CARLO GAVAZZI | UDM 40 - PROGRAMMING | User manual | UDM40 Datasheet

Add to My manuals
14 Pages

advertisement

CARLO GAVAZZI | UDM 40 - PROGRAMMING | User manual | UDM40 Datasheet | Manualzz

Digital Panel Meters

Modular Indicator and Controller

Type UDM40

• The alarm status can be coupled to the different colour of the display

• Linearization of V, A and Hz inputs up to 16 points

• Multi-input modular instrument 4-DGT LED

• 0.1% RDG basic accuracy

• TRMS AC current and voltage measurements

• AC/DC current measurements; selectable full scales

(200µA to 5A)

• AC/DC voltage measurements; selectable full scales

(200mV to 500V)

• °C or °F temperature measurements

(Pt100-250-500-1000, Ni100, TC J-K-S-T-E)

• Resistance measurements; selectable full scales

(20

to 20k)

• Dual rate, speed, frequency and period measurement

(0.001Hz to 50kHz)

• Up to 4 independent alarm set-points (optional)

• 20mA/10VDC analog output (optional)

• Serial port RS485 or RS232 (optional)

• MODBUS, JBUS communication protocol

• Front protection degree: IP67, NEMA12

• LED display, selectable colour (red, amber, green)

Product Description

µp-based digital panel meter, 4-DGT LED indicator, for current, voltage, temperature, resistance, rate, frequency, speed and period measurements. Measuring ranges and functions easily programmable from the keypad or from the PC by means of optional UdmSoft software. UDM 40 includes storage min-max functions and double level protection password. Housing for panel mounting with front protection degree: IP67, NEMA12.

How to order

UDM40 XXX XX XX X XX

Model

Slot A

Slot B

Slot C

Slot D

Options

How to order

UdmSoft-kit

UdmSoft-kit: software plus communication cable for programming UDM40 by means of PC.

UdmSoft: software for programming UDM35/40/60 by means of PC, downloadable from www.carlogavazzi.com.

Type Selection

Slot A (measuring inputs) Slot B (communication) Slot C (communication and alarm) Slot D (power supply)

LSX: signal inputs:

0.2-2-20mA DC/AC;

0.2-2-20V DC/AC

LSE/

LSF: signal inputs: + AUX:

0.2-2-20mA DC/AC;

0.2-2-20V DC/AC

HSX: signal inputs:

0.2-2-5A DC/AC;

20-200-500V DC/AC

TRX: signal inputs: TC temperature probes (J-K-

S-T-E, Pt100-250-500-

1000) and resistance

(0.02-0.2-2-20k

Ω)

TF1: 0.001Hz to 50kHz for

DC signals: PNP,

NPN, NAMUR, TTL, free of voltage, contacts, voltages up to

14VDC

TF2: 0.001Hz to 50kHz for

AC signals: pick-up, voltages up to

500VAC

XX: None

SX: Serial port RS485

SY: Serial port RS232

AV(*): Single analogue output,

0 to 20mA DC and

0 to 10V DC

XX: None

R1: Single relay output,

(AC1-8AAC, 250VAC)

R2:: Dual relay output,

(AC1-8AAC, 250VAC)

R4:: Dual relay output, (AC1-

8AAC, 250VAC) + dual open collector output

(NPN, 100mA)

R5:: 4 relay outputs

(AC1-5AAC, 250VAC)

AV(*): Single analogue output,

0 to 20mA DC and

0 to 10V DC

(*): The two analogue outputs cannot be used at the same time. It is possible to plug in only one module by instrument.

H:

L:

3:

Options

XX:

TX:

90 to 260V AC/DC

18 to 60V AC/DC

(24 to 48V AC/DC ±

25% according to UL)

10 to 28V DC

(12 to 24V DC ± 15% according to UL)

None

Tropicalization

Specifications are subject to change without notice UDM40 DS ENG 261110 1

UDM40

Input specifications

Analogue inputs

BQ LSX module

BQ LSE/LSF module

BQ HSX module

BQ TRX module

BQ TRX module

BQTF1 module

BQTF2 module

Digital inputs

Number of inputs

Use

Contact reading signal

Close contact resistance

Open contact resistance

Insulation

Accuracy (display, RS485)

Channels and variable

1, mA and V DC/AC

1, mA and V DC/AC + AUX

1, A and V DC/AC

1, temperature

1, resistance

2, frequency

2, frequency

Incl. in the measuring module

1 (voltage-free) key-pad lock

Display hold

Reset of latch alarms

BQ xxx: <0.1mA, <3,5V DC

BQ LSE/BQ LSF: <2.5mA,

<14V DC

BQTF1: <6mA, <7VDC

BQTF2: <0.25mA, <3VDC

Max 1k

Min 500k

Ω(BQTFx: 100kΩ)

Non-insulated

See table “Measuring accuracy”, temperature drifts and minimum-maximum indications”

Additional errors

Humidity

Input frequency

Magnetic field

Temperature drift

Sampling rate

Display refresh time

0.3% RDG (BQTFx: 0.05%),

60% to 90% R.H.

0.4% RDG, 62 to 440 Hz

0.5% RDG (BQTFx: 0.05%)

@ 400 A/m

See table “Measurement accuracy, temperature drifts, and max/min indications”

500 samples/s @ 50 Hz

(escl. BQTFx)

200 msec @ 50Hz

(escl. BQTFx)

Display

Colour

Max and min indication

Measurements

Coupling type

Crest factor

Input impedance

Frequency

Overload

Compensation

RTD

TC

4 DGT,

7 segments height 14.2 mm

Selectable (red, amber, green)

See table “Measurement accuracy, temperature drifts and max min indications”

Current, voltage, temperature, resistance and frequency. For the current and voltage measurements: TRMS measurement of distorted sine waves.

Direct

3; A

Pmax

=1.7In; V

Pmax

=1.7Un

See table “input impedances and overloads”

40 to 440 Hz

See table “input impedances and overloads”

Only temperature measurement module.

- For Pt 100-250-500-1000,

3-wire connection: up to 10

- For resistance measur. with

20

Ω range: up to max 0.1Ω

- For resistance measurements with

≥200Ωrange: up to max 10Ω

Internal cold junction, within temperature range from

0 to +50°C.

Automatic or manual compensation from 0 to 50°C.

Measurement accuracy, temp. drifts, max and min indications

All accuracies and min/max indications are referred to an ambient temp. range of 25°C ±5°C, rel. humidity

60% and scale ratio (electrical/displayed scale) equal to 1. The conversion into °F is obtained acting on the electrical/displayed scale ratio.

Module

BQ LSX/

BQ LSE/

BQ LSF

Inputs Type Accuracy

-200µA to +200µA

-2mA to +2mA

-20mA to +20mA

-200mV to +200mV

-2V to +2V

-20V to +20V

DC/AC

DC: ±(0.1%RDG+3DGT)

0% to 25% FS;

±(0.1%RDG+2DGT)

25% to 110% FS.

TRMS (da 45 a 65Hz)*:

±(0.3%RDG+3DGT)

0% to 25% FS;

±(0.3%RDG+2DGT)

25% to 110% FS.

Temp. drift

±150 ppm/°C

Min. indication ( < ) Max. indicat. ( < )

- 200.0

- 2.000

- 20.00

- 200.0

- 2.000

- 20.00

+ 200.0

+ 2.000

+ 20.00

+ 200.0

+ 2.000

+ 20.00

* <45Hz >65Hz= ±(0.5%RDG+3DGT) 0% to 25% FS; ±(0.5%RDG+2DGT) 25% to 110% FS.

( < ) The min. indication for TRMS measurement (AC or DC) is 0; it is possible to modify the decimal point position.

2 Specifications are subject to change without notice UDM40 DS ENG 261110

UDM40

Measurement accuracy, temp. drifts, max and min indications (cont.)

All accuracies and min/max indications are referred to an ambient temp. range of 25°C ±5°C, rel. humidity

≤60% and scale ratio (electrical/displayed scale) equal to 1. The conversion into °F is obtained acting on the electrical/displayed scale ratio.

Module

BQ HSX

BQ TRX

Thermocouple

Inputs Type Accuracy

-200mA to +200mA

-2A to +2A

-5A to +5A

-20V to +20V

-200V to +200V

-500V to +500V

DC/AC

DC: ±(0.1%RDG+3DGT)

0% to 25% FS;

±(0.1%RDG+2DGT)

25% to 110% FS.

TRMS (45 to 65Hz)*:

±(0.3%RDG+3DGT)

0% to 25% FS;

±(0.3%RDG+2DGT)

25% to 110% FS.

-50°C to +760°C

-58 °F to +1400 °F

-200°C to +1260°C

-328 °F to +2300°F

-200°C to +1000°C

-328°F to +1832°F

-50°C to +1750°C

-58°F to +3182°F

-200°C to +400°C

-328°F to +752°F

J

J

K

K

E

E

S

S

T

T

±(0.2%RDG+1DGT)

±(0.2%RDG+2DGT)

±(0.2%RDG+2DGT)

±(0.2%RDG+4DGT)

±(0.2%RDG+2DGT)

±(0.2%RDG+4DGT)

±(0.2%RDG+2DGT)

±(0.2%RDG+4DGT)

±(0.2%RDG+2DGT)

±(0.2%RDG+4DGT)

Temp. drift

±150 ppm/°C

±150 ppm/°C

Min. indication (

- 200.0

- 2.000

- 5.000

- 20.00

- 200.0

- 500.0

- 50°C

- 58°F

- 200°C

- 328°F

- 200°C

- 328°F

- 50°C

- 58°F

- 200°C

- 328°F

< ) Max. indicat. (

+ 200.0

+ 2.000

+ 5.000

+ 20.00

+ 200.0

+ 500.0

+ 760°C

+ 1400°F

+ 1260°C

+ 2300°F

+ 1000°C

+ 1832°F

+ 1750°C

+ 3182°F

+ 400°C

+ 752°F

* <45Hz >65Hz= ±(0.5%RDG+3DGT) 0% to 25% FS; ±(0.5%RDG+2DGT) 25% to 110% FS.

( < ) The min. indication for TRMS measurement (AC or DC) is 0; it is possible to modify the decimal point position.

< )

Module Inputs Type

BQ TRX

Thermoresistance

BQ TRX

Resistance

BQ TF1

-200°C to +850°C

-328°F to +1562°F

-200.0°C to +200.0°C

-328°F to+392°F

-200.0°C to +200.0°C

-328°F to +392°F

-200.0°C to +200.0°C

-328°F to +392°F

-200.0°C to +200.0°C

-328°F to +392°F

-60°C to +180°C

-76°F to +356°F

0 to 20

0 to 200

0 to 2000

0 to 20.00k

Pt100

Pt100

Pt100

Pt100

Pt250

Pt250

Pt500

Pt500

Pt1000

Pt1000

Ni100

Ni100

NPN (DC)

PNP (DC)

NAMUR (DC)

TTL (DC)

Free of voltage contact (DC)

Accuracy

±(0.2%RDG +2DGT)

±(0.2%RDG +4DGT)

±(0.5%RDG +5DGT)

±(0.5%RDG +5DGT)

±(0.5%RDG +5DGT)

±(0.5%RDG +5DGT)

±(0.5%RDG +5DGT)

±(0.5%RDG +5DGT)

±(0.5%RDG +5DGT)

±(0.5%RDG +5DGT)

±(0.5%RDG +1DGT)

±(0.5%RDG +2DGT)

±(0.2%RDG+2DGT)

25% to 110% FS

±(0.2%RDG+3DGT)

0% to 25% FS

0.001% RDG

±3 digit

BQ TF2

Pick-up (AC)

Voltage (AC) up to

100VAC

Voltage (AC) up to

500VAC

0.001% RDG

±3 digit

Temp. drift

±150 ppm/°C

±150 ppm/°C

± 50 ppm/°C

± 50 ppm/°C

Min. indication

- 200

- 328

- 200.0

- 328.0

- 200.0

- 328.0

- 200.0

- 328.0

- 200.0

- 328.0

- 60

- 76

0

0

0

0

0.000 (*)

00.00 (*)

000.0 (*)

0000 (*)

0.000 (*)

00.00 (*)

000.0 (*)

0000 (*)

Max. indicat.

+ 850

+ 1562

+ 200.0

+ 392.0

+ 200.0

+ 392.0

+ 200.0

+ 392.0

+ 200.0

+ 392.0

+ 180

+ 356

20.00 ( < )

200.0 ( < )

2000 ( < )

20.00 ( < )

9.999

99.99

999.9

9999

9.999

99.99

999.9

9999

( < ) It is possible to modify the decimal point position.

(*) The min indication is -9.99999, ..., -999999 in case of “rotation speed detection” function

Specifications are subject to change without notice UDM40 DS ENG 261110 3

UDM40

Input impedances and overloads

Module

BQ LSX/

BQ LSE/

BQ LSF

BQ HSX

BQ TRX

Thermocouple

BQ TRX

Thermoresistance

BQ TRX

Resistance

BQ TF1

BQ TF2

Inputs

-200µA to +200µA

-2mA to +2mA

-20mA to +20mA

-200mV to +200mV

-2V to +2V

-20V to +20V

-200mA to +200mA

-2A to +2A

-5A to +5A

-20V to +20V

-200V to +200V

-500V to +500V

-50°C to +760°C

-58 °F to +1400 °F

-200°C to +1260°C

-328 °F to +2300°F

-200°C to +1000°C

-328°F to +1832°F

-50°C to +1750°C

-58°F to +3182°F

-200°C to +400°C

-328°F to +752°F

-200°C to +850°C

-328°F to +1562°F

-200.0°C to +200,0°C

-328°F to +392°F

-200.0°C to +200,0°C

-328°F to +392°F

-60°C to +180°C

-76°F to +356°F

0 to 20

0 to 200

0 to 2000

0 to 20.00k

NPN (DC)

PNP (DC)

NAMUR (DC)

TTL (DC)

Free of voltage contact

(DC)

Type

DC/AC

DC/AC

DC/AC

DC/AC

DC/AC

DC/AC

DC/AC

DC/AC

DC/AC

DC/AC

DC/AC

DC/AC

K

K

E

E

S

J

J

S

T

T

Pt100

Pt100

Pt250/Pt100

Pt250/Pt100

Pt1000/Pt500

Pt1000/Pt500

Ni100

Ni100

Pick-up (AC)

Voltage (AC) up to

100VAC

Voltage (AC) up to

500VAC

Impedance Overload (continuous)

≤2,2kΩ

≤22Ω

≤22Ω

≥2,2kΩ

≥200kΩ

≥200kΩ

≤1Ω

≤0.012Ω

≤0.012Ω

≥2MΩ

≥2MΩ

≥2MΩ

5mA

50mA

50mA

10V

50V

50V

0.8A

7.5A

7.5A

750V

750V

750V

I

LK

<0.5µA

800µA (*)

800µA (*)

90µA (*)

90µA (*)

800µA (*)

800µA (*)

800µA (*)

800µA (*)

800µA (*)

90µA (*)

800µA (*)

90µA (*)

600

600

600

600

220 k

950 k

Max 5V

Max 5V

Max 5V

15 VAC/DC

15 VAC/DC

15 VAC/DC

15 VAC/DC

15 VAC/DC

120 VAC/DC

600 VAC/DC

Overloads (1s)

10mA

150mA

150mA

20V

100V

100V

1A

100A

100A

1000V

1000V

1000V

Max 10V

Max 10V

Max 10V

20 VAC/DC

20 VAC/DC

20 VAC/DC

20 VAC/DC

20 VAC/DC

200 VAC/DC

600 VAC/DC

(*) Maximum measuring current generated for resistance equal to 0

4 Specifications are subject to change without notice UDM40 DS ENG 261110

UDM40

Output specifications

Serial output

LED

Connections

Distance

Terminalization

Module: BR SX

Bidirectional (static and dynamic variables).

Display of data reception/transmission

Multidrop, 2 or 4 wires,

1000 m

Directly on the module

Addresses by means of jumper

1 to 247, selectable by means of key-pad

MODBUS RTU/JBUS Protocol

Data (bidirectional)

Dynamic (reading only) Measurement, min value max value

Static (reading/writing)

Data format

Baud rate

Insulation alarm status

All programming parameters, min max reset reset of latch alarm

8 data bit, no parity,

1 stop bit selectable 4800, 9600,19200 and 38400 bit/s

By means of opto-couplers

4000 V rms output to measuring inputs

4000 V rms output to power supply input

RS232

Serial output

Connections

Distance

Data format

Baud rate

Other features

(on request)

Module: BR SY

Bidirectional (static and dynamic variables)

3 wires, max. 15m

1 start bit, 8 data bit, no parity, 1 stop bit

Selectable 4800, 9600,

19200 and 38400 bit/s

Same as RS422/485

Alarm outputs

Alarm type

Alarm set-point

Hysteresis

On-time delay

Off-time delay

Output status

Display colour for alarms

Min response time

Output channels

(on request)

Over-range alarm, up alarm, down alarm, down alarm with start-up deactivation up alarm with latch, down alarm with latch

Adjustable from 0 to 100% of displayed electric range

0 to 100% of displayed range

0 to 255 s

0 to 255 s

Selectable: normally energized

/de-energized

Three available coloures

(green, amber, red) can be coupled to the alarm status (traffic-light function).

500 ms, with filter excluded, without alarm activation delay

1 with module BO R1

(relay output).

2, independent with module

Relay output BO R1, R2, R4

Relay output BO R5

Insulation

Open collector output

Range

Scaling factor

Accuracy

Response time

Termperature drift

Load: 20 mA output

10 V output

Insulation

Notes:

Insulation

Analogue output

Excitation output

BQ LSE Module

Voltage

BQ LSF Module

Voltage

BQTF1 Module

Voltage 1

Voltage 2

Insulation

4, independent with module

BO R4 (2 relay outputs +

2 open collector outputs).

BO R5 (4 relay outputs)

Type SPDT

AC 1: 8A, 250VAC

DC 12: 5A, 24VDC

AC 15: 2.5A, 250VAC

DC 13: 2.5A, 24VDC

Type SPST (NO)

AC 1: 5A, 250VAC

DC 12: 3A, 24VDC

AC 15: 1,5A, 250VAC

DC 13: 1,5A, 24VDC

4000 V

RMS output to measuring input,

4000 V

RMS output to power supply input.

NPN transistor type

V

ON

1.2 VDC/ max. 100 mA

V

OFF

30 VDC max.

By means of opto-couplers

4000 V

RMS output to measuring input

4000 V

RMS output to power supply input

(on request)

Module: BO AV

0 to 20 mADC, 0 to 10 VDC

Programmable within the entire retransmission range; allows to manage the retransmission of all the values from

0 to 20 mA / 0 to 10V

± 0.2% FS (@ 25°C ± 5°C)

10 ms

± 200 ppm/°C

700 Ω

10 k Ω

By means of opto-couplers

4000V rms output to measuring input

4000V rms output to power supply input

The two outputs cannot be used at the same time.

(on request)

13 VDC ±10%, max. 50 mA

25 VDC ±10%, max. 25 mA

8.2VDC ±10%, max 10mA.

13VDC ±10%, max 40mA.

25V

RMS output to measuring input

4000 V

RMS output to power supply input

Specifications are subject to change without notice UDM40 DS ENG 261110 5

UDM40

Software functions

Min / Max storage

Password

1st level

2nd level

Measurement selection

Automatic storage

(in the EEPROM) of the minimum and maximum measured value from the previous memory reset

Numeric code max 4 dgt

2 levels of data protection.

0 to 4999 completly protected.

5000 to 9999 access to programming is protected .

Alarm set-points are directly programmable from the measuring mode.

Depending on the module: measuring range and type of probe (resistance, RTD thermoresistance, TC thermocouple) or measuring type (TRMS or DC).

Function (only BQTFx)

Integration time selection

Displayed function of channel A and B:

F1: scaled value of channel A;

F2: 1/A;

F3: A-B;

F4: (A-B)/B*100;

F5: A/B;

F6: B/(A+B)+100;

F7: rotation sensing.

Automatic or from 100.0 to

999.9 ms only in the current and voltage measurement

(BQTFx excluded).

Scaling factors

Operating mode Electrical scale compression, displayed scale compression/expansion

(max. 2 without filter, up to

Electrical range

10 with filter)

Programmable within the whole measuring range

Programmable within the Decimal point position display range

Displayed range of the variable Programmable within the

Pulse per revolution

Input engineering unit display range

BQTFx only: programmable from 1 to 9999

BQTFx only: programmable among Hz, kHz, rpm, krpm,

Diagnostics

Burn-out:

TC

RTD

BQTFx

Digital filter

Filter operating range

Filtering coefficient

Scaling

Linearization

Points

Input range

Output range

UdmSoft

Supply Specifications

AC/DC voltage

DC voltage only

90 to 260V (standard)

18 to 60V (on request)

(24 to 48V AC/DC ± 25% according to UL)

10 to 28V (on request)

(12 to 24V DC ± 15% according to UL)

Energy consumption

6

30VA/12W (90 to 260V)

20VA/12W (18 to 60V)

7.5W (10 to 28V)

Specifications are subject to change without notice UDM40 DS ENG 261110 rph, krph

The display flashes when the limits of the display range are exceeded and the data are updated up to 20% of the rated display range.

Only temperature inputs

Opening of probe’s connection: EEE indication

Opening of probe’s connection: EEE indication probe’s short circuit:

-EEE indication.

Exceeding of frequency range: Err indication

0 to 9999

1 to 32

Selection of min value of the input range.

Selection of max value of the input range.

Selection of decimal point position.

Selection of min display value.

Selection of max display value.

Up to 16

Selectable by every single point

Selectable by every single point

Software for programming UDM40 by means of PC (Windows 95,

98se, ME, XP) by means of serial port RS485 and relevant connection cable.

The software is available in

English, Spanish, Italian,

German, French. See also

“Programming of

UDM40 by means of PC” .

UDM40

General Specifications

Operating temperature

Storage temperature

Insulation reference voltage

Insulation

Dielectric strength

Rejection

NMRR

CMRR

EMC

0° to 50°C (32° to 122°F)

(H.R. < 90% non-condensing)

-10° to 60°C (14° to 140°F)

(H.R. < 90% non-condensing)

300 V

RMS to ground

(500V input)

See table “Insulation between inputs and outputs”

4000 V

RMS for 1 minute

Safety Standards

Safety

Connections

Cable cross-section area

Housing

Dimensions

Material

Protection degree

40 dB, 40 to 60 Hz

100 dB, 40 to 60 Hz

Weight

EN61000-6-2, IEC61000-6-2

EN61000-6-3, IEC61000-6-3

Approvals

EN 61010-1, IEC 61010-1

Screw type

Max. 2.5 mm 2 ;

Min./Max. screws tightening torque: 0.4 Nm / 0.6 Nm

1/8 DIN, 48 x 96 x 105 mm

PC-ABS, self-extinguishing: UL 94 V-0

Front: IP67, NEMA12

Connections: IP20

520 g approx (included all modules and packing)

CE, UR, CSA

Excitation output

BQ LSF

Continuous LSF/LSE Max 30s

LSF/LSE

BQ LSE

BQ TF1

BQ TF1

(8.2V)

C on tin uo us

T

F1

(8

.2

M ax

3

V)

0s

T

F1

(8

.2

V)

Continuous TF1 Max

30s

TF1

TF1

Not allowed

Insulation between inputs and outputs

Meas.

inputs

Meas.

inputs

Relay

Output

Static

Output

Analogue

Output

Serial

Port

AUX p.supply

90-260VAC/

DC p..supply

18-60VAC/

DC p. supply

-

4kV

4kV

4kV

4kV

25V

4kV

4kV

Relay output

Static output

Analogue output

Serial

Port

AUX p.supply

90-260VAC/ 18-60VAC/

DC p. supply DC p.supply

4kV

-

2kV

4kV

4kV

4kV

4kV

4kV

4kV

2kV

-

4kV

4kV

4kV

4kV

4kV

4kV

4kV

4kV

-

4kV

4kV

4kV

4kV

4kV

4kV

4kV

4kV

-

4kV

4kV

4kV

25V

4kV

4kV

4kV

4kV

-

4kV

4kV

4kV

4kV

4kV

4kV

4kV

4kV

-

-

4kV

4kV

4kV

4kV

4kV

4kV

-

-

Specifications are subject to change without notice UDM40 DS ENG 261110 7

8

UDM40

Available modules Possible module combinations

Type

UDM40 main unit

DC/AC input: 200µA , 2mA, 20mA,

200mA, 2V, 20V

DC/AC input: 200µA , 2mA, 20mA,

200mA, 2V, 20V + excitation output

DC/AC input: 200mA, 2A, 5A,

20V, 200V, 500V

Input: 20Ω, 200Ω, 2kΩ, 20kΩ

TC: J-K-S-T-E, Pt100-250-500-

1000

Pulse signals input: 0.001Hz to

50kHz for DC signals

Pulse signals input: 0.001Hz to

50kHz for AC signals

Analogue output 0 to 20mA, 0 to

10VDC

N. of channels

1

1

1

1

1

2

2

1

Relay output 1

Ordering code

BD 40

BQ LSX

BQ LSE/

BQ LSF

BQ HSX

BQ TRX

BQ TRX

BQ TF1

BQ TF2

BO AV

BO R1

Relay output

Outputs: 2 relays + 2 open collectors

Relay output

RS485 Serial Port

RS232 Serial Port

Power supply 18 to 60V AC/DC

Power supply 90 to 260V AC/DC

Power supply 10 to28V DC

4

1

2

4

1

BO R2

BO R4

BO R5

BR SX

BR SY

BP L

BP H

BP 3

Basic Unit

Measuring inputs: LSX, LSE,

LSF, HSX, TRX, TF1, TF2

RS485 Serial port: SX

RS232 Serial port: SY

Analogue output: AV (*)

Relay outputs and/or open collector: R1, R2, R4, R5

Power supply: H, L, 3

Slot A Slot B Slot C Slot D

(*) Up to 1 module max.

Used calculation formulas

Only for TRMS Measurements

Instantaneous effective voltage (TRMS)

V

1

=

1 n

×

å

n

1

(

V

1

) i

2

Instantaneous effective current (TRMS)

A

1

=

1 n

×

å

n

1

(

A

1

) i

2

Specifications are subject to change without notice UDM40 DS ENG 261110

UDM40

Wiring diagrams

Process signal wiring diagrams

BQ LSX/LSE/LSF

Fig. 1

BQ LSX/LSE/LSF

Fig. 2 BQ LSE/LSF Fig. 3

BQ LSE

/LSF

+

˜

Voltage measurements

˜

-

˜

+

Fig. 4

BQ LSE

/LSF

Voltage measurements

4-wire connection to probe

-

+

+ Vdc

-

Fig. 5

BQ LSE

/LSF

Fig. 6

Voltage measurements

3-wire connection to probe

+

+ Vdc

-

Current measurements

4-wire connection to probe

-

+ Vdc

-

Current measurements

3-wire connection to probe

+

+ Vdc

-

BQ LSE

/LSF

Fig. 7

Wirings for high-level signals

BQ HSX

Fig. 8

BQ HSX

Fig. 9

+

+ Vdc

Current measurements

2-wire connection to probe Current measurements

˜

+

˜

-

Specifications are subject to change without notice UDM40 DS ENG 261110

Voltage measurements

˜

+

˜

-

9

UDM40

Wiring diagrams (cont.)

Wiring diagrams for temperature measurements

BQ TRX

Fig. 10

BQ TRX

Fig. 11

BQ TRX

Fig. 12

Temp. measur. from thermocouple Temp. measur. from thermoresistance

Wiring diagrams for frequency measurements

BQ TF1 Fig. 13 BQ TF1 Fig. 14

Resistance measurements

BQ TF1 Fig.15

ENCODER NPN/PNP

BQ TF1

NAMUR

Fig. 16 BQ TF1

NPN and contact

Fig. 17 BQ TF1 Fig. 18

PNP and contact

10

NPN/PNP TTL

Specifications are subject to change without notice UDM40 DS ENG 261110

UDM40

Wiring diagrams (cont.)

BQ TF1 Fig. 19

BQ TF2

Fig. 20

BQ TF2

Fig. 21

Auxiliary command

BQ TF2

Pick-up max 100VAC Max 500VAC

Fig. 22

Wiring diagrams for power supply

BP H: power supply BP L: power supply BP 3: power supply

Auxiliary command

F1= 630mA T

250V 5x20mm

Wiring diagrams of optional modules

F1= 3.15A T

250V 5x20mm

F1= 3.15A T

250V 5x20mm

BO AV: analogue output

(10V, 20mA DC)

BO R1: 1 relay output BO R2: 2 relay outputs

Specifications are subject to change without notice UDM40 DS ENG 261110

BO R5: 4 relay outputs

11

UDM40

Wiring diagrams of optional modules (cont.)

BO SY: RS232 direct connection to PC by means of COM port.

RS232 has no terminalization.

Vcc

BO R4: dual relay output + dual open collector output: the load resistances (Rc) must be designed so that the close contact current is lower than 100mA; the VDC voltage must be lower than or equal to 30VDC.

VDC: power supply output

Vo+: positive output (open collector transistor).

GND: ground (open collector transistor).

RS1,2,3...N

NON terminalized network

Terminalized network

BR SX: RS485 4-wire connection: additional devices provided with RS485 port (indicated as RS1,2,3...N) are connected in parallel. The termination of the serial port is carried out only on the last instrument of the network. The serial module is provided with a jumper for the termination of the RS485 network as shown in the figure above.

Note: particular types of cables or plants may require an external termination. For the network connections use twisted cable type AWG26.

Programming UDM40 by means of PC

To UDM

1

2

UDM40 is programmable by PC by means of the UdmSoft software (available on request). The user can program all parameters of UDM40 that will be subsequently uploaded and set in the instrument by the RS485 network (BR SX).

Should UDM40 be without the RS485 serial module, all programming parameters will be uploaded and set in the instrument by the RS232 auxiliary serial connection (1) located on the side of the measuring input module using the special connection cable (2) available on request, as shown in the figures on the left. It is also possible to program the instrument using the dot connector (1) by means of the HyperTerminal Windows functions of a PC.

Note: the RS232 auxiliary port IS NOT insulated from the measuring inputs.

To PC

12 Specifications are subject to change without notice UDM40 DS ENG 261110

UDM40

Front panel description

:

- to program values;

- to select functions;

- to scroll display pages.

: for special functions.

4 3 2 1

1. Key-pad

The programming of the configuration parameters and the display may be easily controlled by means of the 4 function keys.

: to enter the programming phase and to confirm the password.

2. Display

Instantaneous measurements:

- 4 digit (max display 9999).

Alphanumeric indications by means of LED display for:

- Display of configuration parameters;

- The measured variable.

3. Alarm status LED

Display any alarm condition

4. Engineering unit

The instrument is supplied with a complete set of self-sticking labels with the main engineering units.

Dimensions Engineering Units

11mm

105mm

48mm

96mm

45mm -0,3/+0,6

92mm -0,3/+0,8

Panel depth: 8mm.

Specifications are subject to change without notice UDM40 DS ENG 261110 13

UDM40

Modules

Input modules Output modules

Scale 1:1

BQ LSX, BQ LSE, BQ

LSF, BQ HSX, BQ TRX,

BQ TF1, BQ TF2

Measuring inputs

BO AV

Single analogue output 10V, 20mA DC

Output modules

BO R1

Single relay output

BO R2

Dual relay output

BO R4

Dual relay output +

Dual open collector

BO R5

4 relay outputs

Serial port modules Power supply modules

14

BR SX

RS485 Serial port

BR SY

RS232 Serial port

BP H

Power supply:

60 to 260V AC/DC

BP L

Power supply:

18 to 60V AC/DC

BP 3

Power supply:

10 to 28V DC

Specifications are subject to change without notice UDM40 DS ENG 261110