs
...
Isolation
3
11
Pv1
UNIVERSAL INPUT
12
TERMINATOR
Isolation
Comm.
Circuit
A/D
Converter
Output
Circuit
Isolation
Control
Circuit
14
15
MODBUS
5 DB
Isolation
13
CT 1
4 DA
16 +
Mv1
17 –
Isolation
Output
Circuit
A/D
Converter
6 +
Mv2
7 –
Isolation
Isolation
18 +
8
9
Di 1
Di 2
Output
Circuit
Input
Circuit
19 +
Do1
Do2
20 –
Display/
Setting
10
1 U
POWER
2 V
CONFIG.JACK
■ UNIVERSAL INPUT CONNECTION (Pv1) e.g.
■ CT1 CONNECTION e.g.
• DC Current (0 – 20mA DC)
• DC Voltage (-1000 – +1000mV DC)
• DC Voltage (-10 – +10V DC)
• Clamp-on Current Sensor
16 +
Mv1
+ 11
k
12
l
INPUT
■ CONTROL OUTPUT 1 CONNECTION e.g.
14
15
– 13
17 –
■ CONTROL OUTPUT 2 CONNECTION e.g.
Load Side
• Thermocouple
–
+
6 +
■ DISCRETE INPUT CONNECTION e.g.
• Mechanical Contact
–
11
CJC
SENSOR
12
+
comp. leadwire
Mv2
7 –
Di 1
8
Di2
13
■ CONTROL OUTPUT 3 & 4 CONNECTION e.g.
Do1
9
18
10
• RTD/Resistor (3-wire)
A
11
B
12
B
13
• Open Collector
+
Di 1
Di2
+
–
Do2
19
+
20
–
+
–
8
9
10
• RTD/Resistor (2-wire)
A
11
B
12
13
• Potentiometer
MAX
MIN
+ 11
– 12
13
http://www.m-system.co.jp/
TC10NM SPECIFICATIONS
ES-9582 Rev.0 Page 6/7
MODEL: TC10NM
Specifications are subject to change without notice.
http://www.m-system.co.jp/
TC10NM SPECIFICATIONS
ES-9582 Rev.0 Page 7/7
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement