Product Brochure
Eaton 5P Tower UPS
Enterprise class battery backup in a space-saving tower design for network closets and computer rooms.
Space-saving: The Eaton 5P tower provides premium
Intelligent Power Software Suite
protection while conserving value space in multiple, slim
tower designs.
By integrating the software with the Eaton 5P, you can:
Efficiency: The 5P provides industry leading efficiency of
•
up to 99 percent.
Manageability:
•฀UPS฀management: By integrating Eaton’s free
Intelligent Power® Software Suite, you can monitor and
manage the power devices on your network.
•฀Energy฀metering:฀The 5P meters energy consumption
at the UPS level.
LCD display: Eaton’s next-generation LCD offers a
•
•
Seamlessly integrate with VMware’s vCenter Server™
virtualization management solution, as well as
virtualization platforms such as Citrix® XenServer,
Microsoft SCVMM™, Red Hat® and other Xen® open
source platforms
Initiate live migration of virtual machines (VM) to
automatically and transparently migrate VMs during
power disruptions to unaffected devices with systems
such as VMware vMotion™ and Microsoft Live Migration
Execute graceful shutdown of computers and virtual
machines/servers during an extended power outage
graphical interface which provides all critical UPS
information in a single screen view.
To learn more, please visit: Eaton.com/intelligentpower
More power: The 5P protects more devices by providing
20 percent more wattage compared to traditional UPSs.
Services and support
Battery life: Eaton’s exclusive ABM® technology increases
battery service life by 50 percent.
ENERGY STAR®: 5P 2200 and 3000 VA
tower models are ENERGY STAR® qualified.
ENERGY STAR helps consumers save
money and protect the environment through
energy efficient products and practices.
Eaton provides product support 24 hours a day, 7 days a
week. From battery replacement to full UPS service plans,
Eaton has one of the top service models in the industry.
Three-year warranty
The 5P warranty covers both the UPS and the batteries
for three years. No other manufacturer in the industry
offers as comprehensive a warranty.
5P TOWER MODEL SELECTION GUIDE*
Catalog number
Rating (VA/watts)
Input connection
Output receptacles
Dimensions (H x W x D), in
Net weight, lb
5P750
750/600
5-15P
(8) 5-15R
9.1 x 5.9 x 13.6
22.7
5P1000
1000/770
5-15P
(8) 5-15R
9.1 x 5.9 x 13.6
24.4
5P1500
1440/1100
5-15P
(8) 5-15R
9.1 x 5.9 x 17.5
35.3
5P2200
1950/1920
5-20P
(4) 5-20R, (4) 5-15R
3.4 x 17.4 x 20.6
65.0
5P3000
3000/2700
L5-30P
(6) 5-20R, (1) L5-30R
3.4 x 17.4 x 25.4
87.0
Tower 120V 50/60 Hz models
Tower 208 or 230V 50/60 Hz models
5P850G
850/600
C14
(6) C13
9.1 x 5.9 x 13.6
21.9
5P1550G
1550/1100
C14
(8) C13
9.1 x 5.9 x 17.5
35.2
*Due฀to฀continuous฀product฀improvement฀programs,฀all฀speciications฀are฀subject฀to฀change฀without฀notice.฀Please฀visit฀Eaton.com/5P฀to฀view฀complete฀and฀updated฀product฀speciications.
Additional options
Connectivity
Network Card-MS
Relay / Serial Interface Card
Environmental Monitoring Probe
What’s in the box
Catalog number
For use with
NETWORK-MS
All models
RELAY-MS
All models
116750224-001
All models (requires Network Card-MS)
5P750 rear panel
•฀User฀manual฀CD฀
•฀฀Intelligent฀Power฀฀
Software฀Suite฀CD฀
•฀฀Quick฀start฀guide฀
•฀USB฀cable฀
•฀RS-232฀cable฀
G models only฀
•฀฀2฀IEC-to-IEC฀jumper฀
cables฀
2200/3000 models only
•฀฀Tower฀pedestals฀and฀
Phillips฀head฀screw฀
driver
5P2200 rear panel
Communication
slot with optional
network card
Communication
slot with optional
network card
RS-232 port
USB port
Remote power
off/Remote on-off
connector
(8) 5-15R
output receptacles
RS-232 port
USB port
Two individually
controlled groups
of outlets
Remote power
off/Remote on-off
connector
Input line cord
with 5-15P
Input line cord
with 5-15P
Two individually
controlled groups
of outlets
(8) 5-15R
output receptacles
To interact with the Eaton 5P Tower UPS,
please visit: Eaton.com/5P
Eaton
Electrical Sector
1000 Eaton Boulevard
Cleveland, OH 44122 USA
Eaton.com
Powerquality.eaton.com
©2013 Eaton
All Rights Reserved
Printed in USA
BR153008EN
May 2013
Eaton is a registered trademark of Eaton
Corporation.
All other trademarks are property of their
respective owners.
ENERGY STAR and the ENERGY STAR
mark are registered U.S. marks. ENERGY
STAR is a registered mark owned by the
U.S. government.
Product Brochure
Eaton 5P Rackmount UPS
Enterprise class battery backup for network closets and small data centers.
Flexibility: The Eaton 5P is available in space saving 1U
and 2U rackmount configurations.
Intelligent Power Software Suite
Efficiency: The 5P provides industry leading efficiency of
•
By integrating software with the Eaton 5P, you can:
up to 99 percent.
Manageability:
•฀UPS฀management: By integrating Eaton’s free
Intelligent Power® Software Suite, you can monitor and
manage the power devices on your network.
•฀Energy฀metering:฀The 5P meters energy consumption
at the UPS level.
LCD display: Eaton’s next-generation LCD offers a
graphical interface which provides all critical UPS
information in a single screen view.
More power: The 5P protects more devices by providing
•
•
Seamlessly integrate with VMware’s vCenter Server™
virtualization management solution, as well as
virtualization platforms such as Citrix® XenServer,
Microsoft SCVMM™, Red Hat® and other Xen® open
source platforms
Initiate live migration of virtual machines (VM) to
automatically and transparently migrate VMs during
power disruptions to unaffected devices with systems
such as VMware vMotion™ and Microsoft Live Migration
Execute graceful shutdown of computers and virtual
machines/servers during an extended power outage
To learn more, please visit: Eaton.com/intelligentpower
20 percent more wattage compared to traditional UPSs.
Services and support
Battery life: Eaton’s exclusive ABM® technology increases
Eaton provides product support 24 hours a day, 7 days a
week. From battery replacement to full UPS service plans,
Eaton has one of the top service models in the industry.
battery service life by 50 percent.
ENERGY STAR®: 5P 2U rackmount models
are ENERGY STAR® qualified. ENERGY STAR
helps consumers save money and protect
the environment through energy efficient
products and practices.
Three-year warranty
The 5P warranty covers both the UPS and the batteries
for three years. No other manufacturer in the industry
offers as comprehensive a warranty.
5P RACKMOUNT MODEL SELECTION GUIDE*
Catalog number
Rating (VA/watts)
Input connection
Output receptacles
Dimensions (H x W x D), in
Net weight, lb
65.0
2U Rackmount, 120V, 50/60 Hz models**
5P1500RT
1440/1440
5-15P
(8) 5-15R
3.4 (2U) x 17.4 x 20.6
5P2200RT
1950/1920
5-20P
(4) 5-15R, (4) 5-20R
3.4 (2U) x 17.4 x 20.6
65.0
5P3000RT
3000/2700
L5-30P
(3) 5-15R, (3) 5-20R, (1) L5-30R
3.4 (2U) x 17.4 x 25.4
87.0
1U Rackmount, 120V, 50/60 Hz models
5P550R
550/420
5-15P
(5) 5-15R
1.7 (1U) x 17.2 x 14.3
17.8
5P750R
750/600
5-15P
(5) 5-15R
1.7 (1U) x 17.2 x 20.0
30.6
5P1000R
1000/770
5-15P
(5) 5-15R
1.7 (1U) x 17.2 x 20.0
32.5
5P1500R
1440/1100
5-15P
(5) 5-15R
1.7 (1U) x 17.2 x 21.8
43.5
1U Global Rackmount, 208/230V, 50/60 Hz models
5P850GR
850/600
C14
(4) C13
1.7 (1U) x 17.2 x 20.0
30.4
5P1550GR
1550/1100
C14
(6) C13
1.7 (1U) x 17.2 x 21.8
42.7
*Due฀to฀continuous฀product฀improvement฀programs,฀all฀speciications฀are฀subject฀to฀change฀without฀notice.฀Please฀visit฀Eaton.com/5Prm฀to฀view฀complete฀and฀updated฀product฀speciications.
**Catalog฀numbers฀that฀end฀in฀RT฀can฀be฀used฀in฀both฀rackmount฀or฀tower฀conigurations.
Options
Connectivity
Network Card-MS
Relay / Serial Interface Card
Catalog number
For use with
NETWORK-MS
All models
What’s in the box
RELAY-MS
All models
116750224-001
All models (requires Network Card-MS)
1U two-post rail kit (optional)
RK2PA
All 1U models except 5P550R
2U two-post rail kit (optional)
103007018-5591
All 2U models
EHBPL1500R-PDU1U
5P550R, 5P750R, 5P1000R,
5P1500R, 5P1500RT
EHBPL2000R-PDU1U
5P2200RT
EHBPL3000R-PDU1U
5P3000RT
Environmental Monitoring Probe
Mounting hardware
Power distribution & bypass
HotSwap Maintenance Bypass
(MBP) The฀HotSwap฀Maintenance฀
Bypass฀allows฀you฀to฀exchange฀or฀
service฀the฀UPS฀without฀shutting฀
down฀the฀connected฀load
5P 2U rear panel
•฀User฀manual฀CD
•฀฀Tower฀pedestals฀฀
•฀฀Intelligent฀Power฀฀
(2U฀models฀only)
Software฀Suite฀CD
•฀฀Phillips฀head฀screw฀
•฀Quick฀start฀guide
driver฀(2U฀models฀only)
•฀฀Four-post฀rail฀kit฀
G models only฀
(5P550R฀ears฀only)
•฀฀2฀IEC-to-IEC฀jumper฀
•฀฀Extra฀wall฀mounting฀ear฀
cables฀
(5P1500R฀&฀5P1550GR)
•฀฀Output฀cable฀locking฀
•฀USB฀cable
system฀
•฀RS-232฀cable
•฀฀Input฀cable฀locking฀
system฀
5P 1U rear panel
5-15P input
plug
RS-232
port
Communication
slot with optional
network card
(8) 5-15R
output receptacles
USB port
Remote power
off/Remote on-off
connector
Two individually
controlled groups
of outlets
USB port
RS-232
port
Remote power
off/Remote on-off
connector
(5) 5-15R
output receptacles
Two individually
controlled groups
of outlets
Communication
slot with optional
network card
To interact with the Eaton 5P rackmount UPS,
please visit: Eaton.com/5Prm
Eaton
Electrical Sector
1000 Eaton Boulevard
Cleveland, OH 44122 USA
Eaton.com
Powerquality.eaton.com
©2013 Eaton
All Rights Reserved
Printed in USA
BR153009EN
May 2013
Eaton is a registered trademark of Eaton
Corporation.
All other trademarks are property of their
respective owners.
ENERGY STAR and the ENERGY STAR
mark are registered U.S. marks. ENERGY
STAR is a registered mark owned by the
U.S. government.
Product Brochure
Eaton 5PX UPS
Enterprise class battery backup with extended runtime designed for virtualized environments.
5PX features and benefits:
Extended Runtime: Add up to four extended battery
modules for maximum runtime.
Virtualization-ready: Available in convenient bundles with
a network card and management software to make going
virtual simple.
Efficiency: Provides industry leading efficiency of up to
99 percent.
Manageability:
•฀ Energy฀metering: The 5PX meters energy consumption
right down to the outlet segments.
No other UPS in the industry offers this capability.
•฀ UPS฀management:฀By integrating Eaton’s free
Intelligent Power® Software Suite, you can monitor and
manage the power devices on your network.
LCD display: Eaton’s next generation LCD offers a
graphical interface which provides all critical UPS
information in a single screen view.
More power: Protects more devices by providing 28
percent more wattage compared to traditional UPSs.
Battery life: Eaton’s exclusive ABM® technology increases
battery service life by 50 percent.
Intelligent Power Software Suite
By integrating the suite with the Eaton 5PX, you can:
•฀ Seamlessly฀integrate฀with฀VMware’s฀vCenter฀Server™
virtualization management solution, as well as
virtualization platforms such as Citrix® XenServer,
Microsoft฀SCVMM™, Red Hat® and other Xen® open
source platforms
•฀ Initiate฀live฀migration฀of฀virtual฀machines฀(VM)฀to฀
automatically฀and฀transparently฀migrate฀VMs฀during฀
power disruptions to unaffected devices with systems
such฀as฀VMware฀vMotion™ and Microsoft Live Migration
•฀ Integrate฀with฀VMware฀vCenter฀Site฀Recovery฀Manager฀฀
To learn more, please visit:
Eaton.com/intelligentpower
Services and support฀
Eaton provides product support 24 hours a day, 7 days a
week. From battery replacement to full UPS service plans,
Eaton has one of the top service models in the industry.
Three-year warranty
The 5PX warranty covers both the UPS and the batteries
for three years. No other manufacturer in the industry
offers as comprehensive a warranty.
The Eaton 5PX is an ENERGY STAR® qualified UPS.
ENERGY STAR is intended to help consumers save
money and protect the environment through energy
efficient products and practices.
5PX MODEL SELECTION GUIDE*
Catalog Number
Rating (VA/Watts)
Input connection
120V, 50/60 Hz
5PX1000RT
1000/1000
5-15P
5PX1500RT
1440/1440
5PX2200RT
1950/1920
5-20P
5PX3000RT2U
3000/2700
L5-30P
5PX3000RT3U
208V/230V, 50/60 Hz
5PX1500iRT
1500/1350
C14-10A
5PX2200iRT
2200/1980
C20-16A
5PX3000iRT2U
3000/2700
120V, 50/60 Hz Virtualization-ready bundles with Network Card-MS
5PX1500RTN
1440 / 1440
5-15P
5PX2200RTN
1950 / 1920
5-20P
5PX3000RTN
3000 / 2700
L5-30P
208/230V, 50/60 Hz Virtualization-ready bundles with Network Card-MS
5PX3000iRTN
3000 / 2700
C20
Extended Battery Modules
DC voltage
For use with
5PXEBM48RT
48V
All 1000, 1500 & 2200 models
5PXEBM72RT2U
All 3000 2U models
72V
5PXEBM72RT3U
All 3000 3U models
Output receptacles
Dimensions (H x W x D), in
(8) 5-15R
Net weight, lb
62
65
65
87
86
3.4 x 17.4 x 20.6
(8) 5-20R
3.4 x 17.4 x 25.4
5.1 x 17.4 x 19.6
(1) L5-30R
(6) 5-20R
(1) C19-16A
(8) C13-10A
(8) C13-10A
3.4 x 17.4 x 25.4
61
63
84
(8) 5-15R
(8) 5-20R
(6) 5-20R, (1) L5-30R
3.4 x 17.4 x 20.6
3.4 x 17.4 x 20.6
3.4 x 17.4 x 25.4
65
65
87
(8) C13, (1) C19
Max qty / UPS
3.4 x 17.4 x 25.4
Dimensions (H x W x D), in
3.4 x 17.4 x 20.6
3.4 x 17.4 x 25.4
5.1 x 17.4 x 19.6
84
Net weight, lb
72
102
98
4
3.4 x 17.4 x 20.6
*Due to continuous product improvement programs, all specifications are subject to change without notice. Please visit Eaton.com/5PX to view complete and updated product specifications.
Additional Options
Connectivity
Network Card-MS
Environmental Monitoring Probe
Power Distribution & Bypass
HotSwap Maintenance Bypass (MBP)
The HotSwap Maintenance Bypass allows
you to exchange or service the UPS without
shutting down the connected load
Catalog Number
For use with
What’s in the box
NETWORK-MS
116750224-001
All models*
All models (requires Network Card-MS)
EHBPL1500R-PDU1U
All 1000 & 1500 models
EHBPL2000R-PDU1U
All 2200 models
EHBPL3000R-PDU1U
All 3000 models
103007018-5591
All models
•฀Tower฀pedestals
•฀Four-post฀rail฀kit
•฀User฀manual฀CD
•฀฀Intelligent฀Power฀Software฀Suite฀CD
•฀Quick฀start฀guide
•฀USB฀cable
•฀฀RS-232฀serial฀cable
•฀฀Phillips฀Head฀screw฀driver฀
•฀฀2฀IEC฀to฀IEC฀jumper฀cables฀
(208V/230V models)
Mounting Hardware
2-post rail kit
* Network Card-MS is included with catalog numbers 5PX1500RTN, 5PX2200RTN, 5PX3000RTN and 5PX3000iRTN.
5PX UPS rear panel
(1000 & 1500 VA)
RS-232
port
USB port
EBM battery
connector
(8) 5-15R
output receptacles
5-15P input
plug
Communication
slot with optional
Network Card
Remote Power Off/
Remote On Off connector
EBM RJ-11
connector
Site wiring
fault indicator
Battery runtime
You can get up to five hours of battery runtime using the internal
batteries and extended battery modules. For a detailed, interactive
battery runtime chart, please visit: Eaton.com/5PX - then view the
individual technical pages for details of each UPS.
Eaton Corporation
8609 Six Forks Road
Raleigh, NC 27615
United States
800.356.5794
Two individually
controlled and metered
groups of outlets
To interact with the Eaton 5PX UPS, please visit:
Eaton.com/5PX
CANADA
Ontario: 416.798.0112
Toll free: 1.800.461.9166
Eaton.com/powerquality
©2011 Eaton Corporation
All Rights Reserved
Printed in USA
5PX01FXA
December 2012
Eaton is a registered trademark of Eaton
Corporation.
All other trademarks are property of their
respective owners.
ENERGY STAR and the ENERGY STAR
mark are registered U.S. marks. ENERGY
STAR is a registered mark owned by the
U.S. government.
Product Brochure
Eaton 5SC UPS
Affordable and reliable protection for small business servers, storage and network equipment
Eaton® 5SC features and benefits:
Flexible integration:
LCD display: The LCD interface provides clear status
•
Convenient form factor: The 5SC fits easily into small
spaces such as kiosks, cash machines and ticket
machines while delivering flexibility with up to eight
outlets.
•
Battery life: Eaton’s exclusive ABM® technology
Adjustable input waveform sensitivity: The 5SC is
adaptable to specific environments, like genset.
increases battery service life by 50 percent with
easy front panel battery replacement to extend
UPS service life.
Intelligent Power Software Suite:
of UPS key parameters such as input and output
voltage, load and battery level, and estimated runtime.
Configuration capabilities are also offered for output
voltage, audible alarm and power input sensitivity.
Manageability:
•
USB, serial and relay connectivity: USB port
is HID-compliant for automatic integration into
Windows, Mac OS and Linux.
•
Eaton Intelligent Power Manager (IPM):
IPM software provides network power management.
5SC is managed over the network through a proxy
server having IPP installed.
By integrating Intelligent Power Manager and
Intelligent Power Protector software with the
5SC, you can:
• Get up-to-the-minute information on the status
of UPS power locally on your PC or remotely
through your PC/server as a proxy
•
Execute graceful, automatic shutdown of
network devices during a prolonged power
disruption, preventing data loss and saving
work-in-progress
•
Manage and optimize power performance
in your virtual environment and manage your
5SC on the same screen
Reliable power protection:
•
Pure sinewave output: When operating in battery mode,
the 5SC provides a high-quality output signal for any
sensitive equipment connected.
•
Buck and boost operation: The 5SC corrects a wide
range of input voltage variations through continuous
regulation without the use of batteries, and ensures
consistent input voltage to the connected equipment.
To learn more, please visit:
Eaton.com/intelligentpower
Eaton 5SC UPS
Ideal for protecting:
• Tower servers
• Network-attached storage
(NAS), network equipment
• ATMs, ticket machines, kiosks
5SC UPS MODEL SELECTION GUIDE1
Rating
Catalog number
(VA/watts)
Input
connection
Output
receptacles
Dimensions
(H x W x D), in
Net weight, lb
5SC Tower 120V, 50/60 Hz models
5SC500
500/350
5-15P (6 ft)
(4) 5-15R
8.2 x 5.9 x 9.4
15.2
5SC750
750/525
5-15P (6 ft)
(6) 5-15R
8.2 x 5.9 x 13.4
23.1
5SC1000
1000/700
5-15P (6 ft)
(8) 5-15R
8.2 x 5.9 x 13.4
25.6
5SC1500
1440/1080
5-15P (6 ft)
(8) 5-15R
8.2 x 5.9 x 16.1
34.0
5SC500G
500/350
C14
(4) C13
8.2 x 5.9 x 9.4
15.0
5SC750G
750/525
C14
(6) C13
8.2 x 5.9 x 13.4
23.1
5SC1500G
1500/1050
C14
(8) C13
8.2 x 5.9 x 16.1
33.5
5SC Tower 230V 50/60 Hz models
Services and support
Eaton provides product support 24 hours a day, 7 days a week. From battery
replacement to full UPS service plans, Eaton has one of the top service models
in the industry.
Three-year warranty
The 5SC warranty covers both UPS and the batteries for three years. No other
manufacturer in the industry offers a warranty as comprehensive.
What’s in the box
• 5SC UPS
• USB, serial cable and software
• Warranty for connected equipment
• User manual and safety instructions
G models only
• 2 IEC output power cords
2
5SC UPS front panel
5SC750 UPS rear panel
Power
LCD scroll
Alarm silence
LCD
interface
USB port
RS-232 port
Userreplaceable
battery with
ABM®
technology
(6) 5-15R
output
receptacles
6-foot input line
cord with 5-15P
(plugs into standard
wall socket)
1
Due to continuing product improvement programs, specifications
are subject to change without notice. For complete specifications
and battery runtimes, visit Eaton.com/5SC.
2
Model 5SC750
To interact with the 5SC UPS, please visit:
Eaton.com/5SC
Eaton
Electrical Sector
1000 Eaton Boulevard
Cleveland, OH 44122 USA
Eaton.com
Powerquality.eaton.com
©2013 Eaton
All Rights Reserved
Printed in USA
BR153027EN
August 2013
Eaton is a registered trademark of Eaton
Corporation.
All other trademarks are property of their
respective owners.
Powerware series
Eaton 9130 Tower UPS
Features
•฀ Protects฀against฀downtime,฀data฀loss฀and฀process฀interruption฀
by฀providing฀continuous,฀clean฀power
•฀ Expands฀monitoring,฀management฀and฀continuous฀uptime฀
capabilities฀with฀the฀Intelligent฀Power®฀Software฀Suite—perfect฀
for฀virtualized฀environments
Product snapshot
•฀ Offers฀premium฀performance฀with฀a฀0.9฀power฀factor฀and฀>95฀
percent฀efficiency฀in฀high฀efficiency฀mode฀
Product rating:
700–3000 VA
•฀ Increases฀battery฀service฀life฀and฀system฀uptime฀with฀ABM®
battery฀charging฀technology
Voltage
120 Vac, 208–240V
Frequency:
50/60 Hz
(auto-sensing)
•฀ Enables฀prolonged฀runtime฀of฀essential฀equipment฀during฀
power฀outages฀by฀allowing฀for฀orderly,฀remote฀shutdown฀of฀
non-critical฀systems฀or฀processes
Configuration:
Tower
•฀ Conserves฀valuable฀space฀with฀a฀slim฀tower฀design
•฀ Provides฀a฀two-year฀limited฀warranty,฀an฀extended฀warranty฀
and฀a฀$250,000฀load฀protection฀guarantee฀(U.S.฀and฀Canada)
Advanced฀power฀protection฀for:
Maximum availability
•฀ IT฀and฀networking฀environments
•฀ ABM฀technology฀increases฀
battery฀life฀and฀system฀
uptime
•฀ Servers,฀networking฀gear
•฀ Telecommunications,฀VoIP,฀security฀systems
•฀ Medical฀systems
•฀ Diagnostics฀and฀medical฀screening
•฀ Patient฀record฀archives
•฀ Manufacturing฀systems
•฀ Chip฀fabrication
•฀ Pharmaceutical฀production
•฀ Chemical฀processing
•฀ Load฀segments฀allow฀for฀
selective฀load฀shedding฀
during฀outages
•฀ Optional฀hot-swappable฀
extended฀battery฀modules฀
(EBMs)฀extend฀backup฀
runtime฀for฀hours
•฀ Internal฀hot-swappable฀
batteries฀can฀be฀replaced฀
without฀powering฀down฀
the฀UPS
•฀ UPS฀startup฀on฀battery฀power
•฀ Optional฀HotSwap฀
Maintenance฀Bypass฀(MBP)฀
enables฀the฀entire฀UPS฀to฀be฀
serviced฀or฀replaced฀without฀
interrupting฀power฀to฀loads
Low total cost of
ownership
•฀ More฀real฀output฀power฀for฀
dollar฀spent฀with฀0.9฀power฀
factor฀
•฀ Cuts฀energy฀usage฀and฀costs฀
with฀>95%฀efficiency฀rating฀in฀
high฀efficiency฀mode
UPS status and
operation
Communications
•฀ A฀standard฀communication฀
slot฀accepts฀cards฀for฀Web,฀
SNMP,฀Modbus฀or฀serial฀
connectivity
•฀ Free฀Intelligent฀Power฀
Software฀Suite฀for฀expanded฀
monitoring,฀management฀
and฀shutdown฀capabilities฀
(compatible฀with฀VMware฀
vCenter฀Server™฀and฀
Microsoft฀SCVMM™)
•฀ Connect฀directly฀to฀the฀
Ethernet฀network฀and฀the฀
Internet฀to฀monitor฀and฀
manage฀the฀UPS฀with฀a฀
standard฀Web฀browser
•฀ Bright,฀front฀panel฀LCD฀
for฀easy฀monitoring฀and฀
management
Bright LCD
user interface
•฀ LEDs฀to฀show฀system฀status
•฀ Direct฀monitoring฀via฀existing฀
management฀systems฀and฀
LANs
•฀ Optional฀FlexPDU฀adds฀
more฀plug-and-play฀
flexibility,฀streamlining฀
power฀distribution
•฀ Monitor฀power฀conditions฀
in฀real฀time฀through฀
existing฀facilities฀or฀building฀
management฀system
•฀ Monitor฀and฀gracefully฀shut฀
down฀multiple฀servers฀and฀
virtual฀machines฀running฀
various฀operating฀systems
•฀ Receive฀alarm฀notifications฀
from฀the฀UPS,฀environmental฀
monitoring฀devices,฀security฀
systems฀or฀through฀your฀
vCenter฀dashboard
For฀more฀information฀
on฀the฀9130,฀please฀visit฀
www.eaton.com/9130
or฀call฀800.356.5794.
Add up to four EBMs for hours of runtime
Extended battery
module connection
Communication bay
Optional FlexPDU and HotSwap MBP for
greater flexibility and uptime
Standard relay
output contact
RS-232 port
Remote
Emergency
Power Off
(REPO)
USB port
Line cord
with 5-15P
Two individually controlled
load segments
UPS rear panel (PW9130L1500T-XL)
2
EATON CORPORATION
Eaton 9130 Tower UPS
Battery runtimes (in minutes)
Load
Internal
w/1
(VA/Watts)
batteries
EBM
PW9130L700T
700/490฀
8฀
N/A฀
525/368฀
12฀
N/A฀
350/245฀
21฀
N/A฀
175/123฀
37฀
N/A฀
PW9130i700T
700/490฀
8฀
N/A฀
525/368฀
12฀
N/A฀
350/245฀
19฀
N/A฀
175/123฀
35฀
N/A฀
PW9130L1000T-XL
1000/700฀
10฀
40฀
750/525฀
13฀
58฀
500/350฀
24฀
85฀
250/175฀
48฀
190฀
PW9130G1000T-XL / PW9130i1000T-XL
1000/700฀
10฀
40฀
750/525฀
13฀
55฀
500/350฀
22฀
82฀
250/175฀
47฀
190฀
PW9130L1500T-XL
1500/1050฀
7฀
34฀
1125/788฀
11฀
44฀
750/525฀
18฀
79฀
375/263฀
38฀
167฀
w/2
EBMs
w/3
EBMs
w/4
EBMs
N/A฀
N/A฀
N/A฀
N/A฀
N/A฀
N/A฀
N/A฀
N/A฀
N/A
N/A
N/A
N/A
N/A฀
N/A฀
N/A฀
N/A฀
N/A฀
N/A฀
N/A฀
N/A฀
N/A
N/A
N/A
N/A
73฀
101฀
172฀
310฀
108฀
152฀
249฀
451฀
149
219
304
569
78฀
103฀
186฀
328฀
110฀
151฀
250฀
431฀
150
223
312
584
63฀
84฀
148฀
278฀
88฀
129฀
207฀
475฀
135
210
267
540
Load
Internal
w/1
w/2
(VA/Watts)
batteries
EBM
EBMs
PW9130i1500T-XL
1500/1050฀
7฀
32฀
61฀
1125/788฀
11฀
47฀
83฀
750/525฀
18฀
81฀
143฀
375/263฀
38฀
171฀
298฀
PW9130L2000T-XL
2000/1400฀
15฀
61฀
111฀
1500/1050฀
21฀
81฀
145฀
1000/700฀
34฀
129฀
198฀
500/350฀
72฀
225฀
449฀
PW9130G2000T-XL / XLEU / PW9130i2000T-XL
2000/1400฀
15฀
61฀
111฀
1500/1050฀
21฀
81฀
145฀
1000/700฀
34฀
129฀
198฀
500/350฀
72฀
225฀
449฀
PW9130L3000T-XL
3000/2100฀
9฀
35฀
66฀
2250/1575฀
13฀
53฀
100฀
1500/1050฀
22฀
86฀
153฀
750/525฀
69฀
168฀
298฀
PW9130G3000T-XL / XLEU / PW9130i3000T-XL
3000/2100฀
9฀
36฀
68฀
2250/1575฀
12฀
49฀
90฀
1500/1050฀
20฀
79฀
143฀
750/525฀
46฀
161฀
267฀
w/3
EBMs
w/4
EBMs
98฀
126฀
208฀
416฀
128
195
262
564
156฀
184฀
293฀
590฀
194
269
410
766
156฀
184฀
293฀
590฀
186
248
431
840
95฀
139฀
221฀
395฀
132
183
267
545
101฀
134฀
180฀
434฀
137
165
240
547
Notes:
Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
Runtimes are shown at a 0.7 power factor.
9130 models
Catalog number
Style number
North American models: 120V, 50/60 Hz
PW9130L700T฀฀
103006426-6591฀
PW9130L1000T-XL฀฀
103006427-6591฀
PW9130L1500T-XL฀฀
103006428-6591฀
PW9130L2000T-XL฀฀
103006429-6591฀
PW9130L3000T-XL฀฀
103006430-6591฀
Global models: 208V, 50/60 Hz
PW9130G1000T-XL฀
103006431-6591฀
PW9130G2000T-XL฀
103006432-6591฀
PW9130G2000T-XLEU฀ 103006478-6591฀
PW9130G3000T-XL฀฀
103006446-6591฀
฀
฀
PW9130G3000T-XLEU฀฀ 103006479-6591฀
International models: 230V, 50/60 Hz
PW9130i700T฀฀
103006433-6591฀
PW9130i1000T-XL฀฀
103006434-6591฀
PW9130i1500T-XL฀฀
103006435-6591฀
PW9130i2000T-XL฀฀
103006436-6591฀
PW9130i3000T-XL฀฀
103006437-6591฀
Extended battery modules
PW9130N1000T-EBM4฀฀ 103006438-6591฀
PW9130N1500T-EBM5฀ 103006439-6591฀
PW9130N3000T-EBM6฀ 103006440-6591฀
(50.0)
Rating
(VA/Watts)
Input
connection1
Output
receptacles
Dimensions
H x W x D, in (mm)
Weight,
lb (kg)
700/630฀
1000/900฀
1500/1350฀
2000/1800฀
3000/2700฀
5-15P฀
5-15P฀
5-15P฀
5-20P฀
L5-30P฀
(6)฀5-15R฀
(6)฀5-15R฀
(6)฀5-15R฀
(1)฀L5-20R,฀(4)฀5-20R฀
(4)฀5-20R,฀(1)฀L5-30R฀
9.1฀x฀6.3฀x฀13.8฀(230฀x฀160฀x฀350)฀
9.1฀x฀6.3฀x฀15.0฀(230฀x฀160฀x฀380)฀
9.1฀x฀6.3฀x฀16.9฀(230฀x฀160฀x฀430)฀
12.8฀x฀8.4฀x฀16.1฀(325฀x฀214฀x฀410)฀
12.8฀x฀8.4฀x฀16.1฀(325฀x฀214฀x฀410)฀
26.9฀(12.2)
32.0฀(14.5)
41.9฀(19.0)
76.1฀(34.5)
76.1฀(34.5)
1000/900฀
2000/1800฀
2000/1800฀
3000/2700฀
฀
3000/2700฀
L6-20P3฀
L6-20P3฀
L6-20P3฀
L6-20P3฀
฀
L6-20P3฀
(1)฀L6-20R,฀(2)฀6-20R฀
(1)฀L6-20R,฀(4)฀6-20R฀
(8)฀C13,฀(1)฀C19฀
(1)฀L6-30R,฀(1)฀L6-20R,฀฀
(2)฀6-20R
(8)฀C13,฀(1)฀C19฀
9.1฀x฀6.3฀x฀15.0฀(230฀x฀160฀x฀380)฀
12.8฀x฀8.4฀x฀16.1฀(325฀x฀214฀x฀410)฀
12.8฀x฀8.4฀x฀16.1฀(325฀x฀214฀x฀410)฀
12.8฀x฀8.4฀x฀16.1฀(325฀x฀214฀x฀410)฀
32.0฀(14.5)
76.1฀(34.5)
76.1฀(34.5)
76.1฀(34.5)
12.8฀x฀8.4฀x฀16.1฀(325฀x฀214฀x฀410)฀
76.1฀(34.5)
700/630฀
1000/900฀
1500/1350฀
2000/1800฀
3000/2700฀
C14฀
C14฀
C14฀
C14฀
C20฀
(6)฀C13฀
(6)฀C13฀
(6)฀C13฀
(8)฀C13,฀(1)฀C19฀
(8)฀C13,฀(1)฀C19฀
9.1฀x฀6.3฀x฀13.8฀(230฀x฀160฀x฀350)฀
9.1฀x฀6.3฀x฀15.0฀(230฀x฀160฀x฀380)฀
9.1฀x฀6.3฀x฀16.9฀(230฀x฀160฀x฀430)฀
12.8฀x฀8.4฀x฀16.1฀(325฀x฀214฀x฀410)฀
12.8฀x฀8.4฀x฀16.1฀(325฀x฀214฀x฀410)฀
26.9฀(12.2)
32.0฀(14.5)
41.9฀(19.0)
76.1฀(34.5)
76.1฀(34.5)
NA฀
NA฀
NA฀
NA฀
NA฀
NA฀
NA฀
NA฀
NA฀
9.1฀x฀6.3฀x฀15.0฀(230฀x฀160฀x฀380)฀
9.1฀x฀6.3฀x฀16.9฀(230฀x฀160฀x฀430)฀
12.8฀x฀8.4฀x฀16.1฀(325฀x฀214฀x฀410)฀
40.8฀(18.5)
53.6฀(24.3)
110.3฀
1
Input cord length is 6 ft
C14, w/detachable L6-20P
3
C20, w/detachable L6-20P
4
This EBM works with 1000 VA model, where available
5
This EBM works with 1500 VA model
6
This EBM works with 2000/3000 VA models, where available
2
Additional notes:
Comprehensive Eaton services available for 9130 Tower products
•฀ Warranty+฀extended฀warranties—3฀or฀5฀years฀total
•฀ On-site฀service฀plans฀for฀startups฀and฀preventive฀and฀
฀ corrective฀maintenance
Visit฀www.eaton.com/9130฀for฀details.
When high voltage 9130 is used at 208V, derate power by 10% and 20% at 200V
When low voltage 9130 is used at 110V, derate power by 10% and 20% at 100V
www.eaton.com/powerquality 1.800.356.5794
3
Technical specifications
1
General
User฀interface฀
฀
฀
LEDs฀
฀
Topology฀฀
Diagnostics฀
UPS฀bypass฀
Dimensions฀
Remote฀฀฀
Emergency฀
Power-off฀(REPO)
Graphical฀LCD฀with฀blue฀backlight฀and฀text฀in฀
English,฀French,฀German,฀Russian฀and฀Spanish
Four฀status-indicating฀LEDs
True฀online,฀double-conversion
Full฀system฀self-test
Automatic฀bypass
See฀models฀table
Emergency฀shutdown฀control฀through฀the฀REPO฀port
Electrical input
Nominal฀voltage฀
Voltage฀range฀
฀
฀
Power฀draw฀฀
of฀UPS฀ ฀
฀
฀
฀
฀
฀
฀
Dedicated฀circuit฀
breaker฀rating฀
฀
฀
฀
฀
120V,฀208V,฀220–240V
120V:฀90–138฀Vac
208/230V:฀160–276฀Vac
700:฀5.8A฀@120V,฀3.4A฀@208V,฀3.0A฀@230V
1000:฀8.3A฀@120V,฀4.8A฀@208V,฀4.3A฀@230V
1500:฀12.5A฀@120V,฀7.2A฀@208V,฀6.5A฀@230V
2000:฀16.6A฀@120V,฀9.6A฀@208V,฀8.7A฀@230V
3000:฀14.4A฀@208V,฀13.0A฀@230V
120V:
700–1500฀VA:฀15A
2000฀VA:฀20A
3000฀VA:฀30A
208/230V:
฀
฀
700–2000฀VA:฀10A
฀
฀
3000฀VA:฀16A
Frequency฀
50/60฀Hz
Frequency฀range฀ 45–65฀Hz
Electrical output
Power฀factor฀
On฀utility฀voltage฀
regulation
On฀battery฀฀
voltage฀regulation
Efficiency฀
Frequency฀฀
regulation
Load฀crest฀factor฀
Voltage฀฀ ฀
waveform
Load฀segments฀
Battery
Battery฀type฀
Battery฀runtime฀
Battery฀฀ ฀
replacement
Start-on-battery฀
Communications
Serial฀port฀
RS-232฀standard,฀for฀interface฀to฀power฀
฀
฀
management฀software
USB฀port฀฀
HID฀standard,฀for฀communicating฀with฀Windows฀98,฀
฀
฀
XP,฀ME฀and฀Vista฀computers
Relay฀output฀
Common฀alarm฀standard
Communications฀฀ Optional฀communication฀slot฀(Mini-Slot)
slot
Optional฀฀฀
SNMP/Web฀card฀for฀direct฀control฀and฀monitoring฀
communication฀ in฀SNMP-based฀networks,฀monitoring฀of฀UPS฀status฀
cards฀
฀
and฀meters฀through฀Web฀browser฀interface฀Relay฀
฀
฀
card฀for฀integration฀to฀industrial฀environment฀and฀
฀
฀
building฀management฀systems,฀remote฀shutdown฀
฀
฀
for฀IBM฀AS/400฀systems
Environmental
Safety฀markings฀
฀
฀
EMC฀markings฀
฀
฀
฀
฀
฀
฀
฀
฀
Audible฀noise฀
Ambient฀฀฀
operating
temperature฀
Storage฀฀ ฀
temperature฀
Relative฀humidity฀
120/208V:฀UL,฀CUL,฀VCCI
230V:฀CE,฀GS
120V:฀FCC฀Class฀B,฀EN55022฀Class฀B฀(1.5฀kVA฀and฀
below);฀FCC฀Class฀A,฀EN55022฀Class฀A฀(2.0฀kVA฀
and฀above)
230V:฀CE฀(per฀IEC/EN62040-2:฀Emissions,฀Category฀
C1;฀Immunity,฀Category฀C2)
<50฀dB
0˚C฀(32˚F)฀to฀+40˚C฀(104˚F)
-20˚C฀(-4˚F)฀to฀+40˚C฀(104˚F)฀with฀batteries฀and฀
-25˚C฀(-13˚F)฀to฀+55˚C฀(131˚F)฀without฀batteries
5–90%฀non-condensing
Heat dissipation for all voltages: 208–240V and 120V
0.9
±3%฀of฀nominal
9130 model
Normal mode,
BTUs/hr
On battery,
BTUs/hr
±3%฀of฀nominal
700 VA
350
554
>95%฀in฀high-efficiency฀mode;฀>86%฀in฀online฀mode
±3%฀Hz฀online
1000 VA
500
674
1500 VA
750
1,011
2000 VA
838
1,348
3000 VA
1,257
1,755
3฀to฀1
Sine฀wave
Two฀configurable,฀individually฀controlled฀receptacles
VRLA฀12V/9฀Ah฀(both฀internal฀and฀external)
>3฀minutes฀with฀internal฀batteries฀@100%฀load
Hot-swappable฀internal฀and฀external฀batteries
Allows฀start฀of฀UPS฀without฀utility฀input
UNITED STATES
8609 Six Forks Road
Raleigh, NC 27615 U.S.A.
Toll Free: 1.800.356.5794
www.eaton.com/powerquality
CANADA
Ontario: 416.798.0112
Toll free: 1.800.461.9166
LATIN AMERICA
South Cone: 54.11.4124.4000
Brazil: 55.11.3616.8500
Andean & Caribbean:
1.949.452.9610
Mexico & Central America:
52.55.9000.5252
1
Due to continuing product improvement programs, specifications are subject to change
without notice.
The 9130 is part of the UPSgrade program
UPSgrade™
www.eaton.com/UPSgrade
EUROPE/MIDDLE EAST/AFRICA
Denmark: 45.3686.7910
Finland: 358.94.52.661
France: 33.1.6012.7400
Germany: 49.0.7841.604.0
Italy: 39.02.66.04.05.40
Norway: 47.23.03.65.50
Portugal: 55.11.3616.8500
Sweden: 46.8.598.940.00
United Kingdom: 44.1753.608.700
ASIA PACIFIC
Australia: 61.2.9693.9366
New Zealand: 64.0.3.343.3314
China: 86.21.6361.5599
HK/Korea/Taiwan: 852.2745.6682
India: 91.11.4223.2300
Singapore/SEA: 65.6825.1668
Eaton, Powerware, ABM, Intelligent Power
and UPSgrade are trade names, trademarks
and/or service marks of Eaton Corporation
or its subsidiaries and affiliates. All other
trademarks are property of their
respective owners.
©2011 Eaton Corporation
All Rights Reserved
Printed in USA
9130TFXA / TN
June 2011
Product Brochure
Eaton 9130 Rackmount UPS
Product snapshot
Product rating:
700–3000 VA
Voltage
120 Vac, 208–240V
Frequency:
50/60 Hz (auto-sensing)
Configuration:
Rackmount
Advanced power protection for:
•฀
IT฀and฀networking฀environments
•฀
Rack฀servers,฀networking฀gear
•฀
Telecommunications,฀VoIP,฀security฀systems
•฀
Medical฀systems
•฀
Diagnostics฀and฀medical฀screening
•฀
Patient฀record฀archives
•฀
Manufacturing฀systems
•฀
Chip฀fabrication
•฀
Pharmaceutical฀production
•฀
Chemical฀processing
Features
•
Protectsagainstdowntime,datalossandprocessinterruption
byprovidingcontinuous,cleanpower
•
GraphicaluserinterfaceprovidesallcriticalUPSinformationon
asinglescreenandenablessettingscontrolatthepushofa
button
•
Providesupto3000VAinonly2Uofrackspace
•
Offerspremiumperformancewitha0.9powerfactorand>95
percentefficiencyinhighefficiencymode
•
IncreasesbatteryservicelifeandsystemuptimewithABM®
batterychargingtechnology
•
Enablesprolongedruntimeofessentialequipmentduring
poweroutagesbyallowingfororderly,remoteshutdownof
non-criticalsystemsorprocesses
•
EnsuresdataandsystemintegritywithIntelligentPower®
Managersupervisorysoftware,whichprovideseasy,versatile,
remotemonitoringandmanagementofmultipledevices
•
Providesatwo-yearlimitedwarranty,anextendedwarranty,
on-siteFlexandon-sitePowerTrustservicecontracts,anda
$250,000loadprotectionguarantee(U.S.andCanada)
Maximum availability
•
ABMtechnologyincreasesbatterylifeandsystemuptime
•
Loadsegmentsallowforselectiveloadsheddingduring
outages
•
Optional2U,hot-swappableextendedbatterymodules(EBMs)
extendbackupruntimeforhours
•
Internalhot-swappablebatteriescanbereplacedwithout
poweringdowntheUPS
•
UPSstartuponbatterypower
•
HotSwapMaintenanceBypass(MBP)andPowerPass
DistributionModules(PPDMs)optionsenabletheentireUPS
tobeservicedorreplacedwithoutpoweringdowncritical
systems
Low total cost of ownership
•
Morerealoutputpowerfordollarspentwith0.9powerfactor
•
Cutsenergyusageandcostswith>95%efficiencyratingin
highefficiencymode
•
3000VAinonly2Uofspacesavesexpensivedatacenterreal
estate
UPS status and operation
Hot-swappable internal batteries in only 2U
•
BrightfrontpanelLCDforeasymonitoringand
management
•
LEDstoshowsystemstatus
•
OptionalFlexPDUaddsmoreplug-and-playflexibility,
streamliningpowerdistribution
•
Multipleoptionsforindustry-standardcommunications
•
IntelligentPowerManagersupervisorysoftwareincludedfree
ofcharge
•
DirectmonitoringviaexistingmanagementsystemsandLANs
Communications
•
AstandardcommunicationslotacceptsinterfacesforWeb,
SNMP,Modbusorserialconnectivity
•
ConnectdirectlytotheEthernetnetworkandtheInternetto
monitorandmanagetheUPSwithastandardWebbrowser
•
Monitorpowerconditionsinrealtimethroughexistingfacilities
orbuildingmanagementsystem
•
Monitorandgracefullyshutdownmultipleserversrunning
variousoperatingsystems
•
ReceivealarmnotificationsfromtheUPS,environmental
monitoringdevicesorsecuritysystems
Add up to four EBMs for hours of runtime
Intelligent Power Software Suite
ByintegratingthesuitewiththeEaton9130,youcan:
•
SeamlesslyintegratewithVMware’svCenterServer™
virtualizationmanagementsolution,aswellas
virtualizationplatformssuchasCitrix®XenServer,
MicrosoftSCVMM™,RedHat®andotherXen®open
sourceplatforms
•
Initiatelivemigrationofvirtualmachines(VM)to
automaticallyandtransparentlymigrateVMsduring
powerdisruptionstounaffecteddeviceswithsystems
suchasVMwarevMotion™andMicrosoftLive
Migration
•
IntegratewithVMwarevCenterSiteRecovery
Manager
Optional FlexPDU and HotSwap
MBP for greater flexibility and
uptime
Four-post rail kit included
(two-post rail kit optional)
Tolearnmore,pleasevisit:Eaton.com/intelligentpower
UPS rear panel (PW9130L1500R-XL2U)
RemoteEmergency
PowerOff(REPO)
Communicationbay
USBport
Network-MScard
(includedwith
PW91304500R-XLLUN)
Twoindividuallycontrolledloadsegments
2
EATON CORPORATION Eaton 9130 Rackmount UPS
Standardrelay
outputcontact
RS-232port
Linecordwith
5-15P
9130 models
Rating
(VA/Watts)
Input
connection1
Output receptacles
Dimensions
H x W x D, in
Weight, lb
700/630
1000/900
1500/1350
5-15P
5-15P
5-15P
(6)฀5-15R
(6)฀5-15R
(6)฀5-15R
3.4฀x฀17.2฀x฀17.7
3.4฀x฀17.2฀x฀17.7
3.4฀x฀17.2฀x฀17.7
35.3
35.3
43.0
2000/1800
2500/2250
3000/2700
1500฀/฀1350
2000฀/฀1800
3000฀/฀2700
5-20P
L5-30P
L5-30P
5-15P
5-20P
L5-30P
(6)฀5-20R,฀(1)฀L5-20R
(6)฀5-20R,฀(1)฀L5-30R
(6)฀5-20R,฀(1)฀L5-30R
(6)฀5-15R
(6)฀5-20R,฀(1)฀L5-20R
(6)฀5-20R,฀(1)฀L5-30R
3.4฀x฀17.2฀x฀23.6฀
3.4฀x฀17.2฀x฀23.6
3.4฀x฀17.2฀x฀23.6
3.4฀(2U)฀x฀17.3฀x฀16.9
3.4฀(2U)฀x฀17.3฀x฀22.6
3.4฀(2U)฀x฀17.3฀x฀22.6
63.9
65.0฀
65.0฀
43.0
63.9
65.0
3000/2700
L6-20P4
(1)฀L6-30R,฀(1)฀L6-20R,฀(2)฀6-20R
3.4฀x฀17.2฀x฀23.6฀
65.0
PW9130G3000R-XL2UEU฀
103006483-6591
3000/2700
L6-20P
(8)฀C13,฀(1)฀C19
3.4฀x฀17.2฀x฀23.6
International models: 230V, 50/60 Hz
PW9130i1000R-XL2U฀
103006455-6591
1000/900
C14
(6)฀C13
3.4฀x฀17.2฀x฀17.7
PW9130i1500R-XL2U฀
103006456-6591
1500/1350
C14
(6)฀C13
3.4฀x฀17.2฀x฀17.7
PW9130i2000R-XL2U฀
103006457-6591
2000/1800
C14
(8)฀C13,฀(1)฀C19
3.4฀x฀17.2฀x฀23.6
PW9130i3000R-XL2U฀
103006463-6591
3000/2700
C20
(8)฀C13,฀(1)฀C19
3.4฀x฀17.2฀x฀23.6
Extended battery modules
PW9130N1000R-EBM2U5฀
103006458-6591
NA
NA
NA
3.4฀x฀17.2฀x฀17.7
PW9130N1500R-EBM2U6฀
103006459-6591
NA
NA
NA
3.4฀x฀17.2฀x฀17.7
PW9130N3000R-EBM2U7฀
103006460-6591
NA
NA
NA
3.4฀x฀17.2฀x฀23.6
TAA Compliant SKUS
Eaton now offers TAA compliant models for the 9130. Please visit Eaton.com/taaups for model specific information.
65.0
Catalog number
Style number
North American models: 120V, 50/60 Hz
PW9130L700R-XL2U฀
103006447-6591
PW9130L1000R-XL2U฀
103006448-6591
PW9130L1500R-XL2U฀
103006449-6591
PW9130L2000R-XL2U฀
103006450-6591
PW9130L2500R-XL2U฀
103006451-6591
PW9130L3000R-XL2U฀
103006452-6591
PW9130L1500R-XL2UN
PW9130L2000R-XL2UN
PW9130L3000R-XL2UN
Global models: 208V, 50/60 Hz
PW9130G3000R-XL2U฀
103006454-6591
4
Catalog number
35.3
43.0฀
63.9฀
65.0฀
48.7
62.0฀
90.6
Description
Input connection
Output receptacles
Dimensions H x W x D, in
Weight, lb
PowerPass Distribution Modules
103002730-6501
PPDM1-HV-US-P2฀3฀kVA
103002732-6591
PPDM1-HV-US-HW฀3฀kVA฀(ROHS)
103002735-6591
PPDM2-LV-US-HW฀3฀kVA฀(ROHS)
103002739-6591
PPDM1-HV-US-P1฀3฀kVA฀(ROHS)
103002742-6501
PPDM2-LV-US-P1฀3฀kVA
IEC320-C208
Hardwire
Hardwire
IEC320-C208
L5-30P8
(1)฀L5-30R฀&฀(6)฀5-20R
Hardwire
Hardwire
(1)฀L14-30R฀&฀(6)฀5-20R
(1)฀L5-30R฀&฀(6)฀5-20R
3.5฀(2U)฀x฀17.0฀x฀23.9
3.5฀(2U)฀x฀17.0฀x฀23.9
3.5฀(2U)฀x฀17.0฀x฀23.9
3.5฀(2U)฀x฀17.0฀x฀23.9
3.5฀(2U)฀x฀17.0฀x฀23.9
20.0
20.0
20.0
20.0
20.0
1.Inputcordlengthis6ft.2.Rackmodelsoccupy2Uofrackspaceandfitinto19-inchracks.3.C14,w/detachableL6-20P.4.C20,w/detachableL6-20P.5.ThisEBM
workswith700/1000VAmodels,whereavailable.6.ThisEBMworkswith1500VAmodel.7.ThisEBMworkswith2000/2500/3000VAmodels,whereavailable.8.
ConnectioncablestotheUPSareincludedwiththePPDM;usetheinputcordfromtheUPSasinputtothePPDM,exceptforhardwireunits.Additional notes:When
highvoltage9130isusedat208V,deratepowerby10%and20%at200V.Whenlowvoltage9130isusedat110V,deratepowerby10%and20%at100V.
Battery runtimes (in minutes)
Load
Internal
(VA/Watts)
batteries
PW9130L700R-XL2U
700/490
14
525/368
20
350/245
32
175/123
64
PW9130L1000R-XL2U
1000/700
10
750/525
13
500/350
24
250/175
48
PW9130L1500R-XL2U
1500/1050
7
1125/788
11
750/525
18
375/263
38
PW9130i1500R-XL2U
1500/1050
7
1125/788
11
750/525
18
375/263
38
w/1 EBM
w/2 EBMs
w/3 EBMs
w/4 EBMs
55
77
124
200
102
140
189
395
148
179
282
552
175
239
414
739
40
58
85
190
73
101
172
310
108
152
249
451
149
219
304
569
34
44
79
167
63
84
148
278
88
129
207
475
135
210
267
540
32
47
81
171
61
83
143
298
98
126
208
416
128
195
262
564
Battery runtime
Youcangetuptofivehoursofbatteryruntimeusingthe
internalbatteriesandextendedbatterymodules.Foradetailed,
interactivebatteryruntimechart,pleasevisit:Eaton.com/9130.
Load
Internal
(VA/Watts)
batteries
PW9130L2000R-XL2U
2000/1400
9
1500/1050
14
1000/700
26
500/350
52
w/1 EBM
w/2 EBMs
w/3 EBMs
w/4 EBMs
45
66
101
197
86
115
185
353
124
165
251
481
163
225
343
629
PW9130L2500R-XL2U
2500/2250
7
31
59
87
1875/1688
10
43
81
121
1250/1125
17
65
120
163
625/563
40
145
228
363
PW9130L3000R-XL2U
3000/2100
5
25
48
72
2250/1575
8
37
72
102
1500/1050
13
60
100
165
750/525
34
138
228
326
PW9130G3000R-XL2U / PW9130G3000R-XL2UEU / PW9130i3000R-XL2U
3000/2100
6
25
45
68
2250/1575
8
34
70
96
1500/1050
14
62
92
156
750/525
34
130
212
355
119
154
203
491
100
137
223
438
96
130
211
442
Notes: Backuptimesareapproximateandmayvarywithequipment,
configuration,batteryage,temperature,etc.Runtimesareshownata0.7
powerfactor.
EATON CORPORATION Eaton 9130 Rackmount UPS
3
Technical specifications
1
General
User interface
LEDs
Topology
Diagnostics
UPS bypass
Dimensions
Rail kit
EBMs
Remote
Emergency
Power-off (REPO)
Graphical LCD with blue backlight and text in
English, French, German, Russian and Spanish
Four status-indicating LEDs
True online, double-conversion
Full system self-test
Automatic bypass
See models table on previous page
4-post rail kit included with all rackmount units
Ship with a 4-post rail kit
Emergency shutdown control
Electrical input
Nominal voltage
Voltage range
120V, 208V, 220–240V
120V: 90–138 Vac
208/230V: 160–276 Vac
Power draw
700: 5.8A @120V, 3.4A @208V, 3.0A @230V
of UPS
1000: 8.3A @120V, 4.8A @208V, 4.3A @230V
1500: 12.5A @120V, 7.2A @208V, 6.5A @230V
2000: 16.6A @120V, 9.6A @208V, 8.7A @230V
2500: 20.8A @208V, 10.9A @230V
3000: 14.4A @208V, 13.0A @230V
Dedicated circuit 120V:
breaker rating
700–1500 VA: 15A
2000 VA: 20A
2500–3000 VA: 30A
208/230V:
700–2000 VA: 10A
3000 VA: 16A
Frequency
50/60 Hz
Frequency range 45–65 Hz
Electrical output
Power factor
On utility voltage
regulation
On battery
voltage regulation
Efficiency
Frequency
regulation
Load crest factor
Voltage
waveform
Load segments
Battery
Battery type
Battery runtime
Battery
replacement
Start-on-battery
0.9
±3% of nominal
Communications
Serial port
RS-232 standard, for interface to power
management software
USB port
HID standard, for communicating with Windows 98,
XP, ME and Vista computers
Relay output
Common alarm standard
Communications Optional communication slots (BD Slot, Mini-Slot)
slot
Optional
SNMP/Web card for direct control and monitoring
communication
in SNMP-based networks, monitoring of UPS status
cards
and meters through Web browser interface Relay
card for integration to industrial environment and
building management systems, remote shutdown
for IBM AS/400 systems
Environmental
Safety markings
EMC markings
120/208V: UL, CUL, VCCI
230V: CE, GS
120V: FCC Class B, EN55022 Class B (1.5 kVA and
below); FCC Class A, EN55022 Class A (2.0 kVA
and above)
230V: CE (per IEC/EN62040-2: Emissions, Category
C1; Immunity, Category C2)
<50 dB
0˚C (32˚F) to +40˚C (104˚F)
Audible noise
Ambient
operating
temperature
Storage
-20˚C (-4˚F) to +40˚C (104˚F) with batteries and
temperature
-25˚C (-13˚F) to +55˚C (131 ˚F) without batteries
Relative humidity 5–90% non-condensing
Heat dissipation for all voltages: 208–240V and 120V
Normal
Mode
700 VA: 350 BTUs/hr
1000 VA: 500 BTUs/hr
1500 VA: 750 BTUs/hr
2000 VA: 838 BTUs/hr
2500 VA: 1,047 BTUs/hr
3000 VA: 1,257 BTUs/hr
Battery 700 VA: 554 BTUs/hr
Mode
1000 VA: 674 BTUs/hr
1500 VA: 1,011 BTUs/hr
2000 VA: 1,348 BTUs/hr
2500 VA: 1,463 BTUs/hr
3000 VA: 1,755 BTUs/hr
1
฀Due฀to฀continuing฀product฀improvement฀programs,฀specifications฀are฀subject฀to฀change฀฀
฀฀without฀notice.
±3% of nominal
>95% in high-efficiency mode; >86% in online mode
±3% Hz online
3 to 1
Sine wave
The฀9130฀is฀part฀of฀the฀UPSgrade฀program฀
฀
฀
฀
฀
Eaton.com/UPSgrade
UPSgrade™
Two configurable, individually controlled receptacles
What’s in the box
•฀
Tower฀pedestals
•฀
Four-post฀rail฀kit
•฀
•฀
VRLA 12V/9 Ah (both internal and external)
>3 minutes with internal batteries @100% load
Hot-swappable internal and external batteries
Allows start of UPS without utility input
User฀manual฀CD
I฀ntelligent฀Power฀Software฀
Suite฀CD
•฀
Quick฀start฀guide
•฀
USB฀cable
•฀
RS-232฀serial฀cable
•฀
Phillips฀Head฀screw฀driver฀
•฀
2฀ ฀IEC฀to฀IEC฀jumper฀cables฀
(208V/230V฀models)
Comprehensive Eaton services available for 9130 Rack products
•฀
Warranty+฀extended฀warranties—3฀or฀5฀years฀total
•฀
On-site฀service฀plans฀for฀startups฀and฀preventive฀and฀corrective฀maintenance
VisitEaton.com/9130RMfordetails.
For more information about the 9130,
visit Eaton.com/9130RM .
Eaton Corporation
ElectricalSector
1111SuperiorAvenue
Cleveland,OH44114USA
Eaton.com
©2012EatonCorporation
AllRightsReserved
PrintedinUSA
9130RFXA
October2012
Eatonisaregisteredtrademark
ofEatonCorporation.
Allothertrademarksareproperty
oftheirrespectiveowners.
Product Brochure
5–11 kVA
Eaton 9PX UPS
Reliable, versatile and efficient backup power for IT equipment, including Cisco switches and servers
Eaton 9PX features and benefits
Reliability: With extended battery runtime options,
hot-swappable batteries, internal bypass and optional
maintenance bypass, the 9PX maximizes the availability
of your IT systems.
More power: The 9PX allows you to connect more
devices by providing up to 28 percent more wattage
compared to traditional UPSs.
Efficiency: The double-conversion online 9PX is the
most efficient UPS in its class with up to 93 percent
efficiency rating in normal mode. Split-phase models
offer both 120V and 208V output without a transformer;
saving vertical rack (U) space, weight and cost.
Increased battery life: Eaton® offers ABM® technology
that increases battery service life by 50 percent. ABM
uses an advanced, three-stage charging technique and
closely monitors battery health to provide advanced
notice when batteries need replacement.
Intuitive LCD interface: Eaton’s next-generation intuitive
LCD interface offers a graphical display that provides
all critical UPS information in a single view. The userfriendly menu allows you to view information and control
settings with the push of a button.
Intelligent Power Software Suite
By integrating the bundled Intelligent Power® Software
Suite (IPSS), you can monitor and manage your network
power devices. IPSS enables you to:
• Seamlessly integrate with VMware’s vCenter™
Server™ virtualization management solution, as well
as virtualization platforms such as Citrix® XenServer,
Microsoft SCVMM™, Red Hat® and other Xen® open
source platforms
• Initiate live migration of virtual machines (VMs)
to automatically and transparently migrate them
during power disruptions to unaffected devices with
systems such as VMware vMotion™ and Microsoft Live
Migration
• Gracefully shutdown computers, VMs and host
servers during an extended power outage
To learn more, please visit: Eaton.com/intelligentpower
Services and support
Eaton provides 24x7 product support. From battery
replacement to full UPS service plans, Eaton has one of
the top service models in the industry.
The Eaton 9PX is an ENERGY STAR® qualified UPS.
ENERGY STAR is intended to help consumers save
money and protect the environment through energy
efficient products and practices.
Versatile configurations
Graphical LCD interface
The 9PX has the versatility to meet the demands of a wide array
of IT applications.
With an LCD interface that tilts 45 degrees for optimal viewing,
rotates to match rack and tower installations, and provides clear
information on UPS status and measurements, the 9PX makes
local management easy.
Each 9PX includes a 4-post rail kit.
The 9PX displays key data such as its up to 93 percent efficiency
rating, alarm history, runtime remaining, load percentage and more
in a graphical format.
Split-phase models incorporate flexible receptacle configurations
that natively offer both 208 and 120 volt. Rear panel of 9PX 6K
split-phase shown above.
The 9PX provides line and match EBMs for extended runtime.
Virtualization-ready UPS
Every 9PX comes with the Network Card-MS and IPSS,
allowing seamless integration into the following industry-leading
virtualization platforms:
Intelligent Power Manager plugs into VMware’s vCenter dashboard.
The bundled Network Card-MS allows the 9PX to connect to an
Ethernet network and the Internet, supporting real-time monitoring
and control of UPSs across the network via a standard Web
browser, SNMP-compliant network management system or power
management software.
2
EATON Eaton 9PX UPS
Eaton.com/9PX
Rear panel overview
Model 9PX6KTF5 (6kVA, 120/208V output)
5
1
9
3
9
12
13
6
11
2
7
4
15
14
UPS
10
8
17
1
Remote Power Off (RPO)
2
EBM detection port
3
Network Card-MS
(bundled with UPS)
4
EBM connector
5
Remote On/Off (ROO)
6
Output relay contact – DB-9
dry contact (common alarm
as standard).
7
USB port (cable included)
8
RS-232 serial communication
port (cable included)
9
Output circuit breaker
protection
10
(2) L6-20R
Transformer
16
18
11 (2) L6-30R
12 Ground bonding screw
13 6-foot line cord with L6-30P
Model 9PX10KSP (10kVA, 120/208V output)
14 Output terminal block for
hardwired applications
1
2
15 30A main circuit breaker
5
7
6
16
UPS
9
(4) 20A circuit breakers
17 (18) 5-20R outlets
8
(accommodates 5-20P
and 5-15P
3
18 L6-30P input cord
19 (2) L14-30R
20
EBM
20 (1) L6-30R
19
4
14
Transformer
To interact with the 9PX and see
additional configurations up close,
please visit Eaton.com/9PX.
EATON Eaton 9PX UPS
Eaton.com/9PX
3
9PX model selection guide
The 9PX UPS is pre-configured into bundles for easy Configuration and deployment. For complete specifications, including interactive
battery runtime graphs, please visit Eaton.com/9PX.
9PX SP 6-10 kVA rack/tower: 120/208 output, 50/60 Hz
Catalog number
Rating (VA/Watts)
Input
9PX6KSP
5500/4900****
L14-30P***
9PX8KSP
8000/7200
Hardwired
9PX10KSP
10000/9000
Hardwired
Output
(1) L14-30R, (1) L6-30R, (6) 5-20R, HW
(2) L14-30R, (1) L6-30R, HW
(2) L14-30R, (1) L6-30R, HW
**UPS and EBM ship with a 4-post rail kit, 9RK. ***Terminal block with L14-30P cord.
**** 6K models derated at 100/200, 120/208, 110/220V (see technical specs).
Dimensions (HxWxD, in.)
6.8 (4U) x 17.3 x 25.6
10.3 (6U) x 17.3 x 27.6
10.3 (6U) x 17.3 x 27.6
Weight (lb.)
157.3
225
225
Extended battery modules: 6-10kVA Split-phase
Catalog number Description
9PXEBM240SP
6K SP EBM (add up to 4 EBMs), Use with 9PX6KSP UPS
EBMCBL240SP
9PX EBM Cable Extension 6kVA Split-Phase , 6 feet (1.8 meters)
9PXEBM360SP
8/10K EBM (add up to 4 EBMs) Use with 9PX8KSP, 9PX10KSP UPS
EBMCBL360SP
9PX EBM Cable Extension 8/10kVA Split-Phase , 6 feet (1.8 meters)
9PX 5-11 kVA 208V output, 50/60 Hz bundles
Catalog number
Rating (VA/watts)
Input
Output
9PX5K
5000/4500
L6-30P**
(2) L6-30R, (2) L6-20R, Hardwired
9PX6K
6000/5400
L6-30P**
(2) L6-30R, (2) L6-20R, Hardwired
9PX6KG
6000/5400
Hardwired
(2) C19, (8) C13, Hardwired
9PX8KHW
8000/7200
Hardwired
Hardwired
9PX8K
8000/7200
Hardwired
Hardwired, (3) L6-30R
9PX11KHW
11000/10000
Hardwired
Hardwired
9PX11K
11000/10000
Hardwired
Hardwired, (3) L6-30R
9PX 5-11 kVA 120/208V output, 50/60 Hz bundles
Catalog number
Rating (VA/watts)
Input
9PX5KTF5
5000/4500
L6-30P**
9PX5KP1
5000/4500
L6-30P
9PX5KP2
5000/4500
Hardwired
9PX6KTF5
6000/5400
L6-30P**
9PX6KP1
6000/5400
L6-30P
9PX6KP2
6000/5400
Hardwired
9PX8KTF5
8000/7200
Hardwired
9PX11KTF5
11000/10000
Hardwired
9PX11KTF11
11000/10000
Hardwired
Output
(1) L6-30R, (2) L6-20R, (18) 5-20R, Hardwired
(1) L14-30R, (1) L6-30R, (6) 5-20R
Hardwired
(1) L6-30R, (2) L6-20R, (18) 5-20R, Hardwired
(1) L14-30R, (1) L6-30R, (6) 5-20R
Hardwired
Hardwired, (2) L6-30R, (18) 5-20R
Hardwired, (2) L6-30R, (18) 5-20R
Hardwired, (2) L14-30R, (8) 5-20R
Dimensions (HxWxD, in.)
5.1 (3U) x 17.3 x 26.6
Weight (lb.)
132
5.1 (3U) x 17.3 x 25.4
163
Dimensions (HxWxD, in.)*
5.1 (3U) x 17.3 x 28.4
5.1 (3U) x 17.3 x 28.4
5.1 (3U) x 17.3 x 27.0
10.2 (6U) x 17.3 x 27.6
10.2 (6U) x 17.3 x 30.0
10.2 (6U) x 17.3 x 27.6
10.2 (6U) x 17.3 x 30.0
Weight (lb.)
106
106
106
190
205
190
205
Dimensions (HxWxD, in.)*
10.2 (6U) x 17.3 x 28.4
10.2 (6U) x 17.3 x 28.4
10.2 (6U) x 17.3 x 28.4
10.2 (6U) x 17.3 x 28.4
10.2 (6U) x 17.3 x 28.4
10.2 (6U) x 17.3 x 28.4
15.3 (9U) x 17.3 x 30.0
15.3 (9U) x 17.3 x 30.0
15.3 (9U) x 17.3 x 27.6
Weight (lb.)
201
203
201
201
203
201
300
300
377
*Each module of every 9PX bundle ships with a 4-post rail kit. **Terminal block with L6-30P cord.
Extended battery modules (EBM) and accessories: 5 and 6kVA
Catalog number Description
9PXEBM180RT
EBM; includes 4-post rail kit, quick start guide, joining brackets for tower configuration and 1-foot connector
cable; add up to 4 EBMs
EBMCBL180
9PX EBM Cable Extension 5 and 6 kVA UPS models, 6 feet (1.8 meters)
CBLADAPT180
Adapter cable from Eaton 9135/MX UPS EBM to 5 and 6 kVA 9PX UPS models
Extended battery modules (EBM) and accessories: 8 and 11kVA
9PXEBM240RT
EBM; includes 4-post rail kit, quick start guide, joining brackets for tower configuration and 1-foot connector
cable. Add up to 5 EBMs with UPS; add up to 12 EBMs with SC240RT
SC240RT
240V supercharger module to add up to 12 EBMs to 8 and 11 kVA 9PX UPS models. Includes 4-post rail kit.
EBMCBL240
Cable Extension 8 and 11 kVA UPS models, 6 feet (1.8 meters)
CBLADAPT240
Adapter cable from 9135, MX and EX RT UPS EBMs to 8 and 11 kVA 9PX UPS models
Power distribution & bypass
Catalog number Description
MBP6K208
208V maintenance bypass module
MBP11K208
208V maintenance bypass module
PW105BA2U420
Basic ePDU
ePBZ79
Basic ePDU
PW105BA0U421
PW105BA2U422
Basic ePDU
Basic ePDU
Compatible 9PX models
Input
Output
All non split-phase 5 and 6 kVA models
L6-30P
(2) L6-30R
All non split-phase 8 and 11 kVA models Hardwired Hardwired, (3) L6-30R
9PX5K, 9PX6K, 9PX5KTF5, 9PX6KTF5,
9PX6KP1, 9PX8KTF5, 9PX8K,
L6-30P
(4) L6-20R
9PX11KTF5, 9PX11K
9PX5K, 9PX6K, 9PX5KTF5, 9PX6KTF5,
9PX6KP1, 9PX8KTF5, 9PX8K,
L6-30P
(16) C13, (4) C19
9PX11KTF5, 9PX11K
9PX5KP1, 9PX6KP1, 9PX11KTF11
L14-30P
(24) 5-20R
9PX5KP1, 9PX6KP1, 9PX11KTF11
L14-30P
(4) L6-20R
Dimensions (HxWxD, in.) Weight (lb.)
5.1 (3U) x 17.3 x 25.4
150
5.1 (3U) x 17.3 x 25.4
143
5.1 (3U) x 17.3 x 26.8
34
Dimensions (HxWxD, in.)
3U rackmount
Rear-mount
Weight (lb.)
9
15
3.5 (2U) x 19.0 x 6.0
10
1.7 (1U) x 17.0 x 5.1
6
66.0 (0U) x 1.89 x 2.0
3.5 (2U) x 19.0 x 6.0
10
10
Other hardware accessories
Catalog number
Description
RK2PC
2-post rail kit for 5
and 6 kVA 9PX models
Battery integration
system and caster kit
BINTSYS
Dimensions (HxWxD, in.)
Weight (lb.)
Fits 2-post racks
5
7.9 x 20.5 x 31.5
30
To interact with the 9PX UPS,
please visit: Eaton.com/9PX
Eaton
Electrical Sector
1111 Superior Avenue
Cleveland, OH 44114 USA
Eaton.com
© 2013 Eaton
All Rights Reserved
Printed in USA
9PX01FXA
December 2013
Eaton is a registered trademark
of Eaton.
All other trademarks are property
of their respective owners.
ENERGY STAR and the ENERGY STAR
mark are registered U.S. marks. ENERGY
STAR is a registered mark owned by the
U.S. government.
Product฀Brochure
Eaton 9170+ UPS
Features
•฀ N+X฀redundancy฀for฀both฀power฀and฀logic฀eliminates฀systemlevel฀single฀point-of-failure
•฀ Easily฀scalable฀to฀adapt฀to฀changing฀IT฀environments฀by฀simply฀
adding฀power฀and/or฀battery฀modules
•฀ True฀double-conversion฀design
•฀ ABM®฀technology฀significantly฀increases฀battery฀service฀life
•฀ Universal฀components฀fit฀in฀any฀order฀without฀affecting฀
UPS฀operation
•฀ Provides฀protection฀against฀all฀nine฀power฀problems
•฀ Complete฀offering฀of฀power฀management฀software฀included฀to฀
ensure฀data฀integrity
•฀ Provides฀investment฀protection฀with฀a฀two-year฀limited฀warranty฀
and฀a฀$250,000฀load฀protection฀guarantee฀(U.S.฀and฀Canada)
Product Snapshot
Power Rating:
3–18 kVA
Input Voltage:
200–240 Vac
Output Voltage: 200–240 Vac
Frequency:
50/60 Hz (auto-sensing)
Configuration:
Tower or rackmount
The฀Eaton®฀9170+฀UPS฀is฀uniquely฀designed฀to฀meet฀the฀everchanging฀needs฀of฀customers฀with฀applications฀such฀as฀data฀
centers,฀networks฀and฀call฀centers.฀Built฀for฀global฀deployment,฀the฀
9170+฀is฀a฀scalable,฀modular,฀flexible฀solution฀that฀combines฀the฀
highest฀level฀of฀reliability฀with฀the฀lowest฀cost฀of฀ownership฀฀
in฀the฀3–18฀kVA฀range.
The฀9170+฀enables฀customers฀to฀build฀a฀power฀solution฀specific฀to฀
their฀needs,฀with฀an฀expandable฀level฀of฀redundancy฀and฀increases฀
runtimes฀through฀plug-and-play฀3฀kVA฀UPS฀and฀battery฀modules.฀
The฀9170+฀can฀be฀configured฀to฀fit฀three-,฀six-,฀nine-฀or฀twelve-slot฀
enclosures,฀and฀is฀available฀for฀tower฀and฀rackmount฀applications.฀
The฀9170+฀also฀features฀a฀Power฀Saver฀mode,฀a฀user-selectable฀
feature฀that฀increases฀unit฀efficiency฀from฀88%฀in฀normal฀operating฀
mode฀to฀97%.฀With฀its฀low฀initial฀investment,฀double-conversion฀
technology,฀ABM฀battery฀management฀system฀and฀high-efficiency฀
Power฀Saver฀mode,฀you฀never฀have฀to฀compromise฀reliability฀for฀
efficiency.
Unique฀to฀the฀9170+฀is฀its฀global฀deployment฀capability.฀By฀using฀
a฀high-frequency฀design,฀housing฀both฀logic฀and฀power฀in฀the฀
power฀module,฀and฀offering฀a฀single-cabinet฀design,฀distributors฀
and฀purchasing฀departments฀around฀the฀world฀have฀fewer฀system฀
components฀to฀contend฀with,฀regardless฀of฀where฀the฀system฀is฀
deployed.
Technical spotlight: Network
level N+X redundancy
As฀business฀moves฀from฀a฀“bricks฀and฀mortar”฀model฀to฀“clicks฀
and฀mortar,”฀the฀need฀for฀system฀availability฀at฀all฀levels฀of฀
enterprise฀is฀rising฀exponentially.฀From฀servers฀to฀routers฀to฀
telecommunication฀installations,฀the฀interdependence฀of฀the฀
technological฀components฀of฀the฀wired฀world฀can฀make฀systems฀
vulnerable฀to฀downtime.฀Many฀precautions฀and฀preventive฀
measures฀are฀taken฀when฀designing฀the฀network,฀including฀power฀
protection.
systems฀with฀a฀single-module฀UPS.฀The฀9170+฀overcomes฀this฀
potential฀obstacle฀with฀its฀modular฀design.฀Redundancy฀comes฀
from฀the฀3฀kVA฀power฀modules฀plugged฀into฀the฀system.฀For฀
example,฀if฀you฀have฀a฀9฀kVA฀solution,฀and฀are฀looking฀for฀N+2฀
redundancy,฀you฀only฀need฀a฀15฀kVA฀UPS฀(five฀power฀modules)฀
with฀the฀9170+,฀instead฀of฀18฀kVA.฀That’s฀because฀the฀five฀
UPS฀modules฀run฀in฀parallel฀within฀the฀system,฀giving฀you฀N+2฀
redundancy,฀without฀the฀additional฀cost฀and฀space฀requirements.
In฀this฀shifting฀world,฀however,฀it’s฀becoming฀more฀evident฀that฀
simple฀power฀protection฀isn’t฀enough.฀A฀new฀level฀of฀reliability฀
is฀needed,฀one฀with฀redundancy,฀and฀thereby฀system฀availability.฀
Today฀users฀can฀opt฀for฀an฀even฀greater฀degree฀of฀redundancy,฀
with฀N+1,฀N+2,฀N+3,฀etc.฀However,฀this฀level฀of฀redundancy฀can฀
quickly฀become฀cost฀prohibitive฀if฀the฀user฀is฀creating฀redundant฀
The฀9170+฀eliminates฀a฀system-level฀single฀point-of-failure.฀
Because฀both฀the฀logic฀and฀power฀are฀housed฀in฀the฀module฀and฀
not฀in฀the฀enclosure,฀there฀is฀a฀redundancy฀for฀the฀entire฀UPS.฀
This฀is฀a฀critical฀distinction฀when฀looking฀for฀multiple฀levels฀of฀
redundancy฀in฀the฀UPS,฀as฀there฀is฀inherent฀vulnerability฀in฀a฀UPS฀
that฀limits฀redundancy฀in฀any฀part฀of฀the฀system.฀
Sample configuration
With฀a฀variety฀cabinet฀sizes฀and฀a฀user-friendly฀design฀you฀can฀
configure฀the฀scalable฀and฀redundant฀9170+฀with฀3฀kVA฀power฀
modules฀and฀battery฀modules฀to฀grow฀with฀your฀requirements.฀
5 power modules:
15 kVA or
12 kVA N+1 or
9 kVA N+2
20 battery modules
9-slot UPS enclosure
2
EATON CORPORATION Eaton 9170+ UPS
9-slot battery enclosure
PRE-CONFIGURED SYSTEMS WITH HARDWIRE INPUT AND OUTPUT
POWER
RATING
INPUT
CONNECTION
OUTPUT
CONNECTIONS
DIMENSIONS
H x W x D (IN/CM)
WEIGHT
(LB/KG)
(1)฀3-slot฀enclosure
(1)฀power฀module
(2)฀battery฀modules
(1)฀caster฀kit
3฀kVA฀expandable฀฀
to฀3฀kVA฀N+1
Hardwired
Hardwired
19.5฀x฀17.0฀x฀25.5/฀฀
49.5฀x฀43.0฀x฀65.0
155.0/69.9
(1)฀6-slot฀enclosure฀
(1)฀power฀module
(2)฀battery฀modules
(1)฀caster฀kit
3฀kVA฀expandable฀฀
to฀9฀kVA฀N+X
Hardwired
Hardwired
33.3฀x฀17.0฀x฀25.5/฀฀
84.5฀x฀43.0฀x฀65.0
155.0/69.9
(1)฀6-slot฀enclosure
(2)฀power฀modules
(4)฀battery฀modules
(1)฀caster฀kit
6฀kVA฀expandable฀฀
to฀9฀kVA฀N+X
Hardwired
Hardwired
33.3฀x฀17.0฀x฀25.5/฀฀
84.5฀x฀43.0฀x฀65.0
232.0/104.8
(1)฀6-slot฀enclosure฀
(3)฀power฀modules
(6)฀battery฀modules
(1)฀caster฀kit
9฀kVA฀expandable฀฀
to฀9฀kVA฀N+X
Hardwired
Hardwired
33.3฀x฀17.0฀x฀25.5/฀฀
84.5฀x฀43.0฀x฀65.0
346.0/156.7
PW9S9K
(1)฀9-slot฀enclosure฀
(3)฀power฀modules
(6)฀battery฀modules
9฀kVA฀expandable฀฀
to฀18฀kVA฀N+X
Hardwired
Hardwired
47.0฀x฀24.0฀x฀28.5/฀฀
119.5฀x฀61.0฀x฀72.5
389.0/176.7
PW12S9K
(1)฀12-slot฀enclosure฀
(3)฀power฀modules
(6)฀battery฀modules
9฀kVA฀expandable฀฀
to฀18฀kVA฀N+X
Hardwired
Hardwired
60.7฀x฀24.0฀x฀28.5/฀฀
154.5฀x฀61.0฀x฀28.5
427.0/193.7
PW12S12K
(1)฀12-slot฀enclosure฀
(4)฀power฀modules
(8)฀battery฀modules
12฀kVA฀expandable฀฀
to฀18฀kVA฀N+X
Hardwired
Hardwired
60.7฀x฀24.0฀x฀28.5/฀฀
154.5฀x฀61.0฀x฀28.5
504.0/228.6
PW12S15K
(1)฀12-slot฀enclosure฀
(5)฀power฀modules
(10)฀battery฀modules
15฀kVA฀expandable฀฀
to฀18฀kVA฀N+X
Hardwired
Hardwired
60.7฀x฀24.0฀x฀28.5/฀฀
154.5฀x฀61.0฀x฀28.5
581.0/263.5
PW12S18K
(1)฀12-slot฀enclosure฀
(6)฀power฀modules
(12)฀battery฀modules
18฀kVA฀฀expandable฀
to฀18฀kVA฀N+X
Hardwired
Hardwired
60.7฀x฀24.0฀x฀28.5/฀฀
154.5฀x฀61.0฀x฀28.5
658.0/298.4
MODEL NUMBER
INCLUDED ITEMS
PW3S3K
PW6S3K
PW6S6K
PW6S9K
Pre-configured systems with hardwire input and receptacles output options
(1)฀6-slot฀enclosure฀
(1)฀power฀module
(2)฀battery฀modules
(1)฀caster฀kit
3฀kVA฀expandable฀฀
to฀9฀kVA฀N+X
Hardwired
(2)฀L14-30R,฀
(2)฀L6-30R,฀
(12)฀5-20R
33.3฀x฀17.0฀x฀25.5/฀฀
84.5฀x฀43.0฀x฀65.0
192.0/86.9
(1)฀6-slot฀enclosure฀
(2)฀power฀modules
(4)฀battery฀modules
(1)฀caster฀kit
6฀kVA฀expandable฀฀
to฀9฀kVA฀N+X
Hardwired
(2)฀L14-30R,฀฀
(2)฀L6-30R,฀
(12)฀5-20R
33.3฀x฀17.0฀x฀25.5/฀฀
84.5฀x฀43.0฀x฀65.0
269.0/121.8
(1)฀6-slot฀enclosure฀
(3)฀power฀modules
(6)฀battery฀modules
(1)฀caster฀kit
9฀kVA฀expandable฀฀
to฀9฀kVA฀N+X
Hardwired
(2)฀L14-30R,฀฀
(2)฀L6-30R,฀฀
(12)฀5-20R
33.3฀x฀17.0฀x฀25.5/฀฀
84.5฀x฀43.0฀x฀65.0
346.0/160.7
PW9S9K-PD
(1)฀9-slot฀enclosure฀
(3)฀power฀modules
(6)฀battery฀modules
9฀kVA฀expandable฀฀
to฀18฀kVA฀N+X
Hardwired
(2)฀L14-30R,฀฀
(2)฀L6-30R,฀฀
(12)฀5-20R
47.0฀x฀24.0฀x฀28.5/฀฀
119.5฀x฀61.0฀x฀72.5
389.0/176.7
PW12S9K-PD
(1)฀12-slot฀enclosure฀
(3)฀power฀modules
(6)฀battery฀modules
9฀kVA฀expandable฀฀
to฀18฀kVA฀N+X
Hardwired
(3)฀L14-30R,฀฀
(3)฀L6-30R,฀฀
(12)฀5-20R
60.7฀x฀24.0฀x฀28.5/฀฀
154.5฀x฀61.0฀x฀28.5
427.0/193.7
PW12S12K-PD
(1)฀12-slot฀enclosure฀
(4)฀power฀modules
(8)฀battery฀modules
12฀kVA฀expandable฀฀
to฀18฀kVA฀N+X
Hardwired
(3)฀L14-30R,฀฀
(3)฀L6-30R,฀฀
(12)฀5-20R
60.7฀x฀24.0฀x฀28.5/฀฀
154.5฀x฀61.0฀x฀28.5
504.0/228.6
PW12S15K-PD
(1)฀12-slot฀enclosure฀
(5)฀power฀modules
(10)฀battery฀modules
15฀kVA฀expandable฀฀
to฀18฀kVA฀N+X
Hardwired
(3)฀L14-30R,฀฀
(3)฀L6-30R,฀฀
(12)฀5-20R
60.7฀x฀24.0฀x฀28.5/฀฀
154.5฀x฀61.0฀x฀28.5
581.0/263.5
PW12S18K-PD
(1)฀12-slot฀enclosure฀
(6)฀power฀modules
(12)฀battery฀modules
18฀kVA฀expandable฀฀
to฀18฀kVA฀N+X
Hardwired
(3)฀L14-30R,฀฀
(3)฀L6-30R,฀฀
(12)฀5-20R
60.7฀x฀24.0฀x฀28.5/฀฀
154.5฀x฀61.0฀x฀28.5
658.0/298.4
PW6S3K-PD
PW6S6K-PD
PW6S9K-PD
Pre-configured systems with line cord input and receptacles output options
PW3S3K-LPD
(1)฀3-slot฀enclosure฀
(1)฀power฀module
(2)฀battery฀modules
3฀kVA฀expandable฀฀
to฀3฀kVA฀N+1
L14-30P
(1)฀L14-30R,฀฀
(1)฀L6-30R,฀฀
(4)฀5-20R
19.5฀x฀17.0฀x฀25.5/฀฀
49.5฀x฀43.0฀x฀65.0
155.0/69.9
PW6S3K-LPD
(1)฀6-slot฀enclosure฀
(1)฀power฀module
(2)฀battery฀modules
3฀kVA฀expandable฀฀
to฀6฀kVA฀N+1
14-50P
(2)฀L14-30R,฀฀
(2)฀L6-30R,฀฀
(12)฀5-20R
33.3฀x฀17.0฀x฀25.5/฀฀
84.5฀x฀43.0฀x฀65.0
192.0/86.9
PW6S6K-LPD
(1)฀6-slot฀enclosure฀
(2)฀power฀modules
(4)฀battery฀modules
6฀kVA฀expandable฀฀
to฀6฀kVA฀N+1
14-50P
(2)฀L14-30R,฀฀
(2)฀L6-30R,฀฀
(12)฀5-20R
33.3฀x฀17.0฀x฀25.5/฀฀
84.5฀x฀43.0฀x฀65.0
269.0/121.8
Notes: 50/60 Hz automatic frequency selection. Input/Output voltages 208–240V or 100/200,120/208, 127/220, 110/220 and 120/240V. Split phase power module offers both high and low output voltage. Universal power
module offers only high output voltage. All 3- and 6-slot enclosure dimensions include caster kit.
EATON CORPORATION Eaton 9170+ UPS
3
UPS CABINET ENCLOSURES WITH HARDWIRE INPUT AND OUTPUT CONNECTIONS
POWER
RATING
INPUT
CONNECTION
OUTPUT
CONNECTIONS
DIMENSIONS
H x W x D (IN/CM)
WEIGHT
(LB/KG)
PW9170+ 3-slot
3฀kVA฀
Hardwired
Hardwired
17.8฀x฀17.0฀x฀25.5/฀฀
45.0฀x฀43.0฀x฀65.0
66.0/30.0฀
PW9170+ 6-slot
3฀to฀9฀kVA
Hardwired
Hardwired
31.5฀x฀17.0฀x฀25.0/฀฀
80.0฀x฀43.0฀x฀65.0
103.0/47.0฀
PW9170+ 9-slot
3฀to฀18฀kVA
Hardwired
Hardwired
47.0฀x฀24.0฀x฀28.5/฀฀
119.5฀x฀61.0฀x฀72.5
158.0/72.0฀
Rackmount
3฀to฀18kVA
Hardwired
Hardwired
47.0฀x฀17.0฀x฀28.5/฀
119.5฀x฀43.0฀x฀72.5
110.0/50.0
PW9170+ 12-slot
3฀to฀18฀kVA
Hardwired
Hardwired
60.8฀x฀24.0฀x฀28.5/฀฀
196.0/89.0฀
154.0฀x฀61.0฀x฀72.5฀฀฀฀฀฀
Rackmount
3฀to฀18฀kVA
Hardwired
Hardwired
60.8฀x฀17.0฀x฀28.5/฀
154.0฀x฀43.0฀x฀72.5
148.0/67.0
6-slot battery cabinet
-
DC฀interconnect฀
option฀ASY-0525฀
required
-
31.5฀x฀17.0฀x฀25.0/฀฀
80.0฀x฀43.0฀x฀65.0
93.0/42.2฀
9-slot battery cabinet
-
DC฀interconnect฀
option฀ASY-0525฀
required
-
47.0฀x฀24.0฀x฀28.5/฀฀
119.5฀x฀61.0฀x฀72.5
148.0/67.1฀
12-slot battery cabinet
-
DC฀interconnect฀
option฀ASY-0525฀
required
-
60.8฀x฀24.0฀x฀28.5/฀฀
154.0฀x฀61.0฀x฀72.5
186.0/84.4฀
Split-phase power module
3฀kVA/2.5฀kW
-
-
4.2฀x฀14.1฀x฀15.3/฀฀
10.6฀x฀35.8฀x฀38.9
17.0/7.7฀
Universal-phase power module
3฀kVA/2.1฀kW
-
-
4.2฀x฀14.1฀x฀15.3/฀฀
10.6฀x฀35.8฀x฀38.9
17.0/7.7฀
-฀
-
-
4.2฀x฀7.0฀x฀14.8/฀฀
10.6฀x฀17.8฀x฀37.6
30.0/13.6฀
3฀kVA
-
฀-
4.2฀x฀14.1฀x฀15.3/฀฀
10.6฀x฀35.8฀x฀38.9
17.0/7.7฀
MODEL NUMBER
Battery cabinet enclosures
Available modules
Battery module
20-amp charger module
Technical specifications
1
ELECTRICAL INPUT
Voltage฀ ฀
฀
฀
฀
฀
Voltage฀range฀
฀
Input฀power฀factor฀฀
Frequency฀฀
฀
GENERAL
208–240V฀or฀200/100,฀208/120,฀฀
220/110,฀240/120฀Vac฀฀฀฀฀
176–276V฀
฀
฀
.98฀
฀
฀
฀
50/60฀Hz฀(±3฀Hz)฀ ฀
฀
฀
฀฀฀฀฀
฀฀฀฀฀
ELECTRICAL OUTPUT
On฀utility฀voltage฀฀ ฀
regulation฀
฀
On฀battery฀฀฀
฀
voltage฀regulation฀ ฀
Efficiency฀
฀
mode฀฀ ฀
฀
Frequency฀regulation฀
฀
฀
฀
฀
True฀double-conversion฀online
Full฀system฀self-test฀on฀power฀up฀
Automatic฀on฀overload฀or฀UPS฀failure฀
See฀Pre-configured฀systems฀table฀฀฀
ENVIRONMENTAL AND SAFETY
±3%฀of฀nominal฀
฀
฀
฀
฀฀฀฀฀
±3%฀of฀nominal฀
฀
฀
฀
฀฀฀฀฀
88%฀normal฀operation;฀97%฀power฀saver฀
(optional฀programmable)฀ ฀
฀
±3฀Hz฀online;฀±0.1฀Hz฀on฀battery฀฀
COMMUNICATIONS
LCD฀
฀
฀
฀
฀
฀
Language฀฀
฀
support฀ ฀฀฀฀฀
Communication฀฀ ฀
ports฀
฀฀฀฀฀
Communication฀฀ ฀
slots฀
฀฀฀฀฀
SNMP฀capability฀ ฀
Contact฀closures฀ ฀
Emergency฀power฀off฀฀฀
(EPO)฀general฀
฀
Topology฀฀
Diagnostics฀
UPS฀bypass฀
Dimensions฀&฀฀
weights
4฀x฀20฀character฀backlit฀display,฀฀
programmable฀
฀฀฀฀฀
English,฀French,฀Spanish฀and฀German฀฀
Safety฀markings฀฀ ฀
EMC฀markings฀฀ ฀
Surge฀฀ ฀฀
฀
suppression฀
฀
Audible฀noise฀฀
฀
Ambient฀฀operating/฀
storage฀temperature฀
฀฀
฀
฀
Relative฀humidity฀ ฀
REPO฀port฀
฀
฀
฀
฀
UL,฀cUL฀฀฀
฀
฀
FCC฀class฀A฀
฀
฀
IEEE/ANSI฀C62.41฀฀
฀฀฀฀
<50฀dBA฀฀
฀
฀
0฀to฀40ºC฀(32฀to฀104ºF)/฀
-20฀to฀40ºC฀(60ºC฀without฀battery)฀
-4฀to฀104ºF฀(140ºF฀without฀battery)฀
5%฀to฀95%,฀non-condensing฀
Meets฀NEC฀code฀645-11฀intent฀฀
and฀UL฀requirements฀
฀฀฀฀
฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀฀
฀฀฀฀
฀
BATTERY
RS-232฀(DB-9)฀
฀
Two฀slots฀(standard)฀
฀
Web/SNMP฀enabled฀card฀options฀
Relay฀card฀option฀ ฀
฀
Input฀for฀external฀EPO฀
฀
฀
฀
฀
฀฀฀฀฀
฀
฀฀฀฀฀
฀
Internal฀battery฀฀ ฀
type฀
฀฀฀฀
Battery฀runtime฀ ฀
Battery฀replacement฀฀
Recharge฀time฀
฀
Sealed,฀lead-acid;฀maintenance฀free฀ ฀
See฀Battery฀Runtimes฀on฀back฀page฀
Hot-swappable฀ ฀
฀
<4฀hours฀standard฀฀
฀
฀฀฀฀฀
1. Due to continuing product improvement programs, specifications are subject to change without notice.
EATON CORPORATION Eaton 9170+ UPS
4
LCD panel
9170+ 9-slot configuration
3 kVA power or charger
module (one per slot)
Communication cards
Rackmount
Battery module (two per slot)
Maximum performance
Maximum availability
Maximum flexibility
•฀ The฀lowest฀overall฀cost฀of฀
ownership฀is฀a฀direct฀result฀
of฀the฀low฀initial฀investment,฀
higher฀operating฀efficiencies฀
and฀programmable฀high฀฀
efficiency
•฀ Double-conversion฀online฀
technology฀is฀universally฀
recognized฀as฀providing฀the฀฀
highest฀availability฀in฀an฀
internet-centric฀global฀
marketplace
•฀ Modular฀design฀delivers฀
scalable,฀flexible฀solutions฀
to฀constantly฀changing฀
equipment฀requirements
•฀ A฀UPS฀solution฀that฀is฀as฀
easy฀to฀install฀and฀operate฀as฀
a฀PC฀฀—universal฀components฀
fit฀in฀any฀order฀in฀any฀
slot฀without฀affecting฀the฀
operation฀of฀the฀system฀or฀
its฀protection฀of฀the฀critical฀
load
•฀ Provides฀protection฀against฀฀
all฀nine฀common฀power฀฀
problems
•฀ Easily฀expanded฀by฀installing฀
additional฀power,฀charger฀or฀
battery฀modules฀to฀support฀
additional฀critical฀applications฀
and฀devices
Maximum service plans
•฀ Internal฀options:฀line฀cord,฀
receptacles,฀communications
•฀ Featuring฀user-friendly฀
LCD฀and฀two฀internal฀
communication฀slots,฀which฀
accept฀a฀wide฀variety฀of฀
connectivity฀devices฀and฀
the฀new฀ConnectUPS฀Web/
SNMP฀card
•฀ Lightweight,฀highperformance฀power฀and฀
battery฀modules฀weigh฀under฀
30฀pounds฀for฀easy฀service฀
and฀hot-swapping
Maximum reliability
•฀ N+X฀power฀and฀logic฀
redundancy฀eliminates฀single฀
point-of-failure,฀providing฀
highest฀reliability฀and฀
availability
•฀ Eaton฀Gold฀Plan฀Plus:฀
Enhance฀and฀extend฀your฀
standard฀UPS฀warranty฀with฀
added฀assurance฀of฀knowing฀
your฀UPS฀is฀installed฀and฀
operating฀properly฀from฀฀
the฀start
•฀ Comprehensive฀coverage฀฀
for฀the฀entire฀UPS
Rackmount
configurations
Adding฀yet฀another฀level฀of฀
flexibility฀to฀the฀unique฀design฀
of฀the฀9170+฀is฀the฀ability฀to฀
configure฀it฀into฀a฀rackmount฀
solution.฀Imagine฀all฀the฀
standard฀benefits฀of฀the฀9170+฀
installed฀in฀a฀standard฀19-inch฀
computer฀rack฀with฀return฀
brackets.
•฀ External฀options:฀rackmount฀
kit,฀casters฀(standard฀on฀
9-฀and฀12-slot฀enclosures),฀
extended฀runtime฀battery฀
cabinets฀(housing฀up฀to฀8฀
hours฀of฀additional฀runtime),฀
wall-mounted฀maintenance฀
bypass฀cabinets
•฀ On-site฀startup฀by฀authorized฀
Eaton฀product฀representative
•฀ Replacement฀UPS฀or฀module฀
delivered฀to฀your฀location
•฀ Original฀UPS฀or฀module฀
picked฀up฀from฀your฀location
•฀ Please฀call฀for฀details
•฀ Redundant฀modularity฀
virtually฀eliminates฀downtime฀
and฀enhances฀serviceability
•฀ ABM฀technology฀significantly฀
increases฀battery฀service฀life
EATON CORPORATION Eaton 9170+ UPS
5
9170+ runtime charts
IN MINUTES (FULL LOAD/HALF LOAD) SPLIT-PHASE MODULE ASY-0673
3฀kVA฀
6฀kVA฀
9฀kVA฀
12฀kVA฀
15฀kVA฀
18฀kVA฀
3฀kVA฀
6฀kVA฀
9฀kVA฀
12฀kVA฀
15฀kVA฀
18฀kVA฀
฀
Load (VA) number of strings (two battery modules per string)
1 String 2 String
3 String
4 String
5 String
6 String
7 String
8 String
9 String
10 String
11 String
12 String
6.5/16฀
฀
฀
฀
฀
฀
27.5/67.5฀
11/27.5฀
6.5/16฀
฀
฀
฀
40/98฀
16/40฀
9.5/23.5฀
6.5/16฀
฀
฀
53.5/132฀
21.5/53.5฀
13/31.5฀
9/21.5฀
6.5/16฀
฀
67.5/167฀
27.5/68฀
16/40฀
11/27.5฀
8/20.5฀
6.5/16฀
83/204฀
33.5/83฀
20/49฀
13.5/33.5฀
10/25฀
8/20฀
98/242฀
40/98฀
23.5/58฀
16/40฀
12/30฀
9.5/23.5฀
115/283฀
46.5/115฀
27.5/67.5฀
19/46.5฀
14/35฀
11/27.5฀
132/324฀
53.5/132฀
31.5/78฀
21.5/53.5฀
16/40฀
12.5/30฀
149/365฀
60.5/149฀
35.5/88฀
24.5/60.5฀
18.5/45฀
14.5/35.5฀
167/408฀฀฀฀
67.5/167฀฀฀
40/98฀฀฀฀฀
฀27.5/68฀฀฀
20.5/50.5฀฀
16/40฀฀฀฀฀฀
13 String 14 String 15 String 16 String 17 String
18 String
19 String
20 String
21 String
22 String
23 String
24 String
185/456฀
75/185฀
44/109฀
30.5/75฀
23/56฀
18/44฀
283/692฀
115/285฀
68/167฀
46.5/115฀
35/86฀
27.5/68฀
302/750฀
123/302฀
73/179฀
50/123฀
37.5/92฀
29.5/73฀
323/790฀
132/324฀
78/191฀
53.5/132฀
40/98฀
31.5/78฀
345/850฀
140/345฀
83/204฀
57/140฀
42.5/105฀
33.5/83฀
365/900฀
149/365฀
88/210฀
60/149฀
45/111฀
35.5/88฀
387/955฀
157/388฀
93/229฀
64/157฀
48/118฀
38/93฀
408/1015฀฀
167/408฀฀฀฀
98/242฀฀฀฀฀
68/167฀฀฀฀฀
51/124฀฀฀฀฀
40/98฀฀฀฀฀฀฀
16/40฀
6.5/16฀
฀
฀
฀
฀
204/501฀
83/204฀
49/120฀
33.5/83฀
25/62฀
20/49฀
223/549฀
90/223฀
53.5/132฀
37/90฀
27.5/67.5฀
21.5/53.5฀
242/595฀
98/242฀
58/143฀
40/98฀
30/73.5฀
23.5/58฀
262/640฀
106/262฀
63/154฀
43/106฀
32.5/79.5฀
25.5/63฀
IN MINUTES (FULL LOAD/HALF LOAD) UNIVERSAL MODULE ASY-0674
Load (VA) number of strings (two battery modules per string)
1 String 2 String
3 String
4 String
5 String
6 String
7 String
8 String
9 String
10 String
11 String
12 String
3฀kVA฀
6฀kVA฀
9฀kVA฀
12฀kVA฀
15฀kVA฀
18฀kVA฀
8/24฀
฀
฀
฀
฀
฀
43/95฀
16/40฀
8/24฀
฀
฀
฀
58/140฀
24/59฀
13/35฀
8/24฀
฀
฀
80/175฀
32/83฀
18/46฀
13/33฀
8/24฀
฀
95/215฀
40/103฀
24/59฀
16/40฀
11.5/31฀
8/24฀
119/240฀
49/114฀
29/63฀
19.5/43.5฀
14.5/31.5฀
11/31.5฀
135/290฀
58/140฀
35/86฀
24/59฀
18/46฀
13/36฀
155/335฀
69/156฀
40/103฀
29/70฀
20.5/51฀
15.5/41฀
65/365฀
83/175฀
46/115฀
33/80฀
24/58฀
18/45฀
200/395฀
90/190฀
54/125฀
36/90฀
28/66฀
20.5/51฀
215/450฀
103/205฀฀฀
58/140฀฀฀฀฀฀
41/100฀฀฀฀฀
31/73฀฀฀฀฀฀
24/58฀฀฀฀฀
13 String 14 String 15 String 16 String 17 String
18 String
19 String
20 String
21 String
22 String
23 String
24 String
3฀kVA฀
6฀kVA฀
9฀kVA฀
12฀kVA฀
15฀kVA฀
18฀kVA฀
225/500฀
113/335฀
63/150฀
47/110฀
34/83฀
27/65฀
335/690฀
156/333฀
100/210฀
70/156฀
51/127฀
41/100฀
350/720฀
165/350฀
107/225฀
75/165฀
56/130฀
44/105฀
365/780฀
175/365฀
115/240฀
80/175฀
58/140฀
45/115฀
375/850฀
183/385฀
121/255฀
85/185฀
61/149฀
48/122฀
395/890฀
190/395฀
125/270฀
90/195฀
66/158฀
54/131฀
425/920฀
198/420฀
135/280฀
95/205฀
71/165฀
57/137฀
450/950฀฀฀
205/440฀฀฀
143/290฀฀฀฀
100/215฀฀฀฀
73/170฀฀฀฀฀
58/140
24/59฀
8/24฀
฀
฀
฀
฀
245/540฀
123/255฀
73/165฀
52/121฀
38/94฀
31.5/72฀
270/600฀
135/273฀
80/178฀
56/130฀
41.5/103฀
34.5/77฀
290/620฀
143/290฀
86/190฀
58/140฀
44.5/113฀
36/83฀
315/650฀
148/315฀
93/200฀
65/147฀
46.5/117฀
38/94฀
For additional information about the
9170+, please visit Eaton.com/9170+
or call 800.356.5794.
Eaton Corporation
Electrical Sector
1111 Superior Avenue
Cleveland, OH 44114 USA
Eaton.com
© 2012 Eaton Corporation
All Rights Reserved
Printed in USA
9170PLFXA
November 2012
Eaton is a registered trademark
of Eaton Corporation.
All other trademarks are property
of their respective owners.
Eaton BladeUPS Maintenance
Bypass Module (MBM)
Features
•฀ Three-Breaker฀Maintenance฀Bypass
฀ ฀
•฀฀Maintenance฀bypass฀breaker,฀rectifier฀input฀breaker฀and฀UPS฀
output฀breaker฀all฀rated฀for฀225A฀@208V฀(150A฀@400V)฀for฀
high฀availability฀even฀as฀the฀UPS฀is฀serviced
•฀ 6U฀Rackmount฀Cabinet
฀ ฀
•฀฀60฀kW฀N+1฀maintenance฀bypass฀in฀just฀6U฀of฀rack฀space;฀
matching฀front฀bezel฀blends฀MBM฀into฀existing฀racks฀of฀
Eaton®฀BladeUPS®฀extended฀battery฀modules
•฀ Breaker฀Interlock฀Bar
฀ ฀
•฀฀Ensures฀correct฀breaker฀sequencing฀during฀transition฀to฀
bypass฀and฀return฀to฀online
•฀ Activate฀UPS฀Bypass฀Mode฀Switch
฀ ฀
•฀฀With฀the฀press฀of฀this฀single฀switch฀the฀BladeUPS฀rack฀is฀
automatically฀placed฀into฀bypass฀and฀the฀entire฀system฀is฀
readied฀for฀the฀transfer฀of฀power
•฀ Designed฀to฀go฀into฀top฀or฀bottom฀of฀the฀enclosure฀(rack)
฀ ฀
•฀฀The฀MBM฀has฀three฀removable฀conduit฀landing฀plates฀on฀
the฀top฀and฀bottom฀of฀the฀cabinet฀to฀ensure฀cable฀entry฀
can฀be฀accommodated฀for฀raised฀floor฀or฀overhead฀wiring฀
installations
The Eaton BladeUPS
Maintenance Bypass Module
(MBM) is a fully featured
maintenance bypass designed
to transfer power from a
fully populated 60 kW N+1
BladeUPS system into bypass,
allowing maintenance and
service to be performed on a
de-energized BladeUPS cabinet
without affecting power to the
critical load. Factory installed
225A @208V (150A @400V)
maintenance bypass breaker
(MBB), UPS Input Breaker (UIB)
and UPS output breaker (UOB).
A breaker interlock bar ensures
the proper sequencing of the
MBB and UOB when bringing the
BladeUPS cabinet off and online.
The MBM’s Activate UPS
Bypass Mode switch simplifies
the process of going to bypass
even further by providing a
single point to transfer all
BladeUPS units into bypass, and
ready the system for the transfer
of power.
The MBM is designed to fit
seamlessly into your data center
environment while occupying
minimal space. The 6U housing
features front panels designed
to mimic the look of BladeUPS
EBM extended battery modules
(EBMs) so that it will fit
aesthetically into your BladeUPS
rack. Behind the removable
front panels are four LEDs that
highlight the current power flow
of the system and enhance the
safety and security of on-site
operators.
The MBM also features a shunt
trip on the bypass breaker
for interfacing with remote
emergency power-off (EPO)
systems, and all breakers have
auxillary contacts (NC and
NO available) for breaker on/
off sensing for integration with
building control or monitoring
systems.
Technical specifications
ENVIRONMENTAL SPECIFICATIONS
GENERAL CHARACTERISTICS
Type
Three-breaker, manual interlock
Installation
Rack mounted, 6U
Input & Output Cabling
Top and bottom entry
Designed kVA/kW rating
60 kVA/60 kW
Color
Black bezels matching BladeUPS
Construction
NEMA 1, IP 23
INPUT/OUTPUT RATINGS 208V MODEL 103007415-5208
Input Voltage
120/208V: Three-phase
Frequency
50/60 Hz
Input Connection
Hardwire 3P + N + PE
Output Voltage
120/208V: Three-phase
Ambient Temperature
0°C to +40°C
+32°F to +104°F
Storage Temperature
-20°C to +70°C
-4°F to +158°F
Relative Humidity
5-95% non-condensing
Altitude
2000 meters (6560ft.) at 40°C/104°F
Audible Noise
Less than 50 dBA at 1 meter
CERTIFICATIONS
Safety
UL 1778 4th edition
IEC 60950-1 edition 1
IEC 62040-1-1 edition 1
EMC
IEC 62040-2 edition 2
Quality
ISO 9001:2000
ISO 14001, 2006
Markings
UL, cUl, CE
ELECTRICAL RATINGS 208V MODEL 103007415-5208
Hazardous materials
RoHS, EU Directive 2002/95/EC Cat. 3
Breaker Frame
225A
USER INTERFACE
Trip rating
225A
Breaker kAIC rating
65kA @ 240V
Frequency
50/60 Hz
Output Connection
Hardwire 3 or 4W + PE
UPS interface
Activate UPS bypass mode switch
Indicator lamps
UPS on bypass
AC Power to bypass
AC Power from UPS
AC Power to loads
Building interface
REPO, 120 V external contact required
1A/1B Aux switch on all breakers
INPUT/OUTPUT RATINGS 400V MODEL 103007415-5400
Input Voltage
230/400V: Three-phase
Frequency
50/60 Hz
Input Connection
Hardwire 3P + N + PE
Output Voltage
230/400V: Three-phase
Frequency
50/60 Hz
PHYSICAL CHARACTERISTICS
Output Connection
Hardwire 3 or 4W + PE
10.5“H x 17.3“W x 29.6“D
Control wire harness provided between UPS and breakers
Weight: 76 lb/34 Kg
ELECTRICAL RATINGS 400V MODEL 103007415-5400
Breaker Frame
225A
Trip rating
150A
Breaker kAIC rating
25kA @ 480V
Front panel with cover removed
UNITED STATES
8609 Six Forks Road
Raleigh, NC 27615 U.S.A.
Toll Free: 1.800.356.5794
www.eaton.com/powerquality
CANADA
Ontario: 416.798.0112
Toll free: 1.800.461.9166
LATIN AMERICA
Argentina: 54.11.4124.4000
Brazil: 55.11.3616.8500
Caribbean: 1.949.452.9610
Mexico & Central America:
52.55.9000.5252
South Cone: 54.11.4343.6323
EUROPE/MIDDLE EAST/AFRICA
Denmark: 45.3686.7910
Finland: 358.94.52.661
France: 33.1.6012.7400
Germany: 49.0.7841.604.0
Italy: 39.02.66.04.05.40
Norway: 47.23.03.65.50
Portugal: 55.11.3616.8500
Sweden: 46.8.598.940.00
United Kingdom: 44.1753.608.700
Rear view of termination points
ASIA PACIFIC
Australia: 61.2.9693.9366
New Zealand: 64.0.3.343.3314
China: 86.21.6361.5599
HK/Korea/Taiwan: 852.2745.6682
India: 91.11.4223.2300
Singapore/SEA: 65.6825.1668
Eaton, BladeUPS and Powerware are trade
names, trademarks and/or service marks
of Eaton Corporation or its subsidiaries
and affiliates.
©2009 Eaton Corporation
All Rights Reserved
Printed in USA
BladeUPS04FXA
September 2009
Download PDF