460ETCMRS Modbus Master to Allen-Bradley PLC FEATURES

460ETCMRS Modbus Master to Allen-Bradley PLC FEATURES
Contact Us:
1-800-249-1612
460ETCMRS
Modbus Master to Allen-Bradley PLC
FEATURES
 Connects a Modbus
RTU Master to 1 - 5
Allen Bradley PLCs
 100 Read & 100 Write
Scan lines can be
transferred supporting
up to 512 Registers or
512 Coils per Scan line
 Map data from up to 750
user defined tags or
register blocks in your
PLC
 Map Modbus Data
directly to tags or
registers in your AllenBradley PLC
 Effortless Browser
Based Configuration, no
programming software is
required
 Simple data translation
allows you to manipulate
data as it passes
between protocols
Get Your Modbus RTU Master Connected Directly to the
Data Table of your Allen-Bradley PLC
The 460ETCMRS moves data between a Modbus RTU Master device and up to 5 different
Allen-Bradley PLC’s. It’s a simple tool to help you integrate legacy or low cost Modbus RTU
controllers into your Allen-Bradley Architecture.
Best of all the product is Made in the USA, is always in stock and comes with 5 year warranty.
How Does the Data Move In and Out of the PLC?
You allocate two areas of tags or register blocks in your Allen-Bradley PLC. One area is a
user defined set of write only tags or register blocks accepting data from your Modbus RTU
device. The other area is full of read only tags or register blocks to send data to your Modbus
RTU device. You directly map Modbus RTU register and coil data into read and write locations
in the data table of your Allen-Bradley PLC.
It’s really that simple. Need to modify your data as it passes from one protocol to the other?
No problem. Each data mapping you apply can be modified with up to 3 mathematic functions.
Add 4 to a value, multiply by 4 and divide by 10 with ease.
Why use Real Time Automation as a Gateway Supplier?
The 460ETCMRS provides an option to access Modbus RTU data without having to upgrade
your PLC or get an expensive in rack solution. While there are certainly a number of other
companies offering stand alone gateways, there is no one who provides the level of support
and service that you receive from RTA.
When you call, a live person answers the phone. When you talk with sales, you will get honest
answers and recommendations even if that means recommending someone else's solution.
When you get support, it is from an engineer who had a hand in the product’s development,
and support doesn't require a ticket or 24 hour wait. We are unashamed of the fact that we
are a smaller company because that means you mean a lot more to us.
Try the RTA difference today and give us a call at 1-800-249-1612 or check out more
information on us and our other solutions at www.rtaautomation.com.
A Word from our Founder
“It’s likely that your business isn’t industrial networking and it shouldn’t be. You make products, design systems, or manage some process. Whatever it
is that you make, monitor or install the process inevitably creates data. If you’re a control engineer and your plant has been around for a few years your
line is probably littered with devices that send out all kinds of data over many different protocols. If you’re an automation device developer you probably
have customers that need to move your data into some other network. Either way, you’ve got a device conversion problem. You have devices that generate ASCII , Modbus RTU, Modbus TCP, BACnet, Profinet, Profibus, Ethernet TCP/IP , Ethernet/IP, DeviceNet or some other completely proprietary
data and now you’re the person that has to move that data to some other network!
I feel your pain… and rather than just my sympathy, I have a solution for you. You see, while your business may not be moving data around a factory
floor mine is. In fact, it’s all that we have done for over twenty years now. Our 460 series of Device Converters is the culmination of those twenty years.
You can now move all of your data, where you want, when you want and how you want. Try us on your next project, I guarantee you wont regret it.
John Rinaldi
460ETCMRS
www.rtaautomation.com
MODBUS RTU FEATURES
Modbus Operation Modes
Modbus RTU Slave
Function Codes Supported
1,2,3,4,5,6,15 & 16
Swapping
Byte and Word Swapping
Maximum Modbus RTU Master Connections
1
Contiguous Data Areas
200 Total - 100 reads & 100 writes
Data Area Limits
512 Contiguous Coils or 512 Contiguous Registers
ETHERNET/IP TAG CLIENT FEATURES
PLC Support
ControlLogix, CompactLogix, FlexLogix, MicroLogix, SLC’s and PLC5E’s
Maximum Number of PLCs Supported
5
Maximum Number of Input Scan Lines per PLC
150
Maximum Number of Output Scan Lines per PLC
150
Net ENI Support
Supported
Supported Data Types
ControlLogix / CompactLogix / FlexLogix: Bit, 32 Bit Array, SINT, INT, REAL, STRING, DINT,
MicroLogix / SLC / PLC5E: 16 Bit Array, INT, REAL, STRING
INCLUDED WITH GATEWAY
120 volt AC wall wart power supply
Manual
6’ power cable with flying leads
5 year hardware warranty
IPSetup software — automatically locates RTA gateway on the network
Unlimited firmware feature upgrades for life
CAT5 crossover cable for direct connection to PC during programming
Complete, unlimited access to our industry leading support staff
ELECTRICAL/ENVIRONMENTAL
DC Input Voltage
8 VDC @ 230 mA to 28 VDC @ 80 mA
Maximum Baud Rate
115K baud
Operating Temperature
-40 C to 85 C
Certification
RoHS-Compliant, UL, CUL, CE Approvals, Class I Div 2
DIMENSIONS
ENCLOSURE / HARDWARE
Size
4.2” x 3.25” x 1”
Weight
5 oz.
Enclosure Type
Anodized aluminum
Mounting
Din rail or panel mount
LEDs
Ethernet link/data LED, Ethernet speed LED, power LED, &
2 general purpose LEDS on side
GATWAY FEATURES & FUNCTIONS
Gateway Security
You can configure up to 9 different users access to
diagnostic and configuration screens.
Alarming
Set <, <=, >=, >, ==, !=, and change-of-state rules on
any data moving through the gateway. If alarm rule is
triggered an email notification can be sent.
Translation Table
Allows for data manipulation during protocol translation. Scaling and other data format changes can occur
in the gateway.
Status and
Counters
Protocol specific status, counters and error messages
are accessible within the gateways diagnostics page.
They can also be delivered to a connected device.
Diagnostic Logging
Page
Allows users to see and log start up sequences, protocol specific messages & error messages.
NOT EXACTLY WHAT YOU WERE LOOKING FOR?
Real Time Automation offers a full line of gateway products. If this isn’t the one
you were looking for chances are we still have right solution for you. Give us a
call at 1-800-249-1612 or check out a listing at www.rtaautomation.com/products.
We also offer custom gateways to help customers dealing with unique needs or
proprietary protocols.
CATALOG #
DESCRIPTION
460ETCMRS
Modbus RTU Master to Allen-Bradley PLC Gateway
For More Information:
1-800-249-1612
[email protected]
.
www.rtaautomation.com
2014 Copyright Real Time Automation. All rights reserved. The Real Time Automation logo is a registered trademark of Real Time Automation Inc.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement