M-system AYDV Instruction manual
M-system AYDV is a deviation alarm that can be used to monitor input signals and trigger alarms when the input signal deviates from a setpoint.
The device has two setpoints, each of which can be independently adjusted. When the input signal goes above or below on of the setpoints, the corresponding relay will be energized.
The device also has two setpoint monitor jacks, which can be used to monitor the voltage corresponding to the setpoints. This can be useful for troubleshooting or for connecting to other devices, such as a data logger.
The AYDV is a versatile device that can be used in a variety of applications, such as:
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
AYDV
INSTRUCTION MANUAL
DEVIATION ALARM
MODEL
■ FRONT PANEL CONFIGURATION
AYDV
BEFORE USE ....
Thank you for choosing M-System. Before use, check the package you received as below.
If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket + input resistor) (1)
Input resistor is provided only with current input type.
■ MODEL NO.
Check that model No. described on specification label is exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you use this product, installation, connection and basic maintenance procedures.
COMPONENT IDENTIFICATION
Body Base Socket
Specification
Label
Setpoint 1 Monitor
Setpoint 2 Monitor
COM.
Setpoint 1 Adj. & LED
Setpoint 2 Adj. & LED
• Explanations
Setpoint 1 and Setpoint 2 Adjustments are used to set the alarm setpoints.
A -5 – +5V DC is output at the setpoint monitor jacks across the COM jack, proportional to the setpoint -50 – +50%.
The LED lights turn on when the coil for each relay is energized.
• Examples
For setting the setpoint 1 relay to trip above 20% deviation, turn Setpoint 1 Adj. until you read 2.0V at Setpoint 1
Monitor.
SET MONITOR
-5–+5V(-50–+50%)
M•UNIT
Model
AYDV
DEVIATION ALARM
No.1
No.2
No.1
SET
No.2
SET
COM
Input Resistor
INSTALLATION
Detach the yellow clamps located at the top and bottom of the unit for separating the body from the base socket.
Clamp
(top & bottom)
DIN Rail
35mm wide
■ DIN RAIL MOUNTING
Set the base socket so that its
DIN rail adaptor is at the bottom. Position the upper hook at the rear side of base socket on the DIN rail and push in the lower. When removing the socket, push down the DIN rail adaptor utilizing a screwdriver (–) and pull.
Spring Loaded
DIN Rail Adaptor
Shape and size of the base socket are slightly different with various socket types.
■ WALL MOUNTING
Refer to the drawings in the following page.
P. 1 / 3 EM-1615 Rev.6
AYDV
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram label on the front of the unit.
When an input resistor is provided with the module, attach it together with input wiring to the input screw terminals.
■ DIMENSIONS mm (inch)
CLAMP
(top & bottom)
7.8 (.31)
DIN RAIL
35mm wide
8 7 6 5
4
50 (1.97) 103 (4.06)
132 (5.20)
2–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
11–M3.5
SCREW
[3.3 (.13)]
9
10 11
40 (1.57)
50 (1.97)
3
1 2
•When mounting, no extra space is needed between units.
■ TERMINAL ASSIGNMENTS mm (inch)
INPUT RESISTOR
(model: REM)
■ CONNECTION DIAGRAM
+ 4
INPUT 2 (ref)
INPUT 1 (meas)
+
R
*
–
5
6
**
**
11 HI
10 LO
9 COM
3 HI
OUTPUT 1
2 LO
1 COM
OUTPUT 2
7
8
U(+)
POWER
V(–)
* Input shunt resistor attached for current input.
** Relay status for output code “1”, at power OFF.
8 7 6
4
5
9
10 11
3
1 2
Input shunt resistor attached for current input.
P. 2 / 3 EM-1615 Rev.6
CHECKING
1) Terminal wiring: Check that all cables are correctly connected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal 7
–␣ 8 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of the full-scale.
4) Alarm operations: Check the alarm operations referring to the figure below.
4) Output load: Check that the output load is 380V AC/
100VA or 125V DC/30W at the maximum. For maximum relay life with inductive load, external protection is recommended.
ALARM RELAY OPERATIONS
Output 1
(9-10)ON
(9-11)ON
Output 2
(1-2)ON
(1-3)ON
Input
(%) 0 ▲
Output 2
Setpoint
50 ▲
Output 1
Setpoint
Trip Operation in Power Failure
• Output 1 : (9 – 10) turn ON with code 1
(9 – 11) turn ON with code 2
• Output 2 : (1 – 2) turn ON with code 1
(1 – 3) turn ON with code 2
100
AYDV
POINTS OF CAUTION
■ GENERAL
• Before you remove the unit from its base socket or mount it, turn off the power supply and input signal for safety.
■ ENVIRONMENT
• When heavy dust or metal particles are present in the air, install the unit inside proper housing and ventilate it.
• Do not install the unit where it is subjected to continuous vibration. Do not apply physical impact to the unit.
• Environmental temperature must be within -5 to +60
°
C (23 to 140
°
F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables (power supply, input and output) close to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
MAINTENANCE
Regular calibration procedure is explained below:
■ CALIBRATION
Warm up the unit for at least 10 minutes.
• Hi Setpoint
Increase the input signal from a value lower than the setpoint and check that the relay trips at the Hi setpoint (Measure the voltage at the Hi setpoint monitor jacks).
• Lo Setpoint
Decrease the input signal from a value higher than the setpoint and check that the relay trips at the Lo setpoint
(Measure the voltage at the Lo setpoint monitor jacks).
When the setpoints are shifted, recalibrate the unit according to the "ADJUSTMENT PROCEDURE" explained earlier.
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies, under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]
P. 3 / 3 EM-1615 Rev.6