Data Aire | DAFC-17 | DB-AIRE - Dunham

FORM NO: MS0701A
DB-AIRE
PRECISION ENVIRONMENTAL CONTROL UNIT
DB-TEMP SYSTEMS
DB-AIRE SYSTEMS
50/60 Hz
DB-AIRE
Precision Environmental Control Systems For Computer Rooms.
DB-AIRE SYSTEMS
State-of-the-art design with microprocessor based liquid crystal display panels,
dual refrigeration circuits, tubular steel frames, large face area A-frame coils, the
DB-Aire series offers a wide range of capacities and cooling mediums in compact,
attractive, furniture grade cabinets. The units can be configured upflow or
downflow.
The DBA (Air Cooled) system features efficiency in eight sizes. Available in
32-91 kW (9-26 tons) nominal capacities.
The DBW/ G (Water/ Glycol) system features units in eight sizes. Available in
32-91 kW (9-26 tons) nominal capacities.
The DBC (Chilled Water) system offers a large faced area coils in the industry's
most compact cabinet available in 25-106 kW (7-30 tons) nominal capacities.
DB-TEMP SYSTEMS
The single refrigerant circuit DB-Temp has been designed to meet the demanding
requirements of the most advanced computer room, yet is sized to provide
complete economical protection for small applications.
Microprocessor based control with liquid crystal display monitoring plus a full
complement of alarms are featured.
The small DB-Temp range is available in 7, 11, 14, 18 kW (2, 3, 4, and 5 ton)
capacities, in air cooled, water/ glycol cooled, and chilled water models. Both
upflow or downflow configurations are available.
The large DB-Temp range of 25, 32, 39, 46 kW (7, 9, 11, 13 ton) air cooled,
water/glycol cooled precision environmental control systems is designed for data
centers and telecommunications room applications. The units can be configured
upflow or downflow.
This concept allows multiple units to be joined together or placed apart (any
combination of capacities). Controls prevent conflicting operations.
GENERAL INFORMATION
DB-Aire units are precision environmental
control systems that bring a new standard of
flexibility and reliable performance to the
computer room. Because room requirements
differ, DB-Aire offers a wide range of sizes
and styles.
DB-TEMP SYSTEMS
7, 11, 14 and 18 kW (2, 3, 4, and 5 ton)
nominal capacities in air-cooled, water/glycol
cooled, or chilled water models.
25, 32, 39 and 46 kW (7, 9, 11, and 13 ton)
nominal capacities in air or water/glycol
cooled models.
DB-Temp utilises a single compressor circuit.
DB-AIRE SYSTEMS
Dual compressor units in 32 through 91 kW
(9 through 26 ton) nominal capacities
available in air cooled or water/ glycol cooled
models.
Chilled water models in 25 through 106 kW
(7 through 30 ton) nominal capacities.
COMPUTER COMFORT
Computer rooms require air which is clean
and properly distributed with precisely
controlled temperatures and humidity.
Building HVAC systems simply are not
designed to meet these demands. But, DBAire units easily accomplish these goals with
top-rated efficiency, 24 hours per day 7 days
a week! DB-Aire units have been designed to
meet the demanding requirements of the most
advanced computer room.
Although building HVAC systems cool your
staff, they fall short of your computer's comfort
need. And they are unable to provide the
close humidity control required in a modern
data processing centre.
DESIGN FEATURES
Each unit is a complete environmental control
system, factory wired, tested, and specifically
designed to provide temperature, humidity,
and dust control for computer room or telecommunications installations.
A specially designed compact tubular steel
frame allows for a minimum space
requirement in your computer room for both
upflow and downflow units while still providing
excellent serviceability. All parts are easily
accessible.
The DB-Processor, a microprocessor based
control displays temperature and humidity on
liquid crystal display (LCD). A comprehensive
diagnostic routine is standard.
HIGH PERFORMANCE LOW COST
DB-Aire’s high-tech, furniture look is clue to its
high performance but belies its more than
competitive price. Every DB-Aire unit comes
with a commitment to excellence as standard
equipment.
TABLE OF CONTENTS
Description
Page
General Information .........................................................3
DB- Aire Monitoring/Control............................................4
Network Monitoring (Optional)......................................7
DB-Temp Design Features .............................................8
DB-Temp Systems............................................................9
Performance Data ..........................................................9
Electrical Data.............................................................12
Dimensional Data ........................................................13
DB- Aire Design Features ..............................................15
DB- Aire Systems.............................................................16
Performance Data ........................................................17
Electrical Data.............................................................19
Dimensional Data ........................................................20
Chilled Water Design Features....................................22
Description
Page
DB-Temp Chilled Water Systems............................... 23
Performance Data........................................................ 23
Electrical Data............................................................. 25
DB- Aire Chilled Water Systems.................................. 26
Performance Data........................................................ 26
Electrical Data............................................................. 28
DB-Temp/DB- Aire Chilled Water Systems............... 29
Dimensional Data........................................................ 29
Remote Air-Cooled Condensers ................................ 32
Technical Data ............................................................ 32
Dry-Air Coolers ............................................................... 33
Technical Data ............................................................ 33
Remove Heat Exchangers............................................ 34
Options and Accessories............................................. 35
Sample Nomenclature................................................... 36
DB-AIRE MONITORING/ CONTROL
The heart of the Environmental Control System
is the microprocessor based DB-Alarm
Proccessor. The liquid crystal display not only
monitors your data center's temperature,
humidity, airflow, and cleanliness, but also
provides component run times, alarm history
and an automatic self-test of the microprocessor
on system start-up. Multiple messages will be
displayed by automatically scrolling from each
message to the next. All of these messages are
spelled out in English language on the liquid
crystal display (LCD). The LCD has 20
characters on 4 rows, high density and backlit.
Multiple alarms will be displayed sequentially in
order of occurrence.
DB-AIRE
STANDARD:
PANEL
MOUNTING
LCD
DISPLAY
The range of user interfaces has two further wall
mounting versions with the same electrical
features as the previous models. The 4x20 LCD
display (with 5mm high characters) of the
available models is back-lit as standard.
Power Supply: from the power board (ρCO)
through the telephone cable
(code S90CONN00*)
Std. Display: LCD 4 x20 (character height =
5mm)
Keypad:
5 external mechanical buttons.
10 mechanical buttons protected
by polycarbonate.
Indicator Leds: 10
OPERATION
Push button control switches allow unit on/off
operation; menu selection for programming,
operational information, diagnostics, and
historical data. A password feature prevents
unauthorized access; separate manual override
switches are provided for fan motor, cool 1, cool
2, heat 1, and humidification operations. With
manual override your DB-Aire unit will never be
down as a result of a control problem - just
activate the appropriate switch and you have
ability to override controls. Another feature is
that all menu programmed information for basic
system operation and alarm parameters is
stored in a non-volatile EEPROM. All historical
information is protected by battery back-up.
PROGRAMMABLE
MONITORING
FUNCTIONS/
The user friendly MENU SELECTION switch
permits step-by-step programming and display
of the following functions:
Ø Temperature Set Point 18 to 29°C (65°F85°F)
Ø Temperature Sensitivity 0.5 to 2.7°C (1°F5 °F)
Ø Humidity Set Point (40% - 60% RH)
Ø Humidity Sensitivity (1% - 10% RH)
Ø Temperature Alarm Points
Ø Humidity Alarm Points
Ø Unit Start Time Delay
Normal functions are monitored and displayed
on the LCD and include, in addition to the above
set points, the following:
Ø Current Temperature (deg C or deg F)
Ø Current Humidity (%RH)
Ø Cooling Stages 1, 2 as applicable
Ø Heating Stages 1, 2, 3
Ø Humidification
Ø Dehumidification
Ø Current percent of capacity and the average
percent of capacity for the last hour of
operation for compressors, humidification,
dehumidification, reheat, and chilled water.
PROGRAMMING
KEY
The programming keys
for the DB-Aire series
controllers provide easy
software updates during
both end-of production
testing and maintenance
procedures.
DB-AIRE MONITORING/ CONTROL
ALARMS
Alarm conditions are also monitored on the LCD
and are enunciated by an audible alarm. The
alarm silence button will quiet the audible alarm
but the display will continue to indicate the alarm
condition until the problem is corrected.
The following alarms are standard:
Ø Compressor High/Low Pressure
Ø High and Low Temperature
Ø High And Low Humidity
Ø No Airflow
Ø Filters Blocked
Ø Humidifier Failure
Ø Manual Override
Ø Power Failure Restart
Ø Compressor Short Cycle
Ø Temperature Sensor Error
Ø Humidity Sensor Error
Ø Firestat Tripped
Ø Local Alarm (Programmable)
Ø Maintenance Due
The local alarm may be programmed to display
any one of the following (optional sensors
required): under the floor water detection, no
water flow, smoke alarm, fan motor over load,
stand by pump on alarm etc. In addition,
incomparable control settings will be identified
on the LCD.
HISTORICAL DATA
In order to facilitate maintenance and service,
component run times for fan motor, compressor
operation reheat stages, humidification and
dehumidification can be recalled and displayed
on the LCD. The current temperature and
humidity, with the minimum and maximum
readings for the last 24 hours of operation, can
be recalled and displayed. The last ten alarms
and hours since occurrence can also be recalled
and displayed. The historical data base is
maintained by battery back-up should power fail.
DB-AIRE MEMORY BOX (Optional)
The high memory capacity (up to 4 Mbyte) and
real time clock mean that the DB-Processor can
act as a true black box recorder, saving all the
alarm situations, the values of the sensors, and
the status of the controlled
devices. The black box
data recorded can be
transferred
to
the
programming key or to a
PC, including via modem.
DIAGNOSTICS
Automatic and manual diagnostic sequences
simplify troubleshooting.
DB-AIRE
PANEL
MOUNTED
GRAPHIC DISPLAY (Optional)
The terminal unit with
back-lit graphic display for
panel
mounting
is
provided with a longer
visual display and more
intense back lighting in
order to allow applications
in different areas. This
terminal unit can be
connected to the local network that allows the
terminal to display (and log through the
respective optional card) the information coming
from the other DB-Aire Units of the network. The
graphic terminal can also be programmed by
means of the DB-ARD system in exactly the
same way as with the control applications for
the DB-Aire. The user who is already
accustomed to the environment will meet no
difficulty in customizing the application on such
a device. The following possibilities are
available to the user: configurability of the
character fonts both with regard to the style and
size. It is thus possible to represent every
alphabet (Chinese, Arabic, etc)
Ø Creation of graphic objects, both static and in
motion, for a more immediate display of the
information (alarms, energized devices, etc)
Ø Display of the graph of the acquired data so
as to obtain, for instance, the temperature
plot in a selectable interval of time
Ø Opportunity to manage a serial printer so as
to print, for instance, the detected alarms
Ø Adjustable brightness.
DB-AIRE MONITORING/ CONTROL
DB PROCESSOR
COMMUNICATION INTERFACES
(Optional)
The DB series of controllers are LonWorks®
compatible, using a special serial board.
Electrical supported standards: RS485 and
FTT10.
Below are the available communication interface
features of the DB-Alarm processor:
BMS interface
The DB controllers
can be connected to
the BMS in the
following ways:
Ø Directly, without
using a gateway,
thanks to the ability of the DB series
controllers to select the protocol used,
Ø Using a gateway that converts the DB
proprietary protocol used by the BMS,
Ø Integrating the driver for the management of
the DB proprietary protocol into the BMS.
The following protocol are used by the DB
controllers to ensure connectability to the other
systems:
This is the protocol designated in 1995 by
ASHRAE (American Society of Heating,
Refrigerating and Air-Conditioning Engineers)
as the organisation’s official protocol.
DB provides a gateway through which all DB
controllers can interface to BACnet™ systems.
Type of supported protocol: BACnet™, PointTo-Point and RS232 communication standard.
THIRD PARTY PROTOCOLS
DB controllers can provide numerous gateways
for interfacing its controls to proprietary
supervisory systems.
Modbus®
Introduced in the 1970s and now one of the
most widely-used BMS protocols.
The DB series controllers can communicate
directly in Modbus protocol®.
Like all DB controllers, it can also be connected
to a Modbus® system using a gateway.
Type of supported protocol: Modbus® slave,
RTU mode; RS485 and RS232 communication
standard.
Trend is a building Automation System very
widespread in the Anglo-Saxon countries and in
general in Europe.
The DB-Aire controller is TREND compatible,
through the proper serial card. TREND deals
with the configuration and the supply of the
interface card. Trend can be contacted directly
on Tel. +44(0)1403211888.
SNMP
With millions of devices
installed world-wide, the
LonWorks®
system
developed by Echelon®,
is one of the dominant
solutions on the market
for the automation and control of industries,
offices, homes and transport.
SNMP (Simple Network Management Protocol)
is a protocol for the management of TCP/IP
networks (the Internet protocol), established in
1988 based on the specifications of the IAB
(Internet Administration Board), the body that
supervises the internet protocol.
All DB controllers can be connected to a 10
Mbps Ethernet™ network via gateway or
PlanVisor, and communicate with systems that
use the SNMP Protocol.
DB-AIRE MONITORING/ CONTROL
Metasys®
is
the
building
automation system developed by
Johnson Controls.
Johnson itself handles the
implementation of the software to control the
interfaced devices into its system.
TCP/IP Gateway
Thanks to this gateway with “WEB server”
capability, all DB-Aire units can now be
connected to a 10Mbps Ethernet™ local
network.
The following functions are therefore possible:
DB-Aire
can
provide
developers
and
system
integrators
with
DLLs
(Dynamic link Libraries) for 16and
32-bit
Windows ®
applications.
Technically, a DLL is a compiled file that
contains a series of functions for use by any
other server process. In particular, the DB-Aire
DLLs contain the software routines that allow
the integration of communication with all DBAire instruments into the application, without
needing to know the used protocol.
Direct modem
All
the
DB-Aire
controllers can be
connected directly to
a traditional or GSM
modem.
They can thus be controlled directly by remote
stations, without requiring the use of a gateway
or intermediate system.
Ø Display the parameters and the data from the
controller using an Internet browser on any
PC connected to the local network or Internet
Ø Send the data to a supervisor PC connected
to the network that is able to handle the
SNMP protocol.
SMS, short message service
Dunham-Bush has payed great attention to
fitting the DB controllers with the ability to
communicate important information directly by
SMS message.
In fact, this is the best communication system
for sending data wherever and promptly.
By simply connecting a GSM modem, the DB
series controllers can not only send alarms and
information, but also receive commands via
SMS that service personnel can use to reset
any alarm or perform the necessary operations,
without having to travel to the installation.
NETWORK MONITORING (OPTIONAL)
NETWATCH
For smaller systems with
the same management
and control requirements
as larger installations,
NetWatch offers the
complete and integrated
solution for all monitoring
and remote management needs. NetWatch, a
versatile data recorder for the controllers
connected in a supervisory network, is also:
Ø an excellent monitoring system. In the event
of alarms, it can send faxes, SMS messages,
call a remote security center, etc.,
Ø an exceptional instrument for remote control.
Using a traditional or GSM modem, it can
display and modify all of the parameters in the
system. Optional 110V or 230V 50/60Hz.
NetVisor
This is the latest generation “WEB based”
supervisory software. It allows refrigeration and
air-conditioning systems to be monitored and
controlled using a simple Internet browser: the
pages displayed on the PC are in HTML format,
the language of the worldwide web. NetVisor is
designed to communicate externally with more
than one protocol.
DB-TEMP DESIGN FEATURES
DB-TEMP MODELS
7-46 KW
2-13 TONS
AIR COOLED
WATER/GLYCOL COOLED
FRAME AND CABINET
The heliarc welded steel frame provides for
maximum strength and ease of access. Side
and front panels can be easily opened and
removed with quarter-turn fasteners allowing full
access to all unit components. All panels include
25mm (1 inch) thick, 1-1/2 lb density insulation
for protection and sound attenuation. DB-Aire's
unique frame design allows for your selection of
either downflow or upflow air patterns in the
same compact dimensions.
COIL SECTION
Designed for draw through application with large
face areas for low velocity air to reduce
turbulence and provide greater efficiency in the
cooling and dehumidification process.
FAN SECTION
The centrifugal forward-curved, double-width,
double-inlet blower configuration is engineered
for quiet, reliable operation. The blowers are
AMCA certified and factory certified dynamically
balanced. The draw through design insures
even air distribution across the coil, low internal
cabinet pressure losses, and static sealing of
the filter section. The fan motor is totally
enclosed and is mounted on an adjustable slide
base.
reheat coils provide ample capacity to maintain
room dry bulb conditions during a system call for
dehumidification. Three equal stages give a
more accurate controlled response to the
requirements of the computer room. The heating
elements are protected by thermal safety
switches. The three stages of reheat create a
noticeable lowering of energy use.
HUMIDIFICATION (OPTIONAL)
The disposable cartridge electric stream
generator humidifier provides humidification
down stream of the cooling coil. The humidifier
is designed to allow all units at any voltage to
produce full rated steam output at an optimum
low water level.
DB-AIRE UMID
INTERFACE
The DB-Aire Umid
interface allows the
control of humidifiers
directly from the DBAire microprocessor
controller.
Steam Generator Humidifier
FILTERS
Computer room air cleanliness is enhanced by
standard 50 mm (2 inch) deep pleated 30
percent efficient filters (based on ASHRAE 5276) which can be easily changed by opening the
front panel for the 2-5 tons models. The DBTemp 7-13 tons models use standard 100 mm
(4 inch) deep pleated 30 percent efficient filters
(based on ASHRAE 52-76)
ELECTRICAL REHEAT
The three stage stainless steel finned tubular
COMPRESSORIZED SYSTEM
The single stage refrigeration circuit includes a
high efficiency and quiet scroll compressor. The
scroll compressor has a high EER, low
DB-TEMP DESIGN FEATURES
sound power level and is highly reliable. The
high efficiency is due to the controlled orbit with
floating seals and advanced scroll geometry
design. There is no contact of the mechanical
parts in the scroll design which eliminates
mechanical wear and tear. The motor is 100%
cooled by suction gas. A check valve is located
directly above the fixed scroll discharge port.
This prevents the compressor from running
backwards after the power has been switched
off (i.e. no rattling and no shutdown noises). The
motor is fitted with an internal thermal overload
protection against maximum operating overload
and loss of refrigerant charge. The refrigeration
circuit includes filter drier, sight glass, adjustable
expansion valve, low pressure override timer,
manual reset high pressure control, short-cycle
timer and rotalock service valves.
Air Cooled Systems- A wide range of sizes of
remote mounted air-cooled condensers are
available from DB-Aire in vertical discharge.
Condensers are manufactured by DB-Aire and
include circuits sized to match the heat rejection
of the corresponding compressor in the DB-
Temp. The industrial duty design includes
galvanized corrosion resistant housings, high
efficiency aluminium finned (optional copper fins
available) copper tube coils; coated fan guard;
energy efficient thermally protected motors
integral factory wired and tested control panel.
Water/Glycol Cooled System - Includes unit
mounted condensers for providing the required
capacity for heat rejection with minimum
water/glycol flow and low total pressure drop.
Dry-Air Cooler For Glycol Systems - A wide
range of sizes of remote mounted dry-air
coolers are available from DB-Aire in vertical
discharge and direct drive. Dry-air coolers are
manufactured by DB-Aire and are sized to
match the heat rejection of the corresponding
DB-Temp unit. The industrial duty design
includes galvanised corrosion resistant housing,
high efficiency aluminium finned (optional
copper fins available) copper tube coils; coated
fan guards; energy efficient, thermally protected
motors and fan cycling controls with integral
factory wired and tested control panel.
DB-TEMP SYSTEMS
AIR COOLED/ GLYCOL COOLED PERFORMANCE DATA
PERFORMANCE AT 35°C (95°F) AMBIENT WITH SPECIFIED CONDENSER/DRY-AIR COOLER
NET CAPACITY KW AT STANDARD AIRFLOW
MODEL
DBTAD/U-02 DBTAD/U-03
DBTGD/U-02 DBTGD/U-03
TOTAL SENS. TOTAL
DBTAD/U-04
DBTGD/U-04
DBTAD/U-05
DBTGD/U-05
SENS. TOTAL SENS. TOTAL
DBTAD/U-07 DBTAD/U-09 DBTAD/U-11
DBTGD/U-07 DBTGD/U-09 DBTGD/U-11
SENS. TOTAL SENS. TOTAL SENS. TOTAL
DBTAD/U-13
DBTGD/U-13
SENS. TOTAL SENS.
26.7DB/ 19.4WB
50% RH
10.3
8.0
12.8
10.2
14.9
13.1
18.5
16.7
26.1
22.3
38.8
32.8
43.3
39.0
50.4
45.4
24DB/ 17WB
50% RH
9.6
7.9
11.9
10.0
13.8
12.9
17.2
16.4
24.3
21.8
36.1
32.1
40.2
38.2
46.8
44.5
24DB/ 16WB
45% RH
9.4
8.4
11.6
10.7
13.6
13.6
16.7
16.7
23.8
23.4
35.3
34.4
39.4
39.4
45.9
45.9
22.2DB/ 15.5WB
50% RH
9.1
7.7
10.4
9.8
13.2
12.6
16.4
16.0
23.1
21.4
34.3
31.5
38.2
37.5
44.5
43.6
22.2DB/ 14.8WB
45% RH
8.7
8.2
10.8
10.5
12.6
12.6
15.7
15.7
22.1
22.1
32.9
32.9
36.7
36.7
42.7
42.7
NET CAPACITY MBH AT STANDARD AIRFLOW
80DB/ 67WB
50% RH
35.2
27.4
43.6
34.7
50.8
44.8
63.1
56.9
89.0
76.0
132.4 111.8 147.6 133.1 171.8 154.9
75DB/ 62.5WB
50% RH
32.7
26.8
40.5
34.1
47.2
43.9
58.7
55.8
82.8
74.5
123.1 109.6 137.3 130.4 159.7 151.8
75DB/ 61WB
45% RH
32.1
28.7
39.7
36.4
46.3
46.3
57.6
57.6
81.1
79.7
120.6 117.2 134.5 134.5 156.5 156.5
72DB/ 60WB
50% RH
31.1
26.3
35.5
33.4
44.9
43.0
55.8
54.7
78.7
73.0
117.0 107.4 130.4 127.8 151.8 148.7
72DB/ 58.6WB
45% RH
29.8
28.1
37.0
35.7
43.1
43.1
53.6
53.6
75.5
75.5
112.3 112.3 125.2 125.2 145.7 145.7
DB-TEMP SYSTEMS
WATER COOLED PERFORMANCE DATA
PERFORMANCE AT 29.4°C (85°F) ENTERING WATER TEMPERATURE
NET CAPACITY KW AT STANDARD AIRFLOW
MODEL
DBTWD/U-02 DBTWD/U-03 DBTWD/U-04 DBTWD/U-05 DBTWD/U-07 DBTWD/U-09 DBTWD/U-11
DTWD/U-13
TOTAL SENS. TOTAL SENS. TOTAL SENS. TOTAL SENS. TOTAL SENS. TOTAL SENS. TOTAL SENS. TOTAL SENS.
26.7DB/ 19.4WB
50% RH
11.2
8.5
13.9
10.8
17.2
14.8
19.7
17.0
27.7
22.6
41.4
33.8
46.7
41.3
54.4
47.0
24DB/ 17WB
50% RH
10.5
8.3
12.9
10.6
16.0
14.5
18.3
16.6
25.8
22.2
38.5
33.1
43.5
40.4
50.6
46.0
24DB/ 16WB
45% RH
10.2
8.9
12.7
11.3
15.7
15.5
17.9
17.8
25.3
23.7
37.8
35.4
42.6
42.6
49.5
49.2
22.2DB/ 15.5WB
50% RH
9.9
8.2
12.3
10.4
15.1
14.2
17.4
16.3
24.5
21.7
36.6
32.4
41.3
39.6
48.0
45.1
22.2DB/ 14.8WB
45% RH
9.5
8.8
11.8
11.1
14.6
14.7
16.7
16.7
23.5
23.2
35.1
34.7
39.7
39.7
46.1
46.1
NET CAPACITY MBH AT STANDARD AIRFLOW
80DB/ 67WB
50% RH
38.3
29.1
47.4
36.9
58.6
50.6
67.1
57.9
94.6
77.2
141.3 115.3 159.5 140.8 185.5 160.2
75DB/ 62.5WB
50% RH
35.7
28.5
44.0
36.1
54.5
49.6
62.4
56.8
88.0
75.7
131.4 113.0 145.4 138.0 172.5 157.0
75DB/ 61WB
45% RH
34.9
30.5
43.2
38.6
53.4
53.0
61.1
60.8
86.2
81.0
128.8 120.9 145.4 145.4 169.0 168.0
72DB/ 60WB
50% RH
33.9
28.0
41.8
35.4
51.7
48.6
59.3
55.6
83.6
74.1
124.8 110.7 141.0 135.2 163.9 153.8
72DB/ 58.6WB
45% RH
32.5
29.9
40.2
37.9
49.7
49.7
56.9
56.9
80.2
79.3
119.8 118.5 135.3 135.3 157.3 157.3
AIR COOLED, WATER/ GLYCOL COOLED
PHYSICAL DATA
DBT*D/U-02
DBT*D/U-03
DBT*D/U-04
DBT*D/U-05
DBT*D/U-07
DBT*D/U-09
DBT*D/U-11
DBT*D/U-13
LENGTH
MODEL
MM
INS
895
35.2
895
35.2
895
35.2
895
35.2
1727
68
1727
68
1727
68
1727
68
WIDTH
MM
INS
867
34.2
867
34.2
867
34.2
867
34.2
902
35.5
902
35.5
902
35.5
902
35.5
HEIGHT
MM
INS
1880
74
1880
74
1880
74
1880
74
1956
77
1956
77
1956
77
1956
77
WEIGHT
KG
LB
280
616
290
638
310
682
320
704
530
1166
540
1188
560
1232
580
1276
ADD 457MM(18 INCH) TO HEIGHT OF UNITS FOR DISCHARGE PLENUM - UP FLOW UNITS ONLY.
BLOWER DATA
STANDARD AIR
VOLUME
CMH
CFM
1700
1000
2550
1500
3400
2000
4250
2500
6796
4000
8500
5000
10200
6000
11050
6500
STANDARD FAN
MOTOR
KW
HP
0.75
1
0.75
1
0.75
1
1.12
1.5
1.5
2
2.2
3
3.0
4
3.7
5
OPTIONAL AIR
VOLUME
CMH
CFM
2550
1500
3060
1800
4250
2500
4590
2700
8500
5000
10200
6000
11050
6500
N/A
N/A
OPTIONAL FAN
MOTOR
KW
HP
1.12
1.5
1.12
1.5
1.12
1.5
1.5
2
2.2
3
3.0
4
3.7
5
N/A
N/A
EXT. STATIC
PRESSURE
MM W.G.
INS W.G.
7.6
0.3
7.6
0.3
7.6
0.3
7.6
0.3
12.7
0.5
12.7
0.5
12.7
0.5
N/A
N/A
SIZE (QUANTITY)
MM
INS
381 x 381 (1)
15 x15 (1)
381 x 381 (1)
15 x15 (1)
254 x 254 (1)
10 x 10 (1)
254 x 254 (1) 254 x 254 (1)
10 x 10 (1)
10 x 10 (1)
254 x 254 (1)
10 x 10 (1)
381 x 381 (1) 381 x 381 (1)
15 x15 (1)
15 x15 (1)
ADD 457MM (18 INCHES) TO HEIGHT OF UNITS FOR DISCHARGE PLENUM - UP FLOW UNITS ONLY
COMPRESSOR DATA
QUANTITY OF COMPRESSORS
REFRIGERANT
HORSEPOWER
50HZ
60HZ
1
1
1
1
1
1
1
1
R 22
R 22
R 22
R 22
R 22
R 22
R 22
R 22
4.0
3.5
5.1
4.9
6.0
5.8
7.0
6.0
8.0
7.0
12.0
11.0
13.0
10.0
15.0
13.0
0.46
5
1.16
12.5
1.16
12.5
1.16
12.5
1.16
12.5
EVAPORATOR DATA @ STANDARD AIRFLOW
FACE AREA
M²
FT²
0.28
3
4
4
4
4
2
3
4
4
M/S
FPM
1.69
333
2.54
500
2.03
400
2.54
500
1.63
320
2.04
400
2.44
480
2.65
520
ROWS OF COIL
FACE VELOCITY
0.28
3
0.46
5
DB-TEMP SYSTEMS
REHEAT SECTION
MODEL
DBT*D/U-02 DBT*D/U-03
STANDARD ELECTRIC
KW
MBH
6.0
20.5
DBT*D/U-04 DBT*D/U-05
DBT*D/U-07 DBT*D/U-09
DBT*D/U-11 DBT*D/U-13
12.0
41.0
12.0
41.0
12.0
41.0
15.0
51.2
15.0
51.2
15.0
51.2
15.0
51.2
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
10
3.6
10
3.6
10
3.6
10
3.6
10
3.6
10
3.6
10
3.6
10
3.6
-
-
HUMIDIFIER SECTION (OPTIONAL)
KG/HR
STANDARD STEAM
GENERATOR CAPACITY LB/HR
KW
FILTERS STANDARD 50MM (2 INCH) THICK 30% ASHRAE STANDARD 52-76
610MM x 610MM (24 x 24) QTY
1
1
1
1
-
-
FILTERS STANDARD 100MM (4 INCH) THICK 30% ASHRAE STANDARD 52-76 (UPFLOW)
406MM x 635MM (16" x 25") QTY
-
-
-
-
3
3
3
3
FILTERS STANDARD 100MM (4 INCH) THICK 30% ASHRAE STANDARD 52-76 (DOWNFLOW)
406MM x 635MM (16" x 25") QTY
-
-
-
-
4
4
4
4
CONNECTION SIZE
LIQUID LINE O.D
COPPER (1/UNIT)
INS
1/2
1/2
1/2
1/2
1/2
5/8
5/8
5/8
HOT GAS LINE O.D
COPPER (1/UNIT)
CONDENSER WATER
- IN OUT
INS
1/2
1/2
1/2
1/2
3/4
7/8
7/8
7/8
INS
7/8
7/8
1 1/8
1 1/8
1 5/8
1 5/8
1 5/8
1 5/8
HUMIDIFIER SUPPLY
INS
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
CONDENSATE DRAIN
INS
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
NOTE : REFER TO OPERATION AND MAINTENANCE FOR RECOMMENDED PIPE SIZING BETWEEN INDOOR AND OUTDOOR UNIT.
AIR COOLED
AIR COOLED CONDENSERS STD SELECTIONS AT 35°C (95°F) AMBIENT, SEA LEVEL*
MODEL
DBTAD/U-02 DBTAD/U-03 DBTAD/U-04 DBTAD/U-05 DBTAD/U-07 DBTAD/U-09 DBTAD/U-11 DBTAD/U-13
MODEL NUMBER
DBRC-04
DBRC-04
DBRC-06
DBRC-06
DBRC-08
DBRC-10
DBRC-13
DBRC-17
*SEE 'REMOTE HEAT EXCHANGER' SECTION FOR MORE INFORMATION.
WATER COOLED
CONDENSER WATER REQUIREMENTS
MAXIMUM DESIGN WATER PRESSURE 1033 KPA
MODEL
DBTWD/U-02 DBTWD/U-03 DBTWD/U-04 DBTWD/U-05 DBTWD/U-07 DBTWD/U-09 DBTWD/U-11 DBTWD/U-13
29.4°C/85°F EWT
LPS/PD IN KPA
GPM/PD IN PSI
0.39/19.3
6.2/2.8
0.7/51.7
11.4/7.5
0.8/20.7
12.0/3.0
1.1/35.9
17.0/5.2
1.0/ 27.6
15.8/ 4.0
1.5/ 24.8
24.0/ 3.6
1.9/ 29.0
30.0/ 4.2
2.5/ 31.0
40.0/ 4.5
23.9°C/75°F EWT
LPS/PD IN KPA
GPM/PD IN PSI
0.3/11.0
4.0/1.6
0.4/19.3
6.2/2.8
0.5/13.8
8.3/2.0
0.7/17.9
10.4/2.6
0.7/ 20.7
11.1/ 3.0
1.1/ 17.9
17.3/ 2.6
1.4/ 20.7
22.0/ 3.0
2.0/ 21.4
31.3/ 3.1
18.3°C/65°F EWT
LPS/PD IN KPA
GPM/PD IN PSI
0.2/6.2
2.6/0.9
0.2/10.3
3.9/1.5
0.3/7.6
5.2/1.1
0.4/9.0
6.5/1.3
0.4/ 13.8
7.1/ 2.0
0.6/ 6.9
10.0/ 1.0
0.8/ 10.3
13.2/ 1.5
1.2/ 13.8
19.0/ 2.0
GLYCOL COOLED
DRY-AIR COOLER SELECTION AT 35°C (95°F) AMBIENT, SEA LEVEL
MODEL
DBTGD/U-02 DBTGD/U-03 DBTGD/U-04 DBTGD/U-05 DBTGD/U-07 DBTGD/U-09 DBTGD/U-11 DBTGD/U-13
GLYCOL
LPS
0.4
0.7
0.7
0.9
1.3
1.7
1.9
2.2
FLOW RATE
GPM
6.4
11.0
11.7
15.0
21.0
27.0
30.0
35.0
PRESSURE DROP
KPA
PSI
21.4
3.1
49.0
7.1
23.4
3.4
31.0
4.5
24.1
3.5
20.0
2.9
25.5
3.7
21.4
3.1
DBFC-05
DBFC-06
DBFC-09
DBFC-09
DBFC-11
DBFC-17
DBFC-21
DBFC-24
DRY-AIR COOLER
DB-TEMP SYSTEMS
AIR COOLED, WATER/ GLYCOL COOLED ELECTRICAL DATA
ELECTRICAL BASED ON STANDARD UNITS (WITH ELECTRIC REHEAT AND ELECTRIC HUMIDIFICATION)
MODEL
380/3/50
415/3/50
208/3/60
230/3/60
460/3/60
DBT*D/U-02 DBT*D/U-03 DBT*D/U-04 DBT*D/U-05 DBT*D/U-07 DBT*D/U-09 DBT*D/U-11 DBT*D/U-13
FLA
15.5
25.8
27.0
29.2
40.7
45.1
51.5
58.1
MCA
MFS
FLA
MCA
MFS
FLA
19
20.0
14.2
17
20.0
30.5
32
35.0
23.8
29
30.0
49.7
33
35.0
24.8
31
35.0
53.7
36
40.0
26.8
33
35.0
57.6
50
50.0
37.2
46
50.0
77.5
55
60.0
41.2
50
60.0
89.3
63
70.0
47.2
57
70.0
100.9
71
90.0
53.2
65
80.0
112.5
MCA
MFS
FLA
MCA
MFS
FLA
MCA
MFS
37
40.0
27.6
34
35.0
13.7
17
20.0
61
70.0
44.9
55
60.0
22.5
28
30.0
66
70.0
48.5
60
60.0
24.3
30
30.0
71
80.0
52.1
64
70.0
26.1
32
35.0
95
110.0
70.1
86
100.0
34.8
43
50.0
109
125.0
80.8
99
125.0
40.4
50
60.0
123
150.0
91.3
111
125.0
45.5
55
70.0
137
175.0
101.7
124
150.0
50.3
61
80.0
ELECTRICAL BASED ON ELECTRIC HUMIDIFICATION WITHOUT ELECTRIC REHEAT
380/3/50
415/3/50
208/3/60
230/3/60
460/3/60
FLA
MCA
MFS
FLA
MCA
MFS
FLA
11.9
14
17.5
10.9
13
15.0
23.8
13.1
16
20.0
12.1
15
17.5
26.4
14.3
17
20.0
13.1
16
20.0
30.3
16.5
20
25.0
15.1
18
20.0
34.3
23.4
28
40.0
21.4
26
35.0
45.8
27.8
33
45.0
25.3
30
45.0
57.7
34.2
41
60.0
31.3
38
50.0
69.3
40.9
49
70.0
37.3
45
60.0
80.9
MCA
MFS
FLA
MCA
MFS
FLA
29
35.0
21.5
26
30.0
10.7
32
40.0
23.8
29
35.0
11.9
37
50.0
27.4
33
45.0
13.7
42
50.0
31.0
38
50.0
15.5
56
80.0
41.4
50.0
70
20.5
70
100.0
52.1
63.0
90
26.1
84
125.0
62.6
76.0
110
31.1
98
150.0
73.1
88.0
125
36.0
MCA
MFS
13
15.0
14
17.5
17
20.0
19
25.0
25
35.0
32
45.0
38
50.0
43
60.0
ELECTRICAL BASED ON NO ELECTRIC REHEAT NO ELECTRIC HUMIDIFICATION
380/3/50
415/3/50
208/3/60
230/3/60
460/3/60
FLA
MCA
MFS
FLA
MCA
MFS
FLA
MCA
MFS
FLA
MCA
MFS
FLA
6.4
8
12.0
5.9
7
10.0
13.8
16
25.0
12.5
15
20.0
6.2
7.6
9
15.0
7.1
8
12.0
16.4
20
30.0
14.8
18
25.0
7.4
8.8
11
17.5
8.1
10
15.0
20.3
25
40.0
18.4
22
35.0
9.2
11.0
13
20.0
10.1
12
17.5
24.3
29
45.0
22.0
26
40.0
11.0
17.9
21
35.0
16.4
20
30.0
35.8
43
70.0
32.4
39
60.0
16.0
22.3
27
40.0
20.3
24
40.0
47.7
57
90.0
43.1
52
80.0
21.6
28.7
34
50.0
26.3
31
50.0
59.3
71
110.0
53.6
64
100.0
26.6
35.4
42
60.0
32.3
38
60.0
70.9
85
125.0
64.1
77
125.0
31.5
MCA
MFS
7
12.0
9
15.0
11
17.5
13
20.0
19
30.0
26
40.0
32
50.0
38
60.0
FAN MOTOR FULL LOAD AMPS @ STANDARD AIR FLOW
380/3/50
415/3/50
208/3/60
230/3/60
460/3/60
1.8
1.7
3.5
3.2
1.6
1.8
1.7
3.5
3.2
1.6
1.8
1.7
3.5
3.2
1.6
2.8
2.6
5.0
4.5
2.2
3.7
3.4
6.5
5.9
3.0
5.1
4.6
9.0
8.1
4.1
6.7
6.2
11.8
10.7
5.4
8.4
7.7
14.0
12.7
6.4
7.0
6.4
16.8
15.2
7.6
8.2
7.5
19.4
17.5
8.8
14.2
13.0
29.3
26.5
13.0
17.2
15.7
38.7
35.0
17.5
22.0
20.1
47.4
42.9
21.2
27.0
24.6
56.8
51.4
25.1
COMPRESSOR NOMINAL RUNNING AMPS
380/3/50
415/3/50
208/3/60
230/3/60
460/3/60
*A= AIR COOLED
FLA = FULL LOAD AMPACITY
4.6
4.2
10.3
9.3
4.6
5.8
5.4
12.8
11.6
5.8
W= WATER COOLED
MCA = MINIMUM CIRCUIT AMPACITY
G= GLYCOL COOLED
MFS = MAXIMUM FUSE SIZE
DB-TEMP SYSTEMS
AIR COOLED, WATER/ GLYCOL COOLED/ CHILLED WATER
DIMENSIONAL DATA
MODEL 2, 3, 4, 5 TON
(UP FLOW)
MODEL 2, 3, 4, 5 TON
(DOWN FLOW)
NOTES : 1.) MINIMUM SPACE REQUIRED IS 914MM (36") ON FRONT ,RIGHT AND LEFT SIDES FOR SERVICE ACCESS.
2.) ALL DIMENSIONS ARE IN MILLIMETER (INCHES).
DB-TEMP SYSTEMS
AIR COOLED, WATER/ GLYCOL COOLED DIMENSIONAL DATA
MODEL 07, 09, 11, 13 TON
(UP FLOW)
MODEL 07, 09, 11, 13 TON
(DOWN FLOW)
NOTES : 1.) MINIMUM SPACE REQUIRED IS 914MM (36") ON FRONT, RIGHT AND LEFT SIDES FOR SERVICE ACCESS.
2.) ALL DIMENSIONS ARE IN MILLIMETER (INCHES).
DB-AIRE DESIGN FEATURES
DB-AIRE MODELS
9 - 26 TONS
32 - 91 KW
AIR COOLED
WATER/GLYCOL COOLED
FRAME AND CABINET
The heliarc welded tubular steel frame provides
for maximum strength and ease of access. Side
and front panels can be easily opened and
removed with quarter-turn fasteners allowing full
access to all unit components. All panels include
25 mm (1 inch) thick 1-1/2lb density insulation
for protection and sound attenuation. DB-Aire's
unique frame design allows for your selection of
either downflow or upflow air patterns in the
same compact dimensions.
A-FRAME COIL
Computer selected coil design, using interwoven
coil surface increases unit efficiency at low
loads. Air is drawn through both circuits of the
coil at low velocity providing effective surface
exposure with minimum turbulence. This
provides greater efficiency in the cooling and
dehumidification process.
FAN SECTION
The 381 mm (15 inch) diameter, centrifugal,
forward-curved,
double-width,
double-inlet
blower configuration is engineered for quiet,
reliable operation. The blowers are AMCA
certified and factory certified dynamically
balanced. The draw through design ensures
even air distribution across the A-frame coil. The
draw through design also ensures low internal
cabinet pressure losses, and static sealing of
the filter section. Fan motors are totally
enclosed and mounted on an adjustable slide
base.
FILTERS
Computer room air cleanliness is enhanced by
standard 100 mm (4 inch) deep pleated 30
percent efficient filters (based on ASHRAE 5276) which can be easily changed through either
side of the unit. Upflow units are changed from
right hand side.
ELECTRICAL REHEAT
The three stage stainless steel finned tubular
reheat coils provide ample capacity to maintain
room dry bulb conditions during a system call for
dehumidification. Three equal stages give a
more accurate controlled response to the
requirements of the computer room. The heating
elements are protected by thermal safety
switches. The three stages of reheat create a
noticeable lowering of energy use.
HUMIDIFICATION (OPTIONAL)
The disposable cartridge electric stream
generator humidifier provides humidification
down stream of the cooling coil. The humidifier
is designed to allow all units at any voltage to
produce full rated steam output at an optimum
low water level.
DB-AIRE UMID
INTERFACE
The DB-Aire Umid
interface allows the
control of humidifiers
directly from the DBAire microprocessor
controller.
Steam Generator Humidifier
DB-AIRE DESIGN FEATURES
COMPRESSORIZED SYSTEMS
The refrigeration system uses two(2) highly
efficient and quiet scroll compressors. The scroll
compressor has a high EER, low sound power
level and is highly reliable. The high efficiency is
due to the controlled orbit with floating seals and
advanced scroll geometry design. There is no
contact of the mechanical parts in the scroll
design which eliminates mechanical wear and
tear. The motor is 100% cooled by suction gas.
A check value is located directly above the fixed
scroll discharge port. This prevents the
compressor from running backwards after the
power has been switched off (i.e. no rattling and
no shut-down noise). The motor is fitted with a
thermostat which protects the compressor if a
malfunction occurs. The refrigeration circuit
includes built in compressor overload protection,
filter drier, sight glass, adjustable expansion
valve, low pressure override timer, manual reset
high pressure control, short-cycle timer and
rotalock service valves.
Air Cooled Systems - A wide range of sizes of
remote mounted air cooled condensers are
available from DB-Aire in vertical discharge.
Condensers are manufactured by DB-Aire and
include circuits sized to match the heat rejection
of the corresponding compressors. The
industrial duty design includes galvanised
corrosion resistant housings, high efficiency
aluminium finned (optional copper fins
available), copper tube coils; coated fan guards,
energy efficient thermally protected motors; and
integral factory wired and tested control panel.
Water/Glycol Cooled Systems - Include unit
mounted condensers for providing the required
capacity for heat rejection with minimum
water/glycol flow and low total pressure drop.
Dry-Air Cooler For Glycol Systems - A wide
range of sizes of remote mounted fluid coolers
are available from DB-Aire in vertical discharge.
Dry-air coolers are manufactured by DB-Aire
and are sized to match the heat rejection of the
corresponding unit. The industrial duty design
includes
galvanised
corrosion
resistant
housings, high efficiency aluminium finned
(optional copper fins available), copper tube
coils; coated fan guards; energy efficient,
thermally protected motors and fan cycling
controls with integral factory wired and tested
control panel.
DB-AIRE SYSTEMS
AIR COOLED/ GLYCOL COOLED PERFORMANCE DATA
PERFORMANCE AT 35°C (95°F) AMBIENT WITH SPECIFIED CONDENSER/ DRY-AIR COOLER
NET CAPACITY KW AT STANDARD AIRFLOW
MODEL
DBAD/U-09
DBGD/U-09
DBAD/U-11
DBGD/U-11
DBAD/U-13
DBGD/U-13
DBAD/U-14
DBGD/U-14
DBAD/U-16
DBGD/U-16
DBAD/U-19
DGAD/U-19
DBAD/U-22
DBGD/U-22
DBAD/U-26
DBGD/U-26
TOTAL
SENS.
TOTAL
SENS.
TOTAL
SENS.
TOTAL
SENS.
TOTAL
SENS.
TOTAL
SENS.
TOTAL
SENS.
TOTAL
SENS.
26.7DB/19.4WB
50% RH
36.6
32.3
45.5
38.8
51.6
45.1
57.9
51.1
67.9
58.7
77.5
66.2
88.1
76.1
102.5
88.5
24.0DB/17.0WB
50% RH
34.1
31.7
42.3
38.1
48.0
44.2
53.8
50.1
63.2
57.5
72.1
64.9
81.9
74.5
95.3
86.8
24.0DB/16.0WB
45% RH
33.4
33.4
41.4
40.7
47.1
47.3
52.8
52.8
61.9
61.5
70.7
69.4
80.3
79.8
93.4
92.8
22.2DB/15.5WB
50% RH
32.4
31.1
40.2
37.3
45.6
43.3
51.1
49.1
60.0
56.4
68.5
63.6
77.8
73.1
90.6
85.0
22.2DB/14.8WB
45% RH
31.1
31.1
38.6
38.6
43.8
43.8
49.1
49.1
57.6
57.6
65.7
65.7
74.7
74.7
86.9
86.9
NET CAPACITY MBH AT STANDARD AIRFLOW
80DB/67.0WB
50% RH
125.0 110.3 155.1 132.5 176.2 153.9 197.5 174.3 231.8 200.2 264.5 225.9 300.5 259.5 349.7 302.0
75DB/62.5WB
50%RH
116.2 108.1 144.3 129.9 163.9 150.8 183.7 170.8 215.6 196.2 246.0 221.4 279.5 254.3 325.2 296.0
75DB/61.0WB
45%RH
113.9 113.9 141.4 138.9 160.6 161.3 180.0 180.0 211.3 209.9 241.1 236.9 273.9 272.1 318.8 316.7
72DB/60.0WB
50%RH
110.4 106.0 137.1 127.3 155.7 147.8 174.5 167.4 204.8 192.3 233.7 217.0 265.5 249.3 309.0 290.1
72DB/58.6WB
45%RH
106.0 106.0 131.6 131.6 149.5 149.5 167.5 167.5 196.6 196.6 224.3 224.3 254.9 254.9 296.6 296.6
DB-AIRE SYSTEMS
WATER COOLED PERFORMANCE DATA
PERFORMANCE AT 29.4°C (85°F) ENTERING WATER TEMPERATURE
NET CAPACITY KW AT STANDARD AIRFLOW
MODEL
DBWD/U-09
DBWD/U-11
DBWD/U-13
DBWD/U-14
DBWD/U-16
DBWD/U-19
DBWD/U-22
DBWD/U-26
TOTAL
SENS.
TOTAL
SENS.
TOTAL
SENS.
TOTAL
SENS.
TOTAL
SENS.
TOTAL
SENS.
TOTAL
SENS.
TOTAL
SENS.
26.7DB/19.4WB
50% RH
38.6
33.0
48.0
41.0
54.4
46.0
61.0
52.1
71.4
59.6
82.0
67.7
92.6
77.4
107.7
90.0
24.0DB/17.0WB
50% RH
35.9
32.3
44.6
40.2
50.6
45.0
56.7
51.0
66.4
58.4
76.3
66.4
86.2
75.8
100.2
88.1
24.0DB/16.0WB
45% RH
35.2
34.6
43.8
43.0
49.6
48.2
55.6
54.6
65.1
62.5
74.8
71.0
84.4
81.1
98.2
94.3
22.2DB/15.5WB
50% RH
34.1
31.7
42.4
39.4
48.1
44.1
53.9
50.0
63.1
57.3
72.5
65.1
81.9
74.3
95.2
86.2
22.2DB/14.8WB
45% RH
32.7
30.7
40.7
38.2
46.2
42.8
51.7
48.5
60.6
55.6
69.6
63.1
78.6
72.1
91.4
83.8
NET CAPACITY MBH AT STANDARD AIRFLOW
80DB/67.0WB
50% RH
131.7 112.5 163.8 139.9 185.7 156.8 208.0 177.7 243.7 203.5 279.9 231.1 316.1 264.0 367.5 306.9
75DB/62.5WB
50%RH
122.5 110.2 152.3 137.1 172.7 153.7 193.5 174.1 226.6 199.4 260.3 226.5 294.0 258.7 341.7 300.7
75DB/61.0WB
45%RH
120.0 117.9 149.3 146.7 169.2 164.4 189.6 186.3 222.1 213.4 255.1 242.3 288.1 276.8 334.9 321.8
72DB/60.0WB
50%RH
116.3 108.0 144.7 134.4 164.0 150.6 183.8 170.6 215.3 195.4 247.3 222.0 279.3 253.5 324.7 294.7
72DB/58.6WB
45%RH
111.7 104.8 138.9 130.3 157.5 146.1 176.5 165.5 206.7 189.6 237.4 215.3 268.1 245.9 311.7 285.9
AIR COOLED, WATER/ GLYCOL COOLED
PHYSICAL DATA
DB*D/U-09
DB*D/U-11
DB*D/U-13
DB*D/U-14
DB*D/U-16
DB*D/U-19
DB*D/U-22
DB*D/U-26
LENGTH
MODEL
MM
INS
1727
68
1727
68
1727
68
2654
104.5
2654
104.5
2654
104.5
2654
104.5
2654
104.5
WIDTH
MM
INS
902
35.5
902
35.5
902
35.5
902
35.5
902
35.5
902
35.5
902
35.5
902
35.5
HEIGHT
MM
INS
1956
77
1956
77
1956
77
1956
77
1956
77
1956
77
1956
77
1956
77
KG
LB
545
1200
630
1381
630
1381
845
1859
895
1969
950
2090
1030
2266
1100
2420
WEIGHT WATER
COOLED
KG
LB
565
1243
655
1440
655
1440
900
1980
960
2112
1020
2244
1060
2332
1150
2530
GLYCOL
COOLED
KG
LB
565
1243
655
1440
655
1440
900
1980
960
2112
1020
2244
1060
2332
1150
2530
AIR COOLED
ADD 457MM(18 INCH) TO HEIGHT OF UNITS FOR DISCHARGE PLENUM - UP FLOW UNITS ONLY.
BLOWER DATA
STANDARD AIR
VOLUME
CMH
CFM
STANDARD FAN
MOTOR
KW
HP
OPTIONAL AIR
VOLUME
CMH
CFM
OPTIONAL FAN
MOTOR
KW
HP
EXT. STATIC
PRESSURE
MM W.G.
INS W.G.
SIZE (QUANTITY)
MM
INS
8500
5000
10200
6000
11000
6500
13600
8000
15300
9000
17000
10000
18700
11000
22100
13000
2.2
3.0
3.0
4.0
3.7
5.0
3.0
4.0
3.7
5.0
4.1
5.5
5.6
7.5
7.5
10
10200
6000
11000
6500
N/A
N/A
15300
9000
17000
10000
20400
12000
22100
13000
N/A
N/A
3.0
4.0
3.7
5.0
N/A
N/A
3.7
5.0
5.6
7.5
5.6
7.5
7.5
10.0
N/A
N/A
12.7
0.5
12.7
0.5
12.7
0.5
12.7
0.5
12.7
0.5
12.7
0.5
12.7
0.5
12.7
0.5
381x381 (1)
15x15 (1)
381x381 (1)
15x15 (1)
381x381 (1)
15x15 (1)
381x381 (2)
15x15 (2)
381x381 (2)
15x15 (2)
381x381 (2)
15x15 (2)
381x381 (2)
15x15 (2)
381x381 (2)
15x15 (2)
COMPRESSOR DATA
QUANTITY OF COMPRESSORS
REFRIGERANT
HORSEPOWER
EACH
50HZ
60HZ
2
2
2
2
2
2
2
2
R 22
R 22
R 22
R 22
R 22
R 22
R 22
R 22
5.5
5.0
7.0
5.5
8.0
7.0
9.0
8.0
10.0
9.0
12.0
10.0
13.0
12.0
15.0
13.0
2.27
24.4
2.27
24.4
2.27
24.4
EVAPORATOR DATA @ STANDARD AIRFLOW
FACE AREA
M²
FT²
1.13
12.2
3
4
4
3
3
4
4
4
M/S
FPM
2.09
409
2.50
491
2.71
5.32
1.67
327
1.88
368
2.09
409
2.29
450
2.71
532
ROWS OF COIL
FACE VELOCITY
1.13
12.2
1.13
12.2
2.27
24.4
2.27
24.4
DB-AIRE SYSTEMS
REHEAT SECTION
MODEL
DB*D/U-09
DB*D/U-11
DB*D/U-13
DB*D/U-14
DB*D/U-16
DB*D/U-19
DB*D/U-22
DB*D/U-26
STANDARD ELECTRIC KW
MBH
15.0
51.2
15.0
51.2
15.0
51.2
22.5
76.8
22.5
76.8
22.5
76.8
22.5
76.8
22.5
76.8
HUMIDIFIER SECTION (OPTIONAL)
STANDARD STEAM
KG/HR
4.6
4.6
4.6
4.6
13.6
13.6
13.6
13.6
GENERATOR
CAPACITY
LB/HR
KW
10.0
3.6
10.0
3.6
10.0
3.6
30.0
9.4
30.0
9.4
30.0
9.4
30.0
9.4
30.0
9.4
FILTERS STANDARD 100MM (4 INCH) THICK 30% ASHRAE STANDARD 52-76 (DOWNFLOW)
508MMx635MM (20"x 25")QTY
-
-
-
5
5
5
5
5
406MMx635MM (16"x 25")QTY
4
4
4
-
-
-
-
-
FILTERS STANDARD 100MM (4 INCH) THICK 30% ASHRAE STANDARD 52-76 (UPFLOW)
508MMx635MM (20"x 25")QTY
-
-
-
4
4
4
4
4
406MMx635MM (16"x 25")QTY
3
3
3
-
-
-
-
-
CONNECTION SIZE
LIQUID LINE O.D
COPPER (2/UNIT)
INS
1/2
1/2
1/2
1/2
5/8
5/8
5/8
5/8
HOT GAS LINE O.D
COPPER (2/UNIT)
INS
1/2
3/4
3/4
3/4
3/4
7/8
7/8
7/8
CONDENSER WATER
- IN OUT
INS
1 5/8
1 5/8
1 5/8
1 5/8
2 1/8
2 1/8
2 1/8
2 1/8
HUMIDIFIER SUPPLY
INS
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
CONDENSATE DRAIN
INS
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
NOTE : REFER TO OPERATION AND MAINTENANCE FOR RECOMMENDED PIPE SIZING BETWEEN INDOOR AND OUTDOOR UNIT.
AIR COOLED
AIR COOLED CONDENSERS STD SELECTIONS AT 35°C(95°F) AMBIENT, SEA LEVEL*
MODEL
DBAD/U-09
DBAD/U-11
DBAD/U-13
DBAD/U-14
DBAD/U-16
DBAD/U-19
DBAD/U-22
DBAD/U-26
DBRC-10
DBRC-13
DBRC-17
DBRC-17
DBRC-20
DBRC-20
DBRC-26
DBRC-30
MODEL NUMBER
*SEE 'REMOTE HEAT EXCHANGER' SECTION FOR MORE INFORMATION.
WATER COOLED
CONDENSER WATER REQUIREMENTS
MAXIMUM DESIGN WATER PRESSURE 1033 KPA
MODEL
DBWD/U-09
DBWD/U-11
DBWD/U-13
DBWD/U-14
DBWD/U-16
DBWD/U-19
DBWD/U-22
DBWD/U-26
29.4°C/85°F EWT
LPS/PD IN KPA
GPM/PD IN PSI
1.7 / 34.5
26.2 / 5.0
2.5 / 41.4
40.0 / 6.0
2.7 / 48.3
42.0 / 7.0
2.7 / 48.3
42.0 / 7.0
2.7 / 48.3
43.0 / 7.0
3.2 / 48.3
50.7 / 7.0
3.3 / 48.3
52.5 / 7.0
4.0 / 72.4
62.6 / 10.5
23.9°C/75°F EWT
LPS/PD IN KPA
GPM/PD IN PSI
1.2 / 27.6
18.6 / 4.0
1.7 / 27.6
27.3 / 4.0
1.9 / 31.0
29.7 / 4.5
1.9 / 31.0
29.7 / 4.5
1.9 / 31.0
30.7 / 4.5
2.2 / 31.0
35.5 / 4.5
2.3 / 31.0
37.1 / 4.5
2.9 / 48.3
46.4 / 7.0
18.3°C/65°F EWT
LPS/PD IN KPA
GPM/PD IN PSI
0.8 / 24.1
11.9 / 3.5
1.1 / 24.1
17.0 / 3.5
1.2 / 27.6
19.0 / 4.0
1.2 / 27.6
19.0 / 4.0
1.3 / 27.6
20.0 / 4.0
1.5 / 27.6
23.0 / 4.0
1.5 / 27.6
23.8 / 4.0
1.9 / 41.4
29.7 / 6.0
GLYCOL COOLED
DRY-AIR COOLER SELECTION AT 35°C (95°F) AMBIENT, SEA LEVEL
MODEL
MODEL NUMBER FLUID COOLER
DBGD/U-09
DBGD/U-11
DBGD/U-13
DBGD/U-14
DBGD/U-16
DBGD/U-19
DBGD/U-22
DBGD/U-26
DBFC-17
DBFC-21
DBFC-24
DBFC-28
DBFC-30
DBFC-37
DBFC-40
DBFC-24(2)
GLYCOL
FLOW RATE
LPS
GPM
1.7
27
1.9
30
2.2
35
2.5
40
3.5
56
3.9
62
4.4
70
5.0
80
PRESSURE DROP
KPA
PSI
20.0
2.9
25.5
3.7
21.4
3.1
18.6
2.8
24.5
3.5
26.2
3.8
20.7
3.0
21.4
3.1
DB-AIRE SYSTEMS
AIR COOLED, WATER/ GLYCOL COOLED ELECTRICAL DATA
ELECTRICAL BASED ON STANDARD UNITS (WITH ELECTRIC REHEAT AND ELECTRIC HUMIDIFICATION)
MODEL
380/3/50
415/3/50
208/3/60
230/3/60
460/3/60
DB*D/U-09
DB*D/U-11
DB*D/U-13
DB*D/U-14
DB*D/U-16
DB*D/U-19
DB*D/U-22
DB*D/U-26
FLA
MCA
MFS
FLA
MCA
MFS
FLA
44.3
52
60.0
40.5
48
50.0
89.3
53.7
62
70.0
49.1
57
60.0
106.3
59.6
69
70.0
54.5
63
70.0
114.3
72.8
85
90.0
66.5
78
80.0
143.1
78.9
92
100.0
72.2
84
90.0
153.4
77.3
90
90.0
70.7
82
90.0
158.0
90.1
104
110.0
82.5
85
100.0
177.9
103.8
119
125.0
95.0
109
125.0
205.1
MCA
MFS
FLA
MCA
MFS
FLA
105
110.0
80.8
95
100.0
40.5
123
125.0
96.1
111
125.0
47.1
132
150.0
103.4
119
125.0
51.2
167
175.0
129.4
151
175.0
63.3
179
200.0
138.7
162
175.0
68.7
184
200.0
142.9
166
175.0
70.1
205
225.0
160.9
186
200.0
80.0
235
250.0
185.5
212
250.0
91.6
MCA
MFS
47
50.0
55
60.0
59
60.0
74
80.0
80
90.0
82
90.0
92
100.0
105
110.0
ELECTRICAL BASED ON ELECTRIC HUMIDIFICATION WITHOUT ELECTRIC REHEAT
380/3/50
415/3/50
208/3/60
230/3/60
460/3/60
FLA
MCA
MFS
FLA
MCA
MFS
FLA
MCA
MFS
FLA
27.0
30
35.0
24.6
28
30.0
57.7
65
80.0
52.1
36.4
41
50.0
33.2
37
45.0
74.7
84
100.0
67.5
42.3
47
60.0
38.7
43
50.0
82.6
92
110.0
74.7
53.0
61
70.0
48.3
55
60.0
106.7
122
150.0
96.5
59.1
67
80.0
54.0
61
70.0
117.1
133
150.0
105.9
57.4
65
70.0
52.5
60
70.0
121.6
138
150.0
110.0
70.2
79
90.0
64.2
72
80.0
141.5
160
200.0
128.0
84.0
94
110.0
76.7
86
100.0
168.8
190
225.0
152.7
MCA
MFS
FLA
MCA
MFS
59
70.0
26.2
30
35.0
76
90.0
32.7
37
45.0
84
100.0
36.9
41
50.0
110
125.0
47.0
54
60.0
120
125.0
52.4
60
70.0
125
150.0
53.7
61
70.0
145
175.0
63.5
72
90.0
171
200.0
75.2
84
100.0
ELECTRICAL BASED ON NO ELECTRIC REHEAT NO ELECTRIC HUMIDIFICATION
380/3/50
415/3/50
208/3/60
230/3/60
460/3/60
FLA
MCA
MFS
FLA
MCA
MFS
FLA
21.5
24
30.0
19.6
21
25.0
47.7
30.9
34
45.0
28.2
31
40.0
64.7
36.8
40
50.0
33.7
37
50.0
72.6
38.7
43
50.0
35.2
39
50.0
80.6
44.8
49
60.0
40.9
45
60.0
91.0
43.1
47
60.0
39.4
43
50.0
95.5
55.9
61
80.0
51.1
56
70.0
115.4
69.7
76
100.0
63.6
70
90.0
142.8
MCA
MFS
FLA
MCA
MFS
FLA
52
70.0
43.1
47
60.0
21.7
71
90.0
58.5
64
80.0
28.2
80
100.0
65.7
72
90.0
32.4
89
110.0
72.9
81
110.0
35.2
101
125.0
82.3
91
125.0
40.6
106
125.0
86.4
95
125.0
41.9
127
175.0
104.4
115
150.0
51.7
157
200.0
129.1
142
175.0
63.4
MCA
MFS
24
30.0
31
40.0
36
45.0
39
50.0
45
60.0
46
60.0
57
70.0
70
90.0
FAN MOTOR FULL LOAD AMPS @ STANDARD AIR FLOW
380/3/50
415/3/50
208/3/60
230/3/60
460/3/60
5.1
4.6
9.0
8.1
4.1
6.7
6.2
11.8
10.7
5.4
8.4
7.7
14.0
12.7
6.4
6.7
6.2
11.8
10.7
5.4
8.4
7.7
14.0
12.7
6.4
8.7
8.0
15.3
13.8
6.9
11.9
10.9
20.6
18.6
9.3
15.7
14.4
29.1
26.3
13.2
12.1
11.0
26.4
23.9
11.4
14.2
13.0
29.3
26.5
13.0
16.0
14.5
34.4
31.1
14.9
18.2
16.6
38.4
34.8
17.1
17.2
15.7
40.1
36.3
17.5
22.0
20.1
47.4
42.9
21.2
27.0
24.6
56.8
51.4
25.1
COMPRESSOR FULL LOAD AMPS
380/3/50
415/3/50
208/3/60
230/3/60
460/3/60
*A = AIR COOLED
FLA = FULL LOAD AMPACITY
8.2
7.5
19.4
17.5
8.8
W = WATER COOLED
MCA = MINIMUM CIRCUIT AMPACITY
G = GLYCOL COOLED
MFS = MAXIMUM FUSE SIZE
DB-AIRE SYSTEMS
AIR COOLED, WATER/ GLYCOL COOLED DIMENSIONAL DATA
MODEL 9, 11, 13 TON
(UP FLOW)
MODEL 14, 16, 19, 22, 26 TON
(UP FLOW)
NOTES : 1.) MINIMUM SPACE REQUIRED IS 914MM (36") ON FRONT, RIGHT AND LEFT SIDES FOR SERVICE ACCESS.
2.) ALL DIMENSIONS ARE IN MILLIMETER (INCHES).
DB-AIRE SYSTEMS
AIR COOLED, WATER/ GLYCOL COOLED DIMENSIONAL DATA
MODEL 9, 11, 13 TON
(DOWN FLOW)
MODEL 14, 16, 19, 22, 26 TON
(DOWN FLOW)
NOTES : 1.) MINIMUM SPACE REQUIRED IS 914MM (36") ON FRONT, RIGHT AND LEFT SIDES FOR SERVICE ACCESS.
2.) ALL DIMENSIONS ARE IN MILLIMETER (INCHES).
CHILLED WATER DESIGN FEATURES
DB-TEMP MODELS
DB-AIRE MODELS
FRAME AND CABINET
The heliarc welded structural steel frame
provides for maximum strength and ease of
access. Side and front panels can be easily
opened and removed with quarter-turn fasteners
allowing full access to all unit components. All
panels include 25 mm (1 inch) thick 1 1/2 lb
density insulation for protection and sound
attenuation. DB-Aire's unique frame design
allows for your selection of either downflow or
upflow air patterns in the same compact
dimensions.
COIL SECTION
The coil is designed for draw through application
with large face areas for low velocity to reduce
turbulence and provide greater efficiency in the
cooling and dehumidification process. The
chilled water flow is controlled by a three-way
modulating mixing valve for accurate and
economical temperature and dehumidification
control.
FAN SECTION
The 380mm (15 inch) diameter, centrifugal
forward-curved,
double-width,
double-inlet
blower configuration is engineered for quiet,
reliable operation. The blowers are AMCA
certified and factory certified dynamically
balanced. All DB-Aire models have a two belt
drive system to assure reliability should one belt
fail. The draw through design ensures even air
distribution across the chilled water coil. It also
ensures low internal cabinet pressure losses,
and static sealing of the filter section. The fan
motor is totally enclosed and is mounted on an
adjustable slide base.
FILTERS
Computer room air cleanliness is enhanced by
pleated 30 percent efficient filters (based on
ASHRAE 52-76). Standard DB-Aire filters are
100mm (4 inch) deep, and may be changed
through the side of the unit. DB Temp filters are
50mm (2 inch) deep and are changed by
opening the front panel.
ELECTRICAL REHEAT
The three stage stainless steel finned tubular
reheat coils provide ample capacity to maintain
room dry bulb conditions during a system call for
dehumidification. Three equal stages give a
more accurate controlled response to the
requirements of the computer room. The heating
elements are protected by thermal safety
switches. The three stages of reheat create a
noticeable lowering of energy use.
HUMIDIFICATION (OPTIONAL)
The disposable cartridge electric stream
generator humidifier provides humidification
down stream of the cooling coil. The humidifier
is designed to allow all units at any voltage to
produce full rated steam output at an optimum
low water level.
DB-AIRE UMID
INTERFACE
The DB-Aire Umid
interface allows the
control of humidifiers
directly from the DBAire microprocessor
controller.
Steam Generator Humidifier
DB-TEMP CHILLED WATER SYSTEMS
CHILLED WATER PERFORMANCE DATA
PERFORMANCE WITH 7.2°C (45°F) CHILLED WATER AT SPECIFIED FLOW RATE
CAPACITY DATA (kW) AT 7.2 DEGREE CELSIUS CHILLED WATER
MODEL
TOTAL
26.7DB/19.4WB
SENSIBLE
50% RH
FLOW RATE L/SEC
DBTCD/U-02
DBTCD/U-03
DBTCD/U-04
DBTCD/U-05
11.3
15.1
21.2
24.8
7.9
11.0
15.3
18.3
0.5
0.6
0.9
1.1
20.7
33.8
15.2
20.0
TOTAL
7.9
10.6
14.9
17.5
23.9DB/16.9WB
SENSIBLE
6.8
9.5
13.1
15.8
50% RH
FLOW RATE L/SEC
0.3
0.5
0.6
0.8
PRESSURE DROP KPA
PRESSURE DROP KPA
11.0
18.6
8.3
11.0
TOTAL
7.3
9.9
13.9
16.4
23.9DB/16.1WB
SENSIBLE
7.1
9.9
13.7
16.4
45% RH
FLOW RATE L/SEC
0.3
0.4
0.6
0.7
PRESSURE DROP KPA
9.7
16.5
6.9
9.7
TOTAL
6.4
8.7
12.1
14.3
22.2DB/15.6WB
SENSIBLE
6.2
8.7
12.0
14.3
50% RH
FLOW RATE L/SEC
0.3
0.4
0.5
0.6
PRESSURE DROP KPA
8.3
13.1
5.5
7.6
TOTAL
6.1
8.4
11.7
13.9
22.2DB/14.8WB
SENSIBLE
6.1
8.4
11.7
13.9
45% RH
FLOW RATE L/SEC
0.3
0.4
0.5
0.6
PRESSURE DROP KPA
7.6
12.4
5.5
6.9
NET CAPACITY MBH AT STANDARD AIRFLOW
TOTAL
38.6
51.4
72.5
84.7
80DB/67WB
SENSIBLE
27.1
37.6
52.1
62.4
50% RH
FLOW RATE GPM
7.7
10.3
14.5
17.0
PRESSURE DROP PSI
3.0
4.9
2.2
2.9
TOTAL
27.0
36.2
50.8
59.7
75DB/62.5WB
SENSIBLE
23.2
32.4
44.7
53.8
50% RH
FLOW RATE GPM
5.4
7.3
10.2
11.9
PRESSURE DROP PSI
1.6
2.7
1.2
1.6
TOTAL
24.9
33.8
47.3
55.9
75DB/61WB
SENSIBLE
24.2
33.8
46.9
55.9
45% RH
FLOW RATE GPM
5.0
6.8
9.5
11.2
PRESSURE DROP PSI
1.4
2.4
1.0
1.4
TOTAL
21.9
29.6
41.4
48.8
72DB/60WB
SENSIBLE
21.0
29.6
40.8
48.8
50% RH
FLOW RATE GPM
4.4
5.9
8.3
9.8
PRESSURE DROP PSI
1.2
1.9
0.8
1.1
TOTAL
20.9
28.7
39.9
47.3
72DB/58.6WB
SENSIBLE
20.9
28.7
39.9
47.3
45% RH
FLOW RATE GPM
4.2
5.7
8.0
9.5
PRESSURE DROP PSI
1.1
1.8
0.8
1.0
DB-TEMP CHILLED WATER SYSTEMS
BLOWER DATA
MODEL
DBTCD/U-02
DBTCD/U-03
DBTCD/U-04
DBTCD/U-05
STANDARD AIR VOLUME
CMH
CFM
1700
1000
2550
1500
3400
2000
4250
2500
STANDARD FAN MOTOR
KW
HP
0.75
1.00
0.75
1.00
0.75
1.00
1.12
1.50
OPTIONAL AIR VOLUME
CMH
CFM
2550
1500
3060
1800
4250
2500
4590
2700
OPTIONAL FAN MOTOR
KW
HP
1.12
1.50
1.12
1.50
1.12
1.50
1.50
2.00
EXT. STATIC PRESSURE
MM W.G.
ING W.G.
7.6
0.3
7.6
0.3
7.6
0.3
7.6
0.3
SIZE (QUANTITY)
MM
INS
254 x 254 (1)
10 x 10 (1)
254 x 254 (1)
10 x 10 (1)
254 x 254 (1)
10 x 10 (1)
254 x 254 (1)
10 x 10 (1)
CHILLED WATER COIL DATA @ STANDARD AIRFLOW
FACE AREA
M²
FT²
0.28
3
0.28
3
0.46
5
0.46
5
4
4
4
4
M/S
FPM
1.69
333
2.54
500
2.03
400
2.54
500
KW
MBH
6.0
20.5
12.0
41.0
12.0
41.0
12.0
41.0
KG/HR
4.6
4.6
4.6
4.6
LB/HR
KW
10
3.6
10
3.6
10
3.6
10
3.6
ROWS OF COIL
FACE VELOCITY
REHEAT SECTION
STANDARD ELECTRIC
HUMIDIFIER SECTION (OPTIONAL)
STANDARD STEAM
GENERATOR CAPACITY
FILTERS STANDARD 50 MM (2 INCH) THICK 30% ASHRAE STANDARD 52-76
610 x 610 (24 x 24)
1
1
1
1
1 1/8
1 1/8
1 1/8
1 1/8
CONNECTION SIZES
CHILLED WATER
INS(OD)
HUMIDIFIER
INS
1/4
1/4
1/4
1/4
CONDENSATE DRAIN
INS(OD)
7/8
7/8
7/8
7/8
U – UPFLOW
D - DOWN FLOW
DB-TEMP CHILLED WATER SYSTEMS
CHILLED WATER ELECTRICAL DATA
ELECTRICAL BASED ON STANDARD UNITS (WITH ELECTRIC REHEAT AND ELECTRIC HUMIDIFIER)
MODEL
FLA
380/3/50
415/3/50
208/3/60
230/3/60
460/3/60
DBTCD/U-02
DBTCD/U-03
DBTCD/U-04
DBTCD/U-05
10.9
20.0
20.0
21.0
MCA
13
25
25
26
MFS
15.0
25.0
25.0
30.0
FLA
10.0
18.4
18.4
19.3
MCA
12
23
23
23
MFS
12.0
25.0
25.0
25.0
FLA
20.2
36.8
36.8
38.3
MCA
24
45
45
47
MFS
25.0
45.0
45.0
50.0
FLA
18.3
33.3
33.3
34.6
MCA
22
41
41
42
MFS
25.0
45.0
45.0
45.0
FLA
9.1
16.7
16.7
17.3
MCA
11
20
20
21
MFS
12.0
20.0
20.0
25.0
ELECTRICAL BASED ON ELECTRIC HUMIDIFICATION WITHOUT ELECTRIC REHEAT
FLA
380/3/50
415/3/50
208/3/60
230/3/60
460/3/60
7.3
7.3
7.3
8.3
MCA
9
9
9
10
MFS
10.0
10.0
10.0
10.0
FLA
6.7
6.7
6.7
7.6
MCA
8
8
8
9
MFS
10.0
10.0
10.0
10.0
FLA
13.5
13.5
13.5
15.0
MCA
16
16
16
17
MFS
17.5
17.5
17.5
17.5
FLA
12.2
12.2
12.2
13.5
MCA
14
14
14
16
MFS
15.0
15.0
15.0
17.5
FLA
6.1
6.1
6.1
6.7
MCA
7
7
7
8
MFS
10.0
10.0
10.0
10.0
ELECTRICAL BASED ON NO ELECTRIC REHEAT NO ELECTRIC HUMIDIFICATION
380/3/50
415/3/50
208/3/60
230/3/60
460/3/60
FLA
1.8
1.8
1.8
MCA
2
2
2
4
MFS
6.0
6.0
6.0
10.0
FLA
1.7
1.7
1.7
2.6
MCA
2
2
2
3
MFS
6.0
6.0
6.0
10.0
FLA
3.5
3.5
3.5
5.0
MCA
4
4
4
6
MFS
12.0
12.0
12.0
15.0
FLA
3.2
3.2
3.2
4.5
MCA
4
4
4
6
MFS
10.0
10.0
10.0
15.0
FLA
1.6
1.6
1.6
1.6
MCA
2
2
2
3
MFS
6.0
6.0
6.0
10.0
*A-AIR COOLED
W-WATER COOLED
FLA = FULL LOAD AMPACITY MCA = MINIMUM CIRCUIT AMPACITY
G-GLYCOL COOLED
MFS = MAXIMUM FUSE SIZE
2.8
DB-AIRE CHILLED WATER SYSTEMS
CHILLED WATER PERFORMANCE DATA
PERFORMANCE WITH 7.2°C(45°F) CHILLED WATER AT SPECIFIED FLOW RATE
NET CAPACITY KW AT STANDARD AIRFLOW
MODEL
DBCD/U07
DBCD/U09
DBCD/U- DBCD/U11
13
DBCD/U15
DBCD/U18
DBCD/U22
DBCD/U26
DBCD30
TOTAL
39.8
56.3
66.7
26.7DB/19.4WB
SENSIBLE
32.2
42.5
47.6
74.9
88.3
112.5
138.0
153.6
183.9
51.5
64.9
78.7
94.0
105.9
124.3
50% RH
FLOW RATE L/SEC
1.7
2.4
2.9
3.2
3.8
4.9
6.0
6.6
7.9
PRESSURE DROP KPA
14.5
TOTAL
28.2
22.8
31.7
40.7
47.6
80.7
129.0
35.9
53.1
39.7
46.9
52.9
62.0
79.4
98.0
108.5
130.4
23.9DB/16.9WB
SENSIBLE
28.2
36.9
40.8
43.9
55.9
67.4
80.1
90.3
105.5
50% RH
FLOW RATE L/SEC
1.2
1.7
2.0
2.3
2.7
3.4
4.2
4.7
5.6
PRESSURE DROP KPA
11.0
15.9
20.0
24.8
29.0
46.9
73.8
22.8
31.7
TOTAL
27.2
37.5
43.6
48.6
57.9
73.0
89.4
99.7
119.0
23.9DB/16.1WB
SENSIBLE
27.2
37.5
42.8
45.5
57.9
70.0
82.7
93.9
108.9
45% RH
FLOW RATE L/SEC
1.2
1.6
1.9
2.1
2.5
3.1
3.9
4.3
5.1
PRESSURE DROP KPA
11.0
14.5
18.6
22.8
26.2
41.4
64.2
20.7
28.3
TOTAL
23.3
32.6
38.2
42.9
50.7
64.5
79.5
88.1
105.8
22.2DB/15.6WB
SENSIBLE
23.3
32.6
37.2
39.7
50.7
61.2
72.5
81.9
95.4
50% RH
FLOW RATE L/SEC
1.0
1.4
1.6
1.8
2.2
2.8
3.4
3.8
4.6
PRESSURE DROP KPA
9.7
13.1
15.9
20.0
22.1
34.5
53.8
17.9
24.1
TOTAL
23.3
31.9
36.8
40.7
48.9
61.2
74.6
83.5
99.0
22.2DB/14.8WB
SENSIBLE
23.3
31.9
36.8
40.7
48.9
61.2
74.6
83.5
99.0
45% RH
FLOW RATE L/SEC
1.0
1.4
1.6
1.8
2.1
2.6
3.2
3.6
4.3
PRESSURE DROP KPA
9.7
13.1
15.9
18.6
21.4
32.4
20.6
16.6
22.8
NET CAPACITY MBH AT STANDARD AIRFLOW
TOTAL
135.8
192.1
227.4
255.5
301.3
383.9
471.1
523.9
627.7
80DB/67WB
SENSIBLE
109.8
145.0
162.5
175.8
221.4
268.5
320.7
361.4
424.0
50% RH
FLOW RATE GPM
27.2
38.5
45.5
51.2
60.3
76.9
94.3
104.9
125.7
2.1
3.3
4.6
5.9
6.9
11.7
18.7
5.2
7.7
PRESSURE DROP PSI
TOTAL
96.2
135.3
160.1
180.6
211.5
270.8
334.2
370.2
445.0
75DB/62.5WB
SENSIBLE
96.2
125.8
139.3
149.9
190.7
230.0
273.2
308.1
360.1
50% RH
FLOW RATE GPM
19.3
27.1
32.0
36.1
42.3
54.2
66.9
74.1
89.1
1.6
2.3
2.9
3.6
4.2
6.8
10.7
3.3
4.6
PRESSURE DROP PSI
TOTAL
92.8
127.9
148.8
165.7
197.5
248.9
305.0
340.1
406.0
75DB/61WB
SENSIBLE
92.8
127.9
145.9
155.4
197.5
238.8
282.1
320.2
371.7
45% RH
FLOW RATE GPM
18.6
25.6
29.8
33.2
39.5
49.8
61.1
68.1
81.3
1.6
2.1
2.7
3.3
3.8
6.0
9.3
3.0
4.1
PRESSURE DROP PSI
TOTAL
79.6
111.1
130.5
146.5
173.0
220.1
271.3
300.6
360.8
72DB/60WB
SENSIBLE
79.6
111.1
127.0
135.6
173.0
208.9
247.4
279.4
325.6
50% RH
FLOW RATE GPM
15.9
22.2
26.1
29.3
34.6
44.1
54.3
60.2
72.2
1.4
1.9
2.3
2.9
3.2
5.0
7.8
2.6
3.5
PRESSURE DROP PSI
TOTAL
79.4
108.9
125.4
138.7
167.0
208.9
254.4
284.8
337.9
72DB/58.6WB
SENSIBLE
79.4
108.9
125.4
138.7
167.0
208.9
254.4
284.8
337.9
45% RH
FLOW RATE GPM
15.9
21.8
25.1
27.8
33.4
41.8
50.9
57.0
67.7
1.4
1.9
2.3
2.7
3.1
4.7
7.1
2.4
3.3
PRESSURE DROP PSI
DB-AIRE CHILLED WATER SYSTEMS
BLOWER DATA
MODEL
STANDARD AIR VOLUME
CMH
CFM
STANDARD FAN MOTOR
KW
HP
OPTIONAL AIR VOLUME
CMH
CFM
OPTIONAL FAN MOTOR
KW
HP
EXT. STATIC PRESSURE
MM WG
INS WG
SIZE (QUANTITY)
MM
INS
DBCD/U07
DBCD/U09
DBCD/U11
DBCD/U13
DBCD/U15
DBCD/U18
DBCD/U22
DBCD/U26
DBCD30
8925
5250
10200
6000
10200
6000
10200
6000
16150
9500
17000
10000
18700
11000
21080
12400
23800
14000
2.2
3.0
3.0
4.0
3.0
4.0
3.7
5.0
3.7
5.0
5.6
7.5
5.6
7.5
7.5
10.0
7.5
10.0
10200
6000
11900
7000
11900
7000
11560
6800
18360
10800
19210
11300
20400
12000
23120
13600
N/A
N/A
3.0
4.0
3.7
5.0
3.7
5.0
5.6
7.5
5.6
7.5
7.5
10.0
7.5
10.0
7.5
10.0
N/A
N/A
12.7
0.5
12.7
0.5
12.7
0.5
12.7
0.5
12.7
0.5
12.7
0.5
12.7
0.5
12.7
0.5
12.7
0.5
381x381(1) 381x381(1) 381x381(1) 381x381(1) 381x381(2) 381x381(2) 381x381(2) 381x381(2) 457x457(2)
15x15(1)
15x15(1)
15x15(1)
15x15(1)
15x15(2)
15x15(2)
15x15(2)
15x15(2)
18x18(2)
CHILLED WATER COIL DATA @ STANDARD AIRFLOW
FACE AREA
M²
FT²
ROWS OF COIL
FACE VELOCITY
M/S
FPM
1.16
12.50
1.16
12.50
1.16
12.50
1.16
12.50
2.32
25.00
2.32
25.00
2.32
25.00
2.32
25.00
2.88
31.00
3
4
5
6
3
4
5
6
6
2.14
420
2.44
480
2.44
480
2.44
480
1.93
380
2.03
400
2.24
440
2.52
496
2.30
452
CHILLED WATER CONTROLS (DESIGN PRESSURE 1722 KPA (HIGH PRESSURE OPTIONAL)
CONTROL METHOD
MODULATE
VALVE BODY
3-WAY
VALVE CV
VALVE SIZE
MM(IN)
10
10
16
25
25
40
40
40
40
25.4(1)
25.4(1)
32.1(1¼)
38.0(1½)
38.0(1½)
51.0(2)
51.0(2)
51.0(2)
51.0(2)
15.0
51.2
15.0
51.2
15.0
51.2
15.0
51.2
22.5
76.8
22.5
76.8
22.5
76.8
22.5
76.8
22.5
76.8
REHEAT SECTION
STANDARD ELECTRIC
KW
MBH
HUMIDIFIER SECTION (OPTIONAL)
STANDARD STEAM
GENERATOR CAPACITY
KG/HR
4.5
4.5
4.5
4.5
13.6
13.6
13.6
13.6
13.6
LB/HR
KW
10
3.6
10
3.6
10
3.6
10
3.6
30
9.4
30
9.4
30
9.4
30
9.4
30
9.4
FILTERS STANDARD 100 MM (4INCH) THICK 30% ASHRAE STANDARD 52-75
508x635 (20x25)
-
-
-
-
1
1
1
1
5
406x635 (16x25)
3
3
3
3
4
4
4
4
-
CONNECTION SIZES
CHILLED WATER
INS(OD)
1 1/8
1 1/8
1 3/8
1 5/8
1 5/8
2 1/8
2 1/8
2 1/8
2 1/8
HUMIDIFIER
INS(OD)
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
CONDENSATE DRAIN
INS(OD)
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
DB-AIRE CHILLED WATER SYSTEMS
CHILLED WATER ELECTRICAL DATA
ELECTRICAL BASED ON STANDARD UNITS (WITH ELECTRIC REHEAT AND ELECTRIC HUMIDIFIER)
MODEL
380/3/50
415/3/50
208/3/60
230/3/60
460/3/60
DBCD/U07
DBCD/U09
DBCD/U11
DBCD/U13
DBCD/U15
DBCD/U18
DBCD/U22
DBCD/U26
DBCD/U30
FLA
27.9
29.5
29.5
31.2
42.6
46.1
46.1
49.9
49.9
MCA
34
35
35
37
51
55
55
58
58
MFS
35.0
35.0
35.0
40.0
60.0
60.0
60.0
60.0
60.0
FLA
25.5
27.1
27.1
28.6
39.0
42.2
42.2
45.7
45.7
MCA
31
32
32
34
47
50
50
54
54
MFS
35.0
35.0
35.0
35.0
50.0
50.0
50.0
60.0
60.0
FLA
50.6
53.5
53.5
55.7
76.5
83.0
83.0
91.5
91.5
MCA
61
64
64
66
92
99
99
107
107
MFS
70.0
70.0
70.0
70.0
100.0
100.0
100.0
110.0
110.0
FLA
45.8
48.4
48.4
50.4
69.2
75.1
75.1
82.8
82.8
MCA
55
58
58
60
83
89
89
97
97
MFS
60.0
60.0
60.0
60.0
90.0
90.0
90.0
100.0
100.0
FLA
22.9
24.2
24.2
25.2
34.6
37.5
37.5
41.4
41.4
MCA
28
29
29
30
42
45
45
48
48
MFS
30.0
30.0
30.0
30.0
45.0
45.0
45.0
50.0
50.0
30.0
ELECTRICAL BASED ON ELECTRIC HUMIDIFICATION WITHOUT ELECTRIC REHEAT
380/3/50
415/3/50
208/3/60
230/3/60
460/3/60
FLA
10.6
12.2
12.2
13.9
22.7
26.2
26.2
30.0
MCA
12
14
14
15
26
30
30
34
34
MFS
12.0
15.0
15.0
15.0
30.0
30.0
30.0
35.0
35.0
FLA
9.6
11.2
11.2
12.7
20.8
24.0
24.0
27.5
27.5
MCA
11
12
12
14
24
27
27
31
31
MFS
12.0
12.0
12.0
15.0
25.0
30.0
30.0
35.0
35.0
FLA
18.9
21.8
21.8
24.0
40.1
46.7
46.7
55.2
55.2
MCA
21
24
24
27
47
53
53
62
62
MFS
25.0
25.0
25.0
30.0
50.0
60.0
60.0
70.0
70.0
FLA
17.1
19.7
19.7
21.7
36.3
42.2
42.2
49.9
49.9
MCA
19
22
22
24
42
48
48
56
56
MFS
20.0
25.0
25.0
25.0
45.0
50.0
50.0
60.0
60.0
FLA
8.6
9.9
9.9
10.9
18.2
21.1
21.1
25.0
25.0
MCA
10
11
11
12
21
24
24
28
28
MFS
10.0
12.0
12.0
12.0
25.0
25.0
25.0
30.0
30.0
15.7
ELECTRICAL BASED ON NO ELECTRIC REHEAT NO ELECTRIC HUMIDIFICATION
380/3/50
415/3/50
208/3/60
230/3/60
460/3/60
FLA
5.1
6.7
6.7
8.4
8.4
11.9
11.9
15.7
MCA
6
8
8
11
11
15
15
20
20
MFS
15.0
20.0
20.0
25.0
25.0
40.0
40.0
50.0
50.0
FLA
4.6
6.2
6.2
7.7
7.7
10.9
10.9
14.4
14.4
MCA
6
8
8
10
10
14
14
18
18
MFS
15.0
20.0
20.0
25.0
25.0
35.0
35.0
45.0
45.0
FLA
9.0
11.8
11.8
14.0
14.0
20.6
20.6
29.1
29.1
MCA
11
15
15
18
18
26
26
36
36
MFS
30.0
35.0
35.0
45.0
45.0
70.0
70.0
90.0
90.0
FLA
8.1
10.7
10.7
12.7
12.7
18.6
18.6
26.3
26.3
MCA
10
13
13
16
16
23
23
33
33
MFS
25.0
35.0
35.0
40.0
40.0
60.0
60.0
80.0
80.0
FLA
4.1
5.4
5.4
6.4
6.4
9.3
9.3
13.2
13.2
MCA
5
7
7
8
8
12
12
17
17
MFS
12.0
17.5
17.5
20.0
20.0
30.0
30.0
40.0
40.0
*A-AIR COOLED
FLA = FULL LOAD AMPACITY
W-WATER COOLED
MCA = MINIMUM CIRCUIT AMPACITY
G-GLYCOL COOLED
MFS = MAXIMUM FUSE SIZE
DB-TEMP/ DB-AIRE CHILLED WATER SYSTEMS
AIR COOLED, WATER/ GLYCOL COOLED/ CHILLED WATER
DIMENSIONAL DATA
MODEL 2, 3, 4, 5 TON
(UP FLOW)
MODEL 2, 3, 4, 5 TON
(DOWN FLOW)
NOTES : 1.) MINIMUM SPACE REQUIRED IS 914MM (36") ON FRONT ,RIGHT AND LEFT SIDES FOR SERVICE ACCESS.
2.) ALL DIMENSIONS ARE IN MILLIMETER (INCHES).
DB-TEMP/ DB-AIRE CHILLED WATER SYSTEMS
DIMENSIONAL DATA
MODEL 7, 9, 11, 13 TON
(UP FLOW)
MODEL 15, 18, 22, 26 TON
(UP FLOW)
NOTES : 1.) MINIMUM SPACE REQUIRED IS 914MM (36") ON FRONT, RIGHT AND LEFT SIDES FOR SERVICE ACCESS.
2.) ALL DIMENSIONS ARE IN MILLIMETER (INCHES).
3.) DEPTH IS 40” FOR 5-ROW AND 6-ROW COIL.
DB-TEMP/DB-AIRE CHILLED WATER SYSTEMS
DIMENSIONAL DATA
MODEL 7, 9, 11, 13 TON
(DOWN FLOW)
MODEL 15, 18, 22, 26 TON
(DOWN FLOW)
MODEL 30 TON
(DOWN FLOW)
NOTES : 1.) MINIMUM SPACE REQUIRED IS 914MM (36") ON FRONT, RIGHT AND LEFT SIDES FOR SERVICE ACCESS.
2.) ALL DIMENSIONS ARE IN MILLIMETER (INCHES).
3.) DEPTH IS 40” FOR 5-ROW AND 6-ROW COIL.
REMOTE AIR-COOLED CONDENSERS
TECHNICAL DATA
PHYSICAL DATA
MODEL
LENGTH 'L'
FANS
QTY
MM (INS)
ELECTRICAL DATA
APPROX.
MTR
RPM
MTR FLA (3-PHASE)
TOTAL L/S
WEIGHT
(CFM)
KG(LBS)
QTY
50Hz
60Hz
380V
415V
208V
230V
(50Hz)
(50Hz)
(60Hz)
(60Hz)
DBRC 04
870 (34¼)
1
2030 (4300)
100 (220)
1
900
1080
-
-
-
-
DBRC 06
870 (34¼)
1
3210 (6800)
111 (244)
1
950
1075
2.0
1.8
3.6
3.3
DBRC 08
870 (34¼)
1
3210 (6800)
122 (268)
1
950
1075
2.0
1.8
3.6
3.3
DBRC 10
870 (34¼)
1
3210 (6800)
134 (295)
1
950
1075
2.0
1.8
3.6
3.3
DBRC 11
870 (34¼)
1
3210 (6800)
180 (400)
1
950
1075
2.0
1.8
3.6
3.3
DBRC 13
1683 (66¼)
2
6420 (13600)
190 (420)
2
950
1075
4.0
3.7
7.3
6.6
DBRC 17
1683 (66¼)
2
6420 (13600)
204 (450)
2
950
1075
4.0
3.7
7.3
6.6
DBRC 20
1683 (66¼)
2
6420 (13600)
265 (583)
2
950
1075
4.0
3.7
7.3
6.6
DBRC 26
2500 (98¼)
3
9630 (20400)
288 (634)
3
950
1075
6.0
5.5
10.9
9.9
DBRC 30
2500 (98¼)
3
9630 (20400)
320 (700)
3
950
1075
6.0
5.5
10.9
9.9
DBRC 34
2500 (98¼)
3
9630 (20400)
355 (780)
3
950
1075
6.0
5.5
10.9
9.9
DBRC 40
3308 (130¼)
4
12838 (27200)
380 (835)
4
950
1075
8.0
7.3
14.6
13.2
DBRC 44
3308 (130¼)
4
12838 (27200)
410 (900)
4
950
1075
8.0
7.3
14.6
13.2
NOTE:
1.) ALL DIMENSIONS ARE IN MM (INCHES).
2.) * = 889(35”), ** = 972(38.25”) FOR DBRC-04
3.) MOTOR FLA FOR DBRC04 IS 1 PHASE 1.3A (220V) / 1.2A (240V) / 1.4A (208V) / 1.2A (230V).
DRY-AIR COOLERS
TECHNICAL DATA
PHYSICAL DATA
MODEL
LENGTH 'L'
ELECTRICAL DATA
FANS
APPROX.
TOTAL L/S
WEIGHT
(CFM)
KG(LBS)
QTY
50Hz
QTY
MM (INS)
MTR
RPM
MTR FLA (3-PHASE)
380V
415V
208V
230V
60Hz
(50Hz)
(50Hz)
(60Hz)
(60Hz)
DBFC 05
870 (34¼)
1
3210 (6800)
100 (220)
1
950
1075
2.0
1.8
3.6
3.3
DBFC 06
870 (34¼)
1
3210 (6800)
111 (244)
1
950
1075
2.0
1.8
3.6
3.3
DBFC 09
870 (34¼)
1
3210 (6800)
122 (268)
1
950
1075
2.0
1.8
3.6
3.3
DBFC 11
1683 (66¼)
2
6420 (13600)
180 (400)
2
950
1075
4.0
3.7
7.3
6.6
DBFC 15
1683 (66¼)
2
6420 (13600)
190 (420)
2
950
1075
4.0
3.7
7.3
6.6
DBFC 17
1683 (66¼)
2
6420 (13600)
204 (450)
2
950
1075
4.0
3.7
7.3
6.6
DBFC 21
2500 (98¼)
3
9630 (20400)
265 (583)
3
950
1075
6.0
5.5
10.9
9.9
DBFC 24
2500 (98¼)
3
9630 (20400)
288 (634)
3
950
1075
6.0
5.5
10.9
9.9
DBFC 28
2500 (98¼)
3
9630 (20400)
320 (700)
3
950
1075
6.0
5.5
10.9
9.9
DBFC 30
3308 (130¼)
4
12838 (27200)
355 (780)
4
950
1075
8.0
7.3
14.6
13.2
DBFC 37
3308 (130¼)
4
12838 (27200)
380 (835)
4
950
1075
8.0
7.3
14.6
13.2
DBFC 40
3308 (130¼)
4
12838 (27200)
410 (900)
4
950
1075
8.0
7.3
14.6
13.2
NOTE: ALL DIMENSIONS ARE IN MM (INCHES).
REMOTE HEAT EXCHANGERS
CONDENSER/DRY-AIR COOLER DATA
CONDENSERS
MODEL
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
04
06
08
10
11
13
17
20
26
30
34
40
44
HEAT REJECTION
THR @ 35°C(95°F) AMB 52°C(125°F) COND
KW/°C
MBH/°F
KW
MBH
0.64
0.91
1.23
1.44
1.67
2.31
2.72
3.28
3.75
4.19
4.54
5.36
5.86
2.2
3.1
4.2
4.9
5.4
6.1
8.2
9.8
12.4
14.5
16.3
19.5
21.6
19.1
27.5
36.5
42.7
47.5
53.8
72.3
86.0
109.4
127.7
143.4
171.2
190.1
65.2
93.9
124.6
145.8
162.1
183.4
246.7
293.5
373.3
435.6
489.4
584.1
648.7
CONNECTION SIZE (INCH)
HOT GAS
1
1
1
1
1
1
1
1
1
1
1
1
1
LIQUID
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
3/8
3/8
5/8
5/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
1 1/8
1 1/8
DRY-AIR COOLER (BASED ON 40% GLYCOL-SEE TABLE 1 FOR CORRECTION FACTORS)
MODEL
DBFC
DBFC
DBFC
DBFC
DBFC
DBFC
DBFC
DBFC
DBFC
DBFC
DBFC
DBFC
05
06
09
11
15
17
21
24
28
30
37
40
NOMINAL
L/S
0.38
0.57
0.95
1.3
1.6
1.7
1.9
2.2
2.5
3.5
3.9
4.4
THR @ 35°C (95°F)
AMB 52°C (125°F)
COND
PRESSURE DROP
GPM
6
9
15
21
25
27
30
35
40
56
62
70
KPa
18.6
8.3
19.3
24.1
29.0
20.0
25.5
21.4
18.6
34.5
26.2
20.7
PSI
2.7
1.2
2.8
3.5
4.2
2.9
3.7
3.1
2.8
5.0
3.8
3.0
KW
11.9
16.0
24.9
30.9
40.7
45.0
55.8
64.5
71.7
85.2
95.3
103.4
MBH
40.6
54.5
84.9
105.6
139
153.7
190.6
220.2
244.8
290.8
325.3
353.0
NO. OF
CIRCUIT
CONN. SIZE
(INCH)
(1 EA PER UNIT)
INTERNAL VOLUME
INLET/OUTLET
1 3/8
1 5/8
1 5/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 5/8
4
8
10
10
12
16
16
21
26
24
32
40
LT
8.3
12.2
18.4
16.8
22.5
28.3
30.6
39.1
47.6
38.7
50.0
63.8
GAL
2.2
3.2
4.8
4.4
5.9
7.5
8.1
10.3
12.6
10.2
13.2
16.9
GLYCOL CORRECTION FACTORS
PERCENT GLYCOL
CAPACITY
PRESSURE DROP
0
10
20
30
40
50
1.07
1.05
1.04
1.02
1.00
0.98
0.88
0.91
0.94
0.97
1.00
1.03
FREEZE POINT
0°C
-3.8
-9.4
-32.2
-23.3
-35.6
32°F
25
15
4
-10
-32
CONDENSER SELECTIONS
MODEL
THR
DBTA 02
KW
11.7
MBH
40
DBTA 03
DBTA 04
DBTA 05
DBTA 07
DBTA 09
DBTA 11
DBTA 13
DBA 09
DBA 11
DBA 13
DBA 14
DBA 16
DBA 19
DBA 22
DBA 26
14.7
17.6
21.4
29.3
43.7
50.7
57.2
42.8
53.1
60.4
67.4
78.3
87.1
101.4
118.1
50
60
73
100
149
173
202
146
181
206
230
267
297
346
403
35°C(95°F)
37.8°C(100°F)
40.5°C(105°F)
CONDENSER
DBRC 04
CONDENSER
DBRC 04
CONDENSER
DBRC 04
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
04
06
06
08
10
13
17
10
13
17
17
20
20
26
30
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
04
06
06
10
13
17
17
13
17
17
20
26
26
30
34
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
DBRC
06
06
08
11
17
20
26
17
20
26
26
26
34
34
44
NOTE : SELECTIONS ARE BASED ON STANDARD AIR FLOWS, 125 DEGREE CONDENSING TEMPERATURE, RETURN AIR TEMPERATURE
75/62.5 OR LESS.
REMOTE HEAT EXCHANGERS
DRY-AIR COOLER SELECTIONS
MODEL
THR
KW
11.7
14.7
17.6
21.4
29.3
43.7
50.7
59.2
42.8
53.1
60.4
67.4
78.3
87.1
101.4
118.1
FLOW RATE
MBH
40
50
60
73
100
149
173
202
146
181
206
230
267
297
346
403
L/S
0.38
0.57
0.76
0.95
130
170
190
2.20
1.70
1.90
2.20
2.50
3.50
3.90
4.40
5.00
GPM
6
9
12
15
21
27
30
35
27
30
35
40
56
62
70
80
35°C(95°F)
COOLER
DBFC 5
DBFC 6
DBFC 9
DBFC 9
DBFC 11
DBFC 17
DBFC 21
DBFC 24
DBFC 17
DBFC 21
DBFC 24
DBFC 28
DBFC 30
DBFC 37
DBRC 40
(2)DBFC 24
DBTG 02
DBTG 03
DBTG 04
DBTG 05
DBTG 07
DBTG 09
DBTG 11
DBTG 13
DBG 09
DBG 11
DBG 13
DBG 14
DBG 16
DBG 19
DBG 22
DBG 26
ALL SELECTIONS ARE BASED ON THE FOLLOWING CONDITIONS :
PD,KPa
18.6
8.3
13.1
19.3
24.1
20.0
25.5
21.4
20.0
25.5
21.4
18.6
24.5
26.2
20.7
21.4
37.8°(100°F)
PD, PSI
2.7
1.2
1.9
2.8
3.5
2.9
3.7
3.1
2.9
3.7
3.1
2.8
3.5
3.8
3.0
3.1
COOLER
DBFC 9
DBFC 9
*DBFC 9
DBFC 15
DBFC 17
DBFC 24
DBFC 28
DBFC 30
DBFC 21
DBFC 28
DBFC 30
DBFC 37
(2) DBFC 21
(2) DBFC 24
(2) DBFC 28
(2)DAFC 30
PD,KPa
3.4
7.6
19.3
11.0
20.0
21.4
18.6
34.5
20.7
11.0
34.5
26.2
22.1
21.4
22.8
22.8
PD, PSI
0.5
1.1
2.8
1.6
2.9
3.1
2.8
5.0
3.0
1.6
5.0
3.8
3.2
3.1
3.3
3.3
RETURN AIR TEMPERATURE 75/62.5 OR LESS, STANDARD WATER FLOWS, STANDARD AIR FLOWS, 40 PERCENT GLYCOL, 125
DEGREE CONDENSING TEMPERATURE, 115 DEGREE AVERAGE FLUID TEMPERATURE. EXAMPLE :
SELECT DRY-AIR COOLER FOR DBGD 11 AT 95 DEGREE AMBIENT FROM CHART, USE DBFC 21
DBGD 11 (THR) TOTAL HEAT REJECTION IS = 173 MBH
DBFC 21 (CAP) CAPACITY IS = 191 MBH
DBAFC 21 (PD) PRESSURE DROP IS = 3.7 PSI AT 30 (GPM) GALLONS PER MIN.
OPTIONS AND ACCESSORIES
Hermetic Compressors
Includes:
Crankcase
accumulators.
atmospheres.
heaters,
suction
Hot Gas Bypass
Prevents compressor short-cycling in low
room load application.
Hot Water Or Steam Reheat
High Filter Efficiency Filters
65% (based on ASHRAE 52-76) efficiency.
25mm (2 inch) pre-filters available to reduce
main filter changes.
Condensate Pump
Smoke Detector
Complete with pump motor, pump, check
valve and automatic control. Available units
mounted and wired or externally mounted and
powered by either 220V/50Hz or 208230V/60Hz.
For systems shut down when smoke is
detected with manual reset.
Remote Panel Mount
Upflow Plenum
Remote mount of DB Processor available
with 3.0m or 15.0m cable.
These economical reheats are controlled by
two way valve. Completely piped, wired and
tested, at the factory.
Complete with attractive grilles for room
discharge of conditioned air.
Adjustable Leveling Jackstands
Allows raising or lowering of units with fully
adjustable rods. Locknuts assures rigidity.
Copper Fin Coils
For
use
in
high
humidity
corrosive
Under Floor Water Detection
Give an alarm signal when it detects water
under floor.
Variable Pitch Palley
Provides adjustable airflow capacity to match
load requirements.
SAMPLE NOMENCLATURE
DB-AIRE SERIES
UP AND DOWN FLOW UNITS
DB
A
D
11
AN
DB-AIRE
AN- 208/230 VOLT, 3 PHASE, 60HZ
AR- 460 VOLT, 3 PHASE, 60HZ
AV- 380 VOLT, 3 PHASE, 50HZ
AU- 415 VOLT, 3 PHASE, 50HZ
A- AIR COOLED
W- WATER COOLED
G- GLYCOL COOLED
C -CHILLED WATER
D- DOWN FLOW
U- UP FLOW
NOMINAL TONS
DB-TEMP SERIES
UP AND DOWN FLOW UNITS
DBT A
D
03
AN
DB-TEMP
AN - 208/230 VOLT, 3 PHASE, 60HZ
AR - 460 VOLT, 3 PHASE, 60HZ
AV - 380 VOLT, 3 PHASE, 50HZ
AU - 415 VOLT, 3 PHASE, 50HZ
A- AIR COOLED
W- WATER COOLED
G- GLYCOL COOLED
C -CHILLED WATER
D- DOWN FLOW
U- UP FLOW
NOMINAL TONS
AIR COOLED CONDENSER AND DRY FLUID COOLER
DBRC
DBFC- DRY-AIR COOLER
DBRC- AIR COOLED
CONDENSER
NOMINAL TONS
06
AN
AN - 208/230 VOLT, 3 PHASE, 60HZ
AV - 380 VOLT, 3 PHASE, 50HZ
AU - 415 VOLT, 3 PHASE, 50HZ