Below you will find brief information for RTU Open Controller 527-0359. This quick start guide helps you set up and commission the RTU Open Controller on the E2 controller, establishing communication between the E2 controller and the RTU Open Controller, as well as configuring the occupancy state setting for the RTU Open Controller. The guide walks you through essential steps such as uploading the Description File, activating the device license, adding the device to the E2 controller, commissioning the device, naming the controller, and viewing the device Status Screen.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

RTU Open Controller 527-0359 Quick Start Guide | Manualzz

quick start guide

E2 Setup with Carrier Corporation’s RTU Open

Controller for 527-0359

This document will guide you through setting up and commissioning the Carrier Corporation’s RTU Open Controller in the E2 controller (CARRIER OPN-RTUM Open Echelon device in the E2).

Note that Open Echelon Description files require E2 firmware version 3.01FO1 or higher.

E2 and Echelon Devices Communications Network Wiring Diagram

Figure 1 - Network Wiring Diagram

Document Part # 026-4921 Rev 0 03-MAY-2012

©2012 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.

Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.

quick start guide

E2 Setup with Carrier Corporation’s RTU Open Controller for 527-0359

Controller Board Echelon Network Cable Connections

Figure 2 - Echelon Network Cable Connections

Carrier Corporation’s RTU Open Controller Board (SW3) Dip Switch Settings

Set SW3 Dip Switches As Shown

BAUD RATE DS-1 DS-2 DS-3 DS-4 DS-5 DS-6 DS-7 DS-8

38.4K baud ON OFF OFF ON OFF ON ON OFF

Document Part # 026-4921 Rev 0 03-MAY-2012

©2012 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.

Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.

Page 2 of 14

quick start guide

E2 Setup with Carrier Corporation’s RTU Open Controller for 527-0359

Third Party Hardware Configuration Notation

The RTU Open’s operation depends upon its occupancy state (Occupied/Unoccupied). The

RTU Open operates continuously in the Occupied Mode by default until the occupancy schedule has been configured.

NOTE: The controller’s OCCUPANCY SOURCE point setting must be initiated through the

Third Party hardware and software setup procedures in order for any Building Automation

System (BAS) to control Occupancy Schedule.

The OCCUPANCY SOURCE point setting must be configured as follows:

• 3 = BAS ON/OFF

STEP 1: Upload the description file to the E2 controller.

1. From UltraSite, connect to your E2 controller.

2. Right-click the E2 icon and select Description File Upload.

3. Browse to the location of the description file and click Upload.

4. After uploading, you will need to reboot the E2 controller.

Figure 3 - Description File Upload

Document Part # 026-4921 Rev 0 03-MAY-2012

©2012 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.

Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.

Page 3 of 14

quick start guide

E2 Setup with Carrier Corporation’s RTU Open Controller for 527-0359

STEP 2: Activate the license of the device.

5. From the E2 front panel (or via the Terminal Mode), press  , 7 (System Configuration), and 9 (Licensing).

6. Press F1 (ADD FEATURE) and enter your license key.

Figure 4 - Add License Screen

STEP 3: Once the license is activated, add the device to the E2 controller.

7. Press  , 7 (System Configuration), 7 (Network Setup), 2 (Connected I/O Boards &

Controllers).

8. Press F2 (NEXT TAB) to go to the C4: Third Party tab. You should see the device in the list.

Enter the number of devices to add and press the  button to save your changes.

Document Part # 026-4921 Rev 0 03-MAY-2012

©2012 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.

Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.

Page 4 of 14

quick start guide

E2 Setup with Carrier Corporation’s RTU Open Controller for 527-0359

Figure 5 - Specify the Number of Devices to Add

Figure 6 - Device Setup Screen

Document Part # 026-4921 Rev 0 03-MAY-2012

©2012 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.

Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.

Page 5 of 14

quick start guide

E2 Setup with Carrier Corporation’s RTU Open Controller for 527-0359

STEP 4: Commission the Echelon device.

9. Press  , 7 (System Configuration), 7 (Network Setup), 1 (Network Summary).

10.Use the UP and DOWN arrow keys to highlight the device name and then press 

(Commission).

11.Select the method to use for identifying the device. Select from the list:

• 1 = Service Pin --> The physical button on the controller must be pressed. This is the preferred method for device accuracy.

• 2 = Entering Neuron ID(s) directly --> Echelon device address should consist of 12 characters. The device is identified via remote communication using the Neuron ID.

Use this selection if the Neuron ID of the device is available.

• 3 = Specifying a range of nodes --> The network is scanned for neuron addresses.

Figure 7 - Commission the Device

Document Part # 026-4921 Rev 0 03-MAY-2012

©2012 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.

Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.

Page 6 of 14

quick start guide

E2 Setup with Carrier Corporation’s RTU Open Controller for 527-0359

Figure 8 - Select Method for Identifying the Controller

Figure 9 - Identifying the Controller Using the Neuron ID

Document Part # 026-4921 Rev 0 03-MAY-2012

©2012 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.

Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.

Page 7 of 14

quick start guide

E2 Setup with Carrier Corporation’s RTU Open Controller for 527-0359

STEP 5: Name the controller device.

12.Press  , 7 (System Configuration), 7 (Network Setup), 1 (Network Summary).

13.Use the UP and DOWN arrow keys to highlight the generic LonMark Device name and then Press  (SETUP).

14.Enter the desired device name in the Name field highlighted and then press the  to return to the Network Summary screen.

NOTE: By default, any Third Party (Open Echelon) devices that are initiated in E2 will always have a generic naming sequence as shown:

Example: LONMARK_001, LONMARK_002, LONMARK_003

Figure 10 - Network Summary Screen

Document Part # 026-4921 Rev 0 03-MAY-2012

©2012 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.

Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.

Page 8 of 14

quick start guide

E2 Setup with Carrier Corporation’s RTU Open Controller for 527-0359

Figure 11 - Changing the Device Name

Figure 12 - Changing the Device Name

Document Part # 026-4921 Rev 0 03-MAY-2012

©2012 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.

Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.

Page 9 of 14

quick start guide

E2 Setup with Carrier Corporation’s RTU Open Controller for 527-0359

Figure 13 - Network Summary Screen

STEP 6: View the device Status Screen.

15.Press  and then 5 (Configured Applications). A list of all configured applications in

E2 displays on the screen.

16.Use the UP and DOWN arrow keys to highlight the device name on the Configured Applications screen and then press  . The device Status Screen displays.

NOTE: By default, if there are one or more devices of the same type configured in E2, a list of all common devices will display (Summary Screen) in reference to the numeric or alphanumeric character sequence of the devices labeled.

Example: AHU-1, AHU-2, AHU-3, RTU-1, RTU-2, RTU-3

Document Part # 026-4921 Rev 0 03-MAY-2012

Page 10 of 14

©2012 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.

Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.

quick start guide

E2 Setup with Carrier Corporation’s RTU Open Controller for 527-0359

Figure 14 - Main Menu

Figure 15 - Configured Applications

Document Part # 026-4921 Rev 0 03-MAY-2012

Page 11 of 14

©2012 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.

Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.

quick start guide

E2 Setup with Carrier Corporation’s RTU Open Controller for 527-0359

Figure 16 - Summary Screen

Figure 17 - Device Status Screen

Document Part # 026-4921 Rev 0 03-MAY-2012

Page 12 of 14

©2012 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.

Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.

quick start guide

E2 Setup with Carrier Corporation’s RTU Open Controller for 527-0359

Figure 18 - General Tab

Figure 19 - Inputs Tab

Document Part # 026-4921 Rev 0 03-MAY-2012

Page 13 of 14

©2012 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.

Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.

quick start guide

E2 Setup with Carrier Corporation’s RTU Open Controller for 527-0359

Figure 20 - Outputs Tab

Document Part # 026-4921 Rev 0 03-MAY-2012

This document may be photocopied for personal use.

Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.

Page 14 of 14

The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such products at any time without notice.

Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user.

026-4921 03-MAY-2012 Emerson is a trademark of Emerson Electric Co. ©2012 Emerson Climate Technologies Retail Solutions, Inc. All rights reserved.

advertisement

Key Features

  • Description File Upload
  • License Activation
  • Device Addition
  • Commissioning
  • Naming the device
  • Viewing device Status
  • Occupancy state settings
  • E2 controller communication

Frequently Answers and Questions

What is the minimum E2 firmware version required for Open Echelon Description files?
E2 firmware version 3.01FO1 or higher is required.
How do I configure the Occupancy State of the RTU Open Controller?
The Occupancy State setting must be initiated through the Third Party hardware and software setup procedures. The OCCUPANCY SOURCE point should be configured as '3 = BAS ON/OFF'.
What is the preferred method for identifying the device during commissioning?
The preferred method for device accuracy is to use the Service Pin, which requires pressing the physical button on the controller.
What does the generic naming sequence for Third Party devices look like?
By default, Third Party (Open Echelon) devices will have a generic naming sequence like 'LONMARK_001', 'LONMARK_002', etc.