Series 300

We Keep Your Power On

®

Power Transfer Switches

Power Outage Protection

Where would you be without a constant flow of electrical power? We often take for granted that power will always be around when we need it. In reality, power failures are very common. And when the power goes out, your business suffers. Power failures are unpredictable. They can occur at any time and for any number of reasons— a bolt of lightning, a power surge, a blackout, an accident or even equipment failure. They come without warning and often at the most inconvenient times.

It

s for this reason that many businesses and other entities have invested in emergency power backup systems.

Typically, the system consists of an engine generator and an automatic transfer switch

(ATS) which transfers the load from the utility to the generator.

An ATS with built-in control logic monitors your normal power supply and senses any interruptions. When the utility power fails, the ATS automatically starts the engine and transfers the load after the generator has reached proper voltage and frequency. This happens in a matter of seconds after the power failure occurs. When the utility power has been restored, the ATS will automatically switch the load back, and after a time delay, it will shut down the engine. With an

Automatic Transfer Switch, you are protected

24 hours a day, seven days a week.

Series 300 Power Transfer Switches Typical Applications

Telecom

In the telecommunications industry, providing a high level of service and dependability is crucial.

Lost power means an interruption in service for your customers and lost business for your company.

For instance, with cell sites scattered across a wide geographical region and in many remote areas, the chances of an interruption in power are increased, making Automatic Transfer Switches a valuable resource at each location. To maintain dependable service, each cell site must be monitored

24 hours a day. This can be very difficult without some type of remote monitoring and testing capability. The Series 300 Transfer Switch, combined with ASCO ’ s monitoring and control management system, is a cost-effective, packaged solution which can help meet both of these challenging objectives without a major investment at each cell site. With ASCO ’ s connectivity solutions you can remotely monitor and control numerous sites from around the corner or around the world.

Commercial/Retail, Light Industrial

The retail industry is very competitive. An electrical power failure can have a dramatic impact on a retailer ’ s bottom line. If power is interrupted during peak shopping times, the effect could be extremely damaging to present and future business. A power interruption will not only suspend shopping, it can also create safety problems, result in lost transaction data, lost account information and damage to data collection equipment. In addition, retailers who rely on controlled climates to protect valuable inventory could suffer even greater losses, especially if the power failure occurs at a time when no one is available to rectify the situation. To avoid any of these power outage problems, simply install a backup generator with an ASCO Series 300 Transfer Switch and power outage concerns will be a thing of the past.

Municipal

The ASCO Series 300 Transfer Switch can be a critical component of a municipal government ’ s emergency power backup system. Residents of townships, cities and counties rely on police, fire, ambulance/first aid and other critical public sector services. An interruption in power would affect the ability of emergency services to effectively respond to the needs of the community.

When time is a critical factor, such as when responding to a fire alarm or an emergency call, an

ASCO Series 300 Transfer Switch can be a lifesaver, switching power to the backup generator.

While not all municipal services are a matter of life and death, they are always expected to be there.

Agriculture

Maintaining electrical power is vital to an agriculture operation. If the flow of power is interrupted, your operation could be at risk unless the backup generator is quickly activated. A prolonged power outage can affect numerous aspects of the operation, from housing and feeding livestock to processing and producing the end product. With an ASCO Series 300 Transfer Switch, power will automatically be transferred over to your backup generator, eliminating the need to manually switch from utility to generator. When power is restored, the ASCO Series 300 Transfer Switch will, after an adjustable time delay to allow for utility stabilization, automatically switch the load back to the utility service.

3

Series 300 Power Transfer Switches

4

Maximum Reliability & Excellent Value

With a Series 300 Transfer Switch, you get a product backed by ASCO

Power Technologies, the industry leader responsible for virtually every major technological advance in the Transfer Switch industry.

The ASCO Series 300 was designed for one purpose–to automatically transfer critical loads in the event of a power outage. Each and every standard component was designed by ASCO engineers for this purpose.

The rugged construction and proven performance of the ASCO

Series 300 assure the user of many years of complete reliability.

The Series 300 is even designed to handle the extraordinary demands placed on the switch when starting or restarting stalled motors and switching high inrush loads.

ASCO

’ s Series 300 modular, compact design makes it easy to install, inspect and maintain. All parts are accessible from the front so switch contacts can be easily inspected.

Features

The Series 300 is listed to UL 1008 standard for Transfer

Switch Equipment and meets NFPA 110 for Emergency and

Standby Power Systems and the National Electrical Code (NEC)

Articles 700, 701 and 702. CSA listings are also available.

30 through 3000 amps in a compact design.

Available to 600 VAC, single or three phase.

True double-throw operation: The single solenoid design is inherently interlocked and prevents contacts from stopping between sources or from being in contact with both sources at the same time.

UL Listed Withstand & Close-On Ratings

Available Symmetrical Amperes

RMS at 600 VAC

Switch Ratings amps

When Used

With Current

Limiting Fuses

When Used

With Specific

Circuit Breakers

30

70, 100, 104, 150

200 (240 V Max.)

225, 260, 400

600,800,1000,1200

1600, 2000

2600, 3000

100,000

200,000

200,000

200,000

200,000

200,000

200,000

10,000

22,000

22,000

42,000

65,000

85,000

100,000

Note:

Current-limiting fuse should be Class J type through 400 amps: use class L type above 400-amp fuse rating.

Fig. 1:

ASCO Power Transfer Switch rated

200 amperes shown in Type 3R enclosure

There ’ s no danger of the Series 300 ATS transferring loads to a dead source because the

● unique ASCO single-solenoid operator derives power to operate from the source to which the load is being transferred.

Easy-to-read flush-mounted control and display

● panel provides LED indicators for switch position and source availability. It also includes test and time-delay bypass switches as standard features.

Standard engine exerciser for weekly automatic

● testing of engine generator set with or without load.

Adjustable time-delay feature prevents switch from being activated due to momentary utility

● power outages and generator dips.

Supplied with solid neutral termination.

Optional switched neutral pole available.

Accessory kits available.

Available for immediate delivery.

Now available for service entrance applications.

Contact ASCO for assistance.

Designed to Fit Anywhere

The ASCO Series 300 product line represents the most compact design of automatic power transfer switches in the industry. With space in electrical closets being at a premium, the use of wall or floor-mounted ASCO Power Transfer Switches assures designers optimum utilization of space.

All transfer switches through 2000 amps are designed to be completely front accessible. This permits the enclosures to be installed flush to the wall and still allows installation of all power cabling and connections from the front of the switch. Cable entrance plates are also standard on the 1600 and 2000 amp units to install optional side-mounted pull boxes for additional cable bending space.

Fig. 4:

ASCO Power Transfer Switch rated 1000 amperes

Fig. 2:

ASCO Power Transfer Switch rated 200 amperes

Fig. 5:

ASCO Power Transfer Switch rated 2000 amperes shown in Type 3R enclosure

Fig. 3:

ASCO Power Transfer Switch rated 400 amperes

Fig. 6:

ASCO Power Transfer Switch rated 3000 amperes

5

Series 300 Microprocessor Controller

The ASCO Microprocessor Controller is used with all sizes of Power Transfer Switches. It represents the most reliable microprocessor controller in the industry and includes, as standard, all of the voltage, frequency, control, timing and connectivity functions required for most emergency and standby power applications.

Fig. 7:

ASCO Series 300

Microprocessor Controller

6

Fig. 8:

Door-Mounted Control & Display Panel

Control and Display Panel

Easy-to-read flush-mounted control and display panel provides LED indicators for switch position and source availability. It also includes test and time-delay bypass switches.

Voltage & Frequency Sensing

Adjustable three-phase, close-differential voltage sensing on normal source.

Normal source pickup voltage is adjustable to 95% of nominal; drop-out is adjustable from 70% to 90% of nominal.

Frequency sensing on emergency source. Pickup at 95% and dropout at 85% of nominal.

Time Delays

Adjustable time delay to override momentary normal source outages to delay all transfer switch and enginestarting signals.

Transfer to emergency time delay—Adjustable from 0 to 5 minutes for controlled timing of load transfer to emergency.

Retransfer to normal time delay—Adjustable to 30 minutes.

Five-minute unloaded running time delay for emergency engine generator cool down.

Four-second time delay to ignore momentary voltage and frequency transients during initial genset loading.

Standard Selectable Features

Inphase monitor to transfer motor loads, without any intentional off time, to prevent inrush currents from exceeding normal starting levels.

Engine exerciser to automatically test backup generator each week — Includes control switch for testing with or without load.

Selective load disconnect, double-throw contact to operate at an adjustable 0 to 20 second adjustable time delay prior to transfer and reset 0 to 20 seconds after transfer.

60 Hz or 50 Hz selectable switch.

Three-phase/single-phase selectable switch.

Remote Control Features

Terminal provisions for connecting:

Remote test switch.

Remote contact for test or for peak shaving applications.

Circuit will be automatically bypassed if emergency source fails.

Inhibit transfer to emergency.

Remote time-delay bypass switch.

Simple and Accurate

Adjustment of

Voltage, Frequency and Time-Delay

Settings Without

Need for Meters and Variable

Power Supplies

Dip Switches for Enabling

Built-In Control Functions

Customer Control

Interfaces

Fig. 9:

Microprocessor Controller

Performance Features

600 volt spacing per UL and CSA standards.

Interfacing relays are industrial grade, plug-in type with dust covers.

Meets or exceeds the requirements for Electromagnetic Compatibility (EMC).

ANSI C37.90A/IEEE472 Voltage

Surge Test

NEMA ICS-109.21 Impulse

Withstand Test

Digital circuitry isolated from

● line voltages

IEC 801-2 Electrostatic discharge (ESD) immunity

ENV50140 and IEC 803-1: Radiated electromagnetic field immunity

IEC 801-4 Electrical fast transient (EFT) immunity

ENV50142 Surge transient immunity

ENV50141: Conducted radio-frequency field immunity

EN55011: Group 1, Class A conducted and radiated emissions

Optically isolated RS-485 Serial Port

Battery to

Maintain Engine

Exerciser Clock

Settings

Retransfer to

Normal Adjustable

Time Delay

Transfer to

Emergency Adjustable

Time Delay

Serial

Communication Port

7

Series 300 ATS Optional Accessories

8

Accessory 11CD

Deluxe programmable engine exerciser provides ability to uniquely program each day of the week, or blocks of days from one minute to 24 hours with digital readout convenience. Includes “ with or without ” load control switch for exercise period. Load indicator in display to show if exerciser is ON or OFF. Timer also includes a permanent battery to maintain settings when normal and emergency power is lost.

Accessory 14AA/14BA

Auxiliary contacts to indicate position of main contacts.Two (2) for normal and two (2) for emergency position (one set is standard).

Accessory 44A

Strip Heater with thermostat for extremely cold areas to prevent condensation and freezing of this condensation. External 120 volt power source required.

Accessory 44G

Strip Heater with thermostat, wired to load terminals: 208-240,

360-380, 460-480, 550-600 volts. Contains wiring harnesses for all transfer switch sizes.

Accessory 72A

Communications Interface Module (RS-485) to allow local or remote communications with ASCO PowerQuest

®

VPi or SiteWeb™ communication products.

ASCO Pulsar

®

450

High-Performance Surge Suppressor

The ASCO Pulsar ® 450 provides unparalleled protection from power surges and transients. It is a high-performance surge suppressor which limits large surges and transients through a unique array of computer-matched metal oxide varistors (MOVs). Unique fourcavity sand packed UL94-5 volt rated housing, UL1449, UL1283, and CSA listed. Available as a separate product only for mounting by customer. Contact ASCO for ordering information.

Field Conversion Kits for Series 300 Transfer Switches

Kit No.

K601111

K613127-001

K613127-002

K609027

Description

Deluxe Engine Exerciser Kit (Acc. 11CD)

Strip Heater Kit (125 watt) 120 volt (Acc. 44A)

Strip Heater Kit (125 watt) 208-480 volt (Acc. 44G)

Cable Pull Box (1600-2000 amp)

Fig. 10:

Deluxe Engine

Exerciser

(Accessory 11CD)

Fig. 11:

Strip Heater Kit

(Accessory 44G)

Fig. 12:

Pulsar 450

Surge Suppressor

Series 386 Non-Automatic Power Transfer Switches

User-Initiated Control

ASCO 386 non-automatic transfer switches are generally used in applications where operating personnel are available and the load is not an emergency type requiring automatic transfer of power. The power-switching mechanism and controller is the same hardware used on the highly reliable ASCO Series 300 transfer switches. ASCO 386s are furnished as standard with a momentary-type selector switch to initiate transfer and retransfer. They can also be arranged for remote control via ASCO ’ s communication products.

Electrical Features:

Listed under UL 1008, CSA certified:

- UL listed through 480 VAC.

- CSA certified through 600 VAC.

Door-mounted selector switch for local, manually initiated electrical control.

Sizes from 30 through 3000 amps.

Available to 600 VAC, 50 or 60 Hz.

Rated for all classes of load transfer.

100% tungsten load ratings through 400 amps.

Designed for emergency and standby applications.

Same withstand and close-on rating as Series 300.

Standard Selectable Control Features:

Inphase monitor to transfer motor loads between live sources, without any intentional off time, to prevent inrush currents from exceeding normal starting levels.

Selective load disconnect, double-throw contact to operate at an adjustable 0 to 20 second time delay prior to transfer and reset 0 to 20 seconds after transfer.

High/Low nominal voltage setting. Allows user to adjust for source low reduced voltage conditions in remote areas.

60 Hz or 50 Hz selectable switch.

Single/Three-phase selectable switch.

Fig. 13:

ASCO 386 400 Amp

Type 1 Enclosure w/Optional

Accessories 9C, 9D Source

Availability Lights

Fig. 14:

Control and Display Panel

Control Features:

Switch position indicating signal lights.

One auxiliary contact closed when transfer switch is connected to normal and one closed on emergency, standard feature

14A/14B.

Optional Accessories:

6Q Key-operated, momentary source selector switch furnished instead of the standard selector switch.

9C, 9D Source availability lights to provide operator with a local indication of power source availability.

Accessory 14AA/14BA auxiliary contacts to indicate position of main contacts. Two (2) for normal position and two (2) for emergency position (one set is standard).

72A Communications interface module (RS-485) to allow local or remote communications with ASCO PowerQuest

®

VPi or

SiteWeb™ communication products.

Special Enclosures (Specify by appropriate code in catalog number):

Type 3R: Raintight Type 4: Weatherproof Type 12: Oil Tight

9

Series 300 Power Monitoring & Control

10

ASCO Connectivity Solutions

ASCO PowerQuest ® and SiteWeb™ communications products allow for the monitoring and control of power transfer switches in your Emergency or Standby Power Distribution System. Local Area Networks and Remote networks are supported with either single or multiple points of access, and web-enabled communications allow access to your power system from anywhere around the world.

Features

Monitors and Controls Power Transfer Switches and Engine Generators

Monitors Normal and Emergency Voltages and Frequency

Indicates Transfer Switch Position and Source Availability

Provides Transfer and Retransfer of Loads for System Testing

View Normal and Emergency Voltage and Frequency Settings

View Transfer Switch Time-Delay Settings

Provides Transfer Switch Rating and Identification

Automatic Paging Notifies Personnel, by E-mail or Pager, of Selected System Alarms

View Current, Power and Power Factor with ASCO Power Managers Connected to the System

Powe rQuest

®

Computer

Ph on e

Lin e

Pho ne L ine

TIM

TIM

RS-485

Power

Manager Generator

72A

72A

72A

ATS 1

ATS 2

ATS 32

RS-485

72A

72A

72A

ATS 1

ATS 2

ATS 32

ATS–Automatic Transfer Switch

TIM–Telephone Interface Module

72A–Communication Interface Module

Power

Manager

Generator

PowerQuest

®

VPi is a PC based software package. When combined with the ASCO Communication Interface Module (Acc 72A), the ASCO 5120 Telephone

Interface Module and ASCO 5200 Series Power Manager, as shown above, it provides the most economical communication system for monitoring and control of power transfer switches and engine generators.

The local RS-485 network allows communications with up to 32 power transfer switches and four engine generators. An analog phone connection and ASCO telephone interface module allow for direct dial up, monitoring and control of remote locations. The ASCO Power Manager not only allows you to view current power and power factor readings, but also has a programmable KW set point to initiate transfer of loads to a standby source for peak shaving operations.

Remote

Computer

ISP

TWS

RS-485

Power

Manager

72A

72A

72A

ATS 1

ATS 2

ATS 64

ISP

Local

Computer

Ethernet

Hub www

Firewall

TWS

RS-485

72A

72A

72A

ATS 1

ATS 2

ATS 64

ATS–Automatic Transfer Switch

ISP–Internet Service Provider

TWS–Thin Web Server

72A–Communication Interface Module

Power

Manager

SiteWeb TM is a client-server application requiring no software to be installed on the client computer. When combined with the ASCO Communication Interface

Module (Acc 72A), the ASCO 5500 Series Thin Web Server and the ASCO 5200 Series Power Manager, as shown above, it provides the most comprehensive

Intranet and Internet communication system for the monitoring and control of power transfer switches and engine generators located in your emergency or standby power distribution system.

The SiteWeb TM communication system allows multiple client access, from local or remote locations, and provides for the monitoring of up to 64 power transfer switches and eight engine generators. In addition, automatic paging is provided for all alarm signals.

11

Power Communication Products

Powe rQuest

®

VPi

vs.

Feature

Number of Monitored/Controlled Power Transfer Switches

Number of Monitored/Controlled Gensets

Web Access

Monitor Multiple Sites

Multiple Client Access

Client Software Required

Email / Paging upon Alarms

P Quest V Pi 32.15

32

4

No

Yes

No

Yes

No

64

8

Yes

Yes

Yes

No

Yes

Communication Interface Module (Acc 72A)

Communication Interface Module to allow local, remote or web-enabled communications with ASCO PowerQuest ® VPi or SiteWeb TM communication products.

An accessory 72A is required on each power transfer switch.

Fig. 17:

Telephone

Interface Module

Fig. 16:

Communication

Interface Module

5100 Series Telephone Interface Module

(for use with Powe rQuest

® VPi)

The ASCO Telephone Interface Module (TIM) allows users to dial directly into their

ASCO communications network for monitoring and/or control. The TIM connects to the ASCO communication network via RS-485 and the phone port connects directly into an analog phone jack. Also, the TIM has an RS-232 connector which allows the TIM to be used as the dialing modem.

Supplied with 120 VAC to 18 VDC (nominal) UL approved, class 2 power supply.

5500 Series Thin Web Server

(for use with products)

The ASCO Thin Web Server allows you to monitor and control transfer switches and engine generators anytime over the Internet or an Intranet from anywhere in the world. It also transmits a page message that an alarm has occurred with one or more of the transfer switches. Plus, this is possible from your home computer or anywhere that has Internet service, using the ASCO Thin Web Server singleboard computer with its embedded SiteWeb HTML web pages.

Fig. 18:

Thin Web Server

5200 Series Power Manager

The ASCO 5200 Series Power Manager is a microprocessor metering device specifically designed for transfer switch applications to provide real-time measurements of single and three-phase power systems. It uses digital signal processing technology to measure voltage and phase currents, which it uses to calculate real, reactive, and apparent power and bi-directional energy. All measurements can be displayed locally or at a remote PC via PowerQuest

® or SiteWeb™. It can also collect data for both normal and emergency positions using auxiliary contact inputs from the transfer switch. Eight digital input and four digital outputs available for customer use.

Fig. 19:

ASCO 5200D Series Power Manager

Communications Products for Series 300 Transfer Switches

Description

Communication Interface Module

Telephone Interface Module for Remote Monitoring*

Power Manager with Display*

Acc. Option

72A

Thin Web Server*

Thin Web Server with Modem*

PowerQuest VPi Software Package* —

*Note:

These products are available as separate items only. They can be ordered by catalog numbers shown in above chart.

Catalog No.

5120

5200D

5510E

5510M

VPi 32.15

Dimensions & Shipping Weights for

Series 300 & 386 Transfer Switches

UL Type 1 Enclosure

(See notes below for information on Type 3R, 4 & 12 Enclosures)

Switch Rating amps

30, 70, 100*, 104

*series 386 only

150, 200

225, 260, 400

600, 800, 1000

1200

1600, 2000 1

2600, 3000 2

Neutral

Code

A

B

A

B

A

C

A

C

A

B

A

B

A

B

A

B

A

B

A

B

A

B

A

B

Phase

Poles

3

3

2

2

3

3

2

2

3

3

2

2

3

3

2

2

3

3

3

3

3

3

2

2

Width

17 1/2 (445)

17 1/2 (445)

17 1/2 (445)

17 1/2 (445)

17 1/2 (445)

17 1/2 (445)

17 1/2 (445)

17 1/2 (445)

18 (457)

18 (457)

18 (457)

18 (457)

34 (864)

34 (864)

34 (864)

34 (864)

38 (965)

38 (965)

38 (965)

38 (965)

38 (965)

38 (965)

38 (965)

38 (965)

Dimensions, In. (mm)3

Height

31 (787)

31 (787)

31 (787)

31 (787)

31 (787)

31 (787)

31 (787)

31 (787)

48 (1219)

48 (1219)

48 (1219)

48 (1219)

72 (1829)

72 (1829)

72 (1829)

72 (1829)

87 (2210)

87 (2210)

87 (2210)

87 (2210)

87 (2210)

87 (2210)

91 (2311)

91 (2311)

Depth

11 5/8 (295)

11 5/8 (295)

11 5/8 (295)

11 5/8 (295)

11 5/8 (295)

11 5/8 (295)

11 5/8 (295)

11 5/8 (295)

13 (330)

13 (330)

13 (330)

13 (330)

20 (508)

20 (508)

20 (508)

20 (508)

24 (610)

24 (610)

24 (610)

24 (610)

24 (610)

24 (610)

60 (1524)

60 (1524)

Approx. Shipping

Weight Lb. (kg)4

66 (31)

70 (32)

70 (32)

74 (33)

69 (32)

73 (33)

73 (33)

75 (34)

100 (45)

110 (50)

100 (50)

120 (55)

450 (204)

475 (217)

475 (217)

500 (228)

685 (312)

705 (321)

705 (321)

725 (328)

925 (419)

975 (441)

1700 (771)

2135 (969)

14

Series 300 & 386 External Power Connections

Sizes UL-Listed Solderless Screw-Type Terminals

Switch Rating

(amps)

Ranges of AL-CU Wire Sizes

(Unless Specified Copper Only)

30, 70, 100, 104

150

200

225, 260, 400

600

800, 1000, 1200

1600, 2000

2600

3000

One #14 to 2/0 AWG

One #8 to 3/0 AWG

One #8 to 3/0 AWG CU Only

Two 1/0 AWG to 250 MCM or One #4 AWG to 600 MCM

Two 1/0 AWG to 600 MCM

Four 1/0 to 600 MCM

Six 1/0 to 600 MCM

Twelve 3/0 to 600 MCM

Twelve 3/0 to 600 MCM

Note:

All Series 300 switches are furnished with a solid neutral plate

(unless switched neutral configuration is specified) and terminal lugs.

Specify “ A ” in catalog number to order a neutral plate on the series

386 switches.

Notes:

1. Unit is designed for top cable entry of emergency & load and bottom entry of normal. A cable pull box is also available for all top or bottom cable access when required (optional accessory kit #K609027).

Not required for type 3R, 4 & 12 enclosures where available.

2. Enclosures for 2600, 3000 amps are free-standing with removable top, sides & back.

3. For type 3R, 4 & 12 dimensions, add the following values to the type 1 dimensions: a) 30, 70, 100, 104, 150, 200A–add 1.5 in (38 mm) to the height.

b) 400A - add 1.5 in (38 mm) to the depth.

c) 1200A–type 4 & 12 not available–use 1600 amp switch d) 1600A–add 3 in (76 mm) to the height and 10 in to

(253 mm) to the width.

e) 2000, 2600, 3000A–type 4 & 12 not available.

(Consult ASCO) Type 3R add 4.68 in (118 mm) to the height add 2.0 in (51 mm) to the width and add 13 in (329 mm) to the depth.

4. For type 3R, 4 & 12 weights, add the following values to the type 1 weights: a) 30, 70, 100, 104, 150, 200A–add 15 lbs. (6.8 kg).

b) 400, 600, 800, 1000A–add 40 lbs. (18.1 kg).

c) 1600A–add 60 lbs. (27 kg).

d) 2000A–3000A Type 4 & 12 not available. (Consult ASCO)

5. When temperatures below 32ºF can be experienced, special precautions should be taken, such as the inclusion of space heaters, to prevent condensation and freezing of this condensation.

This is particularly important when environmental enclosures

(Type 3R, 4 & 12) are ordered for installation outdoors.

Ordering Information for Series 300 & 386 Transfer Switches

To order an ASCO Series 300 Power Transfer Switch, complete the following catalog number:

300

Product

300

+

B

Neutral

Code

Blank

Solid

Neutral

B

1

Switched

Neutral

+

3

Poles

2 poles,

1 Ø

3 poles,

3 Ø

+

600

Amperes

Continuous rating

30, 70, 104,

150, 200

2

,

225, 260,

400, 600,

800, 1000,

1200, 1600,

2000

2600, 3000

+

K

L

M

N

Q

R

E

F

H

J

A

4

B

4

C

D

N

Voltage

Code

115

120

208

220

230

240

380

400

415

440

460

480

575

600

+

1

+

Controller

1

X

Options

Insert

X

If optional accessories are required

+

Enclosure

Blank Open Type

C

Type 1

(Standard)

F

G

L

C

Type 3R

Enclosure

Type 4

Enclosure 3

Type 12

Enclosure 3

+

11CD

Optional

Accessories

11CD

Deluxe Engine

Exerciser

14AA/14BA

Auxiliary Contacts

(2 sets)

44A, 44G

Strip Heater w/Thermostat

72A Comm

Interface Module

+ 480 V 60 Hz

Specific

Volt & Freq

This information is necessary to allow correct control settings prior to shipment

To order an ASCO Series 386 Transfer Switch, complete the following catalog number:

386

+

Product

B

Neutral

Code

386

A

Solid

Neutral

B 1

Switched

Neutral

+

3

Phase

Poles

2 poles,

1 Ø

3 poles,

3 Ø

+

600

Amperes

Continuous rating

30, 70, 100,

150, 260,

400, 600,

800, 1000,

1200, 1600,

2000, 3000

+

N

Voltage

Code

+

1

+

X

Controller Options

+

115

120

208

220

230

240

380

400

415

440

460

480

575

600

K

L

M

N

Q

R

E

F

H

J

A

4

B

4

C

D

1

Insert “ X ”

If optional accessories are required

C

Enclosure

Blank Open Type

C

Type 1

(Standard)

F

G

L

Type 3R

Enclosure

Type 4

Enclosure 3

Type 12

Enclosure 3

+

9C/9D

Optional

Accessories

6Q

Key-Operated

Control

9C/9D

Source

Availability Lights

14AA/14BA

Auxiliary Contacts

72A Comm

Interface Module

All Accessories

+ 480 V 60 Hz

Specific

Volt & Freq

This information is necessary to allow correct control settings prior to shipment

Note:

1. Specify neutral code “ C ” for 225, 260, and 400 amperes only.

2. 200 amps limited to 240 volts.

3. Available 30-1600 ampacity. Use Type 3R for 2000-3000 amp applications.

4. 115-120 volt available 30-400 amps only. For other voltages contact ASCO.

Consult ASCO for special ordering when a CSA label is required.

Extended Warranties for Series 300 Transfer Switches

Catalog No.

2EXW300

3EXW300

4EXW300

5EXW300

Description

Two-Year Extended Warranty (Parts & Labor)

Three-Year Extended Warranty (Parts & Labor)

Four-Year Extended Warranty (Parts & Labor)

Five-Year Extended Warranty (Parts & Labor)

15

Start-Up, Commissioning, Service

& Preventive Maintenance

ASCO Services, Inc., provides a wide range of technical services to users of automatic transfer switches in emergency and standby power systems. These services include comprehensive preventive maintenance programs, modifications, upgrades and emergency repairs. Systems serviced range in complexity from a single automatic transfer switch to multiple transfer switches and engine generators.

ASCO Services is a wholly owned subsidiary and the exclusive OEM service arm of ASCO Power

Technologies, the world’s largest manufacturer of power transfer switching and control equipment.

Serving the needs of ASCO’s customers is a major focus; however, ASCO Services is also routinely called upon to perform regular maintenance and emergency repairs on equipment manufactured by others.

ASCO Services offers comprehensive maintenance agreements that detail the preventive care needed to keep emergency power systems ready to respond. A service agreement is an effective way to budget in advance and avoid unexpected expenditures. A 35-point checklist is utilized to assure critical systems and components are kept in top operating condition. These preventive programs can be customized for national accounts.

This customization permits central corporate control of costs and scheduling. Periodic reports provide detailed information as to activity, maintenance performed and corrective action.

ASCO Services deploys more than

75 service personnel strategically located throughout the nation to provide

24-hour response in emergency situations. Each region is manned by experienced personnel who receive ongoing support and training in the newest equipment concepts, design and controls.

Because equipment can be utilized for a long number of years, field representatives also receive education on older designs. This knowledge can be invaluable in addressing total system concerns, evaluating problems and providing solutions on site. Service vans are equipped with parts and advanced testing equipment that facilitate these on-the-spot repairs.

Services 1-800-800-ASCO.

ASIA

AUSTRALIA

BRAZIL

CANADA

GERMANY

JAPAN

MEXICO

SOUTH AFRICA

UNITED ARAB EMIRATES

UNITED KINGDOM

UNITED STATES

Publication 1195-R6

800-937-ASCO

www.asco.com

Florham Park, New Jersey 07932 USA

©

ASCO 2002 Printed in the U.S.A.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement