DeltaV Distributed Control System
S-series Virtual I/O Module 2
Non-intrusive DeltaV
™
I/O simulation
Powerful integration solution
Easy to use
Modular, flexible packaging
Product Data Sheet
February 2016
The S-series Virtual I/O Module 2 provides DeltaV ™ I/O simulation and a high speed Ethernet I/O device integration platform.
Introduction
The DeltaV ™ S-series Virtual I/O Module 2 (VIM2) provides nonintrusive simulation of the DeltaV S-series I/O Cards and digital bus field devices for process simulation when used with
MYNAH Technologies’ MiMiC Simulation Software. DeltaV control strategies and system configurations can be fully tested with this powerful simulation interface.
The VIM2 also provides an interface to Ethernet I/O networks and devices that use e.g. the Modbus TCP or Ethernet/IP protocol drivers. DeltaV S-series controllers can read and write signals from plant floor devices connected to Ethernet
I/O networks such as PLC’s, Motor Control Centers, and
Weigh Scales.
Benefits
Non-Intrusive DeltaV I/O simulation. Use the VIM2 in conjunction with the MYNAH Technologies’ MiMiC
Simulation Software to simulate your DeltaV S-series I/O and digital bus field devices.
Supports DeltaV I/O modules. Provides completely nonintrusive simulation of all DeltaV S-series I/O Modules.
Supports autosensing of I/O and accurate testing of controller loading. DeltaV configuration can be fully tested without modifying the control strategies.
Digital bus support. Provides simulation of all DeltaV Digital
Busses and Foundation Fieldbus function blocks. Supports
Foundation Fieldbus control in the field configuration testing.
Powerful simulation solution. Provides full simulation of up to 64 DeltaV I/O modules per controller. Simulation execution is fast and efficient; the DeltaV controller thinks it’s talking with real IO.
S-series Virtual I/O Module 2 February 2016
Powerful integration solution. Use the VIM2 in conjunction with the MYNAH Ethernet I/O drivers to integrate your DeltaV system with your Ethernet I/O device networks.
Large device capacity. Each VIM2 emulates four DeltaV
Serial Cards and support up to 128 Serial Card Datasets of information from up to 128 network devices in simplex and up to 256 in dual simplex installations as well 16 devices in redundant installations. Communication over the Ethernet
I/O device network is fast and efficient.
Flexible networking. User configurable IP addressing allows the VIM2 to be used in almost any plant environment regardless of networking scheme. The VIM2 and the Ethernet
I/O devices must be on the same IP subnet to communicate.
1:1 Redundancy. Redundancy can be achieved by adding a second VIM2 and configuring the two cards as a redundant pair - when supported by the protocol. The VIM2 appears as four redundant DeltaV Serial Card pairs. Automatic switchover of primary to standby cards is handled like the
DeltaV Serial Card. The operator is given clear notification of a switchover at the operator display. Manual switchover can be controlled in DeltaV Diagnostics.
Easy to use. The VIM2 is easy to use and well integrated into the
DeltaV system. Specific ease of use features include:
Automatic updates. Simulation I/O driver updates for the
VIM2 are included with the MiMiC software releases. Updates are quick and easy over the simulation network.
Seamless Ethernet I/O integration. When used with the MYNAH Ethernet I/O drivers, the VIM2 is seen by the
DeltaV S-series controller e.g. as four DeltaV Serial Cards.
Commissioned VIM2s are then auto-sensed by the DeltaV controller as DeltaV Serial Cards.
Configured in DeltaV Explorer. When serial dataset configuration is used for the Ethernet I/O integration, it is done in the DeltaV Explorer in the same manner as a DeltaV
Serial Card. Ethernet I/O signals can be used in DeltaV Control
Modules, displayed on DeltaV Operate graphics and stored in the DeltaV Continuous Historian.
Intuitive setup. The VIMNet Explorer application provides plug-n-play capability making setup of the VIM2 easy and intuitive. Graphical, drag-n-drop, functionality makes setting up multiple VIM2s almost effortless. VIMNet Explorer is integrated with DeltaV Explorer to make setup of the VIM2 easy and intuitive.
Modular, flexible packaging. The VIM2 mounts in the same manner as the DeltaV controller. It mounts in the controller slot of a DeltaV 2-wide horizontal carrier and uses a standard DeltaV
System Power Supply. The advanced design of the VIM2 will provide years of uninterrupted use.
S-series System Power supply and VIM2.
www.emersonprocess.com
2
S-series Virtual I/O Module 2 February 2016
Product Description
The VIM2 may be used for either DeltaV I/O simulation or
Ethernet I/O device integration. The VIM2 mounts on a 2-wide carrier on either side of the DeltaV controller. A dedicated
DeltaV system power supply is required.
IO Simulation. When used with MYNAH’s MiMiC Simulation
Software, the VIM2 supports I/O simulation all DeltaV S-series
I/O cards including classic IO, F oundation
Fieldbus, ProfibusDP,
DeviceNet, ASi-bus and Serial.
MiMiC Simulation Software provide dynamic simulation for
DeltaV system software acceptance testing and operator training. The MiMiC software works by simulating the DeltaV
I/O. It also simulates field devices using Foundation Fieldbus,
ProfibusDP, DeviceNet and AS-i buses. In order for MiMiC to do this, the real I/O cards are disconnected from the control system. The MiMiC driver writes to the I/O subsystem of the
DeltaV controller. Process models in MiMiC simulate realistic process reactions to control system output signals.
Each process controller being simulated uses one MiMiC
Dataset. A MiMiC server can have up to 32 datasets or ports.
Each dataset can support up to 4000 MiMiC simulation tags.
The I/O simulation driver is provided with the VIM2 hardware, pre-loaded in the VIM2. The MiMiC Simulation Software must be purchased separately from MYNAH Technologies. Technical support for the MiMiC Simulation Software and I/O simulation driver is provided by MYNAH Technologies.
Ethernet I/O Integration. When used with the MYNAH
Ethernet I/O drivers, the VIM2 can communicate with highspeed Ethernet networks over Modbus TCP or Ethernet/IP.
Depending on wich Ethernet I/O driver is used to configure the
VIM2, the DeltaV Controller auto-senses a commissioned VIM2 as four or eight DeltaV Serial Cards or DeviceNet Cards.
In simplex installations these cards will be sensed in slots
57-60 or 61-64.
In dual simplex installations these cards will be sensed in slots
57 to 64.
In redundant installations the redundant pairs will be sensed in slots 57 to 64.Configuration of the I/O signals from the commissioned VIM2 is done in the DeltaV Explorer inthe same manner as either for a DeltaV Serial or DeviceNet Card.
VIMNet Explorer. The VIMNet Explorer utility allows the user to commission the VIM2, setup primary, secondary and/ or redundant VIM2s, and the Ethernet I/O network. The user is able to specify the IP address, Subnet Mask, and Gateway of each VIM2 and set the node address and names of each
Ethernet I/O device that is used by the VIM2. The VIMNet
Explorer is also used to flash upgrade a VIM2 from one version of a driver to another or to replace an existing driver type with another. Only one Ethernet I/O driver may be loaded in the
VIM2 at one time.
The VIMNet Explorer application must run on a workstation that has network connectivity to the Ethernet I/O network. This may be a DeltaV workstation with the 3rd network interface card (NIC) connected to the Ethernet I/O network or may be a non-DeltaV workstation. The VIMNet Explorer runs on the
MS Windows XP or Windows 7 operating system and has an intuitive, graphical user interface. Connection to the VIM2 is done through the RJ-45 Network Connection on the bottom of the VIM2.
The VIMNet Explorer software installation file for the VIM2 is available on a DeltaV v12 and later workstation and on the
DeltaV v12 and later software installation DVD. The VIMNet
Explorer software installation file is also provided with the purchase of a MYNAH Ethernet I/O driver.
VIM2 dual simplex or Redundant setups. Two VIM2s can either be setup as a dual simplex or redundant pair for installations that either consinsts of a lot of slaves or requires backup Ethernet I/O networks. Each VIM2 will be installed on its own 2-wide carrier, with its own system power supply to the left side of simplex or redundant DeltaV Controllers.
If they are setup for dual simplex operation, both VIM2s will work as standalone units, therefore no need for the redundancy link cable.If they are setup for redundant operation, the active and standby VIM2s monitor each other with a continuous status command using the redundancy link cable supplied with each redundant pair. The active VIM2 communicates over the network to the Industrial Ethernet device and the standby sends an intermittent signal to the device to maintain communication integrity.The Ethernet I/O drivers are not provided with the
VIM2 hardware; they must be purchased separately from
MYNAH Technologies. Technical support for the Ethernet I/O drivers is provided by MYNAH Technologies. www.emersonprocess.com
3
S-series Virtual I/O Module 2 February 2016
The DeltaV system with S-series VIM2 and Ethernet I/O integration (simplex VIM2 and DeltaV controller shown)
Supported Industrial
Ethernet Protocols
Modbus TCP. The VIM2 with the Modbus TCP Master Driver supports the following Modbus communications protocol function codes to read and write values to and from a Modbus slave device, as specified by the Modbus Application Protocol
Specification from Modbus-IDA.org.
The VIM2 Modbus TCP/IP Driver supports the following
Modbus function codes:
Code 1 - Read Coil Status
Code 2 - Read Input Status
Code 3 - Read Holding Registers
Code 4 - Read Input Registers
Code 5 - Force Single Coil
Code 6 - Preset Single Register
Code 8 - Diagnostic Loop Back Test
Code 15 - Force Multiple Coils
Code 16 - Preset Multiple Registers www.emersonprocess.com
The VIM2 can function as both a Modbus TCP master and slave simultaneously. Master or slave mode is set at the virtual port level. In master-only mode, this driver can communicate with a maximum of 32 slave devices in a simplex and with 64 slave devices in dual simplex setups. Systems that use both master and slave mode can communicate with a maximum of 16 slaves and 16 masters at the same time. The master and slave capability is available in simplex implementations only.
In redundant applications, only master mode is supported.
Ethernet/IP. The VIM2 with the Ethernet/IP Scanner Driver provides the following compatible functions using the Control and Information Protocol (CIP) as defined in the Ethernet/IP
Specification from Open DeviceNet Vendor Association and
ControlNet International.
The VIM2 Ethernet/IP Scanner Class Driver provides:
Ethernet/IP Scanner Class (originator) functionality.
UCMM (unconnected) messaging client and server Class
3 (connected) messaging client and server, including encapsulated DF1 message Class 1 (I/O) connection client and server.
4
S-series Virtual I/O Module 2
This driver can communicate with a maximum of 32 slave devices in a simplex and with 64 slave devices in dual simplex setups. In redundant applications, only 16 slave devices are supported.
FMC722 Subsea and Generic Ethernet/IP Driver
Both of these drivers can only communicate in a simplex or dual simplex setup. A maximum of 32/64 slave devices is supported with the FMC722 Subsea driver, while a maximum of 128/256 slave devices is supported with the
Generic Ethernet/IP driver.
ODVA Ethernet/IP. The VIM2 with the ODVA Ethernet/IP
Scanner Driver provides the following compatible functions using the Control and Information Protocol (CIP) as defined in the Ethernet/IP Specification from Open DeviceNet Vendor
Association and ControlNet International.
The VIM2 Ethernet/IP Scanner Class Driver provides:
Ethernet/IP Scanner Class (originator) functionality.
UCMM (unconnected) messaging client and server Class
3 (connected) messaging client and server, including encapsulated DF1 message Class 1 (I/O) connection client and server.
This driver can only communicate in a simplex or dual simplex setup. A maximum of 244 slave slave devices in a simplex and 488 slave devices in dual simplex setups is supported.
DeltaV Licensing Guidelines
DeltaV Software Licensing Requirements (DST count) will be used with the ODVA Ethernet/IP driver when DeviceNet
Card based Datamapping is selected as for any other v12 and later DeviceNet device. The number of DSTs per connected
DeviceNet device will be 1 DST in most cases. The DST type counted will be the most valuable type used to reference a signal for each device. If references are made to more than
16 signals from a device, additional signal references beyond the 16th reference will each count as a DST. A motor starter, for example, with 4 to 5 signal references, will consume 1 DST
(typicall an AI or DO DST). A remote I/O island will consume
1 DST for the first 16 signal references, and 1 DST for each additional signal reference beyond the 16th signal reference.
For DeltaV versions prior to v12, each signal referenced from a connected Ethernet device will count as 1 DST each.
February 2016
Using all other drivers and options, the DST count will be impacted by DeltaV Module configuration by ussingregisters, in the same way as Serial Card registers. The following guidelines can be applied:
A DeltaV Serial Card data set can contain up to 100 values
(a value can be any Boolean, 8-bit or 16-bit number), and up to16 data sets are supported by each of the 2 ports on the serial card. If the data set registers are configured as floating point or 32-bit values, then the maximum value is 50.
However, the serial device, in general, limits the total capacity of the interface.
Each data set counts as one DST as long as a single module references all values in the data set. If multiple modules reference values in a data set, then the DST count for the data set is equal to the number of modules referencing the data set.
Values used in modules containing control function blocks will be counted as Control DSTs.
S-series system power supply and VIM2 details.
www.emersonprocess.com
5
S-series Virtual I/O Module 2 February 2016
Hardware Specifications
Power requirement
Maximum current
Fuse protection (internal)
Power dissipation
User Memory
Mounting
Size dimensions
Operating temperature
Storage temperature
Relative humidity
Airborne contaminants
Shock (normal operating conditions)
Vibration (operative limit)
Specifications for the S-series Virtual I/O Module 2
Supplied by System Power Supply through 2-wide Power/Controller Carrier
1.4A at 5 VDC
3.0 A, non-replaceable fuses
5.0 W typical, 7.0 W maximum
48 MB
On right slot of power/controller carrier
4.1 cm w x 19.9 cm h x 14.0 cm d
Environmental specifications
0° to 60°C (32° to 140°F)
-40° to 85°C (-40° to 185°F)
5 to 95%, non-condensing
ISA-S71.04-1985 Airborne Contaminants Class G2
10 g ½-sine wave for 11 ms
1 mm peak-to-peak from 5 Hz to 16 Hz, 0.5 g from 16 Hz to 150 Hz
Green – Power
Red – Error
Green – Active
Green – Standby
Yellow flashing – Network
Yellow, flashing – Ctlr IO
All except Power flashing, alternating even and odd
LED Indicators – On Status
Indicates DC power is applied.
Indicates an error condition.
Indicates that the VIM2 is commissioned and active.
Not used.
Indicates valid network communication.
Indicates valid DeltaV I/O Bus communication.
Visual ID of controller initiated from user interface software by ping command
Plant Ethernet Network
Plant Ethernet Network and Redundancy Link
External connections
Two 100BaseTX RJ-45 connectors (simplex mode only)
One 100BaseTX RJ-45 connector (redundant mode)
One 100BaseTX RJ-45 connector (cable supplied with redundant modules) www.emersonprocess.com
6
S-series Virtual I/O Module 2
Software Specifications
February 2016
Max. emulated DeltaV Cards
Modbus TCP, Ethernet/IP
FMC722 Subsea
Generic Ethernet/IP
ODVA Ethernet/IP
ODVA Ethernet/IP
Modbus TCP, Ethernet/IP
FMC722 Subsea, Generic Ethernet/IP
ODVA Ethernet/IP
ODVA Ethernet/IP
Ethernet I/O Capacity
4 simplex in simplex setup
8 simplex in dual simplex setup
4 redundant in redundant setup
Amount of Slaves for Serial Data Drivers
32 in simplex setup / 64 in dual simplex setup
16 in redundant setup
32 in simplex setup / 64 in dual simplex setup
128 in simplex setup / 256 in dual simplex setup
244 in simplex setup / 488 in dual simplex setup
Amount of Slaves for Bus Card Drivers
244 in simplex setup / 488 in dual simplex setup
Max. Data Sets for Serial Data Drivers
128 in simplex setup / 256 in dual simplex setup
128 in redundant setup
128 in simplex setup / 256 in dual simplex setup
128 in simplex setup / 256 in dual simplex setup
Max. Data for Bus Card Drivers
DeviNet Card max limits
System Compatibility
S-series VIM can physically be replaced with S-series VIM2 back to V11.3.1.
Existing Drivers from S-series VIMs will not work with the S-series VIM2 and need to be converted by Mynah before they can be reused.
Ordering Information
Description
S-series Virtual I/O Module 2
Redundant S-series Virtual I/O Module 2
(Includes two VIM2s and one redundancy link cable)
Model Number
SE4026
SE4027 www.emersonprocess.com
7
S-series Virtual I/O Module 2
MYNAH Technologies Product Ordering Information
Description
MiMiC Simulation Software
Modbus TCP/IP Master Driver
Ethernet/IP Scanner Driver
Generic Device Ethernet/IP Scanner Driver
FMC722 Ethernet Protocol Driver
ODVA Ethernet/IP Protocol Driver
PROFINET Protocol Driver
February 2016
Model Number
Contact MYNAH Technologies
Contact MYNAH Technologies
Contact MYNAH Technologies
Contact MYNAH Technologies
Contact MYNAH Technologies
Contact MYNAH Technologies
Contact MYNAH Technologies
Related 3
rd
Party Products
VIMNet Explorer. Used to commission and flash upgrade the
VIM2 and to configure the Ethernet I/O network. Provided with the DeltaV v12 and later software.
MYNAH Technologies. For more information about the MiMiC
Simulation Software or Ethernet I/O drivers, please contact
MYNAH at:
MYNAH Technologies
504 Trade Center Blvd.
Chesterfield, Missouri 63005 USA
+1.636.728.2000
[email protected] www.MYNAH.com
Prerequisites
One power/controller carrier per VIM2. Please refer to the
S-series Horizontal Carriers product data sheet for details.
One dedicated system power supply per VIM2. Please refer to the S-series Power Supplies product data sheet for details.
To use for I/O Simulation with MYNAH’s MiMiC Simulation
Software, a MiMiC base license and DeltaV Railbus Driver
Pack must be purchased from MYNAH. Technical support for the MiMiC Simulation Software and I/O simulation driver is provided by MYNAH.
To use for Ethernet I/O integration, an Ethernet I/O driver must be purchased from MYNAH. Technical support for the
Ethernet I/O drivers is provided by MYNAH.
DeltaV v11.3.1 Systems and higher.
Emerson Process Management
Asia Pacific: 65.6777.8211
Europe, Middle East: 41.41.768.6111
North America, Latin America:
T 1 (800) 833-8314 or
1 (512) 832-3774 www.emersonprocess.com/deltav
©2016, Emerson Process Management. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Company. The DeltaV logo is a mark of one of the Emerson Process Management family of companies. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warrantees or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the design or specification of such products at any time without notice.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project