Warning Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorised importer, distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any local legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
AIR CONDITIONING SYSTEM
COOLING ONLY
[
50
Hz ]
HE AT PUMP
[
50
Hz ]
PCS0316H
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.
JMI-0107 JQA-1452
About ISO 9001
ISO 9001 is a plant certification system defined by the International Organization for
Standardization (ISO) relating to quality assurance. ISO 9001 certification covers quality assurance aspects related to the
“ design, development, manufacture, installation, and supplementary service” of products manufactured at the plant.
About ISO 14001
ISO 14001 is the standard defined by the
International Organization for Standardization
(ISO) relating to environmental management systems. Our group has been acknowledged by an internationally accredited compliance organisation as having an appropriate programme of environmental protection procedures and activities to meet the requirements of ISO 14001.
Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan http://www.daikin.com/global_ac/
Printed in Japan 05/08/005 SW
•
HP
•
SS
Specifications, designs and other content appearing in this brochure are current as of May 2008 but subject to change without notice.
C r r e a tion of
C
1
Stores often feature the latest in designed decor.
This refined beauty attracts people.
Meanwhile, offices have a functional beauty.
This encourages those within to work hard and apply intelligence and passion to their tasks.
In either situation, a certain elegance should fill the space because thinking minds require high quality air conditioning. SkyAir by D aikin realise a comfortable indoor environment. All over the world, stores, offices, and homes prefer the low operating sound, attractive
2
3
Cooling only
Capacity
The values given for
1 HP is for FDGB type,
1.5 HP–6 HP is for FHYC type,
7 HP is for FDMG type,
8 HP–20 HP is for FD type.
HP kW
Btu/h kcal/h
CEILING MOUNTED
CASSETTE TYPE
Page 11– 14
Specifications
Dimensions
Page 39
Page 60
Indoor unit
Outdoor unit
CEILING SUSPENDED TYPE
Page 15– 16
Specifications
Dimensions
Page 39
Page 60
Indoor unit
Outdoor unit
CEILING SUSPENDED
CASSETTE TYPE
Page 17– 18
Specifications
Dimensions
Page 40
Page 61
Indoor unit
Outdoor unit
CEILING MOUNTED
CASSETTE CORNER TYPE
Page 19– 20
Specifications
Dimensions
Page 40
Page 61
Indoor unit
Outdoor unit
CEILING MOUNTED
BUILT-IN TYPE
Page 21– 22
Specifications
Dimensions
Page 41
Page 62
Indoor unit
Outdoor unit
WALL MOUNTED TYPE
Page 23– 24
Specifications
Dimensions
Page 41
Page 62,63
Indoor unit
Outdoor unit
1
2.6
8,900
2,250
FLOOR STANDING TYPE
Page 25– 26
Specifications
Dimensions
Page 42
Page 63
Indoor unit
Outdoor unit
PACKAGED AIR CONDITIONERS
LOW STATIC
PRESSURE TYPE
Specifications
Dimensions
Page 42
Page 64
Indoor unit
Outdoor unit
DUCT
CONNECTION
Page 27– 30
MIDDLE STATIC
PRESSURE TYPE
Specifications
Dimensions
Page 43
Page 64,65
FDBG25AVE
R25JV1
1.5
3.5
11,900
3,010
FHC35KVE
R35GV1
FH35BVE
R35GV1
FHK35FV1
R35GV1
FHB35FV1
R35GV1
2
5.3
18,100
4,560
FHC50KVE
R50GV1
FH50BVE
R50GV1
FHK45FV1
R50GV1
FHB45FV1
R50GV1
2.5
6.4
21,800
5,500
FHC60KVE
R60GV1
FH60BVE
R60GV1
FHK60FV1
R60GV1
FHB60FV1
R60GV1
3
7.7
26,200
6,600
FHYC71KVE FHYC100KVE
R71LUV1 / Y1 R100LUV1 / Y1
FHY71BVE
R71LUV1 / Y1
FHY100BVE
R100LUV1 / Y1
FUY71FJV1
R71LUV1 / Y1
FUY100FJV1
R100LUV1 / Y1
FHYK71FJV1
R71LUV1 / Y1
4
10.5
35,700
9,000
FHYB71FV1
R71LUV1 / Y1
FHYB100FV1
R100LUV1 / Y1
FAY71LVE
R71LUV1 / Y1
FAY100FAVE
R100LUV1 / Y1
FVY71LAVE FVY100LAVE
R71LUV1 / Y1 R100LUV1 / Y1
FDBG35AVE FDBG50AVE
R35JV1 R50GV1
FDBG60AVE FDBG71AVE
R60GV1 R71FUV1 / Y1
(FDMG)
(FDMG)
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
HIGH STATIC
PRESSURE TYPE
Specifications
Dimensions
Page 44,45
Page 65– 67
Indoor unit
Outdoor unit
Outdoor unit (Type without factory charged refrigerant)
(FDYM) (FDYM)
FDMG71AV1 FDMG100AV1
RG71AV1 / Y1 R100FUV1 / Y1
FDYM03FAV1 FDYM04FAV1
R71LUV1 / Y1 R100LUV1 / Y1
FD03KY1
R71FUY1
FD04KY1
R100FUY1
OUTDOOR UNIT
Page 33– 34
Dimensions Page 68– 74
R25JV1 R35GV1 R35JV1 R50GV1 R60GV1
R71LUV1
R71LUY1
R71FUY1
RG71AV1
RG71AY1
R100LUV1
R100LUY1
R100FUY1
R100FUV1
5
12.8
43,600
11,000
6
14.2
48,400
12,200
FHYC125KVE
R125LUY1
FHYC140KVE
R140LUY1
FHY125BVE
R125LUY1
FUY125FJV1
R125LUY1
7
16.8
57,500
14,400
8
24.0
81,800
20,600
10
29.2
99,600
25,100
15
47.9
163,500
41,200
20
58.4
199,400
50,200
FHYB125FV1
R125LUY1
FVY125LAVE
R125LUY1
(FDMG)
(FDMG)
(FDYM)
FDMG125AV1
R125FUY1
FDYM05FAV1
R125LUY1
FDMG140AV1
RG140AY1
FDYM06FAV1
R140LUY1
FDMG180AV1
RG180AY1
FD05KY1
R125FUY1
FD06KY1
RU06KY1
FD08KY1
RU08KUY1
RU08KY1
FD10KY1
RU10KUY1
RU10KY1
FD15KY1
RU08KUY1
×
2
RU08KY1
×
2
FD20KY1
RU10KUY1
×
2
RU10KY1
×
2
R125LUY1 R125FUY1 R140LUY1
RU06KY1
RG140AY1
RG180AY1
RU08KUY1
RU08KY1
RU10KUY1
RU10KY1
RU08KUY1
×
2
RU08KY1
×
2
RU10KUY1
×
2
RU10KY1
×
2
4
Cooling only
Simultaneous operation system TWIN MULTI OPERATION
Capacity
The values given on the right are for the FHYC type.
HP kW
Btu/h kcal/h
3
7.7
26,200
6,600
4
10.5
35,700
9,000
CEILING MOUNTED
CASSETTE TYPE
Indoor unit
Outdoor unit
FHYC35KVE
×
2
R71LUV1 / Y1
FHYC50KVE
×
2
R100LUV1 / Y1
5
12.8
43,600
11,000
FHYC60KVE
×
2
R125LUY1
CEILING SUSPENDED
TYPE
Indoor unit
Outdoor unit
DUCT CONNECTION
MIDDLE STATIC
PRESSURE TYPE
Indoor unit
Outdoor unit
FHY35BVE
×
2
R71LUV1 / Y1
FHY50BVE
×
2
R100LUV1 / Y1
FHY60BVE
×
2
R125LUY1
6
14.2
48,400
12,200
FHYC71KVE
×
2
R140LUY1
FHY71BVE
×
2
R140LUY1
5
OUTDOOR UNIT
Page 33– 34
R71LUV1
R71LUY1
R100LUV1
R100LUY1
Simultaneous operation system TRIPLE MULTI OPERATION
Capacity
The values given on the right are for the FHYC type.
HP kW
Btu/h kcal/h
6
14.2
48,400
12,200
CEILING MOUNTED
CASSETTE TYPE
Indoor unit
Outdoor unit
FHYC50KVE
×
3
R140LUY1
CEILING SUSPENDED
TYPE
Indoor unit
Outdoor unit
DUCT CONNECTION
MIDDLE STATIC
PRESSURE TYPE
Indoor unit
Outdoor unit
FHY50BVE
×
3
R140LUY1
R125LUY1 R140LUY1
Page 31– 32
Specifications Page 46– 48
8
22.2
75,800
19,100
FHYC71KVE
×
3
R200KUY1
FHY71BVE
×
3
R200KUY1
FDYM03FAV1
×
3
R200KUY1
OUTDOOR UNIT
Page 33– 34
R140LUY1 R200KUY1
8
22.2
75,800
19,100
FHYC100KVE
×
2
R200KUY1
Page 31– 32
Specifications Page 46– 48
10
26.6
90,800
22,900
Simultaneously running
2 to 4 units distributes comfort across wide spaces.
FHYC125KVE
×
2
R250KUY1
Simultaneous control with
2 units in spacious space
FHY125BVE
×
2
R250KUY1
FHY100BVE
×
2
R200KUY1
FDYM04FAV1
×
2
R200KUY1
FDYM05FAV1
×
2
R250KUY1
Simultaneous control with
3 units for irregularly shaped space
R200KUY1 R250KUY1
Simultaneous operation system
8
22.2
75,800
19,100
DOUBLE TWIN MULTI
OPERATION
10
Page 31– 32
Specifications Page 46– 48
26.6
90,800
22,900
FHYC50KVE
×
4
R200KUY1
FHYC60KVE
×
4
R250KUY1
FHY50BVE
×
4
R200KUY1
FHY60BVE
×
4
R250KUY1
Simultaneous control with
4 units for large space
R200KUY1 R250KUY1
6
7
Capacity HP
Cooling
The values given on the right are for the FHYC type. Values for other types may differ slightly.
The values given for 8HP to 20HP are for the FDY type.
Heating
CEILING MOUNTED
CASSETTE TYPE
Page 11– 14
Specifications
Dimensions
Page 49
Page 60 kW
Btu/h kcal/h kW
Btu/h kcal/h
Heat pump
1.5
3.75
12,800
3,230
4.22
14,400
3,630
2
5.2
17,800
4,470
5.8
19,800
4,990
Indoor unit
Outdoor unit
FHYC35KVE
RY35FV1A
FHYC50KVE
RY50GAV1A
2.5
6.15
21,000
5,290
7.0
23,900
6,020
3
7.7
26,200
6,600
7.9
27,000
6,800
FHYC60KVE
RY60GAV1A
FHYC71KVE
RY71LUV1 / Y1
CEILING SUSPENDED TYPE
Page 15– 16 Specifications
Dimensions
Page 49
Page 60
Indoor unit
Outdoor unit
CEILING SUSPENDED
CASSETTE TYPE
Page 17– 18 Specifications
Dimensions
Page 50
Page 61
Indoor unit
Outdoor unit
CEILING MOUNTED
CASSETTE CORNER TYPE
Page 19– 20 Specifications
Dimensions
Page 50
Page 61
FHY35BVE
RY35FV1A
Indoor unit
Outdoor unit
FHYK35FJV1
RY35FV1A
CEILING MOUNTED
BUILT-IN TYPE
Page 21– 22 Specifications
Dimensions
Page 51
Page 62
Indoor unit
Outdoor unit
FHYB35FV1
RY35FV1A
WALL MOUNTED TYPE
Page 23– 24
Specifications
Dimensions
Page 51
Page 62,63
Indoor unit
Outdoor unit
FHY50BVE
RY50GAV1A
FHYK45FJV1
RY50GAV1A
FHYB45FV1
RY50GAV1A
FHY60BVE
RY60GAV1A
FHYK60FJV1
RY60GAV1A
FHYK71FJV1
RY71LUV1 / Y1
FHYB60FV1
RY60GAV1A
FHY71BVE
RY71LUV1 / Y1
FUY71FJV1
RY71LUV1 / Y1
FHYB71FV1
RY71LUV1 / Y1
FAY71LVE
RY71LUV1 / Y1
FLOOR STANDING TYPE
Page 25– 26 Specifications
Dimensions
Page 52
Page 63
Indoor unit
Outdoor unit
PACKAGED AIR CONDITIONERS
DUCT
CONNECTION
LOW STATIC
PRESSURE TYPE
Specifications
Dimensions
Page 52
Page 64
Indoor unit
Outdoor unit
Page 27– 30
MIDDLE STATIC
PRESSURE TYPE
Specifications
Dimensions
Page 53
Page 64,65
Indoor unit
Outdoor unit
HIGH STATIC
PRESSURE TYPE
Specifications
Dimensions
Page 54
Page 65– 67
Indoor unit
Outdoor unit
FDYB35KAVE
RY35FV1A
FVY71LAVE
RY71LUV1 / Y1
FDYB50KAVE
RY50GAV1A
FDYB60KAVE
RY60GAV1A
FDYB71KAVE
RY71LUV1 / Y1
FDYM03FAV1
RY71LUV1 / Y1
OUTDOOR UNIT
Page 33– 34
Dimensions Page 68– 74
RY35FV1A RY50GAV1A RY60GAV1A
RY71LUV1
RY71LUY1
4
10.4
35,300
8,900
11.2
38,100
9,600
5
12.8
43,600
11,000
14.2
48,400
12,200
6
14.2
48,400
12,220
16.3
56,000
14,000
FHYC100KVE
RY100LUV1 / Y1
FHYC125KVE
RY125LUY1
FHYC140KVE
RY140LUY1
FHY100BVE
RY100LUV1 / Y1
FHY125BVE
RY125LUY1
FUY100FJV1
RY100LUV1 / Y1
FUY125FJV1
RY125LUY1
8
22.2
75,700
19,100
23.2
79,200
20,000
10
27.1
92,500
23,300
29.5
100,700
25,400
15
43.5
148,000
37,400
44.8
153,000
38,500
20
53.0
181,000
45,600
56.8
194,000
48,800
FHYB100FV1
RY100LUV1 / Y1
FHYB125FV1
RY125LUY1
FAY100FAVE
RY100LUV1 / Y1
FVY100LAVE
RY100LUV1 / Y1
FVY125LAVE
RY125LUY1
FDYM04FAV1
RY100LUV1 / Y1
FDYM05FAV1
RY125LUY1
FDYM06FAV1
RY140LUY1
FDY06KAY1
RY140LUY1
FDY08KAY1
RY200KUY1
FDY10KAY1
RY250KUY1
FDY15KAY1 FDY20KAY1
RY200KUY1
×
2 RY250KUY1
×
2
RY100LUV1
RY100LUY1
RY125LUY1
RY140LUY1 RY200KUY1 RY250KUY1 RY200KUY1
×
2 RY250KUY1
×
2 8
Heat pump
Simultaneous operation system TWIN MULTI OPERATION
Capacity
Cooling / Heating
The values given on the right are for the FHYC type.
HP kW
Btu/h kcal/h
3
7.7/7.9
26,200/27,000
6,600/6,800
4
10.4/11.2
35,300/38,100
8,900/9,600
CEILING MOUNTED
CASSETTE TYPE
Indoor unit
Outdoor unit
FHYC35KVE
×
2
RY71LUV1 / Y1
FHYC50KVE
×
2
RY100LUV1 / Y1
CEILING SUSPENDED
TYPE
Indoor unit
Outdoor unit
DUCT CONNECTION
MIDDLE STATIC
PRESSURE TYPE
Indoor unit
Outdoor unit
FHY35BVE
×
2
RY71LUV1 / Y1
FHY50BVE
×
2
RY100LUV1 / Y1
5
12.8/14.2
43,600/48,400
11,000/12,200
FHYC60KVE
×
2
RY125LUY1
FHY60BVE
×
2
RY125LUY1
6
14.2/16.3
48,400/56,000
12,200/14,000
FHYC71KVE
×
2
RY140LUY1
FHY71BVE
×
2
RY140LUY1
9
OUTDOOR UNIT
Page 33– 34
RY71LUV1
RY71LUY1
RY100LUV1
RY100LUY1
Simultaneous operation system TRIPLE MULTI OPERATION
Capacity
Cooling / Heating
The values given on the right are for the FHYC type.
HP kW
Btu/h kcal/h
14.2/16.3
48,400/56,000
12,200/14,000
CEILING MOUNTED
CASSETTE TYPE
Indoor unit
Outdoor unit
FHYC50KVE
×
3
RY140LUY1
CEILING SUSPENDED
TYPE
Indoor unit
Outdoor unit
DUCT CONNECTION
LOW STATIC
PRESSURE TYPE
Indoor unit
Outdoor unit
DUCT CONNECTION
MIDDLE STATIC
PRESSURE TYPE
Indoor unit
Outdoor unit
FHY50BVE
×
3
RY140LUY1
RY125LUY1 RY140LUY1
Page 31– 32
Specifications Page 54– 56
8
22.2/22.7
75,800/77,500
19,100/19,500
FHYC71KVE
×
3
RY200KUY1
FHY71BVE
×
3
RY200KUY1
FDYB71KAVE
×
3
RY200KUY1
FDYM03FAV1
×
3
RY200KUY1
OUTDOOR UNIT
Page 33– 34
RY140LUY1 RY200KUY1
8
22.2/22.7
75,800/77,500
19,100/19,500
FHYC100KVE
×
2
RY200KUY1
FHY100BVE
×
2
RY200KUY1
FDYM04FAV1
×
2
RY200KUY1
Page 31– 32
Specifications Page 54– 56
10
26.6/28.4
90,800/97,000
22,900/24,400
Simultaneously running
2 to 4 units distributes comfort across wide spaces.
FHYC125KVE
×
2
RY250KUY1
Simultaneous control with
2 units in spacious space
FHY125BVE
×
2
RY250KUY1
FDYM05FAV1
×
2
RY250KUY1
Simultaneous control with
3 units for irregularly shaped space
RY200KUY1 RY250KUY1
Simultaneous operation system
8
DOUBLE TWIN MULTI
OPERATION
22.2/22.7
75,800/77,500
19,100/19,500
Page 31– 32
Specifications Page 54– 56
26.6/28.4
90,800/97,000
22,900/24,400
FHYC50KVE
×
4
RY200KUY1
FHY50BVE
X
4
RY200KUY1
FDYB50KAVE
×
4
RY200KUY1
FHYC60KVE
×
4
RY250KUY1
FHY60BVE
×
4
RY250KUY1
FDYB60KAVE
×
4
RY250KUY1
Simultaneous control with
4 units for large space
RY200KUY1 RY250KUY1
10
11
CEILING MOUNTED
CASSETTE TYPE
FH ( Y ) C
Cooling only
Heat pump
FH(Y)C35KVE–140KVE
FHYC35KVE–140KVE
Sound level
35 / 30 dB(A)
High Low
FHYC71K
Quiet, decor-blending form and easy installation in new or old buildings.
Accessory required for indoor unit (option)
Wired LCD remote controller Wireless LCD remote controller
A signal receiver must be added to the indoor unit.
BRC1C61
Note: R emote controller cable not included. C ables must be procured locally.
Cooling only
BRC7C613W
Heat pump
BRC7C612W
Signal receiver unit
(Installed type)
Wireless remote controller and signal receiver unit are sold as a set.
Guide Line up
P. 3–10
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Standard specifications
P. 39, 46, 49, 54
Options
P. 57
Outer dimension drawings
P. 60
Unified square panels
All models from the 35K to 140K use the same size panel. Multiple unit installations maintain a physical uniformity that is aesthetically pleasing and make it easier to plan ceiling lighting systems and to design interiors.
950 mm
Same for all models
Compact body and quiet operation
Indoor units use an aerodynamically designed
Diffuser Turbo Fan
Diffuser
B lade
Draft resistance has been reduced by incorporating, into a single unit, an impeller and a diffuser to control air flow inside the unit. The Diffuser
Turbo Fan is both quiet during operation and compact.
dB(A)
Indoor unit
35K
50K
60K
71K
100K
125K
140K
High
33
33
35
35
39
42
44
Low
29
29
30
30
34
36
37
Note : Anechoic chamber conversion value, measured according to J IS parameters and
CEILING MOUNTED CASSETTE TYPE
Optimal comfort and convenience assured by 3 air discharge modes
Air direction
Desired situation
Draft prevention setting Standard setting Setting to prevent soiling of ceiling
When drafts are unwanted For gentle drafts
(Ceiling is soiled.)
When ceilings must be kept spotless
Auto-swing
Auto-swing between
10 ° and 40°
Auto-swing between
10 ° and 65°
Auto-swing between
30 ° and 65°
5-levels air direction setting
Settable to 5 different levels between 10 ° and 40°
Settable to 5 different levels between 10 ° and 65°
Settable to 5 different levels between 30 ° and 65°
Draft prevention
(In heating mode)
Auto air direction control
At heating startup and thermo
OFF*, air direction is automatically set to a near horizontal 10˚ to prevent direct exposure to cool
At heating startup and thermo OFF*, air discharge is automatically set to 30˚ to prevent both direct exposure to cool air drafts and con-
The air direction is set automatically to the memorised position of the previous air direction. (Initial setting is 65˚ for heating and 30˚ for cooling.)
Note: Air direction is set to the standard position when the unit is shipped from the factory.
The position can be changed from the remote controller.
*When the thermostat turns off.
Multi-Flow System
4-way flow
1 pattern
3-way flow
Wide air distribution
A newly shaped air discharge opening increases flow without increasing wind speed, hence discharged air reaches farther than before.
4 pattern
2-way flow
3 pattern
Air discharge distribution comparison
•125K
Super Cassette
(m)
2.7
Conventional model
2
2.5 m/sec
2.0 m/sec
1.5 m/sec
2.5 m/sec
2.0 m/sec
1
1.0 m/sec
1.5 m/sec
1.0 m/sec
0.5 m/sec
0.5 m/sec
(m)
3.2
3
2
1
4 (m) 3 2 1 0 1 2 3 4 (m)
" " denotes piping direction. " " denotes sealing member for air discharge outlet (option) .
Note: For 3-way or 2-way flow installation, the sealing member for air discharge outlet
(option) must be used to close off the unused outlet(s).
Air discharge temperature comparison
•125K
(In heating)
Super Cassette
(m)
2.7
2
Conventional model
33˚C
30˚C
33˚C
30˚C
27˚C
27˚C
(m)
3.2
3
2
1
25˚C
25˚C
1
22˚C 22˚C
4 (m) 3 2 1 0 1 2 3 4 (m)
Air direction can be selected according to installation.
Note: Operation sound increases when using 2-way or 3-way
Suitable for high ceilings
Criteria for ceiling height and number of air discharge outlets
Number of air discharge outlets used
Standard
Ceiling heightHigh ceiling
High ceiling
4-way flow
35K–71K
3-way flow
2-way flow
2.7 m
3.0 m
3.5 m
3.0 m
3.3 m
3.5 m
3.5 m
3.8 m
-
100K–140K
4-way flow
3-way flow
2-way flow
3.2 m
3.6 m
3.6 m
4.0 m
4.2 m
4.2 m
4.2 m 4.2 m -
Note: Initial settings are for standard ceiling height and 4-way flow. High ceiling settings
1 and 2 are set from the remote
Two selectable temperature-sensors
Both indoor unit and wired remote controller (option) contain temperature- sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control.
*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room.
**Wireless remote controller does not have a
Programme "Dry"
Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.
Switchable fan speed: High/Low
12
Quick and easy to install
Just 240 mm high.
Installable in tight ceiling spaces
(35K–71K)
240 mm * 1
245 mm * 2
* 1
* 2
298 mm high with 100K – 140K
303 mm high with 100K – 140K
Easy height adjustment
Each corner of the unit has an Adjuster Pocket that lets you easily adjust the unit's suspended height.
Note: If the wireless remote control option is installed, a light receptor unit is housed in one of the adjuster pock-
All models suspended without lift
Installable in any direction
Since the orientation of the intake grill can be adjusted after installing, the direction of the intake grill lines can be unified when multiple units are installed.
Drain pump is equipped as standard accessory with
750 mm lift.
750 mm
Easier to maintain
Stepping motor controls flaps to prevent soiled ceilings
Dust can be kept from blowing onto ceilings by directly setting flaps by hand or by remote control.
Conventional Super Cassette
30
% —40
1 Move to 0 °
2 Move to desired angle
1 Move flaps
directly to
desired angle dirt than before
Heat exchanger cleaning required only once every 3 years
The new long-life filter is 20% more efficient than the previous one. This has enabled further reductions in running costs by extending the heat-exchanger cleaning interval by once every two years to once every three years.
Heat-exchanger cleaning interval
2 years
Conventional
3 years
Super Cassette
Less cleaning work thanks to "Non-dew Flaps" with non-flocking
The use of non-flocking flaps minimises adnerring dart, so less cleaning work is needed.
Self-diagnosis function
Low gas pressure detection
Insufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure.
Easy installation for options
The high-performance filter and other options are easily clipped into place.
There is no need for a screwdriver.
Supports simultaneous running of the twin, triple, and double twin multi operation.
Twin Multi Operation Triple Multi Operation DoubleTwin Multi Operation
See pages 31–32 for details of the Multi Series.
13
CEILING MOUNTED CASSETTE TYPE
Options required for specific operating environments
U lt r a lo n g-life filt e r
Even in smoky environments where the air conditioning is on most of the time, the ultra long-life filter only has to be changed once a year.
Smoky atmosphere: annual filter change
*For dust concentration of 0.3 mg/m 3 (Requires separately sold Air Cleaner.)
1 year (Approx. 5,000 hr) 15 hr/day x 28 day/month x 12 month/year
Ordinary store or office: filter change every 4 years
*For dust concentration of 0.15 mg/m 3
4 years (Approx. 10,000 hr) 8 hr/day x 25 day/month x 4 years
H igh -e ffic ie n c y filt e r
Available in two types: 65% and 90% colorimetry.
F r e s h a ir in t a k e k it
Using this kit, a duct can be fitted to increase the intake of outdoor air.
P a n e l s pa c e r
Use when only minimal space is available between drop ceilings and ceiling slabs.
Panel spacer
200 mm
40 mm
Panel spacer
258 mm
40 mm
For 35K–71K indoor units For 100K–140K indoor units
Note: S ome ceiling constructions may hinder installation.
C ontact your Daikin Dealer before installing your unit.
S e a lin g m e m be r fo r a ir dis c h a r ge o u t le t
Sealing members block air discharge openings not used in 2-way or 3-way blow.
B r a n c h du c t c h a m be r
This chamber lets you connect a round flexible duct to the air discharge opening at any time after the original installation.
Outside Note: *C onnecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be procured locally.
**Outside Air fan interlocked with air conditioning unit is necessary.
Optional PC B (K R P1C 63)is required for interlocking.
***It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating noise and may also influence temperature sending.
The units can be installed in the following different ways.
Chamber type (without T-joint pipe and fan)
Kit name: KDDP55D160
Chamber type (with T-joint pipe and without fan)
Kit name: KDDP55D160K
Flexible duct
(procured locally)
T-joint pipe
(procured locally)
Flexible duct
T-joint pipe
Direct installation type
Kit name: KDDJ55X160
Suction chamber
Connection chamber
Figure 1)
Suction chamber
Duct flange
(with insulation
material)
Signal receiver unit
Intake duct
(procured locally)
(duct length: 4 m max.)
Intake duct
(procured locally)
Intake duct
(procured locally)
Connection chamber
(duct length: 4 m max.)
Refrigerant piping
Notes: R equires an inspection port for maintenance access.
If intake ducts cannot be connected to both connection chambers due, for example, to an obstruction, single intake duct installation is possible.
Figure 1 shows what the installation will look like
Notes: R equires an inspection port for maintenance access.
For dual intake duct installation only. If only a single intake duct can be connected because of an obstruction, etc.,
K DDP55D160 should be used instead.
It is not possible to use this kit simultaneously with the wireless remote controller.
Note: Use of options will increase operating sound.
Features
(Features are explained on P. 37–38.)
Feature Comfort
Mould prevention
Work & Servicing Control features Option Others
Model
Cooling only
Heat pump
*1
*1
*2
*3
*4
*4
*4
*4
* 1 Applicable when wired remote controller is used
* 2 Applicable to R 71LU– R 140LU outdoor units (for temp. down to – 15 °C ) (An option is required.)
* 3 Applicable to R Y71LU– R Y140LU outdoor units (for temp. down to – 5 °C ) and RY200LU– RY250LU outdoor units (for temp. down to – 0°C )
* 4 Applicable to R (Y)71LU– 140LU outdoor units
14
15
CEILING SUSPENDED
TYPE
FH ( Y )
Cooling only
Heat pump
FH(Y)35BVE–125BVE
FHY35BVE–125BVE
Sound level
39 / 35 dB(A)
High Low
FHY71B
Upgrade to a quiet and compact system.
Accessory required for indoor unit (option)
Wired LCD remote controller Wireless LCD remote controller
A signal receiver must be added to the indoor unit.
BRC1C61
Note: R emote controller cable not included. C ables must be procured locally.
Cooling only
BRC7EA66
Heat pump
BRC7E63W
Signal receiver unit
(Installed type)
Wireless remote controller and signal receiver unit are sold as a set.
Spreads comfortable air throughout the room
Auto-swing for comfort in all directions
Wide air discharge openings produce a spreading 100
Installable on ceilings
3.5 m high
100 °
°
airflow
Two selectable temperature-sensors
Both indoor unit and wired remote controller
(option) contain temperature-sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control.
*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room.
**Wireless remote controller does not have a temperaturesensor.
Programme "Dry"
Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.
Switchable fan speed: High/Low
Installation flexibility for freedom of design
Uniform height and depth. Compact design for small-capacity models to meet tighter dimensional constraints.
(mm)
Indoor unit 35B/50B 60B/71B 100B 125B
Height
Width
Depth
960 1,160
195
1,400
680
1,590
Weight of all models reduced (down 10% compared with previous models). Transfer and installation work is less arduous.
Drain pump kit (option) can be easily incorporated
Drain pipe connection can be done inside the unit. Refrigerant and drain pipe outlets are at the same opening.
600 mm
Drain pump kit (built inside main unit)
Reduced edge space, more flexible installation
The unit fits more snugly into tight spaces.
For 71B indoor unit
Dimensions in brackets are for previous model.
30 mm
( 60 mm )
1,160 mm ( 1,300 mm )
1,220 mm ( 1,420 mm )
30 mm
( 60 mm )
All wiring and internal servicing done from below the unit
Pipes more easily rigged, too
Plastic panels are used to conceal piping holes. Holes can be easily punched out without requiring special tools.
*Water used in the test-run can now be drained from the air discharge opening rather than from the side as was formerly the case.
Low gas pressure detection
Supports simultaneous running of the twin, triple and double twin multi operation.
Twin Multi Operation Triple Multi Operation DoubleTwin Multi Operation
CEILING SUSPENDED TYPE
Quiet operation
Sound operation has been reduced on the exposed ceiling suspended type unit.
dB(A)
Indoor unit
35B
50B
60B
71B
100B
125B
High
37
38
38
39
42
44
Low
32
33
33
35
37
39
Note : Anechoic chamber conversion value, measured according to J IS parameters and
Uses quiet stream fan and other quiet technologies.
Sound damper
Turbulent flow
is produced
Straightening vane
Quiet stream fan
Easier to maintain
Long-life filter lasts about 1 year *
Maintenance not required
* For dust concentration of 0.15 mg/m 3
Two time settings (2500 hrs and 1250 hrs) are available to match the installation environment. Maintenance time warning is displayed on the remote controller (filter sign).
Non-dew flap without bristles
Absence of bristles minimises clinging dirt and simplifies cleaning.
Non-dew flap
Easy-clean, flat surfaces
It is easy to wipe dirt off the flat side and lower surfaces of the unit.
For all maintenance tasks, access is from bottom surface.
Improved-oil resistant grille
Oil-resistant plastic is used for the air discharge grille. This improves durability in restaurants and other similar environments.
Note: Intended for use in salons, dining rooms, and ordinary sales floors, this specification is not suitable for kitchens or other harsh environments.
See pages 31–32 for details of the Multi Series.
Features
(Features are explained on P. 37–38.)
Feature Comfort
Mould prevention
Work & Servicing Control features Others
Guide Line up
P. 3–10
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Standard specifications
P. 39, 47, 49, 55
Options
P. 57
Outer dimension drawings
P. 60
Model
Cooling only
*2 *3 *5 *6 *6
Heat pump *2 *4 *5 *6 *6
* 1 Installable on max. 3.5 m high ceiling
* 2 Applicable when wired remote controller is used
* 3 Applicable to R 71LU– R 140LU outdoor units (for temp. down to – 15 °C )
(An option is required.)
* 4 Applicable to R Y71LU– R Y140LU outdoor units (for temp. down to – 5 °C )
and R Y200LU– R Y250LU outdoor units (for temp. down to – 0 °C )
* 5 Optional available
* 6 Applicable to R (Y)71LU– 140LU outdoor units
16
17
CEILING
SUSPENDED CASSETTE
TYPE
Cooling only
FUY
FUY71FJV1–125FJV1
FUY71FJV1–125FJV1 Heat pump
Sound level
40 / 35 dB(A)
High Low
FUY71FJ
Flexibility in installation location.
Installation is also simple.
Accessory required for indoor unit (option)
Wired LCD remote controller Wireless LCD remote controller
A signal receiver must be added to the indoor unit.
BRC1C61
Note: R emote controller cable not included. C ables must be procured locally.
Cooling only
BRC7C529W
Heat pump
BRC7C528W
Signal receiver unit
(Installed type)
Wireless remote controller and signal receiver unit are sold as a set.
CEILING SUSPENDED CASSETTE TYPE
The auto-swing function increases comfort level
Auto-swing 5-levels air direction setting Auto-air direction control
Ultra-thin with quiet operation
Thinner usually means noisier, but
Daikin's exclusive technology has solved this.
Heat exchanger
Sliding shutter
Closes to moderate airflow (70%)
Auto-swing between 0
°
and
60
°
Settable to 5 different levels between 0
°
and 60
°
The air direction is set automatically to the memorised position of the previous air direction. (Initial setting is 60
°
for heating and 30
°
for cooling.)
Draft prevention
(in heating)
At heating startup and thermo OFF*, air direction is automatically set to horizontal
*When the thermostat turns off.
Air direction can be selected according to installation
Selection patterns for air direction and fan speed ratio
Note: Applicable only to the flow configurations shown below.
Standard (100%) Moderate (approx. 70%)
*R equires sealing member for air discharge outlet (optional accessory) for opposing 2-
2-way
flow
3-way
flow
Piping position
4-way
flow
Note: When 2- or 3-way flow configurations are selected, the unused flow outlets must be blocked off with the optional sealing material. Sound during operation will rise by about 2 dB.
Suitable for high ceilings
Criteria for ceiling height and number of air discharge outlets
Standard
Ceiling height
High ceiling 1
High ceiling 2
Number of air discharge outlets used
2-way flow
3.5 m
3.8 m
3.0 m
3.3 m
2.7 m
3.0 m
— 3.5 m 3.5 m
Note: Initial settings are for standard ceiling height and 4-way flow. High ceiling settings
1 and 2 are set from the remote
Programme "Dry"
Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.
Two selectable temperature-sensors
Both indoor unit and wired remote controller (option) contain temperaturesensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control.
*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room.
**Wireless remote controller does not have a
Switchable fan speed: High/Low
Easier to maintain
Long-life filter lasts about 1 year *
Maintenance not required
* For dust concentration of 0.15 mg/m 3
Features
(Features are explained on P. 37–38.)
Feature Comfort
Accessible from below for easy maintenance
Low gas pressure detection
Mould prevention
Work & Servicing
Ultra-thin, quiet design made possible by new
Flat Turbo Fan.
Through use of a high-static-pressure vane and a thorough reduction in flow loss in the path between internal fan suction and air output, we have achieved a thinner fan unit and quiet operation while maintaining airflow. dB(A)
Indoor unit
71FJ
100FJ
125FJ
High
40
43
44
Low
35
38
39
Note : Anechoic chamber conversion value, measured according to J IS parameters and
Quick and easy to install
Simple installation procedure
Simply lock the body in place with suspension bolts to install.
Adjustment is smooth and simple, too.
Suspension bolt
T-type hexagon wrench
Hook
Drain pump is equipped as standard accessory with
500 mm lift.
500 mm
Installable in any direction
Since the orientation of the intake grill can be adjusted after installing, the direction of the intake grill lines can be unified when multiple units are installed.
Note: The panel cannot be turned when the wireless remote controller is in use.
Control features Others
Guide Line up
P. 3–4, 7–8
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Standard specifications
P. 40 and 50
Options
P. 57
Outer dimension drawings
P. 61
Model
Cooling only
Heat pump
*1
*1
*2
*3
*4
*4
*4
*4
* 1 Applicable when wired remote controller is used
* 2 Applicable to R 71LU– 125LU outdoor units (for temp. down to – 15 °C )
(An option is required.)
* 3 Applicable to R Y71LU– 125LU outdoor units (for temp. down to – 5 °C )
* 4 Applicable to R (Y)71LU– 125LU outdoor units 18
19
CEILING MOUNTED
CASSETTE CORNER
TYPE
FH ( Y ) K
FH(Y)K35FV1–71F(J)V1 Cooling only
FHYK35FJV1–71FJV1 Heat pump
Fits in ceiling corners.
Equipped for versatile airflow control.
Sound level
41 / 36 dB(A)
High Low
Accessory required for indoor unit
(option)
Wired LCD remote controller
BRC1C61
Note: R emote controller cable not included. C ables must be procured locally.
Guide Line up
P. 3–4, 7–8
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Standard specifications
P. 40 and 50
Options
P. 58
Outer dimension drawings
P. 61
CEILING MOUNTED CASSETTE CORNER TYPE
Multiple airflow variations for stepped or 3.8 m high ceilings
1 Downward flow 2 Downward flow + Forward flow
Airflow variation
3 Forward flow
Auto-swing
High ceiling installation R equires ceiling tap cutting.
R equires ceiling tap cutting.
Not suited for high c eilings because air currents do not
Required options Air discharge grille, flexible duct
Panel spacers (option) can be installed with all three airflow variations.
Quiet operation dB(A)
Indoor unit High Low
35F(J)
45F(J)
39
39
33
34
60F(J) 41 36
71F(J) 41 36
Note : Anechoic chamber conversion value, measured according to J IS parameters and
Easier to install and service
Drain pump is equipped as standard accessory with
500 mm lift.
500 mm
E x a m ple in s t a lla t io n s
In the corner of a room
(downward flow)
Comfortable cooling from ceiling to floor
(downward flow)
(outward
+ downward flow)
Wind speed profile
Heating (65 ° downward flow ... Standard installation)
3
2
1
(m)
2.0 m/s
1.5 m/s
1.0 m/s
0.5 m/s
0.3 m/s
1 2 3 4 5 6
3.8
3
Wind speed profile
Heating (65 ° downward flow from high ceiling)
On stepped ceilings, downward flow can be blocked and outward flow alone can be used to cool or heat the space.
Air conditioner
2
1
(m)
2.0 m/s
1.5 m/s
1.0 m/s
0.5 m/s
0.3 m/s
1 2 3 4 5 6
Decorative panel
(sold separately)
C over here with decorative panel.
Decorative panels (option) can be installed on the downward air discharge opening to close gaps without stepped room interiors.
Optimal comfort and convenience assured by three air discharge modes
Air direction
Desired situation
Draft prevention setting Standard setting Setting to prevent soiling of ceiling
When drafts are unwanted For gentle drafts
(Ceiling is soiled.)
When ceilings must be kept spotless
Long-life filter lasts about 1 year *
Maintenance not required
* For dust concentration of 0.15 mg/m 3
Low gas pressure detection
Fresh air intake possible
(Site installation required)
A duct can be connected to the rear of the indoor unit to draw in outdoor air.
Auto-swing
Auto-swing between
0 ° and 65°
Auto-swing between
0 ° and 65°
Auto-swing between
0 ° and 65°
5-levels air direction setting
Settable to 5 different levels between 0 ° and 65°
Settable to 5 different levels between 30 ° and 65°
Features
(Features are explained on P. 37–38.)
Feature Comfort
Mould prevention
Settable to 5 different levels between 40 ° and 65°
Draft prevention
(In heating) model
Auto air direction control
At heating startup and thermo OFF*, air discharge is automatically set to a near horizontal 10˚ to prevent direct exposure to cool air drafts.
The air direction is set automatically to the memorised position of the previous air direction. (Initial setting is 65 ° for heating and 30 ° for cooling.)
Note: Air direction is set to the standard position when the unit is shipped from the factory. The position can be changed from the remote controller.
*When the thermostat turns off.
Programme "Dry"
Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.
Switchable fan speed:
High/Low
Work & Servicing
K eep duct no more than 5 m long.
Note: The maximum duct length for connection to the fresh air intake kit is 5 m. C onnecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be
P a n e l s pa c e r (o pt io n )
Use when only minimal space is available between drop ceilings and ceiling slabs.
20mm
C eiling
Panel spacer
Upgrade options for easy installation on stepped ceilings
Air discharge grille Flexible duct
For outward blow, detach the punch-out panel from the duct-connection port on the front of the unit.
Control features Others
Model
Cooling only
*1 *3
Heat pump *2 *3
* 1 Applicable to R 71LU outdoor units (for temp. down to – 15 °C ) (An option is required.)
* 2 Applicable to R Y71LU outdoor units (for temp. down to – 5 °C )
* 3 Applicable to R (Y)71LU outdoor units
*3
*3
20
21
CEILING MOUNTED
BUILT-IN TYPE
FH ( Y ) B
Cooling only
Heat pump
FH(Y)B35FV1–125FV1
FHYB35FV1–125FV1
Clever and compact mini ducted unit provides comfort and flexibility.
Sound level
41 / 35 dB(A)
High Low
FHYB71F
Accessory required for indoor unit
(option)
Wired LCD remote controller
BRC1C61
Note: R emote controller cable not included. C ables must be procured locally.
Guide Line up
P. 3–4, 7–8
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Standard specifications
P. 41, 51
Options
P. 58
Outer dimension drawings
P. 62
CEILING MOUNTED BUILT-IN TYPE
Flexibly adapts to shop interiors
To cope with the challenges of Lshaped or U-shaped spaces, it is possible to install the air discharge unit away from the main unit. At the same time, different types of architectural space can be kept comfortable.
L-shaped space U-shaped space Long space
Programme "Dry"
Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.
Switchable fan speed: High/Low
Quiet operation dB(A)
Indoor unit
35F
45F
60F
71F
100F
125F
High
38
39
41
41
41
44
Low
32
34
35
35
35
38
Note : Anechoic chamber conversion value, measured according to J IS parameters and
Easier to maintain
Long-life filter lasts about 1 year *
Maintenance not required
* For dust concentration of 0.15 mg/m 3
Low gas pressure detection
Insufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure.
Meets diverse of installation needs
The indoor unit can be installed in rooms with as little as 350 mm between the drop ceiling and ceiling slab. It also works with both flexible and ordinary ducts.
S t a n da r d in s t a lla t io n e x a m ple s
In crawl space With canvas bellows and air intake panel (sold separately)
6
4
2 Air conditioner
350 mm or more
6
2
Air conditioner
4
Long-life filter 3
425 mm or more
5
Air blow
Air intake
1
Long-life filter
45 mm
W it h h igh -e ffic ie n c y filt e r
5
Air blow
C e ilin g r e t u r n
Air intake
1
2
Air conditioner
6
4
13 7
3
540 mm or more
5
Air blow
Air intake
1
C e iling re turn w ith high-e ffic ie nc y filte r
6
4
2
Air conditioner
9 7
6
5
Air blow
4
2
Air conditioner
Long-life filter
Air intake
450 mm or more
8
540 mm or more
Air intake
W it h o r din a r y du c t s
Ordinary duct
(procured locally)
10
Air conditioner
9
Ordinary duct
(procured locally)
460 mm or more
8
8 Air blow
Air intake
5
Air blow
Options
1 Decorative panel
2 Air discharge opening adapter
3 Canvas bellows and air intake panel
4
5
6
7
Flexible duct
Air discharge grille
Air discharge chamber
High-performance filter
8 Inspection panel
9 Rear intake blocking pad
10 Air discharge opening flange
11 Rear intake filter chamber
12 Branch duct
13 Low-draft filter chamber
Drain pump is equipped as standard accessory with
250 mm lift.
250 mm
External static pressure can be set depending on duct length, presence of high-efficiency filter, and other installation conditions.
External static pressure pattern
(Pa)
Indoor unit High Standard Low
35F–71F 78 39 20
100F and 125F 98 39
External static pressure is set to standard when the unit is shipped from the factory.
Fresh air intake possible
(Custom installation required with locally
procured materials)
A duct can be connected to the rear of the indoor unit to draw in outdoor air.
Note: The maximum duct length for connection to the fresh air intake kit is 5 m. C onnecting ducts, insect nets, fire dampers, air filters, and other parts should, as required,
H igh -e ffic ie n c y filt e r (o pt io n )
Available in two types: 65% and 90% colorimetry. This filter easily meets dust collection efficiency regulations specified in building codes.
Options have also been upgraded to make installation even easier.
Air discharge opening adapter
Flexible duct
(dia. 200 mm)
Canvas bellows and air Intake panel
Decorative panel
Flexible duct
(dia. 150 mm)
Branch duct
Air discharge chamber
Air discharge grille
Features
(Features are explained on P. 37–38.)
Feature Comfort
Mould prevention
Work & Servicing Control features Option Others
Model
Cooling only
*1 *3 *3
Heat pump
*2 *3 *3
* 1 Applicable to R 71LU– R 125LU outdoor units (for temp. down to – 15 °C ) (An option is required.)
* 2 Applicable to R Y71LU– R Y125LU outdoor units (for temp. down to – 5 °C )
* 3 Applicable to R (Y)71LU– 125LU outdoor units 22
23
WALL MOUNTED
TYPE
FAY
Cooling only
Heat pump
FAY71LVE / FAY100FAVE
FAY71LVE / FAY100FAVE
Made more compact, stylish, and quieter
Sound level
43 / 37 dB(A)
High Low
FAY71L
Sound level
45 / 41 dB(A)
High Low
FAY100FA
FAY71LVE
FAY100FAVE
Accessory required for indoor unit (option)
Wired LCD remote controller Wireless LCD remote controller
A signal receiver must be added to the indoor unit.
Signal receiver unit
(Installed type)
Cooling only
BRC7E619
Heat pump
BRC7EA618
FAY71L
BRC1C61
Note: R emote controller cable not included. C ables must be procured locally.
Cooling only
BRC7C611W
Heat pump
BRC7C610W
FAY100F
Wireless remote controller and signal receiver unit are sold as a set.
Guide Line up
P. 3–4, 7–8
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Standard specifications
P. 41, 51
Options
P. 58
Outer dimension drawings
P. 62, 63
WALL MOUNTED TYPE
Below features only apply to FAY71L.
Drastic size reduction
Reduced size (by 22% in volume,
32% in installation area)makes installation possible in a very limited space.
Conventional model
(FAY71FAVE)
-70 mm
-200 mm
290 mm
1,050 mm
Sophisticated extension design
Compact and stylish design that does not detract from the decor of the room.
Flap is closed when not operating
Easier to install and service
Light weight
Reduced weight by 8kg greatly facilitates installation.
Conventional
(FAY71FAVE)
21 Kg
New model
(FAY71LVE)
13 Kg
Drain pump kit is available as option.
Installs onto side of unit.
Height of drain up
1,000 mm
Indoor unit
Drain-pump kit
(Available to be installed onto right side.)
Drain enclosure can be used on either left and right side.
Drain pan and air filter can be kept clean by mould-proof polystyrene
Removable and washable grille
DIII-NET connection is standard specification. Adapter is not required.
Improved airflow modes realise comfortable air distribution across the entire room
Auto-swing 5-level air direction setting Autoair direction control
10 ° 10 °
Auto-swing from 10 ° to 70° 70
°
S ettable to 5 different levels between 10 ° to 70°
70
°
Comfort even on the far side of the room
To carry air to the far side of long rooms, extrahigh airflow adds 10% more fan speed the "high" setting. Air discharge strength is selected from the remote controller.
Two selectable temperature-sensors
Both indoor unit and wired remote controller (option) contain temperaturesensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control.
*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room.
**Wireless remote controller does not have a
Programme "Dry"
Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.
Switchable fan speed: High/Low
10
°
The air direction is set automatically to the memorised position of the previous air direction.
(Initial setting is 10 ° for cooling and 70 ° for heating.)
70
°
Easier to install and service
Maintenance possible from the front of the unit
All maintenance tasks can be carried out via front access. During service work, attachment and detachment of parts is easier.
Low gas pressure detection
Insufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure.
Features
(Features are explained on P. 37–38.)
Feature Comfort
Mould prevention
Work & Servicing Control features Others
Model
Cooling only
Heat pump
*1
*1
*2
*3
*4
*4
* 1 Applicable when wired remote controller is used
* 2 Applicable to R 71LU/R 100LU outdoor units (for temp. down to – 15 °C ) (An option is required.)
* 3 Applicable to R Y71LU/R Y100LU outdoor units (for temp. down to – 5 °C )
* 4 Applicable to R (Y)71LU/100LU outdoor units
*4
*4
24
FLOOR STANDING
TYPE
FVY
Cooling only
Heat pump
FVY71LAVE–125LAVE
FVY71LAVE–125LAVE
The floor-standing configuration means the FVY is easy to install and maintain.
It can also be installed under high ceilings.
Sound level
41 / 35 dB(A)
High Low
FVY71LA
LCD control panel is standard
Note: This remote controller has a temperaturesensor.
25
Guide Existing models:
FLOOR STANDING TYPE
Quiet operation
Indoor unit
71LA
100LA
125LA
High
41
46
49
Low
35
40
43 dB(A)
Note : Anechoic chamber conversion value, measured according to J IS parameters and
Auto-swing delivers comfort to every corner of the room
FVY units have swinging louver spreads comfortable airflow. Any uncomfortable sensation of sudden change is avoided by a slow cycle of 2 to 3 full swings per minute.
Auto-swing
Manual setting of vertical airflow louvers
Easier to install and service
Lightweight
The unit can be easily transported and installed.
Indoor unit
71 class
100 class
125 class
Conventional
FVY-F
45 kg
63 kg
67 kg
Weight
New model
39
46
47 kg kg kg
Long-life filter lasts about 1 year *
Maintenance not required
*For dust concentration of 0.15 mg/m 3
Filter exchange interval
2 weeks
Conventional filter
Annual
Long-life filter
A good choice for spaces with ceilings so high that heating by ceiling-mounted units is inefficient.
Note: For optimal installation, space factors should be accurately calculated.
Switchable fan speed: High/Low
Vertical airflow adjustment is possible when
(changing between cooling and heating or) to match interior spaces and partitions.
Programme "Dry"
Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.
Low gas pressure detection
Insufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure.
Easy-to-operate, handy LCD control panel
The LCD displays text, numbers and graphics to indicate the temperature setting, timer setting, auto-swing, fan speed, and more. Furthermore, the LCD panel can be detached and used as a remote controller, so air conditioning can be controlled from another room or from the cash register.
(Remote controller cable not included. Cables must be procured locally.)
Two selectable temperature-sensors
Temperature-sensors on both indoor unit and wired remote controller.
Temperature sensing can be set closer to the target area to further improve comfort level.
*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room.
**Wireless remote controller does not have a temperature-sensor.
Features
(Features are explained on P. 37–38.)
Feature Comfort
Mould prevention
Work & Servicing Control features Others
Model
Cooling only
Heat pump
*1
*2
*3
*3
*3
*3
* 1 Applicable to R 71LU– R 125LU outdoor units (for temp. down to – 15 °C ) (An option is required.)
* 2 Applicable to R Y71LU– R Y125LU outdoor units (for temp. down to – 5 °C )
* 3 Applicable to R (Y)71LU– 125LU outdoor units
26
27
DUCT CONNECTION
MIDDLE STATIC PRESSURE TYPE
FDMG/FDYM
Cooling only FDMG71AV1–180AV1
FDYM03FAV1–06FAV1
FDYM03FAV1–06FAV1 Heat pump
Unit can be mounted in the ceiling and air can be delivered freely by duct.
Sound level
39 dB(A)
High
FDYM03FA
(220V)
FDMG100A
FDYM03FA
Accessory required for indoor unit (option)
For FDYM
Wired LCD remote controller Wireless LCD remote controller
BRC1C61
Note: R emote controller cable not included. C ables must be procured locally.
For FDMG
Digital remote controller
Cooling only
BRC4C64
Heat pump
BRC4C62
Signal receiver unit
(Separate type)
Wireless remote controller and signal receiver unit are sold as a set.
Remote controller
KRC47-2A
KRC47-4A
KRC47-1A
Guide Line up
P. 3–10
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Standard specifications
P. 43, 48, 53, 56
Options
P. 59
Outer dimension drawings
P. 64, 65
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
Freedom of layout
The duct system allows the efficient location of discharge outlets in accordance with the room layout
Middle static pressure type is available in a larger than standard space
Duct connection is simpler with standard rear intake chambers
Compact, 295 mm high design makes installation possible where the ceiling space is limited
(For FDYM)
Quiet operation
Indoor unit
FDMG71A
FDMG100A
FDMG125A
FDMG140A
FDMG180A
High
42
44
45
46
47 dB(A) (220V)
LOW
38
36
37
36
37
FDYM03FA
FDYM04FA
FDYM05FA
39
39
44
46 FDYM06FA
Note : Anechoic chamber conversion value, measured according to J IS parameters and
Ordinary duct
(procured locally)
Air conditioner
295 mm
Air blow
Ordinary duct
(procured locally)
305 mm or more
Air intake
Switchable fan speed: High/Low
Programme "Dry"
Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.
Supports simultaneous running of the twin and triple multi operations.
Twin Multi Operation Triple Multi Operation
Low gas pressure detection
Insufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure.
See pages 31–32 for details of the Multi Series.
Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)
When air conditioning two rooms simultaneously, the air discharged into each room must be circulated back to the air conditioner. To achieve this, a ventilation duct should be installed for each room or one of the indicated ventilation grilles should be installed on the partitioning wall or under the door between the rooms.
Partitioning wall
Ventilates air through the partitioning wall.
(See right)
Door-installed ventilation grille
Ventilation grille
Wall-installed ventilation grille
Ventilation grille
Under-door cutout
Under-door cutout
Note: The under-door cutout method should be used only when there is a small volume of airflow.
Features
(Features are explained on P. 37–38.)
Feature Comfort Work & Servicing Control features Others
Model
Cooling only
FDMG
FDYM
*1 *3 *3
Heat pump *2 *3 *3
*
*
1
3
Applicable to R 71LU– R 140LU outdoor units (for temp. down to – 15 °C ) (An option is required.)
* 2 Applicable to R Y71LU– R Y140LU outdoor units (for temp. down to – 5 °C ) and RY200LU– RY250LU outdoor units (for temp. down to – 0°C )
Applicable to R (Y)71LU– 140LU outdoor units
28
DUCT CONNECTION
LOW STATIC PRESSURE TYPE
FDBG/FDYB
Cooling only FDBG25AVE – 71AVE
FDYB35KAVE – 71KAVE Heat pump
Sound level
38 dB(A)
LOW
FDYB50KA
(220V)
FDYB50KA
Accessory required for indoor unit (option)
Cooling only
Digital remote controller Remote controller
KRC47-2A
KRC47-4A
Heat pump
Wired LCD remote controller
KRC47-1A
Wireless LCD remote controller
DUCT CONNECTION
HIGH STATIC PRESSURE TYPE
Cooling only
FD
(
Y
)
FD03KY1–20KY1
FDY06KAY1–20KAY1 Heat pump
Sound level
51 dB(A)
High
FDY06KA
FDY06KA
Accessory required for indoor unit (option)
Cooling only
Remote controller
KRC47-3A
Heat pump
Wired LCD remote controller Wireless LCD remote controller
BRC1C61
Note: R emote controller cable not included. C ables must be procured locally.
Ideal for quiet, beautiful living spaces
Suitable for condominiums and apartments, houses and hotels
Quiet operation
Model
Cooling only
Heat pump
29
Indoor unit High Low dB(A)
FDBG60AVE 42 39
Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria.
BRC4C62
Signal receiver unit
(Separate type)
Wireless remote controller and signal receiver unit are sold as a set.
Compact
Small, lightweight, and easy-to-install outdoor unit.
Durable
To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated PE fins (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.
S uction chamber
[Duct connection]
Air filter
To prevent increased operation sound, avoid installing the air suction grille directly below the suction chamber.
Supports simultaneous running of the triple and double twin multi operations.
Triple Multi Operation Double twin Multi Operation
See pages 31–32 for details of the Multi Series.
Features
(Features are explained on P. 37–38.)
Feature Comfort Work & Servicing Control features Others
*1 *2 *2
Guide Line up
P. 3–10
Outdoor units
P. 33–34
Remote controllers
P. 35–36
* 1 Applicable to R Y71LU outdoor units (for temp. down to – 5 °C )
and R Y200LU– R Y250LU outdoor units (for temp. down to – 0 °C )
* 2 Applicable to R Y71LU outdoor units
Standard specifications
P. 42, 52, 56
Options
P. 59
Outer dimension drawings
P. 64
BRC1C61
Note: R emote controller cable not included. C ables must be procured locally.
BRC4C62
Signal receiver unit
(Separate type)
Wireless remote controller and signal receiver unit are sold as a set.
Recommended for spacious and large-volume areas because of its flexible installation
Suitable for large stores, factories, and other large areas, and for use with housing ducts in homes
Quiet operation Central control
Durable
Highly durable outdoor unit has PE fins for improved resistance to salt corrosion and atmospheric pollution.
Many options are available for use with large-scale and advanced-function centrally controlled systems
Features
(Features are explained on P. 37–38.)
Feature Comfort Work & Servicing Control features Others Guide
Line up
P. 3–4, 7–8
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Standard specifications
P. 44, 45, 53
Model
Cooling only
*3
Options
P. 59
Heat pump *4 *1 *2 *2 *4 *3 Outer dimension drawings
* 1 Applicable to R Y140LU outdoor units (for temp. down to – 5 °C ) and RY200LU– RY250LU outdoor units (for temp. down to – 0°C )
* 2 Applicable to R (Y)140LU outdoor units
* 3 R equired to change the pulley
* 4 FDY06-10 only
P. 65–67
Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)
When air conditioning two rooms simultaneously, the air discharged into each room must be circulated back to the air conditioner. To achieve this, a ventilation duct should be installed for each room or one of the indicate ventilation grilles should be installed on the partitioning wall or under the door between the rooms.
Partitioning wall
Ventilates air through the partitioning wall.
(See right)
Door-installed ventilation grille
Ventilation grille
Wall-installed ventilation grille
Ventilation grille
Under-door cutout
Under-door cutout
Note: The under-door cutout method should be used only when there is a small volume of airflow.
30
Simultaneous operation system
MULTI SERIES
Twin, Triple, and Double Twin Multi-Operation
Simultaneously operates
2 to 4 indoor units using a single outdoor unit.
In large interior spaces a single indoor unit may not be able to provide uniform comfort.
Installation of 2 to 4 units, can provide an effective solution.
In a single-floor restaurant, for example, positioning 4 units at strategic locations realises comfortable airflow that reaches every inch of the room.
Note: This type of system does not allow individual control or independent operation of indoor units. It is not the best choice for large rooms with partitions.
Installing multiple units is economical and realises comfort
Lower cost of installation than for individual pair type
Reduced installation space for outdoor units
Enhanced comfort from distributed indoor units
Indoor units include ceiling mounted cassette type, ceiling suspended type, and duct connection middle and low static pressure type.
Double Twin Multi operation
4 indoor units can be run simultaneously with a single outdoor unit.
Improved comfort level and space-saving for outdoor unit installation
Before
5 HP x 2 units
New
10 HP double twin multi operation
Branch piping kit
Branch piping kit
4 indoor units distribute comfortable airflow throughout the room.
Simultaneous operation of four indoor units can be controlled from a single remote controller.
Requires a single refrigerant piping system.
Triple Multi operation
Branch piping kit
Required about 40% less installation space for outdoor unit
Before
R(Y)125KU x 2 units
New
R(Y)200KU or R(Y)250KU x 1 unit
300 mm 500 mm
300 mm
1000 mm
Twin Multi operation
Simultaneous operation system
MULTI SERIES
Remote controllers for the Multi Series
INDOOR UNIT
CEILING MOUNTED
CASSETTE TYPE
CEILING SUSPENDED TYPE
DUCT CONNECTION
LOW STATIC PRESSURE TYPE
DUCT CONNECTION
MIDDLE STATIC PRESSURE TYPE
A single remote controller controls simultaneous operation of multiple indoor units.
Wired LCD remote controller
(Option)
BRC1C61
Connect the wired remote controller to turn an indoor unit into the master unit.
Supports Two selectable temperature-sensor functions.
Note: Selectable temperature sensing is available with ceiling-mounted cassette and ceilingsuspended models, but not with middle staticpressure models.
Wired remote controller has a temperature-sensor. Depending on the installation conditions, select and set the temperature-sensor of a selected indoor unit or the temperaturesensor of the remote controller.
Note: An indoor unit's temperature-sensor must
be used when the air conditioners
are controlled from another room.
Wireless LCD remote controller
(Option)
Cooling only
Heat pump
Cooling only
Heat pump
BRC7C613W
BRC7C612W
BRC7EA66
BRC7E63W
Heat pump BRC4C62
Cooling only
Heat pump
BRC4C64
BRC4C62
Install the signal receiver unit (part of the optional wireless remote controller) to turn an indoor unit into the master unit.
Because the wireless remote controller does not have a temperature-sensor, select the temperature-sensor of the indoor master unit.
Piping Guideline
Twin Multi Operation
Branch piping kit
L
1
Main pipe
L
Sub unit
L
2
Main unit
Remote controller
Triple Multi Operation
L
1
Branch piping kit
Sub unit
L
2
Sub unit
L
3
Main pipe
L
Main unit
Remote controller
Double Twin Multi Operation
L
3
L
1
Branch piping kit
L
4
Sub unit Sub unit
L
5
L
2
Main pipe
L
Sub unit
L
6
Main unit
Remote controller
Outdoor unit Outdoor unit Outdoor unit
Simultaneous operation system
Max. piping length
Max. branch piping length
Max. branch pipe length difference
Twin Multi Operation
L Max. (L
1
, L
2
) 50 m
Max. (L
1
, L
2
)*
1
20 m
Max. (L
1
, L
2
) Min. (L
1
, L
2
)*
2
10 m
Triple Multi Operation
L Max. (L
1
, L
2
, L
3
) 50 m
Max. (L
1
, L
2
, L
3
) 20 m
Max. (L
1
, L
2
, L
3
) Min. (L
1
, L
2
, L
3
) 10 m
Double Twin Multi Operation
L Max. (L
1
, L
2
) Max. (L
3
, L
4
, L
5
, L
6
) 50 m
Max. (L
1
, L
2
) Max. (L
3
, L
4
, L
5
, L
6
) 20 m
(L
2
L
6
) (L
1
L
3
) 10 m
L
2
L
1
10 m
L
4
L
3
10 m
L
6
L
5
10 m
In case of L
1
L
2
, L
3
L
4
, L
5
L
6
30 m
0.5 m
Max. level difference between outdoor unit and indoor units
Max. level difference between indoor units
* 1 Max. (L 1 , L 2 ) means maximum length out of L 1 and L 2 .
* 2 Min. (L
1
, L
2
) means minimum length out of L
1
and L
2
.
30 m
0.5 m
Refrigerant piping uses terminal branching to facilitate installation.
(Branch piping kits are sold separately. Please use the model indicated on page 59)
30 m
0.5 m
31
Branch piping kit
Branch piping kit
Guide Line up
P. 5–6, 9–10
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Standard specifications
P. 46–48, 54–56
Options
P. 57–59
Outer dimension drawings
P. 60–74
(For Twin Multi) (For Triple Multi) (For Double Twin Multi)
32
OUTDOOR UNIT
Compact unit provides quiet operation.
R(Y)140LU R(Y)71LU
Fitted with wide inlet fan
(Applies to R(Y)71LU–140LU)
Fully shaped aerodynamic propellers are designed to push air with a large wing surface, providing both high blow volume and quiet operation with turbulence.
R(Y)100LU R(Y)125LU
Q uie t O pe ra tion
Fitted with Super Aero Grille
(Applies to R(Y)71LU–140LU)
To suppress turbulence and achieve quiet operation, the curved ribs of the grille are optimised to meet the outflow of air.
Equipped with scroll compressor for quiet operation
(Applies to R(Y)125LU and 140LU)
Smooth running, minimal vibration, low operating sound.
Wide inlet fan
(Applies to R(Y)71LU–140LU)
C o m pa c t
Slim and low-profile design outdoor units
(Applies to R(Y)71LU–140LU)
Compactly designed outdoor unit with interior layout optimised for the smooth airflow.
The design curved Super Aero
Grille restricts the spread of exhaust gas and fits in the same space as conventional outdoor units.
Reduced weight
(Applies to R(Y)71LU-125LU)
The light weight makes delivery and installation easier.
conventional
108 kg
RY100KUV1
New
89 kg
RY100LUV1
500
50
(mm)
33
Operation sound
Heat pump
Outdoor unit dB(A)
Sound level (cool/heating)
RY71LU
RY100LU
RY125LU
RY140LU
48/49
49/52
49/52
54/56
Cooling only
Outdoor unit
Sound level
R71LU
R100LU
R125LU
48
49
49
R140LU 54
Note : Anechoic chamber conversion value, measured according to J IS parameters and
OUTDOOR UNIT
P o w e r fu l
Uses "Receiver" to enhance refrigerant control
(Applies to R(Y)71LU–140LU)
Instead of the using an accumulator to absorb excess refrigerant, Daikin outdoor units have a receiver in the piping located away from the compressor. By preventing the return of liquid to the compressor, the receiver enhances reliability.
Defrost control delivers powerful heating in extremely cold climates
(Applies to RY71LU–140LU) (Heat pump only)
To optimise heating performance, by monitoring the difference in air temperature in the indoor/outdoor heat exchanger and the intake air temperature, the system accurately adjusts to provide the best operating parameters.
This enables defrost mode to be initiated and so minimise indoor declines in temperature caused by frost. For example, if the outdoor airtemperature falls to -1.5
°C, the integrated heating capacity is raised about 20%.
Integral heating capacity and temperature difference
(actual measurement when outdoor temperature is -1.5
°
C)
°
C
25
Defrost begins in this area
20
Integral heating capacity
15
10
5
0
0 10 20 30
Difference between indoor heat exchange temperature and intake air temperature ( T)
40 50 60 70 80
Elapses operation time (min.)
Defrost operation complete
(heating operation restart)
Defrost monitoring start
(monitors to maximum point)
Suited for year-round cooling applications
Cooling is efficient even in winter when indoor temperatures are higher than those outside, such as in underground public spaces or offices with many computers.
• Heat pump/RY71–140LU: possible up to -5
°
C
• Cooling only/R71–140LU: possible up to -15
°
C
• The year-round cooling kit is required as option.
Ins tallation and maintenanc e
Pre charged for up to 30 metres
If refrigerant piping length does not exceed 30 m, there is no need for onsite gas charging.
(Applies to R(Y)71LU–140LU)
Allowed refrigerant pipe length and
level difference
R25J
RY35F
R35J
RY50GA
R50G
RY60GA
R60G
RY71LU
R71LU
RY100LU
R100LU
RY125LU
R125LU
RY140LU
R140LU
RG71A
RA140A
RG180A
R100FU
R125FU
Pre charged
*1
10 m
10 m
10 m
10 m
5 m
30 m
30 m
30 m
30 m
5 m
5 m
Max. length
25 m
20 m
25 m
30 m
30 m
50 m
(Equivalent length 70 m)
50 m
(Equivalent length 70 m)
50 m
(Equivalent length 70 m)
50 m
(Equivalent length 70 m)
50 m
(Equivalent length 70 m)
50 m
(Equivalent length 70 m)
Max. level difference
15 m
15 m
15 m
15 m
15 m
30 m
30 m
30 m
30 m
30 m
30 m
Note: 1 Additional refrigerant charging is required if the
refrigerant pipe is longer than the length.
4-direction piping offers greater layout freedom
(Applies to R(Y)71LU–140LU)
Piping can be run from the front, bottom, right or rear surface according to how the unit is installed.
Facilitates pump down
(Refrigerant recovery function)
A pump-down switch is provided to make it easier to collect refrigerant if the unit is to be moved or layout modified.
Low gas level detection function
(Applies to R(Y)71LU–140LU)
Effective gas monitoring reduces the labor required for operation, maintenance, and repairs.
Flexible design for large room or multi-use
Piping can be drawn out from three directions - front, left side, or below.
200 and 250 class models can be combined for centralised, horizontal-series installation
Common width and depth make series installation easy.
R(Y)200KU R(Y)200KU R(Y)250KU
690 mm
1280 mm 1280 mm 1280 mm
Allowed refrigerant pipe length and
level difference
Pre charged
*1
Max. length Max. level difference
R(Y)200KU
R(Y)250KU
5 m
5 m
50 m
(Equivalent length 70 m)
50 m
(Equivalent length 70 m)
30 m
30 m
Note: 1 Additional refrigerant charging is required if the
refrigerant pipe is longer than the length.
Also adapts to year-round cooling
RY200 K U a n d 250KU can adapt up to 0 ° C.
(Heat pump only)
RU08/10K models are available in two type depending on installation conditions
RU08/10KU models are factory shipped with refrigerant charged for
5 m of piping.
RU08/10K models are factory shipped with no refrigerant charged.
D u r a bilit y
Heat exchange fins provided with anti-corrosion treatment
To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated PE fins (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.
Construction
Non-treated fin
PE fin
Aluminium
(Applies to all outdoor units)
Hydrophilic film
Aluminium
C orrosion resistant acrylic resin
34
35
LCD REMOTE
CONTROLLERS
Necessary optional accessory
Easy-to-read LCD remote controller allows various system control configurations and can control multiple indoor units.
Remote controller options are shown on the page introducing each indoor unit model.
Wired LCD remote controller
Easier to read because LCD screen is larger.
BRC1C61
For easier operation, louver switches, which are frequently used, have been made larger.
Oil-resistant plastic casing.
Only 17 mm thick. Can be installed either recessed or exposed.
Indoor units applicable for the remote controller
CEILING MOUNTED CASSETTE TYPE
CEILING SUSPENDED TYPE
CEILING SUSPENDED CASSETTE TYPE
CEILING MOUNTED CASSETTE CORNER TYPE
WALL MOUNTED TYPE
CEILING MOUNTED BUILT-IN TYPE
*1
DUCT CONNECTION LOW STATIC PRESSURE TYPE
*2
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
DUCT CONNECTION HIGH STATIC PRESSURE TYPE *2
BRC1C61
*1. When the auto-swing function is not available, the message,
THIS FUNCTION IS NOT AVAILABLE is displayed when
the wind direction adjustment button is pressed.
*2. Applicable to only heat pump type.
Wired LCD remote controller with weekly schedule timer
Remote control is equipped with weekly timer function.
BRC1D61
24-hour clock function (1-hour backup for power failures)
Programming function for each day of week.
Scheduling possible of start/stop and temperature limit (5 settings/day)
Programming can be enabled or disabled.
Copy function for programmed schedules.
Indoor units applicable for the remote controller
CEILING MOUNTED CASSETTE TYPE
CEILING SUSPENDED TYPE
CEILING SUSPENDED CASSETTE TYPE
CEILING MOUNTED CASSETTE CORNER TYPE
WALL MOUNTED TYPE
CEILING MOUNTED BUILT-IN TYPE
*1
DUCT CONNECTION LOW STATIC PRESSURE TYPE
*2
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
DUCT CONNECTION HIGH STATIC PRESSURE TYPE *2
BRC1D61
*1. When the auto-swing function is not available, the message,
THIS FUNCTION IS NOT AVAILABLE is displayed when
the wind direction adjustment button is pressed.
*2. Applicable to only heat pump type.
•Standard remote controller (BRC1C61) is not required.
•If the BRC1D61 is connected to the centralised remote controller,
the schedule function is not available.
Wireless LCD remote controller
signal receiver mounted type The wireless remote controller is supplied in a set with a signal receiver.
Shape of signal receiver unit differs according to the indoor unit.
Note: The signal receiver unit shown in the photograph is for mounting inside the decoration panel of the ceiling mounted
W ir e d r e m o te c o ntr o lle r ha s bu ilt-in te m pe ra ture -s e ns or
(Applies to wired remote controllers)
Enables temperature sensing closer to target area for improved comfort. (When using remote control from another room, temperature-sensor in indoor unit's air inlet must be selected.)
Note: The indoor unit’s temperature-sensor is specified at the time of shipment. Temperature sensing with the wired remote controller is not available with the ceiling mounted cassette corner, ceiling-mounted built-in, and duct connection type.
N o n-po la r , do u ble -c o r e c o nne c tio n s pe c ific a tio ns s im plify w ir ing
Non-polar, double-core remote controller wire prevents wiring mistakes. signal receiver unit (or decoration panel) of wireless type is also easy to connect.
F a c ilita te s m a inte na nc e a nd r e pa ir
All initial settings can be set from the remote controller. After interior construction is complete, ceiling mounted units can be remotely set without having to use stepladder access for manual setting.
Setting contents: High ceiling use, air direction, filter type, address for centralised control (group control address is set automatically).
Remote controller is equipped with model name and failure display functions. This facilitates service in the unlikely event of a malfunction.
S k y A ir s ha r e s c o m m o n c o ntr o l w ith
H R V (he a t r e c la im v e ntila tio n) a nd the o the r Da ik in a ir -c o nditio ning u nits , thu s s im plify ing inte r lo c k ing o pe r a tio ns .
Easily adaptable to large-scale, highfunction, centralised remote control systems.
Installing and connecting control wiring between
SkyAir and other Daikin air-conditioning equipment is easy.
Optional adaptor for external commands or remote control of external equipment has been standardised to one type.
Signal receiver unit
(For ceiling mounted
cassette type)
Wireless remote controller
Signal receiver unit is contained inside decoration panel or indoor unit
Heat pump Cooling only
CEILING MOUNTED
CASSETTE TYPE
BRC7C612W BRC7C613W
CEILING SUSPENDED TYPE BRC7E63W BRC7EA66
CEILING SUSPENDED
CASSETTE TYPE
WALL MOUNTED TYPE
FAY71L
FAY100FA
DUCT CONNECTION
LOW STATIC PRESSURE TYPE
DUCT CONNECTION
MIDDLE STATIC PRESSURE TYPE
DUCT CONNECTION
HIGH STATIC PRESSURE TYPE
BRC7C528W BRC7C529W
BRC7EA618 BRC7E619
BRC7C610W BRC7C611W
BRC4C62
BRC4C62
BRC4C62
BRC4C64
LCD REMOTE CONTROLLER
L C D pa n e l s h o w s o pe r a t in g s t a t u s in le t t e r s , n u m be r s , a n d m o t io n .
Airflow / swing display Displays auto-swing operating status and setting position of air discharge angle.
(Not available for ceiling mounted built-in type and duct connection type )
Preset temperature / operation mode display Displays preset room temperature and operating status (fan, dry, cool).
Programming time display Operation start and stop time can be set for individual timers up to 72 hours. The liquid crystal display also shows when it is time to clean the filter, when changeover is under centralised control, and ventilation/cleaning.
Self-diagnosis function Monitors operating status within the system covering 40 items, and displays a message to indicate as soon as a malfunction occurs.
S im ple s y s t e m pr o v ide s a div e r s e a s s o r t m e n t o f c o n t r o l m o de s .
Control pattern Wired remote controller Wireless remote controller
Control by 1 remote controller
(Basic system)
Control by 2 remote controllers
For control from 2 locations such as in room and control room, exits, etc.
Non-polar, double-core
(max. wiring length 500 m)
C onnects 2 wired remote controllers
S ignal receiver unit installed on indoor unit
C ontrol by 1 wireless remote controller and 1 wired remote controller (S ee note 1)
S ignal receiver unit installed on indoor unit
Group control
For simultaneous control of up to 16 indoor units.
Automatic address setting function
Control by external command
Operation and surveillance is carried out using the contact signal from the operation control box in the building surveillance (security) room.
(C ommand from outside)
Optional wiring adaptor for electrical appendices is necessary
C entral remote controller (option)
Automatic address setting function
S ignal receiver unit installed on 1 indoor unit
(C ommand from outside)
Optional wiring adaptor for electrical appendices is necessary
C entral remote controller (option)
Centralised remote control
Centralised control of up to 64 indoor groups from remote location up to 1 kilometer away.
Interlock control with HRV
Link by remote controller group control.
Optional S kyAir series interface adaptor required. *1
HR V
C an be operated simultaneously or independently by remote controller
(set by ventilation mode)
C entral remote controller (option)
Optional S kyAir series interface adaptor required. *1
HR V
C an be operated simultaneously by remote controller
(set by ventilation mode)
C entral remote controller (option)
Zone link control by centralised control.
HR V HR V
HR V for indoor units within a zone are operated by interlocking
C an also be operated independently by remote controller.
Optional interface adaptor for SkyAir series is necessary *1
HR V for indoor units within a zone are operated by interlocking
Optional interface adaptor for S kyAir series is necessary *1
Note: When a wireless remote controller is used, remote control by two remote controllers is not possible.
*1. DIII-net adaptor function is standard equipment for the FAY71L.
Easily adaptable to large-scale, high-function, centralised remote control system.
C e ntra l re m ote c ontrolle r U nifie d on/off c ontrolle r S c h e du le t im e r
DCS302CA61 (Option) DCS301BA61 (Option) DST301BA61 (Option) DCS601C51 (Option)
Centralised control, with setting as simple as it is with a standard remote controller, of up to 64 groups
(1,024 indoor units) is possible.
Centralised control of on/off by group or all at once for up to 256 indoor units.
Interface adaptor for SkyAir series
Enables centralised control via connection to a high-speed, DIII-NET communication system, adopted for the Daikin VRV system.
DTA102A52 (Option) Necessary for interface adaptor for SkyAir series with the central remote control units shown at above.
Note : DIII-net adaptor function is standard equipment for the FAY71L.
Unified control of weekly schedule for up to 1,024 indoor units.
Schedule timer sets on/off time in 1 minute units to be executed twice a day for a week at a time.
With its high functionality, the full color “all-in-one” graphic controller facilitates management of Skyair
System in a variety of ways.
*Please refer to the page 59 for the details.
Central control adaptor kit *2
DTA107A55 (Option)
(for FD series)
*2.The central control adaptor kit for FDB series can be made to order.
36
Abundance of functions that provide comfortable air-conditioning in stores and offices.
Note: Some features only available on selected models. See model pages for full list of features applicable to each unit.
C o m f o r t
A u t o -s w in g
Delivers comfortable air-conditioning to all areas, near to and far from the air-conditioner.
H igh fa n s pe e d m o de
You can increase fan speed approximately 10% higher than the "high" setting.
Applicable for wall mounted type
H igh -c e ilin g a pplic a t io n
Delivers air-conditioning comfort all the way down to the floor in air-conditioning zones with high ceilings.
Air discharge direction angle can be set (fixed setting)
S w in g pa t t e r n s e le c t io n
(draft prevention, standard, ceiling soiling prevention)
You can freely set 3 air discharge positions by remote controller.
Applicable for ceiling mounted cassette type and ceiling mounted
cassette corner type.
(1) Air direction in standard position
(2) Air direction in draft prevention position
(3) Air direction in ceiling soiling prevention position
D r a ft pr e v e n t io n fu n c t io n
(heating)
To prevent cold air drafts, automatically adjusts airflow to horizontal vector when heating initially starts or when the thermostat turns off.
(Horizontal air discharge)
S w it c h a ble fa n s pe e d
High setting provides maximum reach while low setting minimises drafts.
P r o gr a m m e " D r y "
Dehumidification is microprocessor controlled to prevent uncomfortable changes in air temperature.
Useful for reducing uncomfortable humidity without uncomfortable cooling.
Note:When units are installed on high ceilings, depending on the model, various restrictions concerning maximum height, air discharge direction, and choice of options may apply.
T w o s e le c t a ble t e m pe r a t u r e -s e n s o r s
Temperature-sensors are included in the indoor unit and optional wired remote controller.
Temperature sensing closer to target area is possible to further
Use the temperature-sensor in the indoor unit when controlling air conditioning from another room.
Note: Wireless remote controllers have no temperature-sensor.
H o t s t a r t
(after defrost)
Uncomfortable cold air draft is not discharged when heating operation starts or when switching to heat after defrosting.
Y e a r -r o u n d c o o lin g a pplic a ble
Efficient cooling even in winter when indoor temperatures are higher than those outside, such as in underground public spaces or offices with many computers.
• Heat pump/RY71—140LU: possible up to -5 ° C
• Cooling only/R71—140LU: possible up to -15 ° C
• The year-round cooling kit is required as option.
T im e r s e le c t o r
Operation starts when the preset time of the ON timer elapses and stops when the preset time of the
OFF timer elapses.
M o u l d p r e v e n t i o n
M o u ld-r e s is t a n t t r e a t m e n t fo r filt e r
Sanitary filter has mould-resistant treatment.
M o u ld-pr o o fin g dr a in pa n
Mould-proofing maintains hygiene by preventing growth in highly humid conditions.
T w in / triple / double tw in m ulti ope ra tion
Simultaneously operates 2–4 indoor units with a single outdoor unit.
O t h e r s
P E fin
To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated PE fins (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.
In high corrosive areas, regular maintenance needs to be carried out.
37
W o r k a n d S e r v i c i n g
D r a in pu m p m e c h a n is m
Steeper gradient realises more efficient condensate drainage.
High-lift is especially useful for long lengths of drain piping.
P r e c h a r ge d fo r u p t o 3 0 m e t r e s
If refrigerant piping length does not exceed 30 m, there is no need for on-site gas charging.
(Applies to R(Y)71LU–140LU)
L o n g-life filt e r
Maintenance is not required for one year (two years when a ceiling mounted cassette type is used).
C e ilin g s o ilin g pr e v e n t io n fu n c t io n
Daikin's innovative air discharge mechanism keeps airflow away from the ceiling. Ceiling cleaning is less frequently required.
F ilt e r s ign
The filter sign warns you when it is time to clean the filter.
*When using a wired remote controller the sign is displayed in the LCD. When using a wireless remote controller the filter sign lamp illuminates on the signal receiver unit.
L o w ga s pr e s s u r e de t e c t io n
Insufficient gas charging is normally hard to detect.
During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure.Reliability is assured and maintenance and inspection can be carried out more quickly.
E m e r ge n c y o pe r a t io n
If there is a malfunction elsewhere in the system, the fan or compressor can still be operated.
S e lf dia gn o s is fu n c t io n
The operating parameters of indoor and outdoor units, and sensor data at critical locations throughout the system, are constantly monitored using a microcomputer.
To facilitate quick response in the event of a malfunction, a message appears on the LCD of the remote controller and an LED on the unit illuminates.
C o n t r o l f e a t u r e s
A u t o -r e s t a r t
If there is a power outage while the equipment is operating, operations will restart in the same mode as before the power cut when electricity is restored.
A u t o c o o l/h e a t c h a n ge -o v e r
(Heat pump only)
Detects difference in preset temperature and actual room temperature and automatically switches to cooling or heating accordingly.
C o n t r o l by 2 r e m o t e c o n t r o lle r s
Using 2 remote controllers you can operate the equipment locally or from a remote location.
Note: When a wireless remote controller is used, remote control by two remote controllers is not possible.
C o n t r o l by 1 r e m o t e c o n t r o lle r
You can turn up to 16 indoor units on/off with a single remote controller. (When using connected indoor units, the settings must all be the same and on/off will be simultaneous.)
E x t e r n a l c o m m a n d c o n t r o l
Operation and surveillance is carried out using the contact signal from the operation control box in the building surveillance (security) room.
C e n t r a l r e m o t e c o n t r o l
Optional central remote controller enables centralised control of up to 1024 indoor units (64 groups) from up to 1 kilometer away.
I n t e r lo c k c o n t r o l
Enables interlocking control with external equipment such as heat reclaim ventilation (HRV).
O p t i o n s
H igh -e ffic ie n c y filt e r u n it
Two types are available: 65% and 90% colorimetry.
U lt r a lo n g-life filt e r
Requires no maintenance for about 4 years * (10,000 h) in stores and offices.
* For dust concentration of 0.15 mg/m 3
F r e s h -a ir in t a k e k it
You can provide air-conditioning with fresh air from outside. Convenient for places where a ventilation fan cannot be installed.
Note:
*Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be procured locally.
**Outside Air fan interlocked with air conditioning unit is necessary. Optional
PCB(KRP1C63)is required for interlocking.
***It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating noise and may also influence temperature sending.
38
39
CEILING MOUNTED CASSETTE TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Power consumption 1a/1b
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Colour
Airflow rate (H)
Unit
Decoration panel
Sound level (H/L) 2
Dimensions
(H X W X D)
Unit
Decoration panel
Machine weight
Unit
Decoration panel
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation dB(A) mm kg
°
CDB mm mm mm mm m m kW
Btu/h kcal/h kW
35
FHC35KVE
50
FHC50KVE
60
FHC60KVE
71
FHYC71KVE
100
FHYC100KVE
125
FHYC125KVE
140
FHYC140KVE
R35GV1 R50GV1 R60GV1
R71LUV1
R71LUY1
R100LUV1
R100LUY1
R125LUY1 R140LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
3.54/3.5
12,100/11,900
3,040/3,010
1.20/1.20
5.34/5.3
18,200/18,100
4,590/4,560
2.02/2.01
6.44/6.4
22,000/21,800
5,540/5,500
2.45/2.44
7.8/7.7
26,600/26,200
6,700/6,600
3.07/3.07 (V1)
3.05/3.05 (Y1)
10.6/10.5
36,100/35,700
9,100/9,000
4.01/4.01 (V1)
3.96/3.96 (Y1)
13.0/12.8
44,500/43,600
11,200/11,000
4.96/4.96
14.5/14.2
49,400/48,400
12,500/12,200
5.02/5.02
m 3 /min cfm dB(A) mm mm kg kg
°
CWB kW kg
14
494
33/29
230 X 840 X 840
40 X 950 X 950
24
5
15
529
33/29
230 X 840 X 840
40 X 950 X 950
24
5
14 to 23
19
670
35/30
230 X 840 X 840
40 X 950 X 950
24
5
230
40 X
----------
White
19
X
670
35/30
840
950
24
5
X
X
840
950
28
988
39/34
288 X 840 X 840
40 X 950 X 950
28
5
288
40
14 to 25
1,164
42/36
X
X
33
840
950
28
5
X
X
840
950
35
1,235
44/37
288 X 840 X 840
40 X 950 X 950
28
5
Ivory white
1.1
Hermetically sealed rotary type
1.7
2.2
2.24
Hermetically sealed scroll type
3.00
3.75
4.50
1.10
(Charged for 10 m)
1.20
1.50
2.8
3.7
3.7
4.1
(Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)
48
540 X 750 X 270
49
540 X 750 X 270
54
685 X 800 X 300
48
770 X 900 X 320 1,170 X
49
900 X 320 1,170 X
49
900 X 320
54
1,345 X 900 X 320
37
19.4 to 46
42
19.4 to 54
61
19.4 to 46
72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98
21 to 46, -15 to 46 3 (Option installed)
109 o/6.4
o/12.7
o/6.4
o/15.9
o/6.4
o/15.9
o/9.5
o/15.9
o/9.5
o/19.1
o/9.5
o/19.1
o/9.5
o/19.1
I.Do/25 X O.Do/32 I.Do/25 X O.Do/32 I.Do/25 X O.Do/32 I.Do/25 X O.Do/32 I.Do/25 X O.Do/32 I.Do/25 X O.Do/32 I.Do/25 X O.Do/32 o/18.0 (Hole)
25 o/18.0 (Hole)
30 o/18.0 (Hole) o/26.0 (Hole) o/26.0 (Hole) o/26.0 (Hole)
50 (equivalent length 70 m) o/26.0 (Hole)
15 30
Both liquid and gas piping
CEILING SUSPENDED TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Power consumption
Indoor unit
Outdoor unit
Colour
1a/1b
Airflow rate (H)
Indoor unit
Outdoor unit
Sound level (H/L)
Dimensions (H X
Machine weight
W
2
X D)
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
Btu/h kcal/h m kW kW
3 /min cfm dB(A) mm kg
°
CWB kW kg dB(A) mm kg
°
CDB mm mm mm mm m m
35 50 60 71 100 125
FH35BVE FH50BVE FH60BVE FHY71BVE
R71LUV1
FHY100BVE
R100LUV1
FHY125BVE
R35GV1 R50GV1 R60GV1
R71LUY1 R100LUY1
R125LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
3.54/3.4
12,100/11,600
3,040/2,930
1.51/1.50
5.19/5.1
17,700/17,500
4,460/4,400
2.16/2.15
6.6/6.5
22,760/22,200
5,690/5,600
2.80/2.78
7.8/7.7
26,600/26,200
6,700/6,600
3.10/3.10 (V1)
3.08/3.08 (Y1)
10.6/10.5
36,100/35,700
9,100/9,000
3.90/3.90 (V1)
3.85/3.85 (Y1)
13.0/12.8
44,500/43,600
11,200/11,000
4.92/4.92
White
13
458
37/32
195 X 960 X 680
23
195
13
458
38/33
X 960 X 680
16
564
38/33
195 X 1,160 X 680
26
17
600
39/35
195 X 1,160 X 680
27
24
847
42/37
195 X 1,400 X 680
32
14 to 25
30
1,059
44/39
195 X 1,590 X 680
35 24
14 to 23
Ivory white
1.1
Hermetically sealed rotary type
1.7
2.2
2.24
Hermetically sealed scroll type
3.00
3.75
1.10
1.20
1.50
2.8
3.7
3.7
(Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)
540 X
48
750 X 270 540 X
49
750 X 270 685 X
54
800 X 300
48
770 X 900 X 320
49
1,170 X 900 X 320
49
1,170 X 900 X 320
37
19.4 to 46
42
19.4 to 54
61
19.4 to 46
72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98
21 to 46, -15 to 46 3 (Option installed) o/6.4
o/12.7
o/6.4
o/15.9 o/6.4
o/15.9
o/9.5
o/15.9
o/9.5
o/19.1
o/9.5
o/19.1
I.D o/20 X O.D o/26 I.D o/20 X O.D o/26 I.D o/20 X O.D o/26 I.D o/20 X O.D o/26 I.D o/20 X O.D o/26 I.D o/20 X O.D o/26 o/18.0 (Hole)
25 o/18.0 (Hole)
15
30 o/18.0 (Hole) o/26.0 (Hole) o/26.0 (Hole)
50 (equivalent length 70 m)
30 o/26.0 (Hole)
Both liquid and gas piping
Note :
1 Rated cooling capacities are based on the following conditions:
1a
1b
Indoor temp., 27
°
CDB, 19.5
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
Indoor temp., 27
°
CDB, 19.0
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.)
2 Anechoic chamber conversion value, measured according to JIS parameters and criteria.
3
During operation these values are somewhat higher owing to ambient conditions.
This value is for when year-round cooling kit (option) is installed.
CEILING SUSPENDED CASSETTE TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Power consumption 1a/1b
Indoor unit
Colour
Airflow rate (H)
Indoor unit
Outdoor unit
Outdoor unit
Sound level (H/L) 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Max. interunit piping length
Outdoor unit
Max. installation level difference
Heat insulation kW
Btu/h kcal/h kW m 3 /min cfm dB(A) mm kg
°
CWB kW kg dB(A) mm kg
°
CDB mm mm mm mm m m
71
FUY71FJV1
R71LUV1
R71LUY1
100
FUY100FJV1
R100LUV1
R100LUY1
125
FUY125FJV1
R125LUY1
7.8/7.7
26,600/26,200
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
10.6/10.5
36,100/35,700
13.0/12.8
44,500/43,600
6,700/6,600
3.08/3.08 (V1)
3.06/3.06 (Y1)
9,100/9,000
4.07/4.07 (V1)
4.02/4.02 (Y1)
11,200/11,000
4.97/4.97
19
670
40/35
165 X 895 X 895
25
2.24
2.8 (Charged for 30 m)
48
770 X 900 X 320
72 (V1), 71 (Y1)
/ 9.5
/ 15.9
I.D o/20 X O.D o/26 o/26.0 (Hole)
White
29
1,023
43/38
230 X 895 X 895
31
14 to 25
Ivory white
Hermetically sealed scroll type
3.00
3.7 (Charged for 30 m)
49
1,170 X 900 X 320
87 (V1), 84 (Y1)
21 to 46, -15 to 46 3 (Option installed)
/ 9.5
/ 19.1
I.D o/20 X O.D o/26 o/26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
32
1,129
44/39
230 X 895 X 895
31
3.75
3.7 (Charged for 30 m)
49
1,170 X 900 X 320
98
/ 9.5
/ 19.1
I.D o/20 X O.D o/26 o/26.0 (Hole)
CEILING MOUNTED CASSETTE CORNER TYPE
Indoor unit
35
FHK35FV1
Model
Name
Outdoor unit R35GV1
Power supply
Cooling capacity 1a/1b kW
Btu/h kcal/h
3.54/3.4
12,100/11,600
3,040/2,930
45
FHK45FV1
R50GV1
60
FHK60FV1
R60GV1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
5.19/5.1
17,700/17,500
4,460/4,400
6.6/6.5
22,760/22,200
5,690/5,600
Power consumption 1a/1b
Indoor unit
Outdoor unit kW
Colour Unit
Airflow rate (H)
Decoration panel
Sound level (H/L)
Dimensions
(H X W X D)
Unit
2
Decoration panel
Unit
Machine weight
Decoration panel
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Machine weight
Certified operation range m 3 /min cfm dB(A) mm mm kg kg
°
CWB kW kg dB(A) mm kg
°
CDB
1.41/1.40
19.4 to 46
2.25/2.24
2.76/2.74
12
423
39/33
215 X 1,110 X 710
70 X 1,240 X 800
30
8.5
1.1
1.10 (Charged for 10 m)
48
540 X 750 X 270
37
----------
White
12
423
39/34
215 X 1,110 X 710
70 X 1,240 X 800
31
8.5
14 to 23
17
600
41/36
215 X 1,310 X 710
70 X 1,440 X 800
33
9.5
Ivory white
Hermetically sealed rotary type
1.7
1.20 (Charged for 10 m)
49
2.2
1.50 (Charged for 5 m)
54
540 X 750 X 270
42
685 X 800 X 300
61
19.4 to 54 19.4 to 46
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation mm mm mm mm m m o/6.4
o/12.7
I.D o/25 X O.D o/32 o/18.0 (Hole)
25 o/6.4
o/15.9
I.D o/25 X O.D o/32 o/18.0 (Hole) o/6.4
o/15.9
I.D o/25 X O.D o/32 o/18.0 (Hole)
30
15
Both liquid and gas piping
Note :
1 Rated cooling capacities are based on the following conditions:
1a
1b
Indoor temp., 27
°
CDB, 19.5
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
Indoor temp., 27
°
CDB, 19.0
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R125LU is 7.5 m.)
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3 This value is for when year-round cooling kit (option) is installed.
71
FHYK71FJV1
R71LUV1
R71LUY1
7.8/7.7
26,600/26,200
6,700/6,600
3.07/3.07 (V1)
3.05/3.05 (Y1)
17
600
41/36
215 X 1,310 X 710
70 X 1,440 X 800
33
9.5
14 to 25
Hermetically sealed scroll type
2.24
2.8 (Charged for 30 m)
48
770 X 900 X 320
72 (V1), 71 (Y1)
21 to 46
-15 to 46 3 (Option installed) o/9.5
o/15.9
I.D o/25 X O.D o/32 o/26.0 (Hole)
50 (equivalent length 70 m)
30
40
41
CEILING MOUNTED BUILT-IN TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Power consumption 1a/1b
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Colour
Airflow rate (H)
Unit
Decoration panel
Sound level (H/L) 2
Dimensions
(H X W X D)
Unit
Decoration panel
Machine weight
Unit
Decoration panel
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation dB(A) mm kg
°
CDB mm mm mm mm m m kW
Btu/h kcal/h kW m 3 /min cfm dB(A) mm mm kg kg
°
CWB kW kg
35
FHB35FV1
R35GV1
3.54/3.4
12,100/11,600
3,040/2,930
1.47/1.46
45
FHB45FV1
R50GV1
60
FHB60FV1
R60GV1
71
FHYB71FV1
R71LUV1
R71LUY1
100
FHYB100FV1
R100LUV1
R100LUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
5.19/5.1
6.6/6.5
7.8/7.7
10.6/10.5
17,700/17,500
4,460/4,400
2.33/2.32
22,760/22,200
5,690/5,600
2.78/2.76
26,600/26,200
6,700/6,600
3.13/3.13 (V1)
3.11/3.11 (Y1)
36,100/35,700
9,100/9,000
4.00/4.00 (V1)
3.95/3.95 (Y1)
125
FHYB125FV1
R125LUY1
13.0/12.8
44,500/43,600
11,200/11,000
4.74/4.74
11.5
405
38/32
300 X 700 X 800
55 X 880 X 500
30
3.5
14
494
39/34
300 X 700 X 800
55 X 880 X 500
31
3.5
14 to 23
17
600
41/35
300 X 1,000 X 800
55 X 1,100 X 500
41
4.5
----------
White
19
670
41/35
300 X 1,000 X 800
55 X 1,100 X 500
41
4.5
27
953
41/35
300 X 1,400 X 800
55 X 1,500 X 500
51
6.5
14 to 25
35
1,235
44/38
300 X 1,400 X 800
55 X 1,500 X 500
52
6.5
Ivory white
1.1
Hermetically sealed rotary type
1.7
2.2
2.24
Hermetically sealed scroll type
3.00
3.75
1.10
1.20
1.50
2.8
3.7
3.7
(Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)
48
540 X 750 X 270
49
540 X 750 X 270
54
685 X 800 X 300
48
770 X 900 X 320
49
1,170 X 900 X 320
49
1,170 X 900 X 320
37
19.4 to 46
42
19.4 to 54
61
19.4 to 46
72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98
21 to 46, -15 to 46 3 (Option installed) o/6.4
o/12.7
o/6.4
o/15.9
o/6.4
o/15.9
o/9.5
o/15.9
o/9.5
o/19.1
o/9.5
o/19.1
I.D o/25 X O.D o/32 I.D o/25 X O.D o/32 I.D o/25 X O.D o/32 I.D o/25 X O.D o/32 I.D o/25 X O.D o/32 I.D o/25 X O.D o/32 o/18.0 (Hole)
25 o/18.0 (Hole)
30 o/18.0 (Hole) o/26.0 (Hole) o/26.0 (Hole)
50 (equivalent length 70 m) o/26.0 (Hole)
15 30
Both liquid and gas piping
WALL MOUNTED TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Power consumption 1a/1b
Indoor unit
Outdoor unit kW
Btu/h kcal/h kW
71
FAY71LVE
R71LUV1
100
FAY100FAVE
R100LUV1
R71LUY1 R100LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
7.8/7.7
26,600/26,200
6,700/6,600
2.98/ 2.98(V1)
2.96/2.96(Y1)
Indoor unit
Colour
Airflow rate (H)
Outdoor unit
Sound level (H/L) 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Colour
Compressor Type
Motor output
Piping connections
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Max. interunit piping length
Outdoor unit
Max. installation level difference
Heat insulation m 3 /min cfm
° dB(A) mm kg
CWB kW kg dB(A) mm kg
°
CDB mm mm mm mm m m
Note :
1 Rated cooling capacities are based on the following conditions:
(FHB) 1a
1b
Suction temp., 27
°
CDB, 19.5
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
(FAY)
1a
Suction temp., 27
°
CDB, 19.0
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R125LU is 7.5 m.)
Indoor temp., 27
° °
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
CDB, 19.5
Indoor temp., 27
°
CDB, 19.0
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R100LU is 7.5 m.)
2 Anechoic chamber conversion value, measured according to JIS parameters and criteria.
3
During operation these values are somewhat higher owing to ambient conditions.
This value is for when year-round cooling kit (option) is installed.
10.6/10.5
36,100/35,700
9,100/9,000
3.90/3.90 (V1)
3.85/3.85 (Y1)
White
19
670
43/37
290 X 1,050 X 230
13
23
811
45/41
360 X 1,570 X 200
26
14 to 25
Ivory white
Hermetically sealed scroll type
2.24
2.8 (Charged for 30 m)
48
770 X 900 X 320
72 (V1), 71 (Y1)
21 to 46, -15 to 46 3 (Option installed)
3.00
3.7 (Charged for 30 m)
1,170 X
49
900 X 320
87 (V1), 84 (Y1) o/9.5
o/15.9
I.D o/13 X O.D o/18 o/26.0 (Hole) o/9.5
o/19.1
I.D o/20 X O.D o/26 o/26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
FLOOR STANDING TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Indoor unit
Outdoor unit kW
Btu/h kcal/h kW Power consumption 1a/1b
Indoor unit
Colour
Airflow rate (H)
Outdoor unit
Sound level (H/L) 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Max. interunit piping length
Outdoor unit
Max. installation level difference
Heat insulation m 3 /min cfm dB(A) mm kg
°
CWB mm mm mm mm m m kW kg dB(A) mm kg
°
CDB
71
FVY71LAVE
100
FVY100LAVE
125
FVY125LAVE
R71LUV1 R100LUV1
R71LUY1 R100LUY1
R125LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
7.8/7.7
26,600/26,200
6,700/6,600
3.18/3.18 (V1)
3.16/3.16 (Y1)
10.6/10.5
36,100/35,700
9,100/9,000
4.03/4.03 (V1)
3.98/3.98 (Y1)
13.0/12.8
44,500/43,600
11,200/11,000
5.06/5.06
1,850
770 X
635
41/35
X
900
72 (V1), 71 (Y1)
I.D o/20
18
600
39
2.24
48 o/9.5
X o/15.9
X
X 270
2.8 (Charged for 30 m)
320
O.D o/26 o/26.0 (Hole)
White
28
988
46/40
1,850 X 600 X 350
46
14 to 25
Ivory white
Hermetically sealed scroll type
3.00
3.7 (Charged for 30 m)
49
1,170 X 900 X 320
87 (V1), 84 (Y1)
21 to 46, -15 to 46 3 (Option installed) o/9.5
o/19.1
I.D o/20 X O.D o/26 o/26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
1,850
1,170
X
32
1,129
49/43
600
47
3.75
X 350
3.7 (Charged for 30 m)
X o/9.5
o/19.1
I.D o/20
49
900
98
X
X 320
O.D o/26 o/26.0 (Hole)
DUCT CONNECTION LOW STATIC PRESSURE TYPE
Model
Name
Power supply
Cooling capacity unit unit
1a/1b, 4
Power consumption
Indoor
Outdoor
Colour
Airflow rate (H)
Fan
1a/1b
Indoor unit
Outdoor unit
Driving system
Sound level (H/L) 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation m 3 kW
Btu/h kcal/h kW
/min cfm dB(A)
° mm kg
CWB kW kg dB(A) mm kg
°
CDB mm mm mm mm m m
25
FDBG25AVE
R25JV1
35
FDBG35AVE
R35JV1
50
FDBG50AVE
R50GV1
60
FDBG60AVE
R60GV1
71
FDBG71AVE
R71FUV1
R71FUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
2.64/2.60
9,000/8,900
3.54/3.50
12,100/11,900
5.34/5.30
18,200/18,100
7.03/6.97
24,000/23,800
7.80/7.70
26,600/26,200
2,270/2,250
0.88/0.87
13
458
3,040/3,010
1.25/1.24
13
458
4,590/4,560
2.06/2.05
----------
13
458
Direct drive (2 speed)
6,050/6,000
2.76/2.75
18
635
6,700/6,600
2.82/2.80
18
635
260
41/38
X 900
22
X 580
25
41/38
260 X 900 X 580
22
14 to 23
(Charged for 10 m)
560 X
0.7
0.8
46
695
27 o/6.4
o/9.5
3/4B
X 265 o/18.0 (Hole)
19.4 to 46
Ivory white
Hermetically sealed rotary type
1.1
1.7
1.0
(Charged for 10 m)
48
560 X 695 X 265
33 o/6.4
o/12.7
3/4B o/18.0 (Hole)
1.20
(Charged for 10 m)
540 X
49
750 X 270
42
19.4 to 54 o/6.4
o/15.9
3/4B o/18.0 (Hole)
15
41/38
260 X 900 X 580
23
Note :
1 Rated cooling capacities are based on the following conditions:
(FVY)
1a
1b
(FDBG)
Indoor temp., 27
°
Indoor temp., 27
°
1a
1b
CDB, 19.5
°
CWB; outdoor temp. 35
°
CDB, 19.0
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
Suction temp., 27
°
CDB, 19.5
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
Suction temp., 27
°
CDB, 19.0
°
CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R125LU is 7.5 m.)
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
3
During operation these values are somewhat higher owing to ambient conditions.
This value is for when year-round cooling kit (option) is installed.
4 Capacities are gross, with no deduction made for evaporator fan motor heat.
30
Both liquid and gas piping
42/39
260 X 1,300 X 580
31
(Charged for 5 m)
685 X
2.2
1.50
54
800
61 o/6.4
3/4B
X o/15.9
300
19.4 to 46 o/18.0 (Hole)
42/39
260 X 1,300 X 580
31
14 to 25
Hermetically sealed type
2.2
2.10
(Charged for 5 m)
52
816 X 880 X 370
87 (V1), 84 (Y1)
21 to 52 o/9.5
o/15.9
3/4B o/26.0 (Hole)
50 (equivalent length 70 m)
30
42
43
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Indoor unit
Outdoor unit
Power consumption 1a/1b
Indoor unit
Colour
Fan Airflow rate (H)
Outdoor unit
Sound level (H) 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation kW
Btu/h kcal/h kW m 3 /min cfm dB(A) mm kg
°
CWB kW kg dB(A) mm kg
°
CDB mm mm mm mm m m
71
FDMG71AV1
RG71AV1
RG71AY1
8.8/8.7
30,000/29,600
7,600/7,500
3.15/3.13
100
FDMG100AV1
R100FUV1
R100FUY1
125
FDMG125AV1
R125FUY1
140
FDMG140AV1
RG140AY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
10.6/10.5
13.1/12.9
14.5/14.2
36,100/35,700
9,100/9,000
4.08/4.04
44,500/43,600
11,200/11,000
4.89/4.85
----------
49,400/48,400
12,500/12,200
5.25/5.25
180
FDMG180AV1
RG180AY1
17.2/16.8
58,700/57,500
14,700/14,400
6.45/6.45
305 X
23
811
42
1,350
43
X 680 305 X
34
1,200
44
1,550
51
X 680
37
1,306
45
305 X 1,550 X 680
52
14 to 25
Ivory white
2.20
2.4 (Charged for 5 m)
52
Hermetically sealed type
3.00
2.4 (Charged for 5 m)
56
3.75
2.8 (Charged for 5 m)
57
816 X 880 X 370
87 (V1), 84 (Y1)
1,215 X 880 X 370
117 (V1), 109 (Y1)
21 to 52
1,215 X 880 X 370
110 o/9.5
/ 15.9
3/4B o / 26.0 (Hole) o o/9.5
/ 19.1
3/4B
/ 26.0 (Hole) o/9.5
/ 19.1
3/4B o / 26.0 (Hole)
50 (equivalent length 70 m)
30
42
1,412
46
305 X 1,550 X 680
52
Hermetically sealed scroll type
4.50
4.50
2.9 (Charged for 5 m)
55
2.8 (Charged for 5 m)
56
1,345 X 880 X 370
113
21 to 50
1,345 X 880 X 370
114 o/9.5
/ 19.1
3/4B o/26.0 (Hole)
42
1,482
47
305 X 1,900 X 680
58 o/9.5
/ 19.1
3/4B o/26.0 (Hole)
Both liquid and gas piping unit
Model
Name
Power supply
Cooling capacity 1a/1b
Power consumption 1a/1b
Indoor
Colour
Fan
Indoor unit
Outdoor unit
Airflow rate (H)
Outdoor unit
External static pressure
Sound level (H) 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation kW
Btu/h kcal/h kW m 3 /min cfm
Pa(mmH dB(A) mm kg
°
CWB kW kg
2
O) dB(A) mm kg
°
CDB mm mm mm mm m m
71
FDYM03FAV1
R71LUV1
R71LUY1
7.8/7.7
26,600/26,200
6,700/6,600
3.25/3.25 (V1)
3.23/3.23 (Y1)
295 X
20
706
98(10)
39
1,100
42
X 680
2.24
2.8 (Charged for 30 m)
48
770 X 900 X 320
72 (V1), 71 (Y1)
100
FDYM04FAV1
R100LUV1
R100LUY1
R125LUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
10.6/10.5
36,100/35,700
9,100/9,000
4.08/4.08 (V1)
4.03/4.03 (Y1)
13.0/12.8
44,500/43,600
11,200/11,000
5.06/5.06
----------
125
FDYM05FAV1
26
917
98(10)
39
295 X 1,500 X 680
56
35
1,235
98(10)
44
295 X 1,500 X 680
57
14 to 25
Ivory white
Hermetically sealed scroll type
3.00
3.75
3.7 (Charged for 30 m)
49
3.7 (Charged for 30 m)
49
1,170 X 900 X 320
87 (V1), 84 (Y1)
1,170 X 900
98
X
21 to 46, -15 to 46 3 (Option installed)
320
FDYM06FAV1
R140LUY1
49,400/48,400
12,500/12,200
295
14.5/14.2
5.18/5.18
X
140
37
1,306
98(10)
46
1,500
57
X 680
4.50
4.1 (Charged for 30 m)
54
1,345 X 900 X 320
109 o/9.5
/ 15.9
I.D o/25 X O.D o/32
/ 26.0 (Hole) o/9.5
o / 19.1
I.D o/25 X O.D o/32
/ o/9.5
19.1
I.D o/25 X O.D o/32
/ 26.0 (Hole) / 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions:
1a
1b
Suction temp., 27
°
CDB, 19.5
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
Suction temp., 27
°
CDB, 19.0
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.)
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
3
During operation these values are somewhat higher owing to ambient conditions.
This value is for when year-round cooling kit (option) is installed.
o/9.5
/ 19.1
I.D o/25 X O.D o/32 o/26.0 (Hole)
DUCT CONNECTION HIGH STATIC PRESSURE TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Indoor unit
Outdoor unit
71
FD03KY1
R71FUY1
Power consumption 1a/1b
Indoor unit
Colour
Airflow rate (H)
Outdoor unit
Fan External static pressure
Driving system
Sound level (H) 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation kW
Btu/h kcal/h kW m 3 /min cfm
Pa(mmH
2
O) dB(A) mm kg
°
CWB kW kg dB(A) mm kg
°
CDB mm mm mm mm m m
8.1/ 7.9
27,800/ 27,000
7,000/6,800
2.50/2.48
26
917
69 (7)
46
450 X 650 X 850
51
3.0
2.1
(Charged for 5 m)
52
816 X 880 X 370
84 o/9.5
o/15.9
o/26.0 (Hole)
100
FD04KY1
125
FD05KY1
R100FUY1 R125FUY1
Y1: 3 phase, 380–415 V, 50 Hz
11.0/10.8
37,700/36,900
9,500/9,300
3.52/3.48
14.0/13.8
47,600/46,800
12,000/11,800
4.19/4.15
----------
30
1,059
46
1,623
88 (9)
Belt drive
49
450 X 900 X 850
59 72
14 to 25
Ivory white
Hermetically sealed type
3.8
2.4
(Charged for 5 m)
4.5
2.8
(Charged for 5 m)
56 57
1,215 X 880 X 370
109 110
21 to 52 o/9.5
o/19.1
o/9.5
o/19.1
3/4B o/26.0 (Hole) o/26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
140
FD06KY1
RU06KY1
17.4/17.2
59,500/58,800
15,000/14,800
5.7/5.7
52
1,835
51
450 X 1,130 X 850
79
Hermetically sealed scroll type
4.5
3.0
(Charged for 5 m)
59
1,345 X 880 X 320
112 o/9.5
o/19.1
----------
Model
Name
Power supply
Cooling capacity 1a/1b
Indoor unit
Outdoor unit
200
FD08KY1
RU08KUY1 kW
Btu/h kcal/h kW
24.3/24.0
83,000/81,800
20,900/20,600
7.5/7.4
Power consumption 1a/1b
Indoor unit
Outdoor unit
Colour
Airflow rate (H)
Fan External static pressure
Driving system
Sound level (H) 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Colour
Compressor Type
Motor output m 3 /min cfm
Pa(mmH
2
O)
° dB(A) mm kg
CWB
68
2,400
51
500 X 1,130 X 850
93
98 (10)
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Piping connections
Liquid (Flare)
Gas (Brazing)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation kW kg dB(A)
° mm kg
CDB mm mm mm mm m m
7.5
5.0
(Charged for 5 m)
1,220 X
60
1,280
185 o/12.7
o/25.4
X 690
3/4B
Note :
Models RU08K(U)Y1 and RU10K(U)Y1 are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
1b
Suction temp., 27
°
CDB, 19.5
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
Suction temp., 27
°
CDB, 19.0
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
2 Anechoic chamber conversion value, measured according to JIS parameters and criteria.
3
During operation these values are somewhat higher owing to ambient conditions.
Specification for outdoor unit is for a single unit only.
250
FD10KY1
400
FD15KY1
RU10KUY1 RU08KUY1
Y1: 3 phase, 380–415 V, 50 Hz
X 2
29.7/29.2
101,200/ 99,600
48.6/47.9
166,000/163,500
25,500/25,100
9.9/9.8
41,800/41,200
15.0/14.8
----------
83
2,929
136
4,800
500
FD20KY1
RU10KUY1 X 2
59.3/58.4
202,400/199,400
51,000/ 50,200
19.8/19.6
166
5,859
Belt drive
53
500 X 1,330 X 850
104
58
625 X 1,620 X 850
161
14 to 25
Ivory white
Hermetically sealed scroll type
7.5
X 2 9.0
6.1
(Charged for 5 m)
5.0
(Charged for 5 m)
60 3
X 2
61
1,440 X 1,280 X 690
200
21 to 52
(1,220 X 1,280 X 690) X 2
185 X 2 o/15.9
o/31.8
o/12.7
X 2 o/25.4
X 2
147 (15)
60
625 X 1,980 X 850
187
9.0
X 2
6.1
(Charged for 5 m) X 2
61 3
(1,440 X 1,280 X 690) X 2
200 X 2 o/15.9
X 2 o/31.8
X 2
1B
----------
50 (equivalent length 70 m)
30
Both liquid and gas piping
44
45
DUCT CONNECTION HIGH STATIC PRESSURE TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Power consumption 1a/1b
Indoor unit
Colour
Airflow rate (H)
Outdoor unit
Indoor unit
Outdoor unit
Fan External static pressure
Driving system
Sound level (H) 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22) kW
Btu/h kcal/h kW m 3 /min cfm
Pa(mmH
2
O) dB(A) mm kg
°
CWB kW kg
200
FD08KY1
RU08KY1
24.3/24.0
83,000/81,800
20,900/20,600
7.5/7.4
68
2,400
Sound level 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Piping connections
Liquid (Brazing)
Gas (Brazing)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation dB(A) mm kg
°
CDB mm mm mm mm m m
Note :
Models RU08K(U)Y1 and RU10K(U)Y1 are recommended for commercial facilities.
1 Rated cooling capacities are based on the following conditions:
1a
1b
Suction temp., 27
°
CDB, 19.5
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
Suction temp., 27
°
CDB, 19.0
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3 Specification for outdoor unit is for a single unit only.
4
This is the amount of refrigerant required for piping of five meters or less.
Since the unit does not contain refrigerant when shipped from the factory, it must be added at the installation site.
For details, please refer to the installation manual.
250
FD10KY1
400
FD15KY1
RU10KY1 RU08KY1
Y1: 3 phase, 380–415 V, 50 Hz
X 2
29.7/29.2
101,200/ 99,600
25,500/25,100
9.9/9.8
48.6/47.9
166,000/163,500
41,800/41,200
15.0/14.8
----------
83
2,929
136
4,800
500
FD20KY1
RU10KY1 X 2
59.3/58.4
202,400/199,400
51,000/ 50,200
19.8/19.6
166
5,859
98 (10) 147 (15)
51
500 X 1,130 X 850
93
Belt drive
53
500 X 1,330 X 850
104
58
625 X 1,620 X 850
161
14 to 25
Ivory white
Hermetically sealed scroll type
9.0
7.5
X 2 7.5
5.0
(Field charge required for 5 m)
4
60
1,220 X 1,280 X 690
177 o/12.7
o/25.4
6.1
(Field charge required for 5 m)
4
61
1,440 X 1,280 X 690
190 o/15.9
o/31.8
5.0
(Field charge required for 5 m)
4
X 2
21 to 52
60 3
(1,220 X 1,280 X 690) X 2
177 X 2 o/12.7
X 2 o/25.4
X 2
3/4B 1B
60
625 X 1,980 X 850
187
9.0
X 2
6.1
(Field charge required for 5 m)
4
X 2
61 3
(1,440 X 1,280 X 690) X 2
190 X 2 o/15.9
X 2 o/31.8
X 2
----------
50 (equivalent length 70 m)
30
Both liquid and gas piping
Simultaneous operation system TWIN & TRIPLE & DOUBLE TWIN MULTI
CEILING MOUNTED CASSETTE TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Outdoor unit
Indoor unit
Outdoor unit
Power consumption 1a/1b
Indoor unit 3 kW
Btu/h kcal/h kW
Colour
Dimensions
(H X W X D)
Unit
Decoration panel
Airflow rate (H) m 3 /min cfm
Sound level (H/L)
Unit
2
Decoration panel dB(A) mm mm kg
Machine weight
Unit
Decoration panel kg
°
CWB Certified operation range
Colour
Compressor Type
Motor output kW
71
FHYC35KVE X 2
R71LUV1
100
FHYC50KVE X 2
R100LUV1
125
FHYC60KVE X 2
140
FHYC71KVE X 2
200
FHYC100KVE X 2
250
FHYC125KVE
R71LUY1 R100LUY1
R125LUY1 R140LUY1 R200KUY1 R250KUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
X 2
7.8/7.7
26,600/26,200
6,700/6,600
3.17/3.17 (V1)
3.15/3.15 (Y1)
10.6/10.5
36,100/35,700
9,100/9,000
4.06/4.06 (V1)
4.01/4.01 (Y1)
13.0/12.8
44,500/43,600
11,200/11,000
5.01/5.01
14.5/14.2
49,400/48,400
12,500/12,200
5.02/5.02
22.5/22.2
76,800/75,800
19,400/19,100
7.7/7.6
27.1/26.6
92,500/90,800
23,300/22,900
9.7/9.7
-------------
White
14
494
33/29
230 X 840 X 840
15
529
33/29
230 X 840 X 840
19
670
35/30
230 X 840 X 840
19
670
35/30
230 X 840 X 840
28
988
39/34
288 X 840 X 840
33
1,164
42/36
288 X 840 X 840
40 X 950 X 950
24
5
40 X 950 X 950
24
5
40 X 950 X 950
24
5
40 X 950 X 950
24
5
40 X 950 X 950
28
5
40 X 950 X 950
28
5
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Machine weight
Piping
Certified operation range
Liquid (Flare) connections Gas
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation kg dB(A) mm kg
°
CDB mm mm mm mm m m
14 to 25
Ivory white
2.24
3.00
Hermetically sealed scroll type
3.75
4.50
5.5
9.0
2.8
3.7
3.7
4.1
5.3
5.7
(Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 5 m) (Charged for 5 m)
48
770 X 900 X 320
72 (V1), 71 (Y1)
/ o / 9.5
15.9 (Flare)
I.D o/25 X O.D o/32
/ 26.0 (Hole)
49
1,170 X 900 X 320 1,170 X
49
900 X 320
87 (V1), 84 (Y1) 98
21 to 46, -15 to 46 4 (Option installed) o / 9.5
/ 19.1 (Flare)
I.D o/25 X O.D o/32
/ 26.0 (Hole)
/
/ 9.5
19.1 (Flare)
I.D o/25 X O.D o/32
54
1,345 X 900 X 320
109 o
/ 9.5
/ 19.1 (Flare)
I.D o/25 X O.D o/32
/ 26.0 (Hole) / 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
1,220 X
60
1,280
178
X 690 1,440 X 1,280 X 690
202
-5 to 52
61
/ 12.7
/ 25.4 (Flange)
I.D o/25 X O.D o/32
---------
/ 15.9
/ 28.6 (Flange)
I.D o/25 X O.D o/32
---------
Model
Name
Indoor unit
Outdoor unit
Power supply
Cooling capacity 1a/1b kW
Btu/h
Power consumption 1a/1b
Colour
Indoor unit 3
Airflow rate (H) kcal/h
Unit
Decoration panel m kW
3 /min cfm
Sound level (H/L) 2
Dimensions
(H X W X D)
Unit
Decoration panel dB(A) mm mm kg
Machine weight
Unit
Decoration panel
Outdoor unit
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Machine weight
Piping
Certified operation range
Liquid (Flare) connections Gas
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
° kg
CWB kW kg dB(A) mm kg
°
CDB mm mm mm mm m m
140
FHYC50KVE
R140LUY1
14.5/14.2
X
49,400/48,400
12,500/12,200
5.02/5.02
230
40 X
15
529
33/29
X 840
950
24
5
X
X
840
950
3
4.50
4.1 (Charged for 30 m)
54
1,345 X 900 X 320
109
21 to 46, -15 to 46 4 (Option installed)
/ 9.5
/ 19.1 (Flare)
I.D o/25 X O.D o/32
/ 26.0 (Hole)
200
FHYC71KVE X 3
R200KUY1
200
FHYC50KVE
R200KUY1
X 4
VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V, 50 Hz
22.5/22.2
22.5/22.2
76,800/75,800
19,400/19,100
7.7/7.6
76,800/75,800
19,400/19,100
7.7/7.6
230
40
X
X
19
670
840
950
24
5
X
X
840
950
-------------
White
14 to 25
Ivory white
5.5
Hermetically sealed scroll type
5.3 (Charged for 5 m)
5.5
5.3 (Charged for 5 m)
60
1,220 X 1,280 X 690
178
60
1,220 X 1,280 X 690
178
-5 to 52
/ 12.7
/ 25.4 (Flange)
I.D o/25 X O.D o/32
---------
/ 12.7
/ 25.4 (Flange)
I.D o/25 X O.D o/32
---------
50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
Models R200KU and R250KU are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
2
1b
Indoor temp., 27
°
CDB, 19.5
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
Indoor temp., 27
°
CDB, 19.0
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.)
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
3
4
During operation these values are somewhat higher owing to ambient conditions.
Values shown are for a single unit only.
This value is for when year-round cooling kit (option) is installed.
15
529
33/29
230 X 840 X 840
40 X 950
24
5
X 950
250
FHYC60KVE X 4
R250KUY1
27.1/26.6
92,500/90,800
23,300/22,900
9.7/9.7
19
670
35/30
230 X 840 X 840
40 X 950 X 950
24
5
9.0
5.7 (Charged for 5 m)
61
1,440 X 1,280 X 690
202 o / 15.9
/ 28.6 (Flange)
I.D o/25 X O.D o/32
---------
46
47
Simultaneous operation system TWIN & TRIPLE & DOUBLE TWIN MULTI
CEILING SUSPENDED TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Power consumption 1a/1b
Indoor unit 3
Outdoor unit
Indoor unit
Outdoor unit
Colour
Airflow rate (H)
Sound level (H/L) 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Colour
Compressor Type
Motor output m 3 /min cfm dB(A) mm kg
°
CWB kW
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Piping connections
Liquid (Flare)
Gas
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation kW
Btu/h kcal/h kW kg dB(A) mm kg
°
CDB mm mm mm mm m m
71
FHY35BVE
×
2
R71LUV1
100
FHY50BVE
×
2
R100LUV1
125
FHY60BVE
×
2
140
FHY71BVE
×
2
200
FHY100BVE
×
2
250
FHY125BVE
×
R71LUY1 R100LUY1
R125LUY1 R140LUY1 R200KUY1 R250KUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
2
7.8/7.7
26,600/26,200
6,700/6,600
3.20/3.20 (V1)
3.18/3.18 (Y1)
10.6/10.5
36,100/35,700
9,100/9,000
3.95/3.95 (V1)
3.90/3.90 (Y1)
13.0/12.8
44,500/43,600
11,200/11,000
4.98/4.98
14.5/14.2
49,400/48,400
12,500/12,200
5.17/5.17
22.5/22.2
76,800/75,800
19,400/19,100
7.7/7.6
27.1/26.6
92,500/90,800
23,300/22,900
9.7/9.7
White
13
458
37/32
195 X 960 X 680
23
770 X
2.24
2.8
(Charged for 30 m)
48
900 X 320
72 (V1), 71 (Y1)
13
458
38/33
195 X 960 X 680
24
16
564
38/33
195 X 1,160 X 680
26
17
600
39/35
195 X 1,160 X 680
27
3.00
3.7
(Charged for 30 m)
14 to 25
Ivory white
Hermetically sealed scroll type
3.75
4.50
3.7
(Charged for 30 m)
4.1
(Charged for 30 m)
54 49
1,170 X 900 X 320 1,170 X
49
900 X 320
87 (V1), 84 (Y1) 98
21 to 46, -15 to 46 4 (Option installed)
1,345 X 900
109
X 320
24
847
42/37
195 X 1,400 X 680
32
5.5
5.3
(Charged for 5 m)
30
1,059
44/39
195 X 1,590 X 680
35
9.0
5.7
(Charged for 5 m)
61
1,220 X
60
1,280
178
X 690 1,440 X 1,280 X 690
202
-5 to 52
/ 9.5
/ 15.9 (Flare)
I.D o/20 X O.D o/26
/ 26.0 (Hole) o / 9.5
/ 19.1 (Flare)
I.D o/20 X O.D o/26
/ 26.0 (Hole)
/ 9.5
/ 19.1 (Flare)
I.D o/20 X O.D o/26
30
/ 9.5
/ 19.1 (Flare)
I.D o/20 X O.D o/26
/ 26.0 (Hole) / 26.0 (Hole)
50 (equivalent length 70 m)
Both liquid and gas piping o / 12.7
/ 25.4 (Flange)
I.D o/20 X O.D o/26
---------
/ 15.9
/ 28.6 (Flange)
I.D o/20 X O.D o/26
---------
Model
Name
Power supply
Cooling capacity 1a/1b
Indoor unit
Outdoor unit kW
Btu/h kcal/h kW Power consumption 1a/1b
Colour
Indoor unit 3
Airflow rate (H) m 3 /min cfm dB(A) mm kg
°
CWB
Sound level (H/L) 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Colour
Outdoor unit
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Machine weight
Piping
Certified operation range
Liquid (Flare) connections Gas
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation kW kg dB(A) mm kg
°
CDB mm mm mm mm m m
140
FHY50BVE
×
3
R140LUY1
200
FHY71BVE
×
3
R200KUY1
200
FHY50BVE
×
4
R200KUY1
14.5/14.2
49,600/48,400
VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V,50 Hz
22.5/22.2
22.5/22.2
76,800/75,800 76,800/75,800
12,500/12,200
5.17/5.17
19,400/19,100
7.7/7.6
19,400/19,100
7.7/7.6
White
13
458
38/33
195 X 960 X 680
24
4.50
4.1 (Charged for 30 m)
54
1,345 X 900 X 320
109
21 to 46, -15 to 46 4 (Option installed)
17
600
39/35
195 X 1,160 X 680
27
13
458
38/33
195 X 960 X 680
24
14 to 25
Ivory white
Hermetically sealed scroll type
5.5
5.3 (Charged for 5 m)
1,220 X
60
1,280
178
X 690
5.5
5.3 (Charged for 5 m)
60
1,220 X 1,280 X 690
178
-5 to 52 o / 9.5
/ 19.1 (Flare)
I.D o/20 X O.D o/26
/ 26.0 (Hole)
/ 12.7
/ 25.4 (Flange)
I.D o/20 X O.D o/26
--------o / 12.7
/ 25.4 (Flange)
I.D o/20 X O.D o/26
---------
50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
Models R200KU and R250KU are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
Indoor temp., 27
°
CDB, 19.5
°
1b
Indoor temp., 27
°
CDB, 19.0
°
CWB; outdoor temp. 35
CWB; outdoor temp. 35
°
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.)
2 Anechoic chamber conversion value, measured according to JIS parameters and criteria.
3
During operation these values are somewhat higher owing to ambient conditions.
4
Values shown are for a single unit only.
This value is for when year-round cooling kit (option) is installed.
250
FHY60BVE
×
4
R250KUY1
27.1/26.6
92,500/90,800
23,300/22,900
9.7/9.7
16
564
38/33
195 X 1,160 X 680
26
9.0
5.7 (Charged for 5 m)
61
1,440 X 1,280 X 690
202
/ 15.9
/ 28.6 (Flange)
I.D o/20 X O.D o/26
---------
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Indoor unit
Outdoor unit
Power consumption 1a/1b
Indoor
Colour unit 3
Fan Airflow rate (H)
Outdoor unit
External static pressure
Sound level (H) 2
Dimensions (H X W X D)
Machine weight
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (H X W X D)
Piping connections
Machine weight
Certified operation range
Liquid (Flare)
Gas (Flange)
Drain
Max. interunit piping length
Max. installation level difference
Heat insulation
Indoor unit
Outdoor unit kW
Btu/h kcal/h kW m 3 /min cfm
Pa(mmH kW kg dB(A) mm kg
°
CDB mm mm mm mm m m
2
O) dB(A) mm kg
°
CWB
Note :
Models R200KU and R250KU are recommended for commercial facilities.
1 Rated cooling capacities are based on the following conditions:
1a
1b
Suction temp., 27
°
CDB, 19.5
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
Suction temp., 27
°
CDB, 19.0
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
3
During operation these values are somewhat higher owing to ambient conditions.
Values shown are for a single unit only.
200
FDYM04FAV1 × 2
R200KUY1
250
FDYM05FAV1
R250KUY1
× 2
200
FDYM03FAV1 × 3
R200KUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
22.5/22.2
76,800/75,800
19,400/19,100
295
7.7/7.6
X
26
917
98(10)
39
1,500
56
X 680
27.1/26.6
92,500/90,800
23,300/22,900
295 X
9.9/9.9
----------
35
1,235
98(10)
44
1,500
57
X 680
22.5/22.2
76,800/75,800
19,400/19,100
8.0/7.9
20
706
98(10)
39
295 X 1,100 X 680
42
5.5
5.3 (Charged for 5 m)
60
1,220 X 1,280 X 690
178
14 to 25
Ivory white
Hermetically sealed scroll type
9.0
5.7 (Charged for 5 m)
61
1,440 X 1,280 X 690
202
-5 to 52
5.5
5.3 (Charged for 5 m)
60
1,220 X 1,280 X 690
178 o / 12.7
o / 25.4
/ / 32O.D.
---------
/ 15.9
/ 28.6
/ / 32O.D.
---------
50 (equivalent length 70 m)
30
Both liquid and gas piping
/ 12.7
/ 25.4
/ / 32O.D.
---------
48
49
CEILING MOUNTED CASSETTE TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Heating capacity 2
Indoor unit
Outdoor unit
Power consumption
Indoor unit
Colour
Cooling 1a/1b
Heating 2
Airflow rate (H)
Unit
Decoration panel
Outdoor unit
Sound level (H/L) 3
Dimensions
(H
×
W
×
D)
Unit
Decoration panel
Machine weight
Certified operation range
Unit
Decoration panel
Cooling
Heating
Colour
Compressor Type
Motor output
Refrigerant charge (R-22) kW
Btu/h kcal/h kW
Btu/h kcal/h kW kW m 3 /min cfm dB(A) mm mm kg kg
°
°
CWB
CDB kW kg
35
FHYC35KVE
RY35FV1A
3.79/3.75
50
FHYC50KVE
RY50GAV1A
5.27/5.2
60
FHYC60KVE
RY60GAV1A
6.24/6.15
71
FHYC71KVE
RY71LUV1
RY71LUY1
7.8/7.7
100
FHYC100KVE
RY100LUV1
RY100LUY1
10.5/10.4
125
FHYC125KVE
RY125LUY1
13.0/12.8
140
FHYC140KVE
RY140LUY1
VE: 1 Phase 220–240/220 V, 50/60 Hz V1: 1 Phase 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
14.5/14.2
12,900/12,800
3,260/3,230
4.22
14,400
3,630
1.51/1.50
1.37
14
494
33/29
230
×
840
×
840
40 × 950 × 950
24
5
18,000/17,800
4,530/4,470
5.8
19,800
4,990
1.92/1.91
1.68
15
529
33/29
230
×
840
×
840
40 × 950 × 950
24
5
14 to 23
15 to 28
21,300/21,000
5,370/5,290
7.0
23,900
6,020
2.35/2.33
2.26
19
670
35/30
230
×
840
×
840
40 × 950 × 950
24
5
26,600/26,200
6,700/6,600
7.9
27,000
35,700/35,300
9,000/8,900
11.2
38,100
6,800 9,600
3.01 /3.01 (V1), 2.99/2.99 (Y1) 3.93 /3.93 (V1), 3.88/3.88 (Y1)
44,500/43,600
11,200/11,000
14.2
48,400
12,200
4.89/4.89
4.68
2.84 (V1), 2.82 (Y1) 3.64 (V1), 3.60 (Y1)
----------
White
19 28
988 670
35/30
230
×
840
×
840
40 × 950 × 950
24
5
39/34
288
×
840
×
840
40 × 950 × 950
28
5
33
1,164
42/36
288
×
840
×
840
40 × 950 × 950
28
12 to 25
15 to 27
5
49,400/48,400
12,500/12,200
16.3
56,000
14,000
4.95/4.95
4.84
35
1,235
44/37
288
×
840
×
840
40 × 950 × 950
28
5
Ivory white
Hermetically sealed rotary type
1.3
1.12
(Charged for 10 m)
1.7
2.2
2.24
Hermetically sealed scroll type
3.00
3.75
4.50
1.55
1.75
2.8
3.7
3.7
4.1
(Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)
Piping connections
Sound level (Cooling/Heating) 3
Dimensions (H
×
W
×
D)
Machine weight
Certified operation range
Cooling
Heating
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation dB(A) mm kg
°
CDB
°
CWB mm mm mm mm m m
540
47/48
×
750
41
×
270
49/51
685
×
800
×
300
51
19.4 to 46
-10 to 15.5
685
54/54
×
880
75
×
350 770
48/49
×
900
×
320
73 (V1), 72 (Y1)
49/52
1,170
×
900
×
320
89 (V1), 86 (Y1)
1,170
-5 to 46
49/52
×
900
101
×
320
-10 to 15
1,345
54/56
×
900
112
×
320 o/6.4
o/12.7
o/18.0 (Hole)
20 o/6.4
o/15.9
o/18.0 (Hole)
30 o/6.4
o/15.9
o/18.0 (Hole) o/9.5
o/15.9
o/26.0 (Hole) o/9.5
o/19.1
I.Do/25
×
O.Do/32 I.Do/25
×
O.Do/32 I.Do/25
×
O.Do/32 I.Do/25
×
O.Do/32 I.Do/25
×
O.Do/32 o/9.5
o/9.5
o/19.1
o/19.1
I.Do/25
×
O.Do/32 I.Do/25
×
O.Do/32 o/26.0 (Hole) o/26.0 (Hole)
50 (equivalent length 70 m) o/26.0 (Hole)
15 30
Both liquid and gas piping
CEILING SUSPENDED TYPE unit unit
Model
Name
Power supply
Cooling capacity
Heating capacity
Indoor
Outdoor
1a/1b
2
Power consumption
Cooling 1a/1b
Heating 2
Colour
Airflow rate (H)
Indoor unit
Outdoor unit
Sound level (H/L)
Dimensions (H
Machine weight
Certified operation range
Colour
X W
3
X D)
Cooling
Heating
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level (Cooling/Heating) 3
Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation m kW
Btu/h kcal/h kW
Btu/h kcal/h kW kW
3 /min cfm dB(A) mm kg
°
CWB
°
CDB kW kg dB(A) mm kg
°
CDB
°
CWB mm mm mm mm m m
35
FHY35BVE
50
FHY50BVE
60
FHY60BVE
71
FHY71BVE
100
FHY100BVE
125
FHY125BVE
RY50GAV1A RY60GAV1A
RY71LUV1 RY100LUV1
RY35FV1A
RY71LUY1 RY100LUY1
RY125LUY1
VE: 1 Phase 220–240/220 V, 50/60 Hz V1: 1 Phase 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
3.5/3.5
12,100/11,900
3,040/3,000
4.1
14,000
5.0/4.85
16,900/16,600
4,260/4,200
5.5
18,800
6.3/6.15
21,400/21,000
5,390/5,300
7.1
24,200
7.8/7.7
26,600/26,200
6,700/6,600
7.9
27,000
10.5/10.4
35,700/35,300
9,000/8,900
11.2
38,100
13.0/12.8
44,500/43,600
11,200/11,000
14.2
48,400
3,520
1.58/1.57
1.37
13
458
37/32
195 X 960 X 680
23
4,750
2.17/2.16
1.96
13
458
38/33
195 X 960 X 680
24
14 to 23
15 to 28
6,100
3.14/3.12
2.94
16
564
38/33
195 X 1,160 X 680
26
6,800
3.04/3.04 (V1), 3.02/3.02 (Y1)
9,600
3.82/3.82 (V1), 3.77/3.77 (Y1)
3.69 (V1), 3.64 (Y1) 2.98 (V1), 2.95 (Y1)
White
17
600
24
847
195 X
39/35
1,160
27
X 680 195 X
42/37
1,400
32
X
12 to 25
15 to 27
680
12,200
4.85/4.85
4.77
30
1,059
44/39
195 X 1,590 X 680
35
Ivory white
1.3
Hermetically sealed rotary type
1.7
2.2
2.24
Hermetically sealed scroll type
3.00
3.75
1.12
1.55
1.75
2.8
3.7
3.7
(Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)
47/48
540 X 750 X 270
41 o/6.4
o/12.7
I.D o/20 X O.D o/26 o/18.0 (Hole)
20
49/51
685 X 800 X 300
51
19.4 to 46
-10 to 15.5
54/54
685 X 880 X 350
75
48/49
770 X 900 X 320
73 (V1), 72 (Y1)
49/52
1,170 X 900 X 320
89 (V1), 86 (Y1)
-5 to 46
-10 to 15
49/52
1,170 X 900 X 320
101 o/6.4
o/15.9
I.D o/20 X O.D o/26 o/18.0 (Hole)
30
15 o/6.4
o/15.9
I.D o/20 X O.D o/26 o/18.0 (Hole) o/9.5
o/15.9
I.D o/20 X O.D o/26 o/9.5
o/19.1
I.D o/20 X O.D o/26 o/9.5
o/19.1
I.D o/20 X O.D o/26 o/26.0 (Hole) o/26.0 (Hole)
50 (equivalent length 70 m) o/26.0 (Hole)
30
Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions:
1a
1b
Indoor temp., 27
°
CDB, 19.5
°
Indoor temp., 27
2
Rated heating capacities are based on the following conditions:
Indoor temp., 20
°
°
CDB, 19.0
°
CWB; outdoor temp. 35
CWB; outdoor temp. 35
CDB; outdoor temp., 7
°
°
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
CDB, 6
°
CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
3
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
CEILING SUSPENDED CASSETTE TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Heating capacity 2
Indoor unit
Outdoor unit
Power consumption
Indoor unit
Cooling 1a/1b
Heating 2
Colour
Airflow rate (H)
Outdoor unit
Sound level (H/L) 3
Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level (Cooling/Heating) 3
Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation kW kg dB(A) mm kg
°
CDB
°
CWB mm mm mm mm m m kW
Btu/h kcal/h kW
Btu/h kcal/h kW kW m 3 /min cfm dB(A) mm kg
°
CWB
°
CDB
71
FUY71FJV1
RY71LUV1
RY71LUY1
7.8/7.7
26,600/26,200
6,700/6,600
7.9
27,000
6,800
100
FUY100FJV1
RY100LUV1
RY100LUY1
V1: 1 Phase 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
10.5/10.4
35,700/35,300
9,000/8,900
11.2
38,100
9,600
3.02/3.02 (V1), 3.00/3.00 (Y1)
2.87 (V1), 2.84 (Y1)
19
670
40/35
165 X 895 X 895
25
3.99/3.99 (V1), 3.94/3.94 (Y1)
3.66 (V1), 3.62 (Y1)
White
29
1,023
43/38
230 X 895 X 895
31
12 to 25
15 to 27
FUY125FJV1
RY125LUY1
13.0/12.8
44,500/43,600
11,200/11,000
14.2
48,400
12,200
4.90/4.90
4.61
230
125
32
1,129
44/39
X 895
31
X 895
2.24
2.8 (Charged for 30 m)
48/49
770 X 900 X 320
73 (V1), 72 (Y1) o/9.5
o/15.9
o/26.0 (Hole)
Ivory white
Hermetically sealed scroll type
3.00
3.7 (Charged for 30 m)
49/52
1,170 X 900 X 320
89 (V1), 86 (Y1)
-5 to 46
-10 to 15 o/9.5
o/19.1
I.D o/20 X O.D o/26 o/26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
3.75
3.7 (Charged for 30 m)
49/52
1,170 X 900 X 320
101 o/9.5
o/19.1
o/26.0 (Hole)
CEILING MOUNTED CASSETTE CORNER TYPE
Indoor unit
35
FHYK35FJV1
Model
Name
Power supply
Cooling capacity 1a/1b
Heating capacity 2
Outdoor unit
Power consumption
Indoor unit
Colour
Cooling 1a/1b
Heating 2
Airflow rate (H)
Unit
Decoration panel
Outdoor unit
Sound level (H/L) 3
Dimensions
(H X W X D)
Unit
Decoration panel
Machine weight
Certified operation range
Unit
Decoration panel
Cooling
Heating
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level (Cooling/Heating) 3
Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation mm mm mm mm m m kW kg dB(A) mm
° kg
°
CDB
CWB kW
Btu/h kcal/h kW
Btu/h kcal/h kW kW m 3 /min cfm dB(A) mm mm kg kg
°
°
CWB
CDB
RY35FV1A
3.5/3.5
12,100/11,900
3,040/3,000
4.1
14,000
3,520
1.47/1.46
1,25
12
423
39/33
215 X 1,110 X 710
70 X 1,240 X 800
30
8.5
1.3
1.12 (Charged for 10 m)
47/48
540
×
750
×
270
41 o/6.4
o/12.7
I.D o/25 × O.D o/32 o/18.0 (Hole)
20
45
FHYK45FJV1
RY50GAV1A
60
FHYK60FJV1
RY60GAV1A
71
FHYK71FJV1
RY71LUV1
RY71LUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
5.0/4.85
6.3/6.15
16,900/16,600
4,260/4,200
5.5
18,800
4,740
1.95/1.94
1.72
21,400/21,000
5,390/5,300
7.1
24,000
6,080
2.87/2.85
2.65
7.8/7.7
26,600/26,200
6,700/6,600
7.9
27,000
6,800
3.01/3.01 (V1), 2.99/2.99 (Y1)
2.91 (V1), 2.88 (Y1)
----------
White
12
423
39/34
215 X 1,110 X 710
70 X 1,240 X 800
31
8.5
14 to 23
15 to 28
Ivory white
Hermetically sealed rotary type
1.7
1.55 (Charged for 10 m)
49/51
685
×
800
×
300
51
19.4 to 46
-10 to 15.5
17
600
41/36
215 X 1,310 X 710
70 X 1,440 X 800
33
9.5
2.2
1.75 (Charged for 5 m)
54/54
685
×
880
×
350
75
17
600
41/36
215 X 1,310 X 710
70 X 1,440 X 800
33
9.5
12 to 25
15 to 27
Hermetically sealed scroll type
2.24
2.8 (Charged for 30 m)
48/49
770
×
900
×
320
73 (V1), 72 (Y1)
-5 to 46
-10 to 15 o/6.4
o/15.9
I.D o/25 × O.D o/32 o/18.0 (Hole)
15
30 o/6.4
o/15.9
I.D o/25 × O.D o/32 o/18.0 (Hole) o/9.5
o/15.9
I.D o/25 × O.D o/32 o/26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions:
1a
1b
Indoor temp., 27
°
CDB, 19.5
°
Indoor temp., 27
2
Rated heating capacities are based on the following conditions:
Indoor temp., 20
°
°
CDB, 19.0
°
CWB; outdoor temp. 35
CWB; outdoor temp. 35
CDB; outdoor temp., 7
°
°
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY125LU is 7.5 m.)
CDB, 6
°
CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY125LU is 7.5 m.)
3
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
50
CEILING MOUNTED BUILT-IN TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Heating capacity 2
Indoor unit
Outdoor unit
Power consumption
Indoor unit
Cooling 1a/1b
Heating 2
Colour Unit
Airflow rate (H)
Decoration panel
Outdoor unit
Sound level (H/L) 3
Dimensions
(H X W X D)
Machine weight
Unit
Decoration panel
Unit
Certified operation range
Decoration panel
Cooling
Heating
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level (Cooling/Heating) 3
Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation kW
Btu/h kcal/h kW
Btu/h kcal/h kW kW m 3 /min cfm dB(A) mm mm kg kg
°
CWB
°
CDB kW kg dB(A) mm kg
°
°
CDB
CWB mm mm mm mm m m
35
FHYB35FV1
RY35FV1A
3.5/3.5
12,100/11,900
3,040/3,000
4.1
14,000
3,520
1.53/1.52
1.34
11.5
405
38/32
300 X 700 X 800
55 X 880 X 500
30
3.5
45
FHYB45FV1
RY50GAV1A
60
FHYB60FV1
RY60GAV1A
71
FHYB71FV1
RY71LUV1
RY71LUY1
100
FHYB100FV1
RY100LUV1
RY100LUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
5.0/4.85
6.3/6.15
7.8/7.7
10.5/10.4
16,900/16,600
4,260/4,200
5.5
18,800
21,400/21,000
5,390/5,300
7.1
24,200
26,600/26,200
6,700/6,600
7.9
27,000
35,700/35,300
9,000/8,900
11.2
38,100
4,750
1.97/1.96
1.92
300
55 X
14
494
39/34
X 700
880
31
3.5
X
X
800
500
14 to 23
15 to 28
6,100
2.91/2.89
2.71
6,800
3.07/3.07 (V1), 3.05/3.05 (Y1)
9,600
3.92/3.92 (V1), 3.87/3.87 (Y1)
17
600
41/35
300 X 1,000 X 800
55 X 1,100 X 500
41
4.5
3.06 (V1), 3.03 (Y1) 3.75 (V1), 3.70 (Y1)
----------
White
300
55
X
X
19
670
41/35
1,000
1,100
41
4.5
X
X
800
500
27
953
41/35
300 X 1,400 X 800
55 X 1,500 X 500
51
6.5
12 to 25
15 to 27
125
FHYB125FV1
RY125LUY1
13.0/12.8
44,500/43,600
11,200/11,000
14.2
48,400
12,200
4.67/4.67
4.63
35
1,235
44/38
300 X 1,400 X 800
55 X 1,500 X 500
52
6.5
Ivory white
1.3
Hermetically sealed rotary type
1.7
2.2
2.24
Hermetically sealed scroll type
3.00
3.75
1.12
1.55
1.75
2.8
3.7
3.7
(Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)
47/48
540 X 750 X 270
41 o/6.4
o/12.7
I.D o/25 X O.D o/32 o/18.0 (Hole)
20
49/51
685 X 800 X 300
51
19.4 to 46
-10 to 15.5
54/54
685 X 880 X 350
75 o/6.4
o/15.9
I.D o/25 X O.D o/32 o/18.0 (Hole)
30 o/6.4
o/15.9
I.D o/25 X O.D o/32 o/18.0 (Hole)
15
48/49
770 X 900 X 320
73 (V1), 72 (Y1)
49/52
1,170 X 900 X 320
89 (V1), 86 (Y1)
-5 to 46
-10 to 15
49/52
1,170 X 900 X 320
101 o/9.5
o/15.9
I.D o/25 X O.D o/32 o/9.5
o/19.1
I.D o/25 X O.D o/32 o/9.5
o/19.1
I.D o/25 X O.D o/32 o/26.0 (Hole) o/26.0 (Hole)
50 (equivalent length 70 m) o/26.0 (Hole)
30
Both liquid and gas piping
WALL MOUNTED TYPE
Model
Name
Power Supply
Cooling capacity 1a/1b
Heating capacity 2
Indoor unit
Outdoor unit
Power consumption
Indoor unit
Cooling 1a/1b
Heating 2
Colour
Airflow rate (H)
Outdoor unit
Sound level (H/L) 3
Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level (Cooling/Heating) 3
Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation kW kg dB(A) mm kg
°
CDB
°
CWB mm mm mm mm m m kW
Btu/h kcal/h kW
Btu/h kcal/h kW kW m 3 /min cfm dB(A) mm kg
°
°
CWB
CDB
71
FAY71LVE
100
FAY100FAVE
RY71LUV1 RY100LUV1
RY71LUY1 RY100LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
7.8/7.7
26,600/26,200
6,700/6,600
7.9
27,000
6,800
2.92/2.92 (V1), 2.90/2.90 (Y1)
2.85 (V1), 2.82 (Y1)
10.5/10.4
35,700/35,300
9,000/8,900
11.2
38,100
9,600
3.82/ 3.82 (V1), 3.77/ 3.77 (Y1)
3.66 (V1), 3.61 (Y1)
White
19
670
43/37
290 X 1,050 X 230
13
23
811
45/41
360 X 1,570 X 200
26
12 to 25
15 to 27
Ivory white
Hermetically sealed scroll type
2.24
2.8 (Charged for 30 m)
48/49
770 X 900 X 320
73 (V1), 72 (Y1)
3.00
3.7 (Charged for 30 m)
49/52
1,170 X 900 X 320
89 (V1), 86 (Y1)
-5 to 46
-10 to 15 o/9.5
o/15.9
I.D o/13 X O.D o/18 o/26.0 (Hole) o/9.5
o/19.1
I.D o/20 X O.D o/26 o/26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
51
Note :
1
Rated cooling capacities are based on the following conditions:
(FHYB)
1b
(FAY)
1a
1b
1a
Suction temp., 27
°
Indoor temp., 27
°
CDB, 19.5
°
CWB; outdoor temp. 35
CDB, 19.0
°
CWB; outdoor temp. 35
°
2
Rated heating capacities are based on the following conditions:
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
Suction temp., 27
°
CDB, 19.0
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY125LU is 7.5 m.)
Indoor temp., 27
°
CDB, 19.5
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
(FHYB) Suction temp., 20
°
CDB; outdoor temp., 7
°
CDB, 6
°
CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY125LU is 7.5 m.)
(FAY) Indoor temp., 20
°
CDB; outdoor temp., 7
°
CDB, 6
°
CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
3
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
FLOOR STANDING TYPE
Model
Name
Indoor unit
Outdoor unit
Cooling capacity
Heating capacity
1a/1b
2
Power consumption
Indoor unit
Cooling 1a/1b
Heating 2
Colour
Airflow rate (H)
Outdoor unit
Sound level (H/L) 3
Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level (Cooling/Heating) 3
Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation kW
Btu/h kcal/h kW
Btu/h kcal/h kW kW m 3 /min cfm dB(A) mm kg
°
CWB
°
CDB kW kg dB(A) mm kg
°
CDB
°
CWB mm mm mm mm m m
71
FVY71LAVE
100
FVY100LAVE
125
FVY125LAVE
RY71LUV1 RY100LUV1
RY71LUY1 RY100LUY1
RY125LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
7.8/7.7
26,600/26,200
6,700/6,600
7.9
27,000
6,800
3.12/3.12 (V1), 3.10/3.10 (Y1)
3.00 (V1), 2.97 (Y1)
10.5/10.4
35,700/35,300
9,000/8,900
11.2
38,100
9,600
3.95/3.95 (V1), 3.90/3.90 (Y1)
13.0/12.8
44,500/43,600
11,200/11,000
14.2
48,400
12,200
4.99/4.99
4.73
18
635
41/35
1,850 X 600 X 270
39
3.75 (V1), 3.70 (Y1)
White
28
988
46/40
1,850 X 600 X 350
46
12 to 25
15 to 27
32
1,129
49/43
1,850 X 600 X 350
47
770 X
2.24
2.8 (Charged for 30 m)
48/49
900 o/9.5
I.D o/20 X
X o/15.9
320
73 (V1), 72 (Y1)
O.D o/26 o/26.0 (Hole)
Ivory white
Hermetically sealed scroll type
3.00
3.7 (Charged for 30 m)
49/52
1,170 X 900 X 320
89 (V1), 86 (Y1)
-5 to 46
-10 to 15 o/9.5
o/19.1
I.D o/20 X O.D o/26 o/26.0 (Hole)
50 (equivalent length 70 m)
3.75
3.7 (Charged for 30 m)
1,170
49/52
X
I.D o/20
900
101 o/9.5
o/19.1
X
X 320
O.D o/26 o/26.0 (Hole)
30
Both liquid and gas piping
DUCT CONNECTION LOW STATIC PRESSURE TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Heating capacity 2
Power consumption
Indoor unit
Cooling 1a/1b
Heating 2
Colour
Airflow rate (H)
Outdoor unit
Indoor unit
Outdoor unit
Fan External static pressure
Driving system
Sound level (H/L) 3
Dimensions(H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Colour
Compressor Type
Motor output
Refrigerant charge (R-22) kW
Btu/h kcal/h kW
Btu/h kcal/h kW kW m 3 /min cfm
Pa(mmH
2
O) dB(A) mm kg
°
CWB
°
CDB kW kg
35
FDYB35KAVE
50
FDYB50KAVE
60
FDYB60KAVE
71
FDYB71KAVE
RY71LUV1
RY35FV1A RY50GAV1A RY60GAV1A
RY71LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
3.79/3.75
12,900/12,800
5.27/5.20
18,000/17,800
6.24/6.15
21,300/21,000
7.8/7.7
26,600/26,200
3,260/3,230
4.22
14,400
3,630
1.51/1.50
1.33
4,530/4,470
5.80
19,800
4,990
2.01/2.00
1.78
5,370/5,290
7.0
23,900
6,020
2.38/2.36
2.29
6,700/6,600
7.9
27,000
6,800
3.08/3.08
(V1), 3.06/3.06
(Y1)
2.91
(V1), 2.88
(Y1)
----------
13
460
18
635
20 (2)
Direct drive (2 speed)
22
41/ 38
260 X 900 X 580
43/ 40
260 X 1,300 X 580
31 23
14 to 23
15 to 28
12 to 25
15 to 27
1.3
1.12
(Charged for 10 m)
Ivory white
Hermetically sealed rotary type
1.7
1.55
(Charged for 10 m)
2.2
1.75
(Charged for 5 m)
Hermetically sealed scroll type
2.24
2.8
(Charged for 30 m)
Sound level (Cooling/Heating) 3
Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation dB(A) mm kg
°
CDB
°
CWB mm mm mm mm m m
47/48
540 X 750 X 270
41 o/6.4
o/12.7
o/18.0 (Hole)
20
49/51
685 X 800 X 300
51
19.4 to 46
-10 to 15.5
o/6.4
o/15.9
o/18.0 (Hole)
15
3/4B
30
54/54
685 X 880 X 350
75
Both liquid and gas piping o/6.4
o/15.9
o/18.0 (Hole)
48/49
770 X 900 X 320
73 (V1), 72 (Y1)
-5 to 46
-10 to 15 o/9.5
o/15.9
o/26.0 (Hole)
50 (equivalent length 70 m)
30
Note :
1
Rated cooling capacities are based on the following conditions:
(FVY)
1a
Indoor temp., 27
°
CDB, 19.5
°
1b
Indoor temp., 27
°
(FDYB) 1a
1b
CDB, 19.0
°
Suction temp., 27
°
CWB; outdoor temp. 35
°
CWB; outdoor temp. 35
CDB, 19.5
°
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
CWB; outdoor temp. 35
Suction temp., 27
°
CDB, 19.0
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
2
Rated heating capacities are based on the following conditions:
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
(FVY) Indoor temp., 20
°
CDB; outdoor temp., 7
°
CDB, 6
°
CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
(FDYB) Suction temp., 20
°
CDB; outdoor temp., 7
°
CDB, 6
°
CWB. Equiv. refrigeration piping, 5 m (horizontal).
3
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
52
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Heating capacity 2
Indoor unit
Outdoor unit
Power consumption
Indoor unit
Cooling 1a/1b
Heating 2
Colour
Fan Airflow rate (H)
Outdoor unit
External static pressure
Sound level (H) 3
Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level (Cooling/Heating) 3
Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Piping connections
Liquid (Flare)
Gas (Flare)
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation kW kg dB(A) mm kg
°
CDB
°
CWB mm mm mm mm m m kW
Btu/h kcal/h kW
Btu/h kcal/h kW kW m 3 /min cfm
Pa(mmH
2
O) dB(A) mm kg
°
CWB
°
CDB
71
FDYM03FAV1
RY71LUV1
RY71LUY1
100
FDYM04FAV1
RY100LUV1
RY100LUY1
125
FDYM05FAV1
RY125LUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
10.5/10.4
13.0/12.8
7.8/7.7
26,600/26,200
6,700/6,600
7.9
27,000
35,700/35,300
9,000/8,900
11.2
38,100
6,800 9,600
3.19/3.19 (V1), 3.17/3.17 (Y1) 4.00/4.00 (V1), 3.95/3.95 (Y1)
2.95 (V1), 2.92 (Y1) 3.91 (V1), 3.86 (Y1)
----------
20
706
98 (10)
39
295 X 1,100 X 680
42
26
917
98 (10)
39
295 X 1,500 X 680
56
44,500/43,600
11,200/11,000
295 X
14.2
48,400
12,200
4.99/4.99
4.75
35
1,235
98 (10)
44
1,500
57
X 680
12 to 25
15 to 27
2.24
2.8 (Charged for 30 m)
48/49
770 X 900 X 320
73 (V1), 72 (Y1) o/9.5
o/15.9
I.Do/25 X O.Do/32 o/26.0 (Hole)
Ivory white
Hermetically sealed scroll type
3.00
3.7 (Charged for 30 m)
3.75
3.7 (Charged for 30 m)
49/52
1,170 X 900 X 320
89 (V1), 86 (Y1)
49/52
1,170 X 900 X 320
101
-5 to 46
-10 to 15 o/9.5
o/19.1
o/9.5
o/19.1
I.Do/25 X O.Do/32 I.Do/25 X O.Do/32 o/26.0 (Hole) o/26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
140
FDYM06FAV1
RY140LUY1
14.5/14.2
49,400/48,400
12,500/12,200
16.3
56,000
14,000
5.10/5.10
4.96
37
1,306
98 (10)
46
295 X 1,500 X 680
57
4.50
4.1 (Charged for 30 m)
54/56
1,345 X 900 X 320
112 o/9.5
o/19.1
oI.Do/25 X O.Do/32 o/26.0 (Hole)
53
DUCT CONNECTION HIGH STATIC PRESSURE TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Heating capacity 2
Power consumption
Indoor unit
Outdoor unit
Colour
Airflow rate (H)
Indoor unit
Outdoor unit
Cooling 1a/1b
Heating 2
Fan External static pressure
Driving system
Sound level (H) 3
Dimensions(H X W X D) 5
Machine weight
Certified operation range
Cooling
Heating
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level (Cooling/Heating) 3
Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Piping connections
Liquid (Flare)
Gas
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation kW
Btu/h kcal/h kW
Btu/h kcal/h kW kW m 3 /min cfm
Pa(mmH
2
O) dB(A) mm kg
°
CWB
°
CDB kW kg dB(A) mm kg
°
°
CDB
CWB mm mm mm mm m m
140
FDY06K A Y1
RY140LUY1
14.5/14.2
49,500/48,500
12,500/12,220
15.3
52,200
13,200
5.14/5.14
4.54
52
1,835
108 (11)
450 X 1,130 X 850
80
12 to 25
4.5
4.1
(Charged for 30 m)
54/56
1,345 X 900 X 320
112
-5 to 46
-10 to 15
/ 9.5
/ 19.1 (Flare)
/ 26.0 (Hole)
51
200
FDY08K A Y1
250
FDY10K A Y1
400
FDY15K A Y1
RY200KUY1 RY250KUY1 RY200KUY1
Y1: 3 phase, 380–415 V (4 wires), 50 Hz
X 2
22.5/22.2
76,800/75,700
27.6/27.1
94,200/92,500
44.0/43.5
150,000/148,000
19,300/19,100
23.2
79,200
20,000
7.2/7.1
6.1
68
2,400
23,700/23,300
29.5
100,700
25,400
9.3/9.2
8.8
---------
83
2,929
37,800/37,400
44.8
153,000
38,500
14.4/14.2
12.2
136
4,800
500
FDY20K A Y1
RY250KUY1 X 2
53.9/53.0
184,000/181,000
46,400/45,600
56.8
194,000
48,800
18.5/18.3
17.6
166
5,859
500 X 1,130 X 850
94
118 (12)
Belt drive
53
500 X 1,330 X 850
105
14 to 25
58
625 X 1,620 X 850
161
147 (15)
60
625 X 1,980 X 850
187
15 to 27
Ivory white
5.5
4.0
(Charged for 5 m)
Hermetically sealed scroll type
9.0
5.5
(Charged for 5 m)
5.5
X 2 9.0
X 2
4.0
5.5
(Charged for 5 m) X 2 (Charged for 5 m) X 2
60/62
1,220 X 1,280 X 690
180
0 to 50
-10 to 15
61/63
1,440 X 1,280 X 690
206
/ 12.7
/ 25.4 (Flange)
3/4B
/ 15.9
/ 28.6 (Flange)
(1,220
---------
50 (equivalent length 70 m)
30
Both liquid and gas piping
X
60/62
1,280
180 X
4
X
2
690 ) X 2 (1,440
0 to 50
-10 to 15
/ 12.7
X 2
/ 25.4
X 2 (Flange)
1B
X
61/63
1,280
206 X
4
X
2
/ 15.9
X 2
690 )
/ 28.6
X 2 (Flange)
X 2
Note :
Models RY200KU and RY250KU are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
1b
Suction temp., 27
°
CDB, 19.5
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
Suction temp., 27
°
CDB, 19.0
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
2
Rated heating capacities are based on the following conditions:
Suction temp., 20
°
CDB; outdoor temp., 7
°
CDB, 6
°
CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
3
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
4 Specification for outdoor unit is for a single unit only.
5
Without control box.
Simultaneous operation system
TWIN & TRIPLE & DOUBLE TWIN MULTI
CEILING MOUNTED CASSETTE TYPE
Model
Name
Indoor unit
Outdoor unit
Power supply
Cooling capacity
Heating capacity
1a/1b
2 kW
Btu/h kcal/h kW
Btu/h kcal/h
Power consumption
Cooling 1a/1b
Heating 2
Colour Unit
Indoor unit 3 kW kW
Decoration panel
Airflow rate (H) m 3 /min cfm
Sound level (H/L)
Dimensions
(H X W X D)
Unit
4
Decoration panel dB(A) mm
Machine weight
Certified operation range
Unit
Decoration panel
Cooling
Heating mm kg kg
°
CWB
°
CDB
Outdoor unit
Colour
Compressor Type
Motor output kW
Refrigerant charge (R-22) kg
Piping
Sound level (Cooling/Heating) dB(A)
Dimensions (H X
Machine weight
W X D) mm
Certified operation range
Cooling
Heating kg
°
CDB
°
CWB connections
Liquid (Flare)
Gas mm mm
Drain Indoor unit
Outdoor unit mm mm
Max. interunit piping length
Max. installation level difference
Heat insulation m m
71
FHYC35KVE X 2
RY71LUV1
RY71LUY1
100
FHYC50KVE X 2
RY100LUV1
RY100LUY1
FHYC60KVE X
RY125LUY1
2
-------------
White
140
FHYC71KVE X
RY140LUY1
2
200
FHYC100KVE X
RY200KUY1
2
250
FHYC125KVE X
RY250KUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
7.8/7.7
10.5/10.4
13.0/12.8
14.5/14.2
22.5/22.2
27.1/26.6
26,600/26,200 35,700/35,300 44,500/43,600 49,400/48,400 76,800/75,800 92,500/90,800
6,700/6,600
7.9
27,000
6,800
3.11/3.11 (V1), 3.09/3.09 (Y1)
2.94 (V1), 2.92 (Y1)
9,000/8,900
11.2
38,100
9,600
3.98/3.98 (V1), 3.93/3.93 (Y1)
3.69 (V1), 3.65 (Y1)
11,200/11,000
14.2
48,400
12,200
4.94/4.94
4.73
12,500/12,200
16.3
56,000
14,000
4.95/4.95
4.84
19,400/19,100
22.7
77,500
19,500
7.7/7.6
6.5
23,300/22,900
28.4
97,000
24,400
9.7/9.7
9.2
2
14
494
33/29
230 X 840 X 840
40 X 950 X 950
24
5
230
40
X
X
15
529
33/29
840
950
24
5
X
X
840
950
230
40 X
19
670
35/30
X 840
950
24
5
X
X
840
950
230
40
35/30
X
X
19
670
840
950
24
5
X
X
840
950
288
40
X
X
28
988
39/34
840
950
28
5
X
X
840
950
288
40 X
33
1,164
42/36
X 840
950
28
5
X
X
840
950
12 to 25
15 to 27
14 to 25
15 to 27
Ivory white
Hermetically sealed scroll type
2.24
3.00
3.75
4.50
5.5
9.0
2.8
3.7
3.7
4.1
4.0
5.5
(Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 5 m) (Charged for 5 m)
48/49
770 X 900 X 320
73 (V1), 72 (Y1)
/ 9.5
/ 15.9 (Flare)
I.D o/25 X O.D o/32
/ 26.0 (Hole)
49/52
1,170 X 900 X 320
89 (V1), 86 (Y1)
-5 to 46
-10 to 15
49/52
1,170 X 900 X 320
101 o / 9.5
/ 19.1 (Flare)
I.D o/25 X O.D o/32
/ 26.0 (Hole)
/ 9.5
/ 19.1 (Flare)
I.D o/25 X O.D o/32
54/56
1,345 X 900 X 320
112
/ 9.5
/ 19.1 (Flare)
I.D o/25 X O.D o/32
/ 26.0 (Hole) / 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
60/62
1,220 X 1,280 X 690
180
61/63
1,440 X 1,280 X 690
206
0 to 50
-10 to 15
/ 12.7
o / 25.4 (Flange)
I.D o/25 X O.D o/32
---------
/ 15.9
/ 28.6 (Flange)
I.D o/25 X O.D o/32
---------
Model
Name
Indoor unit
Outdoor unit
Power supply
Cooling capacity
Heating capacity
1a/1b
2
Power consumption
Cooling 1a/1b
Heating 2
Indoor unit 3
Colour Unit
Decoration panel
Airflow rate (H) m 3 /min
Sound level (H/L) 4 cfm dB(A)
Dimensions
(H X W X D)
Machine weight
Certified operation range
Unit
Decoration panel
Unit
Decoration panel
Cooling
Heating mm mm kg kg
°
CWB
°
CDB
Outdoor unit
Colour
Compressor Type
Motor output kW
Refrigerant charge (R-22) kg
Piping
Sound level (Cooling/Heating) dB(A)
Dimensions (H X W X D) mm
Machine weight
Certified operation range connections
Liquid (Flare)
Gas
Cooling
Heating kg
°
CDB
°
CWB mm mm
Drain Indoor unit
Outdoor unit mm mm
Max. interunit piping length
Max. installation level difference
Heat insulation m m kW
Btu/h kcal/h kW
Btu/h kcal/h kW kW
140
FHYC50KVE X 3
RY140LUY1
14.5/14.2
49,400/48,400
12,500/12,200
16.3
56,000
14,000
4.95/4.95
4.84
15
529
33/29
230 X 840 X 840
40 X 950 X 950
24
5
12 to 25
15 to 27
4.50
4.1 (Charged for 30 m)
54/56
1,345 X 900 X 320
112
-5 to 46
-10 to 15 o / 9.5
/ 19.1 (Flare)
I.D o/25 X O.D o/32
/ 26.0 (Hole)
200
FHYC71KVE X 3
RY200KUY1
200
FHYC50KVE X
RY200KUY1
4
VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V, 50 Hz
22.5/22.2
22.5/22.2
76,800/75,800
19,400/19,100
22.7
77,500
19,500
7.7/7.6
6.5
76,800/75,800
19,400/19,100
22.7
77,500
19,500
7.7/7.6
6.5
-------------
White
19
670
35/30
230 X 840 X 840
40 X 950 X 950
15
529
33/29
230 X 840 X 840
40 X 950 X 950
24
5
14 to 25
15 to 27
Ivory white
Hermetically sealed scroll type
24
5
5.5
4.0 (Charged for 5 m)
60/62
1,220 X 1,280 X 690
180
5.5
4.0 (Charged for 5 m)
60/62
1,220 X 1,280 X 690
180
0 to 50
/ 12.7
o / 25.4 (Flange)
I.D o/25 X O.D o/32
---------
-10 to 15
/ 12.7
/ 25.4 (Flange)
I.D o/25 X O.D o/32
---------
50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
Models RY200KU and RY250KU are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
1b
Indoor temp., 27
°
CDB, 19.5
°
Indoor temp., 27
°
CDB, 19.0
°
CWB; outdoor temp. 35
CWB; outdoor temp. 35
°
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
2
Rated heating capacities are based on the following conditions:
Indoor temp., 20
°
CDB; outdoor temp., 7
°
CDB, 6
°
CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
3
Values shown are for a single unit only.
4 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
250
FHYC60KVE X 4
RY250KUY1
27.1/26.6
92,500/90,800
23,300/22,900
28.4
97,000
24,400
9.7/9.7
9.2
19
670
35/30
230 X 840 X 840
40 X 950 X 950
24
5
9.0
5.5 (Charged for 5 m)
61/63
1,440 X 1,280 X 690
206
/ 15.9
/ 28.6 (Flange)
I.D o/25 X O.D o/32
---------
54
55
Simultaneous operation system
TWIN & TRIPLE & DOUBLE TWIN MULTI
CEILING SUSPENDED TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Heating capacity 2
Power consumption
Indoor unit
3
Cooling 1a/1b
Heating 2
Colour
Airflow rate (H)
Outdoor unit
Indoor unit
Outdoor unit
Sound level (H/L) 4
Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Colour
Compressor Type
Motor output kW
Btu/h kcal/h kW
Btu/h kcal/h kW kW m 3 /min cfm dB(A) mm kg
°
CWB
°
CDB kW
Refrigerant charge (R-22) kg
Piping
Sound level (Cooling/Heating) dB(A)
Dimensions (H X W X D) mm
Machine weight
Certified operation range connections
Cooling
Heating
Liquid (Flare)
Gas kg
°
CDB
°
CWB mm mm
Drain Indoor unit
Outdoor unit mm mm
Max. interunit piping length
Max. installation level difference
Heat insulation m m
71
FHY35BVE
×
2
RY71LUV1
100
FHY50BVE
×
2
RY100LUV1
125
FHY60BVE
×
2
140
FHY71BVE
×
2
200
FHY100BVE
×
2
250
FHY125BVE
×
RY71LUY1 RY100LUY1
RY125LUY1 RY140LUY1 RY200KUY1 RY250KUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
7.8/7.7
10.5/10.4
13.0/12.8
14.5/14.2
22.5/22.2
27.1/26.6
2
26,600/26,200
6,700/6,600
7.9
27,000
6,800
3.14/3.14 (V1)
3.12/3.12 (Y1)
3.08 (V1), 3.05 (Y1)
35,700/35,300
9,000/8,900
11.2
38,100
9,600
3.87/3.87 (V1)
3.82/3.82 (Y1)
3.74 (V1),3.69 (Y1)
44,500/43,600
11,200/11,000
14.2
48,400
12,200
4.91/4.91
4.83
49,400/48,400
12,500/12,200
16.3
56,000
14,000
5.10/5.10
4.99
76,800/75,800
19,400/19,100
22.7
77,500
19,500
7.7/7.6
6.5
92,500/90,800
23,300/22,900
28.4
97,000
24,400
9.7/9.7
9.2
195 X
13
458
37/32
960
23
2.24
2.8
X 680
(Charged for 30 m)
White
13
458
38/33
195 X 960 X 680
24
12 to 25
15 to 27
16
564
38/33
195 X 1,160 X 680
26
3.00
3.7
(Charged for 30 m)
195 X
17
600
39/35
1,160
27
X 680
Ivory white
Hermetically sealed scroll type
3.75
4.50
3.7
(Charged for 30 m)
4.1
(Charged for 30 m)
24
847
42/37
195 X 1,400 X 680
32
5.5
4.0
14 to 25
15 to 27
(Charged for 5 m)
30
1,059
44/39
195 X 1,590 X 680
35
9.0
5.5
(Charged for 5 m)
48/49
770 X 900 X 320
73 (V1), 72 (Y1)
/
/ 9.5
15.9 (Flare)
I.D o/20 X O.D o/26
/ 26.0 (Hole)
1,170
49/52
X 900 X 320
89 (V1), 86 (Y1)
-5 to 46
49/52
1,170 X 900 X 320
101
-10 to 15 o / 9.5
/ 19.1 (Flare)
I.D o/20 X O.D o/26
/ 26.0 (Hole)
/ 9.5
/ 19.1 (Flare)
I.D o/20 X O.D o/26
30
54/56
1,345 X 900 X 320
112
/
/ 9.5
19.1 (Flare)
I.D o/20 X O.D o/26
/ 26.0 (Hole) / 26.0 (Hole)
50 (equivalent length 70 m)
Both liquid and gas piping
60/62
1,220 X 1,280 X 690
180
61/63
1,440 X 1,280 X 690
206
0 to 50
-10 to 15
/ 12.7
o / 25.4 (Flange)
I.D o/20 X O.D o/26
---------
/ 15.9
/ 28.6 (Flange)
I.D o/20 X O.D o/26
---------
Model
Name
Indoor unit
Outdoor unit
Power supply
Cooling capacity 1a/1b
Heating capacity 2 kW
Btu/h kcal/h kW
Power consumption
Indoor unit
3
Cooling 1a/1b
Heating 2
Colour
Airflow rate (H)
Btu/h kcal/h kW kW m 3 /min cfm
Sound level (H/L) 4
Dimensions (H
Machine weight
Certified operation range
X W X D)
Cooling
Heating dB(A) mm kg
°
CWB
°
CDB
Outdoor unit
Colour
Compressor Type
Motor output kW
Refrigerant charge (R-22) kg
Piping
Sound level (Cooling/Heating) 4 dB(A)
Dimensions (H X W X D) mm
Machine weight
Certified operation range connections
Liquid (Flare)
Gas
Cooling
Heating kg
°
CDB
°
CWB mm mm
Drain Indoor unit
Outdoor unit mm mm
Max. interunit piping length
Max. installation level difference
Heat insulation m m
140
FHY50BVE
×
3
RY140LUY1
14.5/14.2
49,400/48,400
12,500/12,200
16.3
56,000
14,000
5.10/5.10
4.99
13
458
38/33
195 X 960 X 680
24
12 to 25
15 to 27
4.50
4.1 (Charged for 30 m)
54/56
1,345 X 900 X 320
112
-5 to 46
-10 to 15 o / 9.5
/ 19.1 (Flare)
I.D o/20 X O.D o/26
/ 26.0 (Hole)
200
FHY71BVE
×
3
RY200KUY1
200
FHY50BVE
×
4
RY200KUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V, 50 Hz
22.5/22.2
76,800/75,800
22.5/22.2
76,800/75,800
19,400/19,100
22.7
77,500
19,500
7.7/7.6
6.5
19,400/19,100
22.7
77,500
19,500
7.7/7.6
6.5
White
17
600
39/35
195 X 1,160 X 680
27
13
458
38/33
195 X 960 X 680
24
5.5
4.0 (Charged for 5 m)
60/62
1,220 X 1,280 X 690
180
14 to 25
15 to 27
Ivory white
Hermetically sealed scroll type
5.5
4.0 (Charged for 5 m)
60/62
1,220 X 1,280 X 690
180
0 to 50
/ 12.7
o / 25.4 (Flange)
I.D o/20 X O.D o/26
---------
-10 to 15
/ 12.7
/ 25.4 (Flange)
I.D o/20 X O.D o/26
---------
50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
Models RY200KU and RY250KU are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
1b
Indoor temp., 27
°
CDB, 19.5
°
Indoor temp., 27
°
CDB, 19.0
°
CWB; outdoor temp. 35
CWB; outdoor temp. 35
°
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
2
Rated heating capacities are based on the following conditions:
Indoor temp., 20
°
CDB; outdoor temp., 7
°
CDB, 6
°
CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
3
Values shown are for a single unit only.
4 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
250
FHY60BVE
×
4
RY250KUY1
27.1/26.6
92,500/90,800
23,300/22,900
28.4
97,000
24,400
9.7/9.7
9.2
16
564
38/33
195 X 1,160 X 680
26
9.0
5.5 (Charged for 5 m)
61/63
1,440 X 1,280 X 690
206 o / 15.9
/ 28.6 (Flange)
I.D o/20 X O.D o/26
---------
DUCT CONNECTION LOW STATIC PRESSURE TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Indoor unit
Outdoor unit
Heating capacity 2
Power consumption
Indoor unit 3
Cooling 1a/1b
Heating 2
Colour
Airflow rate (H) m 3 /min cfm
Fan External static pressure Pa(mmH
2
O)
Sound level (H) 4 dB(A) mm Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
°
° kg
CWB
CDB kW
Btu/h kcal/h kW
Btu/h kcal/h kW kW
Outdoor unit
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level (Cooling/Heating) 4
Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Piping connections
Liquid
Gas
Drain Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation kW kg dB(A) mm kg
°
CDB
°
CWB mm mm mm mm m m
200
FDYB50KAVE × 4
RY200KUY1
76,800/75,800
19,400/19,100
200
FDYB71KAVE × 3
RY200KUY1
250
FDYB60KAVE × 4
RY250KUY1
22.5/22.2
VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V, 50 Hz
22.5/22.2
27.1/26.6
76,800/75,800
19,400/19,100
92,500/90,800
23,300/22,900
22.7
77,500
19,500
7.7/7.6
6.5
22.7
77,500
19,500
7.7/7.6
6.5
–––
28.4
97,000
24,400
9.7/9.7
9.2
13
458
18
635
260 X
41
900
23
X 580
14 to 25
15 to 27
5.5
18
635
20 (2)
43
260 X 1,300 X 580
31
14 to 25
15 to 27
Ivory white
Hermetically sealed scroll type
5.5
260 X
43
1,300
31
9.0
X
14 to 25
15 to 27
580
4.0 (Charged for 5 m)
60/62
1,220 X 1,280 X 690
180
12.7 (Flare)
25.4 (Flange)
4.0 (Charged for 5 m)
60/62
1,220 X 1,280 X 690
180
0 to 50
-10 to 15
12.7 (Flare)
25.4 (Flange)
3/4B
–––
50 (equivalent length 70 m)
30
Both liquid and gas piping
5.5 (Charged for 5 m)
61/63
1,440 X 1,280 X 690
206
15.9 (Flare)
28.6 (Flange)
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
Model
Name
Indoor unit
Outdoor unit
Power supply
Cooling capacity
Heating capacity
1a/1b
2
Power consumption
Cooling 1a/1b
Heating 2
Colour
Indoor unit 3
Fan Airflow rate (H)
External static pressure
Sound level (H) 4
Dimensions (H X W X D)
Machine weight
Certified operation range
Cooling
Heating
Outdoor unit
Colour
Compressor Type
Motor output
Refrigerant charge (R-22) kW kg
Piping connections
Sound level (Cooling/Heating) 4 dB(A)
Dimensions (H X W X D) mm
Machine weight
Certified operation range
Liquid (Flare)
Gas
Drain
Cooling
Heating
Indoor unit kg
°
CDB
°
CWB mm mm mm
Outdoor unit mm
Max. interunit piping length
Max. installation level difference m m
Heat insulation m 3 /min cfm
Pa(mmH
2
O) dB(A) mm kg
°
CWB
°
CDB kW
Btu/h kcal/h kW
Btu/h kcal/h kW kW
200
FDYM04FAV1
×
2
RY200KUY1
22.5/22.2
76,800/75,800
19,400/19,100
22.7
250
FDYM05FAV1
×
2
RY250KUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
27.1/26.6
92,500/90,800
200
FDYM03FAV1
×
3
RY200KUY1
22.5/22.2
76,800/75,800
19,400/19,100
22.7
77,500
19,500
7.7/7.6
6.5
23,300/22,900
28.4
97,000
24,400
9.9/9.9
9.2
----------
77,500
19,500
8.0/7.9
6.8
1,220 X
26
917
98 (10)
39
295 X 1,500 X 680
56
5.5
4.0 (Charged for 5 m)
60/62
1,280
180
X 690
35
1,235
98 (10)
44
295 X 1,500 X 680
57
14 to 25
15 to 27
Ivory white
Hermetically sealed scroll type
9.0
5.5 (Charged for 5 m)
61/63
1,440 X 1,280 X 690
206
0 to 50
-10 to 15
20
706
98 (10)
39
295 X 1,100 X 680
42
5.5
4.0 (Charged for 5 m)
1,220
60/62
X 1,280
180
X 690 o / 12.7
/ 25.4 (Flange)
I.D o/25 X O.D o/32
--------o / 15.9
/ 28.6 (Flange)
I.D o/25 X O.D o/32
---------
50 (equivalent length 70 m)
30
Both liquid and gas piping
/ 12.7
/ 25.4 (Flange)
I.D o/25 X O.D o/32
---------
Note :
Models RY200KU and RY250KU are recommended for commercial facilities.
1 Rated cooling capacities are based on the following conditions:
1a
1b
Suction temp., 27
°
CDB, 19.5
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal).
Suction temp., 27
°
CDB, 19.0
°
CWB; outdoor temp. 35
°
CDB. Equiv. refrigeration piping, 5 m (horizontal)
2
Rated heating capacities are based on the following conditions:
3
Suction temp., 20
°
CDB; outdoor temp., 7
°
CDB, 6
°
CWB. Equiv. refrigeration piping, 5 m (horizontal)
4
Values shown are for a single unit only.
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
56
Indoor unit
CEILING MOUNTED CASSETTE TYPE
Name of option Remark
Kit name
Cooling only
FHC35K/50K/60K
FHYC35K/50K/60K/71K
FHYC100K/125K/140K
Heat pump
FHYC35K/50K/60K/71K FHYC100K/125K/140K
Decoration panel
Sealing member for air discharge outlet
Panel spacer
Fresh air intake kit 1 Chamber type
Without the T-joint pipe and fan
With the T-joint pipe,without fan
Direct installation type
Chamber connection kit 2
High-efficiency filter (Colorimetric method 65%)
(Colorimetric method 90%)
Replacement high-efficiency filter
(Colorimetric method 65%)
(Colorimetric method 90%)
High-efficiency filter chamber
Replacement long-life filter
Ultra long-life filter
Replacement ultra long-life filter
Branch duct chamber
Remote controller
Wired LCD remote controller with weekly schedule timer
Central remote controller 4
Wireless type
Unified ON/OFF controller 4
Wired type 3
Schedule timer 4 i ntelligent Touch Controller 4
Adaptor for wiring 5
Wiring adaptor for electrical appendices 5
Interface adaptor for SkyAir series
Installation box for adaptor PCB
BYC125K-W1
KDBHJ55K160
KDBP55H160WA
KDDP55D160
KDDP55D160K
KDDJ55X160
KKSJ55K160
KAFP556D80
KAFP557D80
KAFP556D160
KAFP557D160
KAFP552H80 KAFP552H160
KAFP553H80 KAFP553H160
KDDFP55D160
KAFJ551K160
KAFP55D160
KAFJ55K160H
KDJ55K80 KDJ55K160
BRC1C61
BRC7C613W
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP1BA57
KRP4AA53
DTA102A52
KRP1B98
BYC125K-W1
KDBHJ55K160
KDBP55H160WA
KDDP55D160
KDDP55D160K
KDDJ55X160
KKSJ55K160
KAFP556D80
KAFP557D80
KAFP556D160
KAFP557D160
KAFP552H80 KAFP552H160
KAFP553H80 KAFP553H160
KDDFP55D160
KAFJ551K160
KAFP55D160
KAFJ55K160H
KDJ55K80 KDJ55K160
BRC1C61
BRC7C612W
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP1BA57
KRP4AA53
DTA102A52
KRP1B98
Note:
1
2
Refer to page 14 for the details.
3
Required for installing high-efficiency or ultra long-life filter.
4
Wiring for wired remote controller to be procured locally.
5
This optional accessory requires DTA102A52.
Installation box for adaptor PCB (KRP1B98) is necessary.
CEILING SUSPENDED TYPE
Name of option Remark
Replacement long-life filter Resin net
Drain-up kit
L-type piping kit (for upward direction)
Remote controller Wired type 1
Wireless type
Wired LCD remote controller with weekly schedule timer
Central remote controller 2
Unified ON/OFF controller 2
Schedule timer 2 i ntelligent Touch Controller 2
Adaptor for wiring
Wiring adaptor for electrical appendices 3
Interface adaptor for SkyAir series
Installation box for adaptor PCB
Note:
1
2
Wiring for wired remote controller to be procured locally.
3
This optional accessory requires DTA102A52.
Installation box for adaptor PCB (KRP1CA93) is necessary.
Kit name
FH(Y)35B
KHFJ5F50
Cooling only
FH(Y)50B FH(Y)60B FHY71B FHY100B
KAFJ501D56
KDU50B50VE
KAFJ501D80
KDU50B71VE
KHFJ5F60 KHFJ5F80
BRC1C61
BRC7EA66
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP1BA54
KRP4AA52
DTA102A52
KRP1CA93
KAFJ501D112
FHY125B
KAFJ501D160
KDU50B125VE
KHFJ5F160
FHY35B
Heat pump
FHY50B FHY60B FHY71B FHY100B
KAFJ501D56
KDU50B50VE
KHFJ5F50
KAFJ501D80
KDU50B71VE
KHFJ5F60 KHFJ5F80
BRC1C61
BRC7E63W
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP1BA54
KRP4AA52
DTA102A52
KRP1CA93
KAFJ501D112
FHY125B
KAFJ501D160
KDU50B125VE
KHFJ5F160
57
CEILING SUSPENDED CASSETTE TYPE
Name of option Remark
Replacement long-life filter
Sealing member for air discharge outlet 1
Decoration panel for air discharge
Vertical flap kit
L-connection piping kit
Remote controller Wired type 2
Wireless type
Wired LCD remote controller with weekly schedule timer
Central remote controller 3
Unified ON/OFF controller 3
Schedule timer 3 i ntelligent Touch Controller 3
Wiring adaptor for electrical appendices 4
Interface adaptor for SkyAir series
Installation box for adaptor PCB
Note:
1
2
Required at time of installation for setting two-way opposing air flow.
3
Wiring for wired remote controller to be procured locally.
4
This optional accessory requires DTA102A52.
Installation box for adaptor PCB (KRP1B97) is necessary.
FUY71FJ
KDBHJ49F80
KDBTJ49F80
KDGJ49F80
KHFJ49F80
Cooling only
FUY100FJ/125FJ
KAFJ495F140
BRC1C61
BRC7C529W
BRC1D61
KDBHJ49F140
KDBTJ49F140
KDGJ49F140
KHFJ49F140
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP4AA53
DTA102A52
KRP1B97
Kit name
FUY71FJ
KDBHJ49F80
KDBTJ49F80
KDGJ49F80
KHFJ49F80
Heat pump
FUY100FJ/125FJ
KAFJ495F140
BRC1C61
BRC7C528W
BRC1D61
KDBHJ49F140
KDBTJ49F140
KDGJ49F140
KHFJ49F140
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP4AA53
DTA102A52
KRP1B97
CEILING MOUNTED CASSETTE CORNER TYPE
Name of option Remark
Decoration panel
Panel spacer
Air discharge blind panel
Replacement long-life filter
Discharge grille
Flexible duct with shutter
Resin net
Remote controller Wired type 1
Wired LCD remote controller with weekly schedule timer
Central remote controller 2
Unified ON/OFF controller 2
Schedule timer 2 i ntelligent Touch Controller 2
Adaptor for wiring (interlock for fresh air intake fan)
Wiring adaptor for electrical appendices
Interface adaptor for SkyAir series
Note: 1 Wiring for wired remote controller to be procured locally.
2 This optional accessory requires DTA102A52.
FHK35F/45F
BYK45FJW1
KPBJ52F56W
KDBJ52F56W
KAFJ521F56
K-HV7AW
KFDJ52F56
Cooling only
BRC1C61
BRC1D61
FHK60F/FHYK71F
BYK71FJW1
KPBJ52F80W
KDBJ52F80W
KAFJ521F80
K-HV9AW
KFDJ52F80
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP1B51
KRP4AA51
DTA102A52
Kit name
Heat pump
FHYK35FJ/45FJ
BYK45FJW1
KPBJ52F56W
KDBJ52F56W
KAFJ521F56
K-HV7AW
KFDJ52F56
BRC1C61
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP1B51
KRP4AA51
DTA102A52
FHYK60FJ/71FJ
BYK71FJW1
KPBJ52F80W
KDBJ52F80W
KAFJ521F80
K-HV9AW
KFDJ52F80
CEILING MOUNTED BUILT-IN TYPE
Name of option Remark
Decoration panel
Service access panel
High-efficiency filter (Colorimetric method 65%)
(Colorimetric method 90%)
Replacement long-life filter
Filter chamber for bottom suction
Filter chamber for rear suction
Canvas duct
Resin net
Discharge grille
Discharge chamber
Branch duct
Flexible duct
/ 150)
/ 200)
/ 150)
/ 200)
/ / 150
/ 150)
Kit name
FHB35F/45F
Cooling only
FHB60F/FHYB71F
BYBS45DJW1 BYBS71DJW1
FHYB100F FHYB125F
BYBS125DJW1
KTBJ25K56W KTBJ25K80W
KAFJ252L56 KAFJ252L80
KTBJ25K160W
KAFJ252L160
KAFJ253L56 KAFJ253L80
KAFJ251K56 KAFJ251K80
KAFJ253L160
KAFJ251K160
KAJ25L56D KAJ25L80D
KAJ25L56B KAJ25L80B
KSA-25K56 KSA-25K80
K-DG4DW
K-DG7DW
K-DGC4D
K-DGC7D
KAJ25L160D
KAJ25L160B
K-DG5DW
K-DG9DW
KSA-25K160
K-DG4DW
K-DG7DW
K-DGC5D
K-DGC9D
K-DGC4D
K-DGC7D
K-DDV20A
K-DG5DW
K-DG9DW
K-DGC5D
K-DGC9D
FHYB35F/45F FHYB60F/71F FHYB100F FHYB125F
BYBS45DJW1 BYBS71DJW1 BYBS125DJW1
KTBJ25K56W KTBJ25K80W
KAFJ252L56 KAFJ252L80
KTBJ25K160W
KAFJ252L160
KAFJ253L56
KAFJ251K56
Heat pump
KAFJ253L80
KAFJ251K80
KAFJ253L160
KAFJ251K160
KAJ25L56D
KAJ25L56B
KAJ25L80D
KAJ25L80B
KAJ25L160D
KAJ25L160B
KSA-25K56
K-DG4DW
K-DG7DW
K-DGC4D
K-DGC7D
KSA-25K80
K-DG5DW
K-DG9DW
K-DGC5D
K-DGC9D
KSA-25K160
K-DG4DW
K-DG7DW
K-DGC4D
K-DGC7D
K-DDV20A
K-DG5DW
K-DG9DW
K-DGC5D
K-DGC9D
K-FDS151D (1 m) K-FDS152D (2 m) K-FDS153D (3 m)
K-FDS154D (4 m) K-FDS155D (5 m) K-FDS156D (6 m)
K-FDS151D (1 m) K-FDS152D (2 m) K-FDS153D (3 m)
K-FDS154D (4 m) K-FDS155D (5 m) K-FDS156D (6 m)
/ 200)
Blind board
Adaptor for discharge
Flange for suction
Remote controller Wired type 1
Wired LCD remote controller with weekly schedule timer
Central remote controller 2
Unified ON/OFF controller 2
Schedule timer 2 i ntelligent Touch Controller 2
Adaptor for wiring (interlock for fresh air intake fan)
Wiring adaptor for electrical appendices 3
Interface adaptor for SkyAir series
K-FDS201D (1 m) K-FDS202D (2 m) K-FDS203D (3 m)
K-FDS204D (4 m) K-FDS205D (5 m) K-FDS206D (6 m)
K-FDS201D (1 m) K-FDS202D (2 m) K-FDS203D (3 m)
K-FDS204D (4 m) K-FDS205D (5 m) K-FDS206D (6 m)
KBBJ25K56 KBBJ25K80
KDAJ25K56 KDAJ25K71
KDJ2507K56 KDJ2507K80
BRC1C61
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP1BA54
KRP4AA51
DTA102A52
KBBJ25K160
KDAJ25K140
KDJ2507K160
KBBJ25K56 KBBJ25K80
KDAJ25K56 KDAJ25K71
KDJ2507K56 KDJ2507K80
BRC1C61
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP1BA54
KRP4AA51
DTA102A52
KBBJ25K160
KDAJ25K140
KDJ2507K160
Note:
1
Wiring for wired remote controller to be procured locally.
2
This optional accessory requires DTA102A52.
3 Installation box for adaptor PCB (KRP1B97) is necessary.
WALL MOUNTED TYPE
Kit name
Name of option Remark
Drain-up kit
Remote controller Wired type 1
Wireless type
Wired LCD remote controller with weekly schedule timer
FAY71L
K-KDU572CVE
Cooling only
BRC1C61
BRC7E619
BRC1D61
FAY100FA
BRC7C611W
Central remote controller
Unified ON/OFF controller
DCS302CA61
DCS301BA61
DCS302CA61 2
DCS301BA61 2
Schedule timer DST301BA61 DST301BA61 2 i ntelligent Touch Controller
Wiring adaptor for electrical appendices (2)
Interface adaptor for SkyAir series 3
DCS601C51
KRP4AA51 3
DCS601C51 2
Installation box for adaptor PCB KRP4AA93
1
Wiring for wired remote controller to be procured locally.
2
This optional accessory requires DTA102A52.
3
Installation box for adaptor PCB (KRP4AA93) is necessary.
KRP4AA51
DTA102A52
FAY71L
K-KDU572CVE
Heat pump
BRC1C61
BRC7EA618
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP4AA51 3
FAY100FA
BRC7C610W
DCS302CA61 2
DCS301BA61 2
DST301BA61 2
DCS601C51 2
KRP4A51
DTA102A52
KRP4AA93
FLOOR STANDING TYPE
Kit name
Name of option Remark
Replacement long-life filter
Wired LCD remote controller with weekly schedule timer
Central remote controller 1
Unified ON/OFF controller 1
Schedule timer 1 i ntelligent Touch Controller 2
Remote controller for 2 remote control system
Adaptor for wiring 2
Group control adaptor 2
Interface adaptor for SkyAir series
Installation box for adaptor PCB
Note:
1
2
This optional accessory requires DTA102A52.
Installation box for adaptor PCB (KRP4A95) is necessary.
Cooling only
FVY71LA/100LA/125LA
KAFJ95L160
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
BRC1C61
KRP1BA57
KRP4AA52
DTA102A52
KRP4A95
Heat pump
FVY71LA/100LA/125LA
KAFJ95L160
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
BRC1C61
KRP1BA57
KRP4AA52
DTA102A52
KRP4A95
58
Indoor unit
DUCT CONNECTION TYPE
Name of option Remark
Wired LCD remote controller with weekly schedule timer
Remote controller
Low static pressure type
Cooling only Heat pump
FDBG25A/
35A/50A
FDBG60A/
71A
FDYB35KA/
50KA
FDYB60KA/
71KA
-------
KRC47-1A
BRC1D61
-------
Middle static pressure type
Cooling only Heat pump
FDMG71A/
100A/125A/
140A/180A
FDYM03FA/
04FA/05FA/
06FA
FDYM03FA/
04FA/05FA/
06FA
-------
KRC47-1A
BRC1D61
-------
BRC1D61
-------
Wired LCD remote controller
Digital remote controller
Digital remote controller for duct heater use
Wireless remote controller
Central remote controller
Unified ON/OFF controller
Schedule timer i ntelligent Touch Controller
Remote sensor (for indoor temperature)
Central control adaptor kit
Adaptor for wiring
Wiring adaptor for electrical appendices
Switch box for adaptor kit
Interface adaptor for SkyAir series
Installation box for adaptor PCB
-------
KRC47-2A
KRC47-4A
-------
-------
-------
-------
-------
-------
-------
-------
-------
-------
-------
-------
BRC1C61
-------
-------
BRC4C62
DCS302CA61 1
DCS301BA61 1
DST301BA61 1
DCS601C51 1
-------
-------
KRP1BA54
KRP4AA52
KRP1B100
DTA102A52
-------
3
Suction grille
Drain pan cover
KDGF19A45 KDGF19A71
KKD19A1
KDGF19A45 KDGF19A71
KKD19A1
Note:
1
2
This optional accessory requires DTA102A52.
3
This optional accessory requires DTA107A55.
4
This optional accessory requires KRP1B100.
5
Installation plate for adaptor PCB (KRP4A95) is necessary.
In case of using KRC17-2B or field supplied remote controller, 3-Minutes Timer (field supplied) is required.
-------
KRC47-2A
KRC47-4A
-------
-------
-------
-------
-------
-------
-------
-------
-------
-------
-------
-------
-------
-------
BRC1C61
-------
-------
BRC1C61
-------
-------
BRC4C64 BRC4C62
DCS302CA61 1 DCS302CA61 1
DCS301BA61 1 DCS301BA61 1
DST301BA61 1 DST301BA61 1
DCS601C51 1 DCS601C51 1
-------------
-------
-------
-------
-------
KRP4AA51 4
-------
DTA102A52
-------
-------
-------
KRP4AA51 4
-------
DTA102A52
-------
-------
-------
High static pressure type
Cooling only Heat pump
FD03K/
04K/05K/
06K/08K/
10K
FD15K/
20K
-------
FDY06KA/08KA/
10KA/15KA/20KA
BRC1D61
------KRC47-3A KRC47-3A/
KRC17-2B 5
-------
KRC47-5
-------
BRC1C61
-------
-------
-------
DCS302CA61 2
DCS301BA61 2
DST301BA61 2
DCS601C51 2
KRCS01-1B
DTA107A55
-------
-------
-------
-------
-------
BRC4C62
DCS302CA61
-------
KRP1BA57 3
KRP4AA53 3
-------
DTA102A52
1
DCS301BA61 1
DST301BA61 1
DCS601C51 1
-------
-------
-------
KRP1B100
-------
-------
New communication functions in the user-friendly icon based multilingual controller simplity centralised control of the system
Special
Function 1
Special
Function 2
Special
Function 3
Special
Function 4
Doubling of number of connectable indoor unit by adding a D -NET PLUS adapter (Optional)
Support for centralised control from else where., using a PC with a Web browser (Optional)
Sending of e-mail alerts to a specified address when malfunctions occur (Optional)
Built-in Ethernet port for connecting to the Internet or an intranet
Special
Function 5
Simple interlock function
Yearly schedule
Power proportional distribution*
(option)
Auto cool/heat change-over
Temperature Limitation
Labor saving Overall energy savings
Simplified BMS
Colour LCD Touch panel Icon display
Multilingual (English, French, German,
Spanish, Italian, or Chinese)
* Limitations apply to some models and functions.
For details please contact your local sales office.
DCS601C51
• CSV output of power proportional distribution results (Optional)
PCMCIA
Flash
Memory
Special
Function 2
Remote monitoring and control
Special
Function 3
Trouble reports
Special
Function 4
Unification adapter for computerised control
[DCS302A52]
Unified ON/OFF and status monitoring from the central monitoring panel
Pi Port
Forced OFF contact input
• Connection to power consumption metre
when using power proportional
distribution function. (Optional)
Forced OFF command from fire alarm monitoring panel
RS-232C
D -NET
Mobile Phone
Special
Function 3
Trouble reports
Special
Function 1
D -NET Plus Adapter
(option) [DCS601A52]
Indoor Unit HRV
Number of indoor unit expanded from 64 to 128.
Necessary for optional interface adaptor for SkyAir series (DTA112BA51) with the Intelligent Touch Controller.
Outdoor unit
59
Name of option Remark
Drain piping kit
Central drain plug
Air direction adjustment grille
Drain plug
Refrigerant branch piping For twin multi
For triple multi
Year-round cooling kit
Note:
1
One set includes 5 pieces for 5units.
Name of option Remark
Refrigerant branch piping For twin multi
For triple multi
For double twin multi
Kit name
R25J
R35J
-------
-------
KPW937A4
KKP937A4 1
R35G
R50G
R60G
KIS95
-------
R71FU
R100FU
R125FU
Cooling only
RG71A
RG140A
RG180A
R71LU
-------
KKPJ5F180
-------
-------
KHR58C21
-------
------KRK5F80V1
R100LU
R125LU
KRK5F140V1
R140LU
KHD58C21A
KHD58D33
KRK5F160V1
RY35F
RY50G(A)
R60G(A)
KIS95
-------
-------
Heat pump
RY71LU
RY100LU
RY125LU
RY140LU
-------
KKPJ5F180
-------
-------
KHR58C21
-------
-------
KHD58C21A
KHD58D33
Kit name
R200KU
KHD58C23A
KHR58P322H
KHRJ5F224F
Cooling only
R250KU
KHD58C24A
-------
KHRJ5F280F
RY200KU
KHD58C23A
Heat pump
KHR58P322H
KHRJ5F224F
RY250KU
KHD58C24A
-------
KHRJ5F280F
D I M E N S I O N S
(Unit: mm)
CEILING MOUNTED CASSETTE TYPE
Suspension bolt
4-M8 M10
Note3.
( 0~550 55
950
A view
3
295
840 55
6
7
8 5
240 260
270
315
4 1 2
Notes:
1 Location of unit's Name Plate
For Main body: Switch Box Cover inside surface of suction grille.
For decoration panel: Panel frame inside surface of suction grille.
2
When installing an optional accessory, refer to the
installation drawings.
For fresh air intake kit Inspection port is necessary.
For high efficiency filter unit Inspection port is not necessary.
3
In case of using wireless remote controller, this position will
be a signal receiver. Refer to the drawing of wireless remote
controller in detail.
9
300 or less
C
860~890 Ceiling opening
680 Suspension position
420
10
80 2 100=200 85
40
350
4-4M4 Hole
(prepared hole)
75
C view
60
80
Branch duct connection
420
350
40
B
B view
Required space
For fresh air intake kit connection
(direct installation type)
[FH(Y)C35KVE-71KVE]
55
80
840
2 100=200 85
55
12-M4 Hole
(prepared hole)
Branch duct connection
Required space
1500mm or more
1500mm
or more
1500mm
or more
1500mm or more
When the discharge grill is closeout,the required space is
200mm or more.
A
FH(Y)C35KVE-71KVE
FHYC100KVE-140KVE
A
230
288
B
240
298
C
165
195 [FHYC100KVE-140KVE]
55
80
840
2 100=200 85
55
14-M4 Hole
(prepared hole)
350
40
Branch duct connection
A
1
2
5
6
3
4
7
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Power supply connection
Remote control code and control wiring connection
Air discharge grille
Air suction grille
8
9
Port for water supply
Corner decoration cover
10 Drain hose
CEILING SUSPENDED TYPE
FH(Y)35BVE
FH(Y)50BVE
FH(Y)60BVE
FHY71BVE
FHY100BVE
FHY125BVE
A
920
920
1120
1120
1360
1550
B
960
960
1160
1160
1400
1590
18 17 16
170
105
142
90
58
12 9
145 60
A
(Hanging position)
127
10
8
40 50
60 65
Position slit hole for taking out in piping back
(View from the front)
105
15
680
Hanging bolt
4-M8~M10
1
5 11 80
Position : Hole of wall for taking out in piping back
(View from the front)
13
55
6
Obstacle
Floor side
30 or more
(Service space)
Drain pipe connection VP20
(For left piping)
B
The Front
80
3 2
Notes:
1
Location of unit's Name Plate: Bottom of fan housing inside the suction grille.
2
In case of using wireless remote controller, this position will be a signal
3
The remote control code is the standard <about 3 m outside the machine> attached.
(0.5 mm 2 2 wicks O.D. 5.4)
(It is attached to VRV.)
7 5
80
105
170
4
30 or more
(Service space)
Brand name plate
(Note.2)
6
4 o/ 45
55
14
1
2
3
Air discharge grille
Air suction grille
Air filter
4
5
6
Gas pipe connection
Liquid pipe connection
Drain pipe conneciton
9
10
7
8
Earth terminal (inside the electric components box) (M4)
Suspension bracket
Backward piping and wiring connection opening lid
11
Upward piping and wiring connection opening lid
Right side pipe connection
12
13
14
Left back drain pipe connection
Left side drain pipe connection
Right side drain pipe connection
15
16
17
18
Hole of wall for taking out in piping back
Upward drain pipe connection
Upward gas pipe connection
Upward liquid pipe connection
60
D I M E N S I O N S
(Unit: mm)
CEILING SUSPENDED CASSETTE TYPE
Drain connection location for upper piping
163
10
Drain connection location for rear piping
117 10
Drain pipe can be raised up to 350mm from the top surface of the product.
Brand name plate (Note)2)
895
790 Susension position
1500mm
or more
Required space
1500mm
or more
1500mm
or more
1500mm
or more
When closing the discharge grill,the required space is
30mm or more.(Note3)
2
9
5
FUY71FJV1
FUY100FJV1/125FJV1
A
16
51
B
80
147
C
110
177
D
110
177
E
80
147
F
58
125
G
40
107
H
165
230
Notes:
1
2
Location for manufacture's label: on bell mouth.
This is where the signal of wireless remote controller is received.
Refer to the drawing of wireless remote controller in detail.
3
When closing the discharge grille (2 or 3 way discharge), direction of
pipe connection will be limited, please refer to Installation manual.
CEILING MOUNTED CASSETTE CORNER TYPE
5 1 2 3
C
7
6
80
145
185
3
8
1
52 132
4
Suspension bolt
Height of suspension bracket
1000mm or more
(Required space)
1
2
5
6
3
4
7
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Air outlet
Air suction grille
Corner decoration cover
Right pipe/wiring connection
8
9
Rear pipe/wiring connection
Pipe through cover
10 Accessory drain elbow
20mm or more
1500mm or more
Required space
200mm or more
6
148
215
67
250
4
8 9
F
200mm or more
Fresh air intake position
65
80
75
4-M4 hole
61
65
5 20
G
A (Suspension position)
B (Ceiling opening)
C
D
E
20
20 5
10
65
Front discharge duct connection position
(Note.2)
Suspension bolt
4-M8~M10
7
FH(Y)K35.45F(J)V1
A
1150
B C
1200 1110
D
260
E F G
520 1240 4-M4 hole
FH(Y)K60.71F(J)V1 1350 1400 1310 2 230=460
Note. 2:
Location of unit's Name plate
For main body: Bottom part of fan housing inside of Air
suction grille.
For decoration panel: Service lid face inside of Air
suction grille.
When installing an optional accessory, refer to the installation drawings.
For discharge grille
For frexible duct
For panel spacer
For air discharge blind panel
Inspection port is not necessary
1
2
3
4
720 1440
6-M4 hole
5 Wire intake for remote control cord
6
7
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Wire intake
Grounding terminal (M4 in switch box)
Air discharge grille
Air suction grille 8
9
10
Long life air filter
Suspension bracket
CEILING MOUNTED BUILT-IN TYPE
B
C
D
A
65
60
50
Suspension bolt
C
57
A
300 or more
Service space
1
25
595
440
800
(Air suction parelcenter)
315
3 5
2
45 46
6
4
J
K
B
WALL MOUNTED TYPE
[FAY71LVE]
G
E
F
(Ceiling opening)
H (Suspension position)
A View
7
18-M5 hole
160 P.C.D
125
(Knockout hole)
L
A
B View
600
Fresh air intake position
6-M5 hole
(Circumference)
C View
The required ceiling depth varies according to configration of specific system
Sustion air intake position when installing the duct
(Note.3)
A B C D E F
FH(Y)B35FV1/45FV1
FH(Y)B60FV1/71FV1
700
1000
485
785
460
760
3 150=450
5 150=750
760 800
1060 1100
FHYB100FV1/125FV1 1400 1185 1160 7 150=1050 1460 1500
G H J K L
FH(Y)B35FV1/45FV1
FH(Y)B60FV1/71FV1
FHYB100FV1/125FV1
6 65=390
11 65=715
750
1050
650
950
628
927
4 150=600
6 150=900
16 65=1040 1450 1328 1328 9 150=1350
Notes:
1 Location of unit's Name Plate:
Fan housing surface inside of filter.
2 When installing an optional accessory, refer to the
installation drawings.
3 Refer to the separate drawing when installing the duct.
6
7
4
5
1
2
3
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Wire intake for remote control cord
Wire intake
Drain hole
Air filter
Piping direction
Approx.400
232
230
7
Dimensions for full open front panel
9 2 1
50 or more
(Requred space)
Piping direction
104
Outside line
Notes:
1 Location of unit's of NAME Plate:
2
Right side surface of casing
In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.
80 hole
60
6
5
4
Mounting location
3
Name plate Note)2
1050
894
Approx.345
Approx.390
Approx.475
Piping direction
52
50 or more
(Requred space)
2500 or more
For in installation high spaces
120 or less
98
80 hole
Piping
Wiring and intake
1 Front panel
8
9
6
7
4
5
2
3
Front grille
Air outlet
Gas pipe
Liquid pipe
Drain hose
Grounding terminal
Right side pipe connection hole
Left side pipe connection hole
8
62
D I M E N S I O N S
(Unit: mm)
WALL MOUNTED TYPE
Piping direction
[FAY100FAVE]
9
50 or more
(Required space)
50 or more
(Required space)
1570
1
7
8
74
60
40
6 6
200
8-5 x 20 Oval Hole (For wood screw)
5-6 x 20 Oval Hole (For wood screw)
Ceiling surface
120 180
1235
120 120 210
3
120 120 123
100
Brand name plate
Note 2.
2
250 or more
Service space for air filter
Direction for air filter draw out
A A A A A A A A
40
50
70
13- 5 Hole (For wood screw)
2- 12 Hole (For bolt)
Detail A (Mounting hole for installation plate)
6
5
4
Approx. 450
Approx. 580
Approx. 600
Mounting location
60
80 Hole
Piping and wiring intake
Notes:
1
Location of general rated name plate Right side plate outside surface
2 In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.
1
2
3
4
7
8
9
Front grille
Air filter
Discharge outlet
Gas piping connection
Gas piping connection 5
6 Drain piping connection
Earth terminal (M4) (inside cover)
Slit hole for right side piping connection
Slit hole for left side piping connection
FLOOR STANDING TYPE
FVY71LAVE
A
270
FVY100LAVE/125LAVE 350
B
45
44
C
50
49
D
50
E F
110 180
G H
186 242
J
57
130 190 260 266 322 79
K L
144 149
202 229
600
598
200
223
253
68
TAKE OUT DIRECTION
OF AIR-FILTER
8
9
10
APPROX.
36
FULL OPEN
POSITION
OF SUCTION
GRILL
B
C
A
VIEW
260
130 215
414HOLE
(FOR BOLT)
FIXTURE
(ACCESSARY)
330
126
THIS MODEL TO BE FIXED
WITH FIXTURE AS SHOWN BELOW.
IN CASE OF FIXING IT AT THE BOTTOM
IN CASE VIBRATION RESISTANCE
IS REQUIRED, FIX IT AT BOTH
THE BOTTOM AND THE REAR.
7
DETAIL OF CONTROL PANEL
IN CASE OF FIXING IT AT THE REAR
NORMAL INSTALLATION
2-7X15 OBLONG HOLE
(FOR WOOD SCREW)
F
G
H
E
2
1
D
5
4
3
50
OR
M
OR
E
50
OR
M
OR
E
RE
1500
OR MO
REQUIRED SPACE
6
6
6
3
4
1
2
5
SUCTION GRILL
AIR FILTER
THROUGH HOLE FOR SIDE PIPING
THROUGH HOLE FOR SIDE PIPING
THROUGH HOLE FOR SIDE WIRING
6
7
8
9
THROUGH HOLE FOR REAR PIPING/WIRING
THROUGH HOLE FOR BOTTOM PIPING/WIRING
LIQUID PIPE CONNECTION
GAS PIPE CONNECTION
184 184
10 DRAIN PIPE CONNECTION
NOTES:
1
STICKING LOCATION FOR MANUFACTURE'S LABEL
: ON THE SURFACE OF COVER OF SWITCH BOX
INSIDE THE SUCTION GRILL.
63
DUCT CONNECTION LOW STATIC PRESSURE TYPE
B
A
595
3
3
300 or more
Service space
8
C
(Suspension bolt pinch)
684
664
D
126
2
4
5
K
(All around)
E 29
1
6 7
L
(All around)
16
10
151
127 F
G
H
I
J
1
2
6
7
3
4
5
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Ground terminal
8
Switch box
Control wiring intake (for outdoor unit)
Control wiring intake (for remote controller)
Suspension bracket
Note: 1 Location of unit's Name Plate: Chamber cap
FDBG25AVE/35AVE/50AVE
FDYB25KVE/35KAVE/50KAVE
FDBG60AVE/71AVE
FDYB60KAVE/71KAVE
A
900
900
1300
B
704
704
1104
1300 1104
C
755
755
1155
1155
D
3XP150=450
3XP150=450
E
500
500
F
3XP150=450
3XP150=450
G
674
674
H
688
688
I
704
704
J
900
900
6XP150=900 700 6XP150=900 1074 1088 1104 1300
6XP150=900 700 6XP150=900 1074 1088 1104 1300
K L
10-M4
Holes
12-M4
Holes
10-M4
Holes
12-M4
Holes
16-M4
Holes
18-M4
Holes
16-M4
Holes
18-M4
Holes
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
B
A
151
3
3
300 or more
8
C
(Suspension bolt pinch)
D
E
F
126
2
G
(All around)
H 29
1 6 7
1
2
Liquid pipe connection
Gas pipe connection
3
4
Drain pipe connection
Ground terminal
5
6
Switch box
Control wiring intake (for remote controller)
7
8
Control wiring intake (for outdoor unit)
Suspension bracket
Note: 1 Location of unit's Name Plate: Chamber cap
FDMG71AV1
FDMG100AV1/125AV1/140AV1
FDMG180AV1
A
1350
1550
1900
B C
1153 1203
1353 1403
1703 1753
D
1134
1334
1684
E F G
1114 7XP150=1050
1314 7XP150=1050
1664 9XP150=1350
18-M4
Holes
18-M4
Holes
22-M4
Holes
H
727
827
827
4
5
Service space
[FDMG71AV1]
151
8
16
51
1350
1153
1137
1121
7 X P150=1050
[FDMG100AV1/125AV1/140AV1/180AV1]
151
8
16
51
FDMG100AV1/125AV1/140AV1
FDMG180AV1
I
J
K
L
M
20-M4 Holes
(All around)
N
(All around)
I
1550
J K
1353 1337
1900 1703 1687
L
1321
M
7XP150=1050
1671 9XP150=1350
N
20-M4
Holes
24-M4
Holes
64
D I M E N S I O N S
(Unit: mm)
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
210
194
(OPENING)
100
F
(ALL ROUND)
680
600
(SUSPENSION POSITION) 6
236
220
(OPENING)
100
125
K
(ALL ROUND)
DISCHARGE SIDE
2
1
680 OR MORE
(SERVICE SPACE)
25
E
(ALL ROUND)
136
INSPECTION HOLE 450 OR MORE
4
SUCTION SIDE
(NOTE.1)
72
118
287
3 7 5
P
(ALL ROUND)
3
4
1 LIQUID PIPE CONNECTION
[ 9.5(FLARE CONNECTION)]
2 GAS PIPE CONNECTION
[03F: 15.9(FLARE CONNECTION)]
[04~06F: 19.1(FLARE CONNECTION)]
DRAIN PIPE CONNECTION[VP25]
EARTH TERMINAL
(INSIDE SWITCH BOX)
5
6
7
POWER SUPPLY
SUSPENSION BRACKET
[FOR M10 or M8 BOLT]
MANUFACTURER'S LABEL
NOTES:
1
MOUNT THE AIR FILTER AT THE SUCTION SIDE.
SELECT ITS COLORIMETHOD (GRAVITY METHOD)
50% OR MORE.
FDYM03FA
FDYM04FA-06FA
FDYM03FA
FDYM04FA-06FA
FDYM03FA
FDYM04FA-06FA
FDYM03FA
FDYM04FA-06FA
A
1100
1500
H
834
1234
11xP65=715
18xP65=1170
J
850
1250
N
5xP150=750
8xP150=1200
B
K
14- 7 HOLE
20- 7 HOLE
P
16- 7 HOLE
22- 7 HOLE
C
15xP65=975
21xP65=1365
D
1140
1540
E F
38- 4.7 HOLE
50- 4.7 HOLE
30- 4.7 HOLE
44- 4.7 HOLE
G
4xP150=600
7xP150=1050
L
1079
1479
M
1064
1464
DUCT CONNECTION HIGH STATIC PRESSURE TYPE
35 850
756
6
35
3
65
[FD03KY1] [FD04KY1]
FD03KY1 302
FD04KY1
FD05KY1
A
552
735
B
2XP120=240
3XP150=450
4XP150=600
C D
650 700
900 950
900 950
E
750
1000
1000
[FD05KY1]
9
2-M4 Burring holes
(Both sides)
9
Service Space
1200 or more
2 5
148
4
9
3
9
3
46
90 85
1
2-M4 Burring holes
(Both sides)
1
2
Liquid pipe connection
Gas pipe connection
3
4
Drain pipe connection
5
6
Earth terminal
Power supply
Suspension bracket
DUCT CONNECTION HIGH STATIC PRESSURE TYPE
B 850
A
6
B
3
H
(Both sides)
H
(Both sides)
I I
Service Space
3
[FD06KY1] [FD08KY1] [FD10KY1]
FD06KY1
FD08KY1
FD10KY1
A
756
732
B
35
39
732 39
C
967
876
1076
D
5XP.180=900
4XP.180=720
5XP.180=900
E
1130
1130
1330
F G
1180 1230
1180 1230
1380 1430
H
6-M4
Burring holes
5-M4
Burring holes
6-M4
Burring holes
2-M4 Burring holes
(Both sides)
9
I
10
10
J
50
58
58
T
K
58
67
67
1200 or more
2 5
P
4
T
3
L
266
294
294
M
150
160
160
N O
261 75
311
311
100
100
P
148
155
155
V
46
U
Q
58
67
67
1
R S
468 500
T
418
468
450 9
500 10
10
1 Liquid pipe connection
2
3
Gas pipe connection
Drain pipe connection
4 Earth terminal
5
6
Power supply
Suspension bracket
2-M4 Burring holes
(Both sides)
U
90
79
79
V
85
47
47
DUCT CONNECTION HIGH STATIC PRESSURE TYPE
B B
3
3
3
850
A
10
Service
Space
C
3
[FDY06KAY1]
3
[FDY08KAY1]
3
10
[FDY10KAY1]
Air outlet
Air inlet
S
(Both sides)
S
(Both sides)
9
2-M4 Burring holes
(Both sides)
Service Space
325
2
1200 or more
4 9 4
I
Arrow View I 2-M4 Burring holes
(Both sides)
A
FDY06KAY1 756
FDY08KAY1 732
FDY10KAY1
B
35
39
732 39 10
C
9
10
D
967
876
1076
E
5XP180=900
4XP180=720
5XP180=900
F
1130
1130
1330
G H I
1180 1230 9
J
58
1180 1230 10 67
1380 1430 10 67
K
150
L
266
M
418
N
450
O
261
P
90
Q
85
160 294 468 500 311 79 47
160 294 468 500 311 79 47
Note: 1 Location of unit's Name Plate: Lid of control box.
P
46
Q
1
8
6 5 7
1
2
Liquid pipe connection
Gas pipe connection
3 Drain pipe connection
4
5
Earth terminal
Hole for power supply
6 Hole for motor wiring
7
11
Hole for wiring from outdoor unit
8
9
10
Hole for remote controller wiring
Control box
Auxiliary pipe
Suspension bracket
66
D I M E N S I O N S
(Unit: mm)
DUCT CONNECTION HIGH STATIC PRESSURE TYPE
50 or more
Supprting plate
(Commercially available)
50 or more
Supprting plate
(Commercially available)
10
Service Space 7
*1
A
(Upward and downward)
*1
/ 3.1 holes
(Upward and downward)
8
9
8
9
10
10
125 80 80 80
[FD15KY1]
125 80 80 80
[FD20KY1]
FD15KY1
FD20KY1
A B C D
/ 3.1 holes 9XP.150=1350
/ 3.1 holes 11XP.150=1650
1042 1620
1762 1980
E
1710
2070
F G H
1750 1770 24
2110 2220 54
Notes:
1
Prepared holes for M4 tapping screw.
DUCT CONNECTION HIGH STATIC PRESSURE TYPE
50 or more Supprting plate
(Commercially available)
50 or more
Supprting plate
(Commercially available)
Service Space
500 or more
35
*1
/ 3.1 holes
(Both sides)
2
100 600
850
10
12
763
805
Service Space
10
7
35
*1
/ 3.1 holes
(Both sides)
1
5
10
Air outlet
*1
/ 3.1 holes
(Upward and downward)
*1
/ 3.1 holes
(Upward and downward)
Air inlet
6
6
20
4 3 6 5
1
2
Evaporator air outlet connection
Evaporator air inlet connection
3
4
5
6
7
8
Liquid pipe connection (No.1)
Gas pipe connection (No.1)
Liquid pipe connection (No.2)
Gas pipe connection (No.2)
Drain pipe connection
Earth terminal
9
10
Power supply intake
The holes for anchor bolts
2 1 4 3
12580 80 80
[FDY15KAY1]
10
12580 80 80
14
[FDY20KAY1]
9 10 11
500 or more
485 Service Space
35
100 600
850
12
6
*1
3- o / 3.1 holes
(Both sides)
Arrow view
7
8
Arrow view (detail)
A B C D
FDY15KAY1 500
FDY20KAY1
800 or more
9XP150=1350 1042 1620
11XP150=1650 1762 1980
E
1710
F G
1750 1770
H
24
2070 2110 2220 54
Notes: 1 Prepared holes for M4 tapping screw.
763
805 10
5
35
*1
/ 3.1 holes
(Both sides)
1
2
Liquid pipe connection (No.1)
Gas pipe connection (No.1)
3
4
Liquid pipe connection (No.2)
Gas pipe connection (No.2)
Drain pipe connection 5
6
7
8
9
Earth terminal
Hole for power supply
Hole for motor wiring
Hole for wiring from outdoor unit (No.1)
10
11
12
13
Hole for wiring from outdoor unit (No.2)
Hole for remote controller wiring
Control box
The holes for anchor bolts
67
OUTDOOR UNIT // R25JV1, R35JV1
DRAIN OUTLET
(I. D o /15.9 HOSE FOR CONNECTION)
420
4 –HOLES FOR ANCHOR BOLTS
(M8 OR M10)
19
470
695
115
70 8 265
NAME PLATE
WIRING INLET
TERMINAL STRIP
WITH EARTH TERMINAL
R25JV1
R35JV1
A
9.5
12.7
MINIMUM SPACE FOR AIR PASSAGE
SERVICE PORT
GAS STOP VALVE
(o/ A CuT)
WALL HEIGHT ON AIR OUTLET SIDE
=LESS THAN 1200
118
178
21
LIQUID STOP VALVE
(o/6.4CuT)
50 50
OUTDOOR UNIT // R35GV1, RY35FV1A, R50GV1
HOLES FOR ANCHOR BOLTS
(M8 OR M10)
DRAIN OUTLETS
700
520
190
170 60
50
MINIMUM SPACE FOR AIR PASSAGE
530
750
+ 4
0
100 72
15 270
+ 4
0
4 0
NAME
PLATE
34 105
SERVICE PORT
58
EARTH
TERMINAL
(M4)
POWER INTAKE
GAS STOP VALVE
LIQUID STOP VALVE
27
50 50
50
68
D I M E N S I O N S
(Unit: mm)
OUTDOOR UNIT // RY50GAV1A, R60GV1
HOLES FOR ANCHOR BOLTS
(M8 OR M10)
2-DRAIN OUTLET
269
540
800
UNIT NAME PLATE
130
75
EARTH TERMINAL
(M4)
15
POWER INTAKE
LIQUID
STOP VALVE
SERVICE PORT
GAS
STOP VALVE
100
300
UNIT NAME PLATE
LIQUID PIPE
GAS PIPE
MINIMUM SPACE FOR AIR PASSAGE
50
OUTDOOR UNIT // RY60GAV1A
HOLES FOR ANCHOR BOLTS
(M8 OR M10)
50
OUTDOOR
AIR THERMOSTAT
A
H
H 1000
H 1000
A
300
600
69
40
3-DRAIN OUTLET
120 500
881
MINIMUM SPACE FOR AIR PASSAGE
100
177
190
55
TERMINAL COVER
15 350
POWER INTAKE
LIQUID STOP VALVE
GAS STOP VALVE
UNIT NAME PLATE
SERVICE PORT
40
120 110
EARTH TERMINAL
(M4)
30
A
OUTDOOR
AIR THERMOSTAT
100
H 1000
H 1000
A
350
600
OUTDOOR UNIT // R71FUY1, RG71AV1/AY1
30
Hole for anchor bolt 4-M12
146 584
880
150
84
44
2
7
4
3
1
6
5
5
Name plate
90
137
14
102 11
14 67
115
Knock hole for lower piping
391
OUTDOOR UNIT // R(Y)71LUV1/Y1
Hole for anchor bolt 4-M12
8
7
6
3
4
1
2
Gas pipe connection
Liquid pipe connection
Service port (in the unit)
Grounding terminal
Refrigerant piping intake
7
8
5
6 Power supply wiring intake
Control wiring intake
Drain outlet
30
140 620
900
96
140
40
3
4
2
1
7
9
6
5
7
6
5
8
45 376 191
89
142
71
19
16
19 80
145
52
13 67
5
Note: In some circumstances, with certain machine types,
it may not be possible to attach the supplied piping.
1
2
Gas pipe connection
Liquid pipe connection
Service port 3
4
5
Grounding terminal
Refrigerant piping outlet
6
7
Power supply wiring outlet
8
9
Control wiring outlet
Drain outlet
Supplied piping
70
D I M E N S I O N S
(Unit: mm)
OUTDOOR UNIT // R100FUV1/Y1, 125FUY1
Hole for anchor bolt 4-M12
84
38
146 584
880
150
30
4
3
2
1
7
6
5
5
391
OUTDOOR UNIT // R(Y)100LUV1/Y1
Hole for anchor bolt 4-M12
Name plate
90
137
14
102 11
14 67
115
Knock hole for lower piping
8
7
6
7
8
5
6
3
4
1
2
Gas pipe connection
Liquid pipe connection
Service port(in the unit)
Grounding terminal
Refrigerant piping intake
Power supply wiring intake
Control wiring intake
Drain outlet
30
140 620
900
96
140
41
2
1
7
3
4
9
6
5
5
7
6
7
6
5
45 376 191
8
89
142
19
71 16
19 80
145
5
Note: In some circumstances, with certain machine types,
it may not be possible to attach the supplied piping.
52
13 67
1 Gas pipe connection
2 Liquid pipe connection
3
4
Service port
Grounding terminal
5 Refrigerant piping outlet
6
7
Power supply wiring outlet
Control wiring outlet
8 Drain outlet
9 Supplied piping
71
OUTDOOR UNIT // R(Y)125LUY1, 140LUY1
Hole for anchor bolt 4-M12
A
R(Y)125LUY1 1170
B
54
R(Y)140LUY1 1345 55
C
113
D
579
— —
30
140 620
900
96
140
41
3
4
7
6
5
1
2
7
6
5 5
C
D
8
71
89 19
142
16
19 80
145
45
OUTDOOR UNIT // RU06KY1
376 191
Hole for anchor bolt 4-M12
130 620 130
5
80
34
880
30
5
4
1
7
6
3
2
5
320
7
6
name plate
70.5
89
137
14
12
15
145
67
7
6
5 51
15 36
52
13 67
5
6
3
4
1
2
7
8
Gas pipe connection
Liquid pipe connection
Service port (in the unit)
Grounding terminal M5 (in switch box)
Refrigerant piping intake
Power supply wiring intake
Control wiring intake
Drain pipe connection
41
377
644
8
Knock hole for lower pipng
1
4
5
2
3
6
7
8
Gas pipe connection
Liquid pipe connection
Service port (in the unit)
Grounding terminal M5 (in switch box)
Refrigerant piping intake
Power supply wiring intake
Control wiring intake
Drain pipe connection
72
D I M E N S I O N S
(Unit: mm)
OUTDOOR UNIT // RG140AY1/180AY1
Hole for anchor bolt 4-M12
146 584
880
150
84
38
30
4
3
2
1
7
6
5
5
7
6
5
name plate
90
137
14
102 11
14 67
115
14 90
5
3
4
1
2
Gas pipe connection
Liquid pipe connection
Service port(in the unit)
Grounding terminal M5(in switch box)
Refrigerant piping intake
7
8
5
6 Power supply wiring intake
Control wiring intake
Drain outlet
391
OUTDOOR UNIT // RU08KUY1/10KUY1
RU08KUY1
A
76
RU10KUY1 71
B
225
C
1220
229 1440
8
( for side-roted pipes ) 95
1000
( Pitch of foundation bolt holes )
4- 15mm-dia.holes
( Foundation bolt holes )
Notes:
1. The dimensions marked by an asterisk( ) are
those with the installation of the provided pipes.
2.Refer to the installation instructions when the pipes
are routed through the bottom of the unit.
1290
73
3
70
4
690
76
A
32
5
(Knock-out hole)
6
(Knock-out hole)
13
123
150
230
135
2
1280
1
97
62
4
70
name plate
(for frontroted pipes)
265
80
750
80
1
2
3
Liquid pipe connection port.
Gas pipe connection port.
Earth terminal
4
5
6
(M5) (inside of control box)
Power cord routing hole ( side )
Pipe routing hole ( side )
Pipe routing hole ( Bottom )
OUTDOOR UNIT // RU08KY1/10KY1
A
RU08KY1 1220
RU10KY1 1440
1000
( Pitch of anchor bolts )
4- 15 Holls
For anchor bolts
1290
70
4
690
76 32
5
3
1
2
6
32
202 20
97
1280 name plate
OUTDOOR UNIT // R(Y)200KUY1/250KUY1
R(Y)200KUY1
R(Y)250KUY1
A B
228 1220
224 1440
1000
( Pitch of anchor bolts )
4- 15 Holls
For anchor bolts
4
70
80 80
750
1 Liquid pipe conn.
2
3
Gas pipe conn.
Earth terminal
(M5) (in the el.compo. box assy)
5
6
4 Wiring intake ( side )
Refrigerant piping conn. ( side )
Refrigerant piping conn. ( Bottom )
Notes
The dimension ( with marked ) are attached accessory pipe.
95
( In case of side conn. )
3
70
4
1290
4
70
5
690
70 34
13
150 80
97
2 1
1280
6
name plate
265
( In case of front conn. )
750
2
3
1 Liquid pipe conn.
Gas pipe conn.
Earth terminal
4
5
6
(M5) (in the el.compo. box assy)
Wiring intake ( side )
Refrigerant piping conn. ( side )
Refrigerant piping conn. ( Bottom )
74
D I M E N S I O N S
(Unit: mm)
REMOTE CONTROLLER
Wireless type
• REMOTE CONTROLLER DIMENSIONS
TRANSMITTING PART
CEILING MOUNTED CASSETTE TYPE
•RECEIVER INSTALLATION PROCEDURE
RECEIVER
DRAIN PIPING
SIDE
WALL MOUNTED TYPE
•RECEIVER INSTALLATION PROCEDURE
FAY71L RECEIVER
• RECEIVER
DETAIL
REFRIGERANT
PIPING SIDE
62 17.5
• REMOTE CONTROLLER HOLDER
INSTALLATION PROCEDURE
<INSTALLATION TO WALL SURFACE>
LIQUID CRYSTAL
REMOTE CONTROLLER
(WIRELESS)
REMOTE CONTROLLER
HOLDER
•
RECEIVER DETAIL
2-5 x 9 Slot
DECORATION PANEL
• RECEIVER DETAIL
CEILING SUSPENDED TYPE
•RECEIVER INSTALLATION PROCEDURE
The Front RECEIVER
•RECEIVER INSTALLATION PROCEDURE
FAY100FA
RECEIVER
• RECEIVER
DETAIL
70 18
0.5
35
49
(Ceiling opening)
Switch box
(field Supplied parts)
Service space for ceiling installation
Note :
Do not install more than 3 receivers in the vicinity of one another.
With 4 or more units, there is always the possibility of malfunction
Wired type
•REMOTE CONTROLLER DIMENSIONS
• RECEIVER
DETAIL
•REMOTE CONTROLLER INSTALLATION PROCEDURE
A EXPOSED BODY, EXPOSED CORD B EXPOSED BODY, EMBEDDED CORD
17 CONDUIT
STAPLE
120
•DIGITAL REMOTE CONTROLLER
KRC47-2A/ KRC47-4A
110
25
17
18
23 28
46
CORD
OUTLET
HOLE
18
0~5
17
C EXPOSED BODY, EMBEDDED CODE
17
( DISTANCE BETWEEN
REMOTE CONTROLLER
AND CONTROL BOX )
THROUGH HOLE
(fl12~fl16)
CONTROL BOX
NOTE) 1. REMOTE CONTROLLER CORD AND STAPLE ARE NOT
ATTACHED. THEY ARE FIELD SUPPLIED PARTS.
SPECIFICATIONS OF CORD
TYPE
VINYL CORD WITH SHEATH OR CABLE
(INSULATED THICKNESS: 1 mm OR MORE)
SIZE 0.75~1.25 mm 2
TOTAL LENGTH 500 m
* Countries requiring EMC: Shield wire (insulated thickness: 1 mm or more)
•REMOTE CONTROLLER
KRC47-1A
136
124 32
KRC47-3A
136
124 32
92 14
85 85
75
[Space required for outdoor unit installation]
(Unit: mm)
Dimensions inside brackets [ ] indicate case where air direction adjustment guide is adjusted downward.
For R(Y)71LU-140LU
The values represent the case for the R(Y)71 type through R(Y)140 type.
The dimensions in ( ) are for the R(Y)100 and R(Y)140 type (The unit values is mm. )
When there is an obstruction on the inlet side
When there is an obstruction on the outlet side
When the overhead space is open
1. For single unit installation
When there is an obstruction only on the inlet side
When there are obstructions on both sides
100 or
mor e
100 or
mor e
2. For series installation
(more than two units)
When there are obstructions on both sides
100
0 or more
200 or
mor e
When there is an obstruction in the overhead space
1. For single unit installation
When there is an obstruction on the inlet side
500
or less
When the overhead space is open
1. For single unit
installation
2. For series installation
(more than two units)
500
or
more ore
50
or m
(100
)
An obstruction in the overhead space
When there are obstructions on the inlet side and both lateral sides
500
or less
10
0 o r m ore
An obstruction in the overhead space
100 or mo re
15
0 or mo re
15
0 or mo re
15
0 o r m ore
200 or mo re
)
(300
2. For series installation (more than two units)
When there are obstructions on the inlet side and both lateral sides
500
or less
An obstruction in the overhead space
100
0 or mo re
20
0 or mo re
200 or mo re
)
(300
When there is an obstruction in the overhead space
1. For single unit
installation
An obstruction in the overhead space
2. For series installation
(more than two units)
An obstruction in the overhead space
1000
or m ore
500
or
les s
500
or
more
500
or less
100
0 o r mo re
When there are obstructions on both the inlet and outlet sides
Pattern 1
When the obstruction on the outlet side is higher than the unit itself (There is no limit to the height of the obstruction on the outlet side.)
When the overhead space is open
1. For single unit installation
L H
2. For series installation
(more than two units)
L H
500
or m ore
50 or mor
(100) e
100
0 o r mo re
200 or mor e
(300)
For R(Y)200KU / 250KU
In case of single installation
Pattern 1
300 or more
Pattern 1
In case of parallel installation
300 or more
Pattern 1
300 or more
In case of set installation
FRONT
SIDE
500 or more
10 or more
FRONT
SIDE
500 or more
10 or more
10 or more 20 or more
FRONT
SIDE
500 or more
20 or more
10 or more
10 or more 20 or more
FRONT
SIDE
600 or more
10 or more
10 or more 20 or more
10 or more
900 or more
Pattern 2
100 or more
Pattern 2
100 or more
10 or more 20 or more
FRONT
SIDE
500 or more
10 or more
10 or more 20 or more
FRONT
SIDE
500 or more
10 or more
50 or more
FRONT
SIDE
500 or more
50 or more
50 or more 100 or more
FRONT
SIDE
500 or more
100 or more
50 or more
Pattern 2
100 or more
FRONT
SIDE
500 or more
Pattern 3
300 or more
The height of obstacle is free
Pattern 3
The height of obstacle is free
300 or more 50 or more 100 or more
50 or more
10 or more
FRONT
SIDE
200 or more 400 or more
FRONT
SIDE
400 or more
50 or more 100 or more
FRONT
SIDE
500 or more
50 or more
50 or more
50 or more
FRONT
SIDE
500 or more
50 or more
100 or more
100 or more
600 or more
FRONT
SIDE
500 or more
50 or more
Notes:
1
Obstacies height of (Pattern 1) and (Pattern 2) shall be as follows:
Front side 1500 mm
Suction side 500 mm
Side No (imitation)
2
For the service space. if the obstacle of height exceeds the above mentioned dimensions. half of the exceeded dimensions shall be added to the standard service space.
3
When installing a unit. choose the most suitable one from this manual depending on actual conditions such as walking passage and ventilation.
If the number of units is more than that shown in this manual.