Siemens | Synova FC330A | FC330A Auto-addressing analogue fire control panel

FC330A
Synova®
Auto-addressing analogue fire
control panel
Two-loop addressable panel, expandable to 4 loops
Optional 4 or 12 conventional lines (e.g. for retrofit, modernisation)
Commissioning in record time by auto-addressing localisation
Auto-addressing eliminates the setting of dip switches, punch cards, etc.
Automatic localization of interruptions and short circuits
Unshielded cables prevent irksome ground-returns
Periodic self-test facility
Serial interface for third-party building management systems, repeaters,
printer, etc.
Additional cards may be retrofitted at anytime for customized solutions
Maintenance can be matched to customer needs
Fire & Security Products
Siemens Building Technologies
Product features
Synova FC330A has all the requirements for intelligent systems. Addressing is automatic and address allocation takes only seconds. To improve security and increase
speed, distributed intelligence enables detectors to verify danger signals independently.
512 addressable and 384 conventional fire detectors, regardless of type, may be connected to the Synova FC330A fire control panel.
Commissioning, which comprises auto-addressing of all connected elements, is executed by the intelligent SynoLOOP transmission protocol. Time-consuming preparatory
work such as setting dip switches, punch cards, etc., is no longer necessary, providing
reliable on-time commissioning.
Siemens equips all auto-addressable elements with isolators. No separate isolator has
to be planned nor installed. If a short circuit occurs, the panel localises and isolates the
defective cable section. The loop system permits data flow in both directions up to the
error source with optimum safety, until the short-circuit is fixed. This kind of automatic
isolation facilitates fire section planning, as well as adaptation to changing needs.
Expansion with various additional cards permits almost unlimited customised solutions.
The three main fire control panel models
FC330A-1
The FC330A-1 standard
fire control panel features
the SynoLOOP K3X020
master board, an LCD unit,
and the operator keypad.
FC330A-2
The FC330A-2 model consists of the standard control
panel, expandable with
parallel indicator panel
(B3R080)
FC330A-4
The FC330A-4 control
panel can accommodate
A4 and even A3 documents. The panel door
accessible with a key, protects against unauthorized
access. A second inner
door provides easy access
for installation and maintenance access.
2
Siemens Building Technologies
Fire & Security Products
System overview
SynoLINE600
OP
DLO
DF
DM
DBZ
collective
HI
SynoLINE600-Ex
DF-Ex
DT-Ex
DO-Ex
Alarm devices
collective
DJ-Ex
SB
DC
OP
HI
DM-Ex
Alarm reception
centre
(Fire brigade)
SynoLINE300
MT
OH
OP
collective
HI
Fire control
installations (FCI)
DBZ
AI
OH
HI
DM
DF
OP
FBF
FSD
ÜE
up to 4 SynoLOOP max. 512 devices
ABI
EB
AB
CB
Ventilation,
Air cond.
system,
Elevator
DC
VdS periphery:
- Fire brigade control
panel
- Fire brigade key
cabinet
- Remote
transmission unit
addressable
DC
DC
OH
DLO
HI
HI
OP
OP
SynoLINE300
SynoLINE600
DC
SB
DO-Ex
Two RS232
serial interfaces
DT-Ex
DF-Ex
SynoLINE600-Ex
Building management system
Printer
LON-Bus via LON interface
Control
in/output
modules
LON/Synoptic
converter
Databus
Floor repeater panels
Parallel indicators or
Synoptic / relay
Configuration tool SWE330A
Training
3
Siemens Building Technologies
Fire & Security Products
FC330A (two-loop) and its expansions
[4] K3M030
2-loop addressable
expansion card
[5] K3M010
4 conventional lines
expansion card
[12] Z3B171
Relay module
or
[6] K3M020
12 conventional lines
expansion card
[1] FC330A
Control panel
Position A
(up to 2 cards)
[13] Z3I1000
Power supply
Position C
(up to 16
Z3B171)
TS32/35
C/U-rail
[2] Z3S030
Z3S020
[3] K3X020
Master board
Two RS232 ports
Position B
(up to 2 cards)
[11] Z3I830
Mounting plate
[10] K3L100
LED driver card
[9] K3I080
RS232/LON-Bus converter
[7] K3G050
Relay card
or
[8] K3L070
VdS interface card
4
Siemens Building Technologies
Fire & Security Products
FC330A (two-loop) and its expansions (continued)
[1] Fire control panel FC330A
The FC330A fire control panel accommodates
– Smoke, heat and multi-sensor detectors and manual call points from different series
– Special detectors (flame detectors,
Ex-detectors, highly sensitive detectors) for special applications
– Input and output modules
– Conventional line modules and siren
outputs
Fire control panel FC330A is equipped
with state-of-the-art software, virtually
unlimited range of applications may be
programmed easily. It provides
– Intuitive, menu-driven operation
– Definable detector groups or fire
zones
– Dual-detector independence
– Chronological storage and retrieval of
up to 200 events
– Windows-based software tool for
parameter programming, etc.
FC330A-2
[2] Access with key Z3S030/Z3S020
The system operator may access the
fire detection system in three ways: by
passwords, without any password, or
with access keys. Two kinds of key
switches are available:
– Module Z3S030 is integrated in an
existing like-keyed concept
– Module Z3S020 follows the Nordic
fire brigade concept
[3] SynoLOOP master board K3X020
The master board is the basic control
panel module and is part of its basic
equipment. Switched on, the master
board recognises all connected elements and is ready to transmit fire
alarms.
Two auto-addressing SynoLOOP ring
cablings (with 128 detectors each) or
two stub lines (with 32 addressable
detectors each) may be connected to
the master board. The master board
has in addition the built-in:
– 8 Programmable control outputs
– 2 Monitored output (Sirens)
– 2 Control line relays
– Alarm and fault relays (to long distance transmission devices)
Two RS232 interfaces accommodate
various applications:
– System programming
– Printer connection for event protocol
printouts
– LON-bus connection
– Incorporation in a building management system (BMS)
– Connection of the visualiser training
tool, to operate the FC330A via your
PC
[4] Addressable 2-loop expansion
card K3M030
The K3M030 allows to expand the
FC330A by 2 addressable loops with up
to 256 detectors, or 2 stub lines with up
to 32 detectors per stub.
Conventional line expansion cards
Existing, conventional detectors may be
integrated in the new, auto-addressing
system by means of a conventional line
expansion card. The K3M020 card has
two line specifications for each conventional line which allows the use of various conventional detectors. The conventional line expansion card also
makes special applications, such as
connection of beam detectors, possible.
[5] Collective line expansion card
K3M010
The K3M010 allows expansion of the
control panel by:
– 4 conventional lines
– 4 programmable driver outputs
– 2 monitored outputs (Sirens)
– 2 relay switch contacts
[6] Conventional line expansion card
K3M020
The K3M020 allows expansion of the
control panel by up to:
– 12 conventional lines
– 8 programmable driver outputs
[7] Relay card K3G050
Relay card K3G050 triggers fire controls
such as activation of fire doors or air
vents. It offers additionally the following
outputs:
– 8 relay switch contacts (30VDC / 2A)
– 4 programmable outputs (24VDC /
48mA)
– 2 monitored outputs (Sirens) (24VDC
/ 500mA)
A plug is available for the relay card or
the VdS Interface card.
[8] VdS Interface Card K3L070
This card is only needed, when VdS
peripherals are specified.
The card contains the fire service key
box adapter. It also permits the connection to a fire brigade operating panel or
a transmission device. A standard
extinguishing interface is provided. One
plug is provided for the VdS card or the
relay card (K3G050).
5
Siemens Building Technologies
Fire & Security Products
FC330A (two-loop) and its expansions (continued)
[9] LON-bus converter card K3I080
The K3I080 LON-bus converter card is
used to connect to the control panel
with various LON-bus applications:
– Floor repeater panels
– Floor or situational plans
– LED parallel indications
– Various input and output signal possibilities
Converter cards on the LON-bus make
numerous user-oriented solutions possible. For instance, up to 16 floor repeater panels may be connected to the
LON bus and up to 256 addresses can
be managed for max. 9216 LED displays.
The LON-bus converter card is built
directly into the control panel and connected to one of the two RS232 serial
outputs. For more information consult
the datasheet 007349.
[10] LED driver card K3L100
The K3L100 LED driver card can connect 32 external LEDs. They may be up
to 400m away from the control panel.
e.g. for floor plans with allocation to one
or more fire zones, etc.
The LED driver card helps to indicate all
manner of events – 32 LED outputs
(5VDC / 15mA). The configuration tool
SWE330A makes programming even
more convenient.
[12] Relay module Z3B171
The relay module (250VAC / 10A) is an
additional fire event control module,
activated by the control panel’s control
outputs. Up to 16 relay modules may be
connected to the control panel FC330A
[13] Optional power supply Z3I1000
The additional power supply Z3I1000
consists of a power supply – monitoring
card M3P140 and the power supply
B2F040.
This set is needed if the current calculation exceed the power supply output of
the main board. Power supply output of
the Z3I1000 max. 3.5A / 29.6VDC.
Further options for the front of the
fire control panel
Optional components support simple
event visualisation on the fire control
panel.
[12] B3R080
FC330A-2
[11] Mounting plate Z3I830
Mounting plate Z3I830 allows integration of electronic accessories when no
other expansion cards have been installed.
Other control panel-interior options
Various modules, for instance up to
sixteen Z3B171 relay modules, may be
installed quickly and easily on U or C
rails.
FC330A-2
[13] Programmable key
Parallel indicator panel B3R080 with
32 alarm displays for panel module
FC330A-2
The parallel indicator module visualizes
important events, it contains 32 LED
displays. One or more fire zones can be
allocated to each of these 32 LEDs. The
B3R080 may be used without the driver
card K3L100. If external LEDs (using
LED driver card K3L100), and internal
LEDs (parallel indicator panel B3R080)
are used at the same time, display
activation is synchronous. The parallel
indicator panel, built into the front of the
control panel is connected directly to
master board K3X020. This is used
together with control panel type
FC330A-2.
Programmable key
A key on the key pad may serve as
additional input. The key may be programmed for various functions (e.g.
lamp test). It can be easely connected
via the F02F290 to the master board
K3X020.
6
Siemens Building Technologies
Fire & Security Products
Technical data
Type
K3X020
K3M010 K3M020 K3M030 K3L100 K3G050 K3L070 K3I080 Z3B171 B3R080
Current consumption
1) 2)
1) 2)
17mA
Normal operation
128mA
<25mA <72mA 2mA
20mA
12mA
10mA 0mA
2mA
3)
4)
4)
+9mA
+6mA5) +9mA3) +40mA 0mA7) +27mA +6mA6)
Alarm condition
+40mA +40mA 0mA
3)
+9mA
1)
Each loop without any devices consumes additional 14mA
0.2mA normal operation current consumption per addressable device connected
3)
Per activated contact/control line/buzzer, without external load (sounders, etc.)
4)
Per line in alarm
5)
Per activated driver output
6)
Per activated LED
7)
LON devices see document no. 007349
2)
Programmable output
Relay output
Transmission output
Monitored outputs (Sirens)
Programmable input
Programmable key input
Programmable fire zones
Programmable control zones
Cable specification
Mains
Power consumption
Battery
Standards
Colour
Approvals
8 x 24VDC / 40mA
2 x 30VDC / 1A
2 x 30VDC / 1A
2 x 24VDC / 500mA
4
1
512
128
150Ohm / 300nF
115 / 230VAC (+10% / -15%) 50 / 60Hz
< 100VA
2 x 12V / 15Ah (+2 x 12V / 15Ah)
EN54-2, IEC721-3-3 / 3K5
light grey (RAL 7035)
VdS (S 298015); LPCB; a.m.m.
Reference documents
Doc. no.1583
Synova FC330A
Doc. no. 1973
Doc. no. 1923
Synova FC330A
Synova FC330A
Doc. no. 007349
LON-Bus
Planning, Installation, Commissioning,
Operating Programming, Trouble Shooting,
Maintenance
Operating Manual, System Operation for User
Remote indicating & Control devices, Logging
Printer (Installation & Commissioning)
Data Sheet
7
Siemens Building Technologies
Fire & Security Products
Details for ordering
Type
FC330A-1
FC330A-2
FC330A-4
FCA105
B3R080
H23B030
523846
523862
Z3S020
Z3S030
Z3I830
Z3B171
F02F290
TS35
TS32
TKU2
484082
484095
513665
484383
513762
564478
564575
230508
K3M010
K3M020
K3M030
K3G050
K3I080
523817
498418
542160
512970
504768
523820
529015
559344
576000
K3L070
K3L100
Z3I1000
Z3I1020
Siemens Building Technologies AG
Alte Landstr. 411
CH-8708 Männedorf
Tel. +41 1 - 922 6111
Fax +41 1 - 922 6450
Part no
566557
566560
566586
576013
Designation
Fire control panel, 2 LOOP analogue
Fire control panel, 2 LOOP with mounting facility
Fire control panel 2 LOOP in special housing
Weight
11.940kg
11.940kg
22.300kg
Accessory set (EPROM, inscription stripes)
Options for FC330A-2
Parallel indicator panel (32 alarm indicators)
Cover plate
Accessories
Key switch module «Nordic access key»
Key switch module «like-keyed»
Mounting plate for accessories
Relay module with 1 contact 250VAC/10A
Connecting ribbon cable for optional key
U-rail TS35/7.5/122
C-rail TS32/108
Surveillance contact
Expansion
4 Conventional lines card
12 Conventional lines card
2 loop expansion card
Relay card
RS232/LON-bus Converter
VdS-interface card ‘D’
LED driver card for 32 external LED
Additional power supply
Battery extension set (For 2nd battery pack)
0.285kg
0.200kg
0.140kg
0.140kg
0.590kg
0.040kg
0.210kg
0.015kg
0.074kg
0.019kg
0.150kg
0.280kg
0.120kg
0.254kg
0.325kg
0.330kg
0.300kg
0.880kg
0.300kg
© 2003 Copyright by
Siemens Building Technologies AG
Data and design subject to change without notice. Supply subject to
availability.
www.sibt.com
Document no.
007408_b_en_--
Edition
12.2003
Manual FD-C
Section 8