Pepperl+Fuchs 2001A STD Enclosure Protection System Installation & Operation Manual
The 2001A STD Enclosure Protection System is a device that allows the use of general purpose or non-rated electrical or electronic devices in Type 4 or 12 enclosures in place of explosion proof Type 7 enclosures. It operates on a supply of compressed instrument air or inert gas, regulating and monitoring pressure within sealed enclosures to prevent combustible dust accumulation or remove and prevent flammable gas or vapor accumulations. The system includes an electrical power control unit (EPCU) that monitors system operation and controls enclosure power.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
CLASS I APPLICATIONS
2 Cubic Feet Maximum
CLASS II APPLICATIONS
10 Cubic Feet Maximum
M
ODEL
2001A
T
YPE
X
P
RESSURIZATION
/ P
URGING
S
YSTEM
I
NSTALLATION
& O
PERATION
M
ANUAL
STD Style
(Standard)
BEBCO EPS
Pepperl+Fuchs ® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607 • E-mail: [email protected] • www.bebcoeps.com
"Terms & Conditions of Sale" information is printed on every order acknowledgement; copies are available upon request.
We reserve the right to make modifications and no guarantee of the accuracy of the information contained herein is given.
© 2004 Pepperl+Fuchs ® Inc., Twinsburg, Ohio
512166, Dwg No. 129-0208 (Supercedes 2001A-IOM) Printed in U.S.A
Page 2
System Purpose and Description
Purpose, System Description, Important Notes
Page 3
Identifying Your System
Defines specific features of the system
Page 4
General Information
System & Material Specifications, System Accessories,
Spare Parts, Tools & Test Equipment
Page 5
Enclosure and Device Design
Design Requirements, Adjacent Enclosures, Device
Ventilation, Temperature Limitations
Page 6
Installation Overview
Installation Diagram
Page 7
Page 8
Getting Started
Establishing Connection Sizes, Determining Enclosure
Inlet & Outlet Connection Locations
System Mounting
LH, RH, TM, BM & WM Configurations,
FM & PM Configurations
Page 9
Hardware Mounting
Optional Enclosure Protection Vent, Warning
Nameplates
Page 10
Mounting Plate Dimensions
Mounting Plate Dimension Diagrams
Page 11
Mounting Plate Dimensions (cont.)
Mounting Plate Dimension Diagrams
Page 12
Pneumatic Tubing Requirements
Protective Gas Supply Requirements, Pneumatic
Connection Requirements
Page 13
Tubing Connection Points
LH, RH, TM, BM, WM, FM, & PM Configurations
Page 14
Tubing Installation
LH, RH, TM, BM, WM, FM & PM Tubing Configurations
Purpose
Table of Contents
Page 15
Electrical Supply Requirements
General Wiring Requirements, EPCU Power & Alarm
Signal, Enclosure Wiring Methods & Connections
Page 16
Electrical Power Control Unit
General Layout & Conduit Connection Points
Page 17
EPCU Power Rating
Power Rating Nameplate, Assembled Electronics
Page 18
Electrical & Pneumatic Diagrams
LH, RH, TM, BM, WM, FM, & PM Configurations
Page 19
Conduit Installation
EPCU Electrical Conduit, Optional Intrinsic Safety Barrier
Conduit and EPCU Conduit Connection Parts
Page 20
Power Modules & Wiring Diagram
EPCU 120/220 VAC & 24-48 VDC Power Modules
Page 21
Logic Module & Barrier Wiring
Optional ISB Wiring Requirements & Diagram,
EPCU Power Control Modes
Page 22
Barriers & Field Adjustments
ISB Description & Factory Programming, LED Display
Indicators, Timer Functions & Settings
Page 23
Class I Set-Up Procedure
Class I Purging Set-up
Page 24
Class II Set-Up Procedure
Class II Pressurization Set-up
Page 25
Operating Sequence
Class I Purging & Class II Pressurization Operation
Page 26
Trouble - Shooting Procedures
Page 27
Warranty and Liability Statements
Warranty Notes, General Terms, Limitations
Pages 28
& 29 System Maintenance
Pages 30 & 31
Customer Notes
Page 32
Systems Identification & Application Information
Important Notes
Pepperl+Fuchs' Enclosure Protection System’s purpose is to allow the use of general purpose or non-rated electrical or electronic devices, with exception to devices which produce excessive heat, utilize combustible gas, or expose arcing contacts to the hazardous atmosphere, in Type 4 or 12 enclosures in the place of explosion proof
Type 7 enclosures. Other purposes include heat, moisture and dust contamination prevention.
Description
Model 2001A is an enclosure pressurization or purging system that operates on a supply of compressed instrument air or inert gas. It regulates and monitors pressure within sealed (protected) enclosures, to prevent combustible dust accumulation or remove and prevent flammable gas or vapor accumulations. In Class II areas, the system maintains a “safe” (1.0") pressure. In Class I areas, the system accomplishes four air exchanges and maintains a “safe” (0.25") pressure. In addition, the system includes an electrical power control unit (EPCU) that monitors system operation and controls enclosure power. These processes reduce the hazardous (classified) area rating within the enclosure(s), in accordance with the NEC - NFPA 70, Article
500, NFPA 496 and ISA12.4
One (1) permanent file copy and one (1) operations copy of this Manual must be studied and retained by the operator of this System. User’s
Agents are responsible for transferring this Manual to the user, prior to start-up.
The contents of this manual have been arranged to allow the use of this product as a stand-alone device on equipment and enclosures supplied by the user or its agents. The Manual’s parameters encompass both
National Fire Protection Association (NFPA) requirements and
Pepperl+Fuchs requirements. Pepperl+Fuchs therefore acknowledges the use of NFPA 496 as a guideline, that we have enhanced certain NFPA requirements and that additional information has been compiled to complete this document. The Manual is intended as a complete guide and must be considered, unless specifically stated otherwise, that all directives contained herein are Pepperl+Fuchs requirements for safe, practical and efficient use of this product.
This System is not intended for use to protect enclosures or devices which contain ignitable concentrations of gases or vapors. This exclusion generally applies to process or product analyzing systems equipment.
All specifications are subject to change without notice.
2
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
Identifying Your System
This Enclosure Protection System is offered in various styles. For proper installation and operation, examine the System
Model Number Nameplate to identify the System Style, Area Classification, and Type, as noted below.
SERIES
MODEL NUMBER
SYSTEM STYLE
STD - Standard
Requires manual operation of protective gas pneumatics
SYSTEM CLASS RATING
Defines Class & Group rating for
Protection System’s method of use
CI - Class I Purging system (Groups C&D)
IB - Class I Purging system (Group B)
CII - Class II Pressurization system
MAXIMUM
TOTAL
ENCLOSURE
VOLUME
Defines total protected enclosure(s) volume capacity for this particular system. Total enclosure(s) volume must be calculated without regard for consumed volume
Model 2001A-STD-CI Type X
2 CUBIC FEET MAXIMUM ENCLOSURE VOLUME
CLASS I, DIVISION 1, GROUPS C & D TO NONHAZARDOUS
AREA
CLASSIFICATION
Defines the area classification for which the system is suitable for operation
T3C
PURGE CONTROL FOR USE IN HAZARDOUS LOCATIONS. CLASSIFIED BY UNDERWRITERS LABORATORIES
INC . ® IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION
STANDARD FOR PURGED AND PRESSURIZED ENCLOSURES FOR ELECTRICAL EQUIPMENT
NFPA 496- 2003
7L93
APPROVED BY FACTORY MUTUAL AS ASSOCIATED TYPE X PRESSURIZATION CONTROL
EQUIPMENT FOR USE IN HAZARDOUS LOCATIONS. REDUCES THE INTERNAL AREA
OF A CONNECTED ENCLOSURE IN ACCORDANCE WITH DRAWING NUMBER 129-0208.
APPROVAL
MARKINGS &
DEFINITIONS
Identifies the current third party approvals for this system
SYSTEM TYPE
Type X
Reduces the internal enclosure area
Division rating from
Division 1 to nonhazardous
To assist you through the installation and operation of your pressurization / purge system, Pepperl+Fuchs has provided the following information boxes throughout this manual. This information is intended to clarify certain differences between the model styles and configurations and to warn the user / installer of potential dangers of electrical shock or enclosure over pressurization.
HELPFUL HINT IMPORTANT NOTE WARNING
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
3
General Information
System Specifications
System Dimensions:
Shipping Weight (Lbs.):
Operating Temp. Range:
Supply Pressure Range:
Supply Requirements:
Safe Press. Setpoint(CI/CII):
Safe Press. Flowrate:
Class I Exchange Time:
System Supply Port:
Enclosure Supply Fitting:
Enclosure Reference Fitting:
EPCU Conduit Port Size:
EPCU Power Requirements:
(European 240 voltage only)
EPCU Power Consumption:
Power Relay Contacts:
Alarm Relay N.O. Contact:
Alarm Relay N.C. Contact:
See Pages 10 & 11
38
-20° F - 120° F
* 5 - 120 PSI max.
Clean Air or Inert Gas
0.25"/1" @ Safe Press.
** 0.1 - 3.5 SCFH / Cubic Ft.
*** As required
1/4" Tube Fitting
1/4" Tube Fitting
1/4" Tube Fitting
1/2" FPT
120 VAC 60 Hz 1Ø
240 VAC 50 Hz 1Ø
500 mA
20 Amps @ 240 VAC
20 Amps @ 28 VDC
**** 20 Amps @ 48 VDC
20 Amps @ 240 VAC
20 Amps @ 28 VDC
15 Amps @ 240 VAC
10 Amps @ 28 VDC
* With EPV-1 Vent - 120 psi max. to 5 PSI minimum
Without EPV-1 Vent - 5 psi maximum
In order to comply with the NFPA 496 standard requiring protection against over pressurization of the protected enclosure, the installer must install one of the following items in addition to the enclosure protection system.
a) Install an EPV-1 Enclosure Protection Vent on the protected enclosure.
b) Install a tamper-proof regulator upstream of the enclosure protection system's system supply inlet to pre-regulate protective gas supply to 5 psi max.
In addition, for small, tightly sealed enclosures, or to compensate for a fluctuating protective gas supply, it may be necessary to pre-regulate the protective gas supply to a constant 5 psi regardless of whether an EPV-1 is installed.
This will reduce the amount of "drifting" that can normally occur when maintaining a "Safe" pressure inside a protected enclosure. The pre-regulation can be accomplished by installing TR-10G Tamper-Proof Regulator accessories or equivalent.
For applications which require a steady "Safe" pressure setting or for protective gas supplies which may have dramatic pressure fluctuations, it may be necessary to utilize the PR-10 or PR-10G self relieving Precision
Regulators or equivalent to pre-regulate the protective gas supply to a constant 5 PSI (please consult factory for more information).
** Enclosure integrity determines actual flow rate
*** Time required to exchange 4 volumes within the enclosure(s), based on actual measured safe pressure flowrate or 5 minutes, whichever is greater
Material Specifications
Regulator Body:
Regulator Handle:
Enclosure Pressure Gauge:
Tube Fittings:
Tubing:
System Nameplates:
Fastener Hardware:
Mounting Plate:
Zinc w/ Enamel Finish, Brass
Polycarbonate
Alum. w/ Enamel Finish
316 SS Forged Body
316 SS 1/4" .035 Welded
Silkscreened Lexan ® & SS
Stainless Steel Screws & Bolts
316 14 Ga #3 Brush SS
EPCU Enclosure Body:
Enclosure Warning Nameplate:
Bead Blast Cast Aluminum
Silkscreened SS
Lexan ® is a registered trademark of the General Electric Corporation
Recommended Spare Parts
Qty Description Part # (supercedes)
1 Enclosure Pressure Indicator-CI
1 Enclosure Pressure Indicator-CII
510023 (001000)
513235 (001027)
1 Enclosure Pressure Control Regulator 513315 (002000)
1 Safe Pressure Switch-CI 510356 (005200)
1 Safe Pressure Switch-CII
1 Series 2000 Logic Module-Ver. 2.0
510357 (005205)
510279 (005000)
1 Series 2000 VAC Power Module
1 Installation & Operation Manual
1 Enclosure Warning Nameplate-CI
1 Enclosure Warning Nameplate-CII
510304 (005020)
129-0208
513008 (EWN-1)
513009 (EWN-2)
Reference part number above for current spare parts pricing. Immediate pricing is available to all confirmed customers.
Installation Tools & Testing Equipment
1/2" chuck drill
Complete set of drill bits
1/2" conduit knockout punch or 0.875" hole saw
Complete set of tubing, conduit bending, instrument fitting and electrical craftsman hand tools
0 - 250 scfh flowmeter (connected upstream of Protection
System to determine air consumption and flow during set-up)
Model 2001A System Accessories
Optional Enclosure Protection Vents
EPV-1-SA-00
EPV-1-SA-90
Straight w/ Spark Arrestor
Rt Angle w/ Spark Arrestor
Additional Items
SMK -2, -3 or -10
RAH
RAB-1
LCK
TCK
TR-10G
PR-10
PR-10G
SRM-4000
NJ...
System Mounting Kit
Div. 1 Remote Alarm Horn
Div. 1 Remote Alarm Beacon
L Fitting Conduit Kit
T Fitting Conduit Kit
Tamper-Proof Regulator w/ Gauge
Precision Regulator
Precision Regulator w/ Gauge
Switch Resistor Module
P+F NAMUR Sensor
4
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
Enclosure & Device Design
Enclosure Design Requirements
1.
All windows must be shatterproof and sized as small as possible.
2.
All NFPA 496 required markings must be placed on or near all enclosure doors and covers.
3.
The enclosure must withstand an internal pressure of five (5) inches of water without sustaining permanent deformation and resist all corrosive elements in the surrounding atmosphere.
4.
All lightweight objects in the enclosure, such as paper or insulation, must be firmly secured.
5.
The enclosure should be constructed from materials such as metal or anti-static polycarbonate to meet or exceed Type 4 or 12 performance requirements, but does not require third party approval.
6.
The installation of obstructions or other barriers which block or impede the flow of protective gas must be avoided.
7.
The creation of air pockets or other areas which trap flammable gases within the enclosure or devices must be avoided.
8.
The enclosure should be located in an area where impact hazards are minimal.
9.
If the enclosure is nonmetallic and contains equipment which utilizes or switches power loads greater than 2500
VA, it must be constructed from substantially noncombustible materials, such as materials designed to meet or exceed ANSI/UL94 ratings of 94 V-0 or 94 5V.
Adjacent Enclosures
1.
Adjacent enclosures must be protected by one of the following means: a) purged or pressurized in series with the protected enclosure; b) purged or pressurized separately; or c) protected by other means; e.g. explosion proof enclosures, hermetically sealed devices or intrinsic safe circuits.
2.
Adjacent purged or pressurized enclosures must be designed to meet all construction requirements above.
Total Volume Calculation
1.
The total volume of all pressurized enclosures, devices and wireways must be considered.
2.
All enclosure, device and wireway volumes must be calculated without consideration of internally consumed space.
Device Ventilation
1.
Enclosed devices within the protected enclosure which do not exceed 1.22 cubic inches of free volume do not require ventilation to the protected enclosure.
2.
If the free volume of an internal device exceeds 1.22
cubic inches it must be protected by one of the following means: a) ventilated on the top and bottom sides with one (1) square inch of opening for each four hundred (400) cubic inches of volume within the internal protected enclosure, at a minimum diameter of one (1) quarter inch; b) purged in series with the protected enclosure or be purged separately; or c) protected by other means; e.g. explosion proof devices, hermetically sealed housings or intrinsic safe circuits.
Temperature Limitations
1.
The enclosure must have no surface area which exceeds
80 percent of the flammable or ignitable substance’s auto-ignition temperature.
2.
Internal devices which exceed this temperature must be protected by one of the following manners.
a) The device is enclosed in a chamber which is cUL or
FM listed as a hermetically sealed device which prohibits the entrance of flammable or ignitable substance, and maintains a surface temperature below temperature limits.
b) It can be proven by testing that the devices will not ignite the substance involved.
c) The device is purged in a separate enclosure that bears an ETW (Enclosure Temperature Warning
Nameplate). Devices may only be accessed after power has been removed and the device has been allowed to cool to safe temperature, or the area is positively known to be nonhazardous.
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
5
Installation Overview
Typical Left Hand Configuration Installation Diagram
Model 2002-STD-CI-LH Shown
ENCLOSURE
PROTECTION
VENT
PROTECTED
ENCLOSURE
ENCLOSURE
PROTECTION
SYSTEM
ENCLOSURE
REFERENCE
TUBING
ENCLOSURE
SUPPLY TUBING
ENCLOSURE
CONNECTION
FITTINGS
SERVICE
VALVE
PROTECTIVE
GAS SUPPLY
SYSTEM
SUPPLY TUBING
EPCU BREATHER
DRAIN FITTING
ENCLOSURE
WARNING
NAMEPLATE
6
EPCU POWER & ALARM SIGNAL
WIRING CONDUIT & SEAL
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
1/2"
PROTECTIVE
GAS SUPPLY
HEADER
Getting Started
Establishing Connection Sizes, Lengths & Bends
TYPICAL SINGLE PROTECTED ENCLOSURE CONNECTIONS
ENCLOSURE PROTECTION VENT
(Optional)
C
REFERENCE
ENCLOSURE
PROTECTION
SYSTEM
SUPPLY
PROTECTED
ENCLOSURE
A B E
Description
A
System
Supply Tubing
B
Enclosure
Supply
C
Enclosure
Reference
*Tubing or Pipe Diameter
Maximum Tubing / Pipe Length and
Maximum Number of Bends / Elbows
1/4" O.D. Tubing
Fully Reamed
20 Feet
10 Bends
1/4" O.D. Tubing
Fully Reamed
1/4" O.D. Tubing
Fully Reamed
5 Feet
5 Bends
20 Feet
10 Bends
D E
Multi - Enclosure Optional Remote
Connections Venting
1/2" I.D. Pipe
Fully Reamed
1/2" I.D. Pipe
Fully Reamed
10 Feet
5 Elbows
30 Feet
5 Elbows
1/2"
PROTECTIVE
GAS SUPPLY
HEADER
TYPICAL MULTIPLE PROTECTED ENCLOSURE CONNECTIONS
B D D
ENCLOSURE
PROTECTION
SYSTEM
SUPPLY
PROTECTED
ENCLOSURE
PROTECTED
ENCLOSURE
REFERENCE
PROTECTED
ENCLOSURE
A C
*NOTE: Tube and pipe sizes are trade sizes and are not equal in inside diameters.
DO NOT substitute tube for pipe with same trade size.
HELPFUL HINTS
To ensure adequate protective gas flow to the protected enclosure(s), all piping and tubing must be fully reamed.
Precautions must be taken to prevent crimping and other damage to protective gas piping and tubing.
When protecting multiple enclosures with a single enclosure protection system, the enclosures must be connected in series from the smallest to the largest to ensure adequate protective gas flow.
Determining Enclosure Inlet & Outlet Connection Locations
INLET
Connections for Heavier than
Air Gases and Vapors
OUTLET
INLET
OUTLET
HELPFUL HINTS
If flammable gases are lighter than air, the inlet connection to each enclosure must enter near a bottom corner. The outlet connection, for an optional enclosure protection vent or piping to an adjacent protected enclosure, must exit near an extreme opposite top corner. See diagrams to the left.
If flammable gases are heavier than air, inlet and outlet connections must be reversed.
In all cases, the most prevalent gas must determine the location of inlet and outlet connections.
Connections for Lighter than
Air Gases and Vapors
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
7
System Mounting
IMPORTANT NOTES
The system should be mounted at EYE LEVEL.
Care must be taken to ensure the system and all protruding components are clear of all enclosure accesses (doors and covers) and conduit, pipe, tubing or cable entries.
LH, RH, TM, BM and WM configurations are intended for mounting adjacent to the protected enclosure.
LH, RH, TM & BM configurations are also suitable for
2" schedule 40 pipe mounting.
Determine the mounting configuration of your system using the diagrams on pages 10 & 11.
Remove and save the manila envelope (containing the enclosure warning nameplate) which may be taped to the outer surface of the mounting flange.
Although all systems are factory tested and calibrated, we strongly suggest a bench test of basic functions prior to installation.
Mounting LH, RH, TM, BM & WM Configurations
1 . Transfer hole pattern of System mounting plate to intended surface.
2.
Check for obstructions hindering bolt fastening, drill and ream the mounting holes before mounting the system.
3.
Secure the system to the enclosure, or other mounting surface, using one (1) SMK-3 or equivalent - six (6) 3/8" x 3/4" stainless steel bolts, nuts and lock washers.
*WM requires one (1) SMK-2 or equivlent - four (4) 3/8" x 3/4" stainless steel bolts, nuts and lock washers.
Mounting FM & PM Configurations
HELPFUL HINTS
FM and PM configurations are designed to mount through a panel cutout one (1) inch smaller than the overall height and width of the system mounting plate, using clips and fasteners provided with SMK -10. This design feature eliminates the need to drill the system mounting bolt holes in the protected enclosure.
FM configurations are intended for mounting adjacent to the protected enclosure.
PM configurations are intended for mounting through a cutout in the protected enclosure surface.
1.
Transfer panel cutout pattern to the intended surface.
2.
Check for obstructions which could prohibit bolt fastening or system pneumatic and electrical connections.
3.
Cut panel cutout pattern on the intended surface.
4.
Deburr all cutout surfaces.
5.
Secure system to enclosure using SMK-10, or equivalent
- ten (10) 1/4" x 3/4" stainless steel nuts, bolts, mounting clips and lock washers.
Typical Examples of Surface, Pipe, Panel & Frame Mounted Systems
Typical Surface Mounted System
(Model 1002-LPS-LH Type Z shown)
8
Typical Pipe Mounted System
(Model 1002-LPS-LH Type Z shown)
Typical Panel/Frame Mounted System
(Model 1002-LPS-PM Type Z shown)
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
Hardware Mounting
Optional Enclosure Protection Vent
All configurations must be mounted in a true vertical position.
The vent must be located to provide access for routine testing of the vent’s flapper assembly. A minimum 8" clearance is required below the vent opening.
1.
Determine the vent’s mounting configuration, i.e.;
-00 vertical mount or -90 side mount. (See photos below)
2.
Determine vent location and layout vent mounting hole on the protected enclosure. (As determined on page 7,
“Getting Started”)
3.
Using a 0.875" hole saw or 1/2" conduit punch, drill and deburr the enclosure protection vent mounting hole.
4.
Remove the hub mounting nut from the vent hub and place the hub, with O-ring intact, through the mounting hole. The O-ring must be on the outside of the protected enclosure.
5.
Reinstall the hub mounting nut to the mounting hub from inside the protected enclosure and tighten.
Warning Nameplate(s)
An EWN (Enclosure Warning Nameplate) must be located in a prominent position on or near all enclosure accesses
(doors and covers).
One (1) EWN is provided with each system, located in the manila envelope taped to the mounting flange of the system.
Additional EWN’s are available from Pepperl+Fuchs.
All EWNs provide labeled spaces allowing the customer to mark the protected enclosure with: 1) a T Code (temperature identification number), 2) Class, Group and Division of surrounding area, and 3) NFPA pressurization Type X, Y or Z, as may be required by plant and local codes and is required by NFPA 496.
An ETW (Enclosure Temperature Warning nameplate) must be located in a prominent position on or near all enclosure accesses (doors and covers) when the temperature of an internal component exceeds 80 percent of the ignition temperature of the flammable vapor, gas or dust involved.
An ETW warns the operator to deenergize all equipment for a specified length of time, allowing the protected equipment to cool before opening the protected enclosure. The length of time required is determined by the customer and can be factory or field engraved.
All EWNs and ETWs are furnished with an adhesive back, but should also be riveted or screwed to the protected enclosure.
EPV - 1 - SA - 00
Vertical Mount
Enclosure Warning Nameplate - Class I
Enclosure Warning Nameplate - Class II
EPV - 1 - SA - 90
Side Mount
Enclosure Temperature Warning Nameplate
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
9
20"
Mounting Plate Dimensions
Model 2001A
.375" O.D.
TYP. 6
10.5"
4"
3.375"
.625"
.6875"
10.5"
4"
3.375"
.625"
.6875"
.375" O.D.
TYP. 6
10" 9.5"
20"
18" 19.312"
11"
2001A-STD-LH
(Left Hand Configuration)
11"
2001A-STD-RH
(Right Hand Configuration)
IMPORTANT NOTE
Dimensions DO NOT include Systems ordered with an
Area Classification of IB (Class I, Division 1, Group B).
Consult factory for mounting plate dimensions.
10.5" 10.5"
10
20.75"
10.5"
4.25"
10.375"
19.25"
2001A-STD-TM
(Top Mount Configuration)
.375" O.D.
TYP. 6
20.75"
20.0625"
11.25"
2001A-STD-BM
(Bottom Mount Configuration)
.375" O.D.
TYP. 6
4.25"
10.5"
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
Mounting Plate Dimensions (cont.)
Model 2001A
6"
12.5"
20"
18"
2"
9"
.375" O.D.
TYP. 4
1"
TYPICAL -WM
MOUNTING FLANGE
11"
2001A-STD-WM
(Wall Mount Configuration)
IMPORTANT NOTE
Dimensions DO NOT include Systems ordered with an
Area Classification of IB (Class I, Division 1, Group B).
Consult factory for mounting plate dimensions.
.25" O.D.
TYP. 10
Panel Cutout
12" 10.25"
1.25"
Panel Cutout
21"
22"
13"
2001A-STD-FM & 2001A-STD-PM
(Frame & Panel Mount Configuration)
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
11
Pneumatic Tubing Requirements
Protective Gas Supply Requirements
The protective gas supply to the protection system must be a clean, instrument quality compressed air or nitrogen and must contain no more than trace amounts of flammable gas, vapor or dust.
The protective gas supply compressor intake must originate in a nonhazardous location. Suction duct passing through a hazardous location and the protection system tubing and piping must be fabricated from noncombustible materials suitable for prevailing hazards and environmental conditions.
The protective gas supply must originate from a dedicated instrument quality compressed air header (1/2" pipe or larger), no farther than twenty (20) feet from the protection system. Local compressors and gas cylinders should not be used before consulting with Pepperl+Fuchs.
The protective gas supply to the protection system must be equipped with a tamper-proof regulator set at 5 psi maximum.
Exception: If the protected enclosure(s) is equipped with an
EPV-1 Enclosure Protection Vent, the protective gas supply to the protection system must not exceed 120 psi maximum,
5 psi minimum. (See page 4, "System Specifications" for additional information concerning protective gas supply requirements.)
SC-4 NC-4
SYSTEM SUPPLY FITTINGS
Pneumatic Connection Requirements
ALL FITTINGS MAY BE CUSTOMER OR FACTORY FURNISHED
1.
For system supply, one (1) SC-4 1/4" Male Straight
Connector or one (1) NC-4 1/4" Male Elbow Connector or equivalent fitting per system.
NOTE: Above fitting is required only if protection system is furnished with an optional In Line Filter Kit
(Model ILFK) accessory.
One (1) similar fitting which will connect the inert gas supply tubing to the inert gas supply header connection point and one (1) lot of 1/4" O.D., .035" wall thickness, welded or seamless stainless steel tubing.
2.
For enclosure supply, one (1) EFC-4 1/4" Flush
Connector, or one (1) EBC-4 1/4" Feed-Through
Connector or equivalent fitting per system.
3.
For enclosure reference, one (1) EFC-4 1/4" Flush
Connector, or one (1) EBC-4 1/4" Feed-Through
Connector or equivalent fitting per system.
4.
One (1) lot of 1/4" O.D., .035" wall thickness, welded or seamless stainless steel tubing.
5.
For multiple enclosure connections, two (2) EPC-10 1/2"
Pipe Mounting Hubs or equivalent and 1/2" 150# rated pipe couplings & unions per interconnection.
One (1) lot 150# rating 1/2" galvanized or aluminum pipe and fittings, fully reamed and unrestricted.
PM Pneumatic Connection Requirements
In addition to item numbers 1, 4 and 5 above, the following fittings are required for all PM configurations.
1.
For system supply on PM configurations, one (1) additional EBC-4 or equivalent 1/4" Through Bulkhead
Fitting per system is required.
2.
For atmospheric reference, one (1) PRB-4 or equivalent
1/4" female bulkhead fitting and stainless steel sintered element is required.
EFC-4 EBC-4
ENCLOSURE SUPPLY & REFERENCE FITTINGS
PRB-4
SYSTEM ATMOSPHERIC REFERENCE FITTING
12
EPC-10
MULTIPLE ENCLOSURE CONNECTION FITTING
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
Tubing Connection Points
LH, RH, TM, BM, WM & FM Configuration Connection Points
Enclosure
Pressure
Gauge
Enclosure
Reference
Inlet
Flame
Arrestor
Venturi
Orifice
Mounting
Plate
System
Supply
Inlet
Enclosure
Pressure
Control
Regulator
Enclosure
Supply
Outlet
PM Configuration Connection Points
Enclosure
Pressure
Gauge
Atmospheric
Reference
Inlet
Electrical
Power
Control Unit
Flame
Arrestors
Mounting
Plate
System
Supply
Inlet
Enclosure
Pressure
Control
Regulator
Enclosure
Supply
Outlet
HELPFUL HINT
Pneumatic Connections are bolded.
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
13
Tubing Installation
HELPFUL HINTS
All work must be performed by technicians qualified in pneumatic tubing and electrical conduit installation.
Pepperl+Fuchs recommends the use of .035" wall thickness, welded or seamless stainless steel tubing.
If flexible tubing is used, it must be installed in a manner which will protect it from damage and corrosion.
Tubing LH, RH, TM, BM, WM & FM Configurations
System Supply Connections
1.
Select or install a protective gas supply header tap, fitted with the proper tube size fitting and located within twenty (20) feet of the enclosure protection system.
2.
If a service valve is placed between the protective gas supply header and the enclosure protection system, it must be installed in close proximity of the protected enclosure and be labeled in accordance with NFPA 496,
2003 edition.
3.
Select the appropriate fittings required to connect the protective gas supply to the protection system regulator as determined on page 12, “Pneumatic Tubing
Requirements”.
4.
Determine appropriate tubing route from the protective gas supply header to the protection system regulator.
5.
Bend tubing using industrial grade benders, check tubing fit to ensure proper seating between the tubing and fittings. Fully ream all tubing ends.
6.
Install tubing and tighten all fittings to fitting manufacturer’s specifications. Secure tubing to appropriate structural supports as required.
Enclosure Supply & Reference Connections
1.
Choose location for the enclosure supply connection(s) based on the requirements on page 7, “Getting Started”.
2.
Place the enclosure reference connection fitting directly behind the enclosure protection system whenever possible. For systems protecting multiple enclosures in series, the enclosure reference connection fitting must be placed on the last enclosure in the series.
(See page 7, “Getting Started”)
3.
Drill and deburr enclosure supply and reference fitting holes on the protected enclosure. Mount the fittings.
4.
Determine appropriate route for the enclosure supply and reference tubing.
5.
Bend tubing using industrial grade benders, check tubing fit to ensure proper seating between the tubing and fittings. Fully ream all tubing ends.
6.
Install tubing and tighten all fittings to fitting manufacturer’s specifications. Secure tubing to appropriate structural supports as required.
Tubing PM Configurations
Enclosure Bulkhead Fittings
1.
Select the fittings required to install the System Supply,
System Supply Bulkhead Fitting and Atmospheric
Reference Bulkhead Fitting, (see page 12, “Pneumatic
Tubing Requirements”).
2.
Choose location for the system supply bulkhead fitting.
This fitting allows the protective gas supply to pass through the wall of a protected enclosure to the protection system’s regulator supply inlet connection.
3.
Choose location for the atmospheric reference bulkhead fitting. This fitting allows the enclosure pressure gauge and Electrical Power Control Unit (EPCU) to reference atmospheric pressure.
4.
Drill and deburr system supply and reference bulkhead fitting holes in the protected enclosure. Mount the fittings.
System Supply & Reference Connections
1.
Select or install a protective gas supply header tap, fitted with the proper tube size fitting and located within twenty (20) feet of the enclosure protection system.
2.
If a service valve is placed between the protective gas supply header and the protection system, it must be in close proximity of the protected enclosure and labeled in accordance with NFPA 496.
3.
Determine appropriate tubing route from the protective gas supply header to the system supply bulkhead fitting.
4.
Determine appropriate tubing route from the system supply bulkhead fitting to the protection system regulator.
5.
Determine appropriate tubing route from the atmospheric reference bulkhead fitting to the enclosure pressure gauge’s reference inlet connection.
6.
Bend tubing using industrial grade benders, check tubing fit to ensure proper seating between the tubing and fittings. Fully ream all tubing ends.
7.
Install tubing and tighten all fittings to fitting manufacturer’s specifications. Secure tubing as required.
14
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
Electrical Supply Requirements
General Wiring Requirements
WARNING
THIS DEVICE CONTAINS ELECTRICAL PARTS WHICH
CAN CAUSE SHOCK OR INJURY
All electrical connections, conduit and fittings on the protected enclosure must be suitable for the hazardous location in which they are installed. In addition, all conduit and wire must be installed in accordance with NEC as required and all relevant plant and local codes.
Conduit seals must be utilized on all electrical conduit connections and poured with an approved compound prior to operation of the protection system.
Exception: Do not use seals on conduit used as a protected
“wireway” to supply protective gas to adjacent protected enclosures. The same conduit can be utilized for both electrical and pneumatic service to an adjacent protected enclosure(s), provided the conduit is oversized to allow a minimum free clearance equal to or larger than the pipe size required between multiple enclosures as stated on page 7,
“Getting Started”.
HELPFUL HINT
Pepperl+Fuchs recognizes it may be impractical to pour all electrical conduit seals prior to installation in the field. However, all conduit connections must be sealed for proper testing and operation of the
Enclosure Protection System. Therefore,
Pepperl+Fuchs recommends the use of temporary seals such as duct seal or masking tape for bench or shop testing, prior to final field installation.
Typical Enclosure Wiring Methods
I n a general sense, protected enclosures should be wired similar to explosion proof enclosures, in accordance with
Article 500 of the National Electric Code - NFPA 70.
Single conductor wiring should be placed in rigid metal conduit, seal-flex conduit or other mediums approved for use in the hazardous location surrounding the protected enclosure. Additionally, NFPA 496 requires the use of approved seals on all pressurized enclosure conduit wiring entries, in accordance with NFPA 70. Furthermore, the use of an approved seal is simply the most practical way to prevent excessive leakage through conduit connections.
However, while explosion proof enclosures require conduit seals on all cable entries, in accordance with NFPA 70. Other methods of sealed cable entries that are suitable for hazardous locations can be used, such as compression glands.
In conclusion, there are two primary goals. First, the installer should ensure that all associated wiring and cable is protected by pressurization or other means, such as explosion proof conduit or intrinsic safety barriers. Secondly, the installer should ensure that all associated conduit and wireways are sealed to conserve protective gas, unless they are used to supply protective gas to other enclosures or devices.
Typical Enclosure Wiring Connections
Conduit
Explosion
Proof Device
Seal
Conduit
Intrinsically
Safe Or Fiber
Optic Device
EPCU Power Requirements
The Electrical Power Control Unit's (EPCU) electrical power source must originate from a circuit breaker or fused disconnect suitable for the hazardous location in which it is installed. The power source should be uninterrupted and the switch must be located within fifty (50) feet of the protected enclosure(s) and the enclosure protection system and be properly marked. For EPCU power specifications see page
4, "System's Specifications".
Alarm Signal Requirements
Pepperl+Fuchs strongly recommends use of the optional alarm system contacts of the EPCU, connected to an alarm system located in a constantly attended location to indicate the failure of the enclosure protection system. For EPCU alarm signal specifications see page 4, "System's
Specifications".
Seal
Gland
Fitting
Cable
Conduit
Seal
Pressurized
Raceway
Intrinsically
Safe Or Fiber
Optic Device
Independently
Pressurized
Device
Adjacent
Pressurized
Device
Protected Enclosure
Or Device
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
15
Electrical Power Control Unit
Power Mode
Selector Switch
General Layout & Electrical Conduit Connections
EPCU Electrical Rating
Nameplate
Power Mode
Selector Switch
(Optional Mounting Hole
-Factory Use Only-)
Type 7
Explosion Proof
Enclosure
LED Display
Type 7
Explosion Proof
Screw Cover
Type 7
Explosion Proof
Breather Drain
(See Important
Notes below)
1/2" NPT Conduit
Connection Ports
Typical 6
(See Important
Notes below)
IMPORTANT NOTES
For proper moisture drainage of the Type 7 enclosure, the installer must 1) move the Type 7 breather drain to one of the bottom conduit entrances or 2) use drain seals on all conduit connected to the bottom two conduit entrances.
The Type 7 breather drain is not provided or required with PM configurations.
Top two conduit entrances will be dedicated for Intrinsic Safe wiring ONLY when the EPCU is supplied with
Pepperl+Fuchs' optional ISB Intrinsic Safety Barriers.
EPCU LED Displays
Class I - Alarm Only Class I - Alarm & Bypass
16
Class II - Alarm Only Class II - Alarm & Bypass
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
EPCU Power Rating
EPCU Electrical Power Rating Nameplate
The EPCU (Electrical Power Control Unit) of this Type "X" purging / pressurization system is offered in various styles. For proper installation and operation, begin by examining the EPCU Electrical Rating Nameplate to identify the System Input voltage and power requirements, enclosure power and alarm contact ratings and third party approval markings. Next, match the LED display of your EPCU with one of the displays shown on page 16. The EPCU LED Display will help identify the options featured on your system e.g. Normal Running mode or Conditional Bypass Class I purging (timer) or Class II pressurization
(no timer).
EPCU SERIAL
NUMBER
REQUIRED WARNING
STATEMENTS
MODEL 2000 ELECTRICAL POWER CONTROL UNIT
CAUTION: OPEN CIRCUIT BEFORE REMOVING COVER
ATTENTION: OUVRIR LE CIRCUIT AVANT D'ENLEVER LE COUVERCLE
SERIAL NO.
XXXXXX INPUT VOLTAGE & POWER REQUIREMENTS
CSA Encl. 3
CLASS I, DIV. 1, Gr C&D
CLASS II, DIV. 1, Gr E, F, G HAS
UL & FM APPROVALS ONLY
ENCL POWER & ALARM CONTACTS
ARE RATED 120/240 VAC, 20 AMPS
120 SINGLE PHASE, 60 CYCLE, 1 AMP
240 SINGLE PHASE, 50 CYCLE, 1 AMP
AREA CLASSIFICATION
Defines the area classifications for which the EPCU is suitable for operation
EPCU INPUT POWER
REQUIREMENTS
Factory set at time of order
Assembled EPCU Electronics Module
Logic Module
Power Module
Cable
120/240 VAC
Power Module Pressure Switch
Module
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
17
Electrical & Pneumatic Diagrams
LH, RH, TM, BM, WM & FM Configurations
Electrical Power
Supply Conduit
Hub
Optional Enclosure
Protection Vent
Conduit Seal Union Union Conduit Seal
System
Supply
Breather
Venturi
Orifice
Electrical Power
Control Unit
Drain
Sintered
Vent
Enclosure
Pressure Gauge
Enclosure
Reference
Tubing
System Supply
Tubing
Enclosure
Supply
Tubing
Enclosure Pressure
Control Regulator
Enclosure Reference
Bulkhead Fitting
Enclosure Supply
Bulkhead Fitting
Protected Enclosure
PM Configurations
Optional Enclosure
Protection Vent
Electrical Power
Supply Conduit
Hub
System
Supply
Atmospheric Pressure
Reference Bulkhead
Fitting
System Supply
Bulkhead Fitting
Inlet
Electrical Power
Conduit
Conduit Seal Union Union
Atmospheric
Reference
Tubing
Enclosure Pressure
Gauge
Enclosure
Pressure
Reference
Enclosure
Pressure
Reference
Electrical Power
Control Unit
Enclosure Pressure
Control Regulator
System
Supply
Tubing Enclosure
Supply
Discharge
Conduit Seal
Electrical
Power to
Enclosure
18
Protected Enclosure
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
Conduit Installation
EPCU Electrical Conduit
Unplug the four unlabeled conduit entrances located on the sides and bottom of the EPCU enclosure (See page 16,
"EPCU Layout" for conduit entrance layout).
The installer must mount the Type7 drain fitting supplied with the system (except for PM configurations) in one of the bottom conduit entrances of the EPCU, or utilize drain seals on all conduit connected to the bottom two (2) conduit entrances of the EPCU.
Following the instructions listed below, install all conduit, fittings and seals (or drain seals if utilized) between the
EPCU, alarm system (if utilized) and the protected enclosure(s). Plug all remaining EPCU conduit entrances.
1.
Choose the location for the enclosure’s electrical conduit connection(s) based on the requirements on page 15,
“Electrical Supply Requirements”.
2.
Drill and deburr enclosure conduit fitting holes in the protected enclosure. Mount the fittings.
3.
Determine appropriate route for the enclosure electrical enclosure and alarm signal conduit.
4.
Measure, cut and thread conduit, check conduit fit to insure proper seating. Fully ream all conduit.
5.
Install conduit and tighten all fittings to fitting manufacturers specifications. Secure conduit to appropriate structural supports as required.
6.
Seal all conduit with an approved compound prior to operation of the protection system.
Optional Intrinsic Safety Barrier Conduit
Systems supplied with optional Intrinsic Safety Barriers (ISB) will be supplied with clearly labeled isolated conduit entries, a solid body wireway with snap cover and plexiglass wiring partitions. These accessories provide a fully isolated wiring path to the barrier wiring terminal located on the lower left corner of the EPCU Logic Module. All IS wiring must be isolated.
1.
Choose the location for the enclosure’s IS conduit connection(s) based on the requirements on page 15,
“Electrical Supply Requirements”.
2.
Drill and deburr enclosure conduit fitting holes in the protected enclosure. Mount the fittings.
3.
Determine appropriate route for the IS conduit.
4.
Measure, cut and thread conduit, check conduit fit to insure proper seating. Fully ream all conduit.
5.
Install conduit and tighten all fittings to fitting manufacturers specifications. Secure conduit to appropriate structural supports as required.
6.
Seal all conduit with an approved compound prior to operation of the protection system.
EPCU Conduit Connection Parts
Fitting Kits Can Be Factory Furnished
1.
To connect enclosure power from the EPCU to the protected enclosure, one (1) LCK (L fitting Conduit Kit) or equivalent conduit elbow, coupling and seal fittings.
2.
For EPCU to enclosure wiring connection with one (1) additional conduit connection path, one (1) TCK (T fitting
Conduit Kit) or equivalent conduit tee, coupling and seal fittings.
IMPORTANT NOTE
Model LCK & TCK are offered primarily to OEM's attempting to achieve a "field ready" installation. In all cases, limited pipe fitting skills will be required.
Pre-cut 150# galvanized steel pipe nipples can be acquired from local plumbing shops, but a hole saw or punch and wrenches are required to install kits.
TCK “T” Fitting
Conduit Kit
LCK “L” Fitting
Conduit Kit
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
19
Power Modules & Wiring Diagram
EPCU 120/240 VAC Power Module Layout
Isolated Coil
Voltage Transformer
Power Control Switch
Cable Header
Voltage Input Selector
Header (factory set for
120 VAC power)
Pressure Switch
Cable Header
Logic Module
Cable Header
1 Amp Input Fuse
Redundant Safe
Pressure Relay
Rapid Exchange ®
Solenoid Valve (RESV)
Relay
Alarm Relay
RESV Factory Wiring
Terminal
Enclosure
Power Relays
20 Amp Enclosure
Power Fuse
EPCU 120/240 VAC
Power Module
VAC & VDC Power Module Electrical Wiring Diagram
Field Wired
Power Module
Terminals
20 AMP
1
1
FUSES 1
Isolated
Enclosure
Power Relays
NO
12
12
12
NO
Isolated
Alarm
Relay
NO NC
1 2 3 4 5 6 7 8 9 10
Power Module
Wiring Terminal
EPCU Power
Supply Terminals
120 VAC
*240 VAC ( Optional voltage )
Gnd
Gnd
Hot
Hot
Neu
Neu
In Out In
Enclosure
Power
Supply
Terminals
Out
NO Com NC
Remote Alarm
Relay Terminals
* European Single Phase 240 VAC only.
Power and alarm terminals are feed-thru dry switch contacts.
Caution should be exercised to ensure that the EPCU wiring is properly connected.
All terminal connections to the EPCU should be wired with spade or round lugs.
20
Using 12 gauge maximum to 16 gauge minimum wire only, check EPCU power requirements (See page 15) and wire to the EPCU power source and alarm system (if utilized). Then route power source(s) through the EPCU power in and out terminals to all non-rated devices within the protected enclosure(s).
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
Logic Module & Barrier Wiring
Barrier Fault & Active
Status Indicators
Barrier C
Socket
Barrier B
(Installed)
Barrier A
Socket
EPCU Logic Module & Pressure Switch Module
Primary
Microprocessor
Factory
Programing
Header
Redundant
Controller
(GAL)
Power Module
Cable Header
Primary Safe
Pressure Switch
EPCU Pressure
Switch Module
EDT, SLT &
RET Timers Barrier
Wiring
Terminal
Pressure Switch
Calibration Access
LED Status
Display
EPCU Logic Module
Optional ISB Wiring Requirements
( - ) BLUE ( + ) BROWN
INTRINSICALLY SAFE AUXILIARY INPUTS
A B C
+ + +
All optional intrinsic safety (IS) wiring must be isolated from all other electrical wiring using the dedicated IS conduit entrances and wireway of the EPCU, (See "Optional ISB
Conduit Installation" on page 19 for more details). In addition, all wiring must be installed in accordance with the NEC and all relevant local and plant codes.
The Intrinsic Safety Barriers are designed to function in conjunction with a customer furnished switch and SRM-
4000 Switch Resistor Module, or an NJ... NAMUR sensor.
The customer supplied switch must have dry contacts which contain no inductance or capacitance.
The SRM-4000 Switch Resistor Module and the NJ...NAMUR
sensor are supplied with approximately ten (10) feet of wiring. Using 16 to 18 gauge shielded wire, the cable lengths can be extended to a maximum of 100 feet.
In all applications, the module of the Switch Resistor Module
Cable must be installed as close to the customer supplied switch as possible for proper operation.
Wiring lugs are not recommended for Intrinsic Safety Barrier wiring connections.
See page 22 for barrier operation and factory programing.
Space for Optional
Redundant Safe
Pressure Switch
EPCU Power Control Modes
NORMAL RUNNING (NR) MODE
EPCU features an on-off push-button power control switch to activate control functions. Switch must be depressed to initiate start-up. After completion of start-up, safe pressure must be lost or switch must be depressed to deenergize enclosure power relays.
CONDITIONAL BYPASS (CB) MODE
EPCU features an on-off-bypass power control switch to activate control functions. Switch must be set to "on" position to initiate start-up. After enclosure power is energized, safe pressure must be lost or switch must be set to "off" position to deenergize enclosure power. After enclosure power is energized, switch may be set to "bypass" position, to temporarily latch enclosure power relays. A flashing LED then indicates bypass engaged, and the enclosure can then be accessed without deenergizing power (performed under specific conditions). Following access, safe pressure must be reestablished to resume normal operation. At that time, the switch may be reset to the on position, without disruption of enclosure power. Alarm relay normally deenergizes only upon loss of safe pressure, but can be factory programmed to deenergize when bypass is engaged, if specified at time of order.
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
21
Barriers & Field Adjustments
Optional Intrinsic Safety Barriers Description
The EPCU Logic Module can accommodate up to three intrinsic safety barriers, to interact with remote devices and affect operation of the EPCU. The barriers are installed and programmed by the factory at time of order, and they are designed to function either in conjunction with a customer furnished switch and a Pepperl+Fuchs furnished resistor network cable, or a Pepperl+Fuchs furnished proximity detector. Each barrier develops a low power signal, to create a two wire closed loop circuit. Operational status of each barrier is indicated by a green LED to show active (closed switch) status, and by a red LED to show faulted (line breakage) cable status. All barriers can be reprogrammed to duplicate other barrier functions as required, upon specific request.
Optional ISB Factory Programing
Barrier A Function - when switch opens
Disables start-up cycle
Deenergizes enclosure power and alarm relay
Functions parallel to safe pressure switch
Barrier B Function - when switch opens
Not programmed for this model - custom applications only
Barrier C Function - when switch closes
Energizes RESV Relay - custom applications only
LED Display Indicators
Power Off: Enclosure Power Relays Deenergized
Power On: Enclosure Power Relays Energized
Safe Pressure: Enclosure Pressure > 0.15" or 0.50" w.c.
Timer Running: Exchange Timer Active - Class I Only
Alarm Active: Enclosure Pressure < 0.15" or 0.50" w.c.
Bypass Engaged: Control Bypass Active - CB Mode
Field Adjustable Timer Functions
EDT (Exchange Delay Timer) (FA Style only) provides a time delay to prevent Rapid Exchange ® solenoid valve from energizing until safe pressure can be stabilized.
SLT (Solenoid Latching Timer) (FA Style only) provides a time delay to keep the Rapid Exchange ® solenoid valve energized until Rapid Exchange ® pressure is detected. If the pressure is not detected, the EPCU will reset.
RET (Rapid Exchange ® Timer) provides a time delay after
Rapid Exchange ® pressure is detected, to allow four volume exchanges (ten volumes for motors) prior to energizing the enclosure power relays. In Class I areas only, if Rapid
Exchange ® pressure is lost or interrupted during time delay cycle, the EPCU will reset.
EDT, SLT & RET Timer Settings
Rotary Switch
Body
E
F
D
C
B
A
9
0
8
EDT & SLT Timer
POSITION TIME IN SECONDS
D
E
F
9
A
B
C
6
7
4
5
8
2
3
0
1
50
55
60
65
70
75
80
25
30
35
40
45
5
10
15
20
1
2
3
4
5
6
7
RET Timer
POSITION TIME IN MINUTES
D
E
F
9
A
B
C
6
7
4
5
8
2
3
0
1
50
55
60
65
70
75
80
25
30
35
40
45
5
10
15
20
NOTE: Power must be removed from the EPCU via the local disconnect switch for approximately 10 seconds for timer adjustments to reset.
EDT & SLT Timers are not functional on Model 2001A.
22
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
Class I Set-up Procedure
HELPFUL HINTS
Regulator may be in the locked position upon arrival. To adjust regulator, pull handle to outward position.
To test the vent’s operation, gently prod the vent flapper open with a soft pointed object, ( example: eraser end of a pencil) ensuring that the vent valve works freely. On vertically configured vents, this can be accomplished from within the protected enclosure. Side mounted -90 configured vents can be tested by removing the pipe plug at the bottom of the mounting tee. Multiple operations require only one test per day if enclosure is not opened or left unattended.
Class I Purging Set-up
1.
Close the Enclosure Pressure Control Regulator fully by turning counterclockwise (CCW).
2.
Temporarily connect the inert gas supply to a 0 to 250
SCFH flowmeter. Connect the outlet of the flowmeter to the Enclosure Pressure Control Regulator.
3.
Check operation of Enclosure Protection Vent (if utilized).
4.
Seal enclosure(s) and adjust Enclosure Pressure Control
Regulator by opening slowly clockwise (CW) to set a
“Safe” 0.25 inch pressure on the Enclosure Pressure
Indicator.
NOTE: If pressure setting is difficult to stabilize or set, see page 26, “Trouble-Shooting Procedures”.
5.
When safe enclosure pressure is stabilized, measure flow of inert gas supply through Protection System, to calculate required exchange time, based on the Class I exchange time chart located to the left. Close the
Enclosure Pressure Control Regulator fully.
6.
Set RET timer (see page 21 for timer location) for required exchange time based on the Class I Volume Exchange
Time, five (5) minute minimum.
7.
Install and tighten cover of EPCU. Ensure the conduit is sealed with approved compounds.
8.
Depress the On-Off push-button (NR mode) or turn selector switch to the On position (CB mode). All LEDs should illuminate fully for two seconds (self test), then all
LEDs should turn off except Power Off (solid red) and
Alarm Activated (flashing red) LEDs.
9.
Turn Enclosure Pressure Control Regulator slowly CW to set the Enclosure Pressure Indicator to a "Safe" 0.25
inch pressure. The Safe Pressure and Timer Running
LEDs should be on, the Alarm Active LED should turn off.
Check for a 0.10 to 0.15 inch trip point by slowly stroking the indicator from 0.10 to 0.25 inch readings. The Safe
Pressure, Alarm Active and Timer Running LEDs should turn on and off when the indicator reads between 0.10
and 0.15 inches.
10. Having ensured that the Safe Pressure and Timer Running
LEDs are functioning properly, Start-Up Procedures located on page 25 may now be followed to step through a complete start up cycle, ensuring that the System functions normally during all phases of operation.
CLASS I VOLUME EXCHANGE TIME CHART
MEASURED FLOW
0.10 SCFM / 6 SCFH
0.25 SCFM / 15 SCFH
0.50 SCFM / 30 SCFH
0.75 SCFM / 45 SCFH
1 SCFM / 60 SCFH
REQUIRED EXCHANGE TIME
40 Minutes per Cubic Foot
16 Minutes per Cubic Foot
8 Minutes per Cubic Foot
5.5 Minutes per Cubic Foot
4 Minutes per Cubic Foot
2 SCFM / 120 SCFH
3 SCFM / 180 SCFH
2 Minutes per Cubic Foot
1.5 Minutes per Cubic Foot
4 SCFM / 240 SCFH or greater 1 Minute per Cubic Foot
NOTE: The volume exchange time chart is based on a four
(4) enclosure volume exchange. Multiply the required exchange time above by 2.5 for applications requiring a ten (10) volume exchange (motors).
Regardless of enclosure volume or system flow rate,
Pepperl+Fuchs requires that operators withhold power to the enclosure while inducing Class I exchange, for at least five (5) minutes. Normal exchange time calculations should be doubled if large obstructions block inert gas flow.
The Start-Up Instruction Nameplate Exchange Time Slot will be blank, but the unit may feature a set of direct factor nameplates with self-adhesive backing such as “TEN
MINUTES”, for application to the start-up instructions, dependent on how the system was specified and purchased.
Field modification of this nameplate, to show a direct factor, is acceptable as noted above if the method used to mark the nameplate does not deface the instructions listed. Materials used for the marking must be indelible and withstand prevailing environmental conditions.
11. Cease testing and remove test equipment (Flowmeter).
12. Connect the inert gas supply directly to the Enclosure
Pressure Control Regulator.
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
23
Class II Set-up Procedure
HELPFUL HINTS
Regulator may be in the locked position upon arrival. To adjust regulator, pull handle to outward position.
To test the vent’s operation, gently prod the vent flapper open with a soft pointed object, ( example: eraser end of a pencil) ensuring that the vent valve works freely. On vertically configured vents, this can be accomplished from within the protected enclosure. Side mounted -90 configured vents can be tested by removing the pipe plug at the bottom of the mounting tee. Multiple operations require only one test per day if enclosure is not opened or left unattended.
Class II Pressurization Set-up
1.
Close the Enclosure Pressure Control Regulator fully, by turning it counterclockwise (CCW).
2.
Remove all traces of combustible dust from the protected enclosure using a suitable vacuum tool.
3.
Check operation of Enclosure Protection Vent (if utilized).
4.
Seal all protected enclosure(s).
5.
Depress the On-Off push-button (NR mode) or turn selector switch to the On position (CB mode). All LEDs should illuminate fully for two seconds (self test), then all
LEDs should turn off except Power Off (solid red) and
Alarm Activated (flashing red) LEDs.
6.
Turn Enclosure Pressure Control Regulator slowly CW to set the Enclosure Pressure Indicator to a "Safe" 1.0 inch pressure. The Safe Pressure and Power On LEDs should be on, the Alarm Active should be off. The EPCU will energize enclosure power at this time. Check for a 0.50
to 0.55 inch trip point by slowly stroking the indicator from 0.40 to 1.0 inch readings. The Safe Pressure,
Power On and Alarm Active LEDs should turn on and off when the indicator reads between 0.50 and 0.55 inches.
NOTE: If pressure setting is difficult to stabilize or set, see page 26, “Trouble-Shooting Procedures”.
7.
Having ensured that all LEDs are functioning properly,
Start-Up Procedures located on page 25 may now be followed to step through a complete start up cycle, ensuring that the System functions normally during all phases of operation.
Model
Identification
Nameplate
Enclosure
Pressure
Control
Regulator
Conditional
Bypass
Operating
Instructions
EPCU Power
Selector
Switch
Enclosure
Pressure
Gauge
Start - Up
Instruction
Nameplate
LED Status
Nameplate
EXP EPCU
Enclosure
System
LED
Display
24
Model 2001A-STD-LH
Front View
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
Operating Sequence
WARNING
Do not exceed a “Safe” pressure with the Enclosure Pressure Control Regulator.
Operators must follow step-by-step sequence of the Start-Up Instructions Nameplate on the Protection System.
Do not use the Bypass Modes without first securing a "Hot Work" permit.
Never leave the system unattended in Bypass Modes.
Class I Purging Operation
With the inert gas supply on, RET Timer set properly,
EPCU power and alarm system energized (if utilized) . .
1.
Carefully read Start-Up Instruction Nameplate on system.
2.
Check operation of the Enclosure Protection Vent (Model
EPV-1, if utilized), opening it manually several times, (see page 23, “Helpful Hint”).
3.
Seal protected enclosure(s).
4.
Depress the On-Off push-button (NR mode) or turn selector switch to the On position (CB mode). Each LED should illuminate fully for two seconds, then all LEDs should turn off except Power Off (solid red) and Alarm
Activated (flashing red) LEDs.
5.
Turn Enclosure Pressure Control Regulator slowly CW to set the Enclosure Pressure Indicator to a "Safe" 0.25
inch pressure. The Safe Pressure and Timer Running
LEDs should be on, the Alarm Active LED should turn off.
NOTE: If the Safe Pressure or Timer Running LEDs blink on and off or "flicker" during this cycle, EPCU will reset
RET timer.
6.
Standby until the EPCU completes the timing cycle and energizes enclosure power. Safe Pressure LED should stay on, Timer Running LED should turn off and Power
On LED should turn on.
7.
Ensure the Protection System Enclosure Pressure
Indicator maintains a “Safe” 0.25 inch pressure for one
(1) minute. Readjust Enclosure Pressure Control
Regulator if required.
8.
If "Safe" 0.25 inch pressure is lost, the EPCU will deenergize enclosure power and activate alarm system
(if utilized).
Class II Pressurization Operation
With the inert gas supply connected, EPCU power energized and alarm system energized (if utilized) . .
1.
Carefully read Start-Up Instruction Nameplate on system.
2.
Check operation of the Enclosure Protection Vent (Model
EPV-1, if utilized), opening it manually several times, (see page 23, “Helpful Hint”).
3.
Remove all traces of combustible dust.
4.
Seal protected enclosure(s).
5.
Depress the On-Off push-button (NR mode) or turn selector switch to the On position (CB mode). Each LED should illuminate fully for two seconds, then all LEDs should turn off except Power Off (solid red) and Alarm
Activated (flashing red) LEDs.
6.
Turn Enclosure Pressure Control Regulator slowly CW to set the Enclosure Pressure Indicator to a "Safe" 1.0 inch pressure. The Safe Pressure and Power On LEDs should be on, the Alarm Active LED should turn off.
NOTE: If the Safe Pressure or Power On LEDs blink on and off or "flicker" during this cycle, EPCU will reset enclosure power.
7.
Ensure the Protection System Enclosure Pressure
Indicator maintains a “Safe” 1.0 inch pressure for one (1) minute. Readjust Enclosure Pressure Control Regulator if required.
8.
If "Safe" 1.0 inch pressure is lost, the EPCU will deenergize enclosure power and activate alarm system (if utilized).
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
25
Trouble - Shooting Procedures
Problem or Fault
Enclosure pressure control regulator will not hold a safe pressure.
Possible Causes
Leakage around gasketing, covers, seams, piping and tubing connections, conduit connections and electrical conduit seals of the enclosure.
Corrective Action
Tighten enclosure latches: Where tightening is not feasible, and gasketing materials are not practical, holes or gaps can be closed with silicone sealant applied from inside the protected enclosure.
Enclosure pressure indicator reading is difficult to stabilize.
Insufficient enclosure leakage or opening of the venturi orifice is crimped too small.
Remove the orifice, cut off the crimped end and ream the tube, then recrimp and reinstall the tube to note effect. As tube is shortened, reamed, and recrimped, sensitivity decreases, allowing easier adjustment of setpoint on the enclosure.
Enclosure Pressure Indicator "Drifts" up or down from the "Safe" pressure setting.
Application involves a small, tightly sealed enclosure and/or a fluctuating protective gas supply.
Pre-regulate the protective gas supply upstream of the enclosure protection system to 5 PSI maximum.
For dramatic fluctuations in the protective gas supply, it may be necessary to utilize a self-relieving low flow precision regulator to preregulate the protective gas supply.
Enclosure Pressure Indicator reads a
"Safe" pressure but the Safe Pressure
LED is not illuminated.
Conduit seal between EPCU and protected enclosure is not poured or is leaking pressure back into the EPCU.
EPCU breather drain is clogged (all systems except PM configurations).
Safe Pressure switch is out of calibration.
With area positively known to be nonhazardous, remove screw cover of the EPCU and attempt a complete start-up procedure. If the system works properly, check enclosure power conduit seal for leakage and the EPCU breather drain for blockage.
If the system does not operate properly, calibrate the Safe Pressure switch.
Calibrate by slowly adjusting counterclockwise to decrease the setpoint, and clockwise to raise the setpoint.
(Do not attempt to calibrate the switch until all efforts to make the switch respond properly have failed)
Problems persists, or if the system does not appear to be operating properly.
Persisting problems.
Contact Pepperl+Fuchs Applications/
Customer Service Department at
(330) 486-0002 for more information.
This section covers the most common problems documented with these systems. Any problems not covered in this section should be addressed directly to our factory. Please address all service needs to Pepperl+Fuchs, Inc. - Customer
Service Department at (330) 486-0002.
26
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
Warranty Terms and Conditions
PEPPERL+FUCHS STANDARD 24-MONTH WARRANTY
1.
Limited Warranty. Pepperl + Fuchs, Inc. (“P+F”) warrants Purge Units and components for Purge Units manufactured by
P+F (“Product” or “Products”) to be free from defects in material and workmanship under Normal Use for a period of twenty-four (24) months from the date of shipment of such Products from P+F’s warehouse or place of manufacture (or from P+F’s authorized representative or distributor). Only the original purchaser of such Products (the “Customer”) shall be entitled to the benefit of the foregoing Limited Warranty. No representative, agent or salesman of P+F is authorized to give or provide any warranty or make any representation contrary to or in addition to the foregoing Limited Warranty.
2.
Inspection and Claims. Customer must inspect and test all Products upon receipt. All claims under the Limited Warranty provided herein must be made within thirty (30) days of the discovery of the defect. Customer must obtain shipping instructions from P+F prior to returning any Product, which Product must be returned at Customer’s expense in accordance with P+F’s instructions.
3.
Limitations and Exclusions. “Normal Use” shall mean use and operation within rated capacities, at the correct voltage, and with any required maintenance as provided in the applicable P+F Operating Manuals. The Limited Warranty provided herein does not apply to (i) any Products which have been altered or modified in any way or disassembled by the
Customer or anyone else, (ii) any Products which have been subject to misuse, negligence or accident, or improperly installed, changed, substituted or replaced, (iii) any part or component not manufactured by P+F, or (iv) any part or component that is subject to wear or consumption. For parts or components not manufactured by P+F, the Customer or any other user or owner shall have only the warranty provided by the manufacturer of such part or component. The
Limited Warranty set forth herein is also subject to the following:
(1) The Limited Warranty is limited to electronic and mechanical performance only, as expressly detailed in the product specifications, and does not apply to cosmetic appearance;
(2) The Limited Warranty shall not apply to any cables attached to, or integrated with, any Products.
(3) The Limited Warranty shall not apply to any Products which are stored, or utilized, in harsh environmental or electrical conditions outside P+F’s written specifications.
THE LIMITED WARRANTY SET FORTH HEREIN IS THE ONLY WARRANTY MADE BY P+F WITH RESPECT TO THE
PRODUCTS. IT IS EXPRESSLY AGREED AND UNDERSTOOD THAT P+F MAKES NO WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. EXCEPT FOR THE LIMITED WARRANTY SET FORTH
HEREIN, THERE IS NO OTHER WARRANTY, EXPRESS, IMPLIED OR STATUTORY; AND THERE IS NO AFFIRMATION OF
FACT OR PROMISE BY P+F WITH REFERENCE TO THE PRODUCTS. IN NO EVENT SHALL P+F BE LIABLE FOR
ACTUAL OR ANTICIPATED LOST PROFITS OR FOR INCIDENTAL OR CONSEQUENTIAL OR PUNITIVE DAMAGES OR
FOR DAMAGES RESULTING FROM BUSINESS INTERRUPTION, OR INJURY OR DEATH OF PERSONS, OR INJURY TO
PROPERTY. P+F’S LIABILITY ON ANY CLAIM OF ANY KIND ARISING OUT OF, CONNECTED WITH OR RESULTING
FROM THE DESIGN, MANUFACTURE, SALE, REPAIR OR OPERATION OF A PRODUCT, SHALL NOT EXCEED THE
PRICE ALLOCABLE TO THAT PRODUCT OR THE PART THEREOF WHICH GIVES RISE TO THE CLAIM. THE REMEDY
SET FORTH IN THIS LIMITED WARRANTY CONSTITUTES THE SOLE AND EXCLUSIVE REMEDY OF THE CUSTOMER.
P+F SHALL NOT BE LIABLE FOR PENALTIES OF ANY DESCRIPTION.
4.
Limitation of Remedies. In the event of P+F’s liability, whether on this Limited Warranty or based on contract, tort
(including, but not limited to, negligence and strict liability) or otherwise, Customer’s sole and exclusive remedy will be limited to, at P+F’s option, the repair or replacement (f/o/b P+F’s place of manufacture) by P+F of any non-conforming items for which claim is made by Customer in accordance with paragraph 2, or the repayment of the portion of the purchase price paid by Customer attributable to the non-conforming item.
5.
Responsibility of Customer: Safety and Protection Precautions. P+F takes great care to design and build reliable and dependable Products; however, some Products can fail eventually. Customer must take precautions to design its equipment to prevent property damage and personal injury in the unlikely event of a failure. AS A MATTER OF POLICY,
P+F DOES NOT RECOMMEND THE INSTALLATION OF PRODUCTS AS THE SOLE DEVICE FOR THE PROTECTION OF
PERSONNEL OR PROPERTY AND, THEREFORE, THE CUSTOMER SHOULD BUILD IN REDUNDANCY OR DUAL
CONTROL USING APPROVED SAFETY DEVICES FOR THESE APPLICATIONS.
6.
Conflicts. In the event there is any conflict between the provisions of this Limited Warranty and any provisions contained in any orders, offers, acceptances or other writings or statements provided or made by Customer to P+F, the provisions of this Limited Warranty shall prevail, and the contract between P+F and the Customer shall be deemed formed only upon the provisions set forth in this Limited Warranty, and any additional or conflicting provision inserted by Customer shall be of no force or effect.
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
27
System Maintenance
Regular Maintenance
Drain the Protection System Regulator frequently and clean System with non-solvent cleaning agents only.
Long Term Maintenance
Calibrate the enclosure pressure indicator to 0 inches by venting the purge pressure reference port and the protected enclosure to atmosphere and adjusting the calibration screw in the lower center portion of the indicator’s face.
Fully open the enclosure pressure control regulator, to blow out any deposits around the tip of the valve and to ensure that the enclosure protection vent is operating properly, then carefully readjust system according to the set-up procedure and operating sequence on pages 23 through 25. Replace or tighten stem packing nut as required to prohibit stem packing leakage.
Carefully disassemble the enclosure protection vent by loosening the two bottom hex nuts that hold the unit together.
(DO NOT REMOVE CAP NUTS ON TOP OF VENT BODY)
Carefully clean the flapper valve and vent body seats with warm soap and water, being careful not to extend the vent valve beyond its normal opening point, and being careful not to exert any stress on the valve hinge.
Examine the entire Protection System and the protected enclosure(s), and replace any defective parts during routine shutdown of the protected enclosure(s). Parts are available from Pepperl+Fuchs on immediate notice as required.
MAINTENANCE SCHEDULE
Date Work Performed Performed by
28
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
Date
MAINTENANCE SCHEDULE
Work Performed Performed by
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
29
CUSTOMER NOTES
30
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
CUSTOMER NOTES
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
31
NOTES:
SYSTEMS IDENTIFICATION & APPLICATION INFORMATION
Date of Installation
Unit Serial #
Item
Customer P.O.#
Customer Project#
Service
Type
Features
Application
Local Sales Representative
32
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
advertisement
Key Features
- Pressurization or purging system
- Operates on compressed air or inert gas
- Regulates and monitors pressure in enclosures
- Prevents dust accumulation or removes flammable gas/vapor
- Includes an EPCU for system monitoring and control
- Reduces hazardous area rating within enclosures