Delta Electronics | OPT-1250xxxx Series | Product Brochures

Index
Miniature Circuit Breaker
2
Miniature Circuit Breaker (80A - 125A)
18
MINI
24
Isolator
28
Changeover Switch
32
Residual Current Circuit Breaker (RCCB) 16A - 63A
36
Residual Current Circuit Breaker (RCCB) 80A - 125A
44
Residual Current Circuit Breaker with Overload and Short Circuit Protection (RCBO)
48
Distribution Board
54
2
Miniature Circuit Breaker
Electrical Distribution needs are continuously
evolving in residential, commercial and industrial
sectors. Improved operational safety, continuity
of service, greater convenience and operating
cost have assumed a tremendous significance.
Miniature Circuit Breakers have been designed to
continuously adapt to these changing needs.
Range
6A to 40A - ‘B’ Curve
0.5A to 63A - ‘C’ Curve
0.5A to 63A - ‘D’ Curve
0.5A to 63A for DC Application
Execution
Single Pole (1P)
Single Pole & Neutral (1P+N)
Double Pole (2P)
Three Pole (3P)
Three Pole & Neutral (3P+N)
Four Pole (4P)
Specification
IS 8828 / IEC 60898 / EN 60898
Features
s 0RECISEHAMMERACTION
s 0LATES!RC#HUTEFOREFFECTIVEARCQUENCHING
s ,ONGERELECTRICALLIFE
s 7IDERANGE
s 6ALUEFORMONEY
s ,OWPOWERCONSUMPTIONTHUSCOSTEFFECTIVE
Energy saving
Accessories - Auxiliary Switch
- Shunt Trip
3
MIN IA TU RE C IRC U IT B R EAKER
CONSTRUCTION
Miniature Circuit Breakers have precisely formed moulded case & cover of flame retardant high strength thermo-plastic material having high melting
point, low water absorption, high dielectric strength and temperature with stand.
The Switching Mechanism is independent, manual and trip free, i.e., the breaker trips internally even if the operating knob is held in ON position.
The Contact Mechanism comprises of fixed & moving contacts specially designed for reliability, long life and anti-weld properties.
The Arc Extinguishing Device comprises of 15 plates arc chute. The arc under the influence of the magnetic field and arc guide is moved into the
arc chute where it is rapidly split and quenched.
The tripping mechanism is Thermal Magnetic Type.
Thermal Operation
The thermal operation provides protection from moderate overloads. Under overload condition, a thermo-metallic element (bimetallic strip) deflects
until it operates a latching mechanism allowing the main contacts to open.
Magnetic Operation
In magnetic operation, large overloads or short circuit current actuates a solenoid causing a plunger to strike the latching mechanism rapidly opening
the main contacts.
INTERNAL VIEW
Outgoing Terminal
Bimetal Carrier
Bimetal Strip
Latch
Arc-chutes Holder
Arc-chutes
Solenoid
Knob / Dolly
Arc-runner
Moving Contact Arm
Plunger
Fixed Contact
Incoming Terminal
(Dual Termination)
4
MINIA T URE CIRCUI T B R E A KE R
TECHNICAL INFORMATION
Standard Conformity
IS 8828 / IEC 60898-1 / EN 60898-1
Type / Series
B
C
D
Rated Current (In)
A
6-40
0.5 - 63*
0.5 - 63*
Rated Voltage (Ue)
V~
240/415
240/415
240/415
Rated Frequency (f)
Hz
50
No. of Poles (Execution)
1P, 1P+N, 2P, 3P, 3P+N, 4P
Rated Short Circuit Breaking Capacity
kA
Magnetic Release Setting
10
10
0.5 - 32A - 10 kA
40A - 63A - 4.5kA
(3-5)In
(5-10)In
(10-20)In
Rated Insulation Voltage (Ui)
V
660
Rated Impulse Voltage (Uimp)
kV
4
Electrical / Mechanical Endurance (no. of operations)
<32A
20000
>32A
10000
Ambient Working Temperature
Terminal Capacity (max)
Vibration
(oC)
-5°C to 55°C
sq.mm
25
g
3
Shock
40mm free fall
Protection Class
IP-20
Installation Position
Vertical / Horizontal
Mounting
Clip on DIN Rail (35mm x 7.5mm)
Case & Cover
Moulded, flame-retardant thermoplastic material.
**
* Current Ratings -
0.5, 1, 2, 3, 4, 5, 6, 8, 10, 13, 16,
20, 25, 32, 40, 50, 63
1P
1P+N
2P
3P
3P+N
4P
Single Pole
Single Pole Neutral
Double Pole
Three Pole
Three Pole Neutral
Four Pole
5
MIN IA TU RE C IRC U IT B R EAKER
CHARACTERISTICS CURVES
Thermal Tripping
As per
IS:8828:96
B Curve
Magnetic Tripping
No tripping
Tripping
Time
Hold
Trip
Time
current
current
limits
current
current
limits
I1
I2
t
I4
I5
t
>1h
3xIN
1.13 x IN
1.45 x IN
C Curve
B Curve
C Curve
D Curve
1.13 x IN
>1h
1.45 x IN
D Curve
<1h
1.13 x IN
1.45 x IN
l3 = 2.55 x lN
5 x IN
5xIN
<1h
>1h
>0.1s
>0.1s
10 x IN
10xIN
<1h
<0.1s
<0.1s
>0.1s
20 x IN
<0.1s
1 s < t < 60s for lN < 32A
1 s < t < 120s for lN > 32A
TRIPPING CHARACTERISTICS
Based on the Tripping Characteristics, MCBs are available in ‘B’, ‘C’ and ‘D’ curve to suit different types of applications.
‘B’ Curve: for protection of electrical circuits with equipment that does not cause surge current (lighting and distribution circuits). Short circuit release is set to
(3 - 5) In
‘C’ Curve: for protection of electrical circuits with equipment that causes surge current (inductive loads and motor circuits).
Short circuit release is set to (5 - 10) In
‘D’ Curve: for protection of electrical circuits which causes high inrush current, typically 12-15 times the thermal rated current (transformers, X-ray machines
etc.) Short circuit release is set to (10 - 20) In
CURRENT LIMITING DESIGN
In a current limiting breaker, the tripping & arc control mechanism are so designed that
under short circuit conditions, the contacts are physically separated and the
electrodynamic forces set up by fault current, assist the extinction in less than half
cycle.
The figure shows the current limiting effect of circuit breakers.
Fault Traces for Voltage & Current
0
=
Point of fault initiation
tx
=
Contact opening time (i.e., creation of arc)
t1
=
Current / Voltage peak (i.e., current limitation)
t2
=
Time to total extinction of arc
(i.e., complete shutdown of fault current)
6
MINIA T URE CIRCUI T B R E A KE R
HAMMER TRIP MECHANISM
Current Limiting design in itself may not fulfill the requirement of quick breaking
(instantaneous action) mainly due to inertia of the Latch mechanism and
interconnected sequence of operations.
A Hammer directly connected to the plunger strikes the moving contact arm
with a force proportional to the peak current there by forcibly separating the
moving contact from the fixed contact much before the latch mechanism
operates. This further reduces the opening time of the circuit breaker.
Plunger
Hammer
AMBIENT TEMPERATURE COMPENSATION / DIVERSITY FACTOR CHART
K1
Maximum Permissible Rated Current
(K1 Factor)
K2
Graph 1
Diversity Factor
(K2 Factor)
Graph 2
Calculation
In / switch = K1 x K2 x In
Example
4 MCBs with In = 10A, and the amb. temp. is 50oC kept with no gap in between
Solution
K1 =0.89 (from graph 1)
K2 =0.78 (from graph 2)
In / pole = 0.89 x 0.78 x 10 = 6.94 A
EFFECT OF FREQUENCY VARIATION
MCBs are designed to operate at AC frequency 50 / 60 Hz. However, MCBs specially suitable for DC applications and for frequencies upto 400Hz can be
supplied on request.
These can be used on different frequencies in supply from 16 2/ 3 - 60 Hz without any deration.
For higher frequencies, normal MCBs can be used with a multiplication factor which shall only affect its magnetic trip current.
Supply
Frequency
Multiplication Factor
100Hz
1.1
AC
200Hz
1.2
DC
400Hz
1.5
1.5
7
MIN IA TU RE C IRC U IT B R EAKER
L E T T H R O U G H E N E R G Y I 2T
MAXIMUM BACKUP PROTECTION
At site, no. of MCBs are used for outgoing connection. To protect the MCBs under
short circuit (higher capacity), we need to put fuses in the incoming side. The
current rating of fuses should not be more than the values given in the table.
COLD RESISTANCE
& POWER LOSS DETAILS
MCB
Current Rating
Backup
Fuse Rating
1
25
2
35
4
50
6
80
10-63
100
The power loss value declared are at rated current.
Rated Current
Cold Resistance
Power Loss per Pole
IN (A)
RI (m)
Pv (W)
1
1178.00
1.3
2
281.00
1.5
4
92.00
2.2
6
16.55
0.7
10
11.68
1.4
13
10.10
1.7
16
8.00
2.2
20
5.25
2.5
25
3.78
3.1
32
2.57
3.4
40
1.94
3.9
63
1.40
7.3
Remarks:- Tolerance ±5%
8
MINIA T URE CIRCUI T B R E A KE R
DC APPLICATION
MCBs for DC application are specially designed to meet tough arc quenching
conditions. While selecting circuit breaker for DC applications following parameters
have to be taken into consideration.
Normal Circuit Currents
The rating and normal running temperature of the MCB are unaffected by DC. The MCB
can be selected using the thermal section of the standard time / current curves .
Magnetic tripping on DC is different from the equivalent AC by a peak factor of 1.4
ie., for ‘B’ curve AC MCB, magnetic range
= (3-5) ln
for DC MCB, magnetic range
= 1.4(3-5)ln = (4-7)ln
for ‘C’ curve AC MCB, magnetic range
= (5-10)ln
for DC MCB, magnetic range
= 1.4(5-10)ln =(7-14)ln
Short Circuit Currents
The maximum short circuit current possible on a DC system is determined
by the voltage of the battery and the total internal resistance of the cells.
It is given by Ohm’s law :
Isc =
Vb
Rb
Where, Isc is the Short Circuit Current
Vb is the voltage of the battery (with 100% charged battery)
Rb is the internal resistance of the battery cells
(this is usually stated by the manufacturer)
Circuit Time Constant
L
The time constant is given by : R
where L is the inductance of the circuit
R is the resistance of the circuit
The time constant is usually given in milliseconds (ms.). Ideally, DC circuits would be mainly resistive (i.e. a low number), as inductive circuits produce a back
emf when the current suddenly falls. This in turn tends to prolong arcing during switching operations, and so reduce contact life.
Circuit Voltage
The voltage of the circuit is dependent upon the power supply. The lower the voltage the easier switching operations will be, but the voltage makes no difference
to the running of the MCBs.
Contact life can be significantly increased by reducing the voltage, drop accross each pole. This can be achieved by wiring poles in series.
MCBs have been successfully tested on DC and can be used under the following conditions :
L/R
15ms max
Voltage
12-130V
Short Circuit Breaking Capacity
1 kA
Magnetic Release Setting
4-7 ln
9
MIN IA TU RE C IRC U IT B R EAKER
ACCESSORIES
AUXILIARY CONTACT
Attachment used for Signalling, Indication, Annunciation and Interlocking.
Standard Conformity
:
IS 13947-1, IEC 60947-1
Rated Current (In)
A
:
6
Rated Voltage (Ue)
V ac
:
240
Contact Configuration
:
1 NO + 1 NC / 2 NO + 2 NC
Utilization Category
:
AC 11
Electrical Endurance (No. of operations)
:
10000
:
10
Terminal Capacity (Max)
mm2
Protection Class
:
IP - 20 as per IEC-60529 / IS-2147
Mounting
:
Left side of MCB
(Factory assembled)
SHUNT TRIP
Attachment used for remote tripping.
Standard Conformity
Coil Consumption
Rated Voltage (ac) (Ue)
(dc) (Ue)
Frequency
Operating Voltage Range
Electrical Endurance (No. of ops)
Terminal Capacity (Max)
Protection Class
VA
V
V
Hz
mm2
Mounting
Shunt Trip Connection Diagram
D1
Outgoing
:
:
:
:
:
:
:
:
:
:
IS 13947-3, IEC 60947-3
6
240
48, 24, 12
50
70% - 110% of rated voltage
10000
25
IP-20 as per IS-2147
& IEC 60529 / IS-2147
Right side of MCB
(Factory assembled)
Shunt Trip Coil
1.
To trip the Circuit Breaker through Shunt Trip Coil, 70% to 110% of the rated voltage is
to be applied across D1 & D2
2.
Incoming
D2 Coil Terminal
Incoming Connection
10
The Shunt Trip coil is short time rated and it trips the breaker instantaneously.
(i.e., continuous duty not required)
S.T.
240V
MINIA T URE CIRCUI T B R E A KE R
DISCRIMINATION DATA
MCB
Downstream
C curve
MCB Upstream C Curves
10A
13A
16A
20A
25A
32A
40A
50A
63A
0.5 to 5A
50
65
80
100
125
160
200
250
315
65
80
100
125
160
200
250
315
100
125
160
200
250
315
125
160
200
250
315
160
200
250
315
6A
10A
13A
16A
20A
200
25A
250
315
250
315
32A
315
40A
50A
MCB
Downstream
B curve
MCB Upstream B Curves
10A
13A
16A
20A
25A
32A
40A
50A
63A
0.5 to 5A
6A
30
39
48
60
75
96
120
150
189
6A
30
39
10A
48
60
75
96
120
150
189
48
60
75
96
120
150
189
60
75
96
120
150
189
75
96
120
150
189
96
120
150
189
120
150
189
13A
16A
20A
25A
32A
189
40A
50A
MCB
Downstream
C curve 16A
MCCBs
Upstream
20A 25A 32A
0.5 to 6A 1100 1200 1400 1700
10A
-
1100 1200 1400
16A
-
-
-
1300
40A
50A
63A 80A 100A 125A 160A 200 250A 320A 400A 500A 630A 800A 1000A 1250A 1600A
2000 2500 3400 4800 5800 6700
T
T
T
T
T
T
T
T
T
T
1700 2100 2500 3000 3500 4300
T
T
T
T
T
T
T
T
T
T
T
1600 1900 2100 2400 2700 3200 8300
T
T
T
T
T
T
T
T
T
T
1600 1900 2100 2400 2700 2500 8300
T
20A
-
-
-
-
25A
-
-
-
-
-
32A
-
-
-
-
-
-
40A
-
-
-
-
-
-
-
50A
-
-
-
-
-
-
-
-
63A
-
-
-
-
-
-
-
-
1700 1800 2000 2200 2500 5400 8700
1800 2000 2200 2500 5400 8700
1500 1700 2000 4300 7000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1300 1500 3600 5900 9000
-
T
1100 2800 5200 8200
Prospective Fault Levels to which selectivity is achieved ( T = Total Selectivity )
Discrimination with Fuses
HRC Fuse Upstream Type Gg
MCBs
Downstream
20A
0.5 to 6A
700
10A
13A
16A
HRC Fuse Link Upstream
25A
32A
40A
50A
63A
80A
100A
125A
160A
850
960
1200
1350
1750
2800
4500
5200
6000
700
960
1200
1350
1750
2800
4500
5200
6000
850
1200
1200
1750
2800
4500
5200
6000
960
1100
1500
2500
3200
5200
6000
20A
1100
1500
2500
3200
4500
5200
25A
960
1350
2000
3200
4500
5200
1200
1750
2800
4500
5200
1750
2800
4500
5200
2500
3200
4500
3200
4500
32A
40A
50A
63A
11
MIN IA TU RE C IRC U IT B R EAKER
SELECTION CHART
Rating of MCBs for specified no. of fittings
(“B” Series MCBs)
For Household Applications
Appliances
Capacity /
watt (Load)
(240V~ 1ph)
Current Rating
of MCB
Type of MCB
Air Conditioner
1.0 tonnes
1.5 tonnes
2.0 tonnes
10A
16A
20A
“C” series
“C” series
“C” series
Refrigerator
165 litres
350 litres
3A
4A
“C” series
“C” series
Oven cum Griller
4500W
1750W
32A
10A
“B” series
“B” series
Oven only
Hot Plate only
Room Heater
750W
2000W
1000W
2000W
6A
10A
6A
10A
“B” series
“B” series
“B” series
“B” series
Washing Machine
Washing Machine
(with heater)
300W
2A
“C” series
1300W
8A
“C” series
1000W
2000W
3000W
6000W
6A
10A
16A
32A
“B” series
“B” series
“B” series
“B” series
750W
1250W
6A
8A
“B” series
“B” series
1200W
1500W
8A
10A
“B” series
“B” series
Water Heater
(storage/instant)
Electric iron
Auto Toaster
(2 slices)
Electric Kettle
Lamp
(Watt)
Number of Lamps
Rating (A)
20W
8
12
1
1.5
40W
2
10
12
0.5
2
2.5
60W
1
4
8
12
0.5
1.5
3
4
80W
1
2
5
8
12
0.5
1
2
4
5
100W
1
2
4
1
1.5
2.5
“B” series MCB is used for all Lighting Applications
Selection of MCB for Motor Protection
S. No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
kW
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
3.75
5.5
7.5
10
15
18.5
22
30
HP
0.24
0.34
0.50
0.74
1.01
1.47
2.01
2.95
4.02
5.03
7.37
10.05
13.40
20.11
24.80
29.49
40.21
1 Phase 230V DOL
Starting
Full Load
MCB
Current
Selection
C
2.8
10
3.2
10
3.5
10
4.8
16
6.2
20
8.7
25
11.8
32
17.5
50
20.0
63
24.0
80
26.0
80
47.0
125
—
—
—
—
—
—
—
—
—
—
3 Phase 400V DOL
Starting
Full Load
MCB
Current
Selection
C
0.9
2
1.2
2
1.2
2
1.8
3
2.0
3
2.6
6
3.5
10
4.4
10
6.3
16
8.2
20
11.2
25
14.4
40
21.0
50
27.0
100
32.0
125
38.0
125
51.0
125
3 Phase 400V Assisted Starting Star Delta
Full Load
Current
—
—
—
—
—
—
—
—
6.3
8.2
11.2
14.4
21.0
27.0
32.0
38.0
51.0
C
—
—
—
—
—
—
—
—
16
20
32
40
50
63
—
—
—
Calculation Formulae :
Incomer Current Rating, For Single Phase :
Total Load in Watts
240V
Incomer Current Rating, For Three Phase :
Total Load in Watts
—3X240V
12
“C” series MCB is used for all Motor Applications
Note :
One lighting circuit can have upto 800W or upto 10 lighting points
One power circuit can have upto 2000W or 1 power points
MCB Selection
D
—
—
—
—
—
—
—
—
10
10
16
25
32
40
50
63
63
MINIA T URE CIRCUI T B R E A KE R
SINGLE POLE (1P)
Current
Rating (A)
‘B’ Curve
Cat No.
‘C’ Curve
Cat No.
‘D’ Curve
Cat No.
0.5
DHMCCSPF0x5
DHMCDSPF0x5
DHMCESPF0x50013
1
DHMCCSPF001
DHMCDSPF001
DHMCESPF0010013
2
DHMCCSPF002
DHMCDSPF002
DHMCESPF0020013
3
DHMCCSPF003
DHMCDSPF003
DHMCESPF0030013
4
DHMCCSPF004
DHMCDSPF004
DHMCESPF0040013
5
DHMCCSPF005
DHMCDSPF005
DHMCESPF0050013
6
DHMCBSPF006 DHMCCSPF006
DHMCDSPF006
DHMCESPF0060013
10
DHMCBSPF010 DHMCCSPF010
DHMCDSPF010
DHMCESPF0100013
16
DHMCBSPF016 DHMCCSPF016
DHMCDSPF016
DHMCESPF0160013
20
DHMCBSPF020 DHMCCSPF020
DHMCDSPF020
DHMCESPF0200013
32
DHMCBSPF032 DHMCCSPF032
DHMCDSPF032
DHMCESPF0320013
35
SINGLE POLE & NEUTRAL (1P+N)
DOUBLE POLE (2P)
‘DC’ MCB.*
Cat No.
DHMCESPF0350013
40
DHMCBSPF040 DHMCCSPF040
DHMCDSPF040
50
DHMCCSPF050
DHMCDSPF050
DHMCESPF0500013
63
DHMCCSPF063 DHMCDSPF063
DHMCESPF0630013
Current
Rating (A)
‘C’ Curve
Cat No.
0.5
DHMCCSNF0x5
1
DHMCCSNF001
2
DHMCCSNF002
3
DHMCCSNF003
4
DHMCCSNF004
5
DHMCCSNF005
6
DHMCCSNF006
10
DHMCCSNF010
16
DHMCCSNF016
20
DHMCCSNF020
32
DHMCCSNF032
40
DHMCCSNF040
50
DHMCCSNF050
63
DHMCCSNF063
Current
Rating (A)
DHMCESPF0400013
‘C’ Curve
Cat No.
‘D’ Curve
Cat No.
‘DC’ MCB.*
Cat No.
0.5
DHMCCDPF0x5
DHMCDDPF0x5
DHMCEDPF0x50013
1
DHMCCDPF001
DHMCDDPF001
DHMCRDPF0010013
2
DHMCCDPF002
DHMCDDPF002
DHMCRDPF0020013
3
DHMCCDPF003
DHMCDDPF003
DHMCRDPF0030013
4
DHMCCDPF004
DHMCDDPF004
DHMCRDPF0040013
5
DHMCCDPF005
DHMCDDPF005
DHMCRDPF0050013
6
DHMCCDPF006
DHMCDDPF006
DHMCRDPF0060013
10
DHMCCDPF010
DHMCDDPF010
DHMCRDPF0100013
16
DHMCCDPF016
DHMCDDPF016
DHMCRDPF0160013
20
DHMCCDPF020
DHMCDDPF020
DHMCRDPF0200013
32
DHMCCDPF032
DHMCDDPF032
35
DHMCRDPF0320013
DHMCRDPF0350013
40
DHMCCDPF040
DHMCDDPF040
DHMCRDPF0400013
50
DHMCCDPF050
DHMCDDPF050
DHMCRDPF0500013
63
DHMCCDPF063
DHMCDDPF063
DHMCRDPF0630013
*MCB suitable for DC application.
13
MIN IA TU RE C IRC U IT B R EAKER
THREE POLE (3P)
Current
Rating (A)
‘B’ Curve
Cat No.
‘C’ Curve
Cat No.
‘D’ Curve
Cat No.
‘DC’ MCB.*
Cat No.
0.5
DHMCCTPF0x5
DHMCDTPF0x5
DHMCDTPF0x5
1
DHMCCTPF001
DHMCDTPF001
DHMCDTPF001
2
DHMCCTPF002
DHMCDTPF002
DHMCDTPF002
3
DHMCCTPF003
DHMCDTPF003
DHMCDTPF003
4
DHMCCTPF004
DHMCDTPF004
DHMCDTPF004
5
DHMCCTPF005
DHMCDTPF005
DHMCDTPF005
6
DHMCCTPF006
DHMCDTPF006
DHMCDTPF006
10
DHMCCTPF010
DHMCDTPF010
DHMCDTPF010
16
DHMCCTPF016
DHMCDTPF016
DHMCDTPF016
20
DHMCCTPF020
DHMCDTPF020
DHMCDTPF020
32
DHMCCTPF032
DHMCDTPF032
DHMCDTPF032
40
DHMCCTPF040
DHMCDTPF040
DHMCDTPF040
50
DHMCCTPF050
DHMCDTPF050
DHMCDTPF050
63
DHMCCTPF063
DHMCDTPF063
DHMCDTPF063
‘C’ Curve
Cat No.
‘D’ Curve
Cat No.
35
THREE POLE - N (3P+N)
FOUR POLE (4P)
Current
Rating (A)
0.5
DHMCCTNF0x5
DHMCDFPF0x5
1
DHMCCTNF001
DHMCDFPF001
2
DHMCCTNF002
DHMCDFPF002
3
DHMCCTNF003
DHMCDFPF003
4
DHMCCTNF004
DHMCDFPF004
5
DHMCCTNF005
DHMCDFPF005
6
DHMCCTNF006
DHMCDFPF006
10
DHMCCTNF010
DHMCDFPF010
16
DHMCCTNF016
DHMCDFPF016
20
DHMCCTNF020
DHMCDFPF020
32
DHMCCTNF032
DHMCDFPF032
40
DHMCCTNF040
DHMCDFPF040
50
DHMCCTNF050
DHMCDFPF050
63
DHMCCTNF063
DHMCDFPF063
‘C’ Curve
Cat No.
‘D’ Curve
Cat No.
Current
Rating (A)
0.5
DHMCCFPF0x5
DHMCDFPF0x5
1
DHMCCFPF001
DHMCDFPF001
2
DHMCCFPF002
DHMCDFPF002
3
DHMCCFPF003
DHMCDFPF003
4
DHMCCFPF004
DHMCDFPF004
5
DHMCCFPF005
DHMCDFPF005
6
DHMCCFPF006
DHMCDFPF006
10
DHMCCFPF010
DHMCDFPF010
16
DHMCCFPF016
DHMCDFPF016
20
DHMCCFPF020
DHMCDFPF020
32
DHMCCFPF032
DHMCDFPF032
40
DHMCCFPF040
DHMCDFPF040
50
DHMCCFPF050
DHMCDFPF050
63
DHMCCTPF063
DHMCDTPF063
35
14
MINIA T URE CIRCUI T B R E A KE R
RAILWAY MCB
Current
Rating (A)
‘DC’ application
Cat. No.
0.5
DHMCRSPF0X50013
1
DHMCRSPF0010013
2
DHMCRSPF0020013
3
DHMCRSPF0030013
4
DHMCRSPF0040013
5
DHMCRSPF0050013
6
DHMCRSPF0060013
10
DHMCRSPF0100013
16
DHMCRSPF0160013
20
DHMCRSPF0200013
32
DHMCRSPF0320013
35
DHMCRSPF0350013
40
DHMCRSPF0400013
50
DHMCRSPF0500013
60
DHMCRSPF0600013
DIMENSIONS (in mm)
ACCESSORIES
SHUNT TRIP
AUXILIARY CONTACT
Description
Cat. No.
12 VDC
MCDST012
24 VDC
MCDST024
Contact Configuration
Current
Cat. No.
48 VDC
MCDST048
1NO + 1NC
6A
MCBAC116
240 VAC
MCDST240
2NO + 2NC
6A
MCBAC226
15
MIN IA TU RE C IRC U IT B R EAKER
INDICATOR LIGHTS
Havells Indicator Light is a new addition to the product range and can be used in both building and industrial installations. Indicator lights are designed for signaling
the incoming supply.
INDICATOR LIGHTS
INDICATOR LIGHTS - SPARES
Volts
Colour
Cat. No.
Colour
Lens Cat. No.
Neon Bulb Cat. No.
240 V
Red
DHMCYSPX000
Red
DCPTMMCX043
DCELDMCL001
240 V
Amber
DHMCXSPX000
Amber
DCPTMMCX051
DCELDMCL001
240 V
Blue
DHMCVSPX000
Blue
DCPTMMCX049
DCELDMCL001
240 V
Green
DHMCZSPX000
Green
DCPTMMCX050
DCELDMCL001
240 V
Clear
DHMCWSPX000
Clear
DCPTMMCX052
DCELDMCL001
APPLICATIONS
z
Distribution Box
z
Three Phase Tier DB
z
Kiosks
z
Load Line DB
z
Meter Boxes
z
Testing Panels
z
Switch Boards
z
MIMIC Panels
z
Control panels
FEATURES
z
Modular Design enables Indicator Lamp replacement with lens of different varieties
z
Very simple installation and easy to replace
z
Easy mounting on DIN rail 35.5 X 7.5 mm.
z
Long life & durable
z
Available in five different colours : Red, Amber, Blue, Green, Clear
16
MINIA T URE CIRCUI T B R E A KE R
TECHNICAL INFORMATION
Specification
IS 13947 (Part 5)
IEC 60947-5-1
Contacts
Light Indication
Other Data
Rated Operation Voltage
240 V ac
Rating Electrical Power
1.2 Watt
Frequency
50 Hz
Type of Lamp Socket
E - 10 Thread
Terminal Capacity
10 mm2
Colour
Light
Permanent
Source
Neon Lamp
Mounting on DIN Rail
35 mm x 7.5 mm
Degree of Protection
IP 20
Ambient Temperature
-5 to 55° C
EASY TO REPLACE SPARES
z
The whole module
z
Colour Cap
z
Old Lamp
DIMENSIONS (in mm)
17
18
Miniature Circuit Breaker
(80 - 125)
Electrical Distribution needs are continuously
evolving in residential, commercial and industrial
sectors. Improved operational safety, continuity
of service, greater convenience and operating
cost have assumed a tremendous significance.
Miniature Circuit Breakers have been designed to
continuously adopt to these changing needs.
Range
80A to 125A - ‘C’ Curve
Execution
Single Pole (1P)
Three Pole (3P)
Three Pole & Neutral (3P+N)
Specification
IS 8828-1996 / IEC 60898 - 2002
Features
s 5NIFORMK!BREAKINGCAPACITYFORTHEENTIRERANGE
s #ONTROLLEVERCOLOURUNAMBIGUOUSLYINDICATESTHE
rated current In of the device
In (A)
Colour
80
(Silver)
100
(Red)
125
(Yellow)
s 0OSITIONINDICATINGDEVICEOPTICALLYTHEOPERATING
status of the device Indicator colour device status
(Red)
ON
(Green) OFF
s 4ESTBUTTONFORVERIlCATIONOFTHETIPPINGMECHANISM
function
19
MIN IA TU RE C IRC U IT B R EAKER
(80- 125A MCB )
TECHNICAL INFORMATION
Standard Conformity
IS 8828 / IEC 60898-1
Type/Series
C
Rated Current (In)
A
80A - 125A*
Rated Voltage (ac) (Ue)
V
240/415
Rated Frequency (f)
Hz
50-60 Hz
Nos. of Poles (Execution)
Rated Short Circuit Breaking Capacity
1P, 3P, 3P+N**
kA
10
Magnetic Release Setting
Rated Insulation Voltage (Ui)
(5-10)In
kV
4
10000
10000
Ambient Working Temperature
(oC)
**-5°C to + 55°C
Terminal Capacity (Max)
mm2
50
Tightening Torque
Nm
3.5
g
3
Electrical Endurance (No. of operations)
Vibration
Shock
40mm fall
Protection Class
Installation Position
Mounting
Case & Cover
*
#
20
Current Ratings - 80A, 100A, 125A
‘D’ Curve MCBs are available on request
IP-20
Vertical / Horizontal
Clip on DIN Rail (35mm x 7.5mm)
Moulded, flame retardant thermoplastic material.
**
1P
Single Pole
3P
Three Pole
3P+N
Three Pole Neutral
MINIA T URE CIRCU I T B R E A K E R
(8 0-125A M CB)
SINGLE POLE (1P)
Current Rating (A)
‘C’ Curve Rating (A)
80
DHMCCSPF080
100
DHMCCSPF100
125
DHMCCSPF125
THREE POLE (3P)
Current Rating (A)
‘C’ Curve Rating (A)
80
DHMCCTPF080
100
DHMCCTPF100
125
DHMCCTPF125
THREE POLE NEUTRAL (3P+N)
Current Rating (A)
‘C’ Curve Rating (A)
80
DHMCCTNF080
100
DHMCCTNF100
125
DHMCCTNF125
21
MIN IA TU RE C IRC U IT B R EAKER
(80- 125A MCB )
TECHNICAL INFORMATION
AUXILIARY CONTACTS
Attachment used for Auxilliary
Circuits
Contact Sequence
Cat. No.
Standard Conformity
: IEC 62019
11 (1NO + 1NC)
MOBAC116
Contact Sequence
: 11, 21*
21 (2NO + 1NC)
MOBAC216
Rated Current (ln)
A
Rated Voltage
Vac : 240
Voltage Category
Impulse Voltage
: 6
: AC 11
kV
Electrical Endurance
: 4
: 10000 operations
Terminal Capacity
Rigid
mm2 : max 4
Flexible
mm2 : max 2.5
Protection Class
: IP-20 as per IS-2147 / IEC-60529
Mounting
t
: on Right side of MCB
* 11 = 1NO + 1NC
21 = 2NO + 1 NC
SHUNT TRIP
Attachment used for Remote Tripping
Voltage
Cat. No.
Standard conformity
: IS: 13947 - 1: 93
24 ac
M0AST024
Rated Current
: 80 - 125
48 ac
M0AST048
Rated Voltage
:
110 ac
M0AST110
ac
: 24, 48, 110, 230, 400
230 ac
M0AST230
dc
: 24, 48, 110, 220, 440
400 ac
M0AST400
: 50
24 dc
M0DST024
: 70% - 110% of rated voltage
48 dc
M0DST048
(ln) A
Frequency
Hz
Operating Voltage
Impulse Voltage
: 4
110 dc
M0DST110
Electrical endurance
kV
: 10000 operations
220 dc
M0DST220
Terminal Capacity
mm2
:
max 2.5 440 dc
M0DST440
UNDER VOLTAGE RELEASE
Protection Class
: IP-20 as per IS-2147 / IEC-60529
Mounting
: To be coupled on Left side of MCB
Attachment used for Tripping Circuit
Breaker at voltage drop between 75% and 45% Un.
Voltage
Cat. No.
Standard conformity
: IS 13947 - 1: 93
24 ac
M0AUV024
Rated Current (ln)
A
: 80 - 125
48 ac
M0AUV048
Rated Voltage
ac
: 24, 48, 110, 230, 400
110 ac
M0AUV110
Frequency
Hz
: 50
230 ac
M0AUV230
: 70% - 110% of rated voltage
400 ac
M0AUV400
Operating Voltage
Impulse Voltage
Electrical Endurance
Terminal Capacity
22
kV
: 4
: 10000 operations
mm2 : max 2.5
Protection Class
: IP-20 as per IS 2147 / IEC 60529
Mounting
: To be coupled on left side of MCB
MINIA T URE CIRCU I T B R E A K E R
(8 0-125A M CB)
ACCESSORIES INSTALLATION
AUXILIARY CONTACTS
SHUNT TRIP & UNDER VOLTAGE RELEASE
Installation (hereinafter only the block) to a circuit breaker or tumbler
Installation (hereinafter only the block) to a circuit breaker or tumbler switch
switch (hereinafter only the device)
(hereinafter only the device)
1. Switch on both the block and the device.
1.
Switch on both the block and the device.
2. Insert metallic shaft from the right onto the device in such a control
2.
Insert metallic shaft from the right onto the device in such a control lever and
lever and the plastic shaft into the block switching system hole.
3. Slide the block from the right onto the device in such a way that one
the plastic shaft into the block switching system hole.
3.
Slide the block from the right onto the device in such a way that one shaft
shaft interconnects control levers and the other interconnects the
interconnects control levers and the other interconnects the switching
switching systems.
systems.
4. Press the block to the device and click the side fixing latches of the
4.
5. Check correct function by switching.
Press the block to the device and click the side fixing latches of the block in
the device recess.
block in the device recess.
5.
Check correct function by switching.
TRIPPING CHARACTERISTICS
‘C’ Curve : for protection of electric circuits with equipment that causes surge current (inductive and motor circuits)
Short circuit release is set to 5 - 10 ln
23
24
Mini MCB
Havells Mini MCB is a single composite device,
which provides, protection against overload
and short circuit faults. It is designed with
unique mounting concept, for use in domestic
& commercial distribution systems, at the most
downstream circuit (switchboards / DESB),
ensuring even higher degree of protection for
discriminating applications.
In normal operation, this new Mini MCB is safe to
use & there is no threat to user and environment.
Range
6A, 10A, 16A, 20A, 25A, 32A
Execution
Single Pole (1P)
Specification
IS 8828-1996
Features
s 0ROTECTIONAGAINSTOVERLOADSHORTCIRCUITINSWITCH
board itself
s 3UITABLEFORBOTH$%3"ANDSWITCHBOARD
s 0OSITIVECONTACTINDICATION
s 3HORTCIRCUITBREAKINGCAPACITYK!
s 0ERFORMANCE3AFETY
s 2ELIABILITY#ONTINUITYOFSERVICE
25
M INI MCB
CONSTRUCTION
Havells Mini MCB is a single composite device, which provides, protection against overload and short circuit faults. It is designed with unique mounting
concept, for use in domestic & commercial distribution systems, at the most downstream circuit (switchboards / DESB), ensuring even higher degree
of protection for discriminating applications.
In normal use, this new Mini MCB is safe to use and without danger to user as well as to environment.
TECHNICAL SPECIFICATION
Specification Reference
:
IS : 8828 : 1996
Rated Current In
:
6A, 10A, 16A, 20A, 25A, 32A .
Rated Voltage Un
:
240 V ac
Tripping Curve
:
C
Rated Insulation voltage
:
500 V ac
Rated Frequency
:
50 Hz
No. of Poles
:
Single Pole
Rated Short Circuit Capacity Icn
:
3kA
Method of Mounting
:
Switch Board Type
Degree of Protection
:
IP 20
Line Terminals
:
6 mm²
Load Terminals
:
6 mm²
Dimensions L x W x D( in mm )
:
56.25 x 47 x 17.7
Net Weight (in Kg)
:
0.085 (approx)
Ambient Temperature
:
- 5°C to + 55°C
Terminals Capacity
MINI MCB
Current Rating (A)
26
Cat No. ‘C’ Curve
6A
DHMNCSPA006
10A
DHMNCSPA010
16A
DHMNCSPA016
20A
DHMNCSPA020
25A
DHMNCSPA025
32A
DHMNCSPA032
MINI M CB
TRIPPING CURVES
DIMENSIONS (in mm)
INSTALLATION INSTRUCTIONS
Seperate the front plate from
Mini MCB by pulling off
Screw mount Mini MCB front
plate on the Switchboard
Hold the Mini MCB in such a
position that knob shows
OFF position
Mini MCB is successfully installed
Connect the outgoing phase wire
on upper terminal & tight it
Connect the outgoing phase wire
on upper terminal & tight it
Push fit the Mini MCB on to the
front plate
27
28
Isolator
They are switch disconnectors with independent
manual operation, capable of making, carrying
and breaking currents under normal circuit
conditions, which may include operating
overload condition and also carry currents under
specified abnormal circuit conditions such as
those of short circuit for a specified time
Range
40A - 63A, 80A - 125A
Execution
Single Pole (1P)
Double Pole (2P)
Three Pole (3P)
Four Pole (4P)
Specification
IS 13947-3 / IEC 60947 - 3
Features
s ,OW7ATT,OSS
s ,ONGER%LECTRICAL,IFE
s 7IDE2ANGE
s 6ALUEFOR-ONEY
s ,OWPOWERCONSUMPTIONTHUSCOSTEFFECTIVE
energy saving
29
IS OLATOR S
TECHNICAL INFORMATION
Standard Conformity
IS 13947-3 & IEC 60947-3
Rated Current (In)
A
40A - 63A, 80 - 125A
Rated Voltage (ac) (Ue)
V
240/415
Rated Frequency (f)
Hz
50
Nos. of Poles (Execution)
1P, 2P, 3P, 4P
Utilization Category
Rated Insulation Voltage (Ui)
AC 22A
V
660
Rated Impulse Voltage (Uimp)
kV
4
Electrical / Mechanical Endurance
(No. of operations)
Nos
10000
Ambient Temperature
0
-5 to +55
Terminal Capacity (Max)
sq.mm
25
Vibration
g
5
C
Shock
40mm free fall
Protection Class
IP-20
Installation Position
Vertical / Horizontal
Mounting
Clip on DIN Rail (35mm x 7.5mm)
Case & Cover
Moulded, flame retardant thermoplastic material.
DIMENSIONS (in mm)
SINGLE POLE (1P)
Current Rating (A)
Cat. No.
40
DHMIOSPX040
63
DHMIOSPX063
DOUBLE POLE (2P)
Current Rating (A)
30
Cat. No.
40
DHMIODPX040
63
DHMIODPX063
80
DHMIOSPX080
100
DHMIOSPX100
125
DHMIOSPX125
ISO LA T ORS
THREE POLE (3P)
Current Rating (A)
Cat. No.
40
DHMIOTPX040
63
DHMIOTPX063
80
DHMIODPX080
100
DHMIODPX100
125
DHMIODPX125
FOUR POLE (4P)
Current Rating (A)
Cat. No.
40
DHMIOFPX040
63
DHMIOFPX063
80
DHMIOTPX080
100
DHMIOTPX100
125
DHMIOTPX125
ISOLATOR FOUR POLE (2 MODULE)
Current Rating (A)
A
72.7
Cat. No. Four Pole
One Module
Two Module
25
DHMIHDPX025
DHMIHFPX025
40
DHMIHDPX040
DHMIHFPX040
B
SP
Isolators
Cat. No. Double Pole
SPN
DP
TP
35.6
53.4
TPN
C
D
E
F
60.0
43.5
45.0
87.5
FP
71.2
31
32
Changeover Switch
MCB Changeover switch finds wide & varied
applications in industries as well as in domestic
sphere for use in low voltage distribution circuits,
wherever continuity of supply is necessary, for
switching to an alternate source of supply from
main supply and vice - versa.
They are switch disconnectors with independent
manual operation, capable of making, carrying
and breaking currents under normal circuit
conditions, which may include operating
overload condition and also carry currents under
specified abnormal circuit conditions such as
those of short circuit for a specified time.
Range
25A & 40A
Execution
Double Pole (2P)
Four Pole (4P)
Specification
IS 13947-3 / IEC 60947 - 3
Features
s #OMPACTCONSTRUCTION
s $OUBLEBREAKCONTACTS
s 3ILVER#ADMIUM/XIDECONTACTTIPS
s 3HROUDEDTERMINALS
s &RONTOPERATIONWITHTHREESTABLEPOSITIONS)/))
s #ENTREPOSITION/&&
s %ASYSNAPON$).2AILMOUNTING
s #ANBEMOUNTEDWITHOTHERPRODUCTSVIZ-#"
ELCB, Isolator in Distribution Board
33
MIN I C H A N GEO VER SW ITCH
CONSTRUCTION
The entire switching mechanism along with the fixed and moving contact assembly are housed in FR thermo plastic moulded case / cover, having high dielectric
strength, excellent mechanical & thermal properties.
The switching mechanism is double break type. The conacts tips are made of Silver Cadmium oxide for long electrical life, sustained current carrying capacity
and they ensure temperature rise is within specified limits.
TECHNICAL INFORMATION
Standard Conformity
:
IS 13947-3 / IEC 60947-3
No. of Poles (Execution)
:
2 Pole, 4 Pole
Rated Current (In)
A
:
25, 40
Rated Voltage (Ue)
V
:
240 ac / 415 ac
Rated Frequency
Hz
:
50
Rated Insulation Voltage
V
:
660
Dielectric Strength
kV
:
2.5
Rated Impulse Voltage
kV
:
4
:
AC 21A
:
-5 to +55
Mechanical Life
:
10000 operations
Electrical Life
:
10000 operations
Mounting
:
Clip on DIN Rail (35mm x 7.5) mm
Mounting Position
:
Vertical / Horizontal
Utilization Category
Ambient Temp.
0
C
Terminal Capacity
mm2
:
10
Weight
Double Pole
gms
:
134
Four Pole
gms
:
268
CONNECTION DIAGRAMS / TERMINAL MARKING
FOUR POLE
TWO POLE
1
5
1
I
2
II
4
6
“I” - Incoming terminals (main supply)
“II” - Incoming terminals (standby supply)
Outgoing terminals (to load)
*
34
Mid position of knob is ‘OFF’ position
5
9
13
I
8
II
2
4
6
8
-2&6
“I” - Incoming terminals (main supply)
-4&8
“II” - Incoming terminals (standby supply)
-1&5
Outgoing terminals (to load)
*
Mid position of knob is ‘OFF’ position
10
12
- 2 , 6, 10 & 14
- 4 , 8, 12 & 16
- 1, 5, 9 & 13
14
16
MINI C HA NGE OV E R S W I T C H
DOUBLE POLE
Rating Amp
Cat. No.
25
DHMIHDPX025
40
DHMIHDPX040
FOUR POLE
Rating Amp
Cat. No.
25
DHMIHFPX025
40
DHMIHFPX040
DIMENSIONS (in mm)
4 Pole
2 Pole
35
36
Residual Current Circuit Breaker
(RCCB) 16A - 63A
The flow of current through electrical facilities
always involves risks. Poorly insulated
equipment, faulty wires and incorrect use of an
electrical device cause currents to flow through
the wrong path (i.e. through the insulation) to the
earth. This current is called ‘Leakage Current’.
Earth leakage is an electrical hazard and is
responsible for electrical shocks and fire risk.
Earth leakage and its associated hazard can be
prevented by Residual Current Circuit Breaker
(RCCB), also popularly known as Earth Leakage
Circuit Breaker (ELCB).
Range
16A - 63A
Sensitivity
30mA, 100mA, 300mA, 500mA
Execution
Double Pole (2P)
Four Pole (4P)
Specification
IEC 61008-1/IS 12640 - 1:2000 / EN 61008-1
Features
s 3IMPLEAND2OBUSTOPERATINGMECHANISM
s 2OTARYHANDLEWITH/./&&INDICATION
s $UALTERMINATIONFOR"US"ARASWELLASCABLE
connection
s !DVANCENEUTRAL
s 4ESTBUTTONFORREGULARINSPECTION
s 0OSITIVECONTACTINDICATION
37
RES IDU A L C U RREN T C IRC U IT B R EAKER
PROTECTION
AGAINST ELECTROCUTION
The use of exposed, substandard, badly wired, wrongly connected or damaged equipment as well as frayed or badly repaired cables reduces the safety of an
installation and increases the risk of person receiving an electric shock.
Electrocution is a passage of current through human body, which is dangerous. The flow of current through human body effects vital functions.
1.
Breathing
2.
Heartbeat
A correctly chosen RCCB can detect small currents flowing to earth and reduces the risk of electrocution. Effect of electric current through human body has
been well researched and following chart summarizes the results:
Effect of electric current through human body has been well researched and following chart summarizes the results:
500 mA
Immediate cardiac arrest resulting in death
70-100 mA
Cardiac fibrillation; the heart begins to vibrate and no longer beats at a steady rate.
This situation is dangerous since it is irreversible
20-30 mA
Muscle contraction can cause respiratory paralysis
10 mA
Muscle contraction : the person remains “stuck” to the conductor
1-10 mA
Prickling sensations
However, electrocution should not be viewed in terms of “current” alone, but in terms of “contact voltage”. A person gets electrocuted by coming in contact with
an object that has a different potential from his/her own. The difference in potential causes the current to flow through the body.
The human body has known limits:
-
Under normal dry conditions, voltage limit = 50V
-
In damp surroundings, voltage limit = 25V
AGAINST INDIRECT CONTACT
Over current protection devices like MCB are unable to act promptly on small earth leakage currents. To comply with wiring regulations, the earth fault loop
impedance in Ohms, multiplied by the rated tripping current of the RCD in amperes must not exceed 50.
Example
For an RCD with a rated tripping current of 30mA, the maximum permissible earth fault loop impedance is calculated as follows: Zs (max) = 50 / In
= 50/0.03 = 1,666
Rated Tripping Current
Maximum permissible earth
of the RCD
fault loop impedance in
10mA
5,000
30mA
1,666
100mA
500
300mA
166
AGAINST FIRE
The majority of fires which occur as a result of faulty wiring are started by current flowing to earth. Fire can be started by fault current of less
than 1 amp.
The normal domestic overload protective device such as a fuse or MCB will not detect such a small current. A correctly chosen RCD will detect
this fault current and interrupt the supply, hence, reducing the risk of a fire starting.
38
RESIDUA L CURRE N T C I R C U I T B R E A KE R
TECHNICAL INFORMATION
TWO POLE
Standard Conformity
FOUR POLE
IS 12640-1: IEC 61008-1
IS 12640-1: IEC 61008-1
A
16, 25, 32, 40, 63
25, 40, 63
mA
30, 100, 300, 500
30, 100, 300, 500
Rated Voltage (Un)
Vac
240
415
Rated Insulation Voltage (Ui)
V
660
660
Rated Frequency
Hz
50
50
Short circuit Withstand Capacity
kA
6
6
Residual Making Breaking Capacity
A
500 A or 10 In wherever is greater
500 A or 10 In wherever is greater
Ambient Temperature
o
-25°C to + 55°C
-25°C to + 55°C
40 mm free fall
40 mm free fall
3
3
10000
10000
Din Rail (35 x 7.5) mm
Din Rail (35 x 7.5) mm
IP 20
IP 20
25
25
Rated Current (In)
Sensitivity
(I n)
C
Shock Resistance
Vibration Resistance
g
Electrical /Mechanical operations
Mounting
Degree of Protection
Terminal Capacity (max)
mm
2
*500 mA is available on request
WORKING PRINCIPLE
The RCCB works on the current balance principle. The supply conductors, i.e. the phases
and the neutral, are passed through a torroid and form the primary windings of a current
transformer. Its secondary winding is connected to a highly sensitive electromagnetic trip relay,
which operates the trip mechanism.
In a healthy circuit, sum of the currents in phases, is equal to the current in the neutral and
the vector sum of all currents is equal to zero. If there is any insulation fault in the current and
leakage current flows to earth, the currents do not balance and their vector sum is not equal
to zero. This imbalance is detected by the core balanced current transformer, the RCCB is
tripped and supply to load is interrupted. The trip mechanism is operated at a residual current
between 50-100% of its rated tripping current.
39
RES IDU A L C U RREN T C IRC U IT B R EAKER
SELECTION
30 mA
A 30 mA ELCB will provide a high degree of protection against electrocution in an accidental shock hazard situation. The current flowing through human body
could be between 80mA and 240mA depending on the resistance of the human body and the voltage across it.
Zone
Physiological Effects
Zone 1
Usually no reactions
Zone 2
Usually no harmful physiological effects
Zone 3
Usually no organic damage to be expected. Likelihood of muscular
contraction and difficulty in breathing, reversible disturbances of formation
and conduction of impulse in the heart and transient cardiac arrest without
ventricular fibrillation increases with current magnitude and time.
Zone 4
In addition to the effects of Zone 3, probability if ventricular fabriliation
increased upto 5% (curve C2) upto 50% (curve C3) and above 50% beyond
curve C3. It increases with magnitude and time, and pathophysiological
effects such as cardiac arrest, breathing arrest and heavy burns may
occur.
To be within zone of the IEC curve as shown above. It is necessary for the ELCB to operate within 50ms at 240 mA and 150ms at 80mA. Both these conditions
are satisfied by 30mA ELCB.
For households, individual outlets, wet areas and temporary installations, ELCB with sensitivity not exceeding 30mA is advisable.
100 mA
A 100mA ELCB will normally give high degree of protection against electrocution but there is a possibility that the shock current could fall below the tripping level
of ELCB. This could occur if additional resistances to that of human body are included in the earth path.
The 100mA RCCB protects against leakage currents and indirect contact with earth loop impedance upto 500 Ohms.
300 / 500mA
A 300/500 mA ELCB may be used where only fire protection is required. eg., on lighting circuits, where the risk of electric shock is small. 300/500mA ELCB
will not give any protection against electrocution.
40
RESIDUA L CURRE N T C I R C U I T B R E A KE R
ACTUATION TIME CHARACTERISTICS
WIRING DIAGRAM
For Single Phase - 2 Wire
For Three Phase - 4 Wire
For Three Phase - 3 Wire
connections
connections
connections
Line
Line
Line
The Havells range of four pole RCCBs can be used to provide residual current protection in 3 phase, 3 wire circuits (no neutral), however a link from the neutral
to an incoming should be made on the supply side of the RCCB, to enable the operation of the RCCB.
41
RES IDU A L C U RREN T C IRC U IT B R EAKER
DOUBLE POLE ‘AC’ TYPE
FOUR POLE ‘AC’ TYPE
Current
Rating (A)
Sensitivity
mA
Cat No.
16
30
DHRMCTDE030016
16
100
DHRMCTDE100016
16
300
DHRMCTDE300016
25
30
DHRMCTDE030025
25
100
DHRMCTDE100025
25
300
DHRMCTDE300025
32
30
DHRMCTDE030032
32
100
DHRMCTDE100032
32
300
DHRMCTDE300032
40
30
DHRMCTDE030040
40
100
DHRMCTDE100040
40
300
DHRMCTDE300040
63
30
DHRMCTDE030063
63
100
DHRMCTDE100063
63
300
DHRMCTDE300063
Sensitivity
mA
Cat No.
25
30
DHRMCRFE030025
25
100
DHRMCRFE100025
25
300
DHRMCRFE300025
40
30
DHRMCRFE030040
40
100
DHRMCRFE100040
40
300
DHRMCRFE300040
63
30
DHRMCRFE030063
63
100
DHRMCRFE100063
63
300
DHRMCRFE300063
Current
Rating (A)
DIMENSIONS (in mm)
2 POLE
42
4 POLE
RESIDUA L CURRE N T C I R C U I T B R E A KE R
DOUBLE POLE ‘A’ TYPE
FOUR POLE ‘A’ TYPE
Current
Rating (A)
Sensitivity
mA
Cat No.
16
30
DHRMAMDF030016
16
100
DHRMAMDF100016
16
300
DHRMAMDF300016
25
30
DHRMAMDF030025
25
100
DHRMAMDF100025
25
300
DHRMAMDF300025
32
30
DHRMAMDF030032
32
100
DHRMAMDF100032
32
300
DHRMAMDF300032
40
30
DHRMAMDF030040
40
100
DHRMAMDF100040
40
300
DHRMAMDF300040
63
30
DHRMAMDF030063
63
100
DHRMAMDF100063
63
300
DHRMAMDF300063
Sensitivity
mA
Cat No.
16
30
DHRMAMFF030016
16
100
DHRMAMFF100016
16
300
DHRMAMFF300016
25
30
DHRMAMFF030025
25
100
DHRMAMFF100025
25
300
DHRMAMFF300025
32
30
DHRMAMFF030032
32
100
DHRMAMFF100032
32
300
DHRMAMFF300032
40
30
DHRMAMFF030040
40
100
DHRMAMFF100040
40
300
DHRMAMFF300040
63
30
DHRMAMFF030063
63
100
DHRMAMFF100063
63
300
DHRMAMFF300063
Current
Rating (A)
43
44
Residual Current Circuit Breaker
(RCCB) 80A - 125A
The flow of current through electrical facilities
always involves risks. Poorly insulated
equipment, faulty wires and incorrect use of an
electrical device cause currents to flow through
the wrong path (i.e. through the insulation) to the
earth. This current is called ‘Leakage Current’.
Earth leakage is an electrical hazard and is
responsible for electrical shocks and fire risk.
Earth leakage and its associated hazard can
be prevented by residual current circuit breaker
(RCCB), also popularly known as Earth Leakage
Circuit Breaker (ELCB).
Range
80A, 100A & 125A
Sensitivity
30mA, 100mA, 300mA, 500mA
Execution
Double Pole (2P)
Four Pole (4P)
Specification
IEC 12640-1 / IEC 61008-1 / EN 61008-1
Features
s 3HORTCIRCUITBREAKINGWITHSTANDCAPACITYK!
s $IFFERENTKNOBPOSITIONTOINDICATEWHETHERITIS
switched by a fault or manually switched OFF (mid
trip)
s 4ESTBUTTONFORREGULARINSPECTION
s #ONTACTPOSITIONINDICATION
45
RES IDU A L C U RREN T C IRC U IT B R EAKER
(80A - 125A R CCB )
TECHNICAL SPECIFICATION
DOUBLE POLE
Specification Reference
FOUR POLE
IEC 61008-1 & IS 12640-1: 2000
IEC 61008-1 & IS 12640-1: 2000
Rated current (In)
A
80, 100, 125
80, 100 , 125
Sensitivity
mA
30, 100, 300
30, 100 ,300, 500*
(I'n)
Rated Voltage (Ue)
V
240 V~
415V~
Rated Insulation voltage (Ui)
V
660
660
Rated Frequency
Hz
50
50
Trip Time
IxI'n<300ms, 5I'n<40ms
Short circuit withstand Capacity
kA
10
10
Residual Making Breaking capacity
A
10 In
10 In
Ambient Working Temperature
o
-25°C to + 55°C
-25°C to + 55°C
40mm free fall
40mm free fall
C
Shock Resistance
Vibration Resistance
g
5
5
Electrical Endurance
operations
>2000
>2000
Mechanical Endurance
operations
>3000
>3000
Din Rail (35 x7.5 mm)
Din Rail (35 x7.5 mm)
IP 20
IP 20
50
50
Mounting
Degree of protection
Terminals Capacity (Max)
*500mA on request
46
mm2
RESID UA L CURRE N T C I R C U I T B R E A K E R
(80A - 125A RCCB)
DOUBLE POLE
Current
FOUR POLE
Sensitivity
Cat No.
Rating (A)
mA
80
30
DHRMCMDF030080
80
100
DHRMCMDF100080
80
300
DHRMCMDF300080
100
30
DHRMCMDF030100
100
100
DHRMCMDF100100
100
300
DHRMCMDF300100
125
30
DHRMCMDF030125
125
100
DHRMCMDF100125
125
300
DHRMCMDF300125
Sensitivity
Cat No.
Current
Rating (A)
mA
80
30
DHRMCMF F030080
80
100
DHRMCMFF100080
80
300
DHRMCMFF300080
100
30
DHRMCMFF030100
100
100
DHRMCMFF100100
100
300
DHRMCMFF300100
125
30
DHRMCMFF030125
125
100
DHRMCMFF100125
125
300
DHRMCMFF300125
DIMENSIONS (in mm)
2 POLE
4 POLE
47
48
Residual Current Circuit Breaker
with Overload and Short Circuit
Protection
Havells New RCBO is a single composite device
which provides protection against over currents
and earth leakage faults in the same width and
profile as that of a standard MCB. It is designed
for use in domestic, commercial and industrial
distribution systems at the most downstream
circuit for ensuring high degree of protection to
the user for a particular circuit. In normal use, it
is safe to use and free of to user as well as to
environment.
Range
6A, 10A, 16A, 20A, 25A, 32A & 40A
Sensitivity
30mA, 100mA, 300mA
Execution
Single Pole with neutral (SPN)
Triple Pole with neutral (TPN)
Specification
IS:12640 Part2, IEC 61009-1, BSEN:61009-1
Features
s 0ULSATINGDCPROTECTION4YPE!
s $ISCRIMINATIONUSINGTIMEDELAY4YPE32#"/
s #ONTROLLEDRESPONSE6$2#"/%LECTRONIC
s 0ROTECTIONINCASEOFLOSSOFSUPPLYNEUTRAL
s %NHANCEDIMMUNITYTONUISANCETRIPPING
49
RES IDU A L C U RREN T C IRC U IT B R EAKER
WITH O VER LO A D & S H O RT C IRC U IT P ROTECTION
CONSTRUCTION
Havells new RCBO is a single composite device which provides protection against over currents and earth leakage faults in the same width and profile as that
of a standard MCB. It is designed for use in domestic, commercial and industrial distribution systems at the most downstream circuit for ensuring high degree
of protection to the user for a particular circuit. In normal use, it is safe to use and poses no threat to user as well as to environment.
FEATURES
z
Positive contact indication: Red for ON , Green for OFF
z
Short circuit breaking capacity 10 kA.
z
Large terminal capacity: RCBOs have 35 mm2 for cool running while in operation.
z
Protection in case of loss of supply neutral: Even in event of loss of supply neutral, Havells RCBO provides protection against earth faults . The Functional
Earth (FE) white color wire connected to earth provides this protection.
z
Controlled response & immunity to nuisance tripping: The trip level and the response time of the Havells VD (Voltage Dependent) RCBO using electronic
circuit is set to very precise values and thereby provide greater immunity to nuisance tripping that can be caused by mains borne noise, surge voltages,
lighting surges, reactive loads, mains filters, etc.
z
Neutral to earth faults: A connection that occurs between N and E on the load side of any RCBO will impact on its performance and cause the trip level
to increase. In the case of a N - E fault, the user may have no way of knowing that this fault exists and that the RCBO has been desensitised. Under this
condition, the Havells VD RCBO provides a far greater level of protection than a normal VI (Voltage Independent) RCBO.
Aesthetics & Convenience
z
The new module’s unique compact construction enables far more devices to be fitted into a distribution board than previously possible, and 2 Module
RCBO can simply replace existing MCB 2 pole when upgrading a board.
z
High stacking density = smaller chasis & distribution boards.
Reliability & continuity of service
z
Enhanced discrimination with Havells MCBs
z
Back up to 10 kA with BS & DIN fuses
z
Retrofits Havells MCBs in distribution boards with no modifications in general
z
Robust construction.
Energy limiting
Havells RCBO meets the requirements for energy let through by IEC & British Standard for energy limiting class 3.
ADDITIONAL RANGE - TYPE A & S
Type A - Pulsating DC Protection: Any electrical appliance with power control has the ability to produce earth fault currents with pulsating DC (rectified AC)
components. RCBOs that provide this type of protection are referred to as Type A RCBOs.
Standard VI RCBOs do not provide this protection, and are referred to as Type AC RCBOs. Havells VD RCBOs have been specifically designed to provide
protection against pulsating DC fault currents.
z
Type S- Selective or Time Delay: RCBOs are also divided into two categories determined by their response time to an earth fault current, as follows
z
General Type - having a trip time<300mS for fault currents of IDn and < 40ms for fault currents > 5IDn.
z
S Type- having a trip time of 150 - 500mS for IDn, and 40 - 130mS for >5IDn.
(IDn is the rated residual operating current of the RCBO)
As the name implies, general types are intended for general purpose use. However, S (selective) types are normally used in conjunction with downstream general
type RCBOs.
The S type effectively provides discrimination in terms of the response time to earth fault currents for upstream ad downstream RCBOs. For example, when two
RCBOs are connected in series the first RCBO will often be an S type.
50
RESIDUA L CURRE N T C I R C U I T B R E A KE R
WIT H OV E R LOA D & S H O R T C I R C U I T P R O T E C TIO N
TECHNICAL INFORMATION
Specification
SPN (2M)
Specification Reference
TPN (4M)
IS 12640 (Part 2) & IEC 61009
IS 12640 (Part 2) & IEC 61009
Rated Current
In
6A, 10A, 16A, 20A,25A, 32A, 40A
6A, 10A, 16A, 20A,25A, 32A, 40A
Rated Residual Operating Current
I'n
30, 100, 300mA.
30, 100, 300mA.
‘C ’curve
‘C ’curve
Instantaneous Tripping Current
Rated Voltage
Un Vac
240V~
415V~
Rated Insulation Voltage
Un Vac
660V
660V
50Hz
50Hz
Rated Frequency
No. of Pole
1P+N
3P+N
Rated Short Circuit Capacity
Icn
10kA
10kA
Rated Residual Making Breaking Capacity
I'm
500A
500A
Operating Characteristics in case of
Residual Currents
‘A’ type
‘A’ type
Method of Mounting
Panel Board Type (DIN Rail)
Panel Board Type (DIN Rail)
Degree of Protection
IP 20
IP 20
Terminals for External Conductors
Net Weight (in Kg)
0.420
0.420
-5°C to + 55°C
-5°C to + 55°C
Mechanical Endurance (No. of Operations)
4000
4000
Electrical Endurance (No. of Operations)
4000
4000
Ambient Working Temperature
Trip Time (milli Second)
Shock Resistance
Vibration Resistance
TIME CURRENT CHARACTERISTICS
C CURVE
<40
<40
40mm free fall
40mm free fall
3g
3g
RESIDUAL CURRENT TRIPPING
CHARACTERISTICS (GENERAL TYPE)
51
RES IDU A L C U RREN T C IRC U IT B R EAKER
WITH O VER LO A D & S H O RT C IRC U IT P ROTECTION
SP&N (1P+N)
DIMENSIONS (in mm) SP&N (1P+N)
52
Current Rating (A)
Sensitivity mA
Cat No.
6
30
DHCEACSN2030006
6
100
DHCEACSN2100006
6
300
DHCEACSN2300006
10
30
DHCEACSN2030010
10
100
DHCEACSN2100010
10
300
DHCEACSN2300010
16
30
DHCEACSN2030016
16
100
DHCEACSN2100016
16
300
DHCEACSN2300016
20
30
DHCEACSN2030020
20
100
DHCEACSN2100020
20
300
DHCEACSN2300020
25
30
DHCEACSN2030025
25
100
DHCEACSN2100025
25
300
DHCEACSN2300025
32
30
DHCEACSN2030032
32
100
DHCEACSN2100032
32
300
DHCEACSN2300032
40
30
DHCEACSN2030040
40
100
DHCEACSN2100040
40
300
DHCEACSN2300040
RESIDUA L CURRE N T C I R C U I T B R E A KE R
WIT H OV E R LOA D & S H O R T C I R C U I T P R O T E C TIO N
TP&N (3P+N)
Current Rating (A)
Sensitivity mA
Cat No.
6
30
DHCEACTN4030006
6
100
DHCEACTN4100006
6
300
DHCEACTN4300006
10
30
DHCEACTN4030010
10
100
DHCEACTN4100010
10
300
DHCEACTN4300010
16
30
DHCEACTN4030016
16
100
DHCEACTN4100016
16
300
DHCEACTN4300016
20
30
DHCEACTN4030020
20
100
DHCEACTN4100020
20
300
DHCEACTN4300020
25
30
DHCEACTN4030025
25
100
DHCEACTN4100025
25
300
DHCEACTN4300025
32
30
DHCEACTN4030032
32
100
DHCEACTN4100032
32
300
DHCEACTN4300032
40
30
DHCEACTN4030040
40
100
DHCEACTN4100040
40
300
DHCEACTN4300040
DIMENSIONS (in mm) TP&N (3P+N)
53
54
Distribution Board DB
Electrical energy has brought along with it a
lot of conveniences, beyond imagination. It’s
consumption has increased manifold be it in
domestic, commercial or industrial applications,
there by creating a need for scientific & effective
method of distribution.
The purpose of electrical wiring is to
systematically distribute current. In the process
the system mainly adopts methods to protect
installation and human life from electrical
hazards such as short circuit, overload and
earth leakage.
The electrical wiring is carried out to distribute
current from a single source of supply to various
circuits, such an arrangement is made inside an
enclosure called Distribution Board.
The Distribution Board is not merely an
enclosure but a comprehensive system in itself,
comprising of copper bus bars, brass neutral
links, earth links to facilitate effective distribution
of current. It incorporates safety devices such
as MCBs, ELCBs and Isolators, which serves to
protect the installation.
A wide range of compact, elegant & economical
DBs with unique features, designed &
engineered to provide user safety, convenience
and operational / maintenance advantages are
offered.
Features
s !ESTHETICALLYSUPERIOR$"STOSUITTHESTYLEOF
your home décor
s #HOICEOFMULTIPLEINCOMER-#")SOLATOR
MCB + RCCB, Changeover + RCCB, Isolator
+ RCCB + TPN RCBO
s 7HEN0ER0HASE)SOLATION$"SAREINUSE
only that phase where the earth leakage
exist gets isolated. This feature avoids the
total outage and allows the other two healthy
phases to remain ON.
s #OMPLETERANGEOF$"SWITHDETACHABLE
gland plates at the top and bottom with
knockouts on the sides of DB to increase
the flexibility of cables / conduit entry from all
directions
s 2EADYTOUSE$"STHATARESUPPLIEDWITH
Neutral Links, Earth Links, Bus Bar and inter
connecting wires / links
s 4OPTWOFOUNDATIONHOLESOFKEYTYPEAND
bottom two of Round type for mounting or
hanging the DB
s +NOCKOUTSATAPPROPRIATEPOSITIONSMAKE
the DBs suitable for wider applications,
minimizing sharp bends of cables
s %ARTH"ARFORBETTERANDlRMEARTHINGAND
for facilitating individual earthing for each
outgoing terminal
s 40.6ERTICALDESIGN$"SHAVEAPROVISION
of mounting 20A SP and 20A TP / 30A TP
sockets on the sides of DB as additional
provision
s "US"AR2ATING!
s 'ASKETSTOENSUREWEATHERPROOFCONDITIONS
s -ASKINGSHEETTOPROTECTTHE$"DURING
construction.
Range
Single Phase & Three Phase Distribution Boards
Specification
IS 13032 /IS 8623
55
DIS TRIBU TION B OAR D
RANGE
S No.
A
Type
SPN
Configuration
SPN DB
&
Consumer DB
Poles
2
Incomer
Outgoing
Device
Single Door
Double Door
4, 8, 12, 16
4, 8, 12, 16
DP MCB
DP Isolator
4, 8, 12
4, 8, 12
DP Changeover
DP RCCB
Application
Simple and economical distribution
RCCB Combination provides more
safety
B
C
TPN
Special
Phase
Application
DBs
Horizontal
4
FP MCB
FP Isolator
FP RCCB
TPN RCBO
4, 6
4, 6
8
FP MCB
+ FP RCCB,
FP Isolator
+ FP RCCB,
FP Isolator
+ TPN RCBO
FP C/O
+ TPN RCBO
4, 6, 8, 12
4, 6, 8, 12
Vertical
8
FP MCB
+FP RCCB,
FP Isolator
+FP RCCB,
FP Isolator
+ TPN RCBO
FP C/O
+ TPN RCBO
4, 8, 12
4, 8, 12
More Versatile
Three phase & Neutral incoming
The outgoing can be single as well as
multi-phase
PPI
(Vertical)
8
FP MCB
+ FP RCCB
FP Isolator
+ FP RCCB
FP Isolator
+ TPN RCBO
FP C/O
+ TPN RCBO
2 + 8, 2 + 12
2 + 8, 2 + 12
Special arrangement to prevent Isolation of
entire outage as only the phase where fault
exist, gets isolated.
Most flexible distribution
PPI
(Horizontal)
4
4
8
FP MCB
+ FP RCCB
FP Isolator
+ FP RCCB
FP Isolator
+ TPN RCBO
FP C/O
+ TPN RCBO
2+4
2+6
2+8
Phase Selector
(Vertical)
8
FP MCB
+ FP RCCB
FP Isolator
+ FP RCCB
FP Isolator
+ TPN RCBO
FP C/O
+ TPN RCBO
4, 6, 8
Phase Selector
Horizontal
56
8
FP MCB
+ FP RCCB
FP Isolator
+ FP RCCB
FP Isolator
+ TPN RCBO
FP C/O
+ TPN RCBO
Three phase & Neutral incoming.
The outgoing can be only single phase
Aesthetic four quardrant design with phase
seggregation facility as in PPI vertical DB
4, 6, 8
TPN incoming, special provision for
immediate selection of phase in case of
failure of any one or two phases
4, 6 , 8
Aesthetically superior Four Quardrant
design with phase selection facility as in
Phase Selector Vertical.
DIST RIBUT ION BOA R D
RANGE
S No.
Type
Configuration
Incomer
Poles
D
Special
Purpose
DBs
Single Door
Double Door
3
Suitable for
TP MCCB
‘G’ frame
80A, 100A, 125A
with 10KA or 16KA
Breaking Capacity
4, 8, 12
4, 8, 12
TPN vertical distribution boards most
reliable for fault level higher than 10 kA.
7 Segment
8
FP MCB
+ FP RCCB
FP Isolator
+ FP RCCB
FP Isolator
+ TPN RCBO
FP C/O
+ TPN RCBO
2+4
2+6
2+8
2+12
2+4
2+6
2+8
2+12
Suitable for high-rise buildings as a single
point distribution in the form of Per Phase
Isolation facility too.
IP 54 DBs
4
FP MCB
+ FP RCCB
FP Isolator
+ FP RCCB
FP Isolator
+ TPN RCBO
FP C/O
+ TPN RCBO
4
DP/SPN MCB
DP Isolator,
DP RCCB
SPN RCBO
6, 8, 10, 12, 16
SPN Prewired DBs 2
8, 12
Designer
TeakWood DB
SPN : 2 DP/SPN MCB
DB
Translucent DB
DP Isolator,
Transparent DB
DP RCCB
SPN RCBO
TPN : 4 FP Isolator/RCCB/
MCB
F
Application
Load Line
8
E
Device
Outgoing
Dust proof & Vermin proof distribution
board meeting IP-54 Ingress Protection
norms as per IEC 60529 : 2000.
Ready to use distribution boards pre-fitted
with MCBs and duly wired.
Aesthetically Superior Designer
Distribution Board to match the décor of
your home.
FP MCB,
FP RCCB
TPN RCBO
MCB
Plastic Enclosures
—
SP, DP, TP, FP
Enclosures
Sheet Steel
Enclosures
—
SP, DP, TP, FP
Plug & Socket
—
SPN, DP, TPN
Protection of Air Conditioners, Motors.
Independent cut-off / connection
57
DIS TRIBU TION B OAR D
MCB DISTRIBUTION BOARDS
SPN DB
SINGLE DOOR DB - IP-40 PROTECTION
No,. of
Capacity of
Sheet
Ways
17.8mm module
Thickness
Cat No.
Incomer + Outgoing
(m.m)
4
4
1.0
DHDMSHOSRW04
8
8
1.0
DHDMSHOSRW08
12
12
1.0
DHDMSHOSRW12
16
16
1.2
DHDMSHOSRW16
s !SPER)30ARTUNIVERSALMOUNTINGWITHCOPPER"US"AR.EUTRALLINK
Earth link, Earthing studs.
s "OTHSIDEDETACHABLEGLANDPLATESWITHKNOCKOUTS
s -ASKINGSHEETIN$OUBLE$OOR$"S
DIMENSIONS (in mm)
No. of
Ways
Dimensions
A
B
C
Knockout Holes (Ø25)
Top
58
Bottom Side (Each Side)
4
139
89
154
3
3
1
8
211
161
226
5
5
1
12
283
233
298
7
7
1
16
355
305
370
9
9
1
DIST RIBUT ION BOA R D
SPN SD COMPAC
No. of
Ways
Capacity of 17.8 mm
Sheet thicknes
module incomer + outgoing Box
04
4
Cat. No.
Cover
1.0
1.0
DHDMSHCSRW04
06
6
1.0
1.0
DHDMSHCSRW06
08
8
1.0
1.0
DHDMSHCSRW08
12
12
1.0
1.0
DHDMSHCSRW12
16
16
1.2
1.2
DHDMSHCSRW16
DIMENSIONS (IN MM)
No. of
Ways
Dimensions
Knockout Holes (I25)
A
B
C
Top
Bottom
Side (Each Side)
04
139
89
149
3
3
1
06
175
125
185
4
4
1
08
211
161
221
5
5
1
12
283
233
293
7
7
1
16
355
305
365
9
9
1
DOUBLE DOOR IP-42
No. of
Capacity of
Sheet
Ways
17.8 mm module
Thickness
Cat No.
Regal Gray
Pearl Ivory
Incomer + Outgoing
Box
Cover
4
4
1.0
1.2
DHDNSHODRW04 DHDNSHODPW04
8
8
1.0
1.2
DHDNSHODRW08 DHDNSHODPW08
12
12
1.0
1.2
DHDNSHODRW12 DHDNSHODPW12
16
16
1.2
1.2
DHDNSHODRW16 DHDNSHODPW16
No. of
Ways
Dimensions
A
B
C
Knockout Holes (Ø25)
Top
Bottom Side (Each Side)
4
179
129
197
3
3
1
8
251
201
269
5
5
1
12
323
273
341
7
7
1
16
395
345
413
9
9
1
59
DIS TRIBU TION B OAR D
SINGLE DOOR CONSUMER DB - IP-40 PROTECTION
No. of
Capacity of
Cat No.
Cat No.
Ways
17.8 mm module
with Isolator
without Isolator
Incomer + Outgoing
(63A Double Pole)
4
2+4
DHDCSHFSRW040001
DHDCSHOSRW04
8
2+8
DHDCSHFSRW080001
DHDCSHOSRW08
12
2 + 12
DHDCSHFSRW120001
DHDCSHOSRW12
DIMENSIONS (in mm)
No. of
Dimensions
Ways
A
B
C
Knockout Holes (Ø25)
Top
Bottom Side
2+4
211
161
226
5
5
2+8
283
233
298
7
7
2+12
355
305
370
9
9
SPN DB WITH ACRYLIC WINDOW
No. of
Capacity of
Sheet
Ways
17.8 mm module
Thickness
Incomer + Outgoing
No. of
Ways
B
C
4
1.0
1.0
DHDMSHOSRA04
08
8
1.0
1.0
DHDMSHOSRA08
12
12
1.0
1.0
DHDMSHOSRA12
16
16
1.2
1.2
DHDMSHOSRA16
Knockout Holes (Ø25)
Top
Bottom Side (Each Side)
04
139
89
154
3
3
1
08
211
161
226
5
5
1
12
283
233
298
7
7
1
16
355
305
370
9
9
1
60
Cover
04
Dimensions
A
Box
Cat No.
DIST RIBUT ION BOA R D
SPN DD
CURVED CHANNEL
No. of
Capacity of
Ways
17.8 mm module
Cat No.
Regal Gray
Pearl Ivory
Incomer + Outgoing
04
4
DHDPSHODRW04
DHDPSHODPW04
08
8
DHDPSHODRW08
DHDPSHODPW08
12
12
DHDPSHODRW12
DHDPSHODPW12
16
16
DHDPSHODRW16
DHDPSHODPW16
DIMENSIONS (in mm)
No. of
Ways
Dimensions
A
B
C
Knockout Holes (Ø25)
Top
Bottom Side (Each Side)
04
175
125
197
3
3
1
08
247
197
269
5
5
1
12
319
269
341
7
7
1
16
391
341
413
9
9
1
61
DIS TRIBU TION B OAR D
TPN HORIZONTAL DB
s !SPER)30ARTUNIVERSALMOUNTINGWITHCOPPER"US"AR.EUTRAL
link, Earth link, Earthing studs and inter-connecting wires.
s "OTHSIDEDETACHABLEGLANDPLATESWITHKNOCKOUTS
s 7ITHPROVISIONOF&0)SOLATOR-#"2##"ASINCOMERAND30OUTGOING
s -ASKINGSHEETIN$OUBLE$OOR$"S
SINGLE DOOR
Cat. No
DIMENSIONS (in mm)
No. of
Capacity of
Ways
17.8 mm module
Dimensions
A
B
C
Incomer
D
Sheet
Thickness
Incomer + Outgoing
Knockout Holes (Ø31)
Top
Bottom Side (Each Side)
DHDMTHOSRW04 4
8 + 12
270
195
285
72
4 +4
1.2
5
5
2
DHDMTHOSRW06 6
8 +18
336
261
351
72
4+4
1.2
6
6
2
DHDMTHOSRW08 8
8 + 24
414
339
429
144
4+4
1.2
8
8
2
DHDMTHOSRW12 12
8 + 36
558
483
573
144
4+4
1.2
11
11
2
62
DIST RIBUT ION BOA R D
TPN SD COMPAC
No. of
Capacity of 17.8 mm
Ways
module incomer + outgoing
Box
Sheet Thicknes
Cover
Cat. No.
04
8 + 12
1.2
1.2
DHDMTHCSRW04
06
8 + 18
1.2
1.2
DHDMTHCSRW06
08
8 + 24
1.2
1.2
DHDMTHCSRW08
12
8 + 36
1.2
1.2
DHDMTHCSRW12
DIMENSIONS (in mm)
No. of
Way
Dimensions
Knockout Holes (I31)
A
B
C
Top
Bottom
Side (Each Side)
04
270
195
280
5
4
2
06
336
261
346
6
4
2
08
414
339
424
8
4
2
12
558
483
568
11
4
2
B. DOUBLE DOOR DB - IP 42 PROTECTION
No. of
Ways
Capacity of
Cat No.
17.8 mm module
Incomer + Outgoing
Regal Grey
Pearl Ivory
4
4 + 12
DHDNTHODRW04
DHDNTHODPW04
6
4 + 18
DHDNTHODRW06
DHDNTHODPW06
4
8 + 12
DHDNPHODRW04
DHDNPHODPW04
6
8 + 18
DHDNPHODRW06
DHDNPHODPW06
8
8 + 24
DHDNTHODRW08
DHDNTHODPW08
12
8 + 36
DHDNTHODRW12
DHDNTHODPW12
DIMENSIONS (in mm)
No. of
Ways
Dimensions
A
B
C
Knockout Holes (Ø31)
484
Top
HAVELLS
Bottom Side (Each Side)
4
251
176
269
5
5
2
6
323
248
341
6
6
2
8
395
320
413
8
8
2
12
534
459
552
11
11
2
63
DIS TRIBU TION B OAR D
TPN VERTICAL DB
A. SINGLE DOOR - IP 40 PROTECTION
Cat. No
No. of
Capacity of
Ways
17.8 mm module
DIMENSIONS (in mm)
Dimensions
A
B
Knockout Holes
C
Incomer + Outgoing
Sheet
(Ø31)
(Ø31)
(Ø38)
(Ø31)
Top
Bottom
Bottom
Side (Each Side)
Thickness
DHDMTVOSRW04
4
8 + 12
465
375
450
7
2
1
2
1.2
DHDMTVOSRW08
8
8 + 24
565
475
550
7
2
1
2
1.2
DHDMTVOSRW12
12
8 + 36
673
583
658
7
2
1
2
1.2
B. DOUBLE DOOR - IP 42 PROTECTION
No. of
Capacity of
Ways
17.8 mm module
Cat No.
Incomer + Outgoing
4
8 + 12
DHDPTVODRW04
8
8 + 24
DHDPTVODRW08
12
8 + 36
DHDPTVODRW12
DIMENSIONS (in mm)
No. of
Ways
Dimensions
A
B
Knockout Holes
C
(Ø31)
(Ø31)
Top
Bottom
(Ø38)
(Ø31)
Bottom Side (Each Side)
4
450
375
460
7
2
1
2
8
550
475
560
7
2
1
2
12
658
583
668
7
2
1
2
64
DIST RIBUT ION BOA R D
TPN PER PHASE ISOLATION DB (VERTICAL)
s !SPER)30ART5NIVERSALMOUNTINGWITHCOPPER"US"AR.EUTRALLINK
Earth link, Earthing studs and inter-connecting wires.
s "OTHSIDEDETACHABLEGLANDPLATESWITHKNOCKOUTS
s 7ITHPROVISIONOF&0)SOLATOR-#"ASMAININCOMER0OLE%,#"INEACHPHASEAND
SP outgoing.
SINGLE DOOR DB - IP 40 PROTECTION
Cat. No
No. of
Capacity of
Ways
17.8 mm module
DIMENSIONS (in mm)
Dimensions
A
B
Sheet
C
Incomer + Outgoing
Knockout Holes (Ø31)
Top
Bottom
Side (Each Side)
Thickness
DHDPTVPSRW08
2+8
8 + (6 + 24)
323
248
338
7
7
6
1.2
DHDPTVPSRW12
2 + 12
8 + (6 + 36)
395
320
410
7
7
6
1.2
65
DIS TRIBU TION B OAR D
B. DOUBLE DOOR DB - IP 42 PROTECTION
No. of
Capacity of
Sheet
Ways
17.8 mm module
Thickness
Cat No.
Incomer + Outgoing
2+8
8 + (6 + 24)
1.2
DHDPTVPDRW08
2 + 12
8 + (6 + 36)
1.2
DHDPTVPDRW08
DIMENSIONS (in mm)
No. of
Dimensions
Ways
A
B
Knockout Holes (Ø31)
C
Top
Bottom
Side (Each Side)
2+8
323
248
333
7
7
6
2 + 12
395
320
405
7
7
6
TPN PPI HORIZONTAL DB
No. of
Ways
Capacity of
Sheet
17.8 mm module
Thickness
Incomer + Outgoing
Box
Cat No.
Cover
04
4 + (6+12)
1.2
1.2
DHDPTHPDRW04
06
8 + (6+18)
1.2
1.2
DHDPTHPDRW06
08
8 + (6+24)
1.2
1.2
DHDPTHPDRW08
TPN PPI HORIZONTAL DIMENSIONS (in mm)
No. of
Ways
Dimensions
A
B
Knockout Holes
C
(Ø31)
Top
Bottom
Side (Each Side)
04
323
268
333
6
6
2
06
395
340
405
8
8
2
66
DIST RIBUT ION BOA R D
TPN PPI HORIZONTAL DIMENSIONS (in mm)
No. of
Ways
08
Dimensions
A
Knockout Holes
B
557
482
C
(Ø31)
587
Top
Bottom
Side (Each Side)
11
11
2
PHASE SELECTOR VERTICAL DB (SINGLE DOOR)
Knockout Holes
No. of
Capacity of
Rating
A
B
C
Ways 17.8 mm module
Top
Bottom Each Side Sheet
Ø25 Ø20 Ø25 Ø20
Ø20 Thikness
Incoming+outgoing
4
8+12
40A
338
323
248
9
8
9
8
3
1.2
4
8+12
63A
338
323
248
9
8
9
8
3
1.2
6
8+18
40A
410
395
320
9
8
9
8
3
1.2
6
8+18
63A
410
395
320
9
8
9
8
3
1.2
8
8+24
40A
410
395
320
9
8
9
8
3
1.2
8
8+24
63A
410
395
320
9
8
9
8
3
1.2
67
DIS TRIBU TION B OAR D
PHASE SELECTOR VERTICAL DB (DOUBLE DOOR)
No. of
Rating
Ways
Cat. No.
Cat. No.
Single Door
Double Door
4
40A
DHDSMVSRZ04040
DHDSNVDRZ04040
4
63 A
DHDSMVSRZ04063
DHDSNVDRZ04063
6
40 A
DHDSMVSRZ06040
DHDSNVDRZ06040
6
63 A
DHDSMVSRZ06063
DHDSNVDRZ06063
8
40 A
DHDSMVSRZ08040
DHDSNVDRZ08040
8
63 A
DHDSMVSRZ08063
DHDSNVDRZ08063
DIMENSIONS (in mm)
Knockout Holes
No. of
Capacity of
Rating
A
B
C
Ways 17.8 mm module
Top
Bottom Each Side Sheet
Ø25 Ø20 Ø25 Ø20
Ø20 Thikness
Incoming+outgoing
PHASE SELECTOR DB (VERTICAL)
No. of
Regal Grey
4
8+12
40A
333
323
248
9
8
9
8
3
1.2
4
8+12
63A
333
323
248
9
8
9
8
3
1.2
6
8+18
40A
405
395
320
9
8
9
8
3
1.2
6
8+18
63A
405
395
320
9
8
9
8
3
1.2
8
8+24
40A
405
395
320
9
8
9
8
3
1.2
8
8+24
63A
405
395
320
9
8
9
8
3
1.2
(Without Rotary Switches & Wires)
Regal Grey
Ways Cat. No. (SD) Vertical
Cat. No. (DD) Vertical
4
DHDSMVSRB04000
DHDSNVDRB04000
6
DHDSMVSRB06000
DHDSNVDRB06000
8
DHDSMVSRB06000
DHDSNVDRB08000
PHASE SELECTOR DB (HORIZONTAL - 4 QUADRANT DESIGN)
(With Rotary Switches & Wires)
No. of
Rating
Ways
Regal Grey
Cat. No. (DD) Vertical
PHASE SELECTOR DB
4
40A
DHDSCHDRZ04040
With six way incomer slot
(Without Rotary Switches & Wires)
4
63A
DHDSCHDRZ04063
With six way incomer slot
No. of
Regal Grey
6
40A
DHDSCHDRZ06040
With eight way incomer slot
Ways
Cat. No. (DD)
6
63A
DHDSCHDRZ06063
With eight way incomer slot
4
DHDSCHDRZ04000
8
40A
DHDSCHDRZ08040
With eight way incomer slot
6
DHDSCHDRZ06000
8
63A
DHDSCHDRZ08063
With eight way incomer slot
8
DHDSCHDRZ08000
68
DIST RIBUT ION BOA R D
SPECIAL PURPOSE DISTRIBUTION BOARDS
LOADLINE DB
s !SPER)30ART5NIVERSALMOUNTINGWITHCOPPER"US"AR.EUTRAL
link, Earth link, Earthing studs and inter-connecting wires.
s "OTHSIDEDETACHABLEGLANDPLATESWITHKNOCKOUTS
s 40-##"'FRAMEASINCOMERAND30$040-#"ASOUTGOING
s (IGHER BREAKING CAPACITY -##"S OR ANY OTHER CONFIGURATION ARE AVAILABLE ON
requirement.
SINGLE DOOR
No. of
Ways
Cat. No.
Rating (A)
4
DHDLVSRWGOTO04
8
DHDLVSRWGOTO08
12
DHDLVSRWGOTO12
DIMENSIONS (in mm)
No. of Ways
Module
Capacity of
17.8 mm
Dimensions
A
B
C
Outgoing
Knockout Holes
(Ø31)
(Ø38)
Top Bottom
(Ø31)
Bottom Side (E. Side)
4
12
685
595
670
7
4
1
2
8
24
793
703
778
7
4
1
2
12
36
901
811
886
7
4
1
2
69
DIS TRIBU TION B OAR D
DOUBLE DOOR
No. of
Cat. No.
Ways
Rating (A)
4
DHDLVDRWGOTO04
8
DHDLVDRWGOTO08
12
DHDLVDRWGOTO12
DIMENSIONS (in mm)
No. of Ways
Module
Capacity of
17.8 mm
Dimensions
A
B
C
Outgoing
Knockout Holes
(Ø31)
(Ø38)
Top Bottom
(Ø31)
Bottom Side (E. Side)
4
12
700
595
670
7
4
1
2
8
24
808
703
778
7
4
1
2
12
36
916
811
886
7
4
1
2
SEVEN COMPARTMENT DB
No. of
Capacity of 17.8mm
Ways
module incomeing + Outgoing
Ways
Cat No.
Cat No.
8+(6+12)
DHDMTHDSRW04
DHDMTHDDRW04
6
8+(6+18)
DHDMTHDSRW06
DHDMTHDDRW06
8
8+(6+24)
DHDMTHDSRW08
DHDMTHDDRW08
12
8+(6 +36)
DHDMTHDSRW12
DHDMTHDDRW12
Ø31
A
B
C
Knockout Holes
4W
456
320
494
8
Sheet
1.2
6W
562
428
602
8
1.2
8W
672
536
710
8
1.6
12W
888
752
926
12
1.6
Thickness
70
Double Door
4
DOUBLE DOOR
DIMENSIONS - (in mm)
No. of
Single Door
DIST RIBUT ION BOA R D
SINGLE DOOR DIMENSIONS (in mm)
No. of
Ø25
Ways
A
B
C
Knockout Holes
Sheet
4W
450
320
430
7
1.6
6W
558
428
538
9
1.6
8W
666
536
646
10
1.6
12W
882
752
862
12
1.6
Thickness
SP&N PREWIRED DB
No. of
Capacity of
Sheet
Ways
17.8 mm module
Thickness
DB fitted with
Incomer+Outgoing Box Cover
2+6 / 2+8
2+10 / 2+12
2+16
2+6/2+8
1.6
1.6
B series SP MCBs 6-32A as outgoing
2+10/2+12
1.6
1.6
B series SP MCBs 6-32A as outgoing
2+16
1.6
1.6
B series SP MCBs 6-32A as outgoing
DIMENSIONS (in mm)
No. of
Ways
Dimensions
Knockout Holes
A
B
C
Top
Bottom
2+6 / 2+8
276
196
296
5
5
2
2+10/2+12
348
268
368
7
7
2
2+16
420
340
440
9
9
2
Ø25
Side (Each Side)
Ø31
TPN HORIZONTAL DOUBLE DOOR - IP54 (NEW)
No. of
Ways
Capacity of 17.8 mm
Sheet Thicknes
Module Incomer + Outgoing Box
Cat. No.
Cover
04
4 + 12
1.6
1.6
DHDMTHODRW040002
08
8 + 24
1.6
1.6
DHDMTHODRW080002
12
8 + 36
1.6
1.6
DHDMTHODRW120002
71
DIS TRIBU TION B OAR D
DIMENSIONS (in mm)
No. of
Dimensions
Ways
TPN DD
Knockout Holes (f31)
A
B
C
Top
Bottom
Side (Each Side)
04
251
196
251
5
5
2
08
395
340
395
8
8
2
12
534
479
534
11
11
2
CURVED CHANNEL
No. of
Capacity of
Ways
17.8 mm module
Cat No.
Incomer + Outgoing
Regal Grey
Pearl Ivory
04
4 + 12
DHDPTHODRW04
DHDPTHODPW04
06
4 + 18
DHDPTHODRW06
DHDPTHODPW06
08
8 + 24
DHDPTHODRW08
DHDPTHODPW08
12
8 + 36
DHDPTHODRW12
DHDPTHODPW12
DIMENSIONS (in mm)
Ways
Dimensions
A
B
C
Knockout Holes (Ø31)
Top
04
251
196
269
5
5
2
06
323
268
341
6
6
2
08
395
340
413
8
8
2
12
534
479
552
11
11
2
VALUE ADD FEATURES
Fixed nut plate design with
extra strength
72
Bottom Side (Each Side)
484
No. of
DIST RIBUT ION BOA R D
DESIGNER DISTRIBUTION BOARDS
TEAK WOOD & TRANSPARENT SPN DOUBLE DOOR DB
No. of
Capacity of
Sheet
Ways 17.8 mm module
Cat No.
Thickness
Transparent
Teakwood
Incomer + Outgoing
Box
Cover
4
12
1.0
1.0
DHDPSHODRT04
DHDPSHODKW04
8
24
1.0
1.0
DHDPSHODRT08
DHDPSHODKW08
12
36
1.0
1.0
DHDPSHODRT12
DHDPSHODKW12
16
48
1.2
1.2
DHDPSHODRT16
DHDPSHODKW16
DIMENSIONS (in mm)
No. of
Dimensions
Ways
A
B
C
Knockout Holes (Ø25)
Top
Bottom Side (Each Side)
04
179
129
189
3
3
1
08
251
201
261
5
5
1
12
323
273
333
7
7
1
16
395
345
405
9
9
1
TRANSLUSENT SPN DB
No. of
Capacity of 17.8 mm
Sheet
Ways
Module Incomer + Outgoing
Thickness Box
4
1.0
04
Cat. No.
DHDPSHODRC04
08
8
1.0
DHDPSHODRC08
12
12
1.0
DHDPSHODRC12
16
16
1.2
DHDPSHODRC16
DIMENSIONS (in mm)
No. of
Ways
Dimensions
Knockout Holes (I25)
A
B
C
Top
Bottom
Side (Each Side)
04
179
128
197
3
3
1
08
251
200
269
5
3
1
12
323
272
341
7
3
1
16
395
344
413
8
3
1
73
DIS TRIBU TION B OAR D
DESIGNER DB TPN DOUBLE DOOR (SIZE EQUAL TO TPN-H DD)
Way of Ways
No. of
Ways
Transparent
Teakwood
4
DHDNTHODRT04
DHDNTHODKW04
6
DHDNTHODRT06
DHDNTHODKW06
8
DHDNTHODRT08
DHDNTHODKW08
Dimensions
A
B
C
Knockout Holes (Ø31)
Top
Bottom Side (Each Side)
4
251
196
261
5
5
2
6
323
268
333
6
6
2
8
395
340
405
8
8
2
MCB ENCLOSURES
PLUG & SOCKET
s
$"SSUITABLEFORTHEPROTECTIONOFAPPLIANCESLIKE!#S-OTORS
s
30OR400LUGAND3OCKET$"S
Item
Capacity of
Cat. No.
17.8mm module
incomer + Outgoing
20A SPN
1
DHDPUSN020
20A DP
2
DHDPUDP020
30A TP
3
DHDPUTN030
DIMENSIONS (in mm)
Item
74
Dimensions
Knockout Holes (Ø25)
A
B
C
D
E
Top
Bottom
20A SP
152
116
167
139
124
2
2
20A DP
152
116
167
139
124
2
2
20A TP
278
230
293
129
114
1
1
30A TP
278
230
293
129
114
1
1
DIST RIBUT ION BOA R D
MCB ENCLOSURE
A. STEEL SHEET
(For Independent cutoff / connection of the Electrical appliances)
No. of Ways
Cat. No.
SP
DHDESSP
DP
DHDESDP
TP
DHDESTP
FP
DHDESFP
DIMENSIONS (in mm)
Item
Dimensions
Knockout Holes (f 25)
Capacity of
A
B
C
D
E
Top
Bottom
17.8 Module
SP
60
160
70
170
30
1
1
1
DP
60
160
70
170
30
1
1
2
TP
98
180
108
190
62
2
2
3
FP
98
180
108
190
62
2
2
4
MCB ENCLOSURE
B. PLASTIC
Item
Cat. No.
SP
DHDEPSP
DP
DHDEPDP
TP
DHDEPTP
FP
DHDEPFP
DIMENSIONS (in mm)
No. of
Capacity for 17.8 Module
Ways
Dimensions
A
B
C
SP
1
140
45
65
DP
2
140
45
65
TP
3
140
81
65
FP
4
140
81
65
75
DIS TRIBU TION B OAR D
CABLE END BOX
Item
No.of Ways
Cat No.
Single Door
Double Door
SPN
4
DHDASHOS04
DHDASHOD04
SPN
8
DHDASHOS08
DHDASHOD08
SPN
12
DHDASHOS12
DHDASHOD12
SPN
16
DHDASHOS16
DHDASHOD16
TPN - Horizontal
4
DHDATHOS04
DHDATHOD04
TPN - Horizontal
6
DHDATHOS06
DHDATHOD06
TPN - Horizontal
8
DHDATHOS08
DHDATHOD08
TPN - Horizontal
12
DHDATHOS12
DHDATHOD12
TPN - Vertical
4/8/12
DHDATVOS04
DHDATVOD04
Loadline
4/8/12
DHDATVLS04
DHDATVLD04
PPI
2+8
DHDATVTS10
DHDATVTD10
PPI
2+12
DHDATVTS14
DHDATVTD14
DIMENSIONS (in mm)
A. SINGLE DOOR DB
Cat. No.
Item
No. of Ways
Dimensions
A
B
C
D
E
F
G
T (Sheet Thickness)
4
139
100
63
3
89
25
154
1.0
DHDASHOS08
8
211
100
63
5
161
25
226
1.0
DHDASHOS12
12
283
100
63
7
233
25
298
1.0
DHDASHOS16
16
355
100
63
9
305
25
370
1.2
4
270
125
78
5
195
37.5
285
1.2
DHDATHOS06
6
336
125
78
6
261
37.5
351
1.2
DHDATHOS08
8
414
125
78
8
339
37.5
429
1.2
DHDATHOS12
12
558
125
78
11
483
37.5
573
1.2
DHDASHOS04
DHDATHOS04
SPN
TPN
DHDATVOS04
Vertical
4/8/12
350
125
87
7
275
37.5
365
1.2
DHDATVLS04
Loadline
4/8/12
350
125
102
7
275
37.5
365
1.2
DHDATVTS10
PPI
2+8
323
125
78
6
248
37.5
338
1.2
2 + 12
395
125
78
7
320
37.5
410
1.2
10
323
125
78
6
248
37.5
338
1.2
14
395
125
78
7
320
37.5
410
1.2
DHDATVTS14
DHDATVTS10
DHDATVTS14
76
Tier
DIST RIBUT ION BOA R D
DIMENSIONS (in mm)
B. DOUBLE DOOR DB
Cat. No.
Item
Ways
Dimensions
A
B
C
D
E
F
G
H
T
4
179
100
74
3
129
25
189
105
1.0
DHDASHOD08
8
251
100
74
5
201
25
261
105
1.0
DHDASHOD12
12
323
100
74
7
283
25
333
105
1.0
DHDASHOD16
16
395
100
74
9
345
25
405
105
1.2
4
251
125
89
5
196
37.5
261
130
1.2
DHDATHOD06
6
323
125
89
6
268
37.5
333
130
1.2
DHDATHOD08
8
395
125
89
8
340
37.5
405
130
1.2
DHDATHOD12
12
558
125
89
11
483
37.5
588
130
1.2
DHDASHOD04
DHDATHOD04
SPN
TPN
DHDATVOD04
Vertical
4/8/12
395
125
98
7
320
37.5
405
130
1.2
DHDATVLD04
Loadline
4/8/12
350
125
130
7
275
37.5
380
130
1.2
DHDATVTD10
PPI
2+8
323
125
89
6
248
37.5
333
130
1.2
2 + 12
395
125
89
7
320
37.5
405
130
1.2
10
323
125
89
6
248
37.5
333
130
1.2
14
395
125
89
7
320
37.5
405
130
1.2
DHDATVTD14
DHDATVTD10
Tier
DHDATVTD14
COMB BUS BAR
No. of Ways
Cat. No.
No. of 17.8 mm
Features
Modules
Three Phase
2
DSCCPADBX022
6
TP I/C & TP O/G
3
DSCCPADBX023
9
TP I/C & TP O/G
4
DSCCPADBX024
12
TP I/C & TP O/G
5
DSCCPADBX025
15
TP I/C & TP O/G
DSCCPADBX026
10
TP I/C & SP O/G
DSCCPADBX027
14
TP I/C & SP O/G
10 SP*
(3 Phase)
14 SP*
(3 Phase)
*For Tire DBs
77
ACCESSORIES FOR DBs
COPPER BUS BAR
No. of Ways
Cat. No.
4
DSCCUPDBP007
6
DSCCUPDBP011
8
DSCCUPDBP008
12
DSCCUPDBP009
16
DSCCUPDBP010
BLANKING PLATE
1 Pole
18mm
DSCPGMDBX001
SPARE DIN RAILS
DIN Rail used in
Cat. No.
Length of DIN Rail
SPN 4W
DSCFEFDBX094
80mm
SPN 8W / TPN 6W
DSCFEFDBX082
163mm
TPN 8W
DSCFEFDBX085
200mm
TPN 4W
DSCFEFDBX088
260mm
TPN 12W
DSCEFEDBX089
273mm
SPARE NEUTRAL LINKS FOR ALL MCB BOARDS
No. of Ways
78
Cat. No.
SPN 4W
DSSDBX0012
SPN 8W
DSSDBX0013
SPN 12W
DSSDBX0014
SPN 16W
DSSDBX0011
TPN 4W
DSSDBX0014
TPN 6W
DSSDBX0016
TPN 8W
DSSDBX0017
TPN 12W
DSSDBX0015
IP RATINGS
The IP (Ingress Protection) rating given to an enclosure states the degree of protection it offers by means of two digits. A summary of these is shown below, for
a more detailed defition, see IEC 60529 : 2000, BS EN 60529 : 1992.
First Digit
Protection against solid foreign objects and access to hazardous parts: The first digit covers protection against penetration by solid objects, which includes
hands and tools such as screwdrivers. At the lowest of seven levels, 0, no protection is offered, either of the equipment itself from damage by intrusion or of a
person contacting live or moving parts. At the highest, there shall be no entry of dust.
Second Digit
Protection against ingress of water: The second digit covers the degree of protection against the entry of water, on a progressive scale. For example, number
1 indicates that dripping water shall have no harmful effect, and number 6, that water projected in powerful jets against the enclosure from any direction shall
have no harmful effects.
No Protection
No Protection
Protected against solid objects up to 50 mm.
Protected against vertically falling
e.g. accidental touch by hands
drops of water
eg. condensation
Protected against direct sprays of
Protected against solid objects up to 12 mm
water up to 15° from the vertical
e.g. fingers
Protected against solid objects over 2.5 mm
e.g. tools and wires
Protected against sprays of water up
to 60° from the vertical
Protected against after splashed from
Protected against solid objects over 1 mm
e.g. tools, wires and small wires
all directions
-limited ingress permitted
Protected against dust
-limited ingress, no harmful deposits
Protected against low pressure jets of
water from all directions
-limited ingress permitted
Totally protected against dust.
Protected against strong jets of water
e.g. for use on ship decks
-limited ingress permitted
The letter X can be used in place of the first or second digit to indicate that tests have either not been made or are not applicable.
79
CATEGORY OF DUTY
The category of duty defines the basic type of circuit and switching capability of the device, and selection should be made accordingly.
Utilisation Category
Typical Applications
AC20/DC20
Connecting and disconnecting under no-load.
Assumes all switching operations are carried out by other capable devices before this device is operated.
AC21/DC21
Switching of resistive loads including moderate overloads.
Suitable for purely resistive type loads devices can switch 150% of its rated current under fault conditions
AC22/DC22
Switching of mixed resistive / inductive loads, including moderate overloads.
Suitable for mixed resistive / inductive loads. Devices can switch 300% of its rated current under fault conditions.
AC23/DC23
Switching of highly inductive loads.
Devices complying with AC23/DC23 are provided mainly as back-up to other means of switching. e.g. contacts. In the event
of failure of functional devices, an AC23 / DC23 type device can safety interrupt a stalled motor current. Where devices are
the only means of controlling individual motors, they should comply with the requirements of appendix A of the standard.
(IEC 60947-3)
Ue = Rated Operational Voltage
Icu Rated Ultimate Short Circuit
The normal line-to-line voltage of the
Breaking Capacity
system should not exceed (Ue)
The calculated prospective fault current at the
incoming terminals of the circuit breaker should
not exceed (Icu).
Exception: Using back-up protection as
specified by the manufacturer.
Ui = Rated Insulation Voltage
Ics Rated Short-time Withstand Current
The voltage on which the dielectric properties
The maximum level of fault current operation
Ui = 660V
have conventionally been based using tests at
after which further service is assured without
Tested@
high voltage and mains frequency. It is intended
loss of performance.
2500V ac 50Hz
to replace this value with (Uimp)
Uimp = The voltage on which clearance
distances are based.
The value of transient peak voltage the circuit
breaker can withstand from switching surges or
lighting strikes imposed on the supply.
e.g. Uimp = 8kV, Tested @8kV peak with
1.2/50m (ms)S impulse wave
Icw Rated Short-time Withstand Current
Circuit breakers of utilisation category ‘B’ have a
short-time delay allowing time-graded selectivity
between circuit breakers in series.
(Icw) is the current the circuit breaker will
withstand for the maximum short-time delay
time. Preferred times are 0.05, 0.1, 0.25, 0.5
and 1.0 second.
In = Rated Current
The current which the circuit breaker will carry
continuously under specified conditions and
on which the time / current characteristics are
based.
Unless otherwise slated (In) is based on
a reference ambient temperature of 30°
centigrade.
80