Victron Skylla TG Battery Charger
 Phoenix MultiPlus Quattro 120VAC - 60HZ
CHARACTERISTICS
24v: 30-50-80A 48v: 25-50A
Perfect chargers for any type of battery
Charge voltage can be precisely adjusted to suit any sealed or unsealed
battery system.
In particular, sealed maintenance free batteries must
charged correctly in order to ensure a long service life. Overvoltage will
result in excessive gassing and venting of a sealed battery. The battery
will dry out and fail.
Controlled charging
Every TG charger has a microprocessor, which accurately controls the
charging in three steps. The charging process takes place in accordance
with the IUoUo characteristic and charges more rapidly than other
processes.
Use of TG chargers as a power supply
As a result of the perfectly stabilised output voltage, a TG charger can be
used as a power supply if batteries or large buffer capacitors are not
ACCESSORIES
available.
Two outputs to charge two battery banks
The TG chargers feature two isolated outputs. The second output, limited
Skylla Control
to approximately 4 A and with a slightly lower output voltage, is intended to
top up a starter battery.
Battery Monitor
To increase battery life: temperature compensation
Every Skylla TG charger comes with a battery temperature sensor. When
connected, charge voltage will automatically decrease with increasing
battery temperature. This feature is especially recommended for sealed
Battery Alarm
batteries which otherwise might be overcharged and dry out due to
venting.
Battery Voltage sense
In order to compensate for voltage loss due to cable resistance, TG
chargers are provided with a voltage sense facility so that the battery
always receives the correct charge voltage.
Charger Switch
A remote on-off switch
An excessively high or
low battery voltage is
indicated by an audible
& visual alarm
Skylla
24/50 TG
24v/48v
24/30 TG
24/50 GMDSS
24/80 TG
24/100 TG
24/30
24/50 TG
24/100 TG
GMDSS
3 phase
3 phase
48/25 TG
Input Voltage
185-265VAC, 320-450VAC, or 180-400VDC
Frequency ( Hz)
45-65
48/50 TG
Charge voltage ’ a bsorption ’ ( V DC )
28.5
57
Charge voltage ’ f loat ’ ( V DC)
26.5
53
Battery capacity ( A h )
Charge current house battery ( A )
(2 )
150-300
250-500
400-800
500-1000
125-250
250-500
30
50
75
100
25
50
Charge current starter battery ( A )
4
n.a.
Charge Characteristic
IUoUo
Temperature Sensor
Yes
Can be used as power supply
Yes
Potential free contacts
Yes
Protection
a,b,c,d
(1 )
Common Characteristic
Temperature:-20 to 60˚C ( 0 - 140˚F ) Max Humidity: 95%
ENCLOSURE
Material & Colour
Aluminium ( blue RAL 5012 )
Battery-Connection
M6 Studs
230 V AC-connection
Screw-clamp 42.5mm² ( AWG 6)
Protection category
IP21
Weight ( kg )
5.5/6
5.5/13
10
10/23
5.5
10
Dimensions ( hxwxd in mm )
365x250x147
365x250x147
365x250x257
365x250x257
365x250x147
365x250x2
57
STANDARDS
Safety
EN 60335-2-29
Emission
EN 55014, EN61000-3-2, EN61000-3-3
Immunity
EN 55014-2
Automotive Directive
95/54/EC
1) Protection a ) Output short circuit b ) Battery reverse polarity detection c) Battery voltage too high d ) Temperature too high
2) Up to 40˚C ambient
WIDE INPUT VOLTAGE 90-265 VAC AND GL APPROVAL MODEL AVAILABLE
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF