Allen-Bradley | SLC 500 1747-L511 | Specifications | Allen-Bradley SLC 500 1747-L511 Specifications

Allen-Bradley SLC 500 1747-L511 Specifications
Artisan Technology Group is your source for quality
new and certified-used/pre-owned equipment
• FAST SHIPPING AND
DELIVERY
• TENS OF THOUSANDS OF
IN-STOCK ITEMS
• EQUIPMENT DEMOS
• HUNDREDS OF
MANUFACTURERS
SUPPORTED
• LEASING/MONTHLY
RENTALS
• ITAR CERTIFIED
SECURE ASSET SOLUTIONS
SERVICE CENTER REPAIRS
Experienced engineers and technicians on staff
at our full-service, in-house repair center
WE BUY USED EQUIPMENT
Sell your excess, underutilized, and idle used equipment
We also offer credit for buy-backs and trade-ins
www.artisantg.com/WeBuyEquipment
InstraView REMOTE INSPECTION
LOOKING FOR MORE INFORMATION?
Visit us on the web at www.artisantg.com for more
information on price quotations, drivers, technical
specifications, manuals, and documentation
SM
Remotely inspect equipment before purchasing with
our interactive website at www.instraview.com
Contact us: (888) 88-SOURCE | sales@artisantg.com | www.artisantg.com
Installation Instructions
SLC 5/01 and SLC 5/02 Modular Processors
(Catalog Numbers 1747-L511, 1747-L514, and 1747-L524)
http://literature.rockwellautomation.com/idc/groups/literature/documents/in/
1747-in011_-mu-p.pdf
FR
Cette publication est disponible en français sous forme électronique (fichier PDF). Pour la
télécharger, rendez-vous sur la page Internet indiquée ci-dessus.
IT
Questa pubblicazione è disponibile in Italiano in formato PDF. Per scaricarla collegarsi al sito
Web indicato sopra.
DE
Diese Publikation ist als PDF auf Deutsch verfügbar. Gehen Sie auf die oben genannte
Web-Adresse, um nach der Publikation zu suchen und sie herunterzuladen.
ES
Esta publicación está disponible en español como PDF. Diríjase a la dirección web indicada
arriba para buscar y descarga esta publicación.
PT
Esta publicação está disponível em portugués como PDF. Vá ao endereço web que aparece
acima para encontrar e fazer download da publicação.
Publication 1747-IN011B-EN-P - September 2007
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Installation Instructions
SLC 5/01 and SLC 5/02 Modular Processors
(Catalog Numbers 1747-L511, 1747-L514, and 1747-L524)
Inside . . .
For
See Page
Important User Information
4
Safety Considerations
5
Install
6
Apply Power to Your
Processor
8
Load Your Software
8
Establish Communications
with the Processor
8
Troubleshoot the Processor
9
Specifications
10
Battery Handling, Storage,
and Transportation
12
Additional Resources
14
Publication 1747-IN011B-EN-P - September 2007
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
4
SLC 5/01 and SLC 5/02 Modular Processors
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment.
Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication
SGI-1.1 available from your local Rockwell Automation sales office or online at
http://www.literature.rockwellautomation.com) describes some important differences between solid state
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying this equipment must
satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot
assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
IMPORTANT
ATTENTION
Identifies information about practices or circumstances that can cause an explosion in
a hazardous environment, which may lead to personal injury or death, property
damage, or economic loss.
Identifies information that is critical for successful application and understanding of
the product.
Identifies information about practices or circumstances that can lead to personal injury
or death, property damage, or economic loss. Attentions help you identify a hazard,
avoid a hazard and recognize the consequences.
SHOCK HAZARD
Labels may be located on or inside the equipment (e.g., drive or motor) to alert people
that dangerous voltage may be present.
BURN HAZARD
Labels may be located on or inside the equipment (e.g., drive or motor) to alert people
that surfaces may be dangerous temperatures.
Publication 1747-IN011B-EN-P - September 2007
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
SLC 5/01 and SLC 5/02 Modular Processors
5
Safety Considerations
ATTENTION
Never install, remove, or wire any module while power is applied.
Also, do not expose processor modules to surfaces or other areas
that may typically hold an electrostatic discharge.
For general recommendations concerning installation safety requirements and
safety related work practices, refer to the requirements specific to your region.
• Europe: Reference the standards found in EN 60204 and your national
regulations.
• United States: Refer to NFPA 70E, Electrical Safety Requirements for
Employee Workplaces.
IMPORTANT
Refer to page 12 for information on proper battery handling,
storage, and transportation.
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or
non-hazardous locations only. The following WARNING statement applies to use in
hazardous locations
WARNING
• Substitution of components may impair suitability for Class I,
Division 2.
• Do not replace components or disconnect equipment unless
power has been switched off or the area is known to be
non-hazardous.
• Do not connect or disconnect components unless power has
been switched off or the area is known to be non-hazardous.
• All wiring must comply with N.E.C. article 501-4(b).
Required Tools
• medium blade screwdriver
• programming equipment
• a 1747-PIC, 1784-KTX, or 1784-PCMK communication interfaces
Publication 1747-IN011B-EN-P - September 2007
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
6
SLC 5/01 and SLC 5/02 Modular Processors
Install
The following sections provide information for installing:
• the battery into the SLC 5/01 (1747-L511)
• the processor in to the chassis
Install the battery
IMPORTANT
If your processor has a battery, make sure it is connected before
installing your processor into the chassis. This provides memory
backup for your processor should the controller power supply
fail.
See page 12 for information regarding proper battery handling and
storage.
1. Open the door of the processor.
2. Remove the jumper from the battery connector socket. Store the jumper in a
safe place for possible future use without the battery.
3. Insert a new or replacement battery in the holder making sure it is held in by
the retainer clips.
4. Plug the battery connector into the socket. See the figure below.
White
Lead
Battery
Connector
Red
Lead
Retainer
Clips
+
Publication 1747-IN011B-EN-P - September 2007
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
SLC 5/01 and SLC 5/02 Modular Processors
7
5. Close the processor door
Install the Processor into the Chassis
ATTENTION
Never install, remove, or wire any module while power is applied.
Also, do not expose processor modules to surfaces or other areas
that may typically hold an electrostatic discharge.
Electrostatic discharge can damage integrated circuits or
semiconductors if you touch backplane connector pins.
If the equipment is not installed and used as described in the SLC
500 Modular Hardware Style User Manual, publication
1747-UM011, the protection provided by the equipment may be
impaired.
1. Turn off power to the chassis where you will insert the processor.
2. Align the circuit board of the processor with the card guide of slot 0 in the
1746 chassis.
Power
Supply
Processor
Release
Card Guide
Protective Wrap
3. Gently slide the processor in until both the top and bottom retainer clips are
secured.
4. Remove the protective wrap after installing the processor.
Publication 1747-IN011B-EN-P - September 2007
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
8
SLC 5/01 and SLC 5/02 Modular Processors
Apply Power to the Processor
To apply power to the processor:
1. Energize the chassis power supply.
2. Check the chassis power supply and processor LEDs. The power LED on the
power supply should be on and the fault LED on the processor should be
flashing.
Indicates the LED is OFF.
POWER
RUN
COMM
Indicates the LED is ON.
CPU FAULT
FORCED I/O
Indicates the LED is FLASHING.
BATTERY LOW
Status of LED does not matter.
The RUN LED on the SLC 5/01 processor is
actually labeled ‘PC RUN.’ Also, the SLC
5/01 processor does not have a COMM
LED.
Load Your Software
Refer to the programming software documentation.
Establish Communications with the Processor
To establish communication with your processor:
1. Connect the 1747-PIC to the processor and your personal computer.
2. Set the communication parameters of the software to match the default
parameters of the processor:
• DH-485
• 19.2K baud
• Node Address = 1
Publication 1747-IN011B-EN-P - September 2007
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
SLC 5/01 and SLC 5/02 Modular Processors
9
Troubleshoot the Processor
Refer to the Troubleshooting chapter in the SLC 500 Modular Hardware Style User
Manual, publication 1747-UM011.
In addition refer to the SLC 500 Instruction Set Reference Manual, publication
1747-RM001. This manual contains explanations and examples for the entire
instruction set as well as for all status words and bits. It also contains explanations
for all possible fault codes found in status word S:6.
Publication 1747-IN011B-EN-P - September 2007
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
10
SLC 5/01 and SLC 5/02 Modular Processors
Specifications
General Specifications
Specification
SLC 5/01 (1747-L511, -L514)
SLC 5/02 (1747-L524)
Program memory
1K or 4K instructions
4K instructions
Additional data storage
0
Maximum I/O capacity
3940 discrete inputs
3940 discrete outputs
Max. local chassis/slots
3/30
Programming software
RSLogix 500
Programming instructions
52
71
8 ms/K
4.8 ms/K
4 µs
2.4 µs
receive
receive or initiate
(1)
Typical scan time
Bit execution (XIC)
DH-485 communication
(2)
Power supply loading @ 5V dc
90 mA
Power supply loading @ 24V dc
0 mA(3)
4096 discrete inputs
4096 discrete outputs
Program scan hold-up time
20 ms to 3 s (dependent on power supply loading)
Noise immunity
NEMA Standard ICS 2-230
Vibration
Displacement: 0.015 inch, peak-to-peak at 5-57 Hz
Acceleration: 2.5 g at 57-2000 Hz
Shock (operating)
30 g
Memory module backup options
1747-M1, -M2
1747-M2
(1) The scan times are typical for a 1K ladder logic program consisting of simple ladder logic and
communication servicing. Actual scan times depend on your program size, instructions used, and the
communication protocol.
(2) A 1747-PIC is required when connecting to the DH-485 channel for programming.
(3) This applies to the processor only. When using the DH-485 port to supply power to a peripheral device such
as a 1747-AIC and 1747-PIC, the current draw is 60 mA DC and 20 mA DC respectively.
Publication 1747-IN011B-EN-P - September 2007
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
SLC 5/01 and SLC 5/02 Modular Processors
11
Environmental Specifications
Specification
Value
Ambient temperature rating
Operating: 0 °C...+ 60 °C (32 °F...140° F)
Storage: 40 °C...85° C (-40 °F...185° F)
Humidity
5 to 95% without condensation
Certifications
Certification
Value
c-UL-us listed
Class 1, Groups A, B, C or D, division 2
CE compliant for all applicable directives
C-Tick marked for all applicable acts
Publication 1747-IN011B-EN-P - September 2007
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
12
SLC 5/01 and SLC 5/02 Modular Processors
Battery Handling, Storage, and Transportation
(Cat. No. 1747-BA)
Battery Handling
ATTENTION
Do not charge the batteries. An explosion could result or cells
could overheat causing burns.
Do not open, puncture, crush, or otherwise mutilate the batteries.
An explosion may result and/or toxic, corrosive, and flammable
liquids would be exposed.
Battery Storage
Store the lithium batteries in a cool, dry environment, typically +20° C to +25° C
(+68° F to +77° F) and 40% to 60% relative humidity.
Battery Transportation
One or Two Batteries
You can ship up to two batteries together within the United States without
restriction. Regulations governing shipment to or within other countries may differ.
Three or More Batteries
Procedures for the transportation of three or more batteries shipped together within
the United States are specified by the Department of Transportation (DOT) in the
Code of Federal Regulations, CFR49, “Transportation.” An exemption to these
regulations, DOT - E7052, covers the transport of certain hazardous materials
classified as flammable solids. This exemption authorizes transport of lithium
batteries by motor vehicle, rail freight, cargo vessel, and cargo-only aircraft,
providing certain conditions are met. Transport by passenger aircraft is not
permitted.
Shipment of depleted batteries for disposal may be subject to specific regulation of
the countries involved or to regulations endorsed by those countries, such as the
Publication 1747-IN011B-EN-P - September 2007
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
SLC 5/01 and SLC 5/02 Modular Processors
13
IATA Restricted Articles Regulations of the International Air Transport Association,
Geneva, Switzerland.
IMPORTANT
Regulations for transportation of lithium batteries are periodically
revised.
ATTENTION
Do not incinerate or dispose of lithium batteries in general trash
collection. Explosion or violent rupture is possible. Batteries
should be collected for disposal in a manner to prevent against
short circuiting, compacting, or destruction of case integrity and
hermetic seal.
For disposal, batteries must be packaged and shipped in accordance with
transportation regulations, to a proper disposal site. The U.S. Department of
Transportation authorizes shipment of “Lithium batteries for disposal” by motor
vehicle only in regulation 173.1015 of CFR 49 (effective January 5, 1983). For
additional information contact:
U.S. Department of Transportation
Research and Special Programs Administration
400 Seventh Street, S.W.
Washington, D.C. 20590
Although the Environmental Protection Agency at this time has no regulations
specific to lithium batteries, the material contained may be considered toxic,
reactive, or corrosive. The person disposing of the material is responsible for any
hazard created in doing so. State and local regulations may exist regarding the
disposal of these materials.
For a lithium battery material safety data sheet, contact the manufacturer.
Sanyo Energy Corporation
600 Supreme Drive
Bensenville, IL 60106
USA
or
Tadarand Electronics
2 Seaview Blvd.
Port Washington, NY 11050
USA
Publication 1747-IN011B-EN-P - September 2007
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
14
SLC 5/01 and SLC 5/02 Modular Processors
Additional Resources
For
Refer to this document
Pub. No.
A more detailed description on how
to install and use your modular SLC
500 system.
SLC 500 Modular Hardware
Style User Manual
1747-UM011
A reference manual that contains
status file data, instruction set, and
troubleshooting information.
SLC 500 Instruction Set
Reference Manual
1747-RM001
If you would like a manual, you can:
• download a free electronic version from the internet:
http://literature.rockwellautomation.com
• purchase a printed manual by contacting your local Allen-Bradley
distributor or Rockwell Automation representative
Publication 1747-IN011B-EN-P - September 2007
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Rockwell Automation Support
Rockwell Automation provides technical information on the web to assist you in
using its products. At http://support.rockwellautomation.com, you can find
technical manuals, a knowledge base of FAQs, technical and application notes,
sample code and links to software service packs, and a MySupport feature that you
can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and
troubleshooting, we offer TechConnect Support programs. For more information,
contact your local distributor or Rockwell Automation representative, or visit
http://support.rockwellautomation.com.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of
installation, please review the information that's contained in this manual. You can
also contact a special Customer Support number for initial help in getting your
module up and running:
United States
1.440.646.3434
Monday – Friday, 8am – 5pm EST
Outside United
States
Please contact your local Rockwell Automation representative for any
technical support issues.
New Product Satisfaction Return
Rockwell tests all of its products to ensure that they are fully operational when
shipped from the manufacturing facility. However, if your product is not
functioning and needs to be returned:
United States
Contact your distributor. You must provide a Customer Support case number
(see phone number above to obtain one) to your distributor in order to
complete the return process.
Outside United
States
Please contact your local Rockwell Automation representative for return
procedure.
Allen-Bradley, Rockwell Automation, TechConnect, SLC, SLC 500, and RSLogix 500 are trademarks of Rockwell Automation,
Inc.
Trademarks not belonging to Rockwell Automation are the property of their respective companies.
Publication 1747-IN011B-EN-P - September 2007
Supersedes Publication 1747-IN011C-MU-P - July 2005
PN 40072-038-01(5)
Copyright © 2007 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Artisan Technology Group is your source for quality
new and certified-used/pre-owned equipment
• FAST SHIPPING AND
DELIVERY
• TENS OF THOUSANDS OF
IN-STOCK ITEMS
• EQUIPMENT DEMOS
• HUNDREDS OF
MANUFACTURERS
SUPPORTED
• LEASING/MONTHLY
RENTALS
• ITAR CERTIFIED
SECURE ASSET SOLUTIONS
SERVICE CENTER REPAIRS
Experienced engineers and technicians on staff
at our full-service, in-house repair center
WE BUY USED EQUIPMENT
Sell your excess, underutilized, and idle used equipment
We also offer credit for buy-backs and trade-ins
www.artisantg.com/WeBuyEquipment
InstraView REMOTE INSPECTION
LOOKING FOR MORE INFORMATION?
Visit us on the web at www.artisantg.com for more
information on price quotations, drivers, technical
specifications, manuals, and documentation
SM
Remotely inspect equipment before purchasing with
our interactive website at www.instraview.com
Contact us: (888) 88-SOURCE | sales@artisantg.com | www.artisantg.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising