ICM Controls ICM317 Installation Guide

Add to my manuals
1 Pages

advertisement

ICM Controls ICM317 Installation Guide | Manualzz

ICM 317

DEFROST TIMER

SPECIFICATIONS

Input

Voltage: 18-30 VAC

Frequency: 50-60 Hz

Power consumption: 1 watt maximum

Outputs (CC, OUT)

Type: Relay

Form: SPST, normally open

Rating: 5 amps @ 240 VAC

Time Delays

Defrost time: Fixed at 10 minutes (± 5%)

Interval time between defrosts:

Pin-selectable 50/70/90 minutes

Power on reset time: 500 ms

Test time: Short across test terminals reduces test time by 256x

Anti-short cycle: 0 or 3 minute pin- selectable

Mechanical

Dimensions: 3.5” x 2.9”

Mounting: Surface mount using

(4) #6 or #8 screws

Environmental

Operating temperature:

-40˚C to 75˚C (-40˚F to 167˚F)

Transient Protection

• IEEE 587 Categories A&B without false output or degradation (6Kv 0.5µs x 100 Khz ring wave) (6Kv 1.2µs x 50 Khz impulse wave)

Compressor Run Times

Actual

Interval Time

Equivalent Test

Time

50 minutes fixed

70 minutes fixed

90 minutes fixed

11.72 seconds

16.41 seconds

21.09 seconds

WIRING DIAGRAM

Defrost Time

Actual

Defrost Time

Equivalent Test

Time

10 minutes fixed

10 minutes fixed

10 minutes fixed

2.34 seconds

2.34 seconds

2.34 seconds

ICM CONTROLS www.icmcontrols.com

7313 William Barry Blvd.

North Syracuse, NY 13212

800.365.5525

LII337