ClimateMaster Tranquility® Modual TMW Water - to - Water Series 10.6, 17.6, 35.2, 50 and 100kW Install Manual

Add to my manuals
36 Pages

advertisement

ClimateMaster  Tranquility® Modual TMW Water - to - Water Series 10.6, 17.6, 35.2, 50 and 100kW  Install Manual | Manualzz
Tranquility® Modular
Water-to-Water
(TMW) Series
Table of Contents
Model Nomenclature
Storage
Pre-Installation
Physical Data
Dimensional Data
Unit Installation
Piping Installation
Load Plumbing Installation
Water Loop Applications
Open Loop - Ground Water Systems
Water Quality Standards
Ground Loop Applications
Electrical - Line Voltage
Electrical - Low Voltage Wiring
Electrical - Accessories
Water Valve Wiring
TMW Series Wiring Diagram Matrix
Electrical Wiring Schematics
CXM/DXM Controls
CXM/DXM Safety Control Reset
Unit Commissioning and Operating Conditions
Piping System Cleaning & Flushing
Unit and System Checkout Procedure
Start Up Procedure
Preventive Maintenance
Warranties
Refrigeration Troubleshooting Form
Revision History
Water-Source Heat Pumps
50Hz-HFC-410A
Installation, Operation &
Maintenance
97B0059N05
Rev.: 5 February, 2016
3
5
5
6
7
9
9
10
11
12
12
14
15
16
17
17
18
19
25
28
29
30
31
32
33
34
35
36
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
This Page Intentionally Left Blank
2
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Model Nomenclature
Z17
1 2
3
4 5 6
7
8
9
10
11
12
13
14
15
TM
W
340
A
U
F
1
0
C
0
C
S
MODEL TYPE
S = STANDARD
TM = TRANQUILITY® MEDIUM TEMPERATURE
LOAD WATER COIL OPTIONS
CONFIGURATION
C = Copper
N = Cupro-nickel
W = WATER TO WATER HEAT PUMP
UNIT SIZE
RESERVED - FUTURE OPTIONS
036
060
120
170
340
0 = NONE
SOURCE WATER COIL OPTIONS
REVISION LEVEL
C = Copper
N = Cupro-nicke l
A = CURRENT
VOLTAGE
HOT WATER GENERATOR OPTIONS
U = 380-420/50/3
V = 220-240/50/1
0 = NONE (036-340)
2 =HOT WATER GENERATOR COIL (036-120 ONLY)
CONTROLS
F = CXM
G = DXM
H = CXM w/LON
J = DXM w/LON
T = CXM w/MPC
U = DXM w/MPC
CABINET INSULATION
1 = COMMERCIAL EXTENDED RANGE
2 = COMMERCIAL EXTENDED RANGE w/ULTRA QUIET
c l i m a t e m a s t e r. c o m
3
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
General Information
Safety
Warnings, cautions, and notices appear throughout this
manual. Read these items carefully before attempting
any installation, service, or troubleshooting of the
equipment.
DANGER: Indicates an immediate hazardous situation,
which if not avoided will result in death or serious
injury. DANGER labels on unit access panels must be
observed.
WARNING: Indicates a potentially hazardous situation,
which if not avoided could result in death or serious
injury.
CAUTION: Indicates a potentially hazardous situation
or an unsafe practice, which if not avoided could result
in minor or moderate injury or product or property
damage.
WARNING!
WARNING! All refrigerant discharged from this unit must
be recovered WITHOUT EXCEPTION. Technicians must
follow industry accepted guidelines and all local, state,
and federal statutes for the recovery and disposal of
refrigerants. If a compressor is removed from this unit,
refrigerant circuit oil will remain in the compressor. To
avoid leakage of compressor oil, refrigerant lines of the
compressor must be sealed after it is removed.
CAUTION!
CAUTION! To avoid equipment damage, DO NOT use
these units as a source of heating or cooling during the
construction process. The mechanical components and
filters will quickly become clogged with construction dirt
and debris, which may cause system damage.
NOTICE: Notification of installation, operation, or
maintenance information, which is important, but which
is not hazard-related.
WARNING!
WARNING! To avoid the release of refrigerant into the
atmosphere, the refrigerant circuit of this unit must be
serviced only by technicians who meet local, state, and
federal proficiency requirements.
4
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Inspection
Upon receipt of the equipment, carefully check the
shipment against the bill of lading. Make sure all units
have been received. Inspect the carton or crating of
each unit, and inspect each unit for damage. Assure
the carrier makes proper notation of any shortages or
damage on all copies of the freight bill and completes a
common carrier inspection report. Concealed damage
not discovered during unloading must be reported to
the carrier within 15 days of receipt of shipment. If not
filed within 15 days, the freight company can deny the
claim without recourse. Note: It is the responsibility of
the purchaser to file all necessary claims with the carrier.
Notify the ClimateMaster Traffic Department of all
damage within fifteen (15) days of shipment.
Storage
Equipment should be stored in its original packaging in
a clean, dry area. Store units in an upright position at all
times. Do not stack TMW170 or 340. The stack limit for
TMW036, 060 and 120 is three.
Unit Protection
Cover units on the job site with either shipping
packaging, vinyl film, or an equivalent protective
covering. Cap the open ends of pipes stored on the
job site. In areas where painting, plastering, and/or
spraying has not been completed, all due precautions
must be taken to avoid physical damage to the units and
contamination by foreign material. Physical damage and
contamination may prevent proper start-up and may
result in costly equipment clean-up.
CAUTION!
CAUTION! All three phase scroll compressors must have
direction of rotation verified at start-up. Verification is
achieved by checking compressor Amp draw. Amp draw
will be substantially lower compared to nameplate values.
Additionally, reverse rotation results in an elevated sound
level compared to correct rotation. Reverse rotation will
result in compressor internal overload trip within several
minutes. Verify compressor type before proceeding.
CAUTION!
CAUTION! DO NOT store or install units in corrosive
environments or in locations subject to temperature or
humidity extremes (e.g., attics, garages, rooftops, etc.).
Corrosive conditions and high temperature or humidity can
significantly reduce performance, reliability, and service life.
Always move and store units in an upright position. Tilting
units on their sides may cause equipment damage.
CAUTION!
CAUTION! CUT HAZARD - Failure to follow this caution
may result in personal injury. Sheet metal parts may have
sharp edges or burrs. Use care and wear appropriate
protective clothing, safety glasses and gloves when
handling parts and servicing heat pumps.
Examine all pipes, fittings, and valves before installing
any of the system components. Remove any dirt or trash
found in or on these components.
Pre-Installation
Installation, Operation, and Maintenance instructions
are provided with each unit.. The installation site chosen
should include adequate service clearance around the
unit. Before unit start-up, read all manuals and become
familiar with the unit and its operation. Thoroughly check
the system before operation.
Prepare units for installation as follows:
1. Compare the electrical data on the unit nameplate
with ordering and shipping information to verify that
the correct unit has been shipped.
2. Keep the cabinet covered with the shipping
packaging until installation is complete and all
plastering, painting, etc. is finished.
3. Verify refrigerant tubing is free of kinks or dents and
that it does not touch other unit components.
4. Inspect all electrical connections. Connections must
be clean and tight at the terminals.
c l i m a t e m a s t e r. c o m
5
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Unit Physical Data
Model
036
Compressor (qty)
060
Scroll (1)
Factory Charge HFC-410A kg per circuit
2.04
120
170
340
Scroll (2)
Scroll (1)
Scroll (2)
2.83
6.8
Water Connection Size
Source/Load (in)
3/4
1
Weight - Operating kg
158
163
329
329
604
Weight - Packaged kg
169
175
349
347
608
3.64
5.04
10.02
13.27
25.44
Hot Water Generator FPT (in)
1-1/2
2
N/A
½
Water Volume (Source)
Liters
Dual isolated compressor mounting
Balanced port expansion valve (TXV)
Insulated Source and Load Water Coils standard
Insulated Refrigerant Circuit standard
Compressor on (green) and fault (red) light
FPT - Female Pipe Thread
Unit Maximum Water Working Pressure
6
Options
Max Working Pressure [kPa]
Base Unit
2,068
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
TMW036 - 120 - Unit Dimensional Data
%
FP
$
FP
Notes:
1. Front & side access is preferred for service
access. However, all components may be
serviced from the front access panel if side
access is not available.
2. While clear access to all removable panels
is not required, installer should take care
to comply with all building codes and allow
adequate clearance for future field services.
FP
&
-
+
*
0
)
/
.
(
'
FP
5HTXLUHG
6HUYLFH$FFHVV
2SWLRQDO
6HUYLFH$FFHVV
$
%
FP
FP
FP
&
5HTXLUHG
6HUYLFH$FFHVV
2SWLRQDO
6HUYLFH$FFHVV
Overall Cabinet
Water to
Water
A
Depth
B
Width
C
Height
Water Connections
1
2
3
4
5
6
D
Source
(Outdoor)
Water In
E
Source
(Outdoor)
Water Out
F
Load
(Indoor)
Water In
G
Load
(Indoor)
Water Out
H
HWG
Water In
J
HWG
Water
Out
Electric Access Plugs
K
Low
Voltage
L
External
Pump
M
Power
Supply
036-060
cm.
77.8
64.5
83.8
6.9
23.9
49.3
62.2
70.9
77.2
53.1
58.2
78.5
120
cm.
77.8
134.4
94
64.0
64.0
76.5
76.5
88.6
88.6
75.9
81.0
87.4
c l i m a t e m a s t e r. c o m
7
8
7RS
9LHZ
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
/HIW
6LGH
9LHZ
)URQW
9LHZ
)DXOW5XQ/LJKWV
&RQWURO:LULQJ
[PP'RXEOH.QRFNRXW
3RZHU6XSSO\:LULQJ
[PP'RXEOH.QRFNRXW
µ )37:DWHU&RQQHFWLRQV
5HIULJ
&LUFXLW
$FFHVV
3DQHO
2SWLRQDO6LQJOH8QLW
FP $GGLWLRQDO
6HUYLFH$FFHVV
6LGH
7RS
&RPSUHVVRU
$FFHVV
3DQHO
(OHFWULFDO
$FFHVV
3DQHO
0LQLPXP FP
5HTXLUHG6HUYLFH
$FFHVV
)URQW
+HDGHU
$FFHVV
3DQHO
6RXUFH
1RWHV'LPHQVLRQVVKRZQLQFHQWLPHWHUVXQOHVVQRWHGRWKHUZLVH
)RUPXOWLSOHXQLWVSODFHGVLGHE\VLGHDOORZ
FPPLQLPXPIURQWDFFHVV
)37)HPDOH3LSH7KUHDG
/RDG
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
TMW170 & 340 - Unit Dimensional Data
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Unit Installation
TMW Unit Location
These units are not designed for outdoor installation.
Locate the unit in an INDOOR area that allows
enough space for service personnel to perform typical
maintenance or repairs.
The installation of water source heat pump units and
all associated components, parts and accessories
which make up the installation shall be in accordance
with the regulations of ALL authorities having
jurisdiction and MUST conform to all applicable codes.
It is the responsibility of the Installing Contractor to
determine and comply with ALL applicable codes and
regulations.
Locate the unit in an indoor area that allows easy
removal of access panels, and has enough space for
service personnel to perform maintenance or repair.
Provide sufficient room to make water and electrical
connections.. Any access panel screws that would be
difficult to remove after the unit is installed should be
removed prior to setting the unit. These units are not
approved for outdoor installation and, therefore, must
be installed inside the structure being conditioned. Do
not locate in areas where ambient conditions are not
maintained within 4-38°C.
WARNING!
WARNING! Do not bend or kink supply lines or hoses.
PIPING INSTALLATION
Installation of Supply and Return Piping
Follow these piping guidelines.
1. Install a drain valve at the base of each supply and
return riser to facilitate system flushing.
2. Install shut-off / balancing valves and unions at
each unit to permit unit removal for servicing.
3. Place strainers at the inlet of each system
circulating pump.
4. Select the proper hose length to allow slack
between connection points. Hoses may vary in
length by +2% to -4% under pressure.
5. Exceeding the minimum bend radius may cause
the hose to collapse which reduces water flow rate.
Install an angle adapter to avoid sharp bends in
the hose when the radius falls below the required
minimum and causes a slight kink.
Insulation is not required on loop water piping
except where the piping runs through unheated
areas or outside the building or when the loop water
temperature is below the minimum expected dew
point of the pipe ambient temperature. Insulation is
required if loop water temperature drops below the
dew point.
Pipe joint compound is not necessary when Teflon
threaded tape is pre-applied to hose assemblies or
when flared-end connections are used. If pipe joint
compound is preferred, use compound only in small
amounts on the pipe threads of the fitting adapters.
Prevent sealant from reaching the flared surfaces of
the joint.
Note: When antifreeze is used in the loop, assure
that it is compatible with Teflon tape or pipe joint
compound employed.
WARNING!
WARNING! Piping must comply with all applicable codes.
Maximum allowable torque for brass fittings is
41 N-m. If a torque wrench is not available, tighten
finger-tight plus one quarter turn. Tighten steel
fittings as necessary.
c l i m a t e m a s t e r. c o m
9
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Piping Installation
WARNING!
WARNING! Polyolester Oil, commonly known as POE
oil, is a synthetic oil used in many refrigeration systems
including those with HFC-410A refrigerant. POE oil, if it
ever comes in contact with PVC or CPVC piping, may
cause failure of the PVC/CPVC. PVC/CPVC piping should
never be used as supply or return water piping with water
source heat pump products containing HFC-410A as
system failures and property damage may result.
Optional pressure-rated hose assemblies designed
specifically for use with ClimateMaster units are available.
Similar hoses can be obtained from alternate suppliers.
Supply and return hoses are fitted with swivel-joint fittings
at one end to prevent kinking during installation.
Refer to Figure 1 for an illustration of a Supply/Return
Hose Kit. Male adapters secure hose assemblies to the
unit and risers. Install hose assemblies properly and
check them regularly to avoid system failure and reduced
service life.
CAUTION!
CAUTION! Corrosive system water requires corrosion
resistant fittings and hoses and possibly water treatment.
Figure 1: Supply/Return Hose Kit
Rib Crimped
Swivel
Brass
Fitting
Brass
Fitting
Length
(0.6m Length Standard)
MPT
MPT
LOAD PLUMBING INSTALLATION
TMW Unit Load Plumbing
The applications are too varied to describe in this
document. However, some basic guidelines will be
presented. Much of the discussions on water loop
applications would be valid for the load plumbing
discussion as well. All plumbing should conform to local
codes with the following considerations:
Wide temperature variation applications such as
heating/cooling coils:
- Employ piping materials that are rated for the
maximum temperature and pressure combination.
This excludes PVC for most heating applications.
- Insure that load water flow in high temperature
heating applications is at least 3.2 l/m per kW
to improve performance and reduce nuisance high
pressure faults.
- DO NOT employ plastic to metal threaded joints
- Utilize a pressure tank and air separator vent system
to equalize pressure and remove air..
Note: The manufacturer strongly recommends all
piping connections, both internal and external to
the unit, be pressure tested by an appropriate
method prior to any finishing of the interior space
or before access to all connections is limited. Test
pressure may not exceed the maximum allowable
pressure for the unit and all components within
the water system. The manufacturer will not be
responsible or liable for damages from water leaks
due to inadequate or lack of a pressurized leak test,
or damages caused by exceeding the maximum
pressure rating during installation.
Swimming Pool Hot Tub Applications:
- Load side heat exchanger should be isolated with
secondary heat exchanger constructed of anticorrosion material in all chlorine/bromine fluid
applications.
Potable Water Applications:
- Load side heat exchanger should be isolated with
secondary heat exchanger for use in potable water
systems.
- Insure load water flow in high temperature heating
applications is at least 3.2 l/m per kW to improve
performance and reduce nuissance to high pressure
faults.
10
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Water-Loop Heat Pump Applications
Commercial systems typically include a number of
units plumbed to a common piping system. Any unit
plumbing maintenance work can introduce air into the
piping system, therefore air elimination equipment is
a major portion of the mechanical room plumbing. In
piping systems expected to utilize water temperatures
below 10°C, 13mm closed cell insulation is required on
all piping surfaces to eliminate condensation. Metal to
plastic threaded joints should never be employed due
to their tendency to leak over time. Teflon tape thread
sealant is recommended for FPT water connections
(commercial class) to minimize internal fouling of the heat
exchanger. Do not overtighten connections and route
piping so as not to interfere with service or maintenance
access. Hose kits are available from ClimateMaster in
Figure 2 for connection between the TMW unit and the
piping system. The hose kits include shut off valves, P/T
plugs for performance measurement, high pressure
stainless steel braid hose, "Y" type strainer 20 mesh
(841 micron) [0.84mm]) with blowdown valve, and "J"
type swivel connection. Balancing valves to facilitate
the balancing of the system, may also be included in
the hose kit. The piping system should be flushed to
remove dirt, piping chips, and other foreign material
prior to operation. See Piping System Cleaning and
Flushing Procedures later in this document. The flow
rate is usually set between 2.4 l/m and 3.2 l/m per kW
of cooling capacity. ClimateMaster recommends 2.7
l/m per kW for most applications of water loop heat
pumps. To insure proper maintenance and servicing,
P/T ports are imperative for temperature and flow
verification, as well as performance checks.
Load Connections
(Hot Water/Chilled Water)
Source Connections
Power Disconnect
Cooling Tower/Boiler Systems typically utilize a
common loop maintained between 16-32°C. The use
of a closed circuit evaporative cooling tower with a
secondary heat exchanger between the tower and the
water loop is recommended. If an open type cooling
tower is used continuously, chemical treatment and
filtering will be necessary.
Low Water Temperature Cutout Setting
CXM or DXM Control: When an antifreeze is selected,
the FP1 jumper (JW3) should be clipped to select the
low temperature 12°C setpoint to avoid nuisance faults.
See Figure 4: Low Water Temperature Cutout - FP1.
c l i m a t e m a s t e r. c o m
11
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Ground-Water Heat Pump Applications
Typical open loop piping is shown in Figure 3. Shut off valves
should be included in case of servicing. Boiler drains or other
valves should be ‘tee’d’ into the line to allow acid flushing of
just the heat exchanger. Pressure temperature plugs should
be used so that flow and temperature can be measured.
WARNING!
WARNING! Polyolester Oil, commonly known as POE
oil, is a synthetic oil used in many refrigeration systems
including those with HFC-410A refrigerant. POE oil, if it
ever comes in contact with PVC or CPVC piping, may
cause failure of the PVC/CPVC. PVC/CPVC piping should
never be used as supply or return water piping with water
source heat pump products containing HFC-410A as
system failures and property damage may result.
Table 1: Water Quality Standards
Water Quality
Parameter
HX
Material
Closed
Recirculating
Water quantity should be plentiful and of good quality.
Consult Table 1 for water quality guidelines. The unit can
be ordered with either a copper or cupro-nickel water heat
exchanger. Copper is recommended for closed loop systems
and open loop ground water systems that are not high in
mineral content or corrosiveness. In conditions anticipating
heavy scale formation or in brackish water, a cupro-nickel
heat exchanger is recommended.
In ground water situations where scaling could be heavy or
where biological growth such as iron bacteria will be present,
a closed loop system is recommended. It is recommended
to install an intermediate heat exchanger to isolate an open
loop from the heat pump loop on open well systems. Heat
exchangers may over time lose heat exchange capabilities
due to a build up of mineral deposits inside. These can be
cleaned only by a qualified service mechanic as acid and
special pumping equipment are required.
Open Loop and Recirculating Well
Scaling Potential - Primary Measurement
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below
pH/Calcium Hardness
Method
-
All
pH < 7.5 and Ca Hardness <100ppm
Index Limits for Probable Scaling Situations - (Operation outside these limits is not recommended)
Scaling indexes should be calculated at 66°C for direct use and HWG applications, and at 32°C for indirect HX use.
A monitoring plan should be implemented.
Ryznar
6.0 - 7.5
All
Stability Index
If >7.5 minimize steel pipe use.
-0.5 to +0.5
Langelier
All
If <-0.5 minimize steel pipe use. Based upon 66°C HWG and
Saturation Index
Direct well, 29°C Indirect Well HX
Iron Fouling
Iron Fe 2+ (Ferrous)
(Bacterial Iron potential)
All
Iron Fouling
All
-
<0.2 ppm (Ferrous)
If Fe2+ (ferrous)>0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.
-
<0.5 ppm of Oxygen
Above this level deposition will occur .
Corrosion Prevention
6 - 8.5
pH
All
Hydrogen Sulfide (H2S)
All
Ammonia ion as hydroxide, chloride,
nitrate and sulfate compounds
All
Monitor/treat as
needed
-
6 - 8.5
Minimize steel pipe below 7 and no open tanks with pH <8
<0.5 ppm
At H2S>0.2 ppm, avoid use of copper and copper nickel piping or HX's.
Rotten egg smell appears at 0.5 ppm level.
Copper alloy (bronze or brass) cast components are OK to <0.5 ppm.
-
<0.5 ppm
Maximum Allowable at maximum water temperature.
Maximum
Chloride Levels
Copper
Cupronickel
304 SS
316 SS
Titanium
-
10$C
<20ppm
<150 ppm
<400 ppm
<1000 ppm
>1000 ppm
24$C
NR
NR
<250 ppm
<550 ppm
>550 ppm
38 C
NR
NR
<150 ppm
< 375 ppm
>375 ppm
Erosion and Clogging
Particulate Size and
Erosion
All
<10 ppm of particles
and a maximum
velocity of 1.8 m/s
Filtered for maximum
841 micron [0.84 mm,
20 mesh] size.
<10 ppm (<1 ppm "sandfree” for reinjection) of particles and a maximum
velocity of 1.8 m/s. Filtered for maximum 841 micron 0.84 mm,
20 mesh] size. Any particulate that is not removed can potentially
clog components.
The ClimateMaster Water Quality Table provides water quality requirements for ClimateMaster coaxial heat exchangers. The water should be evaluated by an
independent testing facility comparing to this Table and when properties are outside of these requirements, an external secondary heat exchanger must be used to
isolate the heat pump heat exchanger from the unsuitable water. Failure to do so will void the warranty for the coaxial heat exchanger and any other components
damaged by a leak.
Notes:
• Closed Recirculating system is identified by a closed pressurized piping system.
• Recirculating open wells should observe the open recirculating design considerations.
• NR - Application not recommended.
• "-" No design Maximum.
12
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
Rev.: 5/6/2014 S
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Ground-Water Heat Pump Applications
In areas with extremely hard water, the owner should
be informed that the heat exchanger may require
occasional acid flushing.
Expansion Tank and Pump
Use a closed, bladder-type expansion tank to minimize
mineral formation due to air exposure. The expansion
tank should be sized to handle at least one minute run
time of the pump to prevent premature pump failure
using its drawdown capacity rating. Discharge water
from the unit is not contaminated in any manner and
can be disposed of in various ways depending on local
building codes; i.e. recharge well, storm sewer, drain
field, adjacent stream or pond, etc. Most local codes
forbid the use of sanitary sewer for disposal. Consult
your local building and zoning department to assure
compliance in your area.
Low Water Temperature Cut-Out Setting
For all open loop systems the -1°C FP1 setting (factory
setting-water) should be used to avoid freeze damage
to the unit. See Figure 4: “Low Water Temperature
Cutout - FP1”.
WARNING!
WARNING! Never jumper terminal “A” from CXM or DXM
board #1 to CXM or DXM board #2 on multi-compressor/
control bound units. See Figure 5 in electrical section of this
document for motorized valve wiring.
NOTICE! Low temperature limit system will not
allow leaving load water temperature (cooling
mode) or leaving source water temperature (heating
mode) to be below 5.6°C.
Water Control Valve
Note the placement of the water control valve. Always
maintain water pressure in the heat exchanger by
placing water control valves at the outlet of the unit to
prevent mineral precipitation. Pilot operated or Taco
slow closing valve’s solenoid valves are recommended
to reduce water hammer. If water hammer persists, a
mini-expansion tank can be mounted on the piping to
help absorb the excess hammer shock. Insure that the
total ‘VA’ draw of the valve can be supplied by the unit
transformer. For instance the Taco slow closing valve
can draw up to 35VA. This can overload smaller 40 or
50 VA transformers depending on the other controls
employed. A typical pilot operated solenoid valve
draws approximately 15VA.
Flow Regulation
Flow regulation can be accomplished by two methods.
First, most water control valves have a built in flow
adjustment. By measuring the pressure drop through
the unit heat exchanger, flow rate can be determined
and compared to Tables 7 and 8. Since the pressure
is constantly varying, two pressure gauges might be
needed. Simply adjust the water control valve until the
desired flow of 1.6 l/m and 2.2 l/m per kW is achieved.
Secondly, a flow control device may be installed. The
devices are typically an orifice of plastic material that
is designed to allow a specified flow rate. These are
mounted on the outlet of the water control valve. On
occasion, these valves can produce a velocity noise
that can be reduced by applying some back pressure.
This is accomplished by slightly closing the leaving
isolation valve of the ground water setup.
Figure 3: Typical Ground-Water Application
Unit Power
Disconnect
Flow
Water
Control Regulator
Valve
Air Pad or
Extruded
polystyrene
insulation board
Pressure
Tank
Water Out
Water In
Shut-Off
Valve
Optional
Filter
P/T Plugs
Boiler
Drains
Thermostat Wiring
c l i m a t e m a s t e r. c o m
13
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Ground-Loop Heat Pump Applications
CAUTION!
CAUTION! The following instructions represent industry
accepted installation practices for Closed Loop Earth
Coupled Heat Pump Systems. They are provided to assist
the contractor in installing trouble free ground loops. These
instructions are recommendations only. State and Local
Codes MUST be followed and installation MUST conform
to ALL applicable Codes. It is the responsibility of the
Installing contractor to determine and comply with ALL
applicable Codes and Regulations.
Pre-Installation
Prior to installation, locate and mark all existing
underground utilities, piping, etc. Install loops for new
construction before sidewalks, patios, driveways, and other
construction has begun. During construction, accurately
mark all ground loop piping on the plot plan as an aid in
avoiding potential future damage to the installation.
to their tendency to corrode. All plastic to metal threaded
fittings should be avoided due to their potential to leak in
earth coupled applications and a flanged fitting substituted.
P/T plugs should be used so that flow can be measured
using the pressure drop of the unit heat exchanger in lieu of
other flow measurement means. Earth loop temperatures
can range between -4 to 43°C, and 2.4 l/m to 3.2 l/m per kW
of cooling capacity is recommended in these applications.
Upon completion of the ground loop piping, pressure test
the loop to assure a leak free system. Horizontal Systems: Test
individual loops as installed. Test entire system when all loops
are assembled. Vertical U-Bends and Pond Loop Systems:
Test Vertical U-bends and pond loop assemblies prior to
installation with a test pressure of at least 689 kPa.
Flushing the Earth Loop
Upon completion of system installation and testing, flush the
system to remove all foreign objects and purge to remove
all air. Flush the loop first with the unit isolated to avoid
flushing debris from the loop into the unit heat exchanger.
Piping Installation
All earth loop piping materials should be limited to only
polyethylene fusion for inground sections of the loop.
Galvanized or steel fitting should not be used at any time due
Table 2: Antifreeze Percentages by Volume
Minimum Temperature for Low Temperature Protection
Type
-12.2°C
-9.4°C
-6.7°C
-3.9°C
Methanol
25%
21%
16%
10%
100% USP food grade Propylene Glycol
38%
25%
22%
15%
Ethanol*
29%
25%
20%
14%
* Must not be denatured with any petroleum based product
Antifreeze
In areas where minimum entering loop temperatures
drop below 5°C or where piping will be routed through
areas subject to freezing, anti-freeze is needed. Alcohols
and glycols are commonly used as antifreezes, however
your local sales manager should be consulted for the
antifreeze best suited to your area. Freeze protection
should be maintained to 9°C below the lowest expected
entering loop temperature. For example, if -1°C is the
minimum expected entering loop temperature, the
leaving loop temperature would be -4 to -6°C and
freeze protection should be at -10°C e.g. -1°C - 9°C =
-10°C. All alcohols should be premixed and pumped
from a reservoir outside of the building when possible
or introduced under water level to prevent fuming.
Initially calculate the total volume of fluid in the piping
system. Then use the percentage by volume shown
in Table 2 for the amount of antifreeze. Antifreeze
concentration should be checked from a well mixed
sample using a hydrometer to measure specific gravity.
14
Low Water Temperature Cut-Out Setting
CXM or DXM Control:
When an antifreeze is selected, the FP1 jumper [JW3]
should be clipped to select the low temperature
12.2°C setpoint to avoid nuisance faults. See Figure 4.
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Ground-Loop Heat Pump Applications
Electrical - Line Voltage
Figure 3a: Typical Ground-Loop Application
CAUTION!
CAUTION! Use only copper conductors for field installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
8QLW3RZHU
'LVFRQQHFW
General Line Voltage Wiring
Be sure the available power is the same voltage and
phase as that shown on the unit serial plate. Line and
low voltage wiring must be done in accordance with
local codes or the National Electric Code, whichever is
applicable.
TMW Power Connection
Line voltage connection is made by connecting the
incoming line voltage wires to the power distribution
block. Consult electrical data table for correct fuse
size.
$LU3DGRU
([WUXGHG
SRO\VW\UHQH
LQVXODWLRQERDUG
7KHUPRVWDW:LULQJ
Transformer
On dual voltage units, the installer must confirm that the
power supply and unit transformer wiring match. Installer
must rewire as needed. Refer to the unit wiring diagram
c l i m a t e m a s t e r. c o m
15
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Electrical - Line Voltage
All field installed wiring, including electrical ground,
must comply with all applicable local codes.
WARNING!
WARNING! Disconnect electrical power source to prevent
injury or death from electrical shock.
Refer to the unit wiring diagrams for a schematic of the
field connections which must be made by the installing
(or electrical) contractor.
WARNING!
WARNING! To avoid possible injury or death due to
electrical shock, open the power supply disconnect switch
and secure it in an open position during installation.
Consult the unit wiring diagram located on the inside
of the compressor access panel to ensure proper
electrical hookup. All final electrical connections must
be made with a length of flexible conduit to minimize
vibration and sound transmission to the building.
TMW Electrical Data
Model
Voltage
Code
Voltage
Voltage
Min/Max
LRA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse
Compressor
QTY
RLA
V
220-240/50/1
198/264
1
13.5
67
13.5
16.9
30
U
380-420/50/3
342/462
1
5.4
38
5.4
6.8
15
TM036
V
220-240/50/1
198/264
1
24.5
153
24.5
30.6
50
U
380-420/50/3
342/462
1
9.6
74
9.6
12.0
20
TMW060
V
220-240/50/1
198/264
2
24.5
153
49.0
55.1
79.6
U
380-420/50/3
342/462
2
9.6
74
19.2
21.6
30
TMW120
V
220-240/50/3
198/264
1
44.9
273
44.9
56.1
100
U
380-420/50/3
342/462
1
18.6
118
18.6
23.3
40
V
220-240/50/3
198/264
2
44.9
273
89.8
101
125
U
380-420/50/3
342/462
2
18.6
118
37.2
46.6
60
TMW170
TMW340
ELECTRICAL - LOW VOLTAGE
Figure 4: Changing FP1-Low Water Temperature
Cutout Setpoint
Thermostat Connections
The aquastat/thermostat should be wired directly to
the CXM/DXM board #1. Note: The TMW second
stage is wired directly to the CXM #2.
Low Water Temperature Cutout - FP1
LT1
LT2
CXM PCB
16
JW3-FP1 jumper
should be
clipped when
antifreeze is
used.
The CXM/DXM control allows the field selection of
source fluid low temperature cutout points. The factory
setting of FP1 is set for water -1°C. In cold temperature
applications jumper JW3 should be clipped as shown
in Figure 4 to change the setting to -12.2°C, a more
suitable temperature when using antifreezes. Never
clip JW3 prior to antifreeze being added to the loop.
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Electrical - Accessories
Accessory Connections
A terminal paralleling the compressor contactor coil
has been provided on the CXM/DXM control of the
TMW line. "A" has been provided to control accessory
devices, such as water valves, electronic air cleaners,
humidifiers, etc. Note: This terminal must be used only
with 24 Volt signals and not line voltage signals.
24 Volt Accessory Wiring
CXM/DXM Terminal Strip
These terminals may
be used to power 24
volt water valves on
units size 036, 060,
170. See Figure 5 for
water valve wiring on
unit sizes 120 and 340.
WARNING!
WARNING! Never jumper terminal “A” from CXM or DXM
board #1 to CXM or DXM board #2 on multi-compressor/
control bound units. See Figure 5 in electrical section of this
document for motorized valve wiring.
Figure 5: Field Wiring of 24 Volt Motorized Valve for Units Size 120 and 340
Water
High Pressure
Switch NC
Valve
Relay 3
Coil
RED
VR3
NO
6
RED
8
Refrigerant
HP Switch
Circuit #1
VR3
NO
RED
2
RED
4
Refrigerant
HP Switch
Circuit #2
,
VR 1
Coil
VR2
Notes - Disconnect red wire at refrigerant HP switch connect to N.O. contact,
connect new red wire from N.O. contact to refrigerant HP switch.
Valve Relay 1, 2 - 13B0001N01 (SPDT) VR1, VR2
Valve Relay 3 - 13B0004N01 (DPDT) VR3
Water
High Pressure
Switch NC
Coil
Coil
Valve
Relay 3
Coil
RED
VR3
NO
6
RED
8
Refrigerant
HP Switch
Circuit #1
RED
VR3
NO
2
RED
4
Refrigerant
HP Switch
Circuit #2
CXM/DXM, LonWorks, or MPC Control Operation
Note: See CXM AOM (part #97B0003N12), DXM AOM (part #97B0003N13), Lon Controller AOM (part
#97B0013N01) or MPC Controller AOM (part #97B0031N01) on the web at climatemaster.com
c l i m a t e m a s t e r. c o m
17
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
TMW Series Wiring Diagram Matrix
All current 50 Hz wire diagrams can be downloaded at www.climatemaster.com/commercial-50hz-wiring
Model
TMW036
TMW036-060
TMW120
Wiring Diagram
Part Number
96B0144N01
96B0144N03
Electrical
V-HZ-PH
220/240-50-1
Control
CXM
-
DXM
-
96B0223N05
CXM
MPC/LON
96B0223N09
DXM
MPC/LON
96B0225N04
CXM
MPC/LON
96B0225N07
DXM
MPC/LON
96B0226N02
-
96B0226N04
TMW170
CXM
96B0226N06
96B0226N09
96B0226N13
96B0227N02
96B0227N04
DXM
CXM
96B0227N10
TMW120
18
96B0146N01
96B0146N02
96B0146N05
96B0146N06
LON
MPC
-
DXM
96B0227N14
AUX WD
TMW036-060
LON
MPC
380/420-50-3
96B0227N06
96B0227N12
LON
MPC
96B0226N11
TMW340
DDC
LON
MPC
CXM/DXM
-
MPC
LON
MPC
LON
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Typical Wiring Diagram
c l i m a t e m a s t e r. c o m
19
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Typical Wiring Diagram
20
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Typical Wiring Diagram
Three Phase 340 Units with CXM - CE
c l i m a t e m a s t e r. c o m
21
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Typical Wiring Diagram
Three Phase TMW 340 Units with DXM - CE
22
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Typical Wiring Diagram
Three Phase 170 Units with CXM - CE
c l i m a t e m a s t e r. c o m
23
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Typical Wiring Diagram
Three Phase TMW 170 Units with DXM - CE
24
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
CXM Controls
CXM Control
For detailed control information, see the CXM
Application, Operation and Maintenance (AOM)
manual (part #97B0003N12).
DIP switch 2: Stage 2 Selection - provides selection of
whether compressor has an “on” delay. If set to stage
2, the compressor will have a 3 second delay before
energizing. Also, if set for stage 2, the alarm relay will
NOT cycle during test mode.
Field Selectable Inputs
Test mode: Test mode allows the service technician to
check the operation of the control in a timely manner. By
momentarily shorting the test terminals, the CXM control
enters a 20 minute test mode period in which all time
delays are sped up 15 times. Upon entering test mode,
the status LED will flash a code representing the last
fault. For diagnostic ease at the thermostat, the alarm
relay will also cycle during test mode. The alarm relay
will cycle on and off similar to the status LED to indicate
a code representing the last fault, at the thermostat. Test
mode can be exited by shorting the test terminals for 3
seconds.
Retry Mode: If the control is attempting a retry of a
fault, the status LED will slow flash (slow flash = one
flash every 2 seconds) to indicate the control is in the
process of retrying.
On = Stage 1. Off = Stage 2
Field Configuration Options
Note: In the following field configuration options,
jumper wires should be clipped ONLY when power is
removed from the CXM control.
Table 3a: CXM/DXM LED and Alarm Relay Operations
Source coil low temperature limit setting: Jumper
3 (JW3-FP1 Low Temp) provides field selection of
temperature limit setting for FP1 of -1°C or -12.2°C
(refrigerant temperature).
Not Clipped = -1°C. Clipped = -12.2°C.
Load coil low temperature limit setting: Jumper
2 (JW2-FP2 Low Temp) provides field selection of
temperature limit setting for FP2 of -1°C or -12.2°C
(refrigerant temperature). Note: This jumper should
only be clipped under extenuating circumstances, as
recommended by the factory.
Not Clipped = -1°C. Clipped = -12.2°C.
Alarm relay setting: Jumper 1 (JW1-AL2 Dry) provides
field selection of the alarm relay terminal AL2 to
be jumpered to 24VAC or to be a dry contact (no
connection).
Not Clipped = AL2 connected to R. Clipped = AL2 dry
contact (no connection).
DIP switch 3: Not Used.
DIP switch 4: DDC Output at EH2 - provides selection
for DDC operation. If set to “DDC Output at EH2,”
the EH2 terminal will continuously output the last fault
code of the controller. If set to “EH2 normal,” EH2 will
operate as standard electric heat output.
On = EH2 Normal. Off = DDC Output at EH2.
NOTE: Some CXM controls only have a 2 position DIP
switch package. If this is the case, this option can be
selected by clipping the jumper which is in position 4
of SW1.
Jumper not clipped = EH2 Normal. Jumper clipped =
DDC Output at EH2.
DIP switch 5: Factory Setting - Normal position is “On.”
Do not change selection unless instructed to do so by
the factory.
Description of Operation
LED
Alarm Relay
Normal Mode
Normal Mode with UPS Warning
CXM is non-functional
Fault Retry
Lockout
Over/Under Voltage Shutdown
On
On
Off
Slow Flash
Fast Flash
Slow Flash
Open
Cycle (closed 5 sec., Open 25 sec.)
Open
Open
Closed
Open (Closed after 15 minutes)
Test Mode - No fault in memory
Flashing Code 1
Cycling Code 1
Test Mode - HP Fault in memory Flashing Code 2
Cycling Code 2
Test Mode - LP Fault in memory
Flashing Code 3
Cycling Code 3
Test Mode - FP1 Fault in memory Flashing Code 4
Cycling Code 4
Test Mode - FP2 Fault in memory Flashing Code 5
Cycling Code 5
Test Mode - CO Fault in memory Flashing Code 6
Cycling Code 6
Test Mode - Over/Under
shutdown in memory
Flashing Code 7
Cycling Code 7
Test Mode - UPS in memory
Flashing Code 8
Cycling Code 8
Test Mode - Swapped Thermistor Flashing Code 9
Cycling Code 9
-Slow Flash = 1 flash every 2 seconds
-Fast Flash = 2 flashes every 1 second
-Flash code 2 = 2 quick flashes, 10 second pause, 2
quick
flashes, 10 second pause, etc.
-On pulse 1/3 second; off pulse 1/3 second
DIP Switches
Note: In the following field configuration options,
DIP switches should only be changed when power is
removed from the CXM control.
DIP switch 1: Unit Performance Sentinel Disable provides field selection to disable the UPS feature.
On = Enabled. Off = Disabled.
c l i m a t e m a s t e r. c o m
25
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
DXM Controls
DXM Control
For detailed control information, see the DXM AOM
(part #97B0003N13),
Table 3b: DXM LED And Alarm Relay Operations
Description of
Operation
Status LED
(green)
Test LED
(yellow)
Fault LED
(red)
Load coil low temperature limit setting: Jumper
2 (JW2-FP2 Low Temp) provides field selection of
temperature limit setting for FP2 of -1°C or -12.2°C
(refrigerant temperature). Note: This jumper should
only be clipped under extenuating circumstances, as
recommended by ClimateMaster technical
services.
Alarm Relay
Normal mode
On
-
Off
Open
Normal mode with UPS
On
-
Flashing Code 8
Cycle (closed 5 sec,
open 25 sec)
DXM is non-functional
Fault Retry
Lockout
Test Mode
Night Setback
ESD
Invalid T-stat Inputs
Off
Slow Flash
Fast Flash
Flashing Code 2
Flashing Code 3
Flashing Code 4
Off
On
-
Off
Flashing fault code
Flashing fault code
-
Open
Open
Closed
-
HP Fault
LP Fault
FP1 Fault
FP2 Fault
CO Fault
Slow Flash
Slow Flash
Slow Flash
Slow Flash
Slow Flash
-
Flashing Code 2
Flashing Code 3
Flashing Code 4
Flashing Code 5
Flashing Code 6
Open
Open
Open
Open
Open
Over/Under Voltages
Slow Flash
-
Flashing Code 7
Open (closed after 15
minutes)
-Slow Flash = 1 flash every 2 seconds
-Fast Flash = 2 flashes every 1 second
-Flash code 2 = 2 quick flashes, 10 second pause, 2
quick flashes, 10 second pause, etc.
-On pulse 1/3 second; off pulse 1/3 second
Field Selectable Inputs
Test mode: Test mode allows the service technician to
check the operation of the control in a timely manner.
By momentarily shorting the test terminals, the DXM
control enters a 20 minute test mode period in which
all time delays are sped up 15 times. Upon entering
test mode, the status LED will flash a code representing
the last fault. For diagnostic ease at the thermostat,
the alarm relay will also cycle during test mode. The
alarm relay will cycle on and off similar to the status
LED to indicate a code representing the last fault, at the
thermostat. Test mode can be exited by shorting the test
terminals for 3 seconds.
Retry mode: If the control is attempting a retry of a fault,
the status LED will slow flash (slow flash = one flash every
2 seconds) to indicate the control is in the process of
retrying.
Field Configuration Options
Note: In the following field configuration options,
jumper wires should be clipped ONLY when power is
removed from the DXM control.
Not Clipped = -1°C. Clipped = -12.2°C.
Alarm relay setting: Jumper 4 (JW4AL2 Dry) provides field selection of the
alarm relay terminal AL2 to be jumpered
to 24VAC or to be a dry contact (no
connection).
Not Clipped = AL2 connected to R.
Clipped = AL2 dry contact
(no connection).
Low pressure normally open: Jumper
1 (JW1-LP norm open) provides field
selection for low pressure input to be
normally closed or normally open.
Not Clipped = LP normally closed.
Clipped = LP normally open.
DIP Switches
Note: In the following field configuration options,
DIP switches should only be changed when power is
removed from the DXM control.
DIP Package #1 (S1)
DIP Package #1 has 8 switches and provides the
following setup selections:
1.1 - Unit Performance Sentinel (UPS) disable: DIP Switch
1.1 provides field selection to disable the UPS feature.
On = Enabled. Off = Disabled.
1.2 - Compressor relay staging operation: DIP 1.2
provides selection of compressor relay staging
operation. The compressor relay can be selected to turn
on with a stage 1 or stage 2 call from the thermostat.
This is used with dual stage units (2 compressors
where 2 DXM controls are being used) or with master/
slave applications. In master/slave applications,
each compressor and fan will stage according to
its appropriate DIP 1.2 setting. If set to stage 2, the
compressor will have a 3 second on-delay before
energizing during a Stage 2 demand. Also, if set for
stage 2, the alarm relay will NOT cycle during test mode.
On = Stage 1. Off = Stage 2.
Source coil low temperature limit setting: Jumper
3 (JW3-FP1 Low Temp) provides field selection of
temperature limit setting for FP1 of -1°C or -12.2°C
(refrigerant temperature).
Not Clipped = -1°C. Clipped = -12.2°C.
26
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
1.3 - Thermostat type (heat pump or heat/cool): DIP
1.3 provides selection of thermostat type. Heat pump
or heat/cool thermostats can be selected. When in
heat/cool mode, Y1 is the input call for cooling stage
1; Y2 is the input call for cooling stage 2; W1 is the
input call for heating stage 1; and O/W2 is the input
call for heating stage 2. In heat pump mode, Y1 is the
input call for compressor stage 1; Y2 is the input call
for compressor stage 2; W1 is the input call for heating
stage 3 or emergency heat; and O/W2 is the input
call for reversing valve (heating or cooling, depending
upon DIP 1.4). On = Heat Pump. Off = Heat/Cool.
1.4 - Thermostat type (O/B): DIP 1.4 provides selection
of thermostat type for reversing valve activation. Heat
pump thermostats with “O” output (reversing valve
energized for cooling) or “B” output (reversing valve
energized for heating) can be selected with DIP 1.4.
On = HP stat with “O” output for cooling. Off = HP stat
with “B” output for heating.
1.5 - Dehumidification mode: DIP 1.5 provides
selection of normal or dehumidification fan mode. In
dehumidification mode, the fan speed relay will remain
off during cooling stage 2. In normal mode, the fan
speed relay will turn on during cooling stage 2.
On = Normal fan mode. Off = Dehumidification mode.
1.6 - DDC output at EH2: DIP 1.6 provides selection
for DDC operation. If set to “DDC Output at EH2,”
the EH2 terminal will continuously output the last fault
code of the controller. If set to “EH2 normal,” EH2 will
operate as standard electric heat output.
On = EH2 Normal. Off = DDC Output at EH2.
1.7 - Boilerless operation: DIP 1.7 provides selection
of boilerless operation. In boilerless mode, the
compressor is only used for heating when FP1 is above
the temperature specified by the setting of DIP 1.8.
Below DIP 1.8 setting, the compressor is not used and
the control goes into emergency heat mode, staging
on EH1 and EH2 to provide heating.
2.2 - Accessory1 relay personality: DIP 2.2 provides
selection of ACC 1 relay personality (relay operation/
characteristics). See table 6c for description of
functionality.
2.3 - Accessory1 relay personality: DIP 2.3 provides
selection of ACC 1 relay options. See table 6c for
description of functionality.
2.4 - Accessory2 relay personality: DIP 2.4 provides
selection of ACC 2 relay personality (relay operation/
characteristics). See table 6c for description of
functionality.
2.5 - Accessory2 relay personality: DIP 2.5 provides
selection of ACC 2 relay personality (relay operation/
characteristics). See table 6c for description of
functionality.
2.6 - Accessory2 relay personality: DIP 2.6 provides
selection of ACC 2 relay options. See table 6c for
description of functionality.
2.7 - Auto dehumidification fan mode or high fan mode:
DIP 2.7 provides selection of auto dehumidification fan
mode or high fan mode. In auto dehumidification mode,
the fan speed relay will remain off during cooling stage 2
IF the H input is active. In high fan mode, the fan enable
and fan speed relays will turn on when the H input is
active.
On = Auto dehumidification mode. Off = High fan
mode.
2.8 - Special factory selection: DIP 2.8 provides special
factory selection. Normal position is “On.” Do not
change selection unless instructed to do so by the
factory.
Table 3c: Accessory DIP Switch Settings
DIP 2.1
DIP 2.2
DIP 2.3
ACC1 Relay Option
On
On
On
Cycle with fan
Off
On
On
Digital NSB
On
Off
On
Water Valve - slow opening
On = normal. Off = Boilerless operation.
On
On
Off
OAD
1.8 - Boilerless changeover temperature: DIP
1.8 provides selection of boilerless changeover
temperature set point. Note that the FP1 thermistor is
sensing refrigerant temperature between the coaxial
heat exchanger and the expansion device (TXV or cap
tube). Therefore, the 10°C setting is not 10°C water,
but approximately 16°C EWT.
Off
Off
Off
Reheat Option - Humidistat
Off
On
Off
Reheat Option - Dehumidistat
DIP 2.4
DIP 2.5
DIP 2.6
ACC2 Relay Option
On
On
On
Cycle with compressor
Off
On
On
Digital NSB
On
Off
On
Water Valve - slow opening
On
On
Off
OAD
On = 10°C. Off = 16°C.
All other DIP combinations are invalid
DIP Package #2 (S2)
DIP Package #2 has 8 switches and provides the
following setup selections:
2.1 - Accessory1 relay personality: DIP 2.1 provides
selection of ACC1 relay personality (relay operation/
characteristics). See table 6c for description of
functionality.
c l i m a t e m a s t e r. c o m
27
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Safety Features - CXM/DXM Controls
Safety Features – CXM/DXM Control
The safety features below are provided to protect
the compressor, heat exchangers, wiring and other
components from damage caused by operation
outside of design conditions.
Anti-short cycle protection: The control features a 5
minute anti-short cycle protection for the compressor.
Note: The 5 minute anti-short cycle also occurs at power
up.
Random start: The control features a random start
upon power up of 5-80 seconds.
Fault Retry: In Fault Retry mode, the Status LED begins
slowly flashing to signal that the control is trying to
recover from a fault input. The control will stage off the
outputs and then “try again” to satisfy the thermostat
input call. Once the thermostat input call is satisfied,
the control will continue on as if no fault occurred.
If 3 consecutive faults occur without satisfying the
thermostat input call, the control will go into “lockout”
mode. The last fault causing the lockout will be stored
in memory and can be viewed at the “fault” LED (DXM
board) or by going into test mode (CXM board). Note:
FP1/FP2 faults are factory set at only one try.
Lockout: In lockout mode, the status LED will begin
fast flashing. The compressor relay is turned off
immediately. Lockout mode can be “soft” reset by
turning off the thermostat (or satisfying the call). A
“soft” reset keeps the fault in memory but resets the
control. A “hard” reset (disconnecting power to the
control) resets the control and erases fault memory.
Lockout with emergency heat: While in lockout mode,
if W becomes active (CXM), emergency heat mode will
occur. If DXM is configured for heat pump thermostat
type (DIP 1.3), emergency heat will become active if O/
W2 is energized.
High pressure switch: When the high pressure switch
opens due to high refrigerant pressures, the compressor
relay is de-energized immediately since the high pressure
switch is in series with the compressor contactor coil. The
high pressure fault recognition is immediate (does not
delay for 30 continuous seconds before de-energizing the
compressor).
High pressure lockout code = 2
Example: 2 quick flashes, 10 sec pause, 2 quick flashes,
10 sec. pause, etc.
Low pressure switch: The low pressure switch must be
open and remain open for 30 continuous seconds during
“on” cycle to be recognized as a low pressure fault. If
the low pressure switch is open for 30 seconds prior to
compressor power up it will be considered a low pressure
(loss of charge) fault. The low pressure switch input is
bypassed for the initial 120 seconds of a compressor run
cycle.
Source coil low temperature (FP1): The FP1 thermistor
temperature must be below the selected low
temperature limit setting for 30 continuous seconds
during a compressor run cycle to be recognized as a
FP1 fault. The FP1 input is bypassed for the initial 120
seconds of a compressor run cycle. FP1 is set at the
factory for one try. Therefore, the control will go into
lockout mode once the FP1 fault has occurred.
FP1 lockout code = 4
Load coil low temperature (FP2): The FP2 thermistor
temperature must be below the selected low
temperature limit setting for 30 continuous seconds
during a compressor run cycle to be recognized as a
FP2 fault. The FP2 input is bypassed for the initial 60
seconds of a compressor run cycle. FP2 is set at the
factory for one try. Therefore, the control will go into
lockout mode once the FP2 fault has occurred.
FP2 lockout code = 5
Condensate overflow: The condensate overflow sensor
must sense overflow level for 30 continuous seconds to
be recognized as a CO fault. Condensate overflow will
be monitored at all times.
CO lockout code = 6
Over/under voltage shutdown: An over/under voltage
condition exists when the control voltage is outside the
range of 19VAC to 30VAC. Over/under voltage shut
down is a self-resetting safety. If the voltage comes
back within range for at least 0.5 seconds, normal
operation is restored. This is not considered a fault
or lockout. If the CXM/DXM is in over/under voltage
shutdown for 15 minutes, the alarm relay will close.
Over/under voltage shut down code = 7
Unit Performance Sentinel-UPS (patent pending): The
UPS feature indicates when the heat pump is operating
inefficiently. A UPS condition exists when:
a) In heating mode with compressor energized, FP2 is
greater than 52°C for 30 continuous seconds, or:
b) In cooling mode with compressor energized, FP1 is
greater than 52°C for 30 continuous seconds, or:
c) In cooling mode with compressor energized, FP2 is
less than 4.5°C for 30 continuous seconds.
If a UPS condition occurs, the control will immediately
go to UPS warning. The status LED will remain on as if
the control is in normal mode. Outputs of the control,
excluding LED and alarm relay, will NOT be affected
by UPS. The UPS condition cannot occur during a
compressor off cycle. During UPS warning, the alarm
relay will cycle on and off. The cycle rate will be “on”
for 5 seconds, “off” for 25 seconds, “on” for 5 seconds,
“off” for 25 seconds, etc.
UPS warning code = 8
Low pressure lockout code = 3
28
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Safety Features
Swapped FP1/FP2 thermistors: During test mode, the
control monitors to see if the FP1 and FP2 thermistors
are in the appropriate places. If the control is in test
mode, the control will lockout with code 9 after 30
seconds if:
a) The compressor is on in the cooling mode and the
FP1 sensor is colder than the FP2 sensor, or:
b) The compressor is on in the heating mode and the
FP2 sensor is colder than the FP1 sensor.
Unit Commissioning & Operating Conditions
Environment – This unit is designed for indoor
installation only. Do not install in an area subject to
freezing or where humidity levels can cause cabinet
condensation.
Power Supply – A voltage variation of +/- 10% of
nameplate utilization voltage is acceptable.
Swapped FP1/FP2 thermistor code = 9.
ESD (DXM only): The ESD (Emergency Shut Down)
mode can be enabled from an external common signal
to terminal ESD to shut down the unit. The green status
light will flash code 3 when the unit is in ESD mode.
ESD mode = code 3 (green “status” LED)
CXM/DXM Controls
Diagnostic Features
The LED on the CXM board advises the technician of
the current status of the CXM control. The LED can
display either the current CXM mode or the last fault in
memory if in test mode. If there is no fault in memory,
the LED will flash Code 1 (when in test mode).
The green status LED and red fault LED on the DXM
board advise the technician of the current status of the
DXM control. The status LED will indicate the current
mode that the DXM control is in. The fault LED will
ALWAYS flash a code representing the LAST fault in
memory. If there is no fault in memory, the fault LED will
flash Code 1. The yellow test LED will turn on when in
test mode.
CXM/DXM Control Start-up Operation
The control will not operate until all inputs and safety
controls are checked for normal conditions. The
compressor will have a 5 minute anti-short cycle delay
at power-up. The first time after power-up that there is
a call for compressor, the compressor will follow a 5 to
80 second random start delay. After the random start
delay and anti-short cycle delay, the compressor relay
will be energized. On all subsequent compressor calls,
the random start delay is omitted.
Operation and performance is primarily dependent
upon water temperatures, water flow rates and
ambient air temperature. This water to water
heat pump is capable of operating over a wide
temperature range and with flow rates of between
1.5 GPM (.1 l/s) and 3 GPM (.19 l/s) per ton, however
usually no more than one of these factors may be at a
minimum or maximum level at a time.
The commissioning table indicates water and
air temperatures which are suitable for initial unit
commissioning in an environment where the flow rate
and water temperature is not yet stable and to avoid
nuisance shut down of the units freeze and refrigerant
pressure safeties.
The operating table indicates the maximum and
minimum temperature ranges of the unit.
For more specific unit performance reference the
product catalog, the submittal data sheets or contact
your supplier for assistance.
BUILDING COMMISSIONING
Cooling
Heating
Unit Size
036
060/120
170/340
036
060/120
Source Min/Max
10/43
10/49
10/32
-1/27
-1/27
10/21
Load Min/Max
16/27
16/32
16/32
16/49
16/49
27/49
Ambient Min/Max
7/43
170/340
4/29
BUILDING OPERATING
COOLING
HEATING
Unit Size
036
060/120
170/340
Source Min/Max
10/49
10/49
10/43
-7/27
-7/27
-7/21
Load Min/Max
10/32
10/32
10/32
16/54
16/54
16/49
Ambient Min/Max
7/43
036
060/120
170/340
4/29
All Temperatures are °C
c l i m a t e m a s t e r. c o m
29
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Piping System Cleaning & Flushing
Cleaning and flushing of the WLHP piping system is the
single most important step to ensure proper start-up
and continued efficient operation of the system.
Follow the instructions below to properly clean and
flush the system:
1. Verify electrical power to the unit is disconnected.
2. Install the system with the supply hose connected
directly to the return riser valve. Use a single length
of flexible hose.
3. Open all air vents. Fill the system with the water.
DO NOT allow system to overflow. Bleed all air from
the system. Pressurize and check the system for
leaks and repair appropriately.
4. Verify all strainers are in place. Start the pumps, and
systematically check each vent to ensure all air is
bled from the system.
5. Verify make-up water is available. Adjust make-up
water appropriately to replace the air which was
bled from the system. Check and adjust the water/
air level in the expansion tank.
6. Set the boiler to raise the loop temperature to
approximately 29°C. Open the a drain at the lowest
point in the system. Adjust the make-up water
replacement rate to equal the rate of bleed.
7. Refill the system and add trisodium phosphate in a
proportion of approximately one pound per .5 kg
per 750 L of water (or other equivalent approved
cleaning agent). Reset the boiler to raise the loop
temperature to about 38°C. Circulate the solution
for a minimum of 8 to 24 hours. At the end of this
period, shut off the circulating pump and drain the
solution. Repeat system cleaning if desired.
8. When the cleaning process is complete, remove the
short-circuited hoses. Reconnect the hoses to the
proper supply, and return connections to each of
the units. Refill the system and bleed off all air.
9. Test the system pH with litmus paper. The system
water should be slightly alkaline (pH 6-8.5). Add
chemicals, as appropriate, to maintain acidity levels.
10. When the system is successfully cleaned, flushed,
refilled and bled, check the main system panels,
safety cutouts and alarms. Set the controls to
properly maintain loop temperatures.
30
CAUTION!
CAUTION! To avoid possible damage to a plastic (PVC)
piping system, do not allow temperatures to exceed 43°C.
CAUTION!
CAUTION! DO NOT use 'stop leak' or any similar chemical
agent in this system. Addition of these chemicals to the
loop water will foul the system and inhibit unit operation.
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Unit & System Checkout
BEFORE POWERING SYSTEM, please check the following:
WARNING!
WARNING! Verify ALL water controls are open and allow
water flow prior to engaging the compressor. Freezing of
the coax or water lines can permanently damage the heat
pump.
Note: The manufacturer strongly recommends all
piping connections, both internal and external to the
unit, be pressure tested by an appropriate method
prior to any finishing of the interior space or before
access to all connections is limited. Test pressure may
not exceed the maximum allowable pressure for the
unit and all components within the water system.
The manufacturer will not be responsible or liable
for damages from water leaks due to inadequate or
lack of a pressurized leak test, or damages caused
by exceeding the maximum pressure rating during
installation.
WARNING!
WARNING! Polyolester Oil, commonly known as POE
oil, is a synthetic oil used in many refrigeration systems
including those with HFC-410A refrigerant. POE oil, if it
ever comes in contact with PVC or CPVC piping, may
cause failure of the PVC/CPVC. PVC/CPVC piping should
never be used as supply or return water piping with water
source heat pump products containing HFC-410A as
system failures and property damage may result.
UNIT CHECKOUT
❑
Balancing/Shutoff Valves: Ensure all isolation
valves are open, water control valves wired and
open or coax may freeze and burst.
❑
Line Voltage and Wiring: Ensure Voltage is
within an acceptable range for the unit and
wiring and fuses/breakers are properly sized.
Low voltage wiring is complete.
❑
Transformer On dual voltage units, the installer
must confirm that the power supply and unit
transformer wiring match. Installer must rewire
as needed. Refer to the unit wiring diagram for
proper connections.
❑
Entering Water: Ensure entering water
temperatures are within operating limits of Table 6.
❑
Low Water Temperature Cutout: Verify low
water temperature cut-out on CXM/DXM is
properly set.
❑
Water Flow Balancing: Verify inlet and outlet
water temperatures on both Load and source
are recorded for each heat pump upon
startup. This check can eliminate nuisance
trip outs and high velocity water flows that
can erode heat exchangers.
❑
Unit Controls: Verify CXM or DXM field
selection options are proper and complete.
SYSTEM CHECKOUT
❑
System Water Temperature: Check load and
source water temperature for proper range and
also verify heating and cooling setpoints for
proper operation.
❑
System pH: System water pH is 6 - 8.5. Proper
pH promotes longevity of hoses and fittings.
❑
System Flushing: Verify all hoses are connected
end to end when flushing to ensure debris
bypasses unit heat exchanger and water valves
etc. Water used in the system must be potable
quality initially and clean of dirt, piping slag,
and strong chemical cleaning agents. Verify all
air is purged from the system. Air in the system
can cause poor operation or system corrosion.
❑
Cooling Tower/Boiler: Check equipment for
proper setpoints and operation.
❑
Standby Pumps: Verify the standby pump is
properly installed and in operating condition.
❑
System Controls: Verify system controls
function and operate in the proper sequence.
❑
Low Water Temperature Cutout: Verify
low water temperature cut-out controls are
provided for the outdoor portion of the loop or
operating problems will occur.
❑
System Control Center: Verify control center
and alarm panel for proper setpoints
and operation.
❑
Strainers: Verify 20 mesh (841 micron) [0.84mm]
strainers are installed in load and source water
piping. Confirm maintenance schedule for
strainers.
❑
Miscellaneous: Note any questionable aspects
of the installation.
WARNING!
WARNING! To avoid equipment damage, DO NOT leave
system filled in a building without heat during the winter
unless antifreeze is added to system water. Condenser
coils never fully drain by themselves and will freeze unless
winterized with antifreeze.
Test Mode Pins
c l i m a t e m a s t e r. c o m
LT1
LT2
Short test
pins together
to enter Test
Mode and
speed-up
timing and
delays for
20 minutes.
CXM Board
31
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Unit Start Up Procedure
WARNING!
WARNING! When the disconnect switch is closed, high
voltage is present in some areas of the electrical panel.
Exercise caution when working with energized equipment.
1.
Adjust all valves to their full open position. Turn on
the line power to all heat pump units.
2. Operate each unit in the cooling cycle. Loop water
temperature entering the heat pumps should be
within the limits shown in the operations table.
3. Operate each heat pump in the heating
cycle immediately after checking cooling
cycle operation. A time delay will prevent the
compressor from re-starting for approximately five
(5) minutes.
4. Establish a permanent operating record by logging
the unit operating conditions at initial start-up for
each unit.
5. If a unit fails to operate, conduct the following
checks:
a. Check the voltage and current. They should
comply with the electrical specifications described
on the unit nameplate.
b. Look for wiring errors. Check for loose terminal
screws where wire connections have been made on
both the line and low-voltage terminal boards.
c. Check the supply and return piping. They must
be properly connected to the inlet and outlet
connections on the unit.
d. If the checks described above fail to reveal the
problem and the unit still will not operate, contact
a trained service technician to ensure proper
diagnosis and repair of the equipment.
Note: Units have a five minute time delay in the
control circuit that can be eliminated by entering test
mode. See controls description for detailed features
of the control.
CAUTION!
Table 6: Water Temperature Change Through
Source Heat Exchanger
Water Flow, gpm [l/m]
Rise, Cooling
°C
Drop, Heating
°C
For Closed Loop: Ground Source or
Closed Loop Systems at
3.2 l/m per kW
5 - 6.7
2.2 - 4.4
For Open Loop: Ground Water
Systems at 1.6 l/m per kW
11.1 - 14.4
5.6 - 9.4
Model
Pressure Drop kPa
l/s
0°C
20°C
30°C
Source/Outdoor Coax
340
2.21
3.34
4.42
11.03
26.88
48.95
8.27
24.82
44.82
7.22
23.10
41.36
6.29
21.29
38.47
170
1.1
1.67
2.21
4.82
17.92
32.40
2.76
11.72
22.75
1.72
11.38
21.37
.88
9.47
19.30
Table 8: Coax Water Pressure Drop TMW036-120
Model
l/s
Pressure Drop kPa
-1°C
10°C
21°C
32°C
Source/Outdoor Coax
036
0.28
0.43
0.57
11.7
28.3
49.0
9.0
23.4
41.4
6.9
19.3
35.2
5.5
16.5
31.0
060
0.47
0.71
0.95
10.3
27.6
47.6
9.0
23.4
42.8
17.2
47.6
88.3
14.5
42.1
80.0
120
0.95
1.42
1.89
11.7
30.3
52.4
9.7
26.2
46.9
8.3
22.8
42.1
6.2
18.6
34.5
Load/Indoor Coax
036
0.28
0.43
0.57
4.1
9.7
18.0
3.4
9.0
16.5
2.1
7.6
15.2
060
0.47
0.71
0.95
9.7
24.1
42.8
9.0
22.1
40.0
8.3
20.7
37.9
120
0.95
1.42
1.89
11.0
26.2
46.9
9.7
24.1
44.1
2.1
22.8
41.4
Must use antifreeze if operation falls in grey area
Operation not recommended
CAUTION! Verify ALL water controls are open and allow
water flow prior to engaging the compressor. Freezing of
the coax or water lines can permanently damage the heat
pump.
32
10°C
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Preventative Maintenance
Heat Exchanger Maintenance –
(Direct Ground Water Applications Only)
If the installation is performed in an area with a known
high mineral content (125 P.P.M. or greater) in the
water, it is best to establish with the owner a periodic
maintenance schedule so the coil can be checked
regularly. Consult the well water applications section
of this manual for a more detailed water coil material
selection. Should periodic coil cleaning be necessary,
use standard coil cleaning procedures which are
compatible with either the heat exchanger material or
copper water lines. Generally, the more water flowing
through the unit the less chance for scaling therefore
2.7 l/m per kW is recommended as a minimum flow.
Heat Exchanger Maintenance –
(All Other Water Loop Applications)
Generally water coil maintenance is not needed
however, if the installation is located in a system with a
known high dirt or debris content, it is best to establish
with the owner a periodic maintenance schedule so the
coil can be checked regularly. These dirty installations
are a result of the deterioration of iron or galvanized
piping or components in the system or open cooling
towers requiring heavy chemical treatment and
mineral buildup through water use. Should periodic
coil cleaning be necessary, use standard coil cleaning
procedures which are compatible with both the heat
exchanger material and copper water lines. Generally,
the more water flowing through the unit, the less
chance for scaling, however flow rates over 3.2 l/m per
kW can produce water (or debris) velocities that can
erode the heat exchanger wall and ultimately produce
leaks.
Clean or replace 20 mesh (841 micron) [0.84mm]
strainer/filters on a timely schedule.
Cabinet
Do not allow water to stay in contact with the cabinet
for long periods of time to prevent corrosion of the
cabinet sheet metal. Generally vertical cabinets are
set up from the floor a few inches for prevention. The
cabinet can be cleaned using a mild detergent.
Refrigerant System
To maintain sealed circuit integrity, do not install service
gauges unless unit operation appears abnormal.
Reference the operating chart for pressure and
temperatures. Verify that air and water flow rates are at
proper levels before servicing the refrigerant circuit.
If the refrigerant circuit is opened for any reason, a new
liquid line filter-drier must be installed.
Compressors
Conduct annual amperage checks to ensure amp draw
is no more than 10% greater than that indicated by
serial plate data.
c l i m a t e m a s t e r. c o m
33
34
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
Rev.: 10/09
Please refer to the CM Installation, Operation and Maintenance Manual for operating and maintenance instructions.
LC079
*LC079*
NOTE: Some countries do not allow limitations on how long an implied warranty lasts, or the limitation or exclusions of consequential or incidental damages, so the foregoing exclusions and limitations may not apply to you. This warranty gives you
specific legal rights, and you may also have other rights which vary from state to state and country to country.
Climate Master, Inc. • Customer Service • 7300 S.W. 44th Street • Oklahoma City, Oklahoma, U.S.A. 73179 • (405) 745-6000 • FAX (405) 745-6068
OBTAINING WARRANTY PERFORMANCE
Normally, the contractor or service organization who installed the products will provide warranty performance for the owner. Should the installer be unavailable, contact any CM recognized Representative. If assistance is required in obtaining warranty
performance, write or call:
LIMITATION OF LIABILITY
CM shall have no liability for any damages if CM’s performance is delayed for any reason or is prevented to any extent by any event such as, but not limited to: any war, civil unrest, government restrictions or restraints, strikes, or work stoppages,
fire, flood, accident, allocation, shortages of transportation, fuel, materials, or labor, acts of God or any other reason beyond the sole control of CM. TO THE FULLEST EXTENT PERMITTED BY APPLICABLE LAW AND SUBJECT TO
THE NEXT SENTENCE, CM EXPRESSLY DISCLAIMS AND EXCLUDES ANY LIABILITY FOR LOSS OF PROFITS, LOSS OF BUSINESS OR GOODWILL, CONSEQUENTIAL, INCIDENTAL, SPECIAL, LIQUIDATED, OR
PUNITIVE DAMAGE IN CONTRACT, FOR BREACH OF ANY EXPRESS OR IMPLIED WARRANTY, OR IN TORT, WHETHER FOR CM’s NEGLIGENCE OR AS STRICT LIABILITY. Nothing in this Agreement is intended to
exclude CM’s liability for death, personal injury or fraud.
LIMITATION OF REMEDIES
In the event of a breach of this Limited Express Warranty or any warranty that is mandatory under applicable imperative law, CM will only be obligated at CM’s option to either repair the failed part or unit or to furnish a new or rebuilt part or unit in exchange for the part or unit which has failed. If after written notice to CM’s factory in Oklahoma City, Oklahoma, U.S.A. of each defect, malfunction or other failure and a reasonable number of attempts by CM to correct the defect, malfunction or other
failure and the remedy fails of its essential purpose, CM shall refund the purchase price paid to CM in exchange for the return of the sold good(s). Said refund shall be the maximum liability of CM. TO THE FULLEST EXTENT PERMITTED BY
APPLICABLE LAW, THIS REMEDY IS THE SOLE AND EXCLUSIVE REMEDY OF THE CUSTOMER AGAINST CM FOR BREACH OF CONTRACT, FOR THE BREACH OF ANY WARRANTY OR FOR CM’S NEGLIGENCE
OR IN STRICT LIABILITY.
Limitation: This Limited Express Warranty is given in lieu of all other warranties. If, notwithstanding the disclaimers contained herein, it is determined by a court or other qualified judicial body that other warranties exist, any such warranty, including
without limitation any express warranty or any implied warranty of fitness for particular purpose and merchantability, shall be limited to the duration of the Limited Express Warranty. This Limited Express Warranty does not exclude any warranty that is
mandatory and that may not be excluded under applicable imperative law.
CM is not responsible for: (1) The cost of any fluids, refrigerant or other system components, or the associated labor to repair or replace the same, which is incurred as a result of a defective part covered by CM’s Limited Express Warranty; (2) The cost
of labor, refrigerant, materials or service incurred in diagnosis and removal of the defective part, or in obtaining and replacing the new or repaired part; (3) Transportation costs of the defective part from the installation site to CM or of the return of any
part not covered by CM’s Limited Express Warranty; or (4) The costs of normal maintenance.
This warranty does not cover and does not apply to: (1) Air filters, fuses, refrigerant, fluids, oil; (2) Products relocated after initial installation; (3) Any portion or component of any system that is not supplied by CM, regardless of the cause of the failure
of such portion or component; (4) Products on which the unit identification tags or labels have been removed or defaced; (5) Products on which payment by Customer to CM or its distributors or Representatives, or the Customer’s seller is in default;
(6) Products which have defects or damage which result from improper installation, wiring, electrical imbalance characteristics or maintenance; or from parts or components manufactured by others; or are caused by accident, misuse, negligence, abuse,
fire, flood, lightning, alteration or misapplication of the product; (7) Products which have defects or damage which result from a contaminated or corrosive air or liquid supply, operation at abnormal temperatures or flow rates, or unauthorized opening
of the refrigerant circuit; (8) Mold, fungus or bacteria damages; (9) Products subjected to corrosion or abrasion; (10) Products, parts or components manufactured or supplied by others; (11) Products which have been subjected to misuse, negligence
or accidents; (12) Products which have been operated in a manner contrary to CM’s printed instructions; (13) Products which have defects, damage or insufficient performance as a result of insufficient or incorrect system design or the improper
application, installation, or use of CM’s products; or (14) Electricity or fuel costs, or any increases or unrealized savings in same, for any reason.
If requested by CM, all defective parts shall be returned to CM’s factory in Oklahoma City, Oklahoma, U.S.A, freight and duty prepaid, not later than sixty (60) days after the date of the request. If the defective part is not timely returned or if CM
determines the part to not be defective or otherwise not to qualify under CM’s Limited Express Warranty, CM shall invoice Customer the costs for the parts furnished, including freight. The warranty on any part repaired or replaced under warranty
expires at the end of the original warranty period.
Warranty parts shall be furnished by CM if ordered through an authorized sales representative of CM (“Representative”) within sixty (60) days after the failure of the part. If CM determines that a parts order qualifies for replacement under CM’s
warranty, such parts shall be shipped freight prepaid to the Representative or the ultimate user, as requested by Representative. All duties, taxes and other fees shall be paid by the ultimate user through the Representative.
GRANT OF LIMITED EXPRESS WARRANTY
CM warrants CM products purchased and installed outside the United States of America (“U.S.A.”) and Canada to be free from material defects in materials and workmanship under normal use and maintenance as follows: (1) All complete air
conditioning, heating or heat pump units built or sold by CM for twelve (12) months from date of unit start-up or eighteen (18) months from date of shipment (from CM’s factory), whichever comes first; and, (2) Repair and replacement parts, which are
not supplied under warranty, for ninety (90) days from date of shipment (from factory).
Disclaimer: It is expressly understood that unless a statement is specifically identified as a warranty, statements made by Climate Master, Inc., a Delaware corporation, U. S. A. (“CM”) or its representatives, relating to CM’s products, whether oral, written or contained in any sales literature, catalog, this or any other agreement or other materials, are not express warranties and do not form a part of the basis of the bargain, but are merely CM’s opinion or commendation of CM’s products. EXCEPT AS
SPECIFICALLY SET FORTH HEREIN AND TO THE FULLEST EXTENT PERMITTED BY APPLICABLE LAW, CM MAKES NO WARRANTY AS TO ANY OF CM’S PRODUCTS, AND CM MAKES NO WARRANTY AGAINST
LATENT DEFECTS OR ANY WARRANTY OF MERCHANTABILITY OF THE GOODS OR OF THE FITNESS OF THE GOODS FOR ANY PARTICULAR PURPOSE.
CLIMATE MASTER, INC.
LIMITED EXPRESS WARRANTY /LIMITATION OF REMEDIES AND LIABILITY
(FOR INTERNATIONAL CLASS PRODUCTS)
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Warranty (International)
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Refrigeration Troubleshooting Form
Refrigeration Troubleshooting Form
Water-to-Water Units
Customer:
Loop Type:
Model #:
Serial #:
Startup Date:
Antifreeze Type & %:
Complaint:
REFRIGERANT: HFC-410A
OPERATING MODE:
HEATING POSITION
HEATING
REFRIG FLOW - HEATING
COOLING
REFRIG FLOW - COOLING
REVERSING
VALVE
11 13
10 12
2
1
SUCTION
CONDENSER (COOLING)
EVAPORATOR (HEATING)
COAX
Load
COOLING POSITION
COMPRESSOR
EXPANSION
VALVE
CONDENSER (HT G)
EVAPORAT OR (CLG)
3
COAX
FILTER
DRIER
DISCHARGE
4
HWG**
Source
5 LT2:
**Turn off HWG before
troubleshooting.
1
2
2a
2b
3
4
4a
4b
5
6
7
8
9
9a
9b
10
11
12
13
13a
13b
Description
Voltage
Compressor Amps
Suction Temp
Suction Press
Saturation Temp
Superheat
Discharge Temp
Discharge Press
Saturation Temp
Subcooling
Liquid Line Temp
HEATING
LIQUID
LINE
Heating
5 LT1:
COOLING
LIQUID
LINE
6
7
8
9
Cooling
Source Water In Tmp
Source Water Out Tmp
Source Water In Pres
Source Water Out Pres
Notes
Temp Diff. =
Press Drop
Flow Rate GPM [l/s]
Load Water In Temp
Load Water Out Temp
Load Water In Pres
Load Water Out Pres
Temp Diff. =
Press Drop
Flow Rate GPM [l/s]
Heat of Extraction (Absorption) or Heat of Rejection:
HE or HR =
Flow Rate x
Fluid Factor: (for Btuh)
Fluid Factor: (for kW)
500 (Water); 485 (Antifreeze)
4.18 (Water); 4.05 (Antifreeze)
Temp. Diff x
c l i m a t e m a s t e r. c o m
Fluid Factor
35
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tr a n q u i l i t y ® M o d u l a r W a t e r- t o - W a t e r ( T M W ) S e r i e s
R e v. : 5 F e b r u a r y, 2 0 1 6
Revision History
Date:
Item:
14 August, 2015
21 July, 2015
Action:
Decoder
Wiring Diagrams
Remove CE Text
Wiring Diagram Matrix
Updated
02 January, 2013
POE Oil Warning
Added
09 August, 2011
Unit Maximum Working Water Pressure
Updated to Reflect New Safeties
Entire Document
Removed i-P Unit Measurements
13 August, 2010
09 September, 2010
First Published
7300 S.W. 44th Street
Oklahoma City, OK 73179
Phone: +1-405-745-6000
Fax: +1-405-745-6058
climatemaster.com
*97B0059N05*
97B0059N05
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time for order may be
changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at +1-405-745-6000
for specific information on the current design and specifications. Statements and other information contained herein are not express warranties
and do not form the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products.
ClimateMaster is a proud supporter of the Geothermal Exchange Organization - GEO. For more information visit geoexchange.org.
© ClimateMaster, Inc. 2006
36
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement