ClimateMaster ATP32H01S and ASUB01 User manual

ClimateMaster ATP32H01S and ASUB01 User manual
Q7300A,C,D,G
Series 2000 Commercial
Thermostat Subbases
INSTALLATION INSTRUCTIONS
APPLICATION
The Q7300 Thermostat Subbases are used with T7300
Thermostats to provide electronic control of commercial
24 Vac single or multistage heat pump or conventional
heating and cooling systems. Select models have terminals for LEDs and remote temperature sensors. Refer to
Table 1. All Q7300 Thermostat Subbases require a
common wire to the supply power.
Table 1. Description of Q7300 Subbases.
Maximum Stagesa,b
Model
Applications
Thermostat Required
Heat
Cool
Q7300A
Conventional
T7300D, F
2
2
Hookup Drawing
9-12
Q7300C
Heat Pump
T7300E, F
3
2
13-15
Q7300D
Heat Pump
T7300E, F
3
2
16
Q7300G
Conventional
T7300D, F
3
3
17
aDepends
b
on model.
All subbases are down selectable and can be configured to control fewer stages than the maximum allowed.
RECYCLING NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash
Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of the old thermostat.
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
® U.S. Registered Trademark
Copyright © 1998 Honeywell Inc. •
• All Rights Reserved
Location
Subbase without Remote-Mounted
Temperature Sensor
Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
See Fig. 1.
Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
Subbase with Remote-Mounted
Temperature Sensor(s)
If only the remote-mounted temperature sensor(s) is used
to sense and control room temperature, then install the
thermostat in an area that is accessible for setting and
adjusting the temperature and settings.
If both the subbase and remote-mounted temperature
sensor(s) are used to sense and control room temperature, then install the subbase about 5 ft above the floor in
an area with good air circulation.
X-XX UL
62-0127-3
Q7300A,C,D,G SERIES 2000 COMMERCIAL THERMOSTAT SUBBASES
YES
NO
NO
5 FEET
(1.5 METERS)
NO
M4823A
Fig. 1. Typical location of thermostat or remote-mounted sensor.
Install the remote-mounted sensor(s) about 5 ft (1.5m)
above the floor in an area with good air circulation at
average temperature. See Fig. 1.
SUBBASE
T
T
T7047C
Do not mount the sensor(s) where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
T
T
T7047G
T
T7047C
T
If more than one remote sensor is required, they must be
arranged in a temperature averaging network consisting of
two, three, four, five or nine sensors. See Fig. 2 through 6.
M4839
IMPORTANT
To avoid electrical interference, which can cause
erratic performance, keep wiring runs as short as
possible and do not run thermostat wires
adjacent to the line voltage electrical distribution
systems. Use shielded cable (Belden type 8762
or equivalent for 2-wire and Belden type 8772 or
equivalent for 3-wire). The cable shield must be
grounded only at the controlled equipment case.
Fig. 3. Two T7047C Sensors and one T7047G Sensor
providing temperature averaging network for
T7300/Q7300 Thermostat/Subbase.
SUBBASE
T
T7047G
T
T7047C
T
SUBBASE
T
T
T
T7047C
T
T
T
T
T7047G
T
T
T7047C
T
T
T7047C
T
T
T
T
M4838
M4840
Fig. 2. Two T7047G Sensors providing
temperature averaging network for
T7300/Q7300 Thermostat/Subbase.
62-0127—3
Fig. 4. Four T7047C Sensors providing
temperature averaging network for
T7300/Q7300 Thermostat/Subbase.
2
Q7300A,C,D,G SERIES 2000 COMMERCIAL THERMOSTAT SUBBASES
SUBBASE
T
T
T7047G
WALL
T7047G
WIRES
THROUGH WALL
T
T
T
T
T7047G
WALL
ANCHORS
(2)
T7047G
T
T
T7047G
T
T
T
T
M4841
MOUNTING
HOLES
Fig. 5. Five T7047G Sensors providing
temperature averaging network for
T7300/Q7300 Thermostat/Subbase.
MOUNTING
SCREWS
M10237
LEDS
SUBBASE
T
T7047C
T
T7047C
T
T
T7047C
T
T
T
WIRING SUBBASE
T7047C
T
T7047C
T
Fig. 7. Mounting the subbase.
T
T
All wiring must comply with local electrical codes and
ordinances. Follow equipment manufacturer wiring
instructions when available. Refer to Fig. 9 through 17 for
typical hookups. A letter code is located near each
terminal for identification.
T7047C
T
T
CAUTION
T
Electrical Shock Hazard.
Power source can shock.
Disconnect power before wiring to prevent
electrical shock or equipment damage.
T7047C
T
T7047C
T
T
T7047C
T
T
1. Loosen the terminal screws on the subbase and
connect the system wires. See Fig. 8.
T
IMPORTANT
Use 18-gauge, solid-conductor color-coded
thermostat cable for proper wiring. If using 18gauge stranded wire, no more than ten wires can
be used. Do not use larger than 18-gauge wire.
M4842
Fig. 6. Nine T7047C Sensors providing
temperature averaging network for
T7300/Q7300 Thermostat/Subbase.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
4. Plug the hole with nonflammable insulation to
prevent drafts from affecting the thermostat.
Mounting Subbase
The subbase mounts horizontally on the wall or a 2 in. x 4 in.
wiring box. Position the subbase horizontally on the wall or
on a 2 in. x 4 in. wiring box.
1. Position and level the subbase or wallplate (for
appearance only). The thermostat functions properly
even when not level.
2. Use a pencil to mark the mounting holes. See Fig. 7.
3. Remove the subbase or wallplate from the wall and
drill two 3/16 in. (5 mm) holes in the wall (if drywall)
as marked. For firmer material such as plaster or
wood, drill two 7/32 in. (5.5 mm) holes. Gently tap
anchors (provided) into the drilled holes until flush
with the wall.
4. Position the subbase over the holes, pulling wires
through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.
FOR WRAPAROUND
INSERTION STRIP
7/16 IN. (11 MM).
FOR STRAIGHT
INSERTION STRIP
5/16 IN. (8 MM).
M4826
Fig. 8. Proper wiring technique.
3
62-0127—3
Q7300A,C,D,G SERIES 2000 COMMERCIAL THERMOSTAT SUBBASES
Typical Wiring Hookups
SUBBASE
RC
Y1
G
X
W1
X4
RH
2
X3
X1
C5
C4
C3
C2
C1
T
T
CA5
CA4
CA3
CA2
CA1
T
T
4
COMPRESSOR
CONTACTOR
EQUIPMENT
MONITOR 2
HEAT
RELAY
FAN
RELAY
T7147 REMOTE COMFORT ADJUST MODULE
GND
EQUIPMENT
MONITOR 1
3
1
L1
(HOT)
L1
(HOT)
L2
L2
1
HEATING
TRANSFORMER
COOLING
TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER.
3
CONNECT GND TO EARTH GROUND.
4
INSTALL FIELD JUMPER BETWEEN X4 AND X TO POWER LEDS FROM SYSTEM TRANSFORMER.
M4939B
Fig. 9. Typical hookup of T7300D,F/Q7300A in one-stage heat and
one-stage cool conventional system with two transformers.
SUBBASE
RC
Y1
G
X
W2
W1
RH
2
COMPRESSOR
CONTACTOR 1
HEAT
RELAY 2
FAN
RELAY
HEAT
RELAY 1
1
L1
(HOT)
L1
(HOT)
L2
L2
1
HEATING
TRANSFORMER
COOLING
TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED
ON A SYSTEM WITH ONE TRANSFORMER.
M10230
Fig. 10. Typical hookup of T7300D,F/Q7300A in two-stage heat and
one-stage cool conventional system with two transformers.
62-0127—3
4
Q7300A,C,D,G SERIES 2000 COMMERCIAL THERMOSTAT SUBBASES
SUBBASE
RC
Y1
G
Y2
X
O
W2
B
W1
RH
2
COMPRESSOR
CONTACTOR 1
1
COMPRESSOR
CONTACTOR 2
COOL
DAMPER
FAN
RELAY
L1
(HOT)
HEAT
RELAY 2
HEAT
RELAY 1
HEAT
DAMPER
1
L1
(HOT)
L2
L2
HEATING
TRANSFORMER
COOLING
TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER.
M10236
Fig. 11. Typical hookup of T7300D,F/Q7300A in two-stage heat and
two-stage cool conventional system with two transformers.
SUBBASE
2
AS
AS
RC
5
G
Y1
Y2
X
3
W2
W1 RH
X4
X3
X1
A2 A3 C5
A1
C4
C2
C3
C1
T
T
7
COMPRESSOR
CONTACTOR 1
DISCHARGE
AIR
SENSOR
HEAT
RELAY 2
EQUIPMENT
ECONOMIZER
MONITOR 2
FAN
RELAY
6
COMPRESSOR
CONTACTOR 2
EQUIPMENT
CA2 CA1
CA5
CA4 CA3
T
T
T7147 REMOTE COMFORT ADJUST MODULE
GND
MONITOR 1
1
HEAT
RELAY 1
L1
(HOT)
L2
L2
1
1
4
L1
(HOT)
HEATING
TRANSFORMER
COOLING
TRANSFORMER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A
SYSTEM WITH ONE TRANSFORMER.
3
USE A1 AND A2 WHEN THE CONTACTS SHOULD BE NORMALLY
CLOSED IN OCCUPIED MODE. USE A2 AND A3 WHEN THE
CONTACTS SHOULD BE NORMALLY OPEN IN OCCUPIED MODE.
4
CONNECT GND TO EARTH GROUND.
5
INSTALL FIELD JUMPER BETWEEN X4 AND X TO POWER LEDS
FROM SYSTEM TRANSFORMER.
6
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
7
DISCHARGE AIR SENSOR IS ONLY COMPATIBLE WITH T7300F
THERMOSTAT.
M4945B
Fig. 12. Typical hookup of T7300D,F/Q7300A in two-stage heat and
two-stage cool conventional system with two transformers.
5
62-0127—3
Q7300A,C,D,G SERIES 2000 COMMERCIAL THERMOSTAT SUBBASES
SUBBASE
5
AS
3
X
AS
Y1
E
O
G
B
W2
X4
R
X3
X1
A1 A2
C5
C4
C2
C3
C1
T
T
6
FAN
RELAY
DISCHARGE
AIR
SENSOR
EQUIPMENT
CA5 CA4
CA3 CA2 CA1 T
T
T7147 REMOTE COMFORT ADJUST MODULE
GND
MONITOR 2
COMPRESSOR
CONTACTOR 1
HEAT
RELAY 2
EM. HT.
RELAY
EQUIPMENT
MONITOR 1
4
2
ECONOMIZER
COOL
CHANGEOVER
VALVE
1
HEAT
CHANGEOVER
VALVE
L1
(HOT)
L2
TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
3
USE A1 AND A2 WHEN THE CONTACT SHOULD BE NORMALLY CLOSED IN OCCUPIED MODE.
4
CONNECT GND TO EARTH GROUND.
5
INSTALL FIELD JUMPER BETWEEN X4 AND X TO POWER LEDS FROM SYSTEM TRANSFORMER.
6
DISCHARGE AIR SENSOR IS ONLY COMPATIBLE WITH T7300F THERMOSTAT.
M4946B
Fig. 13. Typical hookup of T7300E,F/Q7300C in two-stage heat and one-stage cool heat pump system.
SUBBASE
5
AS
AS
X
Y2
Y1
O
G
E
W1
B
X4
R
X3
X1
3
A1 A2
C5
C4
C3
C2
C1
T
T
6
DISCHARGE
AIR
SENSOR
AUX.
HEAT
COMPRESSOR
CONTACTOR 2
EQUIPMENT
MONITOR 2
FAN
RELAY
COMPRESSOR
CONTACTOR 1
CA2
CA1
CA4
CA3
T
T
T7147 REMOTE COMFORT ADJUST MODULE
GND
CA5
EQUIPMENT
EM. HT.
RELAY
COOL
CHANGEOVER
VALVE
MONITOR 1
HEAT
CHANGEOVER
VALVE
ECONOMIZER
2
1
L1
(HOT)
4
L2
TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS.
3
USE A1 AND A2 WHEN THE CONTACTS ARE NORMALLY CLOSE IN OCCUPIED MODE.
4
CONNECT GND TO EARTH GROUND.
5
INSTALL FIELD JUMPER BETWEEN X4 AND X POWER LEDS FROM SYSTEM TRANSFORMER.
6
DISCHARGE AIR SENSOR IS ONLY COMPATIBLE WITH T7300F THERMOSTAT.
M4947B
Fig. 14. Typical hookup of T7300E,F/Q7300C in three-stage heat and two-stage cool heat pump system.
62-0127—3
6
Q7300A,C,D,G SERIES 2000 COMMERCIAL THERMOSTAT SUBBASES
SUBBASE
4
X
6
L
Y
2
O
Y2
E
G
3
W2
W3
X4
X1 X2
R
HEAT
RELAY 2
COMPRESSOR
CONTACTOR 2
EM.
MODE
B
C5 C4
C3
C2
C1
T
T
EQUIPMENT
MONITOR 2
EM. HT.
RELAY
COMPRESSOR
CONTACTOR 1
HEAT
RELAY 3
FAN
RELAY
COOL
CHANGEOVER
VALVE
CA5 CA4 CA3 CA2 CA1
EQUIPMENT
T
T7147 REMOTE COMFORT
ADJUST MODULE
T
GND
MONITOR 1
HEAT
CHANGEOVER
VALVE
5
1
L1
(HOT)
L2
TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
4
INSTALL FIELD JUMPER BETWEEN X4 AND X POWER LEDS
FROM SYSTEM TRANSFORMER.
2
EM. MODE IS ON CONTINUOUSLY IN EMERGENCY HEAT MODE.
24 VAC ARE PRESENT DURING EMERGENCY HEAT MODE.
5
CONNECT GND TO EARTH GROUND.
6
JUMPER W2 TO Y2 FOR SECOND COMPRESSOR. W3 IS AUXILIARY HEAT.
3
EM. HT. RELAY CYCLES IN EMERGENCY HEAT MODE.
M4940B
Fig. 15. Typical hookup of T7300E,F/Q7300C in three-stage heat and two-stage cool heat pump system.
SUBBASE
4
AS
AS X
Y1
G
Y2
E
W2
W3
W1 R
X4
X3
X1
2
A2 A3
A1
C5
C4
C3
C2
C1
T
T
6
DISCHARGE
AIR
SENSOR
COMPRESSOR
CONTACTOR 1
EM. HT.
RELAY
HEAT
RELAY 2
EQUIPMENT
ECONOMIZER
MONITOR 2
5
FAN
RELAY
COMPRESSOR
CONTACTOR 2
EQUIPMENT
HEAT
RELAY 3
CA5 CA4 CA3 CA2 CA1
T
T
T7147 REMOTE COMFORT ADJUST MODULE
GND
MONITOR 1
3
1
HEAT
RELAY 1
L1
(HOT)
L2
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
TRANSFORMER
2
USE A1 AND A2 WHEN THE CONTACTS SHOULD BE NORMALLY CLOSED IN OCCUPIED MODE. USE A2 AND A3 WHEN THE
CONTACTS SHOULD BE NORMALLY OPEN IN OCCUPIED MODE.
3
CONNECT GND TO EARTH GROUND.
4
INSTALL FIELD JUMPER BETWEEN X4 AND X TO POWER LEDS FROM SYSTEM TRANSFORMER.
5
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
6
DISCHARGE AIR SENSOR IS ONLY COMPATIBLE WITH T7300F THERMOSTAT.
M4948B
Fig. 16. Typical hookup of T7300E,F/Q7300D in three-stage heat and two-stage cool heat pump system.
7
62-0127—3
Q7300A,C,D,G SERIES 2000 COMMERCIAL THERMOSTAT SUBBASES
SUBBASE
5
AS
AS
RC
Y1
G
Y2
Y3
X
W3
W2
X4
W1 RH
X3
X1
3
A2 A3
A1
C5
C4
C3
C2
C1
T
COMPRESSOR
CONTACTOR 1
DISCHARGE
AIR
SENSOR
HEAT
RELAY 2
COMPRESSOR
CONTACTOR 2
ECONOMIZER
EQUIPMENT
MONITOR 2
FAN
RELAY
COMPRESSOR
CONTACTOR 3
6
CA2
CA1
T
CA5
CA4
CA3
T7147 REMOTE COMFORT ADJUST MODULE
EQUIPMENT
T
GND
MONITOR 1
HEAT
RELAY 3
1
HEAT
RELAY 1
L1
(HOT)
4
L1
(HOT)
L2
L2
1
HEATING
TRANSFORMER
COOLING
TRANSFORMER
1
T
2
7
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A
SYSTEM WITH ONE TRANSFORMER.
3
USE A1 AND A2 WHEN THE CONTACTS SHOULD BE NORMALLY CLOSED
IN OCCUPIED MODE. USE A2 AND A3 WHEN CONTACTS
SHOULD BE NORMALLY OPEN IN OCCUPIED MODE.
4
CONNECT GND TO EARTH GROUND.
5
INSTALL FIELD JUMPER BETWEEN X4 AND X TO POWER LEDS
FROM SYSTEM TRANSFORMER.
6
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
7
DISCHARGE AIR SENSOR IS ONLY COMPATIBLE WITH T7300F
THERMOSTAT.
M4949B
Fig. 17. Typical hookup of T7300D,F/Q7300G in three-stage heat and three-stage cool conventional system.
A. ENGAGE TABS AT TOP OF THERMOSTAT AND SUBBASE OR WALLPLATE.
Mounting Thermostat on Subbase
Mount the thermostat on the subbase after the subbase is
installed.
1. Engage the tabs at the top of the thermostat and
subbase. See Fig. 18.
2. Press lower edge of the case to latch.
NOTE: To remove the thermostat from the wall,
first pull out at the bottom of the thermostat; then remove the top.
IMPORTANT
Refer to the thermostat installation instructions for
Installer Setup, Settings, Installer System Test
and Troubleshooting information.
B. PRESS LOWER EDGE OF CASE TO LATCH.
M4824A
Fig. 18. Mounting thermostat on subbase.
Home and Building Control
Honeywell
1985 Douglas Drive
Minneapolis, MN 55422-4386
Home and Building Control
Honeywell Limited/Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario
M1V 4Z9
62-0127—3 J.H. Rev. 11-98 Printed in Taiwan R.O.C.
8
www.honeywell.com/yourhome
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement