April 4, 2011
Field Networks
No. 2011120E
Discontinuation Notice of
CV Series SYSMAC BUS/2 Unit and G700 Series
REQUEST
There was modification in portion of product discontinuation notices of Product News No.
2011120E of 2011 April issue.
We have changed the time in effect. It has been changed to March, 2012 from March, 2013.
Please abolish old edition, replace the latest No. 2011120E.
Product Discontinuation
CV Series SYSMAC BUS/2 Unit
Recommended Replacement
Please consider to rebuild the system
with the CompoNet network.
<Remote I/O Master Unit>
CV500-RM211 (Optical type)
CV500-RM221 (Wire type)
<Remote I/O Slave Unit>
CV500-RT211 (Optical type)
CV500-RT221 (Wire type)
G700 Series
<Master Unit>
CJ1W-CRM21, CS1W-CRM21
<Word Slave Units >
CRT1-ID16 etc.
<Building Block Type Slave>
Smart Slice GRT1 Series, GRT1-CRT
<Remote I/O Terminal (Wired type)>
G700-UID16 etc. (G700-U)
<Expansion I/O Terminal>
G700-TID04, G700-TOD04
<Cable for expansion>
G700-CN050
<Remote Terminal (Wired type)>
G700-EID32 etc. (G700-E)
<Twisted-pair Cable>
B200-TW101 etc.
Discontinuation date : The end of March, 2012
Caution on recommended replacement
To replace the conventional network with the recommended replacement network, it is necessary to change
the PLC, too. It will require large amount of design change works for replacement since PLC series and
network type are different. Please consider to purchase spare units of conventional systems, if your
conventional system has operated for a long period. Omron will provide repair and maintenance service for
seven years after product discontinuation.
OMRON Corporation
Industrial Automation Company
No. CDPMAD-110009
20110627(1)
Difference from discontinued product
**
*
--
Model
Body
Color
Dimen
sions
CompoNet
--
-
Wire
connection
-
Mounting
Dimensions
Charact
eristics
Operation
ratings
Operation
methods
-
-
-
-
: Fully compatible
: The change is a little/Almost compatible
: Not compatible
: No corresponding specification
Product Discontinuation and recommended replacement
Remote I/O Master Unit
Product discontinuation
Model
CV500-RM211 (Optical fiber type)
CV500-RM221 (Wired type)
Recommended replacement
Model
CJ1W-CRM21
CS1W-CRM21
Remote I/O Slave Unit
Product discontinuation
Model
CV500-RT211 (Optical fiber type)
CV500-RT221 (Wired type)
Recommended replacement
Model
C500-ID218-CRT
CRT1-ID16 etc.
Remote I/O terminal, Remote Interface (Wired type)
Product discontinuation
Model
G700-UID16
(DC Input)
G700-UID16-1
(DC Input)
G700-UOD16
(Tr Output)
G700-UOD16-1
(Tr Output)
G700-UMD16
(DC Input / Tr Output)
G700-TID04
(DC Input Expansion block)
G700-TOD04
(Tr Output Expansion block)
G700-CN050
(G700-T Expansion cable)
G700-EID32
(DC Input)
G700-EID32-3
(DC Input)
G700-EOD32
(Tr Output)
G700-EMD32
(DC Input / Tr Output)
G700-EMD32-3
(DC Input / Tr Output)
Recommended replacement
Model
CRT1-ID16
CRT1-ID16-1
CRT1-OD16
CRT1-OD16-1
CRT1-MD16
XWT-ID08
XWT-OD08
--CRT1-VID32ML
CRT1-VID32ML
CRT1-VOD32ML
CRT1-VMD32ML
CRT1-VMD32ML
Twisted-pair Cable
Product discontinuation
Model
B200-TW101
B200-TW201
B200-TW501
B200-TW102
B200-TW202
B200-TW502
2
Recommended replacement
Model
-------------
Communications Specifications
Product discontinuation
SYSMAC BUS/2 Wire type
Communications cable:
Shielded twisted-pair cable
Transmission speed: 1.5Mbps
Transmission distance:
500m max. (total per system)
Maximum number of nodes: 32
Maximum number of words: 128 words
Topology: Multidrop
SYSMAC BUS/2 Optical fiber type
Communications cable: H-PCF
Transmission speed: 1.5 Mbps
Transmission distance:
10km (1km max. between nodes)
Maximum number of nodes: 32
Maximum number of words: 128 words
Topology: Daisy chain
Recommendable replacement
CompoNet (1.5Mbps)
Communications cable: 2-core round cable
Transmission speed :
1.5 Mbps
Transmission distance :
Trunk line 100 m max. (total per system)
(300m with repeater units)
Maximum number of nodes:
Word Slave Units:
64 input and 64 output nodes
Bit Slave Units:
128 input and 128 output nodes
Repeater Units: 64 nodes
Maximum number of words:
Out 64 words, In 64 words
Topology: Multidrop
Note: Optical cables can not be used with
CompoNet. Please replace the
network cable, too.