TT6080A IEC Safety Test
Test Report issued under the responsibility of
www.nemko.com
TEST REPORT
IEC 60950-1: 2005 (2nd Edition) and EN 60950-1:2006 + A11:2009
Information technology equipment – Safety –
Part 1: General requirements
Report Reference No...................... :
130708
Date of issue..................................... :
11 December 2009
Total number of pages ......................
56
CB/CCA Testing Laboratory Name : Nemko A/S
Phone: (+47) 22 96 03 30
Address ........................................... :
P.O. Box 73 Blindern, N-0314 Oslo, Norway
Applicant’s name............................ :
Thrane & Thrane A/S
Address ............................................ :
Lundtoftegaardsvej 93D, 2800 Kgs. Lyngby, Denmark
Manufacturer’s name ..................... :
Same as above
Address ............................................ :
Same as above
Factory’s name ............................... :
Same as above
Address ............................................ :
Same as above
Test specification:
Standard ........................................... :
IEC 60950-1:2005 (2nd Edition) and
EN 60950-1:2006 + A11:2009
Test procedure ................................. :
CB / CCA
Non-standard test method…………..:
N/A
Test Report Form No...................... :
IECEN60950_1C
Test Report Form(s) Originator...................... :
SGS Fimko Ltd (Nemko)
Master TRF ................................................... :
Dated 2007-06 (2008 02)
Copyright © 2007 IEC System for Conformity Testing and Certification of Electrical Equipment
(IECEE), Geneva, Switzerland. All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from
the reader's interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB Scheme
procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended
to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
If this Test Report Form is used by non-CCA members, the CIG logo and the reference to the CCA Procedure shall be
removed.
This report is not valid as a CCA Test Report unless signed by an approved CCA Testing Laboratory and
appended to a CCA Test Certificate issued by an NCB in accordance with CCA
This Test Report , when bearing the Nemko name and logo is only valid when issued by a Nemko laboratory,
or by a laboratory having special agreement with Nemko.
- Page 2 of 56 -
Report No. 130708
Test item description .....................:
Power supply
Trade Mark ....................................... :
Thrane & Thrane
Manufacturer .................................... :
Thrane & Thrane A/S
Model/Type reference....................... :
TT-6080A
Ratings ............................................. :
A.c. supply:
100 – 240 VAC, 47 – 63 Hz, 3.6A @ 100 VAC, 1.4 @ 240 VAC
D.c. supply: 24V, 30A
Testing procedure and testing location:
CB/CCA Testing Laboratory:
Testing location/ address ...................... :
Nemko A/S
P.O. Box 73 Blindern, N-0314 Oslo, Norway
Associated CB Laboratory:
Testing location/ address ...................... :
Tested by (name + signature) ..... :
Mikko Luusalo
Approved by (+ signature) ........... :
Ole Morten Aaslund
Summary of testing:
Tests performed (name of test and test clause):
Testing location:
Tested according to national requirements for the
countries listed below.
All tests performed at Nemko A/S, P.O. Box 73
Blindern, N-0314 Oslo, Norway
Summary of compliance with National Differences:
All CENELEC members as listed in EN 60950-1:2006.
TRF No. IECEN60950_1C
- Page 3 of 56 -
Report No. 130708
Copy of marking plate:
Warning marking for hot surfaces:
Markings at terminals:
List of attachments:
Photos (4 pages), Schematics and layouts (24 pages), Transformer specifications (2 pages)
TRF No. IECEN60950_1C
- Page 4 of 56 -
Report No. 130708
Test item particulars .................................................. :
Equipment mobility .................................................... : [] movable [] hand-held
[] transportable
[x] stationary [] for building-in [] direct plug-in
Connection to the mains............................................ : [] pluggable equipment [] type A [] type B
[x] permanent connection
[] detachable power supply cord
[] non-detachable power supply cord
[] not directly connected to the mains
Operating condition ................................................... : [x] continuous
[] rated operating / resting time:
Access location ......................................................... : [x] operator accessible
[] restricted access location
Over voltage category (OVC) ................................... : [] OVC I
[] other:
[x] OVC II
[] OVC III
Mains supply tolerance (%) or absolute mains supply
values ....................................................................... : -10% / +6%
Tested for IT power systems .................................... : [x] Yes (for Norway) [] No
IT testing, phase-phase voltage (V) .......................... : 230 V
Class of equipment ................................................... : [x] Class I [] Class II
[] Not classified
[] Class III
Considered current rating (A) ................................... : 16 A
Pollution degree (PD) ............................................... : [] PD 1
[x] PD 2
[] PD 3
IP protection class .................................................... : IP 20, minimum
Altitude during operation (m) .................................... : < 2000m
Altitude of test laboratory (m) ................................... : 100 m
Mass of equipment (kg) ............................................ : 3.7 kg
Possible test case verdicts:
- test case does not apply to the test object..................: N/A
- test object does meet the requirement .......................: P (Pass)
- test object does not meet the requirement .................: F (Fail)
Testing ..........................................................................:
Date of receipt of test item ............................................: July 2009
Date(s) of performance of tests ....................................: July 2009 – November 2009
TRF No. IECEN60950_1C
[] OVC IV
- Page 5 of 56 -
Report No. 130708
General remarks:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory.
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
Note: This TRF includes EN Group Differences together with National Differences and Special National
Conditions, if any. All Differences are located in the Appendix to the main body of this TRF.
Throughout this report a point is used as the decimal separator.
General product information:
The equipment under test is a power supply.
The equipment has single SELV d.c. output: 30V / 10A. Three units can be stacked and outputs chained to
form 30A output. Higher output currents can be achieved by connecting several supplies in parallel output
configuration.
The equipment is mounted with bolts through holes in enclosure. In stack of several units same bolts go
through all units.
The output represents energy hazard. Terminals for a.c. and d.c. connections are located behind a
protective cover.
The equipment is supplied from a.c. mains supply and has connection for back-up battery.
Maximum recommended ambient (Tmra): 55 °C
Connection to the supply:
Permanent connection with clamp terminals for wires.
1.1.2 - Additional requirements:
Exposure to extreme temperatures, excessive dust, moisture or vibration; to flammable gases; to corrosive
or explosive atmospheres:
This equipment is exposed to adverse environmental conditions and vibration. Separately tested for
applicable environmental conditions.
Electromedical equipment connected to the patient:
This equipment has not been considered as an electromedical equipment intended to be physically
connected to a patient.
TRF No. IECEN60950_1C
- Page 6 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
1
GENERAL
P
1.5
Components
P
1.5.1
General
Refer below:
P
Comply with IEC 60950-1 or relevant component
standard
(see appended table 1.5.1)
P
1.5.2
Evaluation and testing of components
Certified components are
used in accordance with their
ratings, certifications and they
comply with applicable parts
of this standard.
Components not certified are
used in accordance with their
ratings and they comply with
applicable parts of IEC 60950
and the relevant component
standard.
Components, for which no
relevant IEC-standard exists,
have been tested under the
conditions occurring in the
equipment, using applicable
parts of IEC 60950.
P
1.5.3
Thermal controls
No such thermal controls.
P
1.5.4
Transformers
Transformers used are
suitable for their intended
applications and comply with
relevant parts of this standard
and particularly Annex C, see
Annex C – Transformers.
P
1.5.5
Interconnecting cables
No interconnecting cables
provided with the equipment.
N/A
TRF No. IECEN60950_1C
Result - Remark
Verdict
- Page 7 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
1.5.6
Capacitors bridging insulation
X2 (C200, C201, C202, C203)
bridging functional insulation
between primary phases.
Verdict
P
Two Y2 in series (C612,
C613) bridging reinforced
insulation between primary
and secondary.
Y2 (C204, C205, C206)
bridging basic insulation
between primary and
protective earth.
Capacitors are certified
according to IEC 6038414:1993/EN132400:1994.
1.5.7
Resistors bridging insulation
Refer below:
P
1.5.7.1
Resistors bridging functional, basic or supplementary No specific requirements.
insulation
2.10.3 and 2.10.4 apply.
1.5.7.2
Resistors bridging double or reinforced insulation
between a.c. mains and other circuits
No such resistors.
N/A
1.5.7.3
Resistors bridging double or reinforced insulation
between a.c. mains and antenna or coaxial cable
No such resistors.
N/A
1.5.8
Components in equipment for IT power systems
All bridging components rated
for line to line voltage.
P
1.5.9
Surge suppressors
Refer below:
P
1.5.9.1
General
Varistor (RV201) in
compliance with Annex Q.
P
P
(see appended table 1.5.1)
1.5.9.2
Protection of VDRs
Protected by fuse.
P
1.5.9.3
Bridging of functional insulation by a VDR
Varistor (RV201) in
compliance with Annex Q.
P
(see appended table 1.5.1)
1.5.9.4
Bridging of basic insulation by a VDR
Not used.
N/A
1.5.9.5
Bridging of supplementary, double or reinforced
insulation by a VDR
Not used.
N/A
1.6
Power interface
1.6.1
AC power distribution systems
TRF No. IECEN60950_1C
P
TN system (IT for Norway)
P
- Page 8 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
1.6.2
Input current
(see appended table 1.6.2)
P
1.6.3
Voltage limit of hand-held equipment
Not a hand-held equipment.
N/A
1.6.4
Neutral conductor
Neutral insulated as if it was
line.
P
1.7
Marking and instructions
1.7.1
Power rating
The required marking is
located on the outside surface
of the equipment.
P
Rated voltage(s) or voltage range(s) (V) ............... :
100 – 240 VAC
P
P
D.c. supply: 24V
Symbol for nature of supply, for d.c. only............... :
The equipment is for a.c.
supply. Battery used as a
back up only.
N/A
Rated frequency or rated frequency range (Hz) ... :
47 – 63 Hz
P
Rated current (mA or A) ........................................ :
3.6A @ 100 VAC, 1.4 @ 240
VAC
P
D.c. supply: 30A
Manufacturer’s name or trade-mark or identification
mark ...................................................................... :
Thrane & Thrane A/S
P
Model identification or type reference ................... :
TT-6080A
P
Symbol for Class II equipment only ...................... :
The equipment is Class I.
Other markings and symbols ................................ :
The additional marking does
not give rise to
misunderstandings.
P
1.7.2
Safety instructions and marking
Refer below:
P
1.7.2.1
General
Provided with symbol IEC
60417-5041 for hot surfaces.
P
1.7.2.2
Disconnect devices
Disconnect device is
incorporated in the
equipment.
1.7.2.3
Overcurrent protective device
The equipment is provided
with overcurrent protective
device.
1.7.2.4
IT power distribution systems
TN (IT for Norway)
N/A
1.7.2.5
Operator access with a tool
No such operator access
area.
N/A
TRF No. IECEN60950_1C
N/A
N/A
P
- Page 9 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
1.2.7.6
Ozone
The equipment does not
produce ozone.
N/A
1.7.3
Short duty cycles
The equipment is intended for
continuous operation.
N/A
1.7.4
Supply voltage adjustment ................................... :
No voltage selector.
N/A
Methods and means of adjustment; reference to
installation instructions ......................................... :
-
N/A
1.7.5
Power outlets on the equipment .......................... :
No standard power outlets.
N/A
1.7.6
Fuse identification (marking, special fusing
characteristics, cross-reference) ......................... :
Marked in the marking label:
1.7.7
Wiring terminals
Refer below:
P
1.7.7.1
Protective earthing and bonding terminals ........... :
Protective earthing terminal is
marked with symbol IEC
60417-2 No. 5019 on PCB.
P
P
Mains Fuse: 6.3 AT
Battery Fuse: 2 x 30A
Protective bonding terminals
are marked with symbol IEC
60417-2 No. 5017 on PCB.
1.7.7.2
Terminals for a.c. mains supply conductors
Terminal for neutral is marked
with N.
P
1.7.7.3
Terminals for d.c. mains supply conductors
Battery terminals marked to
indicate polarity.
P
1.7.8
Controls and indicators
Refer below:
P
1.7.8.1
Identification, location and marking ..................... :
The function of controls and
indicators affecting safety is
obvious without knowledge of
language etc.
P
1.7.8.2
Colours ................................................................ :
Colours used for functional
indication only.
P
1.7.8.3
Symbols according to IEC 60417..........................:
Line for "ON" and circle for
"OFF" on power switch.
P
1.7.8.4
Markings using figures ........................................:
No such markings
1.7.9
Isolation of multiple power sources ......................:
Both supply connections are
adequately marked.
1.7.10
Thermostats and other regulating devices ...........:
No thermostats or other
regulating devices.
N/A
1.7.11
Durability
The marking withstands
required tests.
P
1.7.12
Removable parts
No removable parts.
TRF No. IECEN60950_1C
N/A
P
N/A
- Page 10 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
1.7.13
Replaceable batteries ..........................................:
No batteries in the equipment.
Language(s) .........................................................:
-
1.7.14
Equipment for restricted access locations ............:
Not intended to RAL.
2
PROTECTION FROM HAZARDS
P
2.1
Protection from electric shock and energy hazards
P
2.1.1
Protection in operator access areas
Refer below:
P
2.1.1.1
Access to energized parts
There is adequate protection
against operator contact with
bare parts at hazardous
voltages.
Checked by test finger and
test pin.
P
Test by inspection ................................................. :
-
P
Test with test finger (Figure 2A) ............................ :
-
P
Test with test pin (Figure 2B) ................................ :
-
P
Test with test probe (Figure 2C) ........................... :
-
N/A
2.1.1.2
Battery compartments
No batteries in the equipment.
N/A
2.1.1.3
Access to ELV wiring
No ELV circuits.
N/A
Working voltage (Vpeak or Vrms); minimum
distance through insulation (mm)
-
2.1.1.4
Access to hazardous voltage circuit wiring
No internal wiring.
2.1.1.5
Energy hazards ..................................................... :
Bridging of hazardous energy
parts is not likely. Tested with
test finger.
N/A

N/A

N/A
P
Outputs of the power supply
represents an energy hazard.
Outputs are adequately
protected from contact.
(see appended table 2.1.1.5)
2.1.1.6
Manual controls
Certified mains switch is
used.
P
2.1.1.7
Discharge of capacitors in equipment
Permanent connection.
N/A
Measured voltage (V); time-constant (s)................ :
-

Energy hazards – d.c. mains supply
Permanent connection. No
accessible disconnection
point.
P
2.1.1.8
TRF No. IECEN60950_1C
- Page 11 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
a) Capacitor connected to the d.c. mains supply .. :
E = 0.5 * 2.2 μF * (24 V) =
0.63 mJ
b) Internal battery connected to the d.c. mains
supply .................................................................... :
No batteries.
N/A
2.1.1.9
Audio amplifiers .................................................... :
No audio amplifiers
N/A
2.1.2
Protection in service access areas
Unintentional contact with
hazardous parts is not likely.
N/A
2.1.3
Protection in restricted access locations
Not intended to RAL.
N/A
2.2
SELV circuits
2.2.1
General requirements
SELV limits are not exceeded
under normal condition and
after a single fault.
P
2.2.2
Voltages under normal conditions (V) ................... :
Within SELV limits.
P
2.2.3
Voltages under fault conditions (V) ....................... :
Within SELV limits.
P
2.2.4
Connection of SELV circuits to other circuits .......:
SELV circuits are only
connected to other SELV
circuits, Limited current
circuits and protective earth.
P
2.3
TNV circuits
2
P
P
N/A
2.3.1 – 2.3.5; No TNV circuits in the equipment.
2.4
Limited current circuits
P
2.4.1
General requirements
Considered
P
2.4.2
Limit values
70 mA for frequency above
100 kHz.
P
Frequency (Hz) ...................................................... :
179 kHz

Measured current (mA) .......................................... :
1) By C612 + C613:
33 mA peak

2) By C612 (C613 shorted):
34.5 mA peak
Measured voltage (V)............................................. :
1) By C612 + C613:
66 mV peak
2) By C612 (C613 shorted):
69 mV peak
TRF No. IECEN60950_1C

- Page 12 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
Measured circuit capacitance (nF or µF) ............... :
<< 0.1 μF

2.4.3
Connection of limited current circuits to other
circuits
Meets the limits of 2.4.2 under
normal and single fault
condition.
P
2.5
Limited power sources
N/A
Limited power sources not considered.
2.6
Provisions for earthing and bonding
P
2.6.1
Protective earthing
Accessible conductive parts
are earthed.
2.6.2
Functional earthing
No such earthing.
2.6.3
Protective earthing and protective bonding
conductors
Refer below:
P
2.6.3.1
General
Refer below:
P
2.6.3.2
Size of protective earthing conductors
No such conductors. Only
earthing traces on PCB and
the enclosure.
2
2.6.3.3
Rated current (A), cross-sectional area (mm ),
AWG ...................................................................... :
-
Size of protective bonding conductors
No such conductors.
2
P
N/A
N/A

N/A

Rated current (A), cross-sectional area (mm ),
AWG ...................................................................... :
-
Protective current rating (A), cross-sectional area
2
(mm ), AWG .......................................................... :
-
Resistance of earthing conductors and their
terminations; resistance (), voltage drop (V), test
current (A), duration (min)...................................... :
Protective current rating: 16A
(20A for US/CAN)
2.6.3.5
Colour of insulation ................................................ :
No earthing wires.
2.6.4
Terminals
Refer below:
P
2.6.4.1
General
Refer below:
P
2.6.4.2
Protective earthing and bonding terminals
Main protective earthing
terminal located in same
terminal block with a.c. mains
supply connectors.
P
2.6.3.4
TRF No. IECEN60950_1C
P
Main protective earth terminal
to enclosure:
1.3 m, 41 mV, 32A, 2 min
1.2 m, 48 mV, 40A, 2 min
N/A
- Page 13 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Rated current (A), type, nominal thread diameter
(mm) ...................................................................... :
12 A, cage clamp terminal
Verdict

2.6.4.3
Separation of the protective earthing conductor from Separate terminals for
protective bonding conductors
protective bonding.
P
2.6.5
Integrity of protective earthing
Refer below:
P
2.6.5.1
Interconnection of equipment
Protective bonding provided
for equipment powered by d.c.
outputs.
P
2.6.5.2
Components in protective earthing conductors and
protective bonding conductors
No switches ore fuses in
protective bonding conductors
P
2.6.5.3
Disconnection of protective earth
The main earthing terminal is
adjacent to mains supply
terminals. Disconnection of
the earth without
disconnecting mains supply is
not likely.
P
2.6.5.4
Parts that can be removed by an operator
Permanent connection.
2.6.5.5
Parts removed during servicing
No need to remove earth
connection during servicing.
P
2.6.5.6
Corrosion resistance
Corrosion not considered
likely.
P
2.6.5.7
Screws for protective bonding
No self-tapping or spaced
thread screws.
N/A
2.6.5.8
Reliance on telecommunication network or cable
distribution system
No connection to TNV or
Cable distribution network.
N/A
2.7
Overcurrent and earth fault protection in primary circuits
P
2.7.1
Basic requirements
Refer below:
P
Instructions when protection relies on building
installation
Adequate fuses provided in
the equipment.
2.7.2
Faults not simulated in 5.3.7
Considered.
P
2.7.3
Short-circuit backup protection
Building installation provides
backup protection.
P
2.7.4
Number and location of protective devices ........... :
1 mains fuse holder adjacent
to a.c. mains switch.
P
2 fuses for both poles of
back-up battery adjacent to
battery terminal.
TRF No. IECEN60950_1C
N/A
N/A
- Page 14 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
2.7.5
Protection by several devices
Fuses for battery are located
together.
P
2.7.6
Warning to service personnel ................................ :
Not required. No fuse in
neutral.
P
2.8
Safety interlocks
N/A
2.8.1 – 2.8.8; No safety interlocks required. No hazard in operator access area.
2.9
Electrical insulation
P
2.9.1
Properties of insulating materials
Neither natural rubber,
materials containing asbestos
nor hygroscopic materials are
used as insulation. No driving
belts or couplings used.
2.9.2
Humidity conditioning
No hygroscopic insulation
materials.
Relative humidity (%), temperature (°C) ............... :
-

2.9.3
Grade of insulation
Basic between primary and
earth. Reinforced between
primary and secondary. Other
insulation is functional.
P
2.9.4
Separation from hazardous voltages
Refer below:
P
Method(s) used ..................................................... :
Method 1 used for secondary
circuits.

P
N/A
2.10
Clearances, creepage distances and distances through insulation
P
2.10.1
General
Refer below:
P
2.10.1.1
Frequency ............................................................. :
Switching frequency is 179
kHz. Normal values are used.
P
2.10.1.2
Pollution degrees ................................................... :
Pollution degree 2
P
2.10.1.3
Reduced values for functional insualtion
Complies with 5.3.4 a) and c)
P
2.10.1.4
Intervening unconnected conductive parts
Considered
P
2.10.1.5
Insulation with varying dimensions
No such insulation
N/A
2.10.1.6
Special separation requirements
No such circuits.
N/A
2.10.1.7
Insulation in circuits generating starting pulses
No such circuits.
N/A
2.10.2
Determination of working voltage
Refer below:
P
2.10.2.1
General
Refer below:
P
TRF No. IECEN60950_1C
- Page 15 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
2.10.2.2
RMS working voltage
(see appended table 2.10.2)
P
2.10.2.3
Peak working voltage
(see appended table 2.10.2)
P
2.10.3
Clearances
Refer below:
P
2.10.3.1
General
Refer below:
P
2.10.3.2
Mains transient voltages
Refer below:
P
a) AC mains supply ............................................... :
2500 V
P
b) Earthed d.c. mains supplies .............................. :
-
N/A
c) Unearthed d.c. mains supplies .......................... :
-
N/A
d) Battery operation ............................................... :
-
N/A
2.10.3.3
Clearances in primary circuits
(see appended table 2.10.3
and 2.10.4)
2.10.3.4
Clearances in secondary circuits
Insulation in secondary
circuits is only functional.
N/A
2.10.3.5
Clearances in circuits having starting pulses
No such circuits.
N/A
2.10.3.6
Transients from a.c. mains supply ........................ :
Insulation in secondary
circuits is only functional.
N/A
2.10.3.7
Transients from d.c. mains supply ........................ :
No transients from back-up
battery.
N/A
2.10.3.8
Transients from telecommunication networks and
cable distribution systems ..................................... :
Not connected to
telecommunication networks
or cable distribution systems
N/A
2.10.3.9
Measurement of transient voltage levels
Not applied.
N/A
a) Transients from a mains suplply
-
N/A
For an a.c. mains supply ....................................... :
-
N/A
For a d.c. mains supply ......................................... :
-
N/A
b) Transients from a telecommunication network :
-
N/A
2.10.4
Creepage distances
Refer below:
P
2.10.4.1
General
Refer below:
P
2.10.4.2
Material group and caomparative tracking index
Material group IIIb is assumed
to be used
P
CTI tests ................................................................. :
-

2.10.4.3
Minimum creepage distances
(see appended table 2.10.3
and 2.10.4)
P
2.10.5
Solid insulation
Refer below:
P
2.10.5.1
General
Refer below:
P
TRF No. IECEN60950_1C
Verdict
P
- Page 16 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
2.10.5.2
Distances through insulation
(see appended table 2.10.5)
2.10.5.3
Insulating compound as solid insulation
Not used.
2.10.5.4
Semiconductor devices
(see appended table 1.5.1)
P
2.10.5.5.
Cemented joints
Pre-preg board rated for
130°C. Complies with c).
P
2.10.5.6
Thin sheet material – General
Insulator on RV200.
(see appended table 1.5.1)
P
2.10.5.7
Separable thin sheet material
Single layer only.
P
Number of layers (pcs)........................................... :
1

2.10.5.8
Non-separable thin sheet material
-
N/A
2.10.5.9
Thin sheet material – standard test procedure
(see appended table 1.5.1)
P
Electric strength test
-

Thin sheet material – alternative test procedure
Not used.
Electric strength test
-

2.10.5.11
Insulation in wound components
Complies with Annex U.
P
2.10.5.12
Wire in wound components
Refer below:
P
Working voltage .................................................... :
(see appended table 2.10.2)
P
a) Basic insulation not under stress ...................... :
No such insulation.
b) Basic, supplemetary, reinforced insulation ....... :
Complies with annex U.
P
c) Compliance with Annex U ................................. :
(see appended table 1.5.1)
P
Two wires in contact inside wound component;
angle between 45 and 90 ................................... :
Tape is used as additional
protection between TIW and
wire crossing at 90°
P
Wire with solvent-based enamel in wound
components
Not used as insulation.
Electric strength test
-

Routine test
-
N/A
Additional insulation in wound components
Not used.
N/A
Working voltage .................................................... :
-
N/A
- Basic insulation not under stress ........................ :
-
N/A
- Supplemetary, reinforced insulation .................... :
-
N/A
2.10.6
Construction of printed boards
Refer below:
P
2.10.6.1
Uncoated printed boards
(see appended table 2.10.3
and 2.10.4)
P
2.10.5.10
2.10.5.13
2.10.5.14
TRF No. IECEN60950_1C
Verdict
P
N/A
N/A
N/A
N/A
- Page 17 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
2.10.6.2
Coated printed boards
No special coating in order to
reduce distances.
2.10.6.3
Insulation between conductors on the same inner
surface of a printed board
Pre-preg board rated for
130°C. See 2.10.5.5.
P
2.10.6.4
Insulation between conductors on different layers of
a printed board
Refer below:
P
Distance through insulation
(see appended table 2.10.5)
P
Number of insulation layers (pcs)........................... :
3
P
2.10.7
Component external terminations
No coatings used to decrease
insulation distances.
N/A
2.10.8
Tests on coated printed boards and coated
components
No coatings used to decrease
insulation distances.
N/A
2.10.8.1
Sample preparation and preliminary inspection
-
N/A
2.10.8.2
Thermal conditioning
-
N/A
2.10.8.3
Electric strength test
-
N/A
2.10.8.4
Abrasion resistance test
-
N/A
2.10.9
Thermal cycling
Not required.
N/A
2.10.10
Test for Pollution Degree 1 environment and
insulating compound
Not used.
N/A
2.10.11
Tests for semiconductor devices and cemented
joints
Pre-preg PCB. Test not
required. Optocouplers are
separately certified.
N/A
P
(see appended table 1.5.1)
2.10.12
Enclosed and sealed parts
3
WIRING, CONNECTIONS AND SUPPLY
P
3.1
General
P
3.1.1
Current rating and overcurrent protection
3.1.1. – 3.1.5; No internal
wiring
N/A
3.1.2
Protection against mechanical damage
-
N/A
3.1.3
Securing of internal wiring
-
N/A
3.1.4
Insulation of conductors
-
N/A
3.1.5
Beads and ceramic insulators
-
N/A
3.1.6
Screws for electrical contact pressure
No screws for electrical
contact pressure.
N/A
TRF No. IECEN60950_1C
Not used.
N/A
- Page 18 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
3.1.7
Insulating materials in electrical connections
No contact pressure through
insulating material.
3.1.8
Self-tapping and spaced thread screws
No such screws.
N/A
3.1.9
Termination of conductors
No internal wiring.
N/A
10 N pull test
-
N/A
3.1.10
Sleeving on wiring
Not used.
N/A
3.2
Connection to a mains supply
3.2.1
Means of connection
Refer below:
P
3.2.1.1
Connection to an a.c. mains supply
Permanent connection with
wiring terminals.
P
3.2.1.2
Connection to a d.c. mains supply
Permanent connection with
wiring terminals.
P
3.2.2
Multiple supply connections
Consideration has been
taken.
P
3.2.3
Permanently connected equipment
Set of terminals provided.
P
Number of conductors, diameter of cable and
conduits (mm) ....................................................... :
3 a.c. conductors and 2 d.c.
conductors. Knock outs for
cables up to 15 mm diameter.

3.2.4
Appliance inlets
Set of terminals provided.
N/A
3.2.5
Power supply cords
Set of terminals provided.
N/A
3.2.5.1
AC power supply cords
Set of terminals provided.
N/A
Type ...................................................................... :
-

Rated current (A), cross-sectional area (mm ),
AWG ..................................................................... :
-

3.2.5.2
DC power supply cords
Set of terminals provided.
N/A
3.2.6
Cord anchorages and strain relief
Permanent connection.
N/A
Mass of equipment (kg), pull (N) .......................... :
-

Longitudinal displacement (mm) ........................... :
-

3.2.7
Protection against mechanical damage
No sharp points or cutting
edges.
P
3.2.8
Cord guards
Permanent connection.
P
P
2
N/A
Diameter or minor dimension D (mm); test mass (g) ............................................................................... :

Radius of curvature of cord (mm) .......................... :

TRF No. IECEN60950_1C
-
- Page 19 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
3.2.9
Supply wiring space
Adequate supply wiring
space.
3.3
Wiring terminals for connection of external conductors
P
3.3.1
Wiring terminals
Cage clamp terminals.
P
3.3.2
Connection of non-detachable power supply cords
No such cord.
N/A
3.3.3
Screw terminals
Cage clamp terminals.
N/A
3.3.4
Conductor sizes to be connected
Refer below:
P
Rated current (A), cord/cable type, cross-sectional
2
area (mm )............................................................. :
A.c. supply: 3.6 A, flexible or
2
solid, 0.08 – 2.5 mm

P
D.c supply: 30 A, flexible, 0.2
2
– 6 mm
3.3.5
Wiring terminal sizes
Cage clamp terminals.
N/A
Rated current (A), type, nominal thread diameter
(mm) ..................................................................... :
-

3.3.6
Wiring terminal design
Adequate clamping pressure
between metal surfaces.
P
3.3.7
Grouping of wiring terminals
A.c. terminals located in same
terminal block with the main
protective earthing terminal.
P
D.c terminals located in
proximity to each other.
3.3.8
Stranded wire
3.4
Disconnection from the mains supply
3.4.1
General requirement
Mains switch is used as a
disconnection device.
P
3.4.2
Disconnect devices
Certified mains switch with
over 3 mm contact
separation.
P
3.4.3
Permanently connected equipment
Mains switch is used as a
disconnection device.
P
3.4.4
Parts which remain energized
Accidental contact not likely.
P
3.4.5
Switches in flexible cords
No cord provided.
3.4.6
Number of poles - single-phase and d.c. equipment
Switch disconnects both
poles.
TRF No. IECEN60950_1C
Loose strand does not contact
conductive parts.
P
P
N/A
P
- Page 20 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
3.4.7
Number of poles - three-phase equipment
Single phase equipment.
3.4.8
Switches as disconnect devices
Marked according to 1.7.8.
3.4.9
Plugs as disconnect devices
Not used.
3.4.10
Interconnected equipment
No interconnections using
hazardous voltages.
P
3.4.11
Multiple power sources
Adequately marked.
P
3.5
Interconnection of equipment
3.5.1
General requirements
See below:
N/A
3.5.2
Types of interconnection circuits .......................... :
SELV circuits
N/A
3.5.3
ELV circuits as interconnection circuits
No ELV.
N/A
3.5.4
Data ports for additional equipment
No data ports.
N/A
4
PHYSICAL REQUIREMENTS
P
4.1
Stability
P
N/A
P
N/A
P
Angle of 10
Unit does not overbalance at
10°.
P
Test force (N) ........................................................:
The unit is not floor-standing.
N/A
4.2
Mechanical strength
4.2.1
General
Complies with the
requirement also after tests
described below are applied.
P
4.2.2
Steady force test, 10 N
No hazard, ref. comment in
appended table 2.10.3,
2.10.4.
P
4.2.3
Steady force test, 30 N
No internal enclosure.
4.2.4
Steady force test, 250 N
No hazard. The test is
performed at all sides of the
enclosure.
P
4.2.5
Impact test
Refer below:
P
Fall test
No hazard as result from the
steel sphere fall test.
P
Swing test
No hazard as result from the
steel sphere swing test.
P
Drop test; height (mm) ...........................................:
Drop test not applicable.
4.2.6
TRF No. IECEN60950_1C
P
N/A
N/A
- Page 21 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
4.2.7
Stress relief test
Metal enclosure.
N/A
4.2.8
Cathode ray tubes
CRT(s) not used in the
equipment.
N/A
Picture tube separately certified ............................:
-
N/A
4.2.9
High pressure lamps
No high pressure lamps in the
equipment.
N/A
4.2.10
Wall or ceiling mounted equipment; force (N) .......:
The mounting means are
adequate.
4.3
Design and construction
4.3.1
Edges and corners
All edges and corners are
rounded and/or smoothed.
P
4.3.2
Handles and manual controls; force (N)............. :
No knobs, grips, handles,
lever etc.
N/A
4.3.3
Adjustable controls
No adjustable controls.
N/A
4.3.4
Securing of parts
No loosening of parts
impairing creepage distances
or clearances is likely to
occur.
4.3.5
Connection by plugs and sockets
No such connection.
N/A
4.3.6
Direct plug-in equipment
Not intended to plug directly
into a wall socket-outlet.
N/A
Torque ..................................................................:
-

Compliance with the relevant mains plug standard
...............................................................................:
-
N/A
4.3.7
Heating elements in earthed equipment
No heating elements
provided.
N/A
4.3.8
Batteries
No batteries in the equipment.
N/A
- Overcharging of a rechargeable battery
-
N/A
- Unintentional charging of a non-rechargeable
battery
-
N/A
- Reverse charging of a rechargeable battery
-
N/A
- Excessive discharging rate for any battery
-
N/A
Oil and grease
Insulation is not exposed to
oil, grease etc.
N/A
4.3.9
TRF No. IECEN60950_1C
P
P
P
- Page 22 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
4.3.10
Dust, powders, liquids and gases
The equipment does not
produce dust or use powders,
liquids or gasses.
N/A
4.3.11
Containers for liquids or gases
No containers for liquids or
gases in the equipment.
N/A
4.3.12
Flammable liquids ................................................:
The equipment does not
contain flammable liquid.
N/A
Quantity of liquid (l) ...............................................:
-
N/A
Flash point (C) ....................................................:
-
N/A
4.3.13
Radiation
Refer below:
N/A
4.3.13.1
General
Refer below:
N/A
4.3.13.2
Ionizing radiation
The equipment does not
generate ionizing radiation.
N/A
Measured radiation (pA/kg) ..................................:
-

Measured high-voltage (kV) .................................:
-

Measured focus voltage (kV) ................................:
-

CRT markings ......................................................:
-

Effect of ultraviolet (UV) radiation on materials
The equipment does not
produce UV radiation.
N/A
Part, property, retention after test, flammability
classification .........................................................:
-
N/A
4.3.13.4
Human exposure to ultraviolet (UV) radiation ......:
The equipment does not
produce UV radiation.
N/A
4.3.13.5
Laser (including LEDs)
No lasers or LEDs
N/A
Laser class ...........................................................:
-
4.3.13.6
Other types ...........................................................:
The equipment does not
generate other types of
radiation.
4.4
Protection against hazardous moving parts
4.4.1
General
No moving parts.
N/A
4.4.2
Protection in operator access areas .....................:
No moving parts.
N/A
4.4.3
Protection in restricted access locations ..............:
No moving parts.
N/A
4.4.4
Protection in service access areas
No moving parts.
N/A
4.5
Thermal requirements
4.3.13.3
TRF No. IECEN60950_1C
Verdict

N/A
N/A
P
- Page 23 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
4.5.1
General
Refer below:
P
4.5.2
Temperature tests
(see appended table 4.5)
P
Normal load condition per Annex L ......................:
Maximum rated load.

4.5.3
Temperature limits for materials
(see appended table 4.5)
P
4.5.4
Touch temperature limits
(see appended table 4.5)
P
4.5.5
Resistance to abnormal heat ................................:
Certified thermoplastic parts
are used.
P
4.6
Openings in enclosures
4.6.1
Top and side openings
Small openings around the
d.c. fuse connectors don’t
allow entry of objects.
P
Dimensions (mm) .................................................:
-

Bottoms of fire enclosures
Fire enclosure construction is
considered to comply with the
requirements. No bottom
openings.
P
Construction of the bottomm, dimensions (mm) ..:
-

4.6.3
Doors or covers in fire enclosures
No doors or covers in fire
enclosure.
N/A
4.6.4
Openings in transportable equipment
The unit is not regarded as
transportable equipment.
N/A
4.6.4.1
Constructional design measures
-
N/A
Dimensions (mm) .................................................:
-

4.6.4.2
Evaluation measures for larger openings
-
N/A
4.6.4.3
Use of metallized parts
-
N/A
4.6.5
Adhesives for constructional purposes
No barrier secured by
adhesive inside enclosure.
N/A
Conditioning temperature (C), time (weeks) ........:
-
4.6.2
Verdict
P

4.7
Resistance to fire
4.7.1
Reducing the risk of ignition and spread of flame
Method 1 is used.
P
Method 1, selection and application of components
wiring and materials
(see appended table 1.5.1)
P
Method 2, application of all of simulated fault
condition tests
-
TRF No. IECEN60950_1C
P
N/A
- Page 24 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
4.7.2
Conditions for a fire enclosure
Refer below:
P
4.7.2.1
Parts requiring a fire enclosure
The fire enclosure is required
to cover all parts except as
listed below.
P
4.7.2.2
Parts not requiring a fire enclosure
Terminal blocks.
P
4.7.3
Materials
4.7.3.1
General
Refer below:
P
4.7.3.2
Materials for fire enclosures
Metal enclosure.
P
4.7.3.3
Materials for components and other parts outside
fire enclosures
Terminals comply with
relevant IEC standards.
P
P
Terminal cover is of V-2
material.
(see appended table 1.5.1)
4.7.3.4
Materials for components and other parts inside fire Minimum V-2 or small parts
enclosures
mounted on PCB of minimum
V-0 material.
4.7.3.5
Materials for air filter assemblies
No air filters.
N/A
4.7.3.6
Materials used in high-voltage components
No high voltage components.
N/A
5
ELECTRICAL REQUIREMENTS AND SIMULATED ABNORMAL CONDITIONS
P
5.1
Touch current and protective conductor current
P
5.1.1
General
Test conducted in accordance
with 5.1.2 to 5.1.7.
5.1.2
Configuration of equipment under test (EUT)
Refer below:
5.1.2.1
Single connection to an a.c. mains supply
Single connection.
5.1.2.2
Redundant multiple connections to an a.c. mains
supply
-
N/A
5.1.2.3
Simultaneous multiple connections to an a.c. mains supply
N/A
5.1.3
Test circuit
Tested according to figure 5A
for star TN or TT distributions
system (and IT for Norway).
P
5.1.4
Application of measuring instrument
Measuring instrument D1 is
used.
P
5.1.5
Test procedure
Refer below:
P
5.1.6
Test measurements
(see appended table 5.1)
P
Supply voltage (V) ................................................:
254V

TRF No. IECEN60950_1C
P
P
P
- Page 25 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Measured touch current (mA) ...............................:
(see appended table 5.1)

Max. allowed touch current (mA) ..........................:
3.5mA (to PE)
0.25mA (to accessible parts)

Measured protective conductor current (mA) .......:
(see appended table 5.1)

Max. allowed protective conductor current (mA) ...:
3.5mA (to PE)

5.1.7
Equipment with touch current exceeding 3,5 mA
The touch current does not
exceed 3.5mA.
N/A
5.1.7.1
General .................................................................:
-
N/A
5.1.7.2
Simultaneous multiple connections to the supply
-
N/A
5.1.8
Touch currents to telecommunication networks and Not connected to a
cable distribution systems and from
telecommunication network
telecommunication networks
nor a cable distribution
system.
N/A
5.1.8.1
Limitation of the touch current to a
telecommunication network or to a cable
distribution system
-
N/A
Supply voltage (V) ................................................:
-

Measured touch current (mA) ...............................:
-

Max. allowed touch current (mA) ..........................:
-

Summation of touch currents from
telecommunication networks
-
N/A
a) EUT with earthed telecommunication ports .....:
-
N/A
b) EUT whose telecommunication ports have no
reference to protective earth
-
N/A
5.1.8.2
Verdict
5.2
Electric strength
5.2.1
General
(see appended table 5.2)
P
5.2.2
Test procedure
(see appended table 5.2)
P
5.3
Abnormal operating and fault conditions
5.3.1
Protection against overload and abnormal
operation
(see appended table 5.3)
5.3.2
Motors
No motors.
5.3.3
Transformers
See Annex C and appended
table C.2.
P
5.3.4
Functional insulation..............................................:
Complies with a) and c).
P
TRF No. IECEN60950_1C
P
P
P
N/A
- Page 26 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
5.3.5
Electromechanical components
No electromechanical
components.
N/A
5.3.6
Audio amplifiers in ITE ..........................................:
No audio amplifiers.
N/A
5.3.7
Simulation of faults
See the enclosed fault
condition tests.
P
5.3.8
Unattended equipment
Fault condition of the thermal
shut down was tested.
P
5.3.9
Compliance criteria for abnormal operating and
fault conditions
Refer below:
P
5.3.9.1
During the tests
No fire or molten metal
occurred and no deformation
of enclosure during the tests.
P
5.3.9.2
After the tests
No reduction of clearance and
creepage distances.
P
No visible signs of damage to
insulation.
Electric strength test is made
on basic, supplementary and
reinforced insulation.
6
CONNECTION TO TELECOMMUNICATION NETWORKS
N/A
6.1 – 6.3; No connection to telecommunication networks.
7
CONNECTION TO CABLE DISTRIBUTION SYSTEMS
7.1 – 7.4.3; No connection to cable distribution systems.
TRF No. IECEN60950_1C
N/A
- Page 27 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
A
ANNEX A, TESTS FOR RESISTANCE TO HEAT AND FIRE
Verdict
N/A
All materials have suitable flame class, no testing required.
B
ANNEX B, MOTOR TESTS UNDER ABNORMAL CONDITIONS (see 4.7.2.2 and
5.3.2)
N/A
No motors.
C
ANNEX C, TRANSFORMERS (see 1.5.4 and 5.3.3)
P
Position ................................................................. :
Primary to SELV

Manufacturer ........................................................ :
Thrane & Thrane

Type ..................................................................... :
T601: 127955B
L600: 127956A

Rated values ....................................................... :
Class F

Method of protection ............................................. :
Overcurrent protection.

The overloaded output shuts
down.
Fuses in secondary coils of
T601
C.1
Overload test
(see appended table 5.3)
P
C.2
Insulation
The insulation fulfil the
requirements in 2.10 and
relevant tests of 5.2.2.
P
Protection from displacement of windings ............:
Secured to the soldering pins
with wrapping.
P
D
ANNEX D, MEASURING INSTRUMENTS FOR TOUCH-CURRENT TESTS
(see 5.1.4)
P
D.1
Measuring instrument
Measuring instrument of
clause D.1 was used.
P
D.2
Alternative measuring instrument
-
E
ANNEX E, TEMPERATURE RISE OF A WINDING (see 1.4.13)
F
ANNEX F, MEASUREMENT OF CLEARANCES AND CREEPAGE DISTANCES
(see 2.10 and Annex G)
TRF No. IECEN60950_1C
N/A
N/A
P
- Page 28 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
G
ANNEX G, ALTERNATIVE METHOD FOR DETERMINING MINIMUM
CLEARANCES
N/A
H
ANNEX H, IONIZING RADIATION (see 4.3.13)
N/A
J
ANNEX J, TABLE OF ELECTROCHEMICAL POTENTIALS (see 2.6.5.6)
N/A
K
ANNEX K, THERMAL CONTROLS (see 1.5.3 and 5.3.8)
K.1
Making and breaking capacity
Thermal limiter shuts down
driver circuitry.
N/A
K.2
Thermostat reliability; operating voltage (V) ......... :
-
N/A
K.3
Thermostat endurance test; operating voltage (V)
.............................................................................. :
-
N/A
K.4
Temperature limiter endurance; operating voltage
(V) ........................................................................ :
Limiter circuit tested for 1000
cycles. No change.
K.5
Thermal cut-out reliability
-
K.6
Stability of operation
No noticeable change.
L
ANNEX L, NORMAL LOAD CONDITIONS FOR SOME TYPES OF ELECTRICAL
BUSINESS EQUIPMENT (see 1.2.2.1 and 4.5.2)
N/A
M
ANNEX M, CRITERIA FOR TELEPHONE RINGING SIGNALS (see 2.3.1)
N/A
N
ANNEX N, IMPULSE TEST GENERATORS (see 1.5.7.2, 1.5.7.3, 2.10.3.9, 6.2.2.1,
7.3.2, 7.4.3 and Clause G.5)
N/A
P
ANNEX P, NORMATIVE REFERENCES

Q
ANNEX Q, Voltage dependent resistors (VDRs) (see 1.5.9.1)
P
P
P
N/A
P
(see appended table 1.5.1)
R
ANNEX R, EXAMPLES OF REQUIREMENTS FOR QUALITY CONTROL
PROGRAMMES
TRF No. IECEN60950_1C
N/A
- Page 29 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
S
ANNEX S, PROCEDURE FOR IMPULSE TESTING (see 6.2.2.3)
N/A
T
ANNEX T, GUIDANCE ON PROTECTION AGAINST INGRESS OF WATER
(see 1.1.2)
N/A
U
ANNEX U, INSULATED WINDING WIRES FOR USE WITHOUT INTERLEAVED
INSULATION (see 2.10.5.4)
(see appended table 1.5.1)
V
ANNEX V, AC POWER DISTRIBUTION SYSTEMS (see 1.6.1)
W
ANNEX W, SUMMATION OF TOUCH CURRENTS
X
ANNEX X, MAXIMUM HEATING EFFECT IN TRANSFORMER TESTS (see clause
C.1)
Y
ANNEX Y, ULTRAVIOLET LIGHT CONDITIONING TEST (see 4.3.13.3)
Z
ANNEX Z, OVERVOLTAGE CATEGORIES (see 2.10.3.2 and Clause G.2)
AA
ANNEX AA, MANDREL TEST (see 2.10.5.8)
BB
ANNEX BB, CHANGES IN THE SECOND EDITION
TRF No. IECEN60950_1C
Verdict
P

P
N/A
P
N/A
P
N/A

- Page 30 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
EN 60950-1:2006 + A11:2009 – CENELEC COMMON MODIFICATIONS
Contents
Add the following annexes:
P
Annex ZA (normative)
Normative references to international publications
with their corresponding European publications
Annex ZB (normative)
Annex ZC (informative)
General
A-deviations
Delete all the “country” notes in the reference document according to the following
list:
1.4.8
1.5.8
2.2.3
2.3.2.1
2.7.1
3.2.1.1
4.3.6
4.7.3.1
6
6.2.2
7.1
G.2.1
1.3.Z1
Special national conditions
Note 2
Note 2
Note
Note 2
Note
Note
Note 1 & 2
Note 2
Note 2 & 5
Note 6.
Note 3
Note 2
1.5.1
1.5.9.4
2.2.4
2.3.4
2.10.3.2
3.2.4
4.7
5.1.7.1
6.1.2.1
2.2.1
7.2
Annex H
Note 2 & 3
Note
Note
Note 2
Note 2
Note 3.
Note 4
Note 3 & 4
Note 2
Note 2
Note
Note 2
1.5.7.1
1.7.2.1
2.3.2
2.6.3.3
2.10.5.13
2.5.1
4.7.2.2
5.3.7
6.1.2.2
6.2.2.2
7.3
P
Note
Note 4, 5 & 6
Note
Note 2 & 3
Note 3
Note 2
Note
Note 1
Note
Note
Note 1 & 2
Add the following subclause:
N/A
1.3.Z1 Exposure to excessive sound pressure
The apparatus shall be so designed and constructed as to present no danger when
used for its intended purpose, either in normal operating conditions or under fault
conditions, particularly providing protection against exposure to excessive sound
pressures from headphones or earphones.
NOTE Z1 A new method of measurement is described in EN 50332-1, Sound system
equipment:
Headphones and earphones associated with portable audio equipment - Maximum sound
pressure level measurement methodology and limit considerations - Part 1: General method
for “one package equipment”, and in EN 50332-2, Sound system equipment: Headphones
and earphones associated with portable audio equipment - Maximum sound pressure level
measurement methodology and limit considerations - Part 2: Guidelines to associate sets
with headphones coming from different manufacturers.
1.5.1
Add the following NOTE:
P
NOTE Z1 The use of certain substances in electrical and electronic equipment is restricted
within the EU: see Directive 2002/95/EC
1.7.2.1
Add the following NOTE:
NOTE Z1 In addition, the instructions shall include, as far as applicable, a warning that
excessive sound pressure from earphones and headphones can cause hearing loss
TRF No. IECEN60950_1C
N/A
- Page 31 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
2.7.1
Replace the subclause as follows:
Result - Remark
Verdict
P
Basic requirements
To protect against excessive current, short-circuits and earth faults in PRIMARY
CIRCUITS, protective devices shall be included either as integral parts of the
equipment or as parts of the building installation, subject to the following, a), b) and
c):
a) except as detailed in b) and c), protective devices necessary to comply with the
requirements of 5.3 shall be included as parts of the equipment;
b) for components in series with the mains input to the equipment such as the
supply cord, appliance coupler, r.f.i. filter and switch, short-circuit and earth fault
protection may be provided by protective devices in the building installation;
c) it is permitted for PLUGGABLE EQUIPMENT TYPE B or PERMANENTLY
CONNECTED EQUIPMENT, to rely on dedicated overcurrent and short-circuit
protection in the building installation, provided that the means of protection, e.g.
fuses or circuit breakers, is fully specified in the installation instructions.
If reliance is placed on protection in the building installation, the installation
instructions shall so state, except that for PLUGGABLE EQUIPMENT TYPE A the
building installation shall be regarded as providing protection in accordance with the
rating of the wall socket outlet.
2.7.2
This subclause has been declared ‘void’.
P
3.2.3
Delete the NOTE in Table 3A, and delete also in this table the conduit sizes in
parentheses.
N/A
3.2.5.1
Replace
N/A
“60245 IEC 53” by “H05 RR-F”;
“60227 IEC 52” by “H03 VV-F or H03 VVH2-F”;
“60227 IEC 53” by “H05 VV-F or H05 VVH2-F2”.
In Table 3B, replace the first four lines by the following:
| Up to and including 6
|
| Over 6 up to and including 10 |
| Over 10 up to and including 16 |
(0,75)
c)
(1,0)
0,75
1,0
1,5
b)
a)
|
|
|
In the conditions applicable to Table 3B delete the words “in some countries” in
a)
condition .
In NOTE 1, applicable to Table 3B, delete the second sentence.
3.3.4
In Table 3D, delete the fourth line: conductor sizes for 10 to 13 A, and replace with
the following:
| Over 10 up to and including 16 |
1,5 to 2,5
|
1,5 to 4
N/A
|
Delete the fifth line: conductor sizes for 13 to 16 A.
4.3.13.6
Add the following NOTE:
NOTE Z1 Attention is drawn to 1999/519/EC: Council Recommendation on the limitation of
exposure of the general public to electromagnetic fields 0 Hz to 300 GHz. Standards taking
into account this Recommendation which demonstrate compliance with the applicable EU
Directive are indicated in the OJEC.
TRF No. IECEN60950_1C
N/A
- Page 32 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Annex H
Replace the last paragraph of this annex by:
Result - Remark
Verdict
N/A
At any point 10 cm from the surface of the OPERATOR ACCESS AREA, the dose
rate shall not exceed 1 μSv/h (0,1 mR/h) (see NOTE). Account is taken of the
background level.
Replace the notes as follows:
NOTE These values appear in Directive 96/29/Euratom.
Delete NOTE 2.
Bibliography
Additional EN standards.

ZA
NORMATIVE REFERENCES TO INTERNATIONAL PUBLICATIONS WITH THEIR
CORRESPONDING EUROPEAN PUBLICATIONS

ZB
SPECIAL NATIONAL CONDITIONS
P
1.2.4.1
In Denmark, certain types of Class I appliances (see 3.2.1.1) may be provided with
a plug not establishing earthing conditions when inserted into Danish socket-outlets.
N/A
1.2.13.14
In Norway and Sweden, for requirements see 1.7.2.1 and 7.3 of this annex.
N/A
1.5.7.1
In Finland, Norway and Sweden, resistors bridging BASIC INSULATION in CLASS I
PLUGGABLE EQUIPMENT TYPE A must comply with the requirements in 1.5.7.1. In
addition when a single resistor is used, the resistor must withstand the resistor test
in 1.5.7.2.
N/A
1.5.8
In Norway, due to the IT power system used (see annex V, Figure V.7), capacitors
are required to be rated for the applicable line-to-line voltage (230 V).
P
1.5.9.4
In Finland, Norway and Sweden, the third dashed sentence is applicable only to
equipment as defined in 6.1.2.2 of this annex.
TRF No. IECEN60950_1C
N/A
- Page 33 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
1.7.2.1
In Finland, Norway and Sweden, CLASS I PLUGGABLE EQUIPMENT TYPE A
intended for connection to other equipment or a network shall, if safety relies on
connection to protective earth or if surge suppressors are connected between the
network terminals and accessible parts, have a marking stating that the equipment
must be connected to an earthed mains socket-outlet.
The marking text in the applicable countries shall be as follows:
In Finland: "Laite on liitettävä suojamaadoituskoskettimilla varustettuun
pistorasiaan"
In Norway: “Apparatet må tilkoples jordet stikkontakt”
In Sweden: “Apparaten skall anslutas till jordat uttag”
In Norway and Sweden, the screen of the cable distribution system is normally not
earthed at the entrance of the building and there is normally no equipotential
bonding system within the building. Therefore the protective earthing of the building
installation need to be isolated from the screen of a cable distribution system.
It is however accepted to provide the insulation external to the equipment by an
adapter or an interconnection cable with galvanic isolator, which may be provided
by e.g. a retailer.
The user manual shall then have the following or similar information in Norwegian
and Swedish language respectively, depending on in what country the equipment is
intended to be used in:
“Equipment connected to the protective earthing of the building installation through
the mains connection or through other equipment with a connection to protective
earthing – and to a cable distribution system using coaxial cable, may in some
circumstances create a fire hazard. Connection to a cable distribution system has
therefore to be provided through a device providing electrical isolation below a
certain frequency range (galvanic isolator, see EN 60728-11).”
NOTE In Norway, due to regulation for installations of cable distribution systems, and in Sweden, a
galvanic isolator shall provide electrical insulation below 5 MHz. The insulation shall withstand a
dielectric strength of 1,5 kV r.m.s., 50 Hz or 60 Hz, for 1 min.
Translation to Norwegian (the Swedish text will also be accepted in Norway):
“Utstyr som er koplet til beskyttelsesjord via nettplugg og/eller via annet jordtilkoplet
utstyr – og er tilkoplet et kabel-TV nett, kan forårsake brannfare. For å unngå dette
skal det ved tilkopling av utstyret til kabel-TV nettet installeres en galvanisk isolator
mellom utstyret og kabel- TV nettet.”
Translation to Swedish:
”Utrustning som är kopplad till skyddsjord via jordat vägguttag och/eller via annan
utrustning och samtidigt är kopplad till kabel-TV nät kan i vissa fall medfőra risk főr
brand. Főr att undvika detta skall vid anslutning av utrustningen till kabel-TV nät
galvanisk isolator finnas mellan utrustningen och kabel-TV nätet.”
TRF No. IECEN60950_1C
Verdict
N/A
- Page 34 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
1.7.5
In Denmark, socket-outlets for providing power to other equipment shall be in
accordance with the Heavy Current Regulations, Section 107-2-D1, Standard Sheet
DK 1-3a, DK 1-5a or DK 1-7a, when used on Class I equipment. For STATIONARY
EQUIPMENT the socket-outlet shall be in accordance with Standard Sheet DK 1-1b
or DK 1-5a.
Verdict
N/A
For CLASS II EQUIPMENT the socket outlet shall be in accordance with Standard
Sheet DKA 1-4a.
2.2.4
In Norway, for requirements see 1.7.2.1, 6.1.2.1 and 6.1.2.2 of this annex.
N/A
2.3.2
In Finland, Norway and Sweden there are additional requirements for the
insulation. See 6.1.2.1 and 6.1.2.2 of this annex.
N/A
2.3.4
In Norway, for requirements see 1.7.2.1, 6.1.2.1 and 6.1.2.2 of this annex.
N/A
2.6.3.3
In the United Kingdom, the current rating of the circuit shall be taken as 13 A, not
16 A.
N/A
2.7.1
In the United Kingdom, to protect against excessive currents and short-circuits in
the PRIMARY CIRCUIT of DIRECT PLUG-IN EQUIPMENT, tests according to 5.3
shall be conducted, using an external protective device rated 30 A or 32 A. If these
tests fail, suitable protective devices shall be included as integral parts of the
DIRECT PLUG-IN EQUIPMENT, so that the requirements of 5.3 are met.
N/A
2.10.5.13
In Finland, Norway and Sweden, there are additional requirements for the
insulation, see 6.1.2.1 and 6.1.2.2 of this annex.
N/A
3.2.1.1
In Switzerland, supply cords of equipment having a RATED CURRENT not
exceeding 10 A shall be provided with a plug complying with SEV 1011 or IEC
60884-1 and one of the following dimension sheets:
N/A
SEV 6532-2.1991
SEV 6533-2.1991
SEV 6534-2.1991
Plug Type 15
Plug Type 11
Plug Type 12
3P+N+PE
L+N
L+N+PE
250/400 V, 10 A
250 V, 10 A
250 V, 10 A
In general, EN 60309 applies for plugs for currents exceeding 10 A. However, a 16
A plug and socket-outlet system is being introduced in Switzerland, the plugs of
which are according to the following dimension sheets, published in February 1998:
SEV 5932-2.1998
SEV 5933-2.1998
SEV 5934-2.1998
3.2.1.1
Plug Type 25
Plug Type 21
Plug Type 23
3L+N+PE
L+N
L+N+PE
230/400 V, 16 A
250 V, 16 A
250 V, 16 A
In Denmark, supply cords of single-phase equipment having a rated current not
exceeding13 A shall be provided with a plug according to the Heavy Current
Regulations, Section 107-2-D1.
CLASS I EQUIPMENT provided with socket-outlets with earth contacts or which are
intended to be used in locations where protection against indirect contact is
required according to the wiring rules shall be provided with a plug in accordance
with standard sheet DK 2-1a or DK 2-5a.
If poly-phase equipment and single-phase equipment having a RATED CURRENT
exceeding 13 A is provided with a supply cord with a plug, this plug shall be in
accordance with the Heavy Current Regulations, Section 107-2-D1 or EN 60309-2.
TRF No. IECEN60950_1C
N/A
- Page 35 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
3.2.1.1
In Spain, supply cords of single-phase equipment having a rated current not
exceeding 10 A shall be provided with a plug according to UNE 20315:1994.
Verdict
N/A
Supply cords of single-phase equipment having a rated current not exceeding 2,5 A
shall be provided with a plug according to UNE-EN 50075:1993.
CLASS I EQUIPMENT provided with socket-outlets with earth contacts or which are
intended to be used in locations where protection against indirect contact is
required according to the wiring rules, shall be provided with a plug in accordance
with standard UNE 20315:1994.
If poly-phase equipment is provided with a supply cord with a plug, this plug shall be
in accordance with UNE-EN 60309-2.
3.2.1.1
In the United Kingdom, apparatus which is fitted with a flexible cable or cord and is
designed to be connected to a mains socket conforming to BS 1363 by means of
that flexible cable or cord and plug, shall be fitted with a ‘standard plug’ in
accordance with Statutory Instrument 1768:1994 - The Plugs and Sockets etc.
(Safety) Regulations 1994, unless exempted by those regulations.
N/A
NOTE ‘Standard plug’ is defined in SI 1768:1994 and essentially means an approved plug
conforming to BS 1363 or an approved conversion plug.
3.2.1.1
In Ireland, apparatus which is fitted with a flexible cable or cord and is designed to
be connected to a mains socket conforming to I.S. 411 by means of that flexible
cable or cord and plug, shall be fitted with a 13 A plug in accordance with Statutory
Instrument 525:1997 - National Standards Authority of Ireland (section 28) (13 A
Plugs and Conversion Adaptors for Domestic Use) Regulations 1997.
N/A
3.2.4
In Switzerland, for requirements see 3.2.1.1 of this annex.
N/A
3.2.5.1
In the United Kingdom, a power supply cord with conductor of 1,25 mm2 is
allowed for equipment with a rated current over 10 A and up to and including 13 A.
N/A
3.3.4
In the United Kingdom, the range of conductor sizes of flexible cords to be
accepted by terminals for equipment with a RATED CURRENT of over 10 A up to
and including 13 A is:
N/A
2
2
• 1,25 mm to 1,5 mm nominal cross-sectional area.
4.3.6
In the United Kingdom, the torque test is performed using a socket outlet
complying with BS 1363 part 1:1995, including Amendment 1:1997 and Amendment
2:2003 and the plug part of DIRECT PLUG-IN EQUIPMENT shall be assessed to
BS 1363: Part 1, 12.1, 12.2, 12.3, 12.9, 12.11, 12.12, 12.13, 12.16 and 12.17,
except that the test of 12.17 is performed at not less than 125 °C. Where the metal
earth pin is replaced by an Insulated Shutter Opening Device (ISOD), the
requirements of clauses 22.2 and 23 also apply.
N/A
4.3.6
In Ireland, DIRECT PLUG-IN EQUIPMENT is known as plug similar devices. Such
devices shall comply with Statutory Instrument 526:1997 - National Standards
Authority of Ireland (Section 28) (Electrical plugs, plug similar devices and sockets
for domestic use) Regulations, 1997.
N/A
TRF No. IECEN60950_1C
- Page 36 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
5.1.7.1
In Finland, Norway and Sweden TOUCH CURRENT measurement results
exceeding 3,5 mA r.m.s. are permitted only for the following equipment:
Verdict
N/A
• STATIONARY PLUGGABLE EQUIPMENT TYPE A that
○
is intended to be used in a RESTRICTED ACCESS LOCATION where
equipotential bonding has been applied, for example, in a
telecommunication centre; and
○
has provision for a permanently connected PROTECTIVE EARTHING
CONDUCTOR; and
○
is provided with instructions for the installation of that conductor by a
SERVICE PERSON;
• STATIONARY PLUGGABLE EQUIPMENT TYPE B;
• STATIONARY PERMANENTLY CONNECTED EQUIPMENT.
6.1.2.1
In Finland, Norway and Sweden, add the following text between the first and
second paragraph of the compliance clause:
If this insulation is solid, including insulation forming part of a component, it shall at
least consist of either
-
two layers of thin sheet material, each of which shall pass the electric
strength test below, or
-
one layer having a distance through insulation of at least 0,4 mm, which shall
pass the electric strength test below.
If this insulation forms part of a semiconductor component (e.g. an optocoupler),
there is no distance through insulation requirement for the insulation consisting of
an insulating compound completely filling the casing, so that CLEARANCES and
CREEPAGE DISTANCES do not exist, if the component passes the electric
strength test in accordance with the compliance clause below and in addition
-
passes the tests and inspection criteria of 2.10.11 with an electric strength
test of 1,5 kV multiplied by 1,6 (the electric strength test of 2.10.10 shall be
performed using 1,5 kV), and
-
is subject to ROUTINE TESTING for electric strength during manufacturing,
using a test voltage of 1,5 kV.
It is permitted to bridge this insulation with a capacitor complying with
EN 132400:1994, subclass Y2.
A capacitor classified Y3 according to EN 132400:1994, may bridge this insulation
under the following conditions:
-
the insulation requirements are satisfied by having a capacitor classified Y3
as defined by EN 132400, which in addition to the Y3 testing, is tested with
an impulse test of 2,5 kV defined in EN 60950-1:2006, 6.2.2.1;
-
the additional testing shall be performed on all the test specimens as
described in EN 132400;
-
the impulse test of 2,5 kV is to be performed before the endurance test in
EN 132400, in the sequence of tests as described in EN 132400.
TRF No. IECEN60950_1C
N/A
- Page 37 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
6.1.2.2
In Finland, Norway and Sweden, the exclusions are applicable for
PERMANENTLY CONNECTED EQUIPMENT, PLUGGABLE EQUIPMENT TYPE B
and equipment intended to be used in a RESTRICTED ACCESS LOCATION where
equipotential bonding has been applied, e.g. in a telecommunication centre, and
which has provision for a permanently connected PROTECTIVE EARTHING
CONDUCTOR and is provided with instructions for the installation of that conductor
by a SERVICE PERSON.
N/A
7.2
In Finland, Norway and Sweden, for requirements see 6.1.2.1 and 6.1.2.2 of this
annex.
N/A
The term TELECOMMUNICATION NETWORK in 6.1.2 being replaced by the term
CABLE DISTRIBUTION SYSTEM.
7.3
In Norway and Sweden, for requirements see 1.2.13.14 and 1.7.2.1 of this annex.
N/A
7.3
In Norway, for installation conditions see EN 60728-11:2005.
N/A
ZC
A-DEVIATIONS (informative)
P
1.5.1
Sweden (Ordinance 1990:944)
P
Add the following:
NOTE In Sweden, switches containing mercury are not permitted.
1.5.1
Switzerland (Ordinance on environmentally hazardous substances SR 814.081,
Annex 1.7, Mercury - Annex 1.7 of SR 814.81 applies for mercury.)
P
Add the following:
NOTE In Switzerland, switches containing mercury such as thermostats, relays and level
controllers are not allowed.
1.7.2.1
Denmark (Heavy Current Regulations)
Supply cords of CLASS I EQUIPMENT, which is delivered without a plug, must be
provided with a visible tag with the following text:
Vigtigt!
Lederen med grøn/gul isolation
må kun tilsluttes en klemme mærket
eller
If essential for the safety of the equipment, the tag must in addition be provided with
a diagram, which shows the connection of the other conductors, or be provided with
the following text:
“For tilslutning af de øvrige ledere, se medfølgende installationsvejledning.”
TRF No. IECEN60950_1C
N/A
- Page 38 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
1.7.2.1
Germany (Gesetz über technische Arbeitsmittel und Verbraucherprodukte (Geräteund Produktsicherheitsgesetz – GPSG) [Law on technical labour equipment and
consumer products], of 6th January 2004, Section 2, Article 4, Clause (4), Item 2).
Verdict
N/A
If for the assurance of safety and health certain rules during use, amending or
maintenance of a technical labour equipment or readymade consumer product are
to be followed, a manual in German language has to be delivered when placing the
product on the market.
Of this requirement, rules for use even only by SERVICE PERSONS are not
exempted.
1.7.5
Denmark (Heavy Current Regulations)
N/A
With the exception of CLASS II EQUIPMENT provided with a socket outlet in
accordance with the Heavy Current Regulations, Section 107-2-D1, Standard Sheet
DK 1-4a, CLASS II EQUIPMENT shall not be fitted with socket-outlets for providing
power to other equipment.
1.7.13
Switzerland (Ordinance on chemical hazardous risk reduction SR 814.81, Annex
2.15 Batteries)
N/A
Annex 2.15 of SR 814.81 applies for batteries.
5.1.7.1
Denmark (Heavy Current Regulations, Chapter 707, clause 707.4)
TOUCH CURRENT measurement results exceeding 3,5 mA r.m.s. are permitted
only for PERMANENTLY CONNECTED EQUIPMENT and PLUGGABLE
EQUIPMENT TYPE B.
TRF No. IECEN60950_1C
N/A
- Page 39 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
1.5.1
TABLE: List of critical components
Object/part No.
Manufacturer/
trademark
Result - Remark
Type/model
Enclosure
Various
Various
Terminal cover
material
Sabic
PCB
AC terminal
(J200)
Verdict
P
Technical data
Mark(s) of
1
conformity )
IEC 60950-1
Tested in the
unit
Lexan FXD921A V-2, min 1.5
mm
UL94
UL (E45329)
Various
Various
FR4, V-0, 4
layer board,
minimum 0.475
mm between
layers, min.
130°C, Electric
strength 3000V
UL94
UL
Wago
736-703
500V, 12A
IEC 60947-1
(UL: 300V, 10A) UL 60947-1
KEMA
UL (E45172)
AC Fuse holder Schurter
(H200)
FAU
250 VAC, 10A,
UL94 V-0, 85°C
IEC 60127-6
UL 512
VDE
UL (E39328)
AC Fuse
(F200)
Various
Various
T6.3A, 6.3 x 32
mm
IEC 60127-2
-
X-Capacitors
(C200, C201,
C202, C203,
C301, C302)
Vishay
MKP 3382 X2
275 VAC, 1μF,
X2, 105°C
IEC 60384-14
nd
2 ed
UL 1283
ENEC 02
Y-Capacitors
(C205, C206)
Vishay
IEC 60384-14
nd
2 ed
EN 132400
UL 1283
ENEC 16
IEC 60384-14
nd
2 ed
EN 132400
UL 1283
ENEC 16
Y-Capacitors
(C204, C612,
C613)
Mains switch
Vishay
Legion
MKP 3366 Y2
MKP 3366 Y2
Metal
Standard
(Edition / year)
300 VAC, 22
nF, Y2, 105°C
300 VAC, 4.7
nF, Y2, 105°C
UL (E109565)
UL (E109565)
UL (E109565)
SS21
250 VAC, 12 A IEC 61058-1
(UL: 10A), UL94 UL 1541
V-0, with lamp
N, VDE
UL (E153399)
Resistor (R200) Various
Various
1 Mohm
IEC 60950-1
Tested in the
unit
Resistors
(R201, R202)
Various
10 Mohm, Cl.
IEC 60950-1
min. 2.0 mm,
Cr. min. 2.5 mm
Tested in the
unit
Various
TRF No. IECEN60950_1C
- Page 40 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Varistor
(RV201)
Thinking
Result - Remark
Verdict
TRV20471
471 V, Type 3
2)
SPD
IEC 61051-2
rd
UL 1449 3 ed
VDE
UL (E314979)
Common mode Epcos
chokes (T200,
T201)
B82723A
250 VAC, 2.7
mH, 125 °C,
UL94 V-0
EN 60938-2
VDE
NTC resistior
(RV200)
Epcos
B57237
3.7A , 10 ohm at IEC 60950-1
25°C
Tested in the
unit
Insulating
tubing on
RV200
Qualtek
Q-200
200°C, 7.9
UL 224
kV/mm, min. 0.8
mm thick
UL (E245010)
Rectifying
Various
diodes (CR301,
CR303, CR305,
CR306)
Various
3A, 600V
IEC 60950-1
Tested in the
unit
Coupled Choke Flux
(L300)
12340029A1
Class F
IEC 60950-1
Tested in the
unit
Bobbin
DuPont
Rynite FR 530 L V-0
UL94
UL (E41938)
Wire
Various
Various
155°C minimum -
-
Bulk capacitors
(C303, C304,
C305)
Various
Various
450 V, 150 μF,
105°C
IEC 60950-1
Tested in the
unit
PWM Controller TI
(U500)
UCC38C43
-
IEC 60950-1
Tested in the
unit
Temperature
control circuit
(U401)
Microchip
TC6502
85°C operating
point
IEC 60950-1
Tested in the
unit
Temperature
control circuit
(U402)
Microchip
TC6502
75°C operating
point
IEC 60950-1
Tested in the
unit
Switching
transistors
(Q600, Q601)
Infineon
IPB60R385CP
650 V, 9 A
IEC 60950-1
Tested in the
unit
TRF No. IECEN60950_1C
- Page 41 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
Common mode Thrane &
choke (T602)
Thrane
L/T70
Bobbin
Sumitomo
Hexion
TE250F6
TE250F8
TS250F6
TS250F8
PM-9630
UP 3420
V-0
V-0
V-0
V-0
V-0
V-0
Various
Various
155°C minimum -
-
Various
Various
Polyester,
155°C minimum
-
Transformer
(T601)
Thrane &
Thrane
L/T65
Bobbin
DuPont
DSM
Sumitomo
FR-530
AV2365SN
PM-9630
V-0
V-0
V-0
UL 94
UL 94
UL 94
UL (E41938)
UL (E47960)
UL (E41429)
TIW
Great Leoflon
Totoku
Young Chang
TRW(F)
TIW-3
STW-F
Class F
Class F
Class F
UL 2353
UL 2353
UL 2353
UL (E211989)
UL (E166483)
UL (E242198)
Wire
Various
Various
155°C minimum -
-
4)
Various
Various
Polyester,
155°C minimum
-
Output fuses
Belfuse
SSQ 10
10 A, 86 VDC
UL 248-1
UL (E20624)
Wire
Tape
Tape
4)
DSM
UL 94
UL 94
UL 94
UL 94
UL 94
UL 94
UL (E43392)
UL (E43392)
UL (E172082)
UL (E172082)
UL (E41429)
UL (E61040)
Coupled Choke Thrane &
(L600)
Thrane
L/T66
Bobbin
DuPont
DSM
Sumitomo
FR-530
AV2365SN
PM-9630
V-0
V-0
V-0
UL 94
UL 94
UL 94
UL (E41938)
UL (E47960)
UL (E41429)
TIW
Great Leoflon
Totoku
Young Chang
TRW(F)
TIW-3
STW-F
Class F
Class F
Class F
UL 2353
UL 2353
UL 2353
UL (E211989)
UL (E166483)
UL (E242198)
Wire
Various
Various
155°C minimum -
-
Various
Various
Polyester,
155°C minimum
-
Tape
4)
TRF No. IECEN60950_1C
- Page 42 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
Optocouplers
(Q702, Q802)
Avago
HCPL-817
See Table: Opto IEC 60747-5-2
Electronic
UL 1577
Devices
CSA/UL 60950
VDE
UL (E55361)
CSA (1253038)
DC terminals
(J100, J101,
J102)
Wago
745-303
630V, 41A
IEC 60947-1
(UL: 300V, 30A) UL 60947-1
KEMA
UL (E45172)
DC input
fuseholders
(H100, H101)
Jenn Feng
JEF-703H
30A
IEC 60950-1
Tested in the
unit
Material
DuPont
Zytel 101L
V-2
UL 94
UL (E41938)
Thermal pads
Berquist
Gap Pad
1500S30
V-0, 200°C, min. IEC 60950-1
0.5 mm, 6000
VAC
Tested in the
unit
1
) An asterisk indicates a mark which assures the agreed level of surveillance
Supplementary information:
2) UL testing performed with 6 kV / 3 kA combination pulse and 15 pulses. Complies with Annex Q
requirements.
3) The component can touch the enclosure when 10N force is applied. Additional insulator is required.
4) Constructional purpose. Not used as basic, supplementary or reinforced insulation.
TRF No. IECEN60950_1C
- Page 43 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
1.5.1
TABLE: Opto Electronic Devices
Result - Remark
P
Manufacturer ............................................... :
Avago
Type............................................................. :
HCPL-817
Separately tested......................................... :
CSA
Bridging insulation ....................................... :
Reinforced
External creepage distance ......................... :
9.0
Internal creepage distance .......................... :
5.4
Distance through insulation ......................... :
0.4
Tested under the following conditions ......... :
5000 V rms
Input............................................................. :
Output.......................................................... :
Supplementary information:
TRF No. IECEN60950_1C
Verdict
- Page 44 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
1.6.2
TABLE: Electrical data (in normal conditions)
Verdict
P
U (V)
I (A)
Irated (A)
P (W)
Fuse #
Ifuse (A)
Condition/status
90
4.04
-
364
F200
4.04
Normal load (10A)
100
3.60
3.6
360
F200
3.60
Normal load (10A)
240
1.48
1.4
355
F200
1.48
Normal load (10A)
254
1.40
-
356
F200
1.40
Normal load (10A)
Supplementary information:
P
2.1.1.5 c1) TABLE: max. V, A, VA test
Voltage (rated)
(V)
Current (rated)
(A)
Voltage (max.)
(V)
Current (max.)
(A)
VA (max.)
(VA)
30
10
30.9
23.8
423
Supplementary information:
The +30V output from the power supply represents an energy hazard: 423 VA. Outputs are adequately
protected from contact.
P
2.1.1.5 c2) TABLE: stored energy
Capacitance C (µF)
Voltage U (V)
Energy E (J)
880
30
0.40
Supplementary information:
-6
E=0,5 CU² x 10
TRF No. IECEN60950_1C
- Page 45 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
2.2
TABLE: evaluation of voltage limiting components in SELV circuits
Component (measured between)
Result - Remark
max. voltage (V)
(normal operation)
Verdict
P
Voltage Limiting Components
V peak
V d.c.
T601 output (pins 7 – 9)
123
-
After CR601
85
31.5
CR601
-
31.5
CR601, L604
After L604
Fault test performed on voltage limiting components
L604 s-c
Voltage measured (V) in SELV circuits
(V peak or V d.c.)
See table 5.3
Supplementary information:
S-c = Short circuit
2.5
TABLE: limited power sources
N/A
Circuit output tested:
Measured Uoc (V) with all load circuits
disconnected:
Isc (A)
Meas.
Normal condition
Single fault:
Supplementary information:
TRF No. IECEN60950_1C
VA
Limit
Meas.
Limit
- Page 46 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
2.10.2
Table: working voltage measurement
Location
Result - Remark
RMS voltage (V)
P
Peak voltage (V) Comments
Voltages measured at L600:
Pin 1 – Pins 7 / 6
198
380
Pin 1 – Pins 8 / 5
198
376
Pin 1 – Pins 9 / 11
223
480
Pin 1 – Pins 10 / 12
222
412
Pin 2 – Pins 7 / 6
198
360
Pin 2 – Pins 8 / 5
199
392
Pin 2 – Pins 9 / 11
223
456
Pin 2 – Pins 10 / 12
223
396
Pin 2 – Pin 7
264
552
Pin 2 – Pin 9
216
472
Pin 2 – Pin 10
254
560
Pin 2 – Pin 12
204
488
Pin 5 – Pin 7
250
512
Pin 5 – Pin 9
278
576
Pin 5 – Pin 10
213
448
Pin 5 – Pin 12
263
528
Voltages measured at T601:
Supplementary information:
Tested with 100 – 240 V a.c. / Load 0 – 10 A
TRF No. IECEN60950_1C
Verdict
- Page 47 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
2.10.3 and
2.10.4
TABLE: Clearance and creepage distance measurements
Clearance (cl) and creepage
distance (cr) at/of/between:
Result - Remark
U peak
(V)
U r.m.s.
(V)
Required cl
(mm)
Verdict
P
cl
(mm)
Required cr
(mm)
cr
(mm)
Functional:
Primary before fuse L – N
339
240
1.5
8.0
2.5
8.0
Primary soldering pins –
Enclosure (below PCB)
576
278
2.3
3.0
2.8
-
Primary – Earth (on PCB)
576
278
2.3
4.0
2.8
4.0
Primary – Earth (on a.c.
terminal)
339
240
1.5
>8
2.5
>8
576
278
4.6
7.2
5.6
8.0
Basic/supplementary:
Reinforced:
Primary – Secondary (Q702 /
Q802)
Supplementary information:
Refer Annex C for distances in transformers.
2.10.5
TABLE: Distance through insulation measurements
Distance through insulation (DTI) at/of:
Thermal Pads (primary parts – enclosure)
Supplementary information:
TRF No. IECEN60950_1C
P
U peak
(V)
U rms
(V)
Test
voltage
(V)
Required DTI
(mm)
DTI
(mm)
576
278
1860
-
-
- Page 48 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
4.3.8
TABLE: Batteries
Result - Remark
N/A
Battery category........................................... :
Manufacturer ............................................... :
Type / model................................................ :
Voltage ........................................................ :
Capacity....................................................... :
Tested and Certified by (incl. Ref. No.) ....... :
Circuit protection diagram:
MARKINGS AND INSTRUCTIONS (1.7.12, 1.7.15)
Location of replaceable battery
Language(s):
Close to the battery
In the servicing instructions
In the operating instructions
TRF No. IECEN60950_1C
Verdict
- Page 49 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
4.3.8
TABLE: Batteries
Result - Remark
Verdict
N/A
The tests of 4.3.8 are applicable only when appropriate battery
data is not available
N/A
Is it possible to install the battery in a reverse polarity position?
N/A
Non-rechargeable batteries
Discharging
Meas.
current
Manuf.
Specs.
Unintentional
charging
Rechargeable batteries
Charging
Meas.
current
Manuf.
Specs.
Discharging
Meas.
current
Manuf.
Specs.
Reversed
charging
Meas.
current
Manuf.
Specs.
Max.
current
during
normal
condition
Max.
current
during
fault
condition
Test results:
Verdict
- Chemical leaks
N/A
- Explosion of the battery
N/A
- Emission of flame or expulsion of molten metal
N/A
- Electric strength tests of equipment after completion of tests
N/A
Supplementary information:
TRF No. IECEN60950_1C
- Page 50 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
4.5
TABLE: Thermal requirements, Three units stacked in horizontal position
P
Supply voltage (V) ........................... :
254
254
100
90

Ambient Tmax (C) ............................ :
25
55
55
22

Maximum measured temperature T of part/at::
Verdict
Allowed
Tmax
(C)
T (C)
1)
2)
2)
2)
C201
63
70
70
63
105
C204
61
70
69
62
100
T200
69
73
76
96
115
C206
62
71
71
65
100
C203
61
70
71
71
105
C306
65
72
72
68
105
L300
83
78
82
94
130
L600
92
80
75
80
130
T601
90
95
83
96
130
T602
88
86
79
79
130
PCB (near L600 and T601)
98
86
79
82
130
J101
73
72
69
61
-
J200
61
69
69
65
-
S200 (switch body)
65
77
70
62
85
H200
61
70
70
63
85
Enclosure top
65
71
70
65
3)
Enclosure bottom
66
74
73
67
3)
C612 / C613
86
80
74
74
105
Temperature T of winding:
t1 (°C)
R1 ()
t2 (°C)
R2 ()
T (C)
Allowed Insulation
class
Tmax (C)
Supplementary information:
1) Units daisy chained and loaded to single 30A load.
2) All 3 units are loaded to 10A.
3) Unintentional contact with the installed power supply is not likely. Symbol IEC 60417-5041 is used.
All measurements are performed on the middle unit of the stack.
TRF No. IECEN60950_1C
- Page 51 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
4.5
TABLE: Thermal requirements, Three units stacked in vertical position
P
Supply voltage (V) ........................... :
100
90
254

Ambient Tmax (C) ............................ :
55
55
55

T (C)
Allowed
Tmax
(C)
Maximum measured temperature T of part/at::
Verdict
1)
2)
1)
C201
69
69
69
105
C204
68
68
69
100
T200
75
75
72
115
C206
70
70
70
100
C203
70
70
70
105
C306
71
71
72
105
L300
82
82
78
130
L600
74
73
79
130
T601
82
79
94
130
T602
77
77
85
130
PCB (near L600 and T601)
76
76
85
130
J101
68
68
70
-
J200
67
67
68
-
S200
68
68
75
85
H200
68
68
69
85
Enclosure top
70
69
72
3)
Enclosure bottom
71
71
74
3)
C612 / C613
74
73
79
105
Temperature T of winding:
t1 (°C)
R1 ()
t2 (°C)
R2 ()
T (C)
Allowed Insulation
class
Tmax (C)
Supplementary information:
1) All 3 units are loaded to 10A.
2) All 3 units are loaded to 9A.
3) Unintentional contact with the installed power supply is not likely. Symbol IEC 60417-5041 is used.All
measurements are performed on the middle unit of the stack.
TRF No. IECEN60950_1C
- Page 52 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
4.5
TABLE: Thermal requirements, Single unit in horizontal position
Verdict
P
Supply voltage (V) ........................... :
90
254
90
254

Ambient Tmax (C) ............................ :
55
55
23
23

Maximum measured temperature T of part/at::
Allowed
Tmax
(C)
T (C)
C201
68
71
54
46
105
C204
68
71
53
45
100
T200
80
75
102
53
115
C206
70
71
57
45
100
C203
72
71
67
45
105
C306
71
73
60
49
105
L300
86
83
98
66
130
L600
76
87
79
70
130
T601
86
107
99
90
130
T602
79
88
74
64
130
PCB (near L600 and T601)
81
92
84
76
130
J101
69
75
57
52
-
J200
67
70
52
45
-
S200
69
76
54
52
85
H200
69
70
55
46
85
Enclosure top
68
71
50
43
1)
Enclosure bottom
69
73
61
52
1)
C612 / C613
74
85
71
63
105
Temperature T of winding:
t1 (°C)
R1 ()
t2 (°C)
R2 ()
T (C)
Allowed Insulation
class
Tmax (C)
Supplementary information:
Loaded to 10A in all measurements.
1) Unintentional contact with the installed power supply is not likely. Symbol IEC 60417-5041 is used.
TRF No. IECEN60950_1C
- Page 53 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
4.5.5
TABLE: Ball pressure test of thermoplastic parts
N/A
Allowed impression diameter (mm) .....................:  2 mm
Part
Verdict

Test temperature Impression diameter
(mm)
(C)
Supplementary information:
Certified thermoplastic parts.
4.7
TABLE: Resistance to fire
Part
P
Manufacturer of
material
Type of material
Thickness Flammability
(mm)
class
Evidence
Supplementary information:
See table 1.5.1.
5.1
P
TABLE: touch current measurement
Measured between:
Measured
(mA)
Limit
(mA)
Line – PE
1.8
3.5
254V, 50 Hz, Normal load
Neutral – PE
2.1
3.5
254V, 50 Hz, Normal load
Line – Output
0.08
0.25
254V, 50 Hz, Normal load
Neutral – Output
0.08
0.25
254V, 50 Hz, Normal load
Line – PE
1.8
3.5
254V, 50 Hz, No load
Neutral – PE
2.1
3.5
254V, 50 Hz, No load
Line – Output
0.03
0.25
254V, 50 Hz, No load
Neutral – Output
0.04
0.25
254V, 50 Hz, No load
Supplementary information:
TRF No. IECEN60950_1C
Comments/conditions
- Page 54 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
5.2
TABLE: Electric strength tests, impulse tests and voltage surge tests
Test voltage applied between:
Verdict
P
Voltage shape Test voltage Breakdown
(AC, DC,
(V)
Yes / No
impulse, surge)
Basic/supplementary:
Primary – Protective Earth
AC
1860
No
AC
3000
No
Reinforced:
Primary – Secondary
Supplementary information:
5.3
TABLE: Fault condition tests
Ambient temperature (C) ....................................:
23

Power source for EUT: Manufacturer, model/type,
output rating .........................................................:
Mains supply, isolating
transformer and variac.

Component
No.
U401
P
Fault
O-c
Supply
voltage
(V)
Test
time
Fuse #
Fuse
current
(A)
100
90 min
F200
3.61
Observation
Fault in middle unit of three unit
stack. All units loaded to 10A at
55°C ambient temperature.
Thermal shut down doesn’t
operate. Thermally stable
condition is reached.
Temperatures:
T601: 142°C
L600: 117°C
No hazard.
Q802, R803 S-c
240
1 min
F200
1.5
Normal operation. No increase in
output voltage. No hazard.
Q702, R715 S-c
240
15 min
F200
1.8
Maximum 34.3V at output. No
excessive temperature rise. No
hazard.
L600 (pin 7
– pin 8)
240
1 min
F200
1)
S-c
TRF No. IECEN60950_1C
Fuse blows immediately. The
equipment does not operate after
replacement of the fuse. No
hazard.
- Page 55 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
Output
O-l
100
15 min
F200
5.05
Output loaded to 15.2 A. The unit
stops operating after 10 minutes.
Circuitry is damaged (R327 has
burnt).
Output
S-c
240
5 min
F200
0.27
The unit shuts down. No hazard.
Fuse blows immediately. Normal
operation after replacement of
the fuse. No hazard.
S-c
240
1 min
F200
1)
C303,
S-c
C304, C305
240
15 min
F200
0.27
C302
Output 0V.
The equipment is damaged.
L300A open circuits and small
SMD components near U300 are
burnt.
No excessive temperature rise.
No hazard.
CR601
S-c
240
1 min
F200
0.28
TR601 output fuse blows
immediately. Normal operation
after replacement of the fuse. No
hazard.
Supplementary information:
1) 2.1 x fuse rating. Fuse blows every time when the fault in primary circuit is repeated 10 times.
TRF No. IECEN60950_1C
- Page 56 of 56 -
Report No. 130708
IEC/EN 60950-1
Clause
Requirement + Test
C.2
TABLE: transformers
Loc.
Tested insulation
Result - Remark
Verdict
P
Working
voltage
peak / V
Working
voltage
rms / V
Required
electric
strength
Required
clearance /
mm
(2.10.2)
(2.10.2)
(5.2)
(2.10.3)
Required
creepage
distance /
mm
(2.10.4)
Required
distance
thr. insul.
(2.10.5)
T601
Reinforced (primary –
secondary and core)
576
278
3000
Va.c.
4.6
5.6
*
L600
Reinforced (primary –
secondary and core)
480
223
3000
Va.c.
4.2
5.0
*
Loc.
Tested insulation
T601
Reinforced (primary – secondary and core)
3000
Va.c.
6.5
6.5
TIW
L600
Reinforced (primary – secondary and core)
3000
Va.c.
6.5
6.5
TIW
Supplementary information:
* 2 or 3 layers / 0.4mm / Annex U
TRF No. IECEN60950_1C
Test
voltage/
V
Measured
clearance /
mm
Measured
creepage
dist./ mm
Measured
distance
thr. insul. /
mm;
number of
layers
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement