Watlow Series L LF, LV Temperature Limit Controller User's Manual
Below you will find brief information for Temperature Limit Controller Series L LF, Temperature Limit Controller Series L LV. Watlow's Series L family of temperature limit controllers* provide an economical limit controller solution for applications where thermal system protection is needed. This manual describes the features and benefits, installation, wiring, user interface, troubleshooting, and specifications of the Series L limit controllers.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
▼
Scroll to page 2
of
20
Series L User’s Manual Series L - Temperature Limit TOTAL CUS CUSTOMER ER SATISF TISFACTI CTION 3 Year Warranty ISO 9001 Registered Company 1241 Bundy Boulevard., Winona, Minnesota USA 55987 Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507 http://www.watlow.com 0600-0044-0001 Rev. B February 2004 Winona, Minnesota USA Made in the U.S.A. $5.00 Safety Information We use note, caution and warning symbols throughout this book to draw your attention to important operational and safety information. A “NOTE” marks a short message to alert you to an important detail. ç CAUTION or WARNING Ó Electrical Shock Hazard CAUTION or WARNING A “CAUTION” safety alert appears with information that is important for protecting your equipment and performance. Be especially careful to read and follow all cautions that apply to your application. A “WARNING” safety alert appears with information that is important for protecting you, others and equipment from damage. Pay very close attention to all warnings that apply to your application. The safety alert symbol, ç (an exclamation point in a triangle) precedes a general CAUTION or WARNING statement. The electrical hazard symbol, Ó (a lightning bolt in a triangle) precedes an electric shock hazard CAUTION or WARNING safety statement. Technical Assistance If you encounter a problem with your Watlow controller, review your configuration information to verify that your selections are consistent with your application: inputs, outputs, alarms, limits, etc. If the problem persists, you can get technical assistance from your local Watlow representative (see back cover), by e-mailing your questions to [email protected] or by dialing +1 (507) 494-5656 between 7 a.m. and 5 p.m., Central Standard Time (CST). Ask for for an Applications Engineer. Please have the following information available when calling: • Complete model number • System wiring information • Series L Limit User’s Manual Warranty These controllers are manufactured by ISO 9001-registered processes and are backed by a three-year warranty. Return Material Authorization (RMA) 1. Call Watlow Customer Service, (507) 454-5300, for a Return Material Authorization (RMA) number before returning any item for repair. We need this information: • Ship to address • Bill to address • Contact name • Phone number • Method of return shipment • Your P.O. number • Detailed description of the problem • Any special instructions • Name and phone number of person returning the product. 2. Prior approval and an RMA number, from the Customer Service Department, is needed when returning any unused product for credit. Make sure the RMA number is on the outside of the carton, and on all paperwork returned. Ship on a Freight Prepaid basis. 3. After we receive your return, we will examine it and try to verify the reason for the return. 4. In cases of manufacturing defect, we will enter a repair order, replacement order or issue credit for material returned. 5. To return products that are not defective, goods must be be in new condition, in the original boxes and they must be returned within 120 days of receipt. A 20 percent restocking charge is applied for all returned stock controls and accessories. 6. If the unit is unrepairable, it will be returned to you with a letter of explanation. 7. Watlow reserves the right to charge for no trouble found (NTF) returns. The Series L Limit user’s manual is copyrighted by Watlow Winona, Inc., © February 2004 with all rights reserved. 1 Overview Watlow's Series L family of temperature limit controllers* provide an economical limit controller solution for applications where thermal system protection is needed. A limit controller is added to applications to prevent over or under temperature conditions. The limit provides safety assurances against instances where a thermal runaway condition occurs as a result of a failed sensor, controller or output device. The Series L limit controller is recommended for any application where thermal system runaway could result in large product scrap costs, damage to system equipment, potential fire hazard or risk to personnel. All Series L limit controllers are Factory Mutual and CSA approved. These controllers are available with or without an operator interface and can be ordered in square 1/8th DIN panel mount, din rail mount, open board or potted module design configurations. Push-on, quick connect spade terminal or removable screw clamp style terminal block ordering options provide the electrical connections. The microprocessor design platform provides improvements in the performance, repeatability, and accuracy offered by Watlow's current line of basic control products. The Series LV includes an operator interface to allow viewing and selection of the limit set point. A red four character, seven segment LED displays the limit set point. The limit set point selection is made with a continuous turn, velocity sensitive rotary encoder. Push to Set operation reduces accidental limit set point adjustments. Limit set point operating range temperature values are customer definable in the product configuration part number. The Series LF offers fixed limit set points. These units are supplied without an operator interface. Limit set point temperature values are customer definable in the product configuration part number. The features and performance of these products make them ideally suited for a wide range of industrial limit control applications in the food preparation, industrial machinery, packaging and plastic markets. Watlow's Series L limit controllers include industry leading service, support and a 3-year warranty. Features and Benefits Four Character LED Display · Improves limit set point adjustment accuracy. Fixed or Adjustable Limit Set Points · Tamper proof operation. · Control flexibility. Push to Set · Reduce accidental limit set point adjustments. Multiple Mounting Options · Minimizes installation time. High or Low Limit Operation · Application flexibility. Fahrenheit or Celsius Operation with Indication · Application flexibility. Sensor Break Protection · Provides positive system shutdown. Agency Approvals · Meets requirements for agency certification. Micro Processor Based Technology · Accurate and repeatable protection. Stock to Four Day Delivery *Also available, Series C, an on-off temperature controller version. Watlow Series L ■ 1 ■ Over view 2 Installation Installing the Open Board Controller 61.7 mm 2.43 in 45.07 mm 1.775 in 61.7 mm 2.43 in 56.3 mm 2.22 in 61.7 mm 2.43 in 45.07 mm 1.775 in 56.3 mm 2.22 in SWDC+ .6 N.O. 55.9 mm 2.20 in 61.7 mm 2.43 in SWDC- .7 COM 55.9 mm 2.20 in N.C. .8 L1 L2 .9 .10 Terminal Designation Sticker Use M2.5 (#4) mounting hardware, not included Terminal Designation Sticker Use M2.5 (#4) mounting hardware, not included Screw Terminal Model Spade Terminal Model Figure 2a 1. Locate and drill four 3.2 mm (0.125 in) holes in the desired panel location. See Figure 2a for hole locations. 2. Mount the controller using four M2.5 (#4) screws. Installing the Potted Controller Terminal Designation Sticker 46.6 mm 1.84 in 70.1 mm 2.76 in 35.1 mm 1.38 in 35.1 mm 1.38 in 102.9 mm 4.05 in 88.9 mm 3.50 in Terminal Designation Sticker Terminal Designation Sticker Use [3.5M] #6 hardware, not included Figure 2b 1. Drill two 5 mm (0.187 in) diameter holes in the desired panel location. See Figure 2b for hole locations. 2. Mount the controller using two M3.5 (#6) screws. Watlow Series L ■ 2 ■ Installation Installing the DIN Rail Mount Controller 94.7 mm 3.73 in 78.1 mm 3.08 in To install or remove, press down here. See Installing/ Removing the DIN Rail Controller procedures below. 90.7 mm 3.57 in 39.1 mm 1.54 in Part Number Label DIN rail, upper mounting clip 101.6 mm 4.00 in 80.3 mm 3.16 in 1. SW-1 112.3 mm 4.42 in 2. SW-2 3. TC-/S1 35 mm x 7.5 mm DIN rail is not included with the assembly 4. TC+/S2 5. S3 Terminal Designation Sticker Agency Label Panel mounting the bracket requires two M3.5 (#6) screws, not included To install, press in here. To remove, pull out here. See Mounting/Removing the DIN Rail Controller procedures below. Spade Terminal Model Screw Terminal Model Figure 3a Sub-Panel Mounting 1. Using the controller as a location template, mark both mounting holes. 2. Drill and tap two 2.7 mm (0.106 in) diameter holes in the desired panel location. See Figure 3a above for hole locations. 3. Mount the controller using two M3.5 (#6) screws. DIN Rail Mounting 1. Place the DIN rail upper mounting clip on the top edge of the DIN rail. See Figure 3a. DIN rail spec, DIN 50022, 35 mm x 7.5 mm (1.38 in x 0.30 in). 2. Press down firmly on the top back edge of the DIN rail bracket and push in on the bottom, front edge of the bracket, . The controller “snaps” securely onto the rail. See Figure 3a. If the controller does not snap on, check to see if the DIN rail is bent. Minimum clipping distance is 34.8 mm (1.37 in), the maximum is 35.3 mm (1.39 in). Removing the DIN Rail Controller 1. Remove power from the system. 2. Remove all the wiring connections from the back of the controller. 3. While pressing down on the top, back edge of the DIN rail bracket, pull forward on the bottom, front edge of the DIN rail bracket. See Figure 3a. Press forward with thumb Removing the Controller from the DIN Rail Bracket 1. Remove power from the system. 2. Remove all the wiring connections from the back of the controller. 3. Remove the DIN rail bracket from the DIN rail. 4. Insert a flat blade screwdriver between the DIN rail bracket and the case. Rotate the screwdriver to release the DIN rail bracket hooks from the ridges on the case, while firmly pushing the controller out the front of the DIN rail bracket. Alternate back and forth between the top and then the bottom. Be sure to support the controller as it comes out of the bracket. See Figure 3b. ç Caution: FM approval requires limit switches to be suitably enclosed to restrict casual user adjustment. Watlow Series L Insert flat blade screwdriver here Figure 3b ■ 3 ■ Installation Installing the Square 1/8 DIN Panel Mount Controller 72.4 mm 2.85 in 68.0 mm 2.68 in Panel Cutout Panel Thickness 1.52 to 3.18 mm (0.060 to 0.125 in) 72.4 mm 2.85 in 68.0 mm 2.68 in 19.1 mm 0.75 in minimum 19.1 mm 0.75 in minimum Spade Terminal Model Customer Front Panel Part Number Label Terminal Blocks Locations on Screw Terminal Models 84.5 mm square 3.33 in Mounting Bracket Spade Terminal Model 19.2 mm 0.76 in 51.7 mm 2.04 in Screw Terminal Models Contact your local Greenlee supplier for the appropriate punch kit and cutout tool for rapid mounting. Figure 4 1. Make the panel cutout using the mounting dimensions above. 2. Remove mounting bracket from the back of the controller. 2. Insert the controller into the panel cutout. 3. While pressing the bezel firmly against the panel, slide the mounting bracket over the back of the controller. Be sure the levers on the mounting bracket line up with the teeth on the case. 4. Press the bracket up to the back of the panel. The controller should fit tightly in the panel cutout. Removing the Panel Mount Square 1/8 DIN Controller 1. Remove power from the system. 2. Remove all the wiring connections from the back of the controller. 3. Slide a thin, wide tool (putty knife) under all three mounting tabs, top then bottom, while pushing forward on the back of the case. Be ready to support the controller as it slides out of the panel cutout. ç Caution: FM approval requires limit switches to be suitably enclosed to restrict casual user adjustment. Watlow Series L ■ 4 ■ Installation 3 Wiring Ó Warning: Use National Electric (NEC) or other country-specific standard wiring and safety practices when wiring and connecting this controller to a power source and to electrical sensors or peripheral devices. Failure to do so may result in damage to equipment and property, and/or injury or loss of life. The terminals on the back of the Series L limits are the same for all of the package styles. They are 6.3 mm (0.25 in) quick connect, push on style terminals or removable screw terminal block. The terminal style is an ordering option. Check the part number to determine your hardware configuration. Refer to the wiring diagrams appropriate for your controller’s configuration. All outputs are referenced to a de-energized state. Wiring Guidelines 1. Use the correct thermocouple type per the model number on the case sticker of the unit. See dimension drawings for sticker locations. • Use correct thermocouple polarity. Red is usually negative. • If you must extend thermocouple leads, use thermocouple extension wire to minimize errors. • Note: Insulated terminals required for quick connect style terminals. For quick connect terminals 1, 2, 6, 7, 8, 9, and 10, AMP P/N 3520406-2 or equivalent recommended. Use Amp crimp tool P/N 58078-3, insert 90391-3. For quick connect terminals 3, 4, and 5, AMP P/N 2-520405-2 or equivalent recommended. Amp crimp tool P/N 58078-3, insert 58079-3. ç Caution: FM approval requires limit switches to be suitably enclosed to restrict casual user adjustment. Watlow Series L Be sure you have good crimp connections on all wire connections. • Insulate the thermocouple mounting from the mounting surface to prevent heat migration input errors. • Thermocouple leads should be routed separately from any high voltage lines. • Long lead lengths create electrical resistance. When using a two-wire RTD, there will be an additional 2.6° C (4.7° F) error for every 1Ω of lead length resistance. That resistance when added to the resistance of the RTD element, can result in erroneous input to the temperature controller. 2. In electrically-noisy environments (heavy switching contactors, motors, solenoids, etc.), use shielded thermocouple lead wire with the shield connected at the sensor end only. 3. Use a separate thermocouple to maintain the limit function of this controller; do not parallel thermocouple input from the primary controller. 4. All wiring and fusing must conform to the National Electric Code (NEC) NFPA70 and any other locally applicable codes. 5. Fuse the independent load voltage on the L1 (hot) side and connect it to the common (C) side of the relay. Note: The model number determines the connection terminal style. See below for terminal locations. 1 2 3 4 5 6 7 8 9 10 ■ 5 ■ 1 2 3 4 5 6 7 8 9 10 Wiring ç Warning: Use National Electric (NEC) or other country-specific standard wiring and safety practices when wiring and connecting this controller to a power source and to electrical sensors or peripheral devices. Failure to do so may result in damage to equipment and property, and/or injury or loss of life. Figure 6a — AC Power Wiring • Nominal voltage options: - 24VÅ (ac) - 120VÅ (ac) - 230 to 240VÅ (ac) 1 2 3 4 5 6 7 8 L2 9 L1 10 L2 L1 Ó WARNING: If high voltage is applied to a low-voltage controller, irreversible damage will occur. Note: Insulated terminals required for quick connect style terminals. For quick connect terminals 1, 2, 6, 7, 8, 9, and 10, AMP P/N 3520406-2 or equivalent recommended. Use Amp crimp tool P/N 58078-3, insert 90391-3. Figure 6b — Thermocouple Input Thermocouples are polarity sensitive. The negative lead (usually red) must be connected to TC-. • Input impedance: >10 MΩ 1 2 Thermocouple - TC- Thermocouple + TC+ 3 4 5 6 7 8 9 10 For quick connect terminals 3, 4, and 5, AMP P/N 2-520405-2 or equivalent recommended. Amp crimp tool P/N 58078-3, insert 58079-3. Figure 6c — RTD Input (100 Ω Platinum DIN curve 0.00385 Ω/Ω/°C) • Terminals S2 and S3 must be shorted for a two-wire RTD • Nominal excitation current: 125 µA 3-Wire RTD* 2-Wire RTD RTD S1 RTD S1 RTD S2 RTD S3 RTD S2 S3 1 2 S1 3 S2 4 S3 5 6 7 8 9 10 *No lead resistance compensation Watlow Series L ■ 6 ■ Wiring ç Warning: Use National Electric (NEC) or other country-specific standard wiring and safety practices when wiring and connecting this controller to a power source and to electrical sensors or peripheral devices. Failure to do so may result in damage to equipment and property, and/or injury or loss of life. Note: Use of an external reset switch may affect FM approval. Only the use of a momentary N.O. switch is valid for approval. Figure 7a — External Reset Switch • Momentary normally open (N.O.), dry contact closure SW-1 1 SW-2 2 Momentary N.O. Switch (customer supplied) 6 7 3 8 4 5 9 10 Figure 7b — Mechanical Relay Output • Form C contacts • 8 A, resistive • 250 VA pilot duty, 120/240VÅ (ac), inductive • 240VÅ (ac) maximum • 30VÎ (dc) maximum Note: Insulated terminals required for quick connect style terminals. • See Quencharc note • For use with ac or dc • Minimum load current 100 mA For quick connect terminals 1, 2, 6, 7, 8, 9, and 10, AMP P/N 3-520406-2 or equivalent recommended. Use Amp crimp tool P/N 58078-3, insert 90391-3. For quick connect terminals 3, 4, and 5, AMP P/N 2520405-2 or equivalent recommended. Amp crimp tool P/N 58078-3, insert 58079-3. • Output does not supply power Customer supplied Quencharc for pilot duty, inductive loads only. See note. External Load 1 2 6 N.O. Normally Open C Common 7 N.C. Normally Closed 8 3 4 5 L2 L1 9 Mechanical Relay 10 N.O. COM. Quencharc Note: Switching pilot duty loads (relay coils, solenoids, etc.) with the mechanical relay output option requires use of an R.C. suppressor. N.C. Internal Circuitry Watlow carries the R.C. suppressor Quencharc brand name, which is a trademark of ITW Paktron. Watlow Part No. 0804-0147-0000. Watlow Series L ■ 7 ■ Wiring System Wiring Examples Power Disconnect Switch L1 120V~(ac) L2 Fuse Customer Supplied Quencharc Fuse Not used 1 2 Fuse High Limit Mechanical Contactor coil Fuse 6 SWDC+ SWDC7 8 L2 9 TC- 3 TC+ 4 5 10 Reset Switch (customer supplied) SW-1 SW-2 L1 + SSR-240-10A-DC1 in out Solid-State Relay Series CV Temperature Controller CV-B1JH-0000-0100-C 1 2 TC- N.O. COM 7 N.C. 8 L2 9 6 3 TC+ 4 5 L1 10 Heater Series LF Limit Control LF-C4JW-0120-AAAA-A Limit Sensor Process Sensor 120V (ac) L1 L2 Series CV Temperature Controller CV-B1JH-0000-0100-C Power Disconnect Switch 1 1 HighTemp. Light 10 L1 3 2 4 (+) 3 5 (-) L2 9 4 TC+ 3 TC- SWDC+ 6 4 2 SWDC7 6 7 (+) V 3 to 32 (dc) in (-) SSR-240-10A-DC1 Solid-State Relay 1 CR-1 5 1 8 1 11 48 to 260 V out 9 10 L1 6 SW-1 1 8 14 (+) 10 15 (-) 11 12 1 4 2 L2 9 7 9 Heater 10 TC+ SW-2 2 3 TC7 COM 17 13 N.O. 6 16 N.C. 8 13 2 12 18 Series LF Limit Controller LF-C4JW-0120-AAAA-A 1 CR R 2 2 High-Temperature Light Figure 8 — System Wiring Examples Watlow Series L ■ 8 ■ Wiring 4 User Interface LV XXXX XXXX XXXX A LIMIT LV F C LED Display: Indicates the limit set point. F or C Indicator Light: Lit to indicate if unit is configured for degrees Fahrenheit or degrees Celsius. ALARM SET PUSH/RESET Key: Press and hold key to adjust the limit set point temperature. New limit set point is entered 3 seconds after the knob stops moving. Press key to reset latched limit output once temperature is back in safe region. Can also be reset through customer supplied external reset switch. ALARM Indicator Light: Lit when limit is tripped. RESET Finger Tip Indent: Insert finger tip into indent for quick and easy set point changes. Limit Set Point Knob: To increase limit set point, turn knob clockwise. To decrease limit set point, turn knob counterclockwise. The new set point is entered 3 seconds after the knob stops moving. Limit set point will not change unless PUSH/RESET key is pressed. Figure 9 — Variable Limit Set Point, Standard Interface ç Caution: FM approval requires limit switches to be suitably enclosed to restrict casual user adjustment. Watlow Series L ■ 9 ■ User Inter face Troubleshooting On indicating limits, the display is not illuminated. • Power supply switch off. • Fuse blown. • Breaker tripped. • Safety interlock door switch activated. • Wiring incorrect or open. • Power supply voltage incorrect. • Defective limit. • Turn switch on. • Replace fuse (check cause of failure). • Reset breaker (check cause of failure). • Close door. • Check wiring. • Verify input power • Repair or replace limit. Troubleshooting thermocouple inputs Temperature reading is in• Sensor or limit may be bad. Sensor concorrect, showing a sensor er- nections may be bad. ror, [Er;In] , or ALARM LED is switching at the wrong temperature. • Ambient temperature in the control cabinet is over 70°C. • Ground loop problem. Can occur when using a switched DC output and a grounded thermocouple. Temperature seems to be decreasing, but actual process is increasing. • Thermocouple polarity is reversed. In the US, red wire insulation denotes the negative wire. • Place a jumper wire across the thermocouple input terminals. The display should indicate ambient temperature. If it does, the limit is OK. - For high limit: Start with limit set point above ambient temperature, ALARM LED should be off. Decrease limit set point until ALARM LED goes on. It should be approximately ambient temperature. - For low limit: Start with limit set point below ambient temperature, ALARM LED should be off. Increase limit set point until ALARM LED goes on. It should be approximately ambient temperature. • Measure temperature in cabinet to ensure it is below 70C. Vent cabinet or add fans if necessary. • Remove power from the system. Use an ohm meter to measure resistance between output DC- and the thermocouple sheath. If there is continuity, replace sensor with an ungrounded thermocouple. • Check thermocouple connections. All connections, including extension wire must maintain the correct polarity. Correct polarity problems. Temperature seems to be • Sensor is bad. Thermocouple is shorted. reading low and not increasing while actual process temperature is increasing. • Check thermocouple connections. Check thermocouple wire insulation to make sure it is not damaged, causing the wires to short (making a new junction). Temperature seems to be offset from actual process temperature, or the ALARM LED switches on at the wrong temperature. The offset changes with changes in process temperature. • Check thermocouple connections. Check to make sure that only thermocouple extension wire of the correct type was used to extend thermocouple leads. Replace if necessary. Watlow Series L • Copper wire was used instead of thermocouple extension wire. Connectors of metals different than thermocouple metal were used to splice or make connections. ■ 10 ■ Troubleshooting Indication Probable Cause(s) Corrective Action Troubleshooting RTD inputs Temperature reading is incor- • Sensor or limit may be bad. Sensor conrect, showing a sensor error, nections may be bad. [Er;In] , or ALARM LED is switching at the wrong temperature. • Place a 110 ohm resistor across the sensor input terminals. - For high limit: Start with limit set point above ambient temperature, ALARM LED should be off. Decrease limit set point until ALARM LED goes on. It should be approximately ambient temperature. If it does, the limit is OK. Sensor or connections may be bad. - For low limit: Start with limit set point below ambient temperature, ALARM LED should be off. Increase limit set point until ALARM LED goes on. It should be approximately ambient temperature. If it does, the limit is OK. Sensor or connections may be bad. • Ambient temperature in the control cab- • Measure temperature in cabinet to ensure it is below 70°C (158°F). Vent cabiinet is over 70°C (158°F). net or add fans if necessary. • Sensor connections may be bad. Exces- • Check sensor connections. Measure lead wire resistance. There will be a 2.6C sive lead wire resistance. (4.7°F) error for every ohm of lead wire resistance. Troubleshooting limit outputs ALARM is not tripped when it should be. ALARM LED is not on (relay is energized in safe condition, N.O. contact is closed and N.C. contact is open). • Temperature appears to be incorrect. See input troubleshooting. • See input troubleshooting. • Limit set point is not set correctly. • Verify limit set point setting. ALARM is tripped when it should not be. ALARM LED is on (relay is de-energized in limit condition, N.O. contact is open and N.C. contact is closed). • Limit output is tripped (latched). • Press RESET key to reset limit. • Output wiring is incorrect. • Verify wiring. Relay outputs act as a switch, they do not source power. • See input troubleshooting. Limit output signal is on when it should not be on. Load LED is on. Limit load is on when it should be off. ALARM LED is off. • Temperature appears to be incorrect, see input troubleshooting. • Limit set point is not set correctly. • Verify limit set point setting. • Limit output is defective. • Repair or replace limit. • Temperature reading is incorrect on dis- • See input troubleshooting. play of indicating controls or limit, see input troubleshooting. • Set point is not set correctly • Verify limit set point setting. • Power switching device (mechanical relay, contactor, etc.) is shorted. Limit output shorted. • Remove wires from output of limit to input of power switching device. If load is still on, replace power switching device. If load turns off, replace limit or sensor. See input troubleshooting.. • Verify wiring. • Output wiring is incorrect. Watlow Series L ■ 11 ■ Troubleshooting Specifications Controller • Microprocessor based, limit controller. • Nominal switching hysteresis, typically 1.7°C (3°F) • High or low limit, factory selectable. • Latching output requires manual reset upon over or under temperature condition. • Manual or automatic reset on power loss, factory selectable. • Internal front panel or external customer supplied momentary reset switch. • Input filter time: 1 second. Operator Interface (model dependent) • Four digit , 7 segment LED displays, .28" high. • °F or °C indicator LED. • ALARM indicator LED. • Continuous turn, velocity sensitive rotary encoder for limit set point adjustment. • Front panel SET/RESET key on variable set point models. • No operator interface on fixed set point models. Standard Conditions For Specifications • Rated line voltage, 50 to 60Hz, 0 to 90% RH noncondensing, 15-minute warm-up. Calibration ambient range: 25°C (77°F) ±3°C Sensor Input Thermocouple • Grounded or ungrounded. • Type E, J, K, T thermocouple types. • >10 MΩ input impedance. • 250 nV input referenced error per 1Ω source resistance. RTD • 2-wire platinum, 100 Ω. • DIN curve (.00385 curve). • 125 µA nominal RTD excitation current. Input Accuracy Span Range Type E: -200 to 800°C or -328 to 1,470°F Type J: 0 to 750°C or 32 to 1,382°F Type K: -200 to 1,250°C or -328 to 2,282°F Type T: -200 to 350°C or -328 to 662°F RTD (DIN): -200 to 800°C or -328 to 1,472°F Thermocouple Input • Calibration accuracy: ±1% of input accuracy span, ±1° at standard conditions and actual calibration ambient. Exception: Type T, ±2.4% of input accuracy span for -200 to 0°C (-328 to 32°F) • Temperature stability: ±0.3 degree per degree change in ambient. Watlow Series L RTD Input • Calibration accuracy: ±1% of input accuracy span ±1° at standard conditions and actual calibration ambient. • Temperature stability: ±0.2 degree per degree change in ambient Allowable Operating Ranges External Reset Switch • Momentary, dry contact closure. See wiring section. Output Types Type E: -200 to 800°C or -328 to 1,470°F Type J: -210 to 1,038°C or -346 to 1,900°F Type K: -270 to 1,370°C or -454 to 2,500°F Type T: -270 to 400°C or -454 to 750°F RTD (DIN): -200 to 800°C or -328 to 1,472°F Electromechanical Relay, Form C • Minimum load current: 100 mA. • 8 A @ 240VÅ (ac) or 30VÎ (dc) maximum, resistive. • 250 VA pilot duty, 120/240VÅ (ac) maximum, inductive. • Use RC suppression for inductive loads. • Electrical life 100,000 cycles at rated current. Agency Approvals Series LF, potted version • UL®873, UL 197, UL 991 recognized temperature limit for cooking industry. File E43684. • ANSI Z21.23 Gas appliance thermostat approval. • CSA C22.2#24 Approved temperature regulator for cooking industry. File #30586. • FM Class 3545 temperature limit switches. File 3017239. • CE - see Declaration of Conformity. Series LF, non-potted version and Series LV • • • • UL 873 recognized temperature regulator. UL 197 reviewed for use in cooking appliances. ANSI Z21.23 Gas appliance thermostat approval. CSA C22.2#24 approved temperature control. File #30586. • FM Class 3545 temperature limit switches. • CE - see Declaration of Conformity. Terminals • 6.4 mm (0.25 in) quick connect, push-on terminals. See order options. Refer to Wiring section for crimp-on terminal recommendations. • Removable screw clamp style terminal blocks. See order options. • Wire gauge 0.1 to 4 mm2 (30 to 12 AWG). Strip length, 8 mm (0.30 in). • Torque: 0.8 Nm (7 in-lb) maximum. ■ 12 ■ Specifications Power • 24VÅ (ac) +10%; -15%; 50/60 Hz, ±5% • 120VÅ (ac) +10%; -15%; 50/60 Hz, ±5% • 230 to 240VÅ (ac) +10%; -15%; 50/60 Hz, ±5% • 10VA maximum power consumption. • Data retention upon power failure via nonvolatile memory. Operating Environment • 0 to 70°C (32 to 158°F) • 0 to 90% RH, non-condensing. • Storage temperature: -40 to 85°C (-40 to 185°F) Dimensions • DIN Rail model can be DIN rail or chassis mount DIN rail spec, DIN 50022, 35 mm x 7.5 mm (1.38 in x 0.30 in) Style Width Height Depth Open board 61.7 mm (2.43 in) 61.7 mm (2.43 in) 45.1 mm (1.78 in) Potted 70.1 mm (2.76 in) 102.9 mm (4.05 in) 46.6 mm (1.84 in) DIN Rail 78.1 mm (3.08 in) 112.3 mm (4.42 in) 90.7 mm* (3.57 in) Square 1/8 DIN Panel 72.4 mm (2.85 in) 72.4 mm (2.85 in) Behind panel 51.7 mm (2.04 in) *Depth including DIN rail, 94.7 mm (3.73 in) Note: These specifications are subject to change without prior notice. Watlow Series L Glossary automatic power reset — A feature in latching limit controllers that does not recognize power outage as a limit condition. When power is restored, the output is re-energized automatically, as long as the temperature is within limits. latched output — Limit control output latches in deenergized condition when over or under temperature condition occurs and cannot be reset unless temperature drops below set point. limit or limit controller — A highly reliable, discrete safety device (redundant to the primary controller) that monitors and limits the temperature of the process or a point in the process. When temperature exceeds or falls below the limit set point, the limit controller interrupts power through the load circuit. A limit controller can protect equipment and people when it is correctly installed with its own power supply, power lines, switch and sensor. manual power reset — A feature in latching limit controllers that does recognize power outage as a limit condition. When power is restored, the output is not reenergized automatically, even if the process is within limits. An operator must use the reset key or switch to manually re-energize the output on power up. manual reset — A feature on a limit controller that requires human intervention to return the limit to normal operation after a limit condition has occurred. safety limit — An automatic limit intended for use in applications where an over-temperature fault may cause a fire. ■ 13 ■ Specifications/Glossar y Ordering Information and Model Numbers Limit Control no user interface L F _ _ _ _ _ _ _ _ A A A A _ Set Point Type F Fixed Limit Set Point Line Voltage C 120VÅ (ac) E 230-240VÅ (ac) G 24VÅ (ac) Controller Package 1 Panel Mount, Square 1/8 DIN -Spade Terminals 2 DIN Rail Mount -Spade Terminals 3 Open Board, not potted -Spade Terminals 4 Potted Case -Spade Terminals 5 Panel Mount, Square 1/8 DIN -Screw Terminals 6 DIN Rail Mount -Screw Terminals 7 Open Board, not potted -Screw Terminals Sensor and Scale H Type J -346 to 1900 Degrees F J Type J -210 to 1038 Degrees C K Type K -454 to 2500 Degrees F L Type K -270 to 1370 Degrees C M Type T -454 to 750 Degrees F N Type T -270 to 400 Degrees C P 100Ω RTD -328 to 1472 Degrees F R 100Ω RTD -200 to 800 Degrees C S Type E -328 to 1470 Degrees F T Type E -200 to 800 Degrees C Limit Type U High Limit, Manual Power Reset W High Limit, Auto Power Reset Y Low Limit, Manual Power Reset Z Low Limit, Auto Power Reset Fixed Limit Set Point Value * XXXX Limit Set Point Value** Overlay/Custom Option A Standard *Note: Limit set point must fall within the sensor operating range. **Note: A (-) is used in the left digit of the operating range to indicate negative values. Watlow Series L ■ 14 ■ Ordering Information Ordering Information and Model Numbers Limit Control, LED display, Front panel reset switch L V - _ _ _ _ - _ _ _ _ - _ _ _ _ - _ Set Point Type V Variable Limit Set Point Line Voltage C 120VÅ (ac) E 230-240VÅ (ac) G 24VÅ (ac) Controller Package 1 Panel Mount, Square 1/8 DIN -Spade Terminals 2 DIN Rail Mount -Spade Terminals 5 Panel Mount, Square 1/8 DIN -Screw Terminals 6 DIN Rail Mount -Screw Terminals Sensor and Scale H Type J -346 to 1900 Degrees F J Type J -210 to 1038 Degrees C K Type K -454 to 2500 Degrees F L Type K -270 to 1370 Degrees C M Type T -454 to 750 Degrees F N Type T -270 to 400 Degrees C P 100Ω RTD -328 to 1472 Degrees F R 100Ω RTD -200 to 800 Degrees C S Type E -328 to 1470 Degrees F T Type E -200 to 800 Degrees C Limit Type U High Limit, Manual Power Reset W High Limit, Auto Power Reset Y Low Limit, Manual Power Reset Z Low Limit, Auto Power Reset Low Limit Set Point Range Limit * XXXX Low Limit Set Point Operating Range Value** High Limit Set Point Range Limit * XXXX High Limit Set Point Operating Range Value Overlay/Custom Option A Standard *Note: Set point ranges must fall within the sensor operating range. **Note: A (-) is used in the left digit of the operating range to indicate negative values. Watlow Series L ■ 15 ■ Ordering Information Notes Watlow Series L ■ 16 ■ Declaration of Conformity Series L Watlow Winona, Inc. 1241 Bundy Blvd. Winona, MN 55987 USA Declares that the following product: Designation: Series L Model Numbers: LF - (C, E or G) (1, 2, 3, 4, 5, 6 or 7) (any letter) (U, W, Y or Z) - (any four numbers or - and three numbers) - (AAAA) - may be followed by additional numbers or letters LV - (C, E or G) (1, 2, 5 or 6) (any letter) (U, W, Y or Z) - (any four numbers or - and three numbers) - (any four numbers) - may be followed by additional numbers or letters Classification: LF and LV = Temperature Regulator Installation Category II, Pollution degree 2 Rated Voltage: 24, 120, 230/240 V~ (ac) Rated Frequency: 50 or 60 Hz Rated Power Consumption: 10VA maximum Meets the essential requirements of the following European Union Directives by using the relevant standards shown below to indicate compliance. 89/336/EEC Electromagnetic Compatibility Directive EN 61326: 1997 With A1, 1998: A2:2001: Electrical equipment for measurement, control and laboratory use – EMC requirements (Industrial Immunity, Class B Emissions). EN 61000-4-2: 1996 + A1, 1998 Electrostatic Discharge Immunity EN 61000-4-3: 1997 Radiated Field Immunity EN 61000-4-4: 1995 Electrical Fast-Transient / Burst Immunity EN 61000-4-5: 1995 + A1, 1996 Surge Immunity EN 61000-4-6: 1996 Conducted Immunity EN 61000-4-11: 1994 Voltage Dips, Short Interruptions and Voltage Variations Immunity EN 61000-3-2: 1995 + A1-3: 1999 Harmonic Current Emissions EN 61000-3-3: 1995 + A1, 1998 Voltage Fluctuations and Flicker 73/23/EEC Low-Voltage Directive EN 60730-1:2000 With A11:2002 and EN 60730-2-9:2002: LXX4 units Automatic electric controls for household and similar use: Particular requirements for temperature sensing controls. EN 61010-1:2001 Safety Requirements of electrical equipment for measurement, All other units control and laboratory use. Part 1: General requirements Raymond D. Feller III Winona, Minnesota, USA Name of Authorized Representative Place of Issue General Manager February 2004 Title of Authorized Representative Date of Issue Signature of Authorized Representative How to Reach Us Your Authorized Watlow Distributor: TOTAL CUSTOMER CUS ER SATISF TISFACTI CTION 3 Year Warranty Corporate Headquarters in the U.S.: Watlow Electric Manufacturing Co. 12001 Lackland Road St. Louis, Missouri, USA 63146 Telephone: +1 (314) 878-4600 Fax: +1 (314) 878-6814 Europe: Watlow GmbH Industriegebiet Heidig Lauchwasenstr. 1, Postfach 1165 Kronau 76709 Germany Telephone: +49 (0) 7253-9400 0 Fax: +49 (0) 7253-9400-44 Watlow France S.A.R.L. Immeuble Somag,16 Rue Ampère, Cergy Pontoise CEDEX 95307 France Telephone: +33 (1) 3073-2425 Fax: +33 (1) 3073-2875 Watlow Italy S.R.L. Via Meucci 14, 20094 Corsico MI Italy Telephone: +39 (02) 4588841 Fax: +39 (02) 458-69954 Watlow Limited Robey Close, Linby Industrial Estate, Linby Nottingham England, NG15 8AA Telephone: +44 (0) 115 9640777 Fax: +44 (0) 115 9640071 Latin America: Watlow de México Av. Fundición #5, Col. Parques Industriales, Querétaro, Qro. México CP-76130 Telephone: +52 (442) 217-6235 Fax: +52 (442) 217-6403 Asia/Pacific: Watlow Australia Pty., Ltd. 23 Gladstone Park Drive, Tullamarine, Victoria 3043 Australia Telephone: +61 (39) 335-6449 Fax: +61 (39) 330-3566 Watlow China, Inc. 179, Zhong Shan Xi Road Hong Qiao Cointek Bldg, Fl. 4, Unit P Shanghai 200051 China Telephone: +86 (21) 6229-8917 Fax: +86 (21) 6228-4654 Watlow Japan Ltd. K.K. Azabu Embassy Heights 106, 1-11-12 Akasaka, Minato-ku, Tokyo 107-0052 Japan Telephone: +81 (03) 5403-4688 Fax: +81 (03) 5403-4646 Watlow Korea Co., Ltd. 3rd F. Taehong Bldg. 20-6, Seocho-gu Yangjae-dong Seoul, Korea 137-130 Telephone: +82 (2) 575-9804 Fax: +82 (2) 575-9831 Watlow Malaysia Sdn Bhd 38B Jalan Tun Dr Awang 11900 Bayan Lepas Penang Malaysia Telephone: +60 (4) 641-5977 Fax: +60 (4) 641-5979 Watlow Singapore Pte. Ltd. Ayer Rajah Crescent #03-23, Ayer Rajah Industrial Estate Singapore 139949 Telephone: +65 773 9488 Fax: +65 778 0323 Watlow Electric Taiwan 10F-1 No. 189 Chi-Shen 2nd Road, Kaohsiung, Taiwan Telephone: +886 (7) 288-5168 Fax: +886 (7) 288-5568
advertisement
Key Features
- Microprocessor based
- Fixed or adjustable limit set points
- Push to Set
- Multiple mounting options
- High or low limit operation
- Fahrenheit or Celsius operation with indication
- Sensor break protection
- Agency Approvals
- Stock to Four Day Delivery
Frequently Answers and Questions
What are the mounting options for the Series L limit controllers?
The Series L limit controllers are available in square 1/8th DIN panel mount, din rail mount, open board or potted module design configurations. Push-on, quick connect spade terminal or removable screw clamp style terminal block ordering options provide the electrical connections.
What is the purpose of the Series L limit controller?
A limit controller is added to applications to prevent over or under temperature conditions. The limit provides safety assurances against instances where a thermal runaway condition occurs as a result of a failed sensor, controller or output device.
What types of sensors can be used with the Series L limit controllers?
The Series L limit controllers can be used with thermocouples (Type E, J, K, T) or RTDs (2-wire platinum, 100 Ω, DIN curve).