Safety Report

Safety Report
Page 2 of 72
Report No.:
11008637 001
Copy of marking plate:
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 3 of 72
Report No.:
11008637 001
Copy of marking plate:
Summary of testing:
The manufacturer declared that the maximum ambient temperature is 40°C.
All test with the CPU (Intel Pentium Genuine 2.80GHz for main board MS-7101 and MS-7222; AMD Athlon
64 2.20GHz for main board MS-7253), HDD (mfr. Hitachi, type: HDS7225nnVLATnn, rating: 5/12Vdc, 1.5A
/2A max.), ODD (mfr. BenQ, type: DW800A, rating: 5/12Vdc, 0.8/1.9A), CPU Fan (mfr. Sanyo, type:
109X9112PT0H016, rating: 12Vdc, 0.31A, 35.3CFM).
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 4 of 72
Report No.:
11008637 001
Particulars: test item vs. test requirements
Equipment mobility .......................................: Movable equipment
Operating condition .......................................: Continuous
Mains supply tolerance (%) ...........................: +10%, -10%
Tested for IT power systems ........................: Yes
IT testing, phase-phase voltage (V) .............: IT, 230V for Norway
Class of equipment .......................................: Class I
Mass of equipment (kg).................................: 6.4 kg
Protection against ingress of water ..............: IPX0
Test case verdicts
Test case does not apply to the test object ..: N/A
Test item does meet the requirement ..........: P(ass)
Test item does not meet the requirement ....: F(ail)
Testing
Date of receipt of test item ...........................: September, 2006
Date(s) of performance of test .....................: September- October, 2006
General remarks
”This report is not valid as a CB Test Report unless appended by an approved CB Testing
Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02”.
The test result presented in this report relate only to the object(s) tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing
laboratory.
"(see Enclosure #)" refers to additional information appended to the report.
"(see appended table)" refers to a table appended to the report.
Throughout this report a point is used as the decimal separator.
Comments:
Summary of compliance with National Differences (for explanation of codes see below):
EU Group Differences, EU Special National Conditions, EU A-Deviations, AR, AT, AU, BE, CA, CH, CN, CZ,
DE, DK, FI, FR, GB, GR, HU, IL, IN, IT, KE, KR, MY, NL, NO, PL, SE, SG, SI, SK, US.
AR=Argentina, AT=Austria, AU=Australia, BE=Belgium, CA=Canada, CH=Switzerland, CN=China,
CZ=Czech Republic, DE=Germany, DK=Denmark, FI=Finland, FR=France, GB=United Kingdom,
GR=Greece, HU=Hungary, IL=Israel, IN=India, IT=Italy, KE=Kenya, KR=Korea, MY=Malaysia, NL=The
Netherlands, NO=Norway, PL=Poland, SE=Sweden, SG=Singapore, SI=Slovenia, SK=Slovakia, US=United
States of America.
For National Differences see end of this test report.
Factory:
MSI Computer (ShenZhen) Co., Ltd.
Longma Information Technology Industrial Park, Tangtou Village, Shiyan Town, Baoan District, Shenzhen City,
Guangdong, P.R. China
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 5 of 72
Report No.:
11008637 001
General product information:
The equipment models MS-6429, MS-6434, MS-6437, Saturn 865, Saturn 800, Saturn 890 is a desktop type
personal computer for general office use.
The internal built-in Switching Power Supply (SPS) is a CB evaluated according to IEC 60950-1: 2001. The
power supply is completely enclosed by a metal enclosure and directly supplied from the mains through its
inlet, for detail information see appended table 1.5.1.
Model MS-6429 is identical to model Saturn 865 except for model designation.
Model MS-6434 is identical to model Saturn 800 except for model designation.
Model MS-6437 is identical to model Saturn 890 except for model designation.
Model MS-6429 is similar to model MS-6434 except for main board and model designation.
Model MS-6429 is similar to model MS-6437 except for main board, CPU type and model designation.
This equipment consists of following critical components:
-
An approved built-in switching power supply provided inside of personal computer (refer to appended
table 1.5.1 for source details).
-
Main board (PCB no: MS-7101 for model MS-6429 and Saturn 865; PCB no: MS-7222 for model MS6434 and Saturn 800; PCB no: MS-7253 for model MS-6437 and Saturn 890).
-
Plastic enclosure.
-
Metal chassis.
-
System Fan.
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 6 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
1
GENERAL
P
1.5
Components
P
1.5.1
General
See below.
P
Comply with IEC 60950 or relevant component
standard
Components, which were found
to affect safety aspects, comply
with the requirements of this
standard or within the safety
aspects of the relevant IEC
component standards (see
appended table 1.5.1).
P
1.5.2
Evaluation and testing of components
Components, which are
certified to IEC and/or national
standards, are used correctly
within their ratings.
Components not covered by
IEC standards are tested under
the conditions present in the
equipment.
P
1.5.3
Thermal controls
No thermal control.
1.5.4
Transformers
Transformers used in approved
SPS.
P
1.5.5
Interconnecting cables
Interconnection cable provided
with the equipment is carrying
signals on energy level below
240VA.
N/A
N/A
Besides for the insulation
materials there are not other
requirements for the
interconnection cables.
1.5.6
Capacitors in primary circuits ...............................: In approved SPS.
1.5.7
Double insulation or reinforced insulation bridged
by components
1.5.7.1
General
N/A
1.5.7.2
Bridging capacitors
N/A
1.5.7.3
Bridging resistors
N/A
1.5.7.4
Accessible parts
N/A
1.5.8
Components in equipment for IT power systems
1.6
Power interface
1.6.1
AC power distribution systems
TRF No.:IECEN60950_1B
Evaluated in the approved
SPS.
In approved SPS.
P
N/A
P
P
TN power system. IT power
system for Norway.
P
TRF originator: SGS Fimko
Page 7 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
1.6.2
Input current
Highest load according to
1.2.2.1 for this equipment is the
HDD, ODD permanently access
and connected to keyboard,
mouse, the dummy loads of
2.5W in each USB ports.
Verdict
P
(Results see appended table)
1.6.3
Voltage limit of hand-held equipment
This appliance is not a handheld equipment.
1.6.4
Neutral conductor
In approved SPS.
1.7
Marking and instructions
1.7.1
Power rating
N/A
P
P
See below.
P
Rated voltage(s) or voltage range(s) (V) .............: 1) 110-120 / 220-240V
2) 220-240V
Symbol for nature of supply, for d.c. only .............: Supplied from AC mains.
P
N/A
Rated frequency or rated frequency range (Hz) ..: 1) 60/50Hz
2) 50Hz
P
Rated current (mA or A) ......................................: 1) 8/4.5A
2) 4A
P
Manufacturer’s name or trademark or identification
mark .....................................................................:
P
Type/model or type reference...............................: MS-6429, MS-6434, MS-6437,
Saturn 865, Saturn 800, Saturn
890
P
Symbol for Class II equipment only .....................: Class I equipment.
P
Other symbols ......................................................: Other symbols do not give rise
to misunderstanding.
P
Certification marks ...............................................: See copy of the marking plate
for the safety marks.
N/A
1.7.2
Safety instructions
User instruction provided.
P
1.7.3
Short duty cycles
Equipment is designed for
continuous operation.
N/A
1.7.4
Supply voltage adjustment ...................................: The voltage marking on
adjustment switch of approved
SPS is clear.
P
Methods and means of adjustment; reference to Same as above.
installation instructions .........................................:
P
1.7.5
Power outlets on the equipment ..........................: No standard power outlets
provided.
TRF No.:IECEN60950_1B
N/A
TRF originator: SGS Fimko
Page 8 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
1.7.6
Fuse identification (marking, special fusing
In approved SPS.
characteristics, cross-reference) .........................:
1.7.7
Wiring terminals
1.7.7.1
Protective earthing and bonding terminals ..........: Appliance inlet is used.
N/A
1.7.7.2
Terminal for a.c. mains supply conductors
Appliance inlet is used.
N/A
1.7.7.3
Terminals for d.c. mains supply conductors
AC supplied equipment.
N/A
1.7.8
Controls and indicators
See below.
1.7.8.1
Identification, location and marking .....................: The marking of the stand-by
switch or functional switch or
indicators were located that
indication of function clearly.
1.7.8.2
Colours ...............................................................: No safety relevant control and
indicator.
1.7.8.3
Symbols according to IEC 60417 .........................: Marking for stand-by type switch
according IEC 60417, No. 5009
(line half inside circle) was
marked on stand-by type switch
button and marking for rocker
type power switch is according
60417-1-IEC-5007 for on
position and 60417-1-IEC-5008
for off position.
1.7.8.4
Markings using figures ........................................:
N/A
1.7.9
Isolation of multiple power sources .....................: Single mains supply.
N/A
1.7.10
IT power distribution systems
To be evaluated during national
approval.
N/A
1.7.11
Thermostats and other regulating devices
No such devices.
N/A
1.7.12
Language(s) .........................................................: Marking label marking and
user’s manual are in English.
See below.
Verdict
P
N/A
P
P
N/A
P

Versions in other languages will
be provided when national
certificate approval.
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 9 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
1.7.13
Durability
The label was subjected to the
permanence of marking test.
The label was rubbed with cloth
soaked with water for 15 s and
then again for 15 s with the
cloth soaked with petroleum
spirit.
Verdict
P
After this test there was no
damage to the label. The
marking on the label did not
fade. There was neither curling
nor lifting of the label edge.
1.7.14
Removable parts
No required markings placed
on removable parts.
1.7.15
Replaceable batteries
The Lithium type RTC battery is
exchangeable → Warning text
provided in user’s manual and
servicing instruction.
N/A
P
CAUTION: Danger of explosion
if battery is replaced incorrectly.
Replace only with same or
equivalent type recommended
by the manufacturer.
Language(s)..........................................................: English.

1.7.16
Operator access with a tool ..................................: See user manual.
P
1.7.17
Equipment for restricted access locations ............: Use of equipment not limited to
restricted access locations.
2
PROTECTION FROM HAZARDS
P
2.1
Protection from electric shock and energy hazards
P
2.1.1
Protection in operator access areas
No hazard in operator
accessible areas.
P
2.1.1.1
Access to energized parts
See below.
P
N/A
Test by inspection ................................................: No access with test finger to
any parts with only basic
insulation to ELV or hazardous
voltage.
The test pin cannot touch
hazardous voltage though any
seams within the appliance.
P
Test with test finger ..............................................: Same as above.
P
Test with test pin ..................................................: Same as above.
P
Test with test probe .............................................: No TNV circuit.
N/A
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 10 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
2.1.1.2
Battery compartments .........................................: No battery compartments
provided.
N/A
2.1.1.3
Access to ELV wiring
N/A
No ELV wiring in operator
access area.
Working voltage (Vpeak or Vrms); minimum
distance (mm) through insulation
Verdict

2.1.1.4
Access to hazardous voltage circuit wiring
2.1.1.5
Energy hazards ....................................................: No energy hazard in operator
access area.
2.1.1.6
Manual controls
No conductive shafts of
operating knobs and handles.
N/A
2.1.1.7
Discharge of capacitors in equipment
In approved SPS.
N/A
No hazardous voltage circuit in
operator access area.
Time-constant (s); measured voltage (V) .............: In approved SPS.
N/A
P

2.1.2
Protection in service access areas
No maintenance works in
operation mode necessary.
N/A
2.1.3
Protection in restricted access locations
The unit is not limited to be used
in restricted access locations.
N/A
2.2
SELV circuits
2.2.1
General requirements
2.2.2
Voltages under normal conditions (V) ..................: Between any conductors of the
SELV circuits 42.4V peak or
60Vd.c. were not exceeded.
P
2.2.3
Voltages under fault conditions (V).......................: Single fault did not cause
excessive voltage in accessible
SELV circuits. Limits of 71V
peak and 120V d.c. were not
exceeded and limits 42.4V
peak and 60V d.c. were not
exceeded for longer than 0.2
seconds.
P
2.2.3.1
Separation by double insulation or reinforced
insulation (method 1)
P
2.2.3.2
Separation by earthed screen (method 2)
N/A
2.2.3.3
Protection by earthing of the SELV circuit
(method 3)
N/A
2.2.4
Connection of SELV circuits to other circuits........: See 2.2.2 and 2.2.3.
2.3
TNV circuits
N/A
2.3.1
Limits
N/A
TRF No.:IECEN60950_1B
P
See below.
P
Method 1 used.
P
TRF originator: SGS Fimko
Page 11 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
2.3.2
2.3.3
Requirement – Test
Result – Remark
Type of TNV circuits .............................................:

Separation from other circuits and from accessible
parts
N/A
Insulation employed..............................................:

Separation from hazardous voltages
N/A
Insulation employed..............................................:
2.3.4
Verdict

Connection of TNV circuits to other circuits
N/A
Insulation employed..............................................:

2.3.5
Test for operating voltages generated externally
N/A
2.4
Limited current circuits
N/A
2.4.1
General requirements
N/A
2.4.2
Limit values
N/A
Frequency (Hz) .....................................................:

Measured current (mA).........................................:

Measured voltage (V) ...........................................:

Measured capacitance (µF) ..................................:

2.4.3
Connection of limited current circuits to other
circuits
2.5
Limited power sources
P
Inherently limited output
N/A
Impedance limited output
N/A
Results see appended table
2.5.
P
Overcurrent protective device limited output
N/A
Regulating network limited output under normal
operating and single fault condition
N/A
Regulating network limited output under normal
operating conditions and overcurrent protective
device limited output under single fault condition
N/A
Output voltage (V), output current (A), apparent
Results see appended table
power (VA)............................................................: 2.5.

Current rating of overcurrent protective device (A)

2.6
Provisions for earthing and bonding
P
2.6.1
Protective earthing
TRF No.:IECEN60950_1B
In approved SPS.
P
TRF originator: SGS Fimko
Page 12 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
2.6.2
Functional earthing
Secondary functional earthing
is connected to protectively
earthed conductive part that is
separated from primary by
basic insulation.
P
2.6.3
Protective earthing and protective bonding
conductors
In approved SPS.
P
2.6.3.1
General
See below.
P
2.6.3.2
Size of protective earthing conductors
No power cord set provided.
2
Rated current (A), cross-sectional area (mm ),
AWG .....................................................................:
2.6.3.3
Size of protective bonding conductors
Verdict
N/A

In approved SPS.
2
P
Rated current (A), cross-sectional area (mm ),
AWG .....................................................................:

2.6.3.4
Resistance (Ω) of earthing conductors and their
Refer to appended table.
terminations, test current (A) ................................:
P
2.6.3.5
Colour of insulation ...............................................: No green/yellow wire used
except in approved SPS.
P
2.6.4
Terminals
See below.
P
2.6.4.1
General
Refer to 2.6.4.2 and 2.6.4.3.
P
2.6.4.2
Protective earthing and bonding terminals
Appliance inlet is used.
P
Rated current (A), type and nominal thread
diameter (mm) ......................................................:

2.6.4.3
Separation of the protective earthing conductor
from protective bonding conductors
Appliance inlet provided. Only
one protective bonding
conductor provided.
P
2.6.5
Integrity of protective earthing
See below.
P
2.6.5.1
Interconnection of equipment
Interconnection of the
equipment only through SELV
circuits.
P
2.6.5.2
Components in protective earthing conductors
and protective bonding conductors
No switch or overcurrent
protective device in protective
earthing or bonding conductor.
P
2.6.5.3
Disconnection of protective earth
Appliance inlet provided.
P
2.6.5.4
Parts that can be removed by an operator
Plug or appliance coupler, the
earth connection is made before
and broken after the hazardous
voltage. No other operator
removable parts.
P
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 13 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
2.6.5.5
Parts removed during servicing
It is not necessary to disconnect
the earth connection except for
the removing of the earthed part
itself.
P
2.6.5.6
Corrosion resistance
All safety earthing connections
in compliance with Annex J.
P
2.6.5.7
Screws for protective bonding
Not used in protective bonding.
P
2.6.5.8
Reliance on telecommunication network or cable
distribution system
No TNV.
2.7
Overcurrent and earth fault protection in primary circuits
P
2.7.1
Basic requirements
Equipment relies on fuse or
circuit breaker of the wall outlet
installation protection of the
building installation in regard to
L to N short-circuit. Over current
protection is provided by the
built-in fuse.
P
Instructions when protection relies on building
installation
Neither pluggable equipment
type B nor permanently
connected equipment.
2.7.2
Faults not covered in 5.3
The protection devices are well
dimensioned and mounted.
P
2.7.3
Short-circuit backup protection
Pluggable equipment type A, the
building installation is
considered as providing shortcircuit backup protection.
P
2.7.4
Number and location of protective devices ..........: Over current protection by one
built-in fuse.
2.7.5
Protection by several devices
2.7.6
Warning to service personnel ...............................: No service work necessary.
N/A
2.8
Safety interlocks
N/A
2.8.1
General principles
N/A
2.8.2
Protection requirements
N/A
2.8.3
Inadvertent reactivation
N/A
2.8.4
Fail-safe operation
N/A
2.8.5
Moving parts
N/A
2.8.6
Overriding
N/A
2.8.7
Switches and relays
N/A
2.8.7.1
Contact gaps (mm) ..............................................:
N/A
TRF No.:IECEN60950_1B
Verdict
N/A
Only one fuse provided.
N/A
P
N/A
TRF originator: SGS Fimko
Page 14 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
2.8.7.2
Overload test
N/A
2.8.7.3
Endurance test
N/A
2.8.7.4
Electric strength test
N/A
2.8.8
Mechanical actuators
N/A
2.9
Electrical insulation
2.9.1
Properties of insulating materials
Natural rubber, asbestos or
hygroscopic materials are not
used.
P
2.9.2
Humidity conditioning
See below.
P
P
Humidity (%) ........................................................: 95% R.H. for 120 h.

Temperature (°C) .................................................: 40 °C

2.9.3
Grade of insulation
P
2.10
Clearances, creepage distances and distances through insulation
P
2.10.1
General
See 2.10.3, 2.10.4 and 2.10.5.
P
2.10.2
Determination of working voltage
The measurements were done
in the approval of the SPS.
P
2.10.3
Clearances
See below, Annex G was not
considered.
P
2.10.3.1
General
Annex F and minimum
clearances considered.
P
2.10.3.2
Clearances in primary circuits
In approved SPS.
P
2.10.3.3
Clearances in secondary circuits
In compliance with 5.3.4.
N/A
2.10.3.4
Measurement of transient voltage levels
Normal transient voltage
considered (overvoltage
category II for primary circuits).
N/A
2.10.4
Creepage distances
In approved SPS.
Insulation materials comply with
requirements of subclauses
2.10, 4.5.1 and 5.2.
P
CTI tests ...............................................................: CTI rating for all materials of
minimum 100.

2.10.5
Solid insulation
In approved SPS.
P
2.10.5.1
Minimum distance through insulation
In approved SPS.
P
2.10.5.2
Thin sheet material
In approved SPS.
P
2.10.5.3
Number of layers (pcs) .........................................:

Electric strength test

Printed boards
TRF No.:IECEN60950_1B
N/A
TRF originator: SGS Fimko
Page 15 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Distance through insulation
N/A
Electric strength test for thin sheet insulating
material
2.10.5.4
Verdict

Number of layers (pcs) .........................................:
N/A
Wound components
N/A
Number of layers (pcs) .........................................:
N/A
Two wires in contact inside wound component;
angle between 45° and 90° ..................................:
N/A
2.10.6
Coated printed boards
No such PCBs provided.
2.10.6.1
General
N/A
2.10.6.2
Sample preparation and preliminary inspection
N/A
2.10.6.3
Thermal cycling
N/A
2.10.6.4
Thermal ageing (°C) .............................................:
N/A
2.10.6.5
Electric strength test
2.10.6.6
Abrasion resistance test

N/A
Electric strength test
2.10.7
2.10.8
N/A

Enclosed and sealed parts ...................................: Not applied for.
N/A
Temperature T1=T2 + Tma – Tamb +10K (°C)....:
N/A
Spacings filled by insulating compound................: In approved SPS.
P
Electric strength test

2.10.9
Component external terminations
In approved SPS.
2.10.10
Insulation with varying dimensions
Insulation kept homogenous.
3
WIRING, CONNECTIONS AND SUPPLY
P
3.1
General
P
3.1.1
Current rating and overcurrent protection
All internal wires are UL
recognized wiring which are
PVC insulated, rated VW-1,
min. 80°C, 300V. Internal wiring
gauge is suitable for current
intended to be carried.
P
3.1.2
Protection against mechanical damage
Wires do not touch sharp
edges and heatsinks which
could damage the insulation
and cause hazard.
P
3.1.3
Securing of internal wiring
Internal wiring is adequately
routed and secured.
P
TRF No.:IECEN60950_1B
P
N/A
TRF originator: SGS Fimko
Page 16 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
3.1.4
Insulation of conductors
The insulation of the individual
conductors is suitable for the
application and the working
voltage. For the insulation
material see 3.1.1.
3.1.5
Beads and ceramic insulators
Not used.
N/A
3.1.6
Screws for electrical contact pressure
No electrical pressure required,
no requirements for
supplementary or reinforced
insulation.
N/A
3.1.7
Insulating materials in electrical connections
All current carrying connections
are metal to metal.
P
3.1.8
Self-tapping and spaced thread screws
No self-tapping or spaced
thread screws used.
P
3.1.9
Termination of conductors
All conductors are reliable
secured.
P
10 N pull test
Considered.
P
3.1.10
Sleeving on wiring
No sleeving used as
supplementary insulation.
3.2
Connection to an a.c. mains supply or a d.c. mains supply
P
3.2.1
Means of connection ............................................: See below.
P
3.2.1.1
Connection to an a.c. mains supply
Appliance inlet.
P
3.2.1.2
Connection to a d.c. mains supply
AC supply.
N/A
3.2.2
Multiple supply connections
Only one mains connection.
N/A
3.2.3
Permanently connected equipment
Not permanently connected
equipment.
N/A
Number of conductors, diameter (mm) of cable
and conduits ........................................................:
Appliance inlets
The appliance inlet complies
with IEC 60320-1. The power
cord can be inserted without
difficulties and does not support
the unit.
3.2.5
Power supply cords
Not provided.
3.2.5.1
AC power supply cords
2
Rated current (A), cross-sectional area (mm ),
AWG .....................................................................:
TRF No.:IECEN60950_1B
N/A
P
N/A
N/A
Type......................................................................:
DC power supply cords
P

3.2.4
3.2.5.2
Verdict


N/A
TRF originator: SGS Fimko
Page 17 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
3.2.6
Cord anchorages and strain relief
Result – Remark
Verdict
N/A
Mass of equipment (kg), pull (N) ........................:

Longitudinal displacement (mm) ..........................:

3.2.7
Protection against mechanical damage
3.2.8
Cord guards
No parts under this unit likely to
damage the power supply cord.
No sharp edge.
P
N/A
D (mm); test mass (g) ..........................................:

Radius of curvature of cord (mm).........................:

3.2.9
Supply wiring space
3.3
Wiring terminals for connection of external conductors
N/A
3.3.1
Wiring terminals
N/A
3.3.2
Connection of non-detachable power supply
cords
N/A
3.3.3
Screw terminals
N/A
3.3.4
Conductor sizes to be connected
N/A
Appliance inlet provided.
Rated current (A), cord/cable type, cross-sectional
area (mm2)............................................................:
3.3.5
N/A

Wiring terminal sizes
N/A
Rated current (A), type and nominal thread
diameter (mm) .....................................................:

3.3.6
Wiring terminals design
N/A
3.3.7
Grouping of wiring terminals
N/A
3.3.8
Stranded wire
N/A
3.4
Disconnection from the mains supply
3.4.1
General requirement
Disconnect device provided.
P
3.4.2
Disconnect devices
Appliance coupler in approved
SPS.
P
3.4.3
Permanently connected equipment
Equipment not permanently
connected.
N/A
3.4.4
Parts which remain energized
No parts remaining energized
after appliance inlet is
disconnected.
N/A
3.4.5
Switches in flexible cords
No switches in flexible cords.
N/A
3.4.6
Single-phase equipment and d.c. equipment
Appliance coupler disconnects
both poles simultaneously.
N/A
TRF No.:IECEN60950_1B
P
TRF originator: SGS Fimko
Page 18 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
3.4.7
Three-phase equipment
Single-phase equipment.
N/A
3.4.8
Switches as disconnect devices
No switch as disconnect
device.
N/A
3.4.9
Plugs as disconnect devices
No plugs as disconnect device.
N/A
3.4.10
Interconnected equipment
Interconnection with other
equipment only via SELV
outputs.
N/A
3.4.11
Multiple power sources
Only one power source.
N/A
3.5
Interconnection of equipment
3.5.1
General requirements
3.5.2
Types of interconnection circuits ..........................: Interconnection circuits of
SELV through the connectors.
3.5.3
ELV circuits as interconnection circuits
4
PHYSICAL REQUIREMENTS
P
4.1
Stability
P
Angle of 10°
Verdict
P
See below.
P
No ELV interconnection.
The equipment does not
overbalance when tilted to 10
degrees.
Test: force (N).......................................................: Equipment is not a
floorstanding unit.
P
N/A
P
N/A
4.2
Mechanical strength
4.2.1
General
After the tests the EUT
complies with the requirements
of sub-clauses 2.1.1, 2.6.1,
2.10 and 4.4.1. See below.
P
4.2.2
Steady force test, 10 N
10N applied to components
other than parts serving as an
enclosure.
P
4.2.3
Steady force test, 30 N
No internal enclosure.
4.2.4
Steady force test, 250 N
250N applied to outer
enclosure and the accessible
enclosure of the SPS. No
energy or other hazards.
P
4.2.5
Impact test
No hazard as result from steel
sphere ball impact test.
P
Fall test
No hazard as result from steel
sphere ball impact test.
P
TRF No.:IECEN60950_1B
P
N/A
TRF originator: SGS Fimko
Page 19 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Swing test
No hazard as result from steel
sphere ball impact test.
4.2.6
Drop test
Not direct plug-in type
N/A
4.2.7
Stress relief test
Metal enclosure.
N/A
4.2.8
Cathode ray tubes
No CRT used.
N/A
Picture tube separately certified ...........................:
Verdict
P
N/A
4.2.9
High pressure lamps
4.2.10
Wall or ceiling mounted equipment; force (N) .....: Not wall or ceiling mounted.
4.3
Design and construction
4.3.1
Edges and corners
4.3.2
Handles and manual controls; force (N) ...............: No handles or controls provided.
N/A
4.3.3
Adjustable controls
None that would cause hazard.
N/A
4.3.4
Securing of parts
Electrical and mechanical
connections can be expected
to withstand usual mechanical
stress. For the protection
solder pins are used.
P
4.3.5
Connection of plugs and sockets
Mismatch of connectors were
prevented by incompatible form
or location.
P
4.3.6
Direct plug-in equipment
Not direct plug-in type.
4.3.7
No high pressure lamp.
N/A
N/A
P
Edges and corners of the
enclosure are rounded.
P
N/A
Dimensions (mm) of mains plug for direct plug-in :
N/A
Torque and pull test of mains plug for direct
plug-in; torque (Nm); pull (N) ................................:
N/A
Heating elements in earthed equipment
TRF No.:IECEN60950_1B
No heating elements.
N/A
TRF originator: SGS Fimko
Page 20 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
4.3.8
Batteries
For non-rechargeable lithium
type RTC battery:
•
There is no reverse polarity
installation could possible
due to design of socket.
•
The battery is protected
from reverse charging by
diode D6 and R412 (for
main board: MS-7101) or
D5 and R256 (for main
board: MS-7222) or D10
and R355 (for main board:
MS-7253)
Verdict
P
Results see appended table
5.3.
4.3.9
Oil and grease
No oil or grease.
N/A
4.3.10
Dust, powders, liquids and gases
The equipment in intended use
not considered to be exposed to
dust, powers, liquids and gases.
N/A
4.3.11
Containers for liquids or gases
No container for liquid or gas.
N/A
4.3.12
Flammable liquids.................................................: No flammable liquid.
N/A
Quantity of liquid (l) ...............................................:
N/A
Flash point (°C).....................................................:
N/A
4.3.13
Radiation; type of radiation ..................................: See below.
P
4.3.13.1
General
See below.
P
4.3.13.2
Ionizing radiation
No ionizing radiation.
4.3.13.3
N/A
Measured radiation (pA/kg) .................................:

Measured high-voltage (kV) ................................:

Measured focus voltage (kV) ...............................:

CRT markings .....................................................:

Effect of ultraviolet (UV) radiation on materials
No UV radiation.
N/A
Part, property, retention after test, flammability
classification ........................................................:
N/A
4.3.13.4
Human exposure to ultraviolet (UV) radiation ......:
N/A
4.3.13.5
Laser (including LEDs)
LED power is far below LED
Class 1 limit.
P
Other optional optical drives
should be evaluated in the end
products.
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 21 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Laser class ...........................................................:
Verdict

4.3.13.6
Other types ..........................................................: No other types radiation.
4.4
Protection against hazardous moving parts
4.4.1
General
See below.
P
4.4.2
Protection in operator access areas
DC fan are protected by
enclosure or metal guard.
P
N/A
P
Other motors should be
evaluated in the end products.
4.4.3
Protection in restricted access locations
N/A
4.4.4
Protection in service access areas
N/A
4.5
Thermal requirements
4.5.1
Maximum temperatures
P
See appended table 4.5.1.
Normal load condition per Annex L.......................: See 1.6.2.
P
P
4.5.2
Resistance to abnormal heat
4.6
Openings in enclosures
P
4.6.1
Top and side openings
P
Dimensions (mm) ................................................: See appended table

Bottoms of fire enclosures
P
Construction of the bottom ...................................: See appended table

4.6.2
N/A
4.6.3
Doors or covers in fire enclosures
N/A
4.6.4
Openings in transportable equipment
N/A
4.6.5
Adhesives for constructional purposes
N/A
Conditioning temperature (°C)/time (weeks) ........:

4.7
Resistance to fire
P
4.7.1
Reducing the risk of ignition and spread of flame
See below.
P
Method 1, selection and application of
components wiring and materials
Use of materials with the
required flammability classes.
P
Method 2, application of all of simulated fault
condition tests
4.7.2
Conditions for a fire enclosure
TRF No.:IECEN60950_1B
N/A
See below.
P
TRF originator: SGS Fimko
Page 22 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
4.7.2.1
Parts requiring a fire enclosure
With having the following parts:
•
Components in secondary
(not supplied by LPS)
•
Insulated wiring
•
components in primary
Verdict
P
The fire enclosure is required.
4.7.2.2
Parts not requiring a fire enclosure
4.7.3
Materials
4.7.3.1
General
See appended table 1.5.1 for
PCB material.
P
4.7.3.2
Materials for fire enclosures
See appended table 1.5.1 for
enclosure material.
P
4.7.3.3
Materials for components and other parts outside
fire enclosures
Front panel (decorative part)
used HB min.
P
4.7.3.4
Materials for components and other parts inside
fire enclosures
Internal components except
small parts are V-2, HF-2 or
better.
P
4.7.3.5
Materials for air filter assemblies
No air filter assemblies.
N/A
4.7.3.6
Materials used in high-voltage components
No high voltage component.
N/A
5
ELECTRICAL REQUIREMENTS AND SIMULATED ABNORMAL CONDITIONS
P
5.1
Touch current and protective conductor current
P
5.1.1
General
See sub-clauses 5.1.2 to 5.1.6.
P
5.1.2
Equipment under test (EUT)
EUT has only one mains
connection.
P
5.1.3
Test circuit
Equipment of figure 5A used.
P
5.1.4
Application of measuring instrument
Using measuring instrument in
annex D.
P
5.1.5
Test procedure
The touch current was
measured from primary to
output connector and metal
chassis.
P
5.1.6
Test measurements
See below.
P
See clasue 4.7.2.1.
N/A
P
Test voltage (V) ...................................................: See appended table 5.1.6.

Measured touch current (mA) ..............................: See appended table 5.1.6.

Max. allowed touch current (mA) .........................: See appended table 5.1.6.

Measured protective conductor current (mA) ......:

Max. allowed protective conductor current (mA) .:

TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 23 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
5.1.7
Equipment with touch current exceeding 3.5 mA : Not exceeded.
N/A
5.1.8
Touch currents to and from telecommunication
No TNV circuit connection.
networks and cable distribution systems and from
telecommunication networks
N/A
5.1.8.1
Limitation of the touch current to a
telecommunication network and a cable
distribution system
N/A
Test voltage (V) ...................................................:

Measured touch current (mA) ..............................:

Max. allowed touch current (mA) .........................:

5.1.8.2
Summation of touch currents from
telecommunication networks ................................:
N/A
5.2
Electric strength
5.2.1
General
See appended table 5.2.
P
5.2.2
Test procedure
See appended table 5.2.
P
5.3
Abnormal operating and fault conditions
5.3.1
Protection against overload and abnormal
operation
See appended table 5.3.
P
5.3.2
Motors
Certified DC fans used, see
table 1.5.1 for detail.
P
5.3.3
Transformers
In approved SPS.
5.3.4
Functional insulation .............................................: Method c). Results see in
appended table 5.3.
5.3.5
Electromechanical components
No electromechanical
component provided.
5.3.6
Simulation of faults
Results see appended table
5.3.
5.3.7
Unattended equipment
None of the listed components
was provided.
N/A
5.3.8
Compliance criteria for abnormal operating and
fault conditions
Neither fire occurred nor molten
metal was emitted. Electric
strength test primary to
secondary, earth and primary to
accessible enclosure wrapped
with metal foil were passed.
P
6
CONNECTION TO TELECOMMUNICATION NETWORKS
TRF No.:IECEN60950_1B
P
P
N/A
P
N/A
P
N/A
TRF originator: SGS Fimko
Page 24 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
6.1
Protection of telecommunication network service persons, and users of other
equipment connected to the network, from hazards in the equipment
N/A
6.1.1
Protection from hazardous voltages
N/A
6.1.2
Separation of the telecommunication network from earth
N/A
6.1.2.1
Requirements
N/A
Test voltage (V) ...................................................:

Current in the test circuit (mA) ............................:

6.1.2.2
Exclusions.............................................................:
N/A
6.2
Protection of equipment users from overvoltages on telecommunication networks
N/A
6.2.1
Separation requirements
N/A
6.2.2
Electric strength test procedure
N/A
6.2.2.1
Impulse test
N/A
6.2.2.2
Steady-state test
N/A
6.2.2.3
Compliance criteria
N/A
6.3
Protection of the telecommunication wiring system from overheating
N/A
Max. output current (A) .........................................:

Current limiting method ........................................:

7
CONNECTION TO CABLE DISTRIBUTION SYSTEMS
N/A
7.1
Protection of cable distribution system service
persons, and users of other equipment
connected to the system, from hazardous
voltages in the equipment
N/A
7.2
Protection of equipment users from overvoltages
on the cable distribution system
N/A
7.3
Insulation between primary circuits and cable
distribution systems
N/A
7.3.1
General
N/A
7.3.2
Voltage surge test
N/A
7.3.3
Impulse test
N/A
A
ANNEX A, TESTS FOR RESISTANCE TO HEAT AND FIRE
N/A
A.1
Flammability test for fire enclosures of movable equipment having a total mass
exceeding 18 kg, and of stationary equipment (see 4.7.3.2)
N/A
A.1.1
Samples................................................................:
TRF No.:IECEN60950_1B

TRF originator: SGS Fimko
Page 25 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
Wall thickness (mm) .............................................:

A.1.2
Conditioning of samples; temperature (°C) ..........:
N/A
A.1.3
Mounting of samples ............................................:
N/A
A.1.4
Test flame (see IEC 60695-11-3)
N/A
Flame A, B, C or D ...............................................:

A.1.5
Test procedure
N/A
A.1.6
Compliance criteria
N/A
Sample 1 burning time (s) ....................................:

Sample 2 burning time (s) ....................................:

Sample 3 burning time (s) ....................................:

A.2
Flammability test for fire enclosures of movable equipment having a total mass not
exceeding 18 kg, and for material and components located inside fire enclosures
(see 4.7.3.2 and 4.7.3.4)
A.2.1
Samples, material.................................................:

Wall thickness (mm) .............................................:

N/A
A.2.2
Conditioning of samples
N/A
A.2.3
Mounting of samples ...........................................:
N/A
A.2.4
Test flame (see IEC 60695-11-4)
N/A
Flame A, B or C ...................................................:

A.2.5
Test procedure
N/A
A.2.6
Compliance criteria
N/A
A.2.7
Sample 1 burning time (s) ....................................:

Sample 2 burning time (s) ....................................:

Sample 3 burning time (s) ....................................:

Alternative test acc. to IEC 60695-2-2, cl. 4 and 8
N/A
Sample 1 burning time (s) ....................................:

Sample 2 burning time (s) ....................................:

Sample 3 burning time (s) ....................................:

A.3
Hot flaming oil test (see 4.6.2)
N/A
A.3.1
Mounting of samples
N/A
A.3.2
Test procedure
N/A
A.3.3
Compliance criterion
N/A
B
ANNEX B, MOTOR TESTS UNDER ABNORMAL CONDITIONS (see 4.7.2.2 and
5.3.2)
TRF No.:IECEN60950_1B
P
TRF originator: SGS Fimko
Page 26 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
B.1
General requirements
Approved DC fan used.
Verdict
N/A
Position ................................................................:

Manufacturer ........................................................:

Type .....................................................................:

Rated values .......................................................:

B.2
Test conditions
P
B.3
Maximum temperatures
N/A
B.4
Running overload test
N/A
B.5
Locked-rotor overload test
N/A
Test duration (days) .............................................:

Electric strength test: test voltage (V) ..................:

B.6
Running overload test for d.c. motors in
secondary circuits
N/A
B.7
Locked-rotor overload test for d.c. motors in secondary circuits
N/A
B.7.1
Test procedure
N/A
B.7.2
Alternative test procedure; test time (h)................:
N/A
B.7.3
Electric strength test
N/A
B.8
Test for motors with capacitors
N/A
B.9
Test for three-phase motors
N/A
B.10
Test for series motors
N/A
Operating voltage (V) ...........................................:
C

ANNEX C, TRANSFORMERS (see 1.5.4 and 5.3.3)
N/A
Position ................................................................:

Manufacturer ........................................................:

Type .....................................................................:

Rated values .......................................................:

Method of protection .............................................:

C.1
Overload test
N/A
C.2
Insulation
N/A
Protection from displacement of windings ............:
N/A
D
ANNEX D, MEASURING INSTRUMENTS FOR TOUCH-CURRENT TESTS
(see 5.1.4)
P
D.1
Measuring instrument
P
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 27 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
D.2
Alternative measuring instrument
N/A
E
ANNEX E, TEMPERATURE RISE OF A WINDING (see 1.4.13)
N/A
F
ANNEX F, MEASUREMENT OF CLEARANCES AND CREEPAGE DISTANCES
(see 2.10)
N/A
G
ANNEX G, ALTERNATIVE METHOD FOR DETERMINING MINIMUM
CLEARANCES
N/A
G.1
Summary of the procedure for determining
minimum clearances
N/A
G.2
Determination of mains transient voltage (V) .......:
N/A
G.2.1
AC mains supply
N/A
G.2.2
DC mains supply
N/A
G.3
Determination of telecommunication network
transient voltage (V)..............................................:
N/A
G.4
Determination of required withstand voltage (V)...:
N/A
G.5
Measurement of transient levels (V).....................:
N/A
G.6
Determination of minimum clearances .................:
N/A
H
ANNEX H, IONIZING RADIATION (see 4.3.13)
N/A
J
ANNEX J, TABLE OF ELECTROCHEMICAL POTENTIALS (see 2.6.5.6)
P
Metal used ...........................................................:

K
ANNEX K, THERMAL CONTROLS (see 1.5.3 and 5.3.7)
N/A
K.1
Making and breaking capacity
N/A
K.2
Thermostat reliability; operating voltage (V) .........:
N/A
K.3
Thermostat endurance test; operating voltage
(V) .......................................................................:
N/A
K.4
Temperature limiter endurance; operating voltage
(V) ........................................................................:
N/A
K.5
Thermal cut-out reliability
N/A
K.6
Stability of operation
N/A
L
ANNEX L, NORMAL LOAD CONDITIONS FOR SOME TYPES OF ELECTRICAL
BUSINESS EQUIPMENT (see 1.2.2.1 and 4.5.1)
TRF No.:IECEN60950_1B
P
TRF originator: SGS Fimko
Page 28 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
L.1
Typewriters
N/A
L.2
Adding machines and cash registers
N/A
L.3
Erasers
N/A
L.4
Pencil sharpeners
N/A
L.5
Duplicators and copy machines
N/A
L.6
Motor-operated files
N/A
L.7
Other business equipment
M
ANNEX M, CRITERIA FOR TELEPHONE RINGING SIGNALS (see 2.3.1)
N/A
M.1
Introduction
N/A
M.2
Method A
N/A
M.3
Method B
N/A
M.3.1
Ringing signal
N/A
M.3.1.1
Frequency (Hz) ....................................................:

M.3.1.2
Voltage (V) ...........................................................:

M.3.1.3
Cadence; time (s), voltage (V) .............................:

M.3.1.4
Single fault current (mA) .......................................:

M.3.2
Tripping device and monitoring voltage ................:
N/A
M.3.2.1
Conditions for use of a tripping device or a
monitoring voltage
N/A
M.3.2.2
Tripping device
N/A
M.3.2.3
Monitoring voltage (V)...........................................:
N/A
N
ANNEX N, IMPULSE TEST GENERATORS (see 2.10.3.4, 6.2.2.1, 7.3.2 and
clause G.5)
N/A
N.1
ITU-T impulse test generators
N/A
N.2
IEC 60065 impulse test generator
N/A
P
ANNEX P, NORMATIVE REFERENCES
Q
ANNEX Q, BIBLIOGRAPHY
TRF No.:IECEN60950_1B
Result – Remark
See 1.6.2
Verdict
P
P
N/A
TRF originator: SGS Fimko
Page 29 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
R
ANNEX R, EXAMPLES OF REQUIREMENTS FOR QUALITY CONTROL
PROGRAMMES
N/A
R.1
Minimum separation distances for unpopulated
coated printed boards (see 2.10.6)
N/A
R.2
Reduced clearances (see 2.10.3)
N/A
S
ANNEX S, PROCEDURE FOR IMPULSE TESTING (see 6.2.2.3)
N/A
S.1
Test equipment
N/A
S.2
Test procedure
N/A
S.3
Examples of waveforms during impulse testing
N/A
T
ANNEX T, GUIDANCE ON PROTECTION AGAINST INGRESS OF WATER
(see 1.1.2)
N/A

U
ANNEX U, INSULATED WINDING WIRES FOR USE WITHOUT INTERLEAVED
INSULATION (see 2.10.5.4)
N/A

V
ANNEX V, AC POWER DISTRIBUTION SYSTEMS (see 1.6.1)
N/A
V.1
Introduction
N/A
V.2
TN power distribution systems
N/A
V.3
TT power systems
N/A
V.4
IT power systems
N/A
W
ANNEX W, SUMMATION OF TOUCH CURRENTS
N/A
W.1
Touch current from electronic circuits
N/A
W.1.2
Earthed circuits
N/A
W.2
Interconnection of several equipments
N/A
W.2.1
Isolation
N/A
W.2.2
Common return, isolated from earth
N/A
W.2.3
Common return, connected to protective earth
N/A
X
ANNEX X, MAXIMUM HEATING EFFECT IN TRANSFORMER TESTS
(see clause C.1)
N/A
X.1
Determination of maximum input current
N/A
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 30 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
X.2
Overload test procedure
N/A
Y
ANNEX Y, ULTRAVIOLET LIGHT CONDITIONING TEST (see 4.3.13.3)
N/A
Y.1
Test apparatus .....................................................:
N/A
Y.2
Mounting of test samples .....................................:
N/A
Y.3
Carbon-arc light-exposure apparatus ..................:
N/A
Y.4
Xenon-arc light exposure apparatus ....................:
N/A
TRF No.:IECEN60950_1B
Result – Remark
Verdict
TRF originator: SGS Fimko
Page 31 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
CENELEC COMMON MODIFICATIONS [C],
SPECIAL NATIONAL CONDITIONS [S] AND A-DEVIATIONS (NATIONAL DEVIATIONS) [A]
(EN 60950-1:2001, Annex ZB and Annex ZC)
General
C: Delete all the "country" notes in the reference
document according to the following list:
1.1.5
Note 2
1.7.2
Note 4
2.2.3
Note
2.3.3
Note 1, 2
2.10.3.1 Note 4
3.2.5.1 Note 2
4.7.3.1 Note 2
6.2.2
Note
7
Note 4
G2.1
Note 1, 2
1.5.8
1.7.12
2.2.4
2.3.4
3.2.1.1
4.3.6
6.1.2.1
6.2.2.1
7.1
Annex H
Note 2
Note 2
Note
Note 2,3
Note
Note 1,2
Note
Note 2
Note
Note 2
1.6.1
2.6
2.3.2
2.7.1
3.2.3
4.7.2.2
6.1.2.2
6.2.2.2
Verdict
P
Deleted.
N/A
Note
Note
Note 2, 7, 8
Note
Note 1, 2
Note
Note
Note
1.2.4.1
S (DK): Certain types of Class I appliances (see
3.2.1.1) may be provided with a plug not
establishing earthing conditions when inserted
into Danish socket-outlets.
Power supply cord is not
provided.
N/A
1.5.1
A (SE, Ordinance 1990:944 and
CH, Ordinance on environmentally hazardous
substances SR 814.013, Annex 3.2, Mercury):
Add NOTE – Switches containing mercury such as
No such switches provided.
N/A
thermostats, relays and level controllers are not allowed.
1.5.8
1.7.2
S (NO): Due to the IT power system used (see
annex V, Fig. V.7), capacitors are required to be
rated for the applicable line-to-line voltage
(230 V).
Considered.
S (FI, NO, SE): CLASS I PLUGGABLE EQUIPMENT
intended for connection to other
equipment or a network shall, if safety relies on
connection to protective earth or if surge
suppressors are connected between the network
terminals and accessible parts, have a marking
stating that the equipment must be connected to
an earthed mains socket-outlet.
To be evaluated when
submitted for national approval.
N/A
FI: "Laite on liitettävä suojamaadoituskoskettimilla To be evaluated when
varustettuun pistorasiaan"
submitted for national approval.
N/A
NO: "Apparatet må tilkoples jordet stikkontakt"
To be evaluated when
submitted for national approval.
N/A
SE: "Apparaten skall anslutas till jordat uttag"
To be evaluated when
submitted for national approval.
N/A
TYPE A
P
The marking text in the applicable countries shall
be as follows:
A (DK, Heavy Current Regulations): Supply cords Power supply cord is not
of class I equipment, which is delivered without a provided.
plug, must be provided with a visible tag with the
following text:
N/A
Vigtigt!
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 32 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
Lederen med grøn/gul isolation må kun tilsluttes
en klemme mærket
eller
If essential for the safety of the equipment, the
tag must in addition be provided with a diagram
which shows the connection of the other
conductors, or be provided with the following text:
"For tilslutning af de øvrige ledere, se
medfølgende instalationsvejledning."
1.7.5
S (DK): Socket-outlets for providing power to
other equipment shall be in accordance with the
Heavy Current Regulations, Section 107-2-D1,
Standard Sheet DK 1-3a, DK 1-5a or DK 1-7a,
when used on Class I equipment. For stationary
equipment the socket-outlet shall be in accordance with Standard Sheet DK 1-1b or DK 1-5a.
1.7.5
A (DK, Heavy Current Regulations):
Class I equipment.
shall not be fitted with socketoutlets for providing power to other equipment.
N/A
A (DE, Gesetz über technische Arbeitsmittel
Shall be evaluated when
(Gerätesicherheitsgesetz) [Law on technical
national approval.
labour equipment {Equipment safety law}], of 23rd
October 1992, Article 3, 3rd paragraph, 2nd
sentence, together with the "Allgemeine
Verwaltungsvorschrift zur Durchführung des
Zweiten Abschnitts des Gerätesicherheitsgesetzes" [General administrative regulation on
the execution of the Second Section of the
Equipment safety law], of 10th January 1996,
article 2, 4th paragraph item 2):
Directions for use with rules to prevent certain
hazards for (among others) maintenance of the
technical labour equipment, also for imported
technical labour equipment shall be written in the
German language.
N/A
No socket-outlets provided.
N/A
CLASS II EQUIPMENT
1.7.12
NOTE: Of this requirement, rules for use even only by service
personnel are not exempted.
1.7.15
A (CH, Ordinance on environmentally hazardous
substances SR 814.013):
Annex 4.10 of SR 814.013 applies for batteries.
No batteries provided.
A (DE, Regulation on protection against hazards This national difference was
by X-ray, of 8th January 1987, Article 5 [Operation deleted by A11 of EN 60950-1.
of X-ray emission source], clauses 1 to 4):
a) A licence is required by those who operate an
X-ray emission source.
b) A licence in accordance with Cl. 1 is not
required by those who operate an X-ray emission
source on which the electron acceleration voltage
does not exceed 20 kV if
1) the local dose rate at a distance of 0,1 m from
TRF No.:IECEN60950_1B
N/A
N/A
TRF originator: SGS Fimko
Page 33 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
the surface does not exceed 1 µSv/h and
2) it is adequately indicated on the X-ray emission
source that
i) X-rays are generated and
ii) the electron acceleration voltage must not
exceed the maximum value stipulated by
the manufacturer or importer.
c) A licence in accordance with Cl. 1 is also not
required by persons who operate an X-ray
emission source on which the electron
acceleration voltage exceeds 20 kV if
1) the X-ray emission source has been granted a
type approval and
2) it is adequately indicated on the X-ray emission
source that
i) X-rays are generated
ii) the device stipulated by the manufacturer or
importer guarantees that the maximum
permissible local dose rate in accordance
with the type approval is not exceeded and
iii) the electron acceleration voltage must not
exceed the maximum value stipulated by the
manufacturer or importer.
d) Furthermore, a licence in accordance with
Cl. 1 is also not required by persons who operate
X-ray emission sources on which the electron
acceleration voltage does not exceed 30 kV if
1) the X-rays are generated only by intrinsically
safe CRTs complying with Enclosure III, No. 6,
2) the values stipulated in accordance with
Enclosure III, No. 6.2 are limited by technical
measures and specified in the device and
3) it is adequately indicated on the X-ray emission
source that the X-rays generated are adequately screened by the intrinsically safe CRT.
2.2.4
S (NO): Requirements according to this annex,
1.7.2 and 6.1.2.1 apply.
No TNV circuits provided.
N/A
2.3.2
S (NO): Requirements according to this annex,
6.1.2.1 apply.
No TNV circuits provided.
N/A
2.3.3 and
2.3.4
S (NO): Requirements according to this annex,
1.7.2 and 6.1.2.1 apply.
No TNV circuits provided.
N/A
2.6.3.3
S (GB): The current rating of the circuit shall be
taken as 13 A, not 16 A.
Considered.
N/A
2.7.1
C: Replace the subclause as follows:
Replaced.
P
Basic requirements
To protect against excessive current, shortcircuits and earth faults in PRIMARY CIRCUITS,
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 34 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
protective devices shall be included either as
integral parts of the equipment or as parts of the
building installation, subject to the following, a), b)
and c):
a) except as detailed in b) and c), protective
devices necessary to comply with the
requirements of 5.3 shall be included as parts of
the equipment;
b) for components in series with the mains input
to the equipment such as the supply cord,
appliance coupler, r.f.i. filter and switch, shortcircuit and earth fault protection may be provided
by protective devices in the building installation;
c) it is permitted for PLUGGABLE EQUIPMENT TYPE B
or PERMANENTLY CONNECTED EQUIPMENT, to rely
on dedicated overcurrent and short-circuit
protection in the building installation, provided
that the means of protection, e.g. fuses or circuit
breakers, is fully specified in the installation
instructions.
If reliance is placed on protection in the building
installation, the installation instructions shall so
state, except that for PLUGGABLE EQUIPMENT TYPE
A the building installation shall be regarded as
providing protection in accordance with the rating
of the wall socket outlet.
S (GB): To protect against excessive currents
The EUT is not direct plug-in
and short-circuits in the PRIMARY CIRCUIT OF
type.
DIRECT PLUG-IN EQUIPMENT, protective device shall
be included as integral parts of the DIRECT PLUGIN EQUIPMENT.
N/A
2.7.2
C: Void.
Void.
N/A
2.10.2
C: Replace in the first line "(see also 1.4.7)" by
"(see also 1.4.8)".
Replaced.
P
2.10.3.1
S (NO): Due to the IT power distribution system
used (see annex V, Fig. V.7), the A.C. MAINS
SUPPLY voltage is considered to be equal to the
line-to-line voltage and will remain at 230 V in
case of a single earth fault
Considered.
P
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 35 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
3.2.1.1
S (CH): Supply cords of equipment having a
not exceeding 10 A shall be
provided with a plug complying with SEV 1011 or
IEC 60884-1 and one of the following dimension
sheets:
Power supply cord is not
provided.
N/A
Power supply cord is not
provided.
N/A
Power supply cord is not
provided.
N/A
RATED CURRENT
Verdict
SEV 6532-2.1991, Plug type 15, 3P+N+PE 250/400 V, 10 A
SEV 6533-2.1991, Plug type 11, L+N
250 V, 10 A
SEV 6534-2.1991, Plug type 12, L+N+PE
250 V, 10 A
In general, EN 60309 applies for plugs for
currents exceeding 10 A. However, a 16 A plug
and socket-outlet system is being introduced in
Switzerland, the plugs of which are according to
the following dimension sheets, published in
February 1998:
SEV 5932-2.1998, Plug type 25, 3L+N+PE 230/400 V, 16 A
SEV 5933-2.1998, Plug type 21, L+N
250 V, 16 A
SEV 5934-2.1998, Plug type 23, L+N+PE
250 V, 16 A
S (DK): Supply cords of single-phase equipment
having a rated current not exceeding 13 A shall
be provided with a plug according to the Heavy
Current Regulations, Section 107-2-D1.
CLASS I EQUIPMENT provided with socket-outlets
with earth contacts or which are intended to be
used in locations where protection against
indirect contact is required according to the wiring
rules shall be provided with a plug in accordance
with standard sheet DK 2-1a or DK 2-5a.
If ply-phase equipment and single-phase
equipment having a RATED CURRENT exceeding
13 A is provided with a supply cord with a plug,
this plug shall be in accordance with the Heavy
Current Regulations, Section 107-2-D1 or
EN 60309-2.
S (ES): Supply cords of single-phase equipment
having a rated current not exceeding 10 A shall
be provided with a plug according to
UNE 20315:1994.
Supply cords of single-phase equipment having a
rated current not exceeding 2,5 A shall be
provided with a plug according to
UNE-EN 50075:1993.
CLASS I EQUIPMENT provided with socket-outlets
with earth contacts or which are intended to be
used in locations where protection against
indirect contact is required according to the wiring
rules, shall be provided with a plug in accordance
with standard UNE 20315:1994.
If poly-phase equipment is provided with a supply
cord with a plug, this plug shall be in accordance
with UNE-EN 60309-2.
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 36 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
S (GB): Apparatus which is fitted with a flexible
cable or cord and is designed to be connected to
a mains socket conforming to BS 1363 by means
of that flexible cable or cord and plug, shall be
fitted with a 'standard plug' in accordance with
Statutory Instrument 1768:1994 – The Plugs and
Socket etc. (Safety) Regulations 1994, unless
exempted by those regulations.
Power supply cord is not
provided.
N/A
S (IE): Apparatus which is fitted with a flexible
cable or cord and is designed to be connected to
a mains socket conforming to I.S. 411 by means
of that flexible cable or cord and plug, shall be
fitted with a 13 A plug in accordance with
Statutory Instrument 525:1997 – National
Standards Authority of Ireland (section 28) (13 A
Plugs and Conversion Adaptors for Domestic
Use) Regulations 1997.
Power supply cord is not
provided.
N/A
3.2.3
C: Delete Note 1 and in Table 3A, delete the
conduit sizes in parentheses.
Deleted.
N/A
3.2.5.1
C: Replace
Replaced.
N/A
NOTE – 'Standard plug' is defined in SI 1768:1994 and
essentially means an approved plug conforming to BS 1363
or an approved conversion plug.
"60245 IEC 53" by "H05 RR-F";
"60227 IEC 52" by "H03 VV-F or H03 VVH2-F";
"60227 IEC 53" by "H05 VV-F or H05 VVH2-F2".
In Table 3B, replace the first four lines by the
following:
Up to and including 6
2)
Over 6 up to and including 10 (0,75)
3)
Over 10 up to and including 16 (1,0)
0,751)
1,0
1,5
In the Conditions applicable to Table 3B delete
1)
the words "in some countries" in condition .
In Note 1, applicable to Table 3B, delete the
second sentence.
3.2.5.1
S (GB): A power supply cord with conductor of
1,25 mm2 is allowed for equipment with a rated
current over 10 A and up to and including 13 A.
Power supply cord is not
provided.
N/A
3.3.4
C: In table 3D, delete the fourth line: conductor
sizes for 10 to 13 A, and replace with the
following:
Deleted.
N/A
"Over 10 up to and including 16
1,5 to 2,5
1,5 to 4"
Delete the fifth line: conductor sizes for 13 to
16 A.
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 37 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
3.3.4
S (GB): The range of conductor sizes of flexible
cords to be accepted by terminals for equipment
with a RATED CURRENT of over 10 A up to and
including 13 A is:
2
2
- 1,25 mm to 1,5 mm nominal cross-sectional
area.
Power supply cord is not
provided.
N/A
4.3.6
S (GB): The torque test is performed using a
socket outlet complying with BS 1363 and the
plug part of DIRECT PLUG-IN EQUIPMENT shall be
assessed to BS 1363: Part 1, 12.1, 12.2, 12.3,
12.9, 12.11, 12.12, 12.16 and 12.17, except that
the test of 12.17 is performed at not less than
125 °C.
The EUT is not direct plug-in
type.
N/A
S (IE): DIRECT PLUG-IN EQUIPMENT is known as
The EUT is not direct plug-in
plug similar devices. Such devices shall comply
type.
with Statutory Instrument 526:1997 – National
Standards Authority of Ireland (Section 28)
(Electrical plugs, plug similar devices and sockets
for domestic use) Regulations, 1997.
N/A
C: Add the following note:
Added.
N/A
No TNV-circuits provided.
N/A
4.3.13.6
Verdict
NOTE Attention is drawn to 1999/519/EC: Council
Recommendation on the limitation of exposure of the general
public to electromagnetic fields 0 Hz to 300 GHz. Standards
taking into account this recommendation are currently under
development.
6.1.2.1
S (FI, NO, SE): Add the following text between
the first and second paragraph:
If this insulation is solid, including insulation
forming part of a component, it shall at least
consist of either
- two layers of thin sheet material, each of which
shall pass the electric strength test below, or
- one layer having a distance through insulation of
at least 0,4 mm, which shall pass the electric
strength test below.
If this insulation forms part of a semiconductor
component (e.g. an optocoupler), there is no
distance through insulation requirement for the
insulation consisting of an insulating compound
completely filling the casing, so that CLEARANCES
AND CREEPAGE DISTANCES do not exist, if the
component passes the electric strength test in
accordance with the compliance clause below
and in addition
- passes the tests and inspection criteria of 2.10.8
with an electric strength test of 1,5 kV multiplied
by 1,6 (the electric strength test of 2.10.7 shall be
performed using 1,5 kV), and
- is subject to ROUTINGE TESTING for electric
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 38 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
strength during manufacturing, using a test
voltage of 1,5 kV.
It is permitted to bridge this insulation with a
capacitor complying with EN 132400:1994,
subclass Y2.
A capacitor classified Y3 according to
EN 132400:1994, may bridge this insulation
under the following conditions:
- the insulation requirements are satisfied by
having a capacitor classified Y3 as defined by
EN 132400, which in addition to the Y3 testing, is
tested with an impulse test of 2,5 kV defined in
EN 60950:2000, 6.2.2.1;
- the additional testing shall be performed on all
the test specimens as described in EN 132400;
- the impulse test of 2,5 kV is to be performed
before the endurance test in EN 132400, in the
sequence of tests as described in EN 132400.
6.1.2.2
S (FI, NO, SE): The exclusions are applicable for
No TNV-circuits provided.
N/A
7.1
S (FI, NO, SE): Requirements according to this
No TNV-circuits provided.
annex, 6.1.2.1 and 6.1.2.2 apply with the term
TELECOMMUNICATION NETWORK in 6.1.2 being
replaced by the term CABLE DISTRIBUTION SYSTEM.
N/A
G.2.1
S (NO): Due to the IT power distribution system
used (see annex V, Fig. V.7), the A.C. MAINS
SUPPLY voltage is considered to be equal to the
line-to-line voltage, and will remain at 230 V in
case of a single earth fault.
Not applied for.
N/A
Annex H
C: Replace the last paragraph of this annex by:
Replaced.
N/A
Replaced.
P
PERMANENTLY CONNECTED EQUIPMENT and
PLUGGABLE EQUIPMENT TYPE B and equipment
intended to be used in a RESTRICTED ACCESS
LOCATION where equipotential bonding has been
applied, e.g. in a telecommunication centre, and
which has provision for a permanently connected
PROTECTIVE EARTHING CONDUCTOR and is provided
with instructions for the installation of that
conductor by a service person.
At any point 10 cm from the surface of the
operator access area, the dose rate shall not
exceed 1 µSv/h (0,1 mR/h) (see note). Account is
taken of the background level.
Replace the notes as follows:
NOTE These values appear in Directive 96/29/Euratom.
Delete Note 2.
Annex P
C: Replace the text of this annex by:
See annex ZA.
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 39 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Annex Q
C: Replace the title of IEC 61032 by "Protection of persons and equipment by
enclosures – Probes for verification".
Verdict
P
Add the following notes for the standards indicated:
IEC 60127
NOTE Harmonized as EN 60127 (Series) (not modified)
IEC 60269-2-1 NOTE Harmonized as HD 630.2.1 S4:2000 (modified)
IEC 60529
NOTE Harmonized as EN 60529:1991 (not modified)
IEC 61032
NOTE Harmonized as EN 61032:1998 (not modified)
IEC 61140
NOTE Harmonized as EN 61140:2001 (not modified)
ITU-T Recommendation K.31
NOTE in Europe, the suggested document is EN 50083-1.
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 40 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Annex ZA
C: NORMATIVE REFERENCES TO INTERNATIONAL PUBLICATIONS WITH
THEIR RELEVANT EUROPEAN PUBLICATIONS
Verdict
P
This European Standard incorporates, by dated or undated reference, provisions
from other publications. These normative references are cited at the appropriate
places in the text and the publications are listed hereafter. For dated references,
subsequent amendments to or revisions of any of these publications apply to this
European Standard only when incorporated in it by amendment or revision. For
undated references, the latest edition of the publication referred to applies
(including amendments).
NOTE When an international publication has been modified by common modifications, indicated by
(mod), the relevant EN/HD applies.


EN 60065:1998 + corr. June 1999
EN 60073:1996
HD 566 S1:1990
HD 214 S2:1980
HD 611.4.1.S1:1992
HD 21 1) Series
HD 22 2) Series
EN 60309 Series
EN 60317-43:1997
EN 60320 Series
HD 384.3 S2:1995
HD 384.4.41 S2:1996
EN 132400:1994 4)
+ A2:1998 + A3:1998 + A4:2001
EN 60417-1
HD 625.1 S1:1996 + corr. Nov. 1996
EN 60695-2-2:1994
EN 60695-2-11:2001




EN 60695-11-10:1999
EN 60695-11-20:1999
EN 60730-1:2000
EN 60825-1:1994 + corr. Febr. 1995 +
A11:1996 + corr. July 1997
EN 60825-2:2000

EN 60851-3:1996
EN 60851-5:1996
EN 60851-6:1996

EN 60990:1999

EN 61965:2001
EN ISO 178:1996
EN ISO 179 Series
EN ISO 180:2000
TRF No.:IECEN60950_1B
IEC 60050-151
IEC 60050-195
IEC 60065 (mod):1998
IEC 60073:1996
IEC 60085:1984
IEC 60112:1979
IEC 60216-4-1:1990
IEC 60227 (mod) Series
IEC 60245 (mod) Series
IEC 60309 Series
IEC 60317-43:1997
IEC 60320 (mod) Series
IEC 60364-3 (mod):1993
IEC 60364-4-41 (mod):1992 3)
IEC 60384-14:1993
IEC 60417-1
IEC 60664-1 (mod):1992
IEC 60695-2-2:1991
IEC 60695-2-11:2000
IEC 60695-2-20:1995
IEC 60695-10-2:1995
IEC 60695-11-3:2000
IEC 60695-11-4:2000
IEC 60695-11-10:1999
IEC 60695-11-20:1999
IEC 60730-1:1999 (mod)
IEC 60825-1:1993
IEC 60825-2:2000
IEC 60825-9:1999
IEC 60851-3:1996
IEC 60825-5:1996
IEC 60851-6:1996
IEC 60885-1:1987
IEC 60990:1999
IEC 61058-1:2000
IEC 61965:2000
ISO 178:1993
ISO 179 Series
ISO 180:1993
TRF originator: SGS Fimko
Page 41 of 72
Report No.:
11008637 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test


EN ISO 527 Series

EN ISO 4892 Series

EN ISO 8256:1996

EN ISO 9773:1998


Result – Remark
Verdict
ISO 261:1998
ISO 262:1998
ISO 527 Series
ISO 386:1984
ISO 4892 Series
ISO 7000:1989
ISO 8256:1990
ISO 9772:1994
ISO 9773:1998
ITU-T:1988 Recommendation K.17
ITU-T:2000 Recommendation K.21
1) The HD 21 series is related to, but not directly equivalent with the IEC 60227 series
2) The HD 22 series is related to, but not directly equivalent with the IEC 60245 series
3) IEC 60364-4-41:1992 is superseded by IEC 60364-4-41:2001
4) EN 132400, Sectional Specification: Fixed capacitors for electromagnetic interference suppression
and connection to the supply mains (Assessment level D), and its amendments are related to, but not
directly equivalent to IEC 60384-14
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 42 of 72
1.5.1
Report No.:
11008637 001
TABLE: list of critical components
Object/part no.
Manufacturer/
trademark
P
Type/model
Technical data
Standard
Mark(s) of
conformity 1.
Switching Power FSP
Supply
(For input 110120 / 220-240V,
8/4.5A,
60/50Hz)
ATX350F
I/P: AC 110120/220-240V,
8/4.5A, 60/50Hz
O/P: DC
20.0A/+3.3V,
20.0A/+5V,
10.0A/+12V1,
13.0A/+12V2,
2.5A/+5Vsb,
0.3A/-12V.
+3.3V &
+5V=130W
max. +12V1 &
+12V2=276W
max. Total
output=350W
max. Class I.
IEC 60950-1:
2001
EN 60950-1:
2001+A11
TÜV, UL, CB
(issued by
Nemko)
(For input 220FSP
240V, 4A, 50Hz)
ATX350F-C
I/P: AC 220240V, 4A, 50Hz
O/P: DC
20.0A/+3.3V,
20.0A/+5V,
10.0A/+12V1,
13.0A/+12V2,
2.5A/+5Vsb,
0.3A/-12V.
+3.3V &
+5V=130W
max. +12V1 &
+12V2=276W
max. Total
output=350W
max. Class I
IEC 60950-1:
2001
EN 60950-1:
2001+A11
TÜV, UL, CB
(issued by
Nemko)
Plastic
Enclosure
--
--
Min. HB
UL 94
UL
Metallic
Enclosure
--
--
Min. 0.8mm
thick
--
--
DC Fan for
system used
(Optional)
AVC
DS09225S12H019
12Vdc, 0.41A
max.,
70.06CFM
EN 60950-1
/A11:2004
IEC 60950-1:
2001
TÜV
CR2032
3 Vdc, 160
mAh, maximum
abnormal
charge current
10 mA.
UL 1642
UL
RTC Battery
Vic-Dawn
(BAT1 for main
board MS-7101,
JBAT1 for main
board MS-7222
and MS-7253)
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 43 of 72
11008637 001
Mitsubishi
CR2032
3.3 Vdc, 200
mAh, maximum
abnormal
charge current
10 mA.
UL 1642
UL
Matsushita
CR2032
3.2 Vdc, 220
mAh, maximum
abnormal
charge current
5mA.
UL 1642
UL
Sony Energy
CR2032
3.3 Vdc, 240
mAh, maximum
abnormal
charge current
10 mA.
UL 1642
UL
Toshiba
CR2032
3.3 Vdc, 220
mAh, maximum
abnormal
charge current
10 mA.
UL 1642
UL
SMD1812P260
TS
SMD1812P260
TF
6 Vdc, 2.6 A.
IEC 60730-1
EN 60730-1
EN 60738-1
TÜV, UL
Raychem
miniSMDC260F- 6 Vdc, 2.6 A.
2
IEC 60730-1
EN 60730-1
TÜV
Littelfuse
1812L260MR
6 Vdc, 2.6 A.
IEC 60730-1
EN 60730-1
EN 144001
EN 144000
TÜV
--
--
V-1 min.
105°C min.
UL 94
UL
Polyswitch (FS3, Polytronics
FS4 for main
Technology
board MS-7101, Corp.
F2, F3 for main
board MS-7222,
FS1, FS2 for
main board MS7253)
PCB
Report No.:
Note(s):
1. An asterisk indicates a mark that assures the agreed level of surveillance.
1.6.2
Fuse #
TABLE: electrical data (in normal conditions)
Irated (A)
U (V)
P (W)
I (A)
P
Ifuse (A)
Condition/status
For model MS-6429 with FSP’s SPS, type ATX350F
F1
--
99V/50Hz
206.9
3.58
3.58
Maximum normal load.
F1
--
99V/60Hz
206.1
3.55
3.55
Maximum normal load.
F1
8
110V/50Hz
204.0
3.27
3.27
Maximum normal load.
F1
8
110V/60Hz
204.1
3.24
3.24
Maximum normal load.
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 44 of 72
Report No.:
11008637 001
F1
8
120V/50Hz
203.8
2.78
2.78
Maximum normal load.
F1
8
120V/60Hz
204.9
2.78
2.78
Maximum normal load.
F1
--
128V/50Hz
204.8
2.65
2.65
Maximum normal load.
F1
--
128V/60Hz
203.8
2.65
2.65
Maximum normal load.
F1
--
132V/50Hz
203.9
2.60
2.60
Maximum normal load.
F1
--
132V/60Hz
204.1
2.60
2.60
Maximum normal load.
F1
--
198V/50Hz
199.9
1.67
1.67
Maximum normal load.
F1
--
198V/60Hz
200.1
1.66
1.66
Maximum normal load.
F1
4.5
220V/50Hz
199.9
1.55
1.55
Maximum normal load.
F1
4.5
220V/60Hz
199.8
1.54
1.54
Maximum normal load.
F1
4.5
240V/50Hz
200.8
1.44
1.44
Maximum normal load.
F1
4.5
240V/60Hz
200.4
1.43
1.43
Maximum normal load.
F1
--
255V/50Hz
200.9
1.39
1.39
Maximum normal load.
F1
--
255V/60Hz
200.8
1.38
1.38
Maximum normal load.
F1
--
264V/50Hz
201.9
1.34
1.34
Maximum normal load.
F1
--
264V/60Hz
201.7
1.34
1.34
Maximum normal load.
For model MS-6434 with FSP’s SPS, type ATX350F
F1
--
99V/50Hz
180.5
3.18
3.18
Maximum normal load.
F1
--
99V/60Hz
181.1
3.17
3.17
Maximum normal load.
F1
8
110V/50Hz
183.0
2.92
2.92
Maximum normal load.
F1
8
110V/60Hz
181.5
2.88
2.88
Maximum normal load.
F1
8
120V/50Hz
178.2
2.47
2.47
Maximum normal load.
F1
8
120V/60Hz
178.2
2.46
2.46
Maximum normal load.
F1
--
128V/50Hz
178.3
2.34
2.34
Maximum normal load.
F1
--
128V/60Hz
178.2
2.33
2.33
Maximum normal load.
F1
--
132V/50Hz
178.0
2.29
2.29
Maximum normal load.
F1
--
132V/60Hz
178.0
2.27
2.27
Maximum normal load.
F1
--
198V/50Hz
176.2
1.49
1.49
Maximum normal load.
F1
--
198V/60Hz
177.1
1.48
1.48
Maximum normal load.
F1
4.5
220V/50Hz
178.0
1.38
1.38
Maximum normal load.
F1
4.5
220V/60Hz
179.0
1.37
1.37
Maximum normal load.
F1
4.5
240V/50Hz
176.8
1.28
1.28
Maximum normal load.
F1
4.5
240V/60Hz
175.8
1.26
1.26
Maximum normal load.
F1
--
255V/50Hz
175.6
1.22
1.22
Maximum normal load.
F1
--
255V/60Hz
176.0
1.21
1.21
Maximum normal load.
F1
--
264V/50Hz
176.9
1.19
1.19
Maximum normal load.
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 45 of 72
F1
--
264V/60Hz
176.2
1.18
Report No.:
11008637 001
1.18
Maximum normal load.
For model MS-6437 with FSP’s SPS, type ATX350F
F1
--
99V/50Hz
101.9
1.85
1.85
Maximum normal load.
F1
--
99V/60Hz
102.1
1.85
1.85
Maximum normal load.
F1
8
110V/50Hz
102.1
1.71
1.71
Maximum normal load.
F1
8
110V/60Hz
102.1
1.70
1.70
Maximum normal load.
F1
8
120V/50Hz
103.8
1.50
1.50
Maximum normal load.
F1
8
120V/60Hz
103.8
1.51
1.51
Maximum normal load.
F1
--
128V/50Hz
104.1
1.44
1.44
Maximum normal load.
F1
--
128V/60Hz
103.8
1.44
1.44
Maximum normal load.
F1
--
132V/50Hz
104.7
1.41
1.41
Maximum normal load.
F1
--
132V/60Hz
105.1
1.41
1.41
Maximum normal load.
F1
--
198V/50Hz
100.8
0.90
0.90
Maximum normal load.
F1
--
198V/60Hz
101.0
0.89
0.89
Maximum normal load.
F1
4.5
220V/50Hz
101.8
0.83
0.83
Maximum normal load.
F1
4.5
220V/60Hz
101.9
0.83
0.83
Maximum normal load.
F1
4.5
240V/50Hz
103.0
0.80
0.80
Maximum normal load.
F1
4.5
240V/60Hz
103.0
0.80
0.80
Maximum normal load.
F1
--
255V/50Hz
103.8
0.76
0.76
Maximum normal load.
F1
--
255V/60Hz
104.3
0.76
0.76
Maximum normal load.
F1
--
264V/50Hz
104.3
0.74
0.74
Maximum normal load.
F1
--
264V/60Hz
104.1
0.74
0.74
Maximum normal load.
For model MS-6429 with FSP’s SPS, type ATX350F-C
F1
--
198V/50Hz
205.58
1.43
1.43
Maximum normal load.
F1
4
220V/50Hz
204.1
1.30
1.30
Maximum normal load.
F1
4
240V/50Hz
204.6
1.20
1.20
Maximum normal load.
F1
--
255V/50Hz
204.4
1.13
1.13
Maximum normal load.
F1
--
264V/50Hz
205.1
1.20
1.20
Maximum normal load.
For model MS-6434 with FSP’s SPS, type ATX350F-C
F1
--
198V/50Hz
176.1
1.23
1.23
Maximum normal load.
F1
4
220V/50Hz
178.8
1.13
1.13
Maximum normal load.
F1
4
240V/50Hz
178.0
1.05
1.05
Maximum normal load.
F1
--
255V/50Hz
176.9
0.98
0.98
Maximum normal load.
F1
--
264V/50Hz
176.3
0.95
0.95
Maximum normal load.
0.70
Maximum normal load.
For model MS-6437 with FSP’s SPS, type ATX350F-C
F1
--
198V/50Hz
TRF No.:IECEN60950_1B
99.7
0.70
TRF originator: SGS Fimko
Page 46 of 72
Report No.:
11008637 001
F1
4
220V/50Hz
92.8
0.59
0.59
Maximum normal load.
F1
4
240V/50Hz
95.7
0.55
0.55
Maximum normal load.
F1
--
255V/50Hz
93.2
0.53
0.53
Maximum normal load.
F1
--
264V/50Hz
94.8
0.51
0.51
Maximum normal load.
Note(s):
2.1.1.5
TABLE: max. V, A, VA test
Voltage (rated)
(V)
N/A
Current (rated)
(A)
Voltage (max.)
(V)
Current (max.)
(A)
VA (max.)
(VA)
Note(s):
2.1.1.7
Condition
TABLE: discharge test
N/A
τ calculated τ measured
(s)
(s)
t u→ 0V
(s)
Comments
Note(s):
2.2.2
TABLE: Hazardous voltage measurement
Transformer
N/A
Location
max. Voltage
V peak
V d.c.
Voltage Limitation
Component
Note(s):
2.2.3
TABLE: SEL voltage measurement
Location
N/A
Voltage measured (V)
Comments
Note(s):
2.4.2
TABLE: limited current circuit measurement
Location
Voltage
(V)
Current
(mA)
N/A
Freq.
(kHz)
Limit
(mA)
Comments
Note(s):
2.5
TABLE: limited power source measurement
TRF No.:IECEN60950_1B
P
TRF originator: SGS Fimko
Page 47 of 72
Limits
Report No.:
Measured
11008637 001
Verdict
For model MS-6429
According to Table 2B (normal condition) for PS/2 port (JKBMS1), Uoc=5.1Vdc
current (in A)
apparent power (in VA)
8
4.1
P
25.5
16.16
P
8
3.8
P
25.5
13.15
P
According to Table 2B (normal condition) for USB port (USB1), Uoc=5.1Vdc
current (in A)
apparent power (in VA)
According to Table 2B (normal condition) for USB port (LAN_USB1), Uoc=5.1Vdc
current (in A)
apparent power (in VA)
8
3.8
P
25.5
12.76
P
8
4.1
P
25.5
13.16
P
8
4.1
P
25.5
13.16
P
According to Table 2B (normal condition) for USB port (USB2), Uoc=5.1Vdc
current (in A)
apparent power (in VA)
According to Table 2B (normal condition) for USB port (USB3), Uoc=5.1Vdc
current (in A)
apparent power (in VA)
For model MS-6434
According to Table 2B (normal condition) for PS/2 port (JKBMS1), Uoc=5.1Vdc
current (in A)
apparent power (in VA)
8
4.1
P
25.5
15.84
P
8
4.3
P
25.5
14.36
P
According to Table 2B (normal condition) for USB port (USB1), Uoc=5.1Vdc
current (in A)
apparent power (in VA)
According to Table 2B (normal condition) for USB port (LAN_USB1), Uoc=5.1Vdc
current (in A)
apparent power (in VA)
8
4.5
P
25.5
14.52
P
8
4.3
P
25.5
13.53
P
8
4.3
P
25.5
13.53
P
According to Table 2B (normal condition) for USB port (JUSB1), Uoc=5.1Vdc
current (in A)
apparent power (in VA)
According to Table 2B (normal condition) for USB port (JUSB2), Uoc=5.1Vdc
current (in A)
apparent power (in VA)
For model MS-6437
According to Table 2B (normal condition) for PS/2 port (JKBMS1), Uoc=5.06Vdc
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 48 of 72
current (in A)
apparent power (in VA)
Report No.:
11008637 001
8
4.3
P
25.3
16.88
P
8
4.4
P
25.35
14.36
P
According to Table 2B (normal condition) for USB port (USB1), Uoc=5.07Vdc
current (in A)
apparent power (in VA)
According to Table 2B (normal condition) for USB port (LAN_USB1), Uoc=5.07Vdc
current (in A)
apparent power (in VA)
8
4.4
P
25.35
14.36
P
8
4.3
P
25.35
13.44
P
8
4.3
P
25.35
13.44
P
According to Table 2B (normal condition) for USB port (JUSB1), Uoc=5.Vdc
current (in A)
apparent power (in VA)
According to Table 2B (normal condition) for USB port (JUSB2), Uoc=5.1Vdc
current (in A)
apparent power (in VA)
Note(s):
2.6.3.4
TABLE: ground continue test
Location
P
Resistance measured (mΩ) Comments
Unit with FSP’s SPS, type ATX350F
Inlet earth pin to metal enclosure
8.9
25A, 1 minute
Inlet earth pin to metal enclosure
10.8
40A, 2 minutes
Inlet earth pin to metal enclosure
9.2
25A, 1 minute
Inlet earth pin to metal enclosure
10.1
40A, 2 minutes
Unit with FSP’s SPS, type ATX350F-C
Note(s):
2.10.2
Table: working voltage measurement
Location
RMS voltage (V)
N/A
Peak voltage (V) Comments
Note(s):
2.10.3 and TABLE: clearance and creepage distance measurements
2.10.4
Clearance cl and creepage
distance dcr at/of:
TRF No.:IECEN60950_1B
Up
(V)
U r.m.s.
(V)
Required
cl (mm)
N/A
cl
(mm)
Required
dcr (mm)
dcr
(mm)
TRF originator: SGS Fimko
Page 49 of 72
Report No.:
11008637 001
Note(s):
2.10.5
TABLE: distance through insulation measurements
Distance through insulation di at/of:
U r.m.s.
(V)
N/A
Test voltage
(V)
Required di
(mm)
di
(mm)
Note(s):
4.5.1
TABLE: maximum temperatures
P
test voltage (V) .............................................: a) 99V

b) 132V
c) 198V
d) 264V
t1 (°C) ..........................................................: --

t2 (°C) ..........................................................: --

Maximum temperature T of part/at:
T (°C)
allowed Tmax (°C)
For model MS-6429 with FSP’s SPS, type ATX350F
Test voltage
a)
b)
--
Pin of AC inlet (SPS)
62.1
62.1
70
CX body (SPS)
63.5
64.1
85
FL1 coil (SPS)
69.4
67.6
105
CX2 body (SPS)
70.1
68.3
85
CY2 body (SPS)
69.0
68.2
85
FL3 coil (SPS)
75.4
70.8
105
PCB under BD1 (SPS)
78.8
74.3
105
C2 body (SPS)
65.2
64.5
85
Heatsink near Q1 (SPS)
69.9
70.7
--
T1 coil (SPS)
79.0
78.0
110
T2 coil (SPS)
67.2
67.0
110
T3 coil (SPS)
67.3
67.8
110
U3 body (SPS)
71.3
72.1
100
L9 coil (SPS)
82.2
84.6
105
Heatsink near BD5 (SPS)
80.3
81.1
--
L1 coil (SPS)
75.5
81.6
105
L6 coil (SPS)
84.3
88.2
105
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 50 of 72
Report No.:
11008637 001
L5 coil (SPS)
77.5
78.4
105
PCB under U1
73.5
74.0
105
PCB under U9
69.6
70.1
105
PCB under U13
68.8
69.2
105
PCB under BIOS1
66.0
66.5
105
BAT1 body
63.8
64.3
--
HDD body
59.0
59.5
--
ODD body
57.2
57.7
--
Outside metal enclosure near SPS
53.3
53.8
70
Outside plastic enclosure near ODD
42.3
42.8
95
Tamb
25.9
25.3
--
Tma
40.0
40.0
--
c)
d)
--
Pin of AC inlet (SPS)
60.6
60.4
70
CX body (SPS)
63.3
63.6
85
FL1 coil (SPS)
65.2
65.2
105
CX2 body (SPS)
66.3
65.9
85
CY2 body (SPS)
66.8
66.5
85
FL3 coil (SPS)
67.3
66.4
105
PCB under BD1 (SPS)
73.3
71.3
105
C2 body (SPS)
63.3
62.9
85
Heatsink near Q1 (SPS)
69.3
70.1
--
T1 coil (SPS)
78.9
77.9
110
T2 coil (SPS)
66.8
66.7
110
T3 coil (SPS)
67.3
67.5
110
U3 body (SPS)
71.1
71.2
100
L9 coil (SPS)
82.9
84.0
105
Heatsink near BD5 (SPS)
80.5
80.5
--
L1 coil (SPS)
77.5
81.2
105
L6 coil (SPS)
85.5
87.5
105
L5 coil (SPS)
77.6
77.5
105
PCB under U1
73.7
73.7
105
PCB under U9
69.7
70.0
105
PCB under U13
69.0
69.1
105
PCB under BIOS1
66.3
66.4
105
BAT1 body
64.0
64.1
--
Test voltage
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 51 of 72
Report No.:
11008637 001
HDD body
58.6
59.1
--
ODD body
56.9
57.5
--
Outside metal enclosure near SPS
55.9
55.6
70
Outside plastic enclosure near ODD
42.6
42.5
95
Tamb
25.4
25.5
--
Tma
40.0
40.0
--
c)
d)
--
Pin of AC inlet (SPS)
62.2
61.4
70
CX body (SPS)
64.3
63.8
85
FL1 coil (SPS)
67.3
66.1
105
CX2 body (SPS)
68.4
66.6
85
CY2 body (SPS)
67.0
65.9
85
FL3 coil (SPS)
72.8
69.3
105
PCB under BD1 (SPS)
73.6
70.4
105
C2 body (SPS)
62.0
61.1
85
Heatsink near Q1 (SPS)
72.4
72.3
--
T1 coil (SPS)
67.8
67.1
110
T2 coil (SPS)
66.0
66.0
110
T3 coil (SPS)
73.9
70.2
110
U3 body (SPS)
71.9
71.5
100
L9 coil (SPS)
82.0
82.9
105
Heatsink near BD5 (SPS)
83.8
83.3
--
L1 coil (SPS)
76.3
79.4
105
L6 coil (SPS)
88.9
91.2
105
L5 coil (SPS)
79.1
79.3
105
PFC choke coil (SPS)
62.1
62.1
105
PCB under U1
77.7
77.6
105
PCB under U9
70.3
70.2
105
PCB under U13
68.5
68.5
105
PCB under BIOS1
66.4
66.4
105
BAT1 body
62.4
62.6
--
HDD body
60.6
60.4
--
ODD body
57.6
57.8
--
Outside metal enclosure near SPS
60.9
60.8
70
Outside plastic enclosure near ODD
43.0
43.0
95
For model MS-6429 with FSP’s SPS, type ATX350F-C
Test voltage
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 52 of 72
Report No.:
11008637 001
Tamb
25.4
25.5
--
Tma
40.0
40.0
--
Temperature T of winding:
R1
(Ω)
R2
(Ω)
T
(°C)
allowed
Tmax (°C)
insulation
class
Note(s):
1) The temperatures were measured under worst normal mode defined in 1.2.2.1 and as described in subclause 1.6.2 and at voltages as described above.
2) All values for T(°C) are re-calculated from Tamb respectively.
3) The maximum ambient temperatures specified by manufacturer is 40°C.
Class B → Tmax = 120°C – 10°C = 110°C
4) System Fan was not provided.
4.5.2
TABLE: ball pressure test of thermoplastic parts
N/A
allowed impression diameter (mm) .................. : ≤ 2 mm
Part

Test temperature
(°C)
Impression diameter
(mm)
Note(s):
4.6.1, 4.6.2 Table: enclosure openings
Location
Top
Left side
Right side
Rear
P
Size (mm)
Comments
-- No openings.
Max. 29.8 x 2.7 30 rectangle openings and no hazardous
parts within 5o projection area.
-- No openings.
Max. 8.0 Numerous hexagon openings and cover by
system fan.
Max. 47.0 x 6.0 Numerous openings and cover by DC fan of
SPS.
Bottom
Front side
Ø9.0 Numerous semicircle openings and above the
openings no components, therefore not likely
that material emits and ignites the supporting
surface.
Ø11.6 Numerous circle openings and no hazardous
parts within 5o projection area.
Ø6.0 Numerous circle openings and no hazardous
parts within 5o projection area.
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 53 of 72
Report No.:
11008637 001
Ø4.9 Numerous circle openings and no hazardous
parts within 5o projection area.
Ø3.2 Numerous circle openings and no hazardous
parts within 5o projection area.
Ø2.3 Numerous circle openings and no hazardous
parts within 5o projection area.
Max. 18.9 x 3.8 One rectangle opening and no hazardous
parts within 5o projection area.
Max. 15.7 x 10.9 Three rectangle opening and no hazardous
parts within 5o projection area.
Max. 9.5 x 9.0 Three rectangle opening and no hazardous
o
parts within 5 projection area.
Max. 17.9 x 4.3 Two rectangle opening and no hazardous
parts within 5o projection area.
Max. 15.0 x 4.8 Numerous rectangle opening and no
hazardous parts within 5o projection area.
Max. 7.9 x 1.4 Two rectangle opening and no hazardous
parts within 5o projection area.
Note(s):
4.7
Part
Table: resistance to fire
P
Manufacturer of material
Type of material
Thickness
(mm)
Flammability
class
--
Metal
0.8
--
Metal
enclosure
Note(s):
5.1.6
Condition
TABLE: touch current measurement
L→ terminal A N → terminal A
(mA)
(mA)
P
Limit
(mA)
Comments
Unit with FSP’s SPS, type ATX350F
System ON
0.8
0.8
3.5
To SELV output earthed part with
switch “e” open.
System ON
0.8
0.8
3.5
To metal enclosure with switch “e”
open
System ON
0.01
0.01
0.25
To accessible surface of plastic
enclosure with metal foil with switch
“e” close.
0.8
3.5
To SELV output earthed part with
switch “e” open.
Unit with FSP’s SPS, type ATX350F-C
System ON
TRF No.:IECEN60950_1B
0.8
TRF originator: SGS Fimko
Page 54 of 72
Report No.:
11008637 001
System ON
0.8
0.8
3.5
To metal enclosure with switch “e”
open
System ON
0.01
0.01
0.25
To accessible surface of plastic
enclosure with metal foil with switch
“e” close.
Note(s):
5.2
TABLE: electric strength tests and impulse tests
Test voltage applied between:
P
Test voltage (V)
Breakdown
Primary to SELV
DC 4242
No
Primary to plastic enclosure
DC 4242
No
Primary to metal enclosure
DC 2461
No
Note(s):
5.3
No.
TABLE: fault condition tests
P
ambient temperature (°C) ...................................... : 25 °C, if not otherwise stated

model/type of power supply ................................... : See table 1.5.1

manufacturer of power supply ............................... : See table 1.5.1

rated markings of power supply ............................. : See table 1.5.1

Component no.
Fault
Test
voltage (V)
Test
time
Fuse
no.
Fuse
Result
current (A)
For model MS-6429 with FSP’s SPS, type ATX350F
1
Ventilation
openings
Blocked
240
1h
F1
0.13
Unit shut down, no hazard.
The maximum temperature:
T1 of SPS=102.4°C,
T2 of SPS=89.6°C,
T3 of SPS=85.3°C,
PCB under U1=83.5°C,
Tamb=25.4°C.
2
CPU Fan
Locked
240
45 min
F1
0.13
Unit shut down, no hazard.
The maximum temperature:
T1 of SPS=48.9°C,
T2 of SPS=44.6°C,
T3 of SPS=46.1°C,
PCB under U1=64.9°C
Tamb=25.5°C.
For model MS-6429 with FSP’s SPS, type ATX350F-C
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 55 of 72
Report No.:
11008637 001
3
Ventilation
openings
Blocked
240
1h
F1
0.13
Unit shut down, no hazard.
The maximum temperature:
T1 of SPS=82.4°C,
T2 of SPS=81.7°C,
T3 of SPS=78.6°C,
PCB under U1=85.0°C,
Tamb=25.4°C.
4
CPU Fan
Locked
240
45 min
F1
0.13
Unit shut down, no hazard.
The maximum temperature:
T1 of SPS=48.0°C,
T2 of SPS=49.0°C,
T3 of SPS=49.7°C,
PCB under U1=79.5°C
Tamb=25.5°C.
5
RTC battery
+ to -
s-c
--
--
--
--
No hazards.
For main board MS-7101
6
D6 pin 2-1 (RTC
battery circuit)
s-c
--
--
--
--
Reverse current of RTC
battery=3.27mA, no hazards.
7
D6 pin 3-1 (RTC
battery circuit)
s-c
--
--
--
--
Reverse current of RTC
battery=3.03mA, no hazards.
For main board MS-7222
8
D5 pin 1-2 (RTC
battery circuit)
s-c
--
--
--
--
Reverse current of RTC
battery=3.29mA, no hazards.
9
D5 pin 3-2 (RTC
battery circuit)
s-c
--
--
--
--
Reverse current of RTC
battery=3.04mA, no hazards.
10
R257 (RTC
battery circuit)
s-c
--
--
--
--
Reverse current of RTC
battery=0.01mA, no hazards.
For main board MS-7253
11
D10 pin 1-2
(RTC battery
circuit)
s-c
--
--
--
--
Reverse current of RTC
battery=1.62mA, no hazards.
12
D10 pin 3-2
(RTC battery
circuit)
s-c
--
--
--
--
Reverse current of RTC
battery=1.47mA, no hazards.
Note(s): In fault column, s-c=short-circuited
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 56 of 72
Report No.:
11008637 001
National Differences
Clause
Result – Remark
Requirement − Test
APPENDIX Australian National Differences according to CB Bulletin No. 110A, June 2006
(AS/NZS 60950.1:2003)
Verdict
P
(IEC Publication 60950-1:2001)
EXPLANATION FOR ABBREVIATIONS
P=Pass, F=Fail, N/A=Not applicable. Placed in the column to the right.
Annex ZZ Variations
1.2
Between the definitions for "Person, service" and
"Range, rated frequency" insert the following:
Potential ignition source
1.2.12.15
Inserted.
N/A
1.2.12.201
After the definition of 1.2.12.15, add the following: Added.
N/A
1.2.12.201 Potential ignition source:
Possible fault which can start a fire if the opencircuit voltage measured across an interruption or
faulty contact exceeds a value of 50 V (peak) a.c.
or d.c. and the product of the peak value of this
voltage and the measured r.m.s. current under
normal operating conditions exceeds 15 VA.
Such a faulty contact or interruption in an
electrical connection includes those which may
occur in conductive patterns on printed boards.
NOTE 201: An electronic protection circuit may be
used to prevent such a fault from becoming a
potential ignition source.
NOTE 202: This definition is from AS/NZS
60065:2003.
1.5.1
Add the following to the end of first paragraph:
Added.
N/A
Add the following to the end of first and third dash Added.
items:
N/A
"or the relevant Australian/New Zealand
Standard."
1.5.2
"or the relevant Australian/New Zealand
Standard."
2.1
Delete the Note.
Deleted.
N/A
3.2.3
Delete Note 2.
Deleted.
N/A
3.2.5
Modify Table 3B as follows:
Replaced.
N/A
Rated current of
equipment A
Over 0.2 up to
and including 3
Nominal
crosssectional
area mm2
AWG or kcmil
(cross-sectional
area in mm2)
see note 2
0.51)
18 [0.8]
Australian National Differences according to CB Bulletin No. 110A, June 2006
Page 57 of 72
Report No.:
11008637 001
National Differences
Clause
Result – Remark
Requirement − Test
Over 3 up to and
including 7.5
0.75
16 [1.3]
Over 7.5 up to
and including 10
(0.75)2) 1.00
16 [1.3]
Over 10 up to
and including 16
(1.0)3) 1.5
14 [2]
Verdict
Replace footnote 1) with the following:
1)
This nominal cross-sectional area is only
allowed for Class II appliances if the length of the
power supply cord, measured between the point
where the cord, or cord guard, enters the
appliances, and the entry to the plug does not
exceed 2 m (0.5 mm² three-core supply flexible
cords are not permitted; see AS/NZS 3191).
Delete Note 1.
4.3.6
Replace paragraph three with:
Replaced.
N/A
Equipment with a plug portion, suitable for
insertion into a 10 A 3-pin flat-pin socket-outlet
complying with AS/NZS 3112, shall comply with
the requirements in AS/NZS 3112 for equipment
with integral pins for insertion into socket-outlets.
4.3.13.5
Add the following to the end of the first paragraph: Added.
N/A
", or AS/NZS 2211.1"
4.7
Add the following paragraph:
Added.
N/A
Add the following after clause 4.7.3.6:
Added.
N/A
4.7.201 Resistance to fire - Alternative tests
However, equipment under
test and materials used in
compliance with requirements
of IEC 60950-1. Alternative
test methods were not
considered.
General
Same as above.
For alternative tests refer to clause 4.7.201.
4.7.201
4.7.201.1
Parts of non-metallic material shall be resistant to
ignition and spread of fire.
This requirement does not apply to decorative
trims, knobs and other parts unlikely to be ignited
or to propagate flames originating from inside the
apparatus, or the following:
(a) Components that are contained in an
enclosure having a flammability category of
FV-0 according to AS/NSZ 4695.707 and
having openings only for the connecting wires
filling the openings completely, and for the
Australian National Differences according to CB Bulletin No. 110A, June 2006
N/A
Page 58 of 72
Report No.:
11008637 001
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
Same as above.
N/A
Same as above.
N/A
ventilation not exceeding 1 mm in width
regardless of the length.
(b) The following parts which would contribute
negligible fuel to a fire:
-
small mechanical parts, the mass of which
does not exceed 4 g, such as mounting
parts, gears, cams, belts and bearings;
-
small electrical components, such as
capacitors with a volume not exceeding
1750 mm3, integrated circuits, transistors and
optocoupler packages, if these components
are mounted on material flammability
category FV-1 or better according to AS/NZS
4695.707
NOTE - In considering how to minimize
propagation of fire and what “small parts” are,
account should be taken of the cumulative effect
of small parts adjacent to each other for the
possible effect of propagating fire from one part to
another.
Compliance is checked by tests of 4.7.201.2,
4.7.201.3, 4.7.201.4 and 4.7.201.5.
For the base materials of printed boards,
compliance is checked by the test of 4.7.201.5.
The tests shall be carried out on parts of nonmetallic material, which have been removed from
the apparatus. When the glow-wire test is carried
out, the parts shall be placed in the same
orientation, as they would be in normal use.
These tests are not carried out on internal wiring.
4.7.201.2
Parts of non-metallic material are subjected to
glow wire test of AS/NZS 4695.2.11, which is
carried out at 550 °C.
Parts for which the glow-wire test cannot be
carried out, such as those made of soft or foamy
material, shall meet the requirements specified in
ISO 9772 for category FH-3 material. The glowwire test shall be not carried out on parts of
materials classified at least FH-3 according to
ISO 9772 provided that the sample was not
thicker than the relevant part.
4.7.201.3
Testing of insulating materials
Parts of insulating materials supporting potential
ignition sources shall be subject to the glow-wire
test of AN/NZS 4695.2.11, which is carried out at
750 °C.
The test shall be also carried out on other parts of
Australian National Differences according to CB Bulletin No. 110A, June 2006
Page 59 of 72
Report No.:
11008637 001
National Differences
Clause
Requirement − Test
Result – Remark
insulating material which are within a distance of
3 mm of the connection.
NOTE - Contacts in components such as switch
contacts are considered to be connections.
For parts, which withstand the glow-wire test but
produce a flame, other parts above the
connection within the envelope of a vertical
cylinder having a diameter of 20 mm and a height
of 50 mm shall be subjected to the needle-flame
test. However, parts shielded by a barrier which
meets the needle-flame test shall not be tested.
The needle-flame test shall be made in
accordance with AS/NZS 4695.2.2 with the
following modifications:
5 Severities
Replace with:
The duration of application of the test flame shall
be 30 s ± 1 s.
8 Test procedure
8.2 Modification:
Replace the first sentence with:
The specimen shall be arranged so that the flame
can be applied to a vertical or horizontal edge as
shown in the examples of figure 1.
8.4 Modification:
The first paragraph does not apply.
Addition:
If possible, the flame shall be applied at least
10 mm from a corner.
8.5 Replacement:
The test shall be made on one specimen. If the
specimen does not withstand the test, the test
may be repeated on two further specimens, both
of which shall then withstand the test.
10 Evaluation of test results
Replace with:
The duration of burning (tb) shall not exceed 30 s.
However, for printed circuit boards, it shall not
exceed 15 s.
The needle-flame test shall not be carried out on
parts of material classified as V-0 or V-1
Australian National Differences according to CB Bulletin No. 110A, June 2006
Verdict
Page 60 of 72
Report No.:
11008637 001
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
according to IEC 60695-11-10, provided that the
sample tested was not thicker than the relevant
part.
4.7.201.4
Testing in the event of non-extinguishing material Same as above.
N/A
If parts, other than enclosures, do not withstand
the glow-wire tests of 4.7.201.3, by failure to
extinguish within 30 s after the removal of the
glow-wire tip, the needle-flame test detailed in
4.7.201.3 is made on all parts of non-metallic
material which are within a distance of 50 mm or
which are likely to be impinged upon by flame
during the tests of 4.7.201.3. Parts shielded by a
separate barrier which meets the needle-flame
test need not to be tested.
NOTE 1 - If the enclosure does not withstand the
glow-wire test the equipment is considered to
have failed to meet the requirement of clause
4.7.201 without the need for consequential
testing.
NOTE 2 - If other parts do not withstand the glowwire test due to ignition of the tissue paper and if
this indicates that burring or glowing particles can
fall onto an external surface underneath the
equipment, the equipment is considered to have
failed to meet the requirement of clause 4.7.201
without the need for consequential testing.
NOTE 3 - Parts likely to be impinged upon by the
flame are considered to be those within the
envelope of a vertical cylinder having a radius of
10 mm and a height equal to the height of the
flame, positioned above the point of the material
supporting in contact with or in close proximity to
connections.
4.7.201.5
Testing of printed boards
Same as above.
The base material of printed boards is subjected
to needle-flame test to Clause 4.7.201.3. The
flame is applied to the edge of the board where
the heat sink effect is lowest when the board is
positioned as in normal use. The flame shall not
be applied to an edge, consisting of broken
perforations, unless the edge is less than 3 mm
for a potential ignition source.
The test is not carried out if the –
- Printed board does not carry any potential
ignition source;
- Base material of printed boards, on which the
available apparent power at a connection
exceeds 15 VA operating at a voltage
exceeding 50 V and equal or less than 400 V
Australian National Differences according to CB Bulletin No. 110A, June 2006
N/A
Page 61 of 72
Report No.:
11008637 001
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
(peak) a.c. or d.c. under normal operating
conditions, is of flammability category FV-1 or
better according to AS/NZS 4695.707, or the
printed boards are protected by an enclosure
meeting the flammability category FV-0
according to AS/NZS 4695.707, or made of
metal, having openings only for connecting
wires which fill the opening completely, or
- Base material of printed boards, on which the
available apparatus power at a connection
exceeds 15 VA operating at a voltage
exceeding 400 V (peak) a.c. or d.c. under
normal operating conditions, and base material
printed boards supporting spark gaps which
provide protection against overvoltages, is of
flammability category FV-0 according to
AS/NSZ 4695.707 or the printed boards are
contained in a metal enclosure, having
openings only for connecting wires fill the
openings completely.
Compliance is determined using the smallest
thickness of the material.
NOTE - Available apparent power is the
maximum apparent power, which can be drawn
from the supplying circuit through a resistive load
whose value is chosen to maximise the apparent
power for more than 2 min when the circuit
supplied is disconnected.
6.2.2
Add the following after the first paragraph:
No TNV.
N/A
No TNV.
N/A
In Australia (this variation does not apply in New
Zealand), compliance with 6.2.2 is checked by the
tests of both 6.2.2.1 and 6.2.2.2.
Delete the note.
6.2.2.1
Delete Note 2.
Add the following after the first paragraph:
In Australia (this variation does not apply in New
Zealand), the electrical separation is subjected to
10 impulses of alternating polarity, using the
impulse test generator of annex N for 10/700 µs
impulses. The interval between successive
impulses is 60 s and the initial voltage, Uc, is:
- for 6.2.1 a):
7.0 kV for hand-held telephones and for
headsets and 2.5 kV for other equipment; and
- for 6.2.1b) and 6.2.1c):
1.5 kV.
Australian National Differences according to CB Bulletin No. 110A, June 2006
Page 62 of 72
Report No.:
11008637 001
National Differences
Clause
Result – Remark
Requirement − Test
Verdict
NOTE 201 - The 7 kV impulse simulates lightning
surges on typical rural and semi-rural network
lines.
NOTE 202 – The 2.5 kV impulse for 6.2.1a) was
chosen to ensure adequacy of the insulation
concerned and does not necessarily simulate
likely overvoltages.
6.2.2.2
Delete the note.
No TNV.
N/A
Add the following after the second paragraph:
In Australia (this variation does not apply in New
Zealand), the a.c. test voltage is:
- for 6.2.1a):
3 kV; and
- for 6.2.1b) and 6.2.1c):
1.5 kV.
NOTE 201 – Where there are capacitors across
the insulation under test, it is recommended that
d.c. test voltages are used.
NOTE 202 – The 3 kV and 1.5 kV values have
been determined considering the low frequency
induced voltages from the power supply
distribution system.
Annex P
Add the following Normative References to Annex Added.
P:
IEC 60065, Audio, Video and similar electronic
apparatus - Safety requirements
AS/NZS 3112, Approval and test specification Plugs and socket-outlets
AS/NZS 3191, Approval and test specification Electric flexible cords
AS/NZS 4695.707, Fire hazard testing of
electrotechnical products - Methods of test for the
determination of the flammability of solid electrical
insulating materials when exposed to an igniting
source
Australian National Differences according to CB Bulletin No. 110A, June 2006
N/A
Page 63 of 72
Report No.:
11008637 001
National Differences
Clause
Result – Remark
Requirement − Test
APPENDIX Canadian National Differences according to CB Bulletin No. 110A, June 2006
(CAN/CSA C22.2 No. 60950-1/UL60950-1)
Verdict
P
(IEC Publication 60950-1:2001)
EXPLANATION FOR ABBREVIATIONS
P=Pass, F=Fail, N/A=Not applicable. Placed in the column to the right.
Special National Conditions
1.1.1
All equipment is to be designed to allow
installations in accordance with the National
Electrical Code (NEC), ANSI/NFPA 70,the
Canadian Electrical Code (CEC), Part I,
CAN/CSA C22.1, and when applicable, the
National Electrical Safety Code, IEEE C2. Also,
unless marked or otherwise identified, installation
is allowed per the Standard for the Protection of
Electronic Computer/Data-Processing Equipment,
ANSI/NFPA 75.
Unit was evaluated according
to IEC 60950-1. The
requirements have to be
checked during national
approval.
N/A
1.4.14
For Pluggable Equipment Type A, the protection
in the installation is assumed to be 20A.
No power cord provided.
N/A
1.5.5
For lengths exceeding 3.05 m, external
interconnecting flexible cord and cable
assemblies are required to be a suitable cable
type (e.g. DP, CL2) specified in the NEC.
Same as above.
N/A
Same as above.
N/A
For lengths 3.05 m or less, external
interconnecting flexible cord and cable
assemblies that are not types specified in the
NEC are required to have special construction
features and identification markings.
1.7.1
Equipment for use on a.c. mains supply systems
with a neutral and more than one phase
conductor (e.g. 120/240 V, 3-wire) require a
special marking format for electrical ratings.
A voltage rating that exceeds an attachment plug
cap rating is only permitted if it does not exceed
the extreme operating conditions in Table 2 of
CAN/CSA C22.2 No. 235, and if it is part of a
range that extends into the Table 2 “Normal
Operating Conditions.” Likewise, a voltage rating
shall not be lower than the specified “Normal
Operating Conditions,” unless it is part of a range
that extends into the “Normal Operating
Conditions.”
2.5
Where a fuse is used to provide Class 2, Limited No such fuse.
Power Source, or TNV current limiting, it shall not
be operator-accessible unless it is not
interchangeable.
Canadian National Differences according to CB Bulletin No. 110A, June 2006
N/A
Page 64 of 72
Report No.:
11008637 001
National Differences
Clause
Requirement − Test
Result – Remark
2.7.1
Suitable NEC/CEC branch circuit protection rated No such components
at the maximum circuit rating is required for all
provided.
standard supply outlets, receptacles and mediumbase or smaller lampholders if the supply branch
circuit protection is not suitable.
Verdict
N/A
Power distribution transformers distributing power
at 100 volts or more, and rated 10 kVA or more,
require transformer overcurrent protection.
3.2
Wiring methods (terminals, leads, etc.) used for
the connection of the equipment to the mains
shall be in accordance with the NEC/CEC.
Appliance inlet used.
N/A
3.2.1
Power supply cords are required to have
attachment plugs rated not less than 125 percent
of the rated current of the equipment.
No such cords provided.
N/A
3.2.3
Permanent connection of equipment to the mains Pluggable equipment.
supply by a power supply cord is not permitted,
except for certain equipment, such as ATMs.
N/A
3.2.5
Power supply cords are required to be no longer
than 4.5 m in length.
No such cords provided.
N/A
Pluggable equipment.
N/A
Flexible power supply cords are required to be
compatible with Article 400 of the NEC, and
Tables 11 and 12 of the CEC.
3.2.9
Permanently connected equipment is required to
have a suitable wiring compartment and wire
bending space.
3.3
Wiring terminals and associated spacings for field Appliance inlet used.
wiring connections shall comply with CSA C22.2
No. 0.
N/A
3.3.3
Wire binding screws are not permitted to attach
conductors larger than 10 AWG (5.3 mm²).
Appliance inlet used.
N/A
3.3.4
Terminals for permanent wiring, including
Appliance inlet used.
protective earthing terminals, are required to be
suitable for U.S./Canadian wire gauge sizes, rated
125 percent of the equipment rating, and be
specially marked when specified (1.7.7).
N/A
3.4.2
Motor control devices are required for cordEquipment is not such a
connected equipment with a motor if the
device.
equipment is rated more than 12A, or if the motor
has a nominal voltage rating greater than 120V,
or is rated more than 1/3 hp (locked rotor current
over 43 A)
N/A
3.4.8
Vertically-mounted disconnect switches and
No such devices incorporated.
circuit breakers are required to have the ”on”
position indicated by the handle in the up position.
N/A
Canadian National Differences according to CB Bulletin No. 110A, June 2006
Page 65 of 72
Report No.:
11008637 001
National Differences
Clause
Requirement − Test
Result – Remark
3.4.11
For computer room applications, equipment with
battery systems capable of supplying 750 VA for
five minutes are required to have a battery
disconnect means that may be connected to the
computer room remote power-off circuit.
Not such an application.
N/A
4.3.12
The maximum quantify of flammable liquid stored No liquids incorporated.
in equipment is required to comply with NFPA 30.
N/A
4.3.13
Equipment with lasers is required to meet Code of Not such an application.
Federal Regulations 21 CFR 1040 (and the
Canadian Radiation Emitting Devices Act, REDR
C1370).
N/A
4.7
For computer room applications, automated
Not such an application.
information storage systems with combustible
media greater than 27 cubic feet are required to
have a provision for connection of either
automatic sprinklers or a gaseous agent
extinguishing system with an extended discharge.
N/A
4.7.3.1
For computer room applications, enclosures with Not such an application.
combustible material measuring greater than 0.9
m² or a single dimension greater than 1.8 m are
required to have a flame spread rating of 50 or
less. For other applications, enclosures with the
same dimensions require a flame spread rating of
200 or less.
N/A
Annex H
Equipment that produces ionizing radiation is
required to comply with the Code of Federal
Regulations, 21 CFR 1020 (and the Canadian
Radiation Emitting Devices Act, REDR C1370).
N/A
No ionizing radiation.
Verdict
Other differences
1.5.1
Components of equipment must be suitable for
the application, and must comply with the
requirements of the equipment standard and the
applicable national (Canadian and/or U.S.)
component or material standards, as far as they
may apply.
Components are approved,
see component list 1.5.1.
The acceptance will be based on the following:
A) A component Certified by a Canadian or U.S.
National Certification Body (NCB) to a
Canadian or U.S. component standard will be
checked for correct application and use in
accordance with its specified rating. Where
necessary, it will also be subject to the
applicable tests of the equipment standard.
B) A component, which has a CB Test
Certificate for compliance with a relevant IEC
component standard, will be checked for
correct application and use in accordance
with its specified ratings. Where necessary, it
Canadian National Differences according to CB Bulletin No. 110A, June 2006
P
Page 66 of 72
Report No.:
11008637 001
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
will also be subject to the applicable tests of
the equipment standard, and to the applicable
tests of the Canadian and/or U.S. component
or material standard, under the conditions
occurring in the equipment.
C) A component, which has no approval as in A)
or B) above or which is used not in
accordance with its specified ratings, will be
subject to the applicable tests of the
equipment standard, and to the applicable
tests of the Canadian and/or U.S. component
or material standard, under the conditions
occurring in the equipment.
D) Some components may require annual retesting, which may be carried out by the
manufacturer, CSA International or another
laboratory
2.3.1
For TNV-2 and TNV-3 circuits with other than
No TNV circuits.
ringing signals and with voltages exceeding
42.4 Vpeak or 60 Vd.c., the maximum acceptable
current through a 2000 ohm resistor (or greater)
connected across the voltage source with other
loads disconnected is 7.1 mA peak or 30 mAd.c.
under normal operating conditions.
N/A
2.3.2
In the event of a single fault, the limits of 2.2.3
No TNV circuits.
apply to SELV Circuits and accessible conductive
parts.
N/A
2.6.3.3
When subject to impedance testing, protective
Refer to the relevant subearthing and bonding are required to be subjected clause on the IEC 60950-1
to the additional test conditions specified.
report.
3.2.1.2
Equipment connected to a centralized d.c. power Not supplied from DC mains.
system, and having one pole of the DC mains
input terminal connected to the main protective
earthing terminal in the equipment, is required to
comply with special earthing, writing, marking and
installation instruction requirements.
N/A
4.2.8.1
Enclosures around CRTs with a face diameter of No CRT.
160mm or more are required to reduce the risk of
injury due to the implosion of the CRT.
N/A
4.3.2
Equipment with handles is required to comply with No handles.
special loading tests.
N/A
5.1.8.3
Equipment intended to receive telecommunication No TNV.
ringing signals is required to comply with a special
touch current measurement tests.
N/A
6.2.1
Enamel coating on winding wire not considered
electrical separation unless subjected to special
investigation.
N/A
No TNV.
Canadian National Differences according to CB Bulletin No. 110A, June 2006
P
Page 67 of 72
Report No.:
11008637 001
National Differences
Clause
Requirement − Test
Result – Remark
6.4
Equipment intended for connection to
No TNV circuits.
telecommunication network outside plant cable is
required to be protected against overvoltage from
power line crosses in accordance with 6.4 and
Annex NAC.
N/A
6.5
Equipment connected to a telecommunications
network and supplied with an earphone intended
to be held against, or in the ear is required to
comply with special acoustic pressure tests.
No TNV circuits.
N/A
M.2
Continuous ringing signals up to 16 mA only are
permitted if the equipment is subjected to special
installation and performance restrictions.
No TNV circuits.
N/A
Canadian National Differences according to CB Bulletin No. 110A, June 2006
Verdict
Page 68 of 72
Report No.:
11008637 001
National Differences
Clause
Requirement − Test
Result – Remark
APPENDIX Korean National Differences according to CB Bulletin No. 110A, June 2006
(K60950)
Verdict
P
(IEC Publication 60950-1:2001)
EXPLANATION FOR ABBREVIATIONS
P=Pass, F=Fail, N/A=Not applicable. Placed in the column to the right.
1.5.101
Addition:
No power cord provided.
N/A
The CISPR requirements have
to be considered during
national approval.
N/A
Plugs for the connection of the apparatus to the
supply mains shall comply with the Korean
requirement (KSC 8305).
7
Addition: EMC
The apparatus shall comply with the relevant
CISPR standards.
Korean National Differences according to CB Bulletin No. 110A, June 2006
Page 69 of 72
Report No.:
11008637 001
National Differences
Clause
Result – Remark
Requirement − Test
APPENDIX US National Differences according to CB Bulletin No. 110A, June 2006
(UL 60950-1)
Verdict
P
(IEC Publication 60950-1:2001)
EXPLANATION FOR ABBREVIATIONS
P=Pass, F=Fail, N/A=Not applicable. Placed in the column to the right.
Special National Conditions
1.1.1
All equipment is to be designed to allow
installations in accordance with the National
Electrical Code (NEC), ANSI/NFPA 70,the
Canadian Electrical Code (CEC), Part I,
CAN/CSA C22.1, and when applicable, the
National Electrical Safety Code, IEEE C2. Also,
unless marked or otherwise identified, installation
is allowed per the Standard for the Protection of
Electronic Computer/Data-Processing Equipment,
ANSI/NFPA 75.
Unit was evaluated according
to IEC 60950-1. The
requirements have to be
checked during national
approval.
N/A
1.4.14
For Pluggable Equipment Type A, the protection
in the installation is assumed to be 20A.
No power cord provided.
N/A
1.5.5
For lengths exceeding 3.05 m, external
interconnecting flexible cord and cable
assemblies are required to be a suitable cable
type (e.g. DP, CL2) specified in the NEC.
Same as above.
N/A
Same as above.
N/A
For lengths 3.05 m or less, external
interconnecting flexible cord and cable
assemblies that are not types specified in the
NEC are required to have special construction
features and identification markings.
1.7.1
Equipment for use on a.c. mains supply systems
with a neutral and more than one phase
conductor (e.g. 120/240 V, 3-wire) require a
special marking format for electrical ratings.
A voltage rating that exceeds an attachment plug
cap rating is only permitted if it does not exceed
the extreme operating conditions in Table 2 of
CAN/CSA C22.2 No. 235, and if it is part of a
range that extends into the Table 2 “Normal
Operating Conditions.” Likewise, a voltage rating
shall not be lower than the specified “Normal
Operating Conditions,” unless it is part of a range
that extends into the “Normal Operating
Conditions.”
2.5
Where a fuse is used to provide Class 2, Limited No such fuse.
Power Source, or TNV current limiting, it shall not
be operator-accessible unless it is not
interchangeable.
N/A
2.7.1
Suitable NEC/CEC branch circuit protection rated No such components
at the maximum circuit rating is required for all
provided.
N/A
US National Differences according to CB Bulletin No. 110A, June 2006
Page 70 of 72
Report No.:
11008637 001
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
standard supply outlets, receptacles and mediumbase or smaller lampholders if the supply branch
circuit protection is not suitable.
Power distribution transformers distributing power
at 100 volts or more, and rated 10 kVA or more,
require transformer overcurrent protection.
3.2
Wiring methods (terminals, leads, etc.) used for
the connection of the equipment to the mains
shall be in accordance with the NEC/CEC.
Appliance inlet used.
N/A
3.2.1
Power supply cords are required to have
attachment plugs rated not less than 125 percent
of the rated current of the equipment.
No such cords provided.
N/A
3.2.3
Permanent connection of equipment to the mains Pluggable equipment.
supply by a power supply cord is not permitted,
except for certain equipment, such as ATMs.
N/A
3.2.5
Power supply cords are required to be no longer
than 4.5 m in length.
No such cords provided.
N/A
Pluggable equipment.
N/A
Flexible power supply cords are required to be
compatible with Article 400 of the NEC, and
Tables 11 and 12 of the CEC.
3.2.9
Permanently connected equipment is required to
have a suitable wiring compartment and wire
bending space.
3.3
Wiring terminals and associated spacings for field Appliance inlet used.
wiring connections shall comply with CSA C22.2
No. 0.
N/A
3.3.3
Wire binding screws are not permitted to attach
conductors larger than 10 AWG (5.3 mm²).
Appliance inlet used.
N/A
3.3.4
Terminals for permanent wiring, including
Appliance inlet used.
protective earthing terminals, are required to be
suitable for U.S./Canadian wire gauge sizes, rated
125 percent of the equipment rating, and be
specially marked when specified (1.7.7).
N/A
3.4.2
Motor control devices are required for cordEquipment is not such a
connected equipment with a motor if the
device.
equipment is rated more than 12A, or if the motor
has a nominal voltage rating greater than 120V,
or is rated more than 1/3 hp (locked rotor current
over 43 A)
N/A
3.4.8
Vertically-mounted disconnect switches and
No such devices incorporated.
circuit breakers are required to have the ”on”
position indicated by the handle in the up position.
N/A
US National Differences according to CB Bulletin No. 110A, June 2006
Page 71 of 72
Report No.:
11008637 001
National Differences
Clause
Requirement − Test
Result – Remark
3.4.11
For computer room applications, equipment with
battery systems capable of supplying 750 VA for
five minutes are required to have a battery
disconnect means that may be connected to the
computer room remote power-off circuit.
Not such an application.
N/A
4.3.12
The maximum quantify of flammable liquid stored No liquids incorporated.
in equipment is required to comply with NFPA 30.
N/A
4.3.13
Equipment with lasers is required to meet Code of Not such an application.
Federal Regulations 21 CFR 1040 (and the
Canadian Radiation Emitting Devices Act, REDR
C1370).
N/A
4.7
For computer room applications, automated
Not such an application.
information storage systems with combustible
media greater than 27 cubic feet are required to
have a provision for connection of either
automatic sprinklers or a gaseous agent
extinguishing system with an extended discharge.
N/A
4.7.3.1
For computer room applications, enclosures with Not such an application.
combustible material measuring greater than 0.9
m² or a single dimension greater than 1.8 m are
required to have a flame spread rating of 50 or
less. For other applications, enclosures with the
same dimensions require a flame spread rating of
200 or less.
N/A
Annex H
Equipment that produces ionizing radiation is
required to comply with the Code of Federal
Regulations, 21 CFR 1020 (and the Canadian
Radiation Emitting Devices Act, REDR C1370).
N/A
No ionizing radiation.
Verdict
Other differences
1.5.1
Some components and materials associated with Components are approved,
the risk of fire, electric shock, or personal injury
see component list 1.5.1.
are required to have component or material
ratings in accordance with the applicable national
(U.S. and Canadian) component or material
requirements. These components include:
attachment plugs, battery packs (rechargeable
type, used with transportable equipment), cathode
ray tubes, circuit breakers, communication circuit
accessories, connectors (used for current
interruption of non-LPS circuits), cord sets and
power supply cords, direct plug-in equipment,
enclosures (outdoor), flexible cords and cables,
fuses (branch circuit), fuseholders, ground-fault
current interrupters, industrial control equipment,
insulating tape, interconnecting cables,
lampholders, limit controls, printed wiring,
protectors for communications circuits,
receptacles, solid state controls, supplementary
protectors, surge suppressors, switches
US National Differences according to CB Bulletin No. 110A, June 2006
P
Page 72 of 72
Report No.:
11008637 001
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
(including interlock switches), thermal cut-offs,
thermostats, multi-layer transformer winding wire,
tubing, wire connectors, and wire and cables.
2.3.1
For TNV-2 and TNV-3 circuits with other than
No TNV circuits.
ringing signals and with voltages exceeding
42.4 Vpeak or 60 Vd.c., the maximum acceptable
current through a 2000 ohm resistor (or greater)
connected across the voltage source with other
loads disconnected is 7.1 mA peak or 30 mA d.c.
under normal operating conditions.
N/A
2.3.2
In the event of a single fault, the limits of 2.2.3
No TNV circuits.
apply to SELV Circuits and accessible conductive
parts.
N/A
2.6.3.3
When subject to impedance testing, protective
Refer to the relevant subearthing and bonding are required to be subjected clause on the IEC 60950-1
to the additional test conditions specified.
report.
3.2.1.2
Equipment connected to a centralized d.c. power Not supplied from DC mains.
system, and having one pole of the DC mains
input terminal connected to the main protective
earthing terminal in the equipment, is required to
comply with special earthing, writing, marking and
installation instruction requirements.
N/A
4.2.8.1
Enclosures around CRTs with a face diameter of No CRT.
160mm or more are required to reduce the risk of
injury due to the implosion of the CRT.
N/A
4.3.2
Equipment with handles is required to comply with No handles.
special loading tests.
N/A
5.1.8.3
Equipment intended to receive telecommunication No TNV.
ringing signals is required to comply with a special
touch current measurement tests.
N/A
6.2.1
Enamel coating on winding wire not considered
electrical separation unless subjected to special
investigation.
N/A
6.4
Equipment intended for connection to
No TNV circuits.
telecommunication network outside plant cable is
required to be protected against overvoltage from
power line crosses in accordance with 6.4 and
Annex NAC.
N/A
6.5
Equipment connected to a telecommunications
network and supplied with an earphone intended
to be held against, or in the ear is required to
comply with special acoustic pressure tests.
No TNV circuits.
N/A
M.2
Continuous ringing signals up to 16 mA only are
permitted if the equipment is subjected to special
installation and performance restrictions.
No TNV circuits.
N/A
No TNV.
US National Differences according to CB Bulletin No. 110A, June 2006
P
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement