LR...24-3 Actuators, On/Off, Floating Point
D148-2W-08
Dimension
Models
LRX24-3-T
LRX24-3
LRX24-3-S
Technical Data
Control
Power supply
Power consumption
Transformer sizing
Electrical connection
LRB24-3
LRX24-3
Overload protection
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
LRB24-3
LRX24-3
Humidity
Ambient temperature
Storage temperature
Housing type
Housing material
Agency listings†
Noise level
Quality standard
LR...24-3-T
Electrical connection
LR...24-3-S
Auxiliary switch
w/Terminal Block
w/3 ft. cable
w/built-in Aux. Switch
on/off, floating point
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 1.5 W
holding 0.2 W
2 VA (class 2 power source)
½” conduit connector
18 GA, plenum rated cable
3 ft [1m]
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0° to 95° rotation
600 Ω
90°, adjustable with mechanical stop
reversible with protected
handle
external push button
N40013 - 06/11 - Subject to change. © Belimo Aircontrols (USA), Inc.
LRB24-3-T
LRB24-3
LRB24-3-S
90 seconds, constant independent of load
150, 95, 60, 45, 35 seconds,
constant independent of load
5 to 95% RH, non-condensing (EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or –S
versions
less than 35 dB (A)
ISO 9001
screw terminal (for 26 to 14 GA wire)
protected (NEMA 2, IP20)
1 SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0° to 100°
† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1
(1.B for -S models)
800-543-9038 USA
20
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
LR...24-3 Actuators, On/Off, Floating Point
2
W193-LR-08
Wiring Diagrams
CAUTION Equipment damage!
3
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
Actuators are provided with color coded wires.
Wire numbers are provided for reference.
4
Actuators may also be powered by 24 VDC.
W123-LR-08
On/Off control
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
Floating Point or On/Off control
N40013 - 06/11 - Subject to change. © Belimo Aircontrols (USA), Inc.
Auxiliary switch
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
21