Below you will find brief information for fuse POWR-GARD. This document covers the fundamentals of overcurrent protection, selection considerations for fuses, time-current curves and peak let-through charts, selective coordination, UL/CSA fuse classes and applications, terms and definitions, motor protection tables, UL fuse classes & selection chart, and a condensed fuse cross reference.
advertisement
Application
Guide
POWR-GARD
Technical Application Guide
This Technical Application Guide or ‘Fuseology’ provides the information needed to select the correct types of Littelfuse POWR-GARD
®
fuses for most applications. If there are any questions or if additional data is needed for a specific use, call the Littelfuse Technical Support and
Engineering Service Group at 1-800-TEC-FUSE (1-800-832-3873), email them at [email protected] or visit us at littelfuse.com.
TECHNICAL APPLICATION GUIDE
Technical Information
White papers, and a library of technical information is available online at
littelfuse.com/technicalcenter
Table of Contents
Fuseology Fundamentals ............................................................... 3
Selection Considerations ............................................................... 5
Time-current Curves and Peak Let-through Charts ........................ 9
Selective Coordination ..................................................................11
UL/CSA Fuse Classes and Applications ........................................14
Terms and Definitions ...................................................................16
Motor Protection Tables ............................................................... 23
UL Fuse Classes & Selection CHart ............................................ 26
Condensed Fuse Cross Reference .............................................. 27 littelfuse.com
2
© 2014 Littelfuse POWR-GARD
®
Products
Technical Application Guide
FUSEOLOGY FUNDAMENTALS
I. OVERCURRENT PROTECTION
FUNDAMENTALS
(FUSES AND HOW THEY WORK)
Introduction
An important part of developing quality overcurrent protection is an understanding of system needs and overcurrent protective device fundamentals. This section discusses these topics with special attention to the application of fuses. If you have additional questions, call our Technical Support Group at
1-800-TEC-FUSE (1-800-832-3873). Definitions of terms used in this section are located towards the end of this Technical
Application Guide.
Why Overcurrent Protection?
All electrical systems eventually experience overcurrents.
Unless removed in time, even moderate overcurrents quickly overheat system components, damaging insulation, conductors, and equipment. Large overcurrents may melt conductors and vaporize insulation. Very high currents produce magnetic forces that bend and twist bus bars.
These high currents can pull cables from their terminals and crack insulators and spacers.
Too frequently, fires, explosions, poisonous fumes and panic accompany uncontrolled overcurrents. This not only damages electrical systems and equipment, but may cause injury or death to personnel nearby.
To reduce these hazards, the National Electrical Code
®
(NEC
®
), OSHA regulations, and other applicable design and installation standards require overcurrent protection that will disconnect overloaded or faulted equipment.
Industry and governmental organizations have developed performance standards for overcurrent devices and testing procedures that show compliance with the standards and with the NEC. These organizations include: the American
National Standards Institute (ANSI), National Electrical
Manufacturers Association (NEMA), and the National
Fire Protection Association (NFPA), all of which work in conjunction with Nationally Recognized Testing Laboratories
(NRTL) such as Underwriters Laboratories (UL).
Electrical systems must meet applicable code requirements including those for overcurrent protection before electric utilities are allowed to provide electric power to a facility.
What is Quality Overcurrent Protection?
A system with quality overcurrent protection has the following characteristics:
1. Meets all legal requirements, such as NEC
®
, OSHA, local codes, etc.
2. Provides maximum safety for personnel, exceeding minimum code requirements as necessary.
© 2014 Littelfuse POWR-GARD
®
Products
3
3. Minimizes overcurrent damage to property, equipment, and electrical systems.
4. Provides coordinated protection. Only the protective device immediately on the line side of an overcurrent opens to protect the system and minimize unnecessary downtime.
5. Is cost effective while providing reserve interrupting capacity for future growth.
6. Consists of equipment and components not subject to obsolescence and requiring only minimum maintenance that can be performed by regular maintenance personnel using readily available tools and equipment.
Overcurrent Types and Effects
An overcurrent is any current that exceeds the ampere rating of conductors, equipment, or devices under conditions of use. The term “overcurrent” includes both overloads and short-circuits.
Overloads
An overload is an overcurrent confined to normal current paths in which there is no insulation breakdown.
Sustained overloads are commonly caused by installing excessive equipment such as additional lighting fixtures or too many motors. Sustained overloads are also caused by overloading mechanical equipment and by equipment breakdown such as failed bearings. If not disconnected within established time limits, sustained overloads eventually overheat circuit components causing thermal damage to insulation and other system components.
Overcurrent protective devices must disconnect circuits and equipment experiencing continuous or sustained overloads before overheating occurs. Even moderate insulation overheating can seriously reduce the life of the components and/or equipment involved. For example, motors overloaded by just 15% may experience less than 50% of normal insulation life.
Temporary overloads occur frequently. Common causes include temporary equipment overloads such as a machine tool taking too deep of a cut, or simply the starting of an inductive load such as a motor. Since temporary overloads are by definition harmless, overcurrent protective devices should not open or clear the circuit.
It is important to realize that fuses selected must have sufficient time-delay to allow motors to start and temporary overloads to subside. However, should the overcurrent continue, fuses must then open before system components are damaged. Littelfuse POWR-PRO
®
and POWR-GARD
® time-delay fuses are designed to meet these types of protective needs. In general, time-delay fuses hold 500% of the rated current for a minimum of ten seconds, yet will still open quickly on higher values of current. littelfuse.com
Technical Application Guide
FUSEOLOGY FUNDAMENTALS
Even though government-mandated high-efficiency motors and NEMA Design E motors have much higher locked rotor currents, POWR-PRO
®
time-delay fuses such as the FLSR_
ID, LLSRK_ID, or IDSR series have sufficient time-delay to permit motors to start when the fuses are properly selected in accordance with the NEC ® .
Short-Circuits
A short-circuit is an overcurrent flowing outside of its normal path. Types of short-circuits are generally divided into three categories: bolted faults, arcing faults, and ground faults. Each type of short-circuit is defined in the Terms and
Definitions section.
A short-circuit is caused by an insulation breakdown or faulty connection. During a circuit’s normal operation, the connected load determines current. When a short-circuit occurs, the current bypasses the normal load and takes a
“shorter path,” hence the term ‘short-circuit’. Since there is no load impedance, the only factor limiting current flow is the total distribution system’s impedance from the utility’s generators to the point of fault.
A typical electrical system might have a normal load impedance of 10 ohms. But in a single-phase situation, the same system might have a load impedance of 0.005 ohms or less. In order to compare the two scenarios, it is best to apply Ohm’s Law (I
= E/R for AC systems). A 480 volt single-phase circuit with the
10 ohm load impedance would draw 48 amperes (480/10 = 48).
If the same circuit has a 0.005 ohm system impedance when the load is shorted, the available fault current would increase significantly to 96,000 amperes (480/0.005 = 96,000).
As stated, short-circuits are currents that flow outside of their normal path. Regardless of the magnitude of overcurrent, the excessive current must be removed quickly.
If not removed promptly, the large currents associated with short-circuits may have three profound effects on an electrical system: heating, magnetic stress, and arcing.
Heating occurs in every part of an electrical system when current passes through the system. When overcurrents are large enough, heating is practically instantaneous. The energy in such overcurrents is measured in ampere-squared seconds (I
2 t). An overcurrent of 10,000 amperes that lasts for
0.01 seconds has an I 2 t of 1,000,000 A 2 s. If the current could be reduced from 10,000 amperes to 1,000 amperes for the same period of time, the corresponding I 2 t would be reduced to 10,000 A
2 s, or just one percent of the original value.
If the current in a conductor increases 10 times, the I
2 t increases 100 times. A current of only 7,500 amperes can melt a #8 AWG copper wire in 0.1 second. Within eight milliseconds (0.008 seconds or one-half cycle), a current of 6,500 amperes can raise the temperature of #12
AWG THHN thermoplastic insulated copper wire from its operating temperature of 75°C to its maximum short-circuit temperature of 150°C. Any currents larger than this may immediately vaporize organic insulations. Arcs at the point of fault or from mechanical switching such as automatic transfer switches or circuit breakers may ignite the vapors causing violent explosions and electrical flash.
Magnetic stress (or force) is a function of the peak current squared. Fault currents of 100,000 amperes can exert forces of more than 7,000 lb. per foot of bus bar. Stresses of this magnitude may damage insulation, pull conductors from terminals, and stress equipment terminals sufficiently such that significant damage occurs.
Arcing at the point of fault melts and vaporizes all of the conductors and components involved in the fault. The arcs often burn through raceways and equipment enclosures, showering the area with molten metal that quickly starts fires and/or injures any personnel in the area. Additional short-circuits are often created when vaporized material is deposited on insulators and other surfaces. Sustained arcing-faults vaporize organic insulation, and the vapors may explode or burn.
Whether the effects are heating, magnetic stress, and/or arcing, the potential damage to electrical systems can be significant as a result of short-circuits occurring.
II. SELECTION CONSIDERATIONS
Selection Considerations for Fuses (600 volts and below)
Since overcurrent protection is crucial to reliable electrical system operation and safety, overcurrent device selection and application should be carefully considered. When selecting fuses, the following parameters or considerations need to be evaluated:
• Current Rating
• Voltage Rating
• Interrupting Rating
• Type of Protection and Fuse Characteristics
• Current Limitation
• Physical Size
• Indication
Current Rating
The current rating of a fuse is the AC or DC current, expressed in amperes, which the fuse is capable of carrying continuously under specified conditions. Fuses selected for a circuit must have ampere ratings that meet NEC
® requirements, namely those found in NEC
®
Articles 240 and
430. These NEC
®
requirements establish maximum ratings and in some cases, minimum ratings. When selecting a fuse, it is generally recommended to select a current rating as close as possible to the system’s normal running current.
littelfuse.com
4
© 2014 Littelfuse POWR-GARD
®
Products
Technical Application Guide
SELECTION CONSIDERATIONS
Voltage Rating
The voltage rating of a fuse is the maximum AC or DC voltage at which the fuse is designed to operate. Fuse voltage ratings must equal or exceed the circuit voltage where the fuses will be installed, and fuses used in DC circuits must be specifically rated for DC applications. In terms of voltage, fuses may be rated for AC only, DC only, or both AC and DC. However, exceeding the voltage ratings or using an AC only fuse in a DC circuit could result in violent destruction of the fuse.
The standard 600 volt rated fuses discussed in this section may be applied at any voltage less than or equal to their rating. For example, a 600 volt fuse may be used in a 277 volt or even a 32 volt system, but not any system exceeding
600 volts.
NOTE: This does not apply to semiconductor fuses and medium voltage fuses. See the semiconductor and medium voltage fuse application information on littelfuse.com for voltage limitations of these fuses.
Interrupting Rating
The interrupting rating of a fuse is the highest available symmetrical rms alternating current that the fuse is required to safely interrupt at its rated voltage under standardized test conditions. A fuse must interrupt all overcurrents up to its interrupting rating without experiencing damage. Standard
UL fuses are available with interrupting ratings of 10,000 A,
50,000 A, 100,000 A, 200,000 A, and 300,000 A.
NEC
®
Article 110.9 requires that all equipment intended to break current at fault levels have an interrupting rating sufficient for the system voltage and current available at the equipment’s line terminals. Refer to Figure 1. It is vitally important to select fuses with interrupting ratings which equal or exceed the available fault current.
Main Switchboard
Available Fault
Current = 125,000A
All fuses in main switchboard must have an A.I.R. of at least
125,000A. Next higher standard rating is 200,000A.
Fuses in panel must have at least an 85,000 A.I.C. Next higher standard rating is 100,000A., but best choice is time-delay fuses with 200,000 A.I.R.
Available Fault
Current = 85,000A
Figure 1 – Interrupting Rating Requirements per NEC
© 2014 Littelfuse POWR-GARD
®
Products
5
The recommendation to standardize on fuses with at least a 200,000 ampere interrupting rating (AIR) ensures that all fuses have an adequate interrupting rating while providing reserve interrupting capacity for future increases in available fault current.
300,000 AIR Fuses
Littelfuse POWR-PRO
®
fuse series have a Littelfuse Self-
Certified interrupting rating of 300,000 amperes rms symmetrical. The 300,000 ampere testing was performed in a Nationally Recognized Testing Laboratory, and the tests were UL witnessed. UL has ruled that fuses with a UL interrupting rating greater than 200,000 amperes must be marked as “Special Purpose Fuses” and may not be labeled as UL Listed Class RK5, RK1, L, etc.
Type of Protection and Fuse Characteristics
Time current characteristics determine how fast a fuse responds to overcurrents. All fuses have inverse time characteristics; that is, the fuse opening time decreases as the magnitude of overcurrent increases. When properly rated in accordance with NEC
® requirements, fuses provide both overload and short-circuit protection to system conductors and components. However, in some instances such as when fuses are used to backup circuit breakers or to provide motor branch circuit short-circuit and ground fault protection, fuses provide only short-circuit protection. A fuse’s response to overcurrents is divided into short-circuits and overloads.
Short-Circuits
A fuse’s short-circuit response is its opening time on highervalue currents. For power fuses, higher-value currents are generally over 500-600% of the fuse’s current rating. As stated earlier, all fuses have inverse time characteristics: the higher the current, the faster the opening time. Since shortcircuits should be removed quickly, inverse time is especially important for short-circuit protection.
Overloads
While fuses must disconnect overloaded conductors and equipment before the conductors and components are seriously overheated, they should not disconnect harmless temporary overloads. To provide sufficient overload protection for system conductors, UL has established maximum fuse opening times at 135% and 200% of a fuse’s current rating. All UL Listed fuses for application in accordance with the National Electrical Code
®
must meet these limits whether they are fast-acting or time-delay fuses.
As just stated, a fuse is designed to respond to two types of overcurrents – short circuits and overloads. As a result, selecting the proper fuse for a given application usually involves deciding whether to use a time-delay fuse or a fast-acting fuse. A more in-depth review of both possible scenarios is important at this time.
littelfuse.com
Technical Application Guide
SELECTION CONSIDERATIONS
Fast-Acting (Normal-Opening) Fuses
Fast-acting fuses (sometimes called “Normal-opening” fuses) have no intentional time-delay. Typical opening times at 500% of the fuse ampere rating range from 0.05 second to approximately 2 seconds. Fast-Acting fuses are suitable for non-inductive loads such as incandescent lighting and general-purpose feeders, or branch circuits with little or no motor load. When protecting motors and other inductive loads, fast-acting fuses must be rated at
200-300% of load currents to prevent nuisance opening on in-rush currents. Fuses with such increased ratings no longer furnish adequate protection from overloads and only provide short-circuit protection. Overload relays or other overload protection devices must be provided to properly protect conductors and equipment from overload conditions.
All fast-acting fuses provide fast short-circuit response within their interrupting rating. Some are considered currentlimiting, such as UL Class T and Class J. Others are noncurrent-limiting, such as UL Class H.
Time-Delay (SLO-BLO
®
) Fuses
Most UL Class CC, CD, G, J, L, RK5 and RK1 fuses, plus some of the UL Listed Miscellaneous fuses are considered time-delay. If so, they are identified as such on the fuse label with the words “Time-Delay”, “T-D”, “D”, or some other suitable marking. Minimum time-delay varies with the fuse class, and to some degree with the fuse ampere rating. UL standards for POWR-GARD
®
fuse series FLNR,
FLNR_ID, FLSR, FLSR_ID, IDSR (UL Class RK5), LLNRK,
LLSRK, LLSRK_ID (UL Class RK1), and JTD, JTD_ID (UL
Class J) require these fuses to carry 500% rated current for a minimum of 10 seconds. Standards for CCMR and KLDR (UL
Class CC and CD) and SLC (UL Class G) fuses require them to carry 200% rated current for a minimum of 12 seconds.
Although there is no UL Classification for time-delay Class
L fuses, it is still permissible for them to be marked “Time-
Delay.” The amount of time-delay is determined by the manufacturer. Littelfuse KLPC series and KLLU series fuses will hold 500% current for 10 seconds or more.
In addition to providing time-delay for surges and short time overloads, time-delay fuses meet all UL requirements for sustained overload protection. On higher values of current, time-delay fuses are current-limiting; meaning they remove large overcurrents in less than one-half cycle (0.00833 seconds). Time-delay fuses provide the best overall protection for both motor and general purpose circuits, and eliminate nuisance fuse opening and most situations of downtime.
Compared to fast-acting fuses, time-delay fuses can be selected with ratings much closer to a circuit’s operating current. For example, on most motor circuits Class RK5 and
RK1 fuses can be rated at 125-150% of a motor’s full load current (FLA). This provides superior overload and shortcircuit protection, and often permits the use of smaller, less expensive disconnect switches. Time-delay fuses have gradually replaced most one-time (UL Class K5) and renewable (UL Class H) fuses. Today, more than 50% of all fuses sold by electrical distributors are time-delay fuses.
Dual Element Fuses
Littelfuse time-delay FLNR, FLNR_ID, FLSR, FLSR_ID, IDSR
(UL Class RK5), and LLNRK, LLSRK, LLSRK_ID (UL Class RK1), and some JTD, JTD_ID (UL Class J) series fuses have true dual-element construction meaning the fuse has an internal construction consisting of separate short-circuit and overload sections or elements. Time-delay elements are used for overload protection, and separate fast acting fuse elements or links are used to provide current-limiting short-circuit protection.
Very Fast-Acting Fuses
This category of fuses exists for limited applications. The principle use of very fast acting fuses is to protect solidstate electronic components, such as semiconductors. Fuse series designated as ‘Semiconductor Fuses’ have special characteristics including quick overload response, very low I
2 t and I peak
currents, and peak transient voltages, that provide protection for components that cannot withstand line surges, low value overloads, or short-circuit currents.
Very fast-acting fuses are designed for very fast response to overloads and short-circuits, and are very current-limiting.
Effect of Ambient Temperature on Fuses
The current carrying capacity of fuses is 110% of the fuse rating when installed in a standard UL test circuit and tested in open air at 25°C ambient. This allows for derating to 100% of rating in an enclosure at 40°C ambient.
FUSE RERATING CURVE
60
40
20
0
A
B
KEY TO CHART:
Curve A - Slo-Blo
®
Fuse
Curve B - Medium and Fast-Acting Fuses
B
A
-60°C
-76°F
-40°C
-40°F
-20°C
-4°F
0°C
32°F
20°C 40°C 60°C 80°C
68°F 104°F 140°F 176°F
AMBIENT TEMPERATURE
100°C
212°F
120°C
248°F
140°C
264°F
Figure 2 – Fuse Rerating Curve
40
60
0
20
littelfuse.com
6
© 2014 Littelfuse POWR-GARD
®
Products
Technical Application Guide
SELECTION CONSIDERATIONS
Current Limitation
A current-limiting fuse is one that opens and clears a fault in less than 180 electrical degrees, or in other words, within the first half electrical cycle (0.00833 seconds). See the definition of Current-limiting Fuse and Figure 13 in the Terms and Definitions section.
NEC
®
Article 240.2 states that a current-limiting overcurrent protective device must reduce the peak let-through current to a value substantially less than the potential peak current that would have occurred if the fuse were not used in the circuit or were replaced with solid conductors of the same impedance. The total destructive heat energy (I
2 t) to the circuit and its components is greatly minimized as a result of using current-limiting fuses.
It is important to note that UL Class H ‘Renewable’ fuses designed decades ago are considered non-current limiting. Other than Midget fuses, almost all other fuse types used in today’s electrical systems and applications are considered currentlimiting per the above parameters. This selection consideration now involves determining the degree or level of current limitation required to properly protect a given device or system.
It is also important to point out that matching fuse holders and/or fuse blocks must reject non-current-limiting fuses and accept only current-limiting fuses of the stated UL Class.
Physical Size
While often overlooked, the physical size or overall dimensions of the fuse to be used in a given application is another important selection consideration to evaluate. There is a trend toward reduction of size in almost everything, and electrical equipment is no exception. Fuse size is actually determined by the size and dimensions of the fuse block or disconnect switch in which it is installed.
While saving space may be an important factor when selecting the proper fuses, other considerations should not be overlooked. Some of these include:
• Does the smallest fuse have the most desirable characteristics for the application?
• Does the equipment in which the fuse will be installed provide adequate space for maintenance?
• Do smaller fuses coordinate well with the system’s other overcurrent protection?
If looking at just physical dimensions, a 600 volt, 60 ampere,
200,000 AIR, time-delay, dual-element UL Class CD fuse is smaller than a similarly rated UL Class J fuse, which is in turn, considerably smaller than a similarly rated UL Class RK1 or Class RK5 fuse.
However, smaller-sized fuses can sometimes have less time-delay or more nuisance openings than their larger counterparts, so it is always important to consider all factors involved.
Indication
The newest consideration for selecting the best fuse for a given application is indication. Many of the more commonly used UL fuse classes are now available in both indicating and non-indicating versions. Built-in, blown-fuse indication that quickly identifies which fuse or fuses within an electrical panel or system have blown can be found on the Littelfuse
POWR-PRO
®
LLSRK_ID Class RK1, FLNR_ID, FLSR_ID and
IDSR Class RK5, and JTD_ID Class J fuse series.
The indicating feature on these fuses provides reduced downtime, increased safety, and reduced housekeeping or troubleshooting headaches and delays. Littelfuse Indicator
® fuses will help lower the costs associated with downtime, provide longer fuse life by minimizing nuisance openings, increase system performance by minimizing equipment damage, and improve safety by minimizing accidents.
III. GENERAL FUSING RECOMMENDATIONS
Based on the above selection considerations, the following is recommended:
Fuses with ampere ratings from 1/10 through 600 amperes
• When available fault currents are less than 100,000 amperes and when equipment does not require the more current-limiting characteristics of UL Class RK1 fuses,
FLNR and FLSR_ID Series Class RK5 current-limiting fuses provide superior time-delay and cycling characteristics at a lower cost than RK1 fuses. If available fault currents exceed
100,000 amperes, equipment may need the additional current-limitation capabilities of the LLNRK, LLSRK and
LLSRK_ID series Class RK1 fuses.
• Fast-acting JLLN and JLLS series Class T fuses possess space-saving features that make them especially suitable for protection of molded case circuit breakers, meter banks, and similar limited-space applications.
• Time-delay JTD_ID and JTD series Class J fuses are used in OEM motor control center applications as well as other
MRO motor and transformer applications requiring spacesaving IEC Type 2 protection.
• Class CC and Class CD series fuses are used in control circuits and control panels where space is at a premium.
The Littelfuse POWR-PRO CCMR series fuses are best used for protection of small motors, while the Littelfuse
KLDR series fuses provide optimal protection for control power transformers and similar devices.
For questions about product applications, call our Technical
Support Group at 800-TEC-FUSE.
© 2014 Littelfuse POWR-GARD
®
Products
7
littelfuse.com
Technical Application Guide
SELECTION CONSIDERATIONS
Fuses with ampere ratings from 601 through 6,000 amperes
For superior protection of most general-purpose and motor circuits, it is recommended to use the POWR-PRO
®
KLPC series Class L fuses. The Class L fuses are the only timedelay fuse series available in these higher ampere ratings.
Information on all the Littelfuse fuse series referenced above can be found on the UL/CSA Fuse Classes and Applications
Charts found later in this Technical Application Guide.
IV. SELECTION CONSIDERATIONS FOR
FUSE HOLDERS
Equally important to the selection of the proper fuse is the correct selection of the proper fuse holder or fuse block for a given application. Fuse holders are available using most of the same Selection Considerations outlined above for UL fuse classes. Considerations for fuse holders include:
• Current Rating
• Voltage Rating
• Interrupting Rating
• Physical Size
• Indication
Additional selection considerations for fuse holders and fuse blocks include:
• Number of poles
• Mounting configuration
• Connector type
Number of Poles
The number of poles for each set of fuses is determined by the characteristics of the circuit. Most fuse block series are available in 1, 2, or 3 pole configurations, although some are also available with four or more poles. The option to gang individual fuse blocks into longer strips will be determined by the available space and type of wire being used.
Mounting Configuration
Depending on the fuse block design, another selection consideration to evaluate is how the fuse block is mounted or inserted into the panel. Historically, fuse blocks simply screwed into the back of the panel, but many newer designs have now added (or replaced the screw-in design with) a DIN rail mounting capability. The DIN rail mounting feature allows the blocks to be quickly installed and removed from the rails.
Connector Type
For Littelfuse fuse blocks, a choice of three connector types or wire terminations is available:
• Screw – for use with spade lugs or ring terminals.
• Screw with Pressure Plate – for use with solid or stranded wire without terminal and recommended for applications where vibration will be a factor.
• Box Lug – the most durable of the three options and used with all types of solid wire and Class B and Class C stranded wire.
There are a few additional aspects to keep in mind when selecting the fuse holder or fuse block needed for a given application. UL Class H blocks accept Class H, Class K5, and
Class R fuses. Similarly, Midget-style fuse blocks accept both Midget and UL Class CC fuses.
Both UL Class R and Class CC fuse holders contain a rejection feature which prevents the insertion of a different
Class or type of fuse. The physical size and dimensions of
UL Class J and Class T fuses accomplish the same thing in preventing the insertion of a different Class of fuse as well.
V. CIRCUIT PROTECTION CHECKLIST
To select the proper overcurrent protective device for an electrical system, circuit and system designers should ask themselves the following questions before a system is designed:
• What is the normal or average current expected?
• What is the maximum continuous (three hours or more) current expected?
• What inrush or temporary surge currents can be expected?
• Are the overcurrent protective devices able to distinguish between expected inrush and surge currents, and open under sustained overloads and fault conditions?
• What kind of environmental extremes are possible? Dust, humidity, temperature extremes and other factors need to be considered.
• What is the maximum available fault current the protective device may have to interrupt?
• Is the overcurrent protective device rated for the system voltage?
• Will the overcurrent protective device provide the safest and most reliable protection for the specific equipment?
• Under short-circuit conditions, will the overcurrent protective device minimize the possibility of a fire or explosion?
• Does the overcurrent protective device meet all the applicable safety standards and installation requirements?
Answers to these questions and other criteria will help to determine the type overcurrent protection device to use for optimum safety, reliability and performance.
littelfuse.com
8
© 2014 Littelfuse POWR-GARD
®
Products
Technical Application Guide
FUSE CHARACTERISTIC CURVES AND CHARTS
The performance capabilities of various fuses are graphically represented by two different types of fuse characteristic curves: time-current curves and peak let-through charts.
These curves and charts define the operating characteristics of a given fuse, and assist system designers and engineers in selecting the proper fuse to protect equipment and electrical systems.
Understanding Time-current Curves
Time-current curves provide a graphical representation or plot of a fuse’s average melting (opening) time at any current. Time-current curves for Littelfuse POWR-GARD
® fuses can be found online at
littelfuse.com/technicalcenter.
In order to make the curves more readable, the performance information is presented on log-log paper. The overcurrent values appear across the bottom and increase in magnitude from left to right. Average melting times appear on the left-hand side of the curve and increase in magnitude from bottom to top. The ampere ratings of the individual fuses for a given series are listed at the top and increase in rating from left to right. Figure 4 shows the average melting time curves for a typical time-delay fuse series.
As discussed earlier in the Fuseology Fundamentals section, time-delay, fast-acting, and very fast-acting fuses all respond differently based on the overcurrents occurring in the systems each is protecting. To illustrate the basic differences between each type of fuse, Figure 5 compares the average melting times for 100 and 600 amp ratings
80
60
40
30
20
800
600
400
300
200
4
3
8
6
2
100 AMP
600 AMP
.8
.6
.4
.3
.2
GREEN = TIME-DELAY FUSE
RED = NORMAL OPENING FUSE
BLUE = VERY-FAST ACTING FUSE
.08
.06
.04
.03
.02
.01
30 40 60 80 100
300 400 600 800 1000
CURRENT IN AMPERES
3000 4000 6000 8000 10000
30000 40000 60000 80000 100000
Figure 5 – Comparison of Average Melting Times for
Three Fuse Types of three fuse types: Littelfuse dual-element, time-delay
LLSRK series class RK1 fuses (green); Littelfuse normal opening NLS series class K5 fuses (red); and Littelfuse very fast acting L60S series semiconductor fuses (blue).
To better illustrate this point, Table 3 also compares the opening times for each of these fuses.
400 A 600 A
.8
.6
.4
.3
.2
4
3
8
6
2
800
600
400
300
200
80
60
40
30
20
.08
.06
.04
.03
.02
.01
30 40 60 80 100
300 400 600 800 1000
2000 3000 4000 6000 8000 10000
CURRENT IN AMPERES
30000 40000 60000 80000 100000
Figure 4 – Average Melting Time Curves for Typical Time-Delay
Fuse Series
AMPERE
RATING
100
600
FUSE TYPE
TIME-DELAY
NORMAL OPENING
VERY FAST-ACTING
TIME-DELAY
NORMAL OPENING
VERY FAST-ACTING
OPENING TIME IN SECONDS
500% RATING 800% RATING 1200% RATING
12 secs.
0.9 secs.
0.14 secs.
2 secs.
1.3 secs.
14 secs.
10 secs.
2 secs.
0.7 secs.
0.02 secs.
0.7 secs.
3 secs.
0.05 secs.
0.3 secs.
>0.01 secs.
0.045 secs.
1.1 secs.
>0.01 secs.
Table 3 – Comparative Opening Times for Time-Delay, Fast-
Acting, and Very Fast-Acting Fuses
Peak Let-through Charts
Peak let-through charts illustrate the maximum instantaneous current through the fuse during the total clearing time. This represents the current limiting ability of a fuse.
Fuses that are current-limiting open severe short-circuits within the first half-cycle (180 electrical degrees or 0.00833 seconds) after the fault occurs. Current-limiting fuses also reduce the peak current of the available fault current to a value less than would occur without the fuse. This reduction is shown in Figure 6.
A fuse’s current-limiting effects are shown graphically on
Peak Let-through charts such as the one shown in Figure 7.
The values across the chart’s bottom represent the available
© 2014 Littelfuse POWR-GARD
®
Products
9
littelfuse.com
Technical Application Guide
FUSE CHARACTERISTIC CURVES AND CHARTS
Peak current which would occur without current limitation
Peak Let-Thru Current
Figure 6 – Current limiting effect of fuses
Time
(also referred to as potential or prospective) rms symmetrical fault current. The values on the chart’s left side represent the instantaneous available peak current and the peak letthrough current for various fuse ratings.
To better explain the function of these charts, let’s run through an example. Start by entering the chart on the bottom at 100,000 rms symmetrical amperes and read upwards to the A-B line. From this point, read horizontally to the left and read the instantaneous peak let-thru current of 230,000 amperes. In a circuit with a typical 15% shortcircuit power factor, the instantaneous peak of the available current is approximately 2.3 times the rms symmetrical value. This occurs since the A-B line on the chart has a
2.3:1 slope.
1000000
800000
600000
400000
300000
200000
100000
80000
60000
40000
30000
20000
10000
8000
6000
4000
3000
2000
1000
800
600
400
300
200
100
A
300 400 600 800 1000
3000 4000 6000 8000 10000
30000 40000
AVAILABLE FAULT CURRENT
SYMMETRICAL R.M.S. AMPERES
60000 80000 100000
Figure 7 – Peak Let-through Charts
Figure 14
B
littelfuse.com
FUSE
AMPERE
RATING
600
400
200
100
60
30
10
The diagonal curves that branch off the A-B line illustrate the current-limiting effects of different fuse ampere ratings for a given fuse series. To continue the example from above, enter the chart in Figure 7 on the bottom at 100,000 rms symmetrical amperes and read upwards to the intersection of the 200 ampere fuse curve. Now read from this point horizontally to the left and read a peak let-through current of approximately 20,000 amperes.
What this tells us is that the 200 ampere fuse has reduced the peak current during the fault from 230,000 amperes to
20,000 amperes. In other words, this is the current-limiting effect of the 200 ampere fuse. 20,000 amperes is less than one-tenth of the available current. This is important because the magnetic force created by current flow is a function of the peak current squared. If the peak let-through current of a current-limiting fuse is one-tenth of the available peak, the magnetic force is reduced to less than 1/100 of what would occur without the fuse.
Using the Peak Let-through Charts
(“Up-Over-and-Down”)
Peak Let-through Charts for Littelfuse POWR-GARD
®
fuses can be found online at littelfuse.com/technicalcenter.
These charts are useful in determining whether a given fuse can properly protect a specific piece of equipment.
For example, given an available fault-current of 100,000 rms symmetrical amperes, determine whether 600 amp
250 volt time-delay Class RK1 fuses can sufficiently protect equipment that has a 22,000 amp short-circuit rating. Refer to Figure 8.
Start by locating the 100,000 A available fault-current on the bottom of the chart (Point A) and follow this value upwards to the intersection with the 600 amp fuse curve (Point B).
Next, follow this point horizontally to the left to intersect with the A-B line (Point C). Finally, read down to the bottom of the chart (Point D) to read a value of approximately 18,000 amps.
Can the fuse selected properly protect the equipment for this application? Yes, the POWR-PRO
®
LLNRK 600 ampere
RK1 current-limiting fuses have reduced the 100,000 amperes available current to an apparent or equivalent
18,000 amps. When protected by 600 amp LLNRK RK1 fuses, equipment with short-circuit ratings of 22,000 amps may be safely connected to a system having 100,000 available rms symmetrical amperes.
This method, sometimes referred to as the “Up-Over-and-
Down” method, may be used to:
1. Provide back-up short-circuit protection to large air power circuit breakers.
2. Enable non-interrupting equipment such as bus duct to be
© 2014 Littelfuse POWR-GARD
®
Products
Technical Application Guide
FUSE CHARACTERISTICS CURVES AND CHARTS
1000000
800000
600000
400000
300000
200000
100000
80000
60000
40000
30000
20000
10000
8000
6000
4000
3000
2000
C B
B
FUSE
AMPERE
RATING
600
400
200
100
60
30
1000
800
600
400
300
200
A
100
D A
300 400 600 800 1000
3000 4000 6000 8000 10000
30000 40000 60000 80000 100000
AVAILABLE FAULT CURRENT
SYMMETRICAL R.M.S. AMPERES
Figure 8 – Peak Let-through Chart for POWR-PRO
®
LLNRK Class
RK1 Dual-Element Fuses Using the Up-Over-and-Down Method installed in systems with available short-circuit currents greater than their short circuit (withstand) ratings.
However, this method may not be used to select fuses for backup protection of molded case or intermediate frame circuit breakers. National Electrical Code
®
(NEC
®
) Article
240.86 requires Series Ratings. Refer to the NEC
®
for more information.
UL Listed fuse-to-circuit breaker series ratings are now available from most national load center and panelboard manufacturers. Listings are shown in their product digests, catalogs, and online. Many local builders have also obtained fuse-to-circuit breaker series ratings. For additional information contact the Littelfuse Technical Support Group at
1-800-TEC-FUSE (1-800-832-3873).
Short-Circuit Current Rating (SCCR)
Since 2005, the NEC
®
has required Industrial Control Panels to be labeled with their SCCR. These labels allow users and inspectors to compare the SCCR of the equipment to the available fault current in order to avoid potential hazards in facilities.
Selective Coordination
A “coordinated” or “selective” system is a system whose overcurrent protective devices have been carefully chosen and their time-current characteristics coordinated.
Only the overcurrent device immediately on the line side of an overcurrent will open for any overload or short-circuit condition.
To further clarify, refer to the Terms and Definitions section for the definition of Selective Coordination and Figure 15 for a graphical example.
Since the advent of electrical and electronic equipment, businesses have become entirely dependent on the continuous availability of electric energy. Loss of power halts all production and order processing, yet expenses continue to increase. Even many UPS systems become unintentionally non-selective causing power loss to computers and other critical equipment. Non-selectivity may defeat otherwise well-engineered UPS systems.
In a selective system, none of this occurs. Overloads and faults are disconnected by the overcurrent protective device immediately on the line side of the problem. The amount of equipment removed from service is minimized, the faulted or overloaded circuit is easier to locate, and a minimum amount of time is required to restore full service.
For these and many other reasons, selectivity is the standard by which many systems are judged and designed.
Fuse Selectivity
To get a better sense of how to ensure that fuses are selectively coordinated within an electrical system, refer to Figure 4 shown earlier in this Technical Application
Guide. This figure shows typical average melting timecurrent curves for one class of fuses. Note that the curves are roughly parallel to each other and that for a given overcurrent, the smaller fuse ratings respond quicker than the larger ratings. The heat energy required to open a fuse is separated into melting I 2 t and arcing I 2 t (see definition of
Ampere-Squared-Seconds). The sum of these is the total clearing I 2 t.
For a system to be considered coordinated, the smaller fuse total clearing I
2 t must be less than the larger fuse melting I
2 t. In other words, if the downstream (branch) fuse opens the circuit before the overcurrent affects the upstream (feeder) fuse element, the system will be considered selective. This can be determined by analyzing curves displaying melting and total clearing I
2 t, or from minimum melting and maximum clearing time-current curves.
But the simplest method of coordinating low voltage power fuses is by using a Fuse Coordination Table such as the one shown in Table 4. This table is only applicable for the
Littelfuse POWR-PRO
®
and POWR-GARD
®
fuse series listed.
Tables such as this greatly reduce design time. For example, the coordination table shows that POWR-PRO KLPC Class
L fuses coordinate at a two-to-one ratio with other Class L fuses, with POWR-PRO LLNRK / LLSRK / LLSRK_ID series
© 2014 Littelfuse POWR-GARD
®
Products
11
littelfuse.com
Technical Application Guide
SELECTIVE COORDINATION
Class RK1 fuses, and POWR-PRO JTD / JTD_ID series Class
J fuses.
In the system shown in Figure 9, the 3000 amp Class L main fuses are at least twice the ratings of the 1500, 1200, and 1000 amp Class L feeder fuses. Using the 2:1 ratio just referenced above, it is determined that these fuses will coordinate. The Coordination Table also shows that the
LLSRK_ID series time-delay RK1 feeder and branch circuit fuses coordinate at a two-to-one ratio with the Class L feeder fuses, so the entire system in Figure 9 would be considered 100% coordinated.
Circuit Breaker Coordination
As a result of the numerous types of circuit breakers and circuit breaker trip units available in today’s market, developing a coordinated circuit breaker system or coordinating circuit breakers with fuses is beyond the scope of this Technical Application Guide. For further questions, contact the Littelfuse Technical Support Group.
NEC
®
Requirements for Selective
Coordination
Component Short-Circuit Protecting Ability
As shown in Figure 10, the NEC
®
requires equipment protection to be coordinated with overcurrent protective devices and the available fault current in order to prevent extensive damage to the equipment. Essentially, this means that electrical equipment must be capable of withstanding heavy overcurrents without damage or be properly protected by overcurrent protective devices that will limit damage.
When a severe fault occurs in an unprotected circuit, current immediately increases to a very high value. This is the available or prospective fault current. Some fuses respond so quickly to the increasing current that they interrupt current within the first half-cycle - or before the current even reaches its first peak. This is illustrated in Figure 6 found earlier in the Technical Application Guide. Such fuses are termed “current-limiting fuses.”
Current-limiting fuses stop damaging current faster than any other protective device, and greatly reduce or totally prevent component damage from high fault currents. This performance capability helps users meet the NEC
®
Article
110.10 requirements listed in Figure 10.
Pre-Engineered Solutions
Applicable code requirements also continue to expand with each new edition of the National Electrical Code ® . As of the
2014 edition of the NEC
®
, the following requirements need to be met – and can be, utilizing Littelfuse POWR-GARD ®
Pre-Engineered Solutions:
• NEC 517.26 – Healthcare Essential Electrical Systems
• NEC 620.82 – Elevators
• NEC 700.27 – Emergency Systems
• NEC 701.27 – Legally Required Standby Systems
• NEC 708.54 – Critical Operations Power Systems
601-6000
601-4000
601-2000
30-600
30-600
30-600
30-600
30-600
30-600
30-600
30-600
30-1200
30-1200
30-600
1-60
AMPERE
RANGE
LINE-SIDE FUSES
L
L
L
RK1
RK1
J
RK5
J
G
T
T
RK5
RK5
RK1
RK1
UL CLASS
KLPC
KLLU
LDC
LLNRK
LLSRK_ID
JTD_ID
IDSR
FLNR_ID
FLSR_ID
KLNR
KLSR
JLLN
JLLS
JLS
SLC
LITTELFUSE
CATALOG
NUMBER
601-6000
L
KLPC
LDC
2:1
2:1
2:1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
LOAD-SIDE FUSES
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
TIME-DELAY FUSES
AMPERE RANGE, UL CLASS AND CATALOG NO.
601-4000
L
30-600
RK1
30-600
J
30-600
RK5
KLLU
2:1
2:1
2:1
N/A
N/A
N/A
N/A
LLNRK
LLSRK_ID
2:1
2:1
2:1
2:1
2:1
2:1
1.5:1
JTD_ID
JTD
2:1
2:1
2:1
2:1
2:1
2:1
1.5:1
FLNR_ID
FLSR_ID
IDSR
4:1
4:1
4:1
8:1
8:1
8:1
2:1
3:1
3:1
3:1
3:1
1.5:1
1.5:1
3:1
3:1
1.5:1
1.5:1
3:1
3:1
3:1
3:1
3:1
3:1
8:1
8:1
8:1
4:1
2:1
2:1
8:1
8:1
0-30
CC
CCMR
2:1
2:1
2:1
2:1
2:1
2:1
2:1
2:1
2:1
N/A
N/A
N/A
N/A
N/A
N/A
2:1
2:1
2:1
3:1
3:1
3:1
1.5:1
3:1
3:1
3:1
2:1
1.5:1
1.5:1
3:1
3:1
FAST-ACTING FUSES
AMPERE RANGE, UL CLASS AND CATALOG NO.
30-600
RK1
30-1200
T
30-600
J
1-60
G
KLNR
KLSR
JLLN
JLLS
JLS SLC
2:1
2:1
2:1
3:1
3:1
3:1
1.5:1
3:1
3:1
3:1
2:1
1.5:1
1.5:1
3:1
3:1
2:1
2:1
2:1
3:1
3:1
3:1
1.5:1
3:1
3:1
3:1
2:1
1.5:1
1.5:1
3:1
3:1
N/A
N/A
N/A
4:1
4:1
4:1
1.5:1
4:1
4:1
4:1
2:1
1.5:1
1.5:1
4:1
4:1
Table 4 – Fuse Coordination Table. Selecting the Correct Fuse Ampere Ratio to Maintain Selectively Coordinated Systems.
(Ratios are expressed as Line-Side Fuse to Load-Side Fuse.) littelfuse.com
12
© 2014 Littelfuse POWR-GARD
®
Products
Technical Application Guide
SELECTIVE COORDINATION
The Littelfuse product line of Pre-Engineered Solutions includes:
• LPS Series POWR-Switch (single elevator shunt-trip disconnect switch)
• LCP Selective Coordination Panel
These products continue to gain in popularity because they meet NEC
®
requirements and offer simple, economical solutions for a variety of applications.
Visit littelfuse.com/lcp for more information on Littelfuse
Pre-Engineered Solution products and corresponding selective coordination requirements.
KLPC
3000
KLPC
1500
KLPC
1200
KLPC
1000
LLSRK
400
LLSRK
400
LLSRK
200
LLSRK
200
Figure 9 – Example of Selectively Coordinated Fused System
NATIONAL ELECTRICAL CODE
®
ARTICLE 110 – Requirements for Electrical Installations
I. General
110.3. Examination, Identification, Installation, and Use of Equipment.
(A) Examination. In judging equipment, considerations such as the following shall be evaluated:
(5) Heating effects under normal conditions of use and also under abnormal conditions likely to arise in service.
(6) Arcing effects.
(B) Installation and Use. Listed or labeled equipment shall be used or installed in accordance with any instructions included in the listing or labeling.
110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage sufficient for the current that is available at the line terminals of the equipment.
Equipment intended to interrupt current at other than fault levels shall have an interrupting rating at nominal circuit voltage sufficient for the current that must be interrupted.
110.10 Circuit Impedance, Short-Circuit Current Ratings, and Other Characteristics. The overcurrent protective devices, the total impedance, the equipment short-circuit current ratings, and other characteristics of the circuit to be protected shall be selected and coordinated to permit the circuit protective devices used to clear a fault to do so without extensive damage to the electrical equipment of the circuit. This fault shall be assumed to be either between two or more of the circuit conductors or between any circuit conductor and the equipment grounding conductor(s) permitted in 250.118. Listed equipment applied in accordance with their listing shall be considered to meet the requirements of this section.
ARTICLE 240 – Overcurrent Protection
240.1 Scope. Parts I through VII of this article provide the general requirements for overcurrent protection and overcurrent protective devices not more than 1000 volts, nominal. Part VIII covers overcurrent protection for those portions of supervised industrial installations operating at voltages of not more than 1000 volts, nominal. Part IX covers overcurrent protection over 1000 volts, nominal.
Informational Note: Overcurrent protection for conductors and equipment is provided to open the circuit if the current reaches a value that will cause an excessive or dangerous temperature in conductors or con ductor insulation. See also Articles 110.9 for requirements for interrupting ratings and 110.10 for require ments for protection against fault currents.
(Reproduced by permission of NFPA)
Figure 10 – National Electrical Code Requires Effective Overcurrent Protection
© 2014 Littelfuse POWR-GARD
®
Products
13
littelfuse.com
Technical Application Guide
UL/CSA FUSE CLASSES AND APPLICATIONS
Overcurrent and short-circuit protection of power and lighting feeders and branch circuits
Current Limiting
Fuses which meet the requirements for current limiting fuses are required to be labeled “Current Limiting”. Fuse labels must include: UL/CSA fuse class, manufacturer’s name or trademark, current rating, AC and/or DC voltage rating, and AC and/or DC interrupting rating. “Time Delay”, “D”, “TD” or equivalent may also be included on the label when the fuse complies with the time delay requirements of its class.
CLASS L
STANDARDS: UL Standard 248-14,
CSA C22.2,
VOLTAGE RATING: 600 volts, AC and/or DC
CURRENT RATINGS: 601-6000 amps
KLPC available
INTERRUPTING RATING: AC: 200,000 amps rms symmetrical amps 100,000, 200,000
Not interchangeable with any other UL fuse class.
Time delay: Class L fuses may be marked “Time-Delay” although UL does not investigate time-delay characteristics of Class L fuses.
KLPC & KLLU: 10 seconds at 500% current rating seconds 500%
LF SERIES: KLPC, KLLU, LDC
CLASS CC/CD
STANDARDS: UL Standard 248-4,
CSA Standard C22.2, No. 106, classified as HRCI Misc.
600
CURRENT RATINGS: UL Class CC: 0-30 amps
Class
INTERRUPTING RATINGS: 200,000 amps rms symmetrical
Time delay optional: Minimum of 12 seconds at 200% current rating.
LF SERIES: Time Delay: CCMR (motors), KLDR (transformers)
Fast
CLASS T
STANDARDS: UL Standard 248-15
CSA classified HRCI-T
VOLTAGE RATINGS:
300 and 600 volts AC, 125 and 300 volts DC
CURRENT RATINGS: 0-1200 amps
900 to 1200 amps UL Recognized for 600V version
INTERRUPTING RATING: 200,000 amps rms symmetrical
Fast-Acting fuses. High degree of current limitation.
Very small fuses; space-saving and non-interchangeable with any other UL fuse class.
LF SERIES: JLLN, JLLS
CLASS R
STANDARDS: UL Standard 248-12,
CSA C22.2,
VOLTAGE RATINGS:
250 and 600 volts, AC; 125 and 300 volts DC
CURRENT RATINGS: 0-600 amps
INTERRUPTING RATING: 200,000 amps rms symmetrical
CLASSES:
Time delay is optional for Class R fuses.
Time Delay fuses are required to hold 500% current rating for a minimum of ten seconds.
Same dimensions as UL Class H fuses, terminals modified to provide rejection feature.
Fits UL Class R fuse holders which reject non Class R fuses.
Physically interchangeable with UL Class H, NEMA Class H, and UL Classes K1 &
K5 when equipment has Class H fuse holders.
CLASS RK1
High degree of current limitation.
Provides IEC Type 2 (no damage) protection for motor starters and control components. Time Delay optional, LLSRK_ID Series provides visual indication of blown fuse.
LF SERIES: Time Delay: LLNRK,
LLSRK, LLSRK_ID
Fast Acting: KLNR, KLSR
CLASS RK5
Moderate degree of current limitation, adequate for most applications. Time delay optional.
FLNR_ID, FLSR_ID and IDSR series provides visual indication of blown fuse.
LF SERIES: FLNR, FLNR_ID,
FLSR, FLSR_ID, and IDSR
CLASS G
STANDARDS: UL Standard 248-5
CSA Standard C22.2, No. 106, classified as HRCI Misc.
480
CURRENT RATINGS: 0-60 amps
INTERRUPTING RATING: 100,000 amps rms symmetrical
Not interchangeable with any other UL fuse class.
Time delay optional: Minimum of 12 seconds at 200% current rating.
LF SERIES: SLC
CLASS J
STANDARDS: UL Standard 248-8,
CSA
600 AC
CURRENT RATINGS: 0-600 amps
INTERRUPTING RATING: 200,000 amps rms symmetrical
Not interchangeable with any other UL fuse class.
Time delay optional: Minimum of 10 seconds at 500% current rating.
LF SERIES: Time Delay: JTD_ID, JTD
Fast Acting: JLS
CLASS K
STANDARDS: UL Standard 248-9; No CSA Standard
VOLTAGE RATINGS: 250 and 600 volts, AC
CURRENT RATING: 0-600 amps
INTERRUPTING RATINGS: Three permitted: 50,000, 100,000, and 200,000 amps symmetrical
Time delay is optional for Class K fuses.
Time Delay fuses are required to hold 500% current rating for a minimum of ten seconds.
Same Dimensions and Physically interchangeable with UL Class H fuse holders.
Class K fuses are not permitted to be labeled Current Limiting because there is no rejection feature as required by NEC
®
Article 240-60(B).
CLASS K1
Same prescribed degree of current limitation as RK1 fuses when tested at 50,000 or 100,000 amps rms symmetrical.
LF SERIES: Time Delay: LLNRK,
LLSRK
Fast
KLSR
Acting:
CLASS K5
Same prescribed degree of current limitation as RK5 fuses when tested at 50,000 or 100,000 amps rms symmetrical.
LF SERIES: NLN, NLS littelfuse.com
14
© 2014 Littelfuse POWR-GARD
®
Products
Technical Application Guide
UL/CSA FUSE CLASSES AND APPLICATIONS
Overcurrent and short-circuit protection of power and lighting feeders and branch circuits
FUSES FOR SUPPLEMENTARY OVERCURRENT PROTECTION
STANDARDS: UL Standard 248-14; CSA Standard C22.2,
No. Three
NOTE: Fuses may be rated for AC and/or DC when suitable for
such
(1) MICRO FUSES
Voltage ratings: UL, 125 volts; CSA, 0-250 volts
Current ratings: UL, 0-10 amps; CSA, 0-60 amps
Interrupting rating: 50 amps rms symmetrical
(2) MINIATURE FUSES (CSA classifies these as Supplemental Fuses)
Voltage ratings: UL, 125 or 250 volts; CSA, 0-600 volts
Current ratings: UL, 0-30 amps; CSA, 0-60 amps
Interrupting rating: 10,000 amps rms symmetrical
(3) MISCELLANEOUS CARTRIDGE FUSES (CSA classifies these as
Supplemental Fuses)
Voltage ratings: UL, 125-1000 volts; CSA, 0-100 volts
Current ratings: UL, 0-30 amps; CSA 0-60 amps
Interrupting ratings: 10,000, 50,000, or 100,000 amps rms symmetrical
Time delay (Optional); Minimum delay at 200% fuse rating:
5 seconds for fuses rated 3 amps or less
12 seconds for fuses rated more than 3 amps
LF SERIES: BLF, BLN, BLS, FLA, FLM, FLQ, FLU, KLK, KLQ KLKD, SPF
NOTE: Littelfuse electronic fuses are also covered by these standards; see electronic section of this catalog, or littelfuse.com for complete listing.
SPECIAL PURPOSE FUSES
There are no UL Standards covering this category of fuses. These fuses have special characteristics designed to protect special types of electrical or electronic equipment such as diodes, SCR, transistors, thyristors, capacitors, integrally fused circuit breakers, parallel cable runs, etc.
Fuses may be UL Recognized for use as a component in UL Listed equipment.
UL Recognized fuses are tested for characteristics such as published interrupting capacity. They are also covered by UL re-examination service.
Non-renewable
VOLTAGE RATINGS: up to 1000 volts AC and/or DC
AMPERE RATINGS: up to 6000 amperes
INTERRUPTING RATINGS: up to 200,000 amperes
Many of these fuses are extremely current limiting. When considering application of these fuses, or if you have special requirements, contact Littelfuse Technical Support
Group for assistance.
LF SERIES: KLC, LA15QS, LA30QS, LA50QS, LA60QS, LA60X, LA70QS, LA100P,
LA120X, LA070URD, LA130URD, L15S, L25S, L50S, L60S, L70S, JLLS 900 amp through 1200 amp
Non-Current Limiting
CLASS H
STANDARDS:
UL Standard 248-6
CSA Standard C22.2, No. 59.1
Also known as NEMA Class H, and sometimes referred to as “NEC” or “Code” fuses
VOLTAGE RATINGS:
AMPERE RATINGS:
250 and 600 volts, AC
0-600 amps
INTERRUPTING RATINGS:
10,000 amps rms symmetrical
Two types: one-time and renewable
Physically interchangeable with UL Classes K1 & K5;
Fits UL Class H fuse holders which will also accept K1, K5, RK5, and RK1 fuses.
Manufacturers are upgrading Class H One-time fuses to Class K5 per UL Standard
248-9D, See Class K fuses.
ONE-TIME FUSES
(NON-RENEWABLE)
Time delay: Optional
Time-delay fuses must hold 500% current rating for a minimum of ten seconds.
LF SERIES: NLKP
RENEWABLE FUSES
Only Class H fuses may be renewable. While time delay is optional, no renewable fuses meet requirements for time delay.
Some renewable fuses have a moderate amount of time delay, referred to as “time lag” to differentiate from true time delay.
LF SERIES: Discontinued - Please cross to RK5 or RK1 class fuses
PLUG FUSES
STANDARDS:
VOLTAGE RATINGS:
AMPERE RATINGS:
INTERRUPTING RATINGS:
UL Standard 248-11,
CSA Standard C22.2, No. 59.1
125 volts AC only
0-30 amps
10,000 amps rms symmetrical. Interrupting rating need not be marked on fuse.
Two types: Edison-base and Type S
EDISON-BASE: Base is same as standard light bulb. All amp ratings interchange able. NEC
®
permits Edison-base plug fuses to be used only as replacements for existing fuses, and only when there is no evidence of tampering or overfusing.
TYPE S: Not interchangeable with Edison-base fuses unless non-removable Type
S fuse adapter is installed in Edison-base fuse socket. To prevent overfusing, adapters have three ampere ratings: 10-15, 16-20, and 21-30 amps.
Time delay: Fuses may be time delay, if so, they are required to hold 200% of rating for 12 seconds minimum.
NOTE: Plug fuses may be used where there is not more than 125 volts between conductors or more than 150 volts from any conductor to ground. This permits their use in 120/240 volts grounded, single-phase circuits.
LF SERIES: Edison-base: TOO, TLO
Type
Type
SOO,
© 2014 Littelfuse POWR-GARD
®
Products
15
littelfuse.com
Technical Application Guide
TERMS AND DEFINITIONS
Adjustable Alarm Level – A setting on a protection relay at which an LED or an output contact operates to activate a visual or audible alarm.
Adjustable Time Delay – A setting on a protection relay that determines the time between the fault detection and relay operation.
AIC or A.I.C. – See Interrupting Capacity.
AIR or A.I.R. – See Interrupting Rating.
Alarm Relay Contact – The output of the relay that acts as a switch and is connected to a visual or audible alarm.
Ambient Temperature – The air temperature surrounding a device. For fuses or circuit breakers in an enclosure, the air temperature within the enclosure.
Ampacity – The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating. It is sometimes informally applied to switches or other devices which are more properly referred to by their ampere rating.
Ampere Rating – The current rating, in amperes, that is marked on fuses, circuit breakers, or other equipment.
Ampere-Squared-Seconds (I
2
t) – A means of describing the thermal energy generated by current flow. When a fuse is interrupting a current within its current-limiting range, the term is usually expressed as melting, arcing, or total clearing I
2 t.
• Melting I 2 t is the heat energy passed by a fuse after an overcurrent occurs and until the fuse link melts. It equals the rms current squared multiplied by the melting time in seconds. For times less than 0.004 seconds, melting I
2 t approaches a constant value for a given fuse.
• Arcing I
2 t is the heat energy passed by a fuse during its arcing time. It is equal to the rms arcing current squared (see definition below), multiplied by arcing time.
• Clearing I
2 t (also Total Clearing I
2 t) is the ampere-squared seconds (I 2 t) through an overcurrent device from the inception of the overcurrent until the current is completely interrupted. Clearing I 2
Arcing I
2 t.
t is the sum of the Melting I 2 t plus the
Analog Output – A 0–1 mA, 4–20 mA or 0–5 Vdc signal from a protection relay used to pass information to a device or controller.
Arc-Blast – A pressure wave created by the heating, melting, vaporization, and expansion of conducting material and surrounding gases or air.
Arc-Flash – The sudden release of heat energy and intense light at the point of an arc. Can be considered a short-circuit through the air, usually created by accidental contact between live conductors.
Arc Gap – The distance between energized conductors or between energized conductors and ground. Shorter arc gaps result in less energy being expended in the arc, while longer gaps reduce arc current. For 600 volts and below, arc gaps of
1.25 inches (32 mm) typically produce the maximum incident energy.
Arc Rating – A rating assigned to material(s) that relates to the maximum incident energy the material can resist before break open of the material or onset of a second-degree burn. The arc rating is typically shown in cal/cm².
Arcing Current (See
Figure 11) – The current that flows through the fuse after the fuse link has melted and until the circuit is interrupted.
Peak current which would occur without current limitation
Peak Let-Thru Current
Arcing
Current
Arcing Energy (I
2 t)
Melting
Current
Melting Energy (I
2 t)
Time
Melting
Time
Arcing
Time
Figure 11 – Arcing and melting currents plus arcing, melting and clearing times
Arcing I
2
t – See Ampere-Squared-Seconds (I 2 t).
Arcing Fault – A short-circuit that arcs at the point of fault. The arc impedance (resistance) tends to reduce the short-circuit current. Arcing faults may turn into bolted faults by welding of the faulted components. Arcing faults may be phase-to-phase or phase-to-ground.
Arcing Time (See Figure 11) – The time between the melting of a fuse link or parting of circuit breaker contacts, until the overcurrent is interrupted.
Arc Voltage (See Figure 12) – Arc voltage is a transient voltage that occurs across an overcurrent protection device during the arcing time. It is usually expressed as peak instantaneous voltage (V peak
or E peak
), or on rare occasion as rms voltage.
Asymmetrical Current – See Symmetrical Current.
Available Short-Circuit Current (also Available or
Prospective Fault Current) – The maximum rms Symmetrical
Current that would flow at a given point in a system under bolted-fault conditions. Short-circuit current is maximum during the first half-cycle after the fault occurs. See definitions of
Bolted Fault and Symmetrical Current.
littelfuse.com
16
© 2014 Littelfuse POWR-GARD
®
Products
Technical Application Guide
TERMS AND DEFINITIONS
PEAK
INSTANTANEOUS ARC VOLTAGE
183% OF CYCLEPEAK
RESTORED VOLTAGE
Figure 12 – Transient overvoltage during arcing time
Figure 2
Blade Fuse – See Knife Blade Fuse.
Body – The part of a fuse enclosing the fuse elements and supporting the contacts. Body is also referred to as cartridge, tube, or case.
Bolted Fault – A short-circuit that has no electrical resistance at the point of the fault. It results from a firm mechanical connection between two conductors, or a conductor and ground. Bolted faults are characterized by a lack of arcing.
Examples of bolted faults are a heavy wrench lying across two bare bus bars, or a crossed-phase condition due to incorrect wiring
Boundaries of Approach – Protection boundaries established to protect personnel from shock and Arc-Flash hazards.
Calorie – The amount of heat needed to raise the temperature of one gram of water by one degree Celsius.1 cal/cm² is equivalent to the exposure on the tip of a finger by a cigarette lighter for one second.
Cartridge Fuse – A fuse that contains a current-responsive element inside a tubular fuse body with cylindrical ferrules (end caps).
Case Size (also Cartridge Size) – The maximum allowable ampere rating of a cartridge fuse having defined dimensions and shape. For example, case sizes for UL Listed Class H, K, J,
RK1, and RK5 are 30, 60, 100, 200, 400, and 600 amperes. The physical dimensions vary with fuse class, voltage, and ampere rating. UL Standards establish the dimensions for each UL
Fuse Class. This catalog’s product section contains case size dimensions for all Littelfuse POWR-GARD
®
fuses.
Clearing I
2
t – See Ampere-Square-Seconds (I
2 t).
Clearing Time (see Figure 11) – The time between the initiation of an overcurrent condition to the point at which the overcurrent is interrupted. Clearing Time is the sum of Melting Time and
Arcing Time.
Conformal Coating – Coating used to protect circuit boards from pollutants, corrosion, and mildew.
Contacts (Fuse) – The external metal parts of the fuse used to complete the circuit. These consist of ferrules, caps, blades or terminals, as shown in this catalog.
Coordination or Coordinated System – See Selective
Coordination.
Continuous Load – An electrical load where the maximum current is expected to continue for three hours or more.
CT Loop – The electrical circuit between a current transformer and a protection relay or monitoring device.
Current-Based Protection – Protection parameters (trip-levels/ data collection etc.) derived from current levels in a circuit.
Current-limiting Fuse (See
Figure 13) – A fuse which, when interrupting currents within its current-limiting range, reduces the current in the faulted circuit to a magnitude substantially less than that obtainable in the same circuit if the device was replaced with a solid conductor having comparable impedance.
To be labeled “current limiting,” a fuse must mate with a fuse block or fuse holder that has either a rejection feature or dimensions that will reject non-current-limiting fuses.
Current which would flow if not interrupted
Current before fault
Fault occurs
Time
Fuse opens and clears short circuit in less than ½ cycle
Arc is extinguished
Figure 13 – Current-limiting Fuse
Current-limiting Range - For an individual overcurrent protective device, the current-limiting range begins at the lowest value of rms symmetrical current at which the device becomes current-limiting (the threshold current) and extends to the maximum interrupting capacity of the device. See definitions of Threshold Current and Interrupting Capacity.
Current Rating – See Ampere Rating.
Current Transformer (CT) – A transformer that produces a current in its secondary circuit in a known proportion to current in its primary circuit.
Data Logging – Collecting and storing information in a format that can be reviewed for trending, troubleshooting and reporting.
DFT (Discrete Fourier Transform) Harmonic Filter – An algorithm used to measure the fundamental component of current and voltage and reject harmonics. This allows lower trip settings and eliminates nuisance trips due to harmonics.
© 2014 Littelfuse POWR-GARD
®
Products
17
littelfuse.com
Technical Application Guide
TERMS AND DEFINITIONS
Distance to Arc – Refers to the distance from the receiving surface to the arc center. The value used for most calculations is typically 18 inches.
Dual-Element Fuse – A fuse with internal construction consisting of a separate time-delay overload element(s) that interrupts overcurrents up to approximately 500%-600% of its nominal rating, plus separate fuse links that quickly open higher value currents. All dual-element fuses have time delay, but, since there are other methods of achieving time delay, not all time-delay fuses have dual-element construction. See Time-
Delay Fuse.
EFCT (Earth Fault Current Transformer) – A current transformer engineered to accurately detect low level groundfault current.
Electrical Hazard Analysis – A study performed to identify the potential electrical hazards to which personnel may be exposed.
The analysis should address both shock and Arc-Flash hazards.
Electrically Safe Work Condition – Condition where the equipment and or circuit components have been disconnected from electrical energy sources, locked/tagged out, and tested to verify all sources of power are removed.
Element – A fuse’s internal current-carrying components that melt and interrupt the current when subjected to an overcurrent of sufficient duration or value. Also called fuse link.
Fail-Safe Mode (also known as Under Voltage or UV) –
Output relay is energized during normal (not tripped) operation.
If the protection relay loses supply voltage, the system will trip or alarm.
Fast-Acting Fuse – May also be termed Normal-opening fuse, this is a fuse that has no intentional or built-in time delay. Actual opening time is determined by the fuse class, the overcurrent, and other conditions. Fast-acting is indicated on the fuse label by “Fast-Acting”, “F-A”, “F”, or other suitable marking.
Fault – Same as Short-Circuit and used interchangeably.
Fault Current – The current that flows when a phase conductor is faulted to another phase or ground.
Feeder Protection – Overcurrent or overvoltage devices installed on a feeder circuit to supplement, compliment or replace downstream protective devices.
Filler – A material, such as granular quartz, used to fill a section or sections of a fuse and aid in arc quenching.
Filter – An algorithm used to measure the fundamental component of current and voltage and reject harmonics. This allows lower trip settings and eliminates nuisance trips due to harmonics.
Flash Hazard Analysis – A study that analyzes potential exposure to Arc-Flash hazards. The outcome of the study establishes Incident Energy levels, Hazard Risk Categories, littelfuse.com
18
Flash Protection Boundaries, and required PPE. It also helps define safe work practices.
Flash Protection Boundary – A protection boundary established to protect personnel from Arc-Flash hazards.
The Flash Protection Boundary is the distance at which an unprotected worker can receive a second-degree burn to bare skin.
Fuse – An overcurrent protective device consisting of one or more current carrying elements enclosed in a body fitted with contacts, so that the fuse may be readily inserted into or removed from an electrical circuit. The elements are heated by the current passing through them, thus interrupting current flow by melting during specified overcurrent conditions.
Ground Continuity Monitor - A protection relay that continuously monitors a ground conductor and trips if this conductor opens or shorts to the ground-check conductor.
Ground-Fault – Unintentional contact between a phase conductor and ground or equipment frame. The words
“ground” and “earth” are used interchangeably when it comes to electrical applications.
Ground-Fault Current – The current that returns to the supply neutral through the ground-fault and the ground-return path.
Ground-Fault Protection – A system that protects equipment from damaging ground-fault current by operating a disconnecting means to open all ungrounded conductors of a faulted circuit. This protection is at current levels less than those required to operate a supply circuit overcurrent device.
Ground-Fault Relay – A protection relay designed to detect a phase-to-ground-fault on a system and trip when current exceeds the pickup setting for greater than the trip time setting.
Hazard Risk Category – A classification of risks (from 0 to
4) defined by NFPA 70E
®
. Each category requires PPE and is related to incident energy levels.
High-Resistance Grounding – Achieved when a neutralground resistor (NGR) is used to limit the current to a low level.
Typically high-resistance grounding is 25 A and lower. See Low-
Resistance Grounding.
I 2
t – See Ampere-Squared-Seconds (I 2 t).
IEEE Device Numbers – The devices in switching equipment are referred to by numbers, according to the functions they perform. These numbers are based on a system which has been adopted as standard for automatic switchgear by IEEE.
This system is used on connection diagrams, in instruction books and in specifications.
IEC Type 2 Protection – Fused protection for control components that prevents damage to these components under short-circuit conditions. See definition of No Damage.
© 2014 Littelfuse POWR-GARD
®
Products
Technical Application Guide
TERMS AND DEFINITIONS
Incident Energy – The amount of thermal energy impressed on a surface generated during an electrical arc at a certain distance from the arc. Typically measured in cal/cm 2 .
Instantaneous Peak Current (I p
or I peak
) – The maximum instantaneous current value developed during the first half-cycle
(180 electrical degrees) after fault inception. The peak current determines magnetic stress within the circuit. See Symmetrical
Current.
Insulation Monitoring – Monitoring the resistance from phase to ground to detect insulation breakdown on a system.
Interrupting Capacity (AIC) – The highest available symmetrical rms alternating current (for DC fuses the highest direct current) at which the protective device has been tested, and which it has interrupted safely under standardized test conditions. The device must interrupt all available overcurrents up to its interrupting capacity. Also commonly called interrupting rating. See Interrupting Rating below.
Interrupting Rating (IR, I.R., AIR or A.I.R.) – The highest RMS symmetrical current, at specified test conditions, which the device is rated to interrupt. The difference between interrupting capacity and interrupting rating is in the test circuits used to establish the ratings.
Inverse-time Characteristics – A term describing protective devices whose opening time decreases with increasing current.
IR or I.R. (also AIR or A.I.R.) – See Interrupting Rating above.
Kiloamperes (kA) – 1,000 amperes.
Knife Blade Fuse – Cylindrical or square body fuses with flat blade terminals extending from the fuse body. Knife blades may be designed for insertion into mating fuse clips and/or to be bolted in place. Knife blade terminals may include a rejection feature that mates with a similar feature on a fuse block of the same class.
Leakage Current – Very low level ground-fault current, typically measured in milliamperes (mA, thousandths of amperes).
Limited Approach Boundary – An approach boundary to protect personnel from shock. A boundary distance is established from an energized part based on system voltage. To enter this boundary, unqualified persons must be accompanied with a qualified person and use the proper PPE.
Low-Resistance Grounding – A Resistance Grounded System that allows high currents to flow during a ground-fault. Typically
100A and higher is considered Low-Resistance grounding. See
High-Resistance Grounding.
Melting Current (see Figure 11) – The current that flows through the fuse from the initiation of an overcurrent condition to the instant arcing begins inside the fuse.
Melting I
2
t – See Ampere-Squared-Seconds (I
2 t).
Melting Time (see Figure 11) – The time span from the initiation of an overcurrent condition to the instant arcing begins inside the fuse.
Motor Protection – Overload protection designed to protect the windings of a motor from high current levels. Modern motor protection relays add many additional features, including metering, data logging and communications.
NEC – In general, the National Electrical Code ® (NEC ® ).
Specifically, as referenced herein, NEC refers to NFPA
Standard 70, National Electrical Code, National Fire Protection
Association, Quincy, MA 02269.
Sections of the NEC reprinted herein, and/or quotations there from, are done so with permission. The quoted and reprinted sections are not the official position of the National
Fire Protection Association which is represented only by the
Standard in its entirety. Readers are cautioned that not all authorities have adopted the most recent edition of the NEC; many are still using earlier editions.
Neutral Grounding Resistor (NGR) – A current-limiting resistor connecting the power-system neutral to ground.
No Damage – A term describing the requirement that a system component be in essentially the same condition after the occurrence of a short-circuit as prior to the short-circuit.
Non-renewable Fuse – A fuse that must be replaced after it has opened due to an overcurrent. It cannot be restored to service.
Normal-opening Fuse – See Fast-Acting Fuse.
Nuisance Trip – An undesired change in relay output due to misinterpreted readings.
One-time Fuse – Technically, any non-renewable fuse. However, the term usually refers to UL Class H fuses and to fast acting
UL Class K5 fuses. Such fuses are not current-limiting and do not have a rejection feature. One-time fuses are also referred to as “Code” fuses.
Open CT Hazard – An open-circuited CT secondary can develop a dangerously high voltage when the primary is energized.
Overcurrent – Any current larger than the equipment, conductor, or devices are rated to carry under specified conditions.
Overload – An overcurrent that is confined to the normal current path (e.g., not a short-circuit), which if allowed to persist, will cause damage to equipment and/or wiring.
Additional information regarding fuse applications for overload protection can be found earlier in this Technical Application
Guide.
© 2014 Littelfuse POWR-GARD
®
Products
19
littelfuse.com
Technical Application Guide
TERMS AND DEFINITIONS
Peak Let-through Current (See Figure 14) – The maximum instantaneous current that passes through an overcurrent protective device during its total clearing time when the available current is within its current-limiting range.
Peak current which would occur without current limitation
Peak Let-Thru Current
Time
Figure 14 – Peak Let-through Current
Phase Current – The current present in a phase conductor.
Phase Voltage – The voltage measured between a phase conductor and ground.
Power Factor (X/R) – As used in overcurrent protection, power factor is the relationship between the inductive reactance (X) and the resistance (R) in the system during a fault. Under normal conditions a system may be operating at a 0.85 power factor (85%). When a fault occurs, much of the system resistance is shorted out and the power factor may drop to 25% or less. This may cause the current to become asymmetrical. See definition of Symmetrical Current. The
UL test circuits used to test fuses with interrupting ratings exceeding 10,000 amperes are required to have a power factor of 20% or less. Since the power factor of test circuits tends to vary during test procedures, actual test circuits are usually set to a 15% power factor. The resulting asymmetrical current has an rms value of 1.33 times the available symmetrical rms. The instantaneous peak current of the first peak after the fault is
2.309 times the available symmetrical rms.
PPE – An acronym for Personal Protective Equipment. It can include clothing, tools, and equipment.
Primary Rating (for CTs) – The current rating of the primary side of a current transformer. The first number in the ratio 500:5 is the primary rating. Under ideal conditions 500 A of primary current flow through the CT will produce 5 A of current out the secondary terminals.
Prohibited Approach Boundary – An approach boundary to protect personnel from shock. Work in this boundary is considered the same as making direct contact with an energized part. Only qualified persons are allowed to enter this boundary and they must use the proper PPE.
Prospective Current – See Available Short-Circuit Current.
littelfuse.com
20
Protection Boundaries – Boundaries established to protect personnel from electrical hazards.
Pulsing – Modulating the ground-fault current on a resistance grounded system using a contactor to short out part of the NGR elements (or to open one of two NGRs connected in parallel).
Another version of pulsing is imposing a higher frequency signal on power lines and using a wand detector to locate the point of fault on a conductor.
QPL (Qualified Products List) – A list of approved fuses and holders that meet various Military specifications.
Qualified Person – A person who is trained, knowledgeable, and has demonstrated skills on the construction and operation of the equipment, and can recognize and avoid electrical hazards that may be encountered.
Rating – A designated limit of operating characteristics based on definite conditions such as current rating, voltage rating and interrupting rating.
Rectifier Fuse – See Semiconductor Fuse.
Rejection Feature – The physical characteristic(s) of a fuse block or fuse holder that prevents the insertion of a fuse unless it has the proper mating characteristics. This may be achieved through the use of slots, grooves, projections, or the actual physical dimensions of the fuse. This feature prevents the substitution of fuses of a Class or size other than the Class and size intended.
Relay – An electrical switch that opens and closes a contact
(or contacts) under the control of another circuit. Typically an electromagnet.
Renewable Element (also Renewable Link) – A renewable fuse current-carrying component that is replaced to restore the fuse to a functional condition after the link opens due to an overcurrent condition.
Renewable Fuse – A fuse that may be readily restored to service by replacing the renewable element after operation.
Resistance-Grounded System – An electrical system in which the transformer or generator neutral is connected to ground through a current-limiting resistor. See Solidly Grounded
System, Ungrounded System.
Restricted Approach Boundary – An approach boundary to protect personnel from shock. A boundary distance is established from an energized part based on system voltage.
Only qualified persons are allowed in the boundary and they must use the proper PPE.
Selective Coordination (See Figure 15) – In a selectively coordinated system, only the protective device immediately on the line side of an overcurrent opens. Upstream protective devices remain closed. All other equipment remains in service, which simplifies the identification and location of overloaded
© 2014 Littelfuse POWR-GARD
®
Products
Technical Application Guide
TERMS AND DEFINITIONS equipment or short-circuits. For additional information, refer to the Selective Coordination pages of this Technical
Application Guide.
A
B C D E
X
In a selective system:
For a fault at "X" only fuse "C" will open.
For a fault at "Y" only fuse "F" will open.
F G H J
Y
Figure 15 – Selective Coordination Example
Semiconductor Fuse – A fuse specifically designed to protect semiconductors such as silicon rectifiers, silicon-controlled rectifiers, thyristors, transistors, and similar components.
Sensitive Ground-Fault Protection – Protection designed to accurately detect extremely low ground-fault current levels without nuisance tripping.
Shock – A trauma subjected to the body by electrical current.
When personnel come in contact with energized conductors, it can result in current flowing through their body often causing serious injury or death.
Short-Circuit (See Figure 16) – A current flowing outside its normal path, caused by a breakdown of insulation or by faulty equipment connections. In a short-circuit, current bypasses the normal load. Current is determined by the system impedance
(AC resistance) rather than the load impedance. Short-circuit currents may vary from fractions of an ampere to 200,000 amperes or more.
Short-Circuit Current Rating (SCCR) – The prospective symmetrical fault current at a nominal voltage to which an apparatus or system is able to be connected without sustaining damage exceeding defined acceptance criteria.
Short-Circuit Rating – The maximum RMS symmetrical shortcircuit current at which a given piece of equipment has been tested under specified conditions, and which, at the end of the test is in essentially the same condition as prior to the test.
Short-circuit ratings (also called withstand ratings) apply to equipment that will be subjected to fault currents, but which are not required to interrupt them. This includes switches, busway (bus duct), switchgear and switchboard structures, motor control centers and transformers.
Most short-circuit ratings are based on tests which last three complete electrical cycles (0.05 seconds). However, if the equipment is protected during the test by fuses or by a circuit breaker with instantaneous trips, the test duration is the time required for the overcurrent protective device to open the circuit.
When protected as such during testing, the equipment instructions and labels must indicate that the equipment shall be protected by a given fuse class and rating or by a specific make, type, and rating of circuit breaker. Circuit breakers equipped with short-delay trip elements instead of instantaneous trip elements have withstand (short-circuit) ratings in addition to their interrupting rating. The breaker must be able to withstand the available fault current during the time that opening is delayed.
CURRENT FLOW
In a "normal" circuit, current is determined by load IMPEDANCE GEN.
(Heavy lines indicate increased current)
GEN.
Accidental connection creates fault
In a short-circuit, current is limited only by impedance of fault path.
Current may increase to many times load current.
Figure 16 – Current Flow in Normal and Short Circuit Situations
Solidly Grounded System – An electrical system in which the neutral point of a wye connected supply transformer is connected directly to ground.
Symmetrical Current – The terms “Symmetrical Current” and “Asymmetrical Current” describe an AC wave symmetry around the zero axis. The current is symmetrical when the peak currents above and below the zero axis are equal in value, as shown in Figure 17 (next page). If the peak currents are not equal, as shown in Figure 18, the current is considered asymmetrical. The degree of asymmetry during a fault is determined by the change in power factor (X/R) and the point in the voltage wave when the fault occurs. See definition of Power
Factor. In general, lower short-circuit power factors increase the degree of asymmetry.
© 2014 Littelfuse POWR-GARD
®
Products
21
littelfuse.com
Equal
Peaks
Technical Application Guide
TERMS AND DEFINITIONS
Symmertrical Current
Zero Axis
Equal
Peaks
Unequal
Peaks
Symmertrical Current
Zero Axis
Figure 18 – Asymmetrical Current
Threshold Current – The minimum current for a given fuse size and type at which the fuse becomes current-limiting. It is the lowest value of available rms symmetrical current that will cause the device to begin opening within the first 1/4 cycle (90 electrical degrees) and completely clear the circuit within 1/2 cycle (180 electrical degrees). The approximate threshold current can be determined from the fuse’s peak let-through charts.
(See Figure 19.)
4000
A
B
Fuse approximate threshold current = 4000A
Zero Axis
Peak let-through current
Asymmertrical Current
Threshold Ratio – Consists of the threshold current divided by the ampere rating of a specific type or class of overcurrent device. A fuse with a threshold ratio of 15 becomes currentlimiting at 15 times its current rating.
Time-Delay Fuse – Fuses designed with an intentional, built-in delay in opening. When compared to fast-opening fuses, timedelay fuses have an increased opening time for overcurrents between approximately 200% and 600% of the fuse’s current rating. Time-delay is indicated on the fuse label by “Time-Delay”,
“T-D”, “D”, or other suitable marking. Time-delay in the overload range (200%-600% of the fuse rating) permits the fuse to withstand system switching surges, motor starting currents, and other harmless temporary overcurrents.
UL Standards require time-delay Class H, K, RK1, RK5, and J fuses to hold 500% of their normal current rating for a minimum of 10 seconds. They must also pass the same opening time tests (135% and 200% of current rating) as fast acting fuses.
Time-delay Class CC, CD, G, Plug, and Miscellaneous fuses have different requirements. For more information, please refer to the corresponding descriptions provided in the Product
Information Section.
For the UL Standard, Class L fuses have no standard timedelay. The time-delay varies from series to series for a given manufacturer, as well as from manufacturer to manufacturer. For reference, Littelfuse KLPC series POWR-PRO
®
fuses hold 500% of rated current for a minimum of 10 seconds.
Ungrounded System – An electrical system in which no point in the system is intentionally grounded. This was most common in process industries where continuity of service during a singlephase-to-ground-fault was required.
Unqualified Person – A person that does not possess all the skills and knowledge or has not been trained for a particular task.
Voltage Rating – The maximum rms AC voltage and/or the maximum DC voltage at which the fuse is designed to operate.
For example, fuses rated 600 volts and below may be applied at any voltage less than their rating. There is no rule for applying
AC fuses in DC circuits such as applying the fuse at half its AC voltage rating. Fuses used on DC circuits must have DC ratings.
Withstand Rating – See Short-Circuit.
Available Fault Current Symmetrical RMS Amperes
Figure 19 – Determining Threshold Current from Peak
Let-through Chart littelfuse.com
22
© 2014 Littelfuse POWR-GARD
®
Products
Technical Application Guide
MOTOR PROTECTION TABLES
Selection of Class RK5 Fuses (FLNR_ID / FLSR_ID / IDSR Series) or POWR-PRO
®
Class
RK1 Fuses (LLNRK / LLSRK / LLSRK_ID Series) Based on Motor Full Load Amps
Using AC Motor Protection Tables to Select Fuse
Ratings
Time-delay RK1 and RK5 fuse ratings selected in accordance with the following recommendations also meet NEC
® requirements for Motor Branch circuit and Short-Circuit
Protection.
Selecting Fuses for Motor Running Protection
Based on Motor Horsepower
Motor horsepower and motor Full Load Amperes (FLA) shown are taken from NEC
®
Tables 430.248 through
430.250 covering standard speed AC motors with normal torque characteristics. Fuse ratings for motors with special characteristics may need to vary from given values.
If motor running protection will be provided by the fuses, select fuse ratings for correct type of motor from Motor
Protection Table Columns headed, “Without Overload
Relays.”
If overload relays will provide principal motor running protection, select fuse ratings for correct type of motor from Motor Protection Table Columns headed, “Back-up
Running Protection” or “With Overload Relays.” Fuse ratings selected from these columns coordinate with most UL Class
10 and 20 overload relays which covers over 90% of motor applications.
Selecting Fuses for Motor Running Protection
Based on Motor Actual Full Load Currents
Better protection is achieved when fuse ratings are based on motor actual FLA obtained from motor nameplates. Locate motor nameplate FLA in the column appropriate for the type of motor and type of protection required. Then select the corresponding ampere rating of the fuse from the first column of that line.
Motor Protection
White Paper
Download our white paper on motor protection at
littelfuse.com/technicalcenter
© 2014 Littelfuse POWR-GARD
®
Products
23
1
1
1
1
6
8
1 1
1 4
1 1
1
⁄
10
12
8
9
15
17 1
5
6
6
1
7
1
7
3
3
2
3
1
4
4
1
6
5
2
2
1
2
2 1
8
⁄
⁄
⁄
⁄
⁄
⁄
⁄
⁄
4
2
10
2
100
110
125
150
70
75
80
90
40
45
50
60
20
25
30
35
175
200
225
250
300
350
400
450
500
600
⁄
10
2
10
4
2
2
⁄
10
⁄
2
⁄
8
⁄
4
⁄
10
⁄
10
8
4
6
⁄
⁄
10
⁄
10
1 ⁄
2
10
⁄
10
15
1
⁄
10
1
⁄
8
2
3
⁄
100
⁄
10
1 ⁄
4
TIME DELAY
UL CLASS RK1
OR RK5 FUSE
AMPERE RATING
MOTOR RUNNING PROTECTION
(USED WITHOUT PROPERLY SIZED
OVERLOAD RELAYS)
MOTOR FULL-LOAD AMPS
BACK-UP MOTOR RUNNING
PROTECTION (USED WITH PROPERLY
SIZED OVERLOAD RELAYS)
MOTOR FULL-LOAD AMPS
MOTOR SERVICE
FACTOR OF 1.15 OR
GREATER OR WITH
TEMP. RISE NOT
OVER 40°C.
MOTOR SERVICE
FACTOR LESS
THAN 1.15 OR
WITH TEMP. RISE
GREATER
THAN 40°C.
MOTOR SERVICE
FACTOR OF 1.15 OR
GREATER OR WITH
TEMP. RISE NOT
OVER 40°C.
MOTOR SERVICE
FACTOR LESS
THAN 1.15 OR
WITH TEMP. RISE
GREATER
THAN 40°C
1.44-1.59
1.60-1.79
1.80-1.99
2.00-2.23
2.24-2.39
2.40-2.55
2.56-2.79
2.80-3.19
3.20-3.59
3.60-3.99
4.00-4.47
4.48-4.79
4.80-4.99
5.00-5.59
5.60-5.99
6.00-6.39
0.08-0.09
0.10-0.11
0.12-0.15
0.16-0.19
0.20-0.23
0.24-0.30
0.32-0.39
0.40-0.47
0.48-0.60
0.64-0.79
0.80-0.89
0.90-0.99
1.00-1.11
1.12-1.19
1.20-1.27
1.28-1.43
6.40-7.19
7.20-7.99
8.00-9.59
9.60-11.99
12.00-13.99
14.00-15.99
16.00-19.99
20.00-23.99
24.00-27.99
28.00-31.99
32.00-35.99
36.00-39.99
40.00-47.99
48.00-55.99
56.00-59.99
60.00-63.99
64.00-71.99
72.00-79.99
80.00-87.99
88.00-99.99
100.00-119.99
120.00-139.99
140.00-159.99
160.00-179.99
180.00-199.99
200.00-239.99
240.00-279.99
280.00-319.99
320.00-359.99
347.83-391.29
360.00-399.99
391.30-434.77
400.00-479.99
434.78-500.00
360.01-400.00
480.00-600.00
521.74-600.00
400.01-480.00
6.96-7.82
7.83-8.69
8.70-10.00
10.44-12.00
13.05-15.00
15.22-17.39
17.40-20.00
21.74-25.00
26.09-30.00
30.44-34.78
34.79-39.12
39.13-43.47
43.48-50.00
52.17-60.00
60.87-65.21
65.22-69.56
69.57-78.25
78.26-86.95
86.96-95.64
95.65-108.69
108.70-125.00
131.30-150.00
152.17-173.90
173.91-195.64
195.65-217.38
217.39-250.00
260.87-300.00
304.35-347.82
1.57-1.73
1.74-1.95
1.96-2.17
2.18-2.43
2.44-2.60
2.61-2.78
2.79-3.04
3.05-3.47
3.48-3.91
3.92-4.34
4.35-4.86
4.87-5.21
5.22-5.43
5.44-6.08
6.09-6.52
6.53-6.95
0.09-0.10
0.11-0.125
0.14-0.15
0.18-0.20
0.22-0.25
0.27-0.30
0.35-0.40
0.44-0.50
0.53-0.60
0.70-0.80
0.87-0.97
0.98-1.08
1.09-1.21
1.22-1.30
1.31-1.39
1.40-1.56
6.53-6.96
6.97-7.83
7.84-8.70
8.71-10.43
10.44-13.04
13.05- 15.21
15.22-17.39
17.40-21.74
21.75-26.09
26.10-30.43
30.44-37.78
37.79-39.13
39.14-43.48
43.49-52.17
52.18-60.87
60.88-65.22
65.23-69.57
69.58-78.26
78.27-86.96
86.97-95.65
95.66-108.70
108.71-130.43
130.44-152.17
152.18-173.91
1.40-1.57
1.58-1.74
1.75-1.96
1.97-2.17
2.18-2.43
2.44-2.60
2.61-2.78
2.79-3.04
3.05-3.48
3.49-3.91
3.92-4.35
4.36-4.87
4.88-5.22
5.23-5.43
5.44-6.09
6.10-6.52
0-0.09
0.10-0.11
0.12-0.13
0.14-0.17
0.18-0.22
0.23-0.26
0.27-0.35
0.36-0.43
0.44-0.52
0.53-0.70
0.71-0.87
0.88-0.98
0.99-1.09
1.10-1.22
1.23-1.30
1.31-1.39
6.01-6.40
6.41-7.20
7.21-8.00
8.01-9.60
9.61-12.00
12.01-14.00
14.01-16.00
16.01-20.00
20.01-24.00
24.01-28.00
28.01-32.00
32.01-36.00
36.01-40.00
40.01-48.00
48.01-56.00
56.01-60.00
60.01-64.00
64.01-72.00
72.01-80.00
80.01-88.00
88.01-100.00
100.01-120.00
120.01-140.00
140.01-160.00
1.29-1.44
1.45-1.60
1.61-1.80
1.81-2.00
2.01-2.24
2.25-2.40
2.41-2.56
2.57-2.80
2.81-3.20
3.21-3.60
3.61-4.00
4.01-4.48
4.49-4.80
4.81-5.00
5.01-5.60
5.61-6.00
0-0.08
0.09-0.10
0.11-0.12
0.13-0.16
0.17-0.20
0.21-0.24
0.25-0.32
0.33-0.40
0.41-0.48
0.49-0.64
0.65-0.80
0.81-0.90
0.91-1.00
1.01-1.12
1.13-1.20
1.21-1.28
160.01-180.00
180.01-200.00
173.92-195.62
195.63-217.39
200.01-240.00
217.40-260.87
240.01-280.00
260.88-304.35
280.01-320.00
320.01-360.00
304.36-347.83
347.84-391.30
391.31-434.78
434.79-521.74
littelfuse.com
Technical Application Guide
MOTOR PROTECTION TABLES
Selection of Class RK5 Fuses (FLNR_ID / FLSR_ID / IDSR Series) or POWR-PRO
®
Class
RK1 Fuses (LLNRK / LLSRK / LLSRK_ID Series) Based on Motor Horsepower
3
1
⁄
3
1 ⁄
2
1
⁄
6
1
⁄
4
1
⁄
4
1
1
⁄
2
2
3
5
7
1
⁄
2
10
1
⁄
4
1
1
⁄
2
2
1
⁄
6
1
⁄
4
3
1
⁄
3
1
⁄
2
15
20
25
30
3
5
7
1
⁄
2
10
3
1
⁄
2
1
⁄
4
1
1
⁄
2
2
40
50
60
75
100
125
150
15
20
25
30
3
5
7
1
⁄
2
10
3
1
⁄
2
1
⁄
4
1
1
⁄
2
2
100
125
150
200
40
50
60
75
MOTOR
HP
6.9
8
10
12
2.2
2.9
3.6
4.9
17
28
40
50
32.2
48.3
62.1
78.2
92
120
150
177
2.5
3.7
4.8
6.9
7.8
11
17.5
25.3
221
285
359
414
80
104
130
154
28
42
54
68
192
248
312
360
480
6.8
9.6
15.2
22
2.2
3.2
4.2
6.0
FULL LOAD
AMPS
4.4
5.8
7.2
9.8
13.8
16
20
24
WITHOUT OVERLOAD
RELAYS
S.F. = 1.15 OR
MORE, TEMP
RISE NOT
OVER 40°C
S.F. = LESS
THAN 1.15 OR
TEMP RISE
MORE THAN
40°C
WITH OVERLOAD RELAYS
S.F. = 1.15 OR
MORE, TEMP
RISE NOT
OVER 40°C
120 VOLT 1-PHASE MOTORS (120V CIRCUIT)
5
7
9
12
15
20
25
30
5
6
1
⁄
4
17
8
10
15
1
20
25
⁄
2
5
6
⁄
10
7
1
⁄
2
9
15
17
1
⁄
2
20
25
30
10
12
15
20
3
1
⁄
2
4
1
⁄
2
5
6
⁄
10
8
35
50
60
230 VOLT 1-PHASE MOTORS (240V CIRCUIT)
2
1
⁄
2
2
1
⁄
2
3
2
⁄
10
4
5
6
⁄
10
7 1
9
10
12
⁄
2
17
1
⁄
2
30*
45
50
2
8
⁄
10
4
4
1
⁄
2
6
1
⁄
4
9
10
15
15
25
35
50
70
200 VOLT 3-PHASE MOTORS (208V CIRCUIT)
3
60
75
90
110
150
175
200*
250
350
400*
500
12
20
30*
40
8
9
4
1
⁄
2
6
2
8
⁄
10
4
5
6
⁄
10
7
1
⁄
2
8
12
20
25*
35
50
70
80
100*
125
150
200*
250
300
400*
450
3
2
⁄
10
5
6
1
⁄
4
7
1
⁄
2
125
150
200
225
300
400
450
600
45
70†
80
100
10
15
25
35
230 VOLT 3-PHASE MOTORS (240V CIRCUIT)
2
8
⁄
10
50
60*
80
100
125
150
175
225
4
5
7
1
⁄
2
8
12
17
1
⁄
2
25
35
300
350
450
600
2
1
⁄
2
3
4
1
⁄
2
6
1
⁄
4
7
1 ⁄
2
1
10
75
90
⁄
2
17
1
⁄
2
25
30*
45
60*
110
150
175
200*
250
350
400*
500
100
150
175
200
35
60
70
90
250
350
400
450
600
9
12
20
30
2
8
⁄
10
4
5
6
⁄
10
7
1
⁄
2
S.F. = LESS
THAN 1.15 OR
TEMP RISE
MORE THAN
40°C
5
6
12
17
7
9
⁄
1
20
25
30
10
⁄
8
10
12
15
2
8
⁄
10
3
1
⁄
2
4
1
⁄
2
6
20
35
50
60
110
150
175
225
40
60
75
90
9
15
25
30*
3
4
1
⁄
2
6
8
300
350
450
500
2
100
125
150
200
35
50
70
80
225
300
400
450
600
2
8
⁄
10
4
5
7
1
⁄
2
8
12
17
1
⁄
2
30
SWITCH OR
FUSE CLIP
RATING
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
60
60
60
60
60
100
100
200
200
200
400
30
30
30
60
30
30
30
30
400
400
600
600
60
60
100
100
100
200
200
200
400
400
400
600
600
30
30
30
30
30
30
30
30
10
15
20
25
2
3
5
7
1
⁄
2
1
⁄
2
3
⁄
4
1
1
1 ⁄
2
75
100
125
150
200
30
40
50
60
20
25
30
40
5
7
1
⁄
2
10
15
1 ⁄
2
3
⁄
4
1
1
1
⁄
2
2
3
50
60
75
100
125
150
200
MOTOR
HP
40
54
65
77
14
21
27
34
96
124
156
180
240
3.4
4.8
7.6
11
1.1
1.6
2.1
3.0
32
41
52
62
11
17
22
27
77
99
125
144
192
2.7
3.9
6.1
9
0.9
1.3
1.7
2.4
FULL LOAD
AMPS
WITHOUT OVERLOAD
RELAYS
S.F. = 1.15 OR
MORE, TEMP
RISE NOT
OVER 40°C
S.F. = LESS
THAN 1.15 OR
TEMP RISE
MORE THAN
40°C
WITH OVERLOAD RELAYS
S.F. = 1.15 OR
MORE, TEMP
RISE NOT
OVER 40°C
S.F. = LESS
THAN 1.15 OR
TEMP RISE
MORE THAN
460 VOLT 3-PHASE MOTORS (480V CIRCUIT)
1
4
⁄
10
2
2
1
⁄
2
3 1
4
⁄
2
5
6
⁄
10
9
12
17 1 ⁄
2
25
30*
40
50
60*
80
90
110
1
1
⁄
4
1
8
⁄
10
3
2
1
⁄
4
2
5
8
⁄
10
3
1
⁄
2
12
15
20
30*
35
45
60*
70
80
1
4
⁄
10
2
2
8
⁄
10
4
4
1
⁄
2
17
6
10
15
1
30
35
45
50
70
⁄
2
150
175
225
300
110
125
175
200*
90
100
125
175
200
225
250 300
575 VOLT 3-PHASE MOTORS (600V CIRCUIT)
80
110
125
150
200*
35
45
60
70
12
17
1
⁄
2
25
30*
1
1
4
⁄
10
1
8
⁄
10
2
1
⁄
2
2
8
⁄
10
4
7
10
25
30*
40
50
7
1
⁄
2
10
12
20
1 1 ⁄
8
1
6
⁄
10
2
3
3
2
⁄
10
4
1
⁄
2
60
75
90
110
150
175
225
30
35
40
60
8
12
15
25
1 1 ⁄
8
1
6
⁄
10
2
1
⁄
4
3
3
1
⁄
2
5
70†
80
100
125
175
200
250
40°C
9
15
17 1
25
⁄
2
35
40
1
4
⁄
10
2
2
1
⁄
2
3 1 ⁄
2
4
5
6
⁄
10
50
60*
75
90
125
150
200
225
300
30
35
40
50
7
1
⁄
2
12
15
20
1 1 ⁄
8
1
6
⁄
10
2
3
3
2
⁄
10
4
1
⁄
2
60
75
90
125
150
175
225
SWITCH OR
FUSE CLIP
RATING
30
30
60
60
60
100
100
100
200
200
200
400
400
30
30
30
30
30
30
30
30
30
30
30
60
60
60
60
100
100
200
200
200
400
30
30
30
30
30
30
30
30
NOTES
S.F. = Motor Service Factor
* Fuse Reducers Required
† 100 Amp Switch Required
Motor Protection
White Paper
Download our white paper on motor protection at
littelfuse.com/technicalcenter
littelfuse.com
24
© 2014 Littelfuse POWR-GARD
®
Products
Technical Application Guide
MOTOR PROTECTION TABLES
Selection of POWR-PRO
®
Class J Fuses (JTD_ID / JTD Series)
Based on Motor Full Load Amps
MOTOR F.L.A.
0.00 – 0.60
0.61 – 0.80
0.81 – 1.00
1.01 – 1.20
1.21 – 1.65
1.66 – 2.00
2.01 – 2.40
2.41 – 3.30
3.31 – 4.10
4.11 – 4.90
4.91 – 6.40
6.41 – 8.00
8.01 – 9.80
9.81 – 12.0
JTD_ID / JTD
AMPERE RATING
2
2
1
⁄
2
5
6
3
4
8
10
12
15
8
⁄
10
1
1
1
1
1
⁄
⁄
4
2
MOTOR F.L.A.
12.1 – 14.5
14.6 – 17.0
17.1 – 21.0
21.1 – 25.0
25.1 – 28.5
28.6 – 34.0
34.1 – 37.0
37.1 – 41.0
41.1 – 48.0
48.1 – 52.0
52.1 – 59.0
59.1 – 66.0
66.1 – 76.0
JTD_ID / JTD
AMPERE RATING
70
80
90
100
40
45
50
60
17
1
/
2
20
25
30
35
MOTOR F.L.A.
76.1 – 84.0
84.1 – 90.0
90.1 – 102
103 – 125
126 – 144
145 – 162
163 – 180
181 – 204
205 – 240
241 – 288
289 – 312
313 – 360
361 – 432
NOTE: For severe motor starting conditions, fuses may be sized up to 225% motor F.L.A. (See NEC ® Article 430.52 for Exceptions)
JTD_ID / JTD
AMPERE RATING
110
125
150
175
200
225
250
300
350
400
450
500
600
Selection of CCMR Time-Delay Fuses Based on Motor Full Load Amps
MOTOR FULL LOAD CURRENT (F.L.A.)
FOR MOTORS WITH AN ACCELERATION
TIME OF 2 SECONDS OR LESS
FOR MOTORS WITH AN ACCELERATION
TIME OF 5 SECONDS OR LESS
MIN. F.L.A. (1)
8.9
11.5
14.3
20.7
23.7
26.6
30.0
35.5
4.6
5.2
5.8
6.9
3.5
3.6
4.1
4.3
2.3
2.6
2.9
3.3
1.2
1.5
1.8
2.1
0.6
0.8
0.9
1.1
0.2
0.3
0.4
0.5
MAX F.L.A. (3)
13.5
15.8
17.8
23.3
26.7
30.0
33.3
40.0
6.9
7.7
8.9
10.0
5.4
5.7
5.8
6.2
3.9
4.3
4.8
5.2
2.1
2.6
3.0
3.4
1.0
1.1
1.3
1.4
0.2
0.4
0.6
0.7
MIN. F.L.A. (1)
8.9
11.2 (2)
13.4 (2)
16.1
18.4
20.7
23.0
27.6
4.6
5.2
5.8
6.9
3.5
3.6
4.1
4.3
2.3
2.6
2.9
3.3
1.2
1.5
1.8
2.1
0.6
0.8
0.9
1.1
0.2
0.3
0.4
0.5
MAX F.L.A. (3)
10.0
11.8
13.4
17.9
20.5
23.1
25.6
30.1
5.2
5.8
6.6
7.7
4.1
4.2
4.3
4.6
3.3
3.4
3.7
4.0
2.1
2.6
3.0
3.2
0.9
1.0
1.1
1.2
0.2
0.4
0.5
0.6
1 Based on NEC ® requirement limiting the rating of time-delay fuses to 175% of motor
F.L.A., or next higher rating.
2 Based on NEC ® exception permitting fuse rating to be increased, but not to exceed,
225% motor F.L.A., however per NEC sized up to 400% of motor F.L.A.
® Article 430.52 Class CC (0-30) fuses can now be
3 Based on Littelfuse CCMR time-delay characteristics.
FOR MOTORS WITH AN ACCELERATION
TIME OF 8 SECONDS OR LESS
MIN F.L.A. (2)
6.8
9.0
10.0
15.6
17.8
20.0
22.3
26.7
4.0
4.5
5.4
6.7
2.8
3.2
3.4
3.6
2.0
2.3
2.5
2.7
1.2
1.4
1.6
1.8
0.6
0.7
0.8
0.9
0.2
0.3
0.4
0.5
MAX F.L.A. (3)
9.0
11.0
15.0
15.9
18.2
20.4
22.7
27.3
4.5
4.9
5.5
6.7
3.5
3.7
3.8
4.2
2.8
2.8
3.1
3.4
1.8
2.3
2.6
2.8
0.8
0.9
1.0
1.1
0.2
0.3
0.5
0.6
CCMR
AMPERE RATING
15
20
25
30
10
12
8
9
35
40
45
50
60
6
6
1 ⁄
4
7
7
1 ⁄
2
2
2
1
⁄
2
3
3
1
⁄
2
4
4
1
⁄
2
5
5
6
⁄
10
1
1
3 ⁄
10
1 ⁄
2
8 ⁄
10
1
1
1 ⁄
4
1 ⁄
2
8 ⁄
10
NOTE: These values were calculated for motors with Locked Rotor
Current (LRA), not exceeding the following values:
MOTOR F.L.A.
0.00 – 1.00
1.01 – 2.00
2.01 – 10.0
10.1 – 17.8
*LRA
850%
750%
650%
600%
*If motor LRA varies from these values, contact Littelfuse.
© 2014 Littelfuse POWR-GARD
®
Products
25
littelfuse.com
Technical Application Guide
UL FUSE CLASSES AND SELECTION CHART
UL CLASS
L
RK1
RK5
J
T
CC
CD
G
Solar
K5
Semiconductor
Midget
(Supplementary)
Plug
Telecom
L15S
L25S
L50S
L60S
L70S
BLF
BLN
BLS
FLA
FLM
FLQ
KLK
KLKD
KLQ
FLU
SOO, TOO
SLO, TLO
L17T
TLN
TLS
CCMR
SPFJ
SPFI
SPXV
SPXI
NLN
KLDR
KLKR
CCMR
SLC
SPF
KLPC
KLLU
LDC
LLNRK
LLSRK_ID
LLSRK
KLNR
KLSR
FLNR_ID
FLNR
FLSR_ID
FLSR
IDSR
JTD_ID
JTD
JLS
JLLN
JLLS
NLS
Time-Delay
Time-Delay
Fast-Acting
Time-Delay
Time-Delay
Time-Delay
Fast-Acting
Fast-Acting
Time-Delay
Time-Delay
Time-Delay
Fast-Acting
Fast-Acting
Time-Delay
Time-Delay
Fast-Acting
Time-Delay
Time Lag
Solar
Solar
Solar
Solar
Solar
Fast-Acting
Very Fast-Acting
Fast-Acting
Fast-Acting
Fast-Acting
Time-Delay
Time-Delay
Time-Delay
Fast-Acting
Fast-Acting
Time-Delay
Fast-Acting
Time-Delay
Medium Time-Delay
Fast-Acting
150
1000
125
125
–
–
–
250
500
600
700
250
125
250
600
250
125
250
500
600
600
600
1 - 1000
1 - 800
10 - 800
1 - 800
10 - 800
0.5 - 15
20 - 30
1 - 30
0.2 - 5
6 - 10
0.1 - 30
0.1 - 30
0.1 - 30
0.1 - 30
0.1 - 30
1 - 6
0.44
11
0.25 - 30
15 - 30
–
–
–
AC RATINGS
600
600
600
600
600
480
–
–
–
–
–
250
600
600
600
250
600
600
250
600
600
600
600
600
250
250
600
600
300
600
200 - 6000 200K / 300K*
601 - 4000
150 - 2000
0.1 - 600
0.1 - 600
0.1 - 600
1 - 600
200,000
200,000
200K / 300K*
1 - 600
200,000
35 - 600
0.1 - 600
0.1 - 600
0.1 - 600
0.1 - 600
0.8 - 600
0.8 - 600
1 - 600
1 - 1200
200K / 300K*
200K / 300K*
200,000
200,000
1 - 1200
600
0.2 - 30
0.1 - 30
0.1 - 30
35 - 60
0.2 - 20
25 - 60
–
–
–
–
–
1 - 600
200K / 300K*
200,000
200,000
200K / 300K*
100,000
–
–
–
–
–
50,000
1 - 600
200,000
10,000
10,000
10,000
10,000
10,000
10,000
100K / 200K*
100,000
10,000
10,000
20,000
10,000
10,000
–
–
–
DC RATINGS
300
125
125
300
300
600
300
500
480
300
600
125
300
300
125
250
–
160
125
300
250
250
300
500
300
300
250
170
1000
1000
1000
1500
1500
250
200
450
–
650
600
500
400
600
500
150
100
250
–
–
–
–
125
300
500
600
–
1000
–
–
170
200 - 6000
601 - 4000
150 - 2000
0.1 - 600
0.1 - 600
0.1 - 600
1 - 600
1 - 30
35 - 600
35 - 600
0.1 - 600
0.1 - 600
0.1 - 600
0.1 - 600
0.8 - 100
110 - 600
–
1 - 60
70 - 1200
1 - 1200
0.2 - 2
4.5 - 10
2.25 - 4
12 - 30
0.1 - 30
0.1 - 30
35 - 60
0.5 - 60
1 - 30
70 - 450
2 - 20
6 - 30
2.5 - 3.5
1 - 600
1 - 7
8 - 30
35 - 60
70 - 200
225 - 600
1 - 60
70 - 1000
1 - 200
225 - 800
10 - 800
–
10 - 800
–
–
–
–
0.1 - 30
0.1 - 30
0.1 - 30
0.1 - 30
–
0.44
11
–
–
70 - 1200
1 - 600
1 - 125
20,000
20,000
50,000
20,000
20,000
20,000
–
20,000
20,000
20,000
10,000
20,000
20K (70 - 200A)
10K (250 - 400A)
20K (400A)
20,000
30,000
15,000
20K (1 - 60A)
50K (70 - 600A)
20K (1 - 60A)
50K (70 - 600A)
20,000
100,000
–
–
–
–
10,000
10,000
50,000
50,000
–
10,000
20,000
–
–
FUSE BLOCKS AND
FUSE HOLDERS
–
LFR25
LFR60
LFR60
LFR25
LFR60
LFR25
LFR60
LFJ60 • LFPSJ
LFT30 •
LSCR002 (700-800A)
LFT60 •
LSCR002 (700-800A)
L60030C • LFPSC •
LINK00_C •
571 • 572 •
LEC • LEY
LFC60060
LFG480 (1 - 20A)
LFG480 (25 - 60A)
LFPHV
LFJ1000
Not Required
LPXV
Not Required
LFH25
LFH60
LSCR • 1LS
(except L70S)
L60030M • LFPSM •
LINK00_M •
571 • 572 •
LEB • LEX
LFPHV
Box Cover Units
LTFD Series
LFR25
LTFD101 •
LFT30060 (cartridge)
* Series are UL Listed with I.R. of 200,000A and Littelfuse
®
self-certified with 300,000A I.R.
littelfuse.com
26
© 2014 Littelfuse POWR-GARD
®
Products
Technical Application Guide
CONDENSED CROSS REFERENCE
Power (Electrical) and Electronic Fuses
This cross reference covers the most popular fuses for which there is a similar Littelfuse standard item. Furnished for your convenience, it is meant to serve as a guide only for product selection. We suggest you check all applicable specifications before making substitutions. For special applications, more complete information, and for fuse block and medium voltage fuse cross referencing, visit littelfuse.com or call 1-800-TEC-FUSE (1-800-832-3873).
COMPETITION
CLL
CLU
CM
CMF
CNM
ATQ
ATQR
AX
BAF
BAN
BBS
CJ
CJS
CLF
A6T
A70P
ACK
AG
AGA
AGC
AGU (1-30A)
AGW
AJT
ANL
ANN
ATC
AT-DE
ATDR
ATM (Ferraz)
ATMR
10KOTN
10KOTS
50KOTN
50KOTS
A
A013F
A015F
A015R
A025F
A050F
A060F
A060URL
A070F
A13X
A25X
A2D-R
A2K-R
A3T
A4BQ
A4BT
A4BY
A4J
A50P (type 1 & 4)
A60X
A6D-R
A6K-R
LITTELFUSE
NLN
NLS
NLN
NLS
251
L15S
L15S
L15S
L25S
L50S
L60S
KLK
L70S
L15S
L25S (AC only)
LLNRK
KLNR
JLLN
KLPC
KLLU or KLPC
KLPC or KLLU
JLS
L50S
L60S
LLSRK_ID
4
KLSR
JLLS
L70S
CCK
SLC
AGA
312
BLN
AGW
JTD_ID
CNL
CNN
ATO (257)
FLNR_ID
3
CCMR
KLKD
KLKR
FLQ
KLDR
481
BLF
BLN
BLS
JLS
JLS
KLPC or KLLU
KLLU or KLPC
KLLU or KLPC
BLF
BLN
FLM
COMPETITION
JJS
JKS
KAA
KAB
KAC
GEB
GEBN
GFA
GFN
GGC
GGM
GLR
GMT
FWH 2
FWP 1
FWX 1
GDA
GDB
GDC
GDL
HLR
J
JDL
JFL
HCLR
HCTR
HEB
HET
JHC
JJN
CSF70P
CTN-R
CTS-R
EBS
ECNR
ECSR
ELN
ELS
CNQ
CRN-R
CRS-R
CSF13X
CSF25X
CSF50P
CSF60C
CSF60X
ERN
ERS
FNA
FNB
FNM
FNQ
FNQ-R
FRN-R
FRS-R
FWA
2
LITTELFUSE
FLQ
FLNR_ID
3
FLSR_ID
L15S
L25S (AC only)
L50S
KLC (AC only)
L60S (AC only)
L70S
KLNR
KLSR
BLS
FLNR_ID
3
FLSR_ID
FLNR or LLNRK
5
FLSR or LLSRK
5
FLNR or LLNRK
5
FLSR or LLSRK
5
FLA
235
FLM
FLQ
KLDR
FLNR_ID
3
FLSR_ID
L15S
L50S
L70S
L25S
216
217
LGR
481
KLKR
KLDR
LEB
LET
LHR
JLS
218
313
LEB
LET
251
FLA
312
235
JTD_ID
JLS
JTD_ID
JLLN
JLLS
JLS
L15S
L25S
KLC
COMPETITION
KRPC-L
KS
KTK
KTKR
KTNR
KTSR
KTU
L
KBH
KLM
KLMR
KLU
KN
KON
KOS
KRPC (SP)
LCL
LCU
LENRK
LESRK
LKN
LKS
LKU
LONRK
LOSRK
LPCC
MDX
MEN
MEQ
MID
MOF
MOL
MTH
NCLR
NON
NOS
LPJ (SP)
LPNRK (SP)
LPSRK (SP)
MCL
MDA
MDL
MDQ
MDV
LITTELFUSE
313
313
315
313
FLM
FLQ
FLA
BLN
BLF
312
KLNR
NLN
NLS
L50S
KLKD
CCMR
KLLU or KLPC
KLNR
NLN
NLS
KLPC
KLPC
KLSR
KLK
KLKR
KLNR
KLSR
KLPC or LDC
KLLU or KLPC
KLPC or KLLU
KLPC or KLLU
LLNRK
LLSRK_ID
FLNR or LLNRK
5
FLSR or LLSRK
5
KLLU
LLNRK
LLSRK_ID
CCMR
JTD_ID
LLNRK
LLSRK_ID
4
KLK
326
1) Check specific mounting dimensions before substituting.
2) Check fuse characteristics and mounting dimensions for specific application before substituting.
3) For
1
/
10
- 30 amperes, order non-indicating FLNR series fuses.
4) Verify voltage for DC applications.
5) Littelfuse has discontinued Class H fuses and recommends upgrading to RK1 or RK5 Class fuses.
LITTELFUSE
NLN
NLKP
NLS
NLN
BLF or BLN
NLN
SLO
TOO
JLLN
JLLS
TLO
FLNR_ID 3
FLM
FLNR_ID
3
FLSR_ID
FLSR_ID
4
L25S
L50S
L70S
1
1
SOO
SAO
SLC
KLSR
SLC
L15S
L25S
L50S
L60S
L70S
SFE
NLS
FLNR or LLNRK
FLSR or LLSRK 5
5
FLNR or LLNRK 5
L15S
KLC
L70S (700 V)
FLNR or LLNRK
FLSR or LLSRK
5
5
L50S
KLNR
KLSR
FLNR or LLNRK
FLSR or LLSRK
5
5
COMPETITION
NRN
NRN (15-60A)
NRS
OT
OTM
OTN
OTS
REN
RES
RF
RFA
RFC
RFL (750V)
RFN (Ferraz)
RFS (Ferraz)
RFV
RHN
RHS
RLN (Ferraz)
RLS (Ferraz)
S
SA
SC
SCLR
SEC
SF13X
TJS
TL
TR
TRM
TRN-R
TRS
TRS-R
XL25X
XL50F
XL70F
SFE
SL
T
TJN
SF25X
SF50P
SF60X
SF70P
A fuse may be used in circuits where the fuse’s voltage rating is equal to or greater than the circuit voltage, unless otherwise stated on the fuse. For example, the FLSR_ID indicating fuse has a voltage rating of 75-600 volts. This fuse can be used on 600 volts, 480 volts, 250 volts, 125 volts, or
75 volts. Never use a fuse in a circuit having a higher rated voltage than the fuse.
© 2014 Littelfuse POWR-GARD
®
Products
27
littelfuse.com
For more information, visit littelfuse.com/TechnicalCenter
Additional technical information and application data for Littelfuse products can be found on littelfuse.com. For questions, contact our Technical
Support Group (800-TEC-FUSE). Specifications, descriptions and illustrative material in this literature are as accurate as known at the time of publication, but are subject to changes without notice. All data was compiled from public information available from manufacturers’ manuals and datasheets.
© 2014 Littelfuse, Inc. Printed in USA.
Form: PFD755
Rev: 1-A-051614
advertisement
Key Features
- Overcurrent protection
- Fuse selection
- Time-current curves
- Peak let-through charts
- Selective coordination
- UL/CSA fuse classes
- Motor protection