Freedom F-8 Installation Manual
R
INSTALLATION INSTRUCTIONS
333 Bayview Avenue
Amityville, New York 11701
For Sales and Repairs, (800) 645-9445
For Technical Service, (800) 645-9440
Publicly traded on NASDAQ
Symbol: NSSC
NAPCO FREEDOM
F-8 CONTROL PANEL
INSTALLATION INSTRUCTIONS
F-TP Touchpad
This manual contains the Installation Instructions for the NAPCO F-8 Control Panel.
It is intended to be used in conjunction with the F-8 Control Panel Programming
Instructions (WI1432) and the F-TP Touchpad, F-LTRANS and F-TAB Installation Instructions (WI1439).
© NAPCO 2005
WI1431A 11/05
System Overview
The NAPCO Freedom F-TP Touchpad Automatic Deadbolt
Security System, a revolutionary new concept in residential security, combines intuitive interactive arming with a passive disarming scheme, providing a system which is not only effortless
to use, but also 100% false alarm resistant during the arming
and disarming sequences.
The system is armed with a simple push of a button ([STAY]
or [AWAY] ) on the F-TP Touchpad control module, followed by
the locking of the home’s deadbolt. To disarm, simply unlock the
deadbolt.
The microprocessor controlled F-TP Touchpad uses information provided by its F-TAB deadbolt sensor and built-in PIR
(Passive Infrared) motion sensor to ensure fool-proof operation.
The F-TAB deadbolt sensor, which is installed in the deadbolt strike hole, senses the state of the deadbolt (locked or
unlocked) and sends this information to the F-TP Touchpad microprocessor, where the decision is made to arm or disarm the
system. There are no moving parts in the F-TAB deadbolt sensor to break or wear out; its adaptive inductive system ensures
trouble free use. If the position of the deadbolt and the F-TAB
sensor changes over time due to the door sagging, deadbolt
replacement, etc., the F-TP Touchpad microprocessor will automatically account for, and make, the necessary adjustments for
these changes.
The F-TP Touchpad’s integral wide-angle PIR motion sensor
acts as an occupancy sensor that provides the microprocessor
with activity information which prevents the user from making
errors during the critical exit and entry periods. For example, if
the user presses the AWAY button, opens and closes the door
and locks the deadbolt but does not leave, the PIR will sense
the user’s presence in the home and automatically default to
STAY mode arming, preventing a false alarm.
If the system is armed in the AWAY mode, the F-TP Touchpad PIR will prevent an intruder from approaching the deadbolt
from inside the premises. If an intruder is detected by the builtin PIR, the system must be disarmed using the F-IFOB digital
key.
By allowing this level of system control without traditional numeric keypad interaction, the Freedom Touchpad System will
provide a significant reduction in false alarms due to user error
and also provide comfortable use of the system to those
customers who might feel uneasy arming and disarming the
system using a traditional keypad.
The Freedom system also supervises all deadbolts in the
system, providing constant deadbolt status on the Touchpad.
This feature, typically found on very elaborate high end security
systems, makes it impossible for the user to arm their system
without first locking all deadbolts.
General Information
The NAPCO Freedom F-8 control panel is designed to work
in conjunction with the Freedom F-8 Touchpad, comprising the
deadbolt-activated security system. The system provides a
maximum of 8 zones, with zones 1 and 2 monitored by the
Touchpad, consisting of the magnetic door contact and Touchpad PIR, respectively. Zones 3 through 6 may be hardwired
zones connected directly to the control panel or wireless devices
reporting to an optional GEM-RECV-XP8 receiver. Zones 7
and 8 may be supported by an optional second Touchpad
(magnetic door contact and PIR), protecting a second exit/entry
door, or may consist of wireless devices.
The system supports a maximum of 2 Touchpads, which
may consist of the following models: F-TP/TAB wireless touchpad (included in F-8KIT1), F-TPG garage touchpad, F-TPBR
bedroom touchpad and F-TP/TAB-H hardwired touchpad. See
ordering information for details.
In cases where the wireless F-TP/TAB Touchpad is used, a
second door may be supported with the use of the F-2D second
door kit, which will transmit magnetic door contact and deadbolt
status into the primary Touchpad. If two wireless Touchpads
are used, a maximum of 4 deadbolts may be protected.
The system may be programmed through the F-PROG
programming tool (the F-PROG is optional and is not UL evaluated), or the PCD-Windows downloading software, version 5.2
or higher.
TABLE OF CONTENTS
ORDERING INFORMATION........................................................................... 3
LISTINGS AND APPROVALS ........................................................................ 3
UL COMPATIBLE SMOKE DETECTORS ...................................................... 3
SPECIFICATIONS .......................................................................................... 4
INSTALLATION & WIRING ............................................................................. 4
PROGRAMMING THE PANEL ...................................................................... 5
F-TP TOUCHPAD OPERATION ..................................................................... 6
FIRE PROTECTION ....................................................................................... 7
TESTING THE SYSTEM................................................................................. 7
F-IFOB DIGITAL KEY OPERATION ............................................................... 7
LOST KEY MODE ........................................................................................... 8
F-PROG KEYPAD OPERATION .................................................................... 8
ZONE FEATURES .......................................................................................... 8
SYSTEM TIMES ............................................................................................. 8
SYSTEM FEATURES ..................................................................................... 9
CENTRAL STATION PROGRAMMING .......................................................... 10
BACKUP TELCO PROGRAMMING ............................................................... 10
PAGER PROGRAMMING............................................................................... 10
REPORT CODES ........................................................................................... 11
ENHANCED COMMUNICATOR FEATURES................................................. 11
SIA CP-01 / MISC FEATURES ....................................................................... 11
WIRELESS...................................................................................................... 11
DOWNLOADING............................................................................................. 12
INSTALLER PROGRAMMING........................................................................ 12
DOWNLOAD-ONLY FEATURES .................................................................... 13
SYSTEM TROUBLES ..................................................................................... 14
CONTACT ID REPORT CODES .................................................................... 15
F-8 PANEL WIRING DIAGRAM ...................................................................... 16
2
NAPCO Freedom F-8 Panel Features:
F-8 Control Panel
• 8 Zones (4 Hardwired/6 Wireless max.)
• 2-wire Fire Zone
• 3 F-TP Touchpad Panics
• Wiraeless Ready
• Bell Supervision
• Telco Line Cut Detection
• Answering Machine Override (Second Call)
• 50 Event Log
Communicator
• 2 Telephone Numbers
• Backup Reporting
• Pager Format
• Contact ID Format
• Individually Report 8 Users
• Opening after Alarm Report (Cancel Code)
• Conditional Closing Report
Ordering Information
F-8KIT1
F-8KIT1-H
F-8KIT2
F-TP/TAB
F-TP/TAB-H
F-2D
F-LTRANS-R
F-IFOB
F-TPBR
F-TPG
F-GDMS
F-GKIT
Includes: F-8 Control Panel, F-TP WirelessReady Touchpad, F-TAB Boltcup Sensor, FBOLT-TRANS Wireless Transmitter (with battery) with Bolt Sensor and Magnetic Door Contact inputs, TRF12 XFormer, (3) F-IFOB Digital
Keys
Freedom F-8 Hardwire Kit. Includes: F-8 Control Panel, F-TP-H Touchpad, F-TAB Boltcup
Sensor, TRF12 XFormer, (3) F-IFOB Digital
Keys
KIT w/PIR, as above plus 45' 65lb pet immune,
microprocessor passive sensor (PIR1680PT)
Wireless-Ready F-TP Touchpad with integral
PIR and Siren, F-TAB Boltcup Sensor, FBOLT-TRANS Wireless Transmitter (with battery) with Boltcup Sensor and Magnetic Door
Contact inputs
Freedom F-8 hardwire Touchpad with integral
PIR, Siren, Bolt Sensor and Magnetic Door
Contact inputs. Also includes F-TAB Boltcup
Sensor
For adding second Freedom Exit/Entry door to
existing Freedom Wireless system. Includes:
F-TAB Boltcup Sensor, F-BOLT-TRANS Wireless Transmitter (with battery) with Boltcup
Sensor and Magnetic Door Contact inputs
Wireless Lock Sensor replacement
Digital credential used to silence alarm, disarm
system in lost key mode
Bedroom Touchpad, provides system control in
bedroom, includes integral PIR and sounder
Garage Door Touchpad provides inputs for FGDMS Garage Door Motor Sensor and Garage Magnetic Door Contact
Garage Door Motor Sensor communicates garage door motor activity to the Touchpad, allowing arm and disarm based on authorized
operation of garage door controller
Garage door kit allows system control through
garage door. Includes F-TPG Garage Door
Touchpad and F-GDMS Garage Door Motor
Listings and Approvals
UL HOUSEHOLD FIRE, BURGLARY WARNING SYSTEM
CONTROL UNIT, AND INTRUSION-DETECTION UNIT.
STANDARDS # 1023, 985
A SINGLE F-TP TOUCHPAD SIREN MEETS THE AUDIBILITY REQUIREMENTS OF UL 985 (RESIDENTIAL FIRE)
AND UL 1023 (RESIDENTIAL BURGLARY)
F-MTAB
F-DRILLJIG
F-PROG*
F-DEMO
F-VINSTALL
F-VHOME
F-TAB-R
F-TP-R
F-8PCB-R
R-TRF12
GEM-RECV-XP8
GEM-RTRANS
GEM-TRANS2
GEM-KEYF
GEM-OUT8
GEM-WP
GEM-SMK
GEM-HEAT
GEM-PIR
GEM-PIRPET
GEM-DT
GEM-GB
RB1000
PCD-WINDOWS
PCI2000/3000
PCL2000B
OI305
WI1438
WI1439
WI1432
WI1431
WI1430
* NOTE: WIRELESS AND ACCESS FEATURES HAVE NOT BEEN
EVALUATED BY UL
UL Compatible Smoke Detectors
F-8 Control Panel Compatible Smoke Detectors
Mfg
Sentrol/
ESL
THE F-TP TOUCHPAD PIR IS APPROVED UNDER STANDARD UL639 INTRUSION DETECTION UNITS
VERIFIED TO COMPLY WITH F.C.C. PART 15 AS CLASS B:
DIGITAL DEVICE
THIS PRODUCT IS APPROVED BY THE CALIFORNIA
STATE FIRE MARSHAL (CSFM) NUMBER 7167-0085:
201
Sensor
MORTISE LOCK APPLICATION TAB
OPTIONAL STEEL DRILLING JIG TOOL
Programming tool for Freedom F-8 Control
Panel
PORTABLE FREEDOM DEMO
NEW NAPCO INSTALLATION TUTORIAL
(cd)
NEW NAPCO CONSUMER VIDEO (vhs)
Replacement F-TAB Bolt Sensor
Replacement Wireless-Ready F-TP Touchpad
Replacement F8 Control Panel circuit board
Replacement 16.5 VAC 20 VA transformer
Wireless Receiver* Supports up to 8 zones, 4
Key Fobs, 4 Smoke Detectors
Recessed Door Transmitter
Window/Door Transmitter
Keyfob Transmitter
Programmable Output Module
Wireless Waterproof Panic Button
Wireless Smoke Detector
Wireless Heat Detector 135°F / Rate of Rise
Wireless PIR
Wireless Pet-Immune PIR
Wireless Dual-Technology Sensor
Wireless Glass-Break Detector
Single Form C Relay Board
WINDOWS PANEL DOWLOADING SOFTWARE, VSN 5.2 (OR HIGHER)
Downloading Interface for IBM Compatible PC
(includes PCL2000B Local Download cable)
Local Download cable
Operating Instructions, F-TP Touchpad
Installation Instructions, Wireless Lock Sensor
(F-LTRANS)
Installation Instructions, F-TP Touchpad, FLTRANS (Wireless Lock Sensor) and F-TAB
Programming Instructions, F-8 Panel
Installation Instructions, F-8 Panel
Installation Instructions, Wireless F-TP/TAB
4-Wire
Smoke Detector
449AT
449C
449CRT
449CST
449CSRT
449CSRH
449CSST
449CLT
449CSLT
449CTE
741U
742U
2-Wire
Smoke Detector
712U
722U
732U
711U
721U
721UT
731U
Detector
Base
701U
702U
702RE
702RU
*521B/BXT (sw 1 on)
System
Sensor
1112
2112
NAPCO
FW-4
2112T
2112TSRB
2100
2100T
2WT-B
**2100AT
1100
FW-2
* Loop Resistance: 30 Ω (max.)
** Loop Resistance: 30 Ω (max.). Refer to WI1471 for installation instructions.
3
Specifications
Maximum Charging Current: ---------------------- 165 mA
Maximum Input Current: ----------------------------- 2.58 A
Current & Voltage Ratings
Alarm Output ------------------------------------------ Burg: 12 VDC, 2 A (max.)
Output Current Limiting ------------------------------ Burg/Fire: 2.25 A
AUX Power: -------------------------------------------- 750 mA
UL Residential Burglary (4 Hour Standby)
Combined Standby Current: -------------------- 500 mA*
Alarm Current Output: ------------------------------- 2 A
(Using Rechargeable 12 VDC 4 AH BATTERY, minimal requirement)
UL Combination Residential Fire and Burglary (24 Hour Standby)
Combined Standby Current: ------------------- 120 mA**
Alarm Current Output: ------------------------------- 95 mA Bell, 275 mA Aux
Power current and 1 F-TP
Touchpad Siren***
(Using Rechargeable 12 VDC 7 AH BATTERY, minimal requirement)
*In Residential Burglary applications Combined Standby current must be
reduced by 160 mA for each F-TP Touchpad.
**In Residential Fire Applications Combined Standby Current must be
reduced by 55 mA for each F-TP Touchpad.
***To disconnect an F-TP Touchpad Siren, do not wire terminal 4 of the
F-TP Touchpad.
Loop Characteristics
Loop Voltage: ------------------------------------------ 5 Volts
Loop Current ------------------------------------------- 1.1 mA
Loop Resistance: -------------------------------------- 300Ω per zone (max.)
Two (2) Wire Fire Loop ------------------------------ 50Ω (max.) or as specified
Device Specifications
Max # Touchpads: ------------------------------------ 2, current = 75 mA
Standby
(160 mA in with Siren On)
Max # Keypads: --------------------------------------- 2, F-PROG,
current = 65 mA
Max # of receivers: ----------------------------------- 2, GEM-RECV-XP8
current = 65 mA each
Max # of F-IFOB Digital Keys ---------------------- 6
Max # of compatible 2-wire
smoke detectors :
10
Max Touchpad wire length : ---------------------- 1000’ total wire length
Miscellaneous
Transformer and Battery
Required Transformer: ------------------------------ NAPCO TRF12 OR
BASLER 16.5 VAC 20VA
Required Battery: ------------------------------------ 12 V 4 AH or 7 AH
Rechargeable
Change Battery every 5 years, or as required.
Installation
Mounting the F-8 Panel
Mount the F-8 Control Panel close to an
unswitched AC source, a cold-water pipe
ground, and a telephone line connection.
Mounting the F-TP Touchpad
The F-TP Touchpad should mounted on the
wall adjacent to the deadbolt strike hole at an
optimal viewing height for the user. Refer to
the F-TP Touchpad Installation Instructions.
Housing Dimensions : ------------------------------ 101/4" x 81/4" x 3"
(26 x 21 x 7.6 cm) HxW xD
Shipping Weight: ------------------------------------- F-8KIT1 8.85 lbs.
Operating Temperature: ----------------------------- 0-49ºC (32-120ºF)
of the next upper level.
For increased
protection, additional detectors should be
installed in areas other than those required,
such as the dining room, bedrooms and utility
room. Heat detectors, rather than smoke
detectors, are recommended in kitchens,
attics, and garages due to conditions that may
result in false alarms and improper operation.
Refer to NFPA Standard 74 (National Fire
Protection Association, Batterymarch Park,
Quincy, MA 02269) for additional information,
including proper mounting methods.
The system must be designed to detect an
intruder attempting to disengage the deadbolt
from the inside of the premises when the system is armed AWAY.
F-TP Touchpad
Wire Color
Control Panel
Terminal
1
RED
16 (+PWR)
2
BLACK
17 (GND)
3
GREEN
18 (GREEN)
4
YELLOW
14 (SIREN PWR)
AC Power and Battery Wiring
Wire as shown in the wiring diagram in the
back of this manual.
WARNING
The FCC restricts the use of this equipment
on certain telephone lines. Read the FCC
statement on the back of this manual to
ensure compliance.
Typical Fire Installation
4
Connect the F-8 Panel EARTH GROUND
screw through a No. 16 AWG or larger wire to
a metal cold-water pipe. Do not use a gas
pipe, plastic pipe or AC ground connections.
Connect a wire with a ground lug crimped or
soldered onto one end and connect it to the
EARTH GROUND screw in the cabinet.
Telephone Wiring
TABLE 1 F-TP TOUCHPAD W IRING
(Where permitted by local codes)
Install smoke detectors outside each sleeping
area and on each floor, including the
basement.
Install the living room and
basement smoke detectors near the stairway
Grounding the F-8 Panel
Complete all wiring before connecting the
battery or AC Power.
Do not plug the
transformer into a switched outlet.
Up to two F-TP Touchpads can be connected
on individual wire runs with #22 AWG wire.
Terminal
#
Wiring
FIGURE 3 Typical Fire Installation
Programming the Panel
Refer to Freedom F-8 Panel Programming Instructions
(WI1432)
TELCO JACK
RJ31X
Defaulting the Panel
1. Remove power from the panel.
2. Remove all wiring from terminal 19 (PGM) and
terminal 3.
3. Connect terminal 19 (PGM) to terminal 3.
4. Apply power to the F-8 Panel.
5. After a few seconds the ARMED, READY and
H SYSTEM TROUBLE LEDs will flash.
6. The F-PROG keypad will beep 3 times
indicating the panel default values have been
loaded.
7. Remove wiring between terminal 19 (PGM)
and terminal 3.
8. Re-install original wiring for terminal 19 (PGM)
and terminal 3.
Bell Circuit Resistor Requirements
If the built-in siren on the F-TP Touchpad is the
only sounding device to be used in the system,
do NOT install an End Of Line resistor. Only
install a 2.2k bell supervision resistor if the F-TP
Touchpad siren is to be disabled. Install the
resistor at the bell or other sounding device.
F-8 Panel at the site
TELCO
PCI2000
J3
J1
J2
TO COMPUTER
TO EXTERNAL
MODEM
LOCAL
TO
J4
TELCO
J5 LINE
OUT TO
Keypad Programming
Refer to WI1432 for information on programming
with the F-PROG keypad.
MODEM
Downloading
The F-8 Panel can be download/uploaded with
PCD-Windows Version 4.2 software using the
Ring Method, Answering Machine
Override
(Second Call) or A6 method of
downloading. The panel can also be automatically
downloaded/uploaded using the PCPreset utilty.
For Site Initiated Downloading, see Auto
Download ID Number [93].
Local Downloading
Wire as shown in Figure 1. Use the power up or
A6 method of establishing a connection. The
power up method is recommended if the panel is
attempting to report.
TELCO
JACK
16
17
+PWR
GND
18
19
RED
BLACK
*RED
*GREEN
*Insulate if not used
PCL2000B
FIGURE 2 REMOTE DOWNLOAD
FIGURE 1 LOCAL DOWNLOAD
Remote Downloading
Wire as shown in Figure 2. The panel can be
remotely download/uploaded using any one of
the following methods:
1. The A6 method
2. Call-in method
3. Answering Machine Override (Second Call)
4. Site-Initiated (PCPreset & A6)
5. Automatic Downloading (Using PCPreset)
Note: If the 2.2k resistor is installed at the F-8
Panel bell terminals, it will be in parallel with the
built-in resistor inside the F-TP Touchpad.
While installing this 2.2k resistor at the F-8
Panel bell terminals will not cause a system
trouble, it will impede the proper supervision of
the siren.
Note: For a UL installation using two F-TP
Touchpads, only one F-TP Touchpad siren
should be activated to ensure proper supervision of the bell circuit wiring. To deactivate
siren of the second F-TP Touchpad, do not
connect the yellow wire.
Wireless Operation
Burglary Zone Wiring
The F-8 Control Panel provides 4 hard-wired,
End-Of-Line Resistor terminated burglary
zones. Wire zones as shown in the wiring
diagram inside the rear housing. All resistors
must be installed, even if the zone is not
used. If required, the feature No End Of Line
Resistor may be programmed, in which case a
direct short across the zone will be the normal
condition (open=fault). NOTE: Not for UL
applications. Program the zone as a No EOL
Resistor Zone [06].
If necessary, use the voltage chart below to
verify proper voltages. These values represent
the DC voltage of the zone while in the
indicated state with reference to the the zone’s
respective ground terminal.
Zone Normal (EOL across zone)
2.5 V
Zone shorted
0V
Zone Open
MODEM
(maximum load of 50 mA).
The GEM-OUT8 is an 8-channel active-low
interface accessory for use with the F-8, providing 8 independent active-low outputs designed
to allow universal voice system and long distance wireless reporting activation simultaneously. Enable location [26-2] to enable the
GEM-OUT8 accessory.
TABLE 3
5V
VOLTAGE AT TERMINALS 3, 5 & 6.
The Freedom F-8 Panel supports two independent wireless systems, each with receivers
and transmitters that are not interchangeable
between the two systems.
The first wireless system allows the Freedom
deadbolt activation/deactivation to be performed by means of an wireless deadbolt transmitter and a receiver located inside the F-TP wireless Touchpad. For more information, see
WI1439.
The second wireless system is comprised of the
GEM-RECV-XP8 receiver and the use of several wireless transmitters to report zone status
and supervision information to the receiver without the use of wires. Each transmitter (such as
wireless smoke detectors, window/door sensors, space-protection devices, etc.) is mapped
to zones 2-8, one for each zone. Note: If an
optional second F-TP Touchpad is used in the
system, "Enable Zone 7 for Wireless" must be
programmed (zone 7 is mapped for this second
F-TP Touchpad).
Fire Zone Wiring (2-Wire)
Wire the Fire Zone as shown in the Wiring
Diagram in the back of this manual. The system supports 2 or 4 wire smoke detectors. An
EOL resistor must be installed, even if the Fire
Zone is not used. See wiring diagram for 4-wire
fire zone.
Fire Zone Normal
Fire Trouble
Fire
TABLE 4
13.0V
13.8V
0.0 V
VOLTAGE AT FIRE ZONE
PGM Wiring
The PGM (Terminal 19) is a switched negative
output that is activated through programming
option(s) that have been selected in
programming addresses [08], [23]-[25].
Connect the device controlled by the PGM
between +PWR and the PGM terminal.
5
F-TP-Touchpad Operation
F-TP Touchpad Indicators
F-TP Touchpad Indicators READY, ARMED,
STAY, FIRE, TBL and AC ● provide system
status.
READY The green READY light shows the
status of the zones in the system, as well as the
optional second deadbolt.
ON indicates that all perimeter zones are secure
and the system is ready to be armed.
FLASHING indicates that at least one zone is
open. To determine the open zone, count
the number of flashes and refer to the zone
list on your security panel.
OFF indicates that the optional deadbolts 2-4 are
not locked. If there are multiple deadbolts in
the system, the other deadbolts must be
locked before the system can be armed.
ARMED The red ARMED light ON indicates that
the system is armed. FLASHING indicates that
the system is in alarm. To determine the zone in
alarm, count the number of flashes and refer to
the zone list on your security panel. Press SILENCE to clear the alarm memory.
STAY The yellow STAY light ON indicates that
the system is armed in the STAY mode, allowing
free movement throughout the premises, while
maintaining perimeter protection.
FIRE The red FIRE light will flash to indicate that
the system is in a Fire Alarm Condition. If a fire
is in progress, evacuate the premises
immediately!
TBL The yellow TROUBLE light will light and the
Touchpad sounder will pulse to indicate that a
system trouble is present.
● AC The green AC Light ON indicates that AC
Power is present.
SIREN - The F-TP Touchpad has an integral
alarm siren. It will sound a steady tone when
intrusion is detected or a distinct pulsating tone
for a fire alarm condition.
Touchpad Controls
(For detailed operation, refer to User Guide
OI305).
STAY Button - Press to arm system in STAY
mode. Perimeter devices such as windows and
doors will be protected, while all interior
protective devices such as motion sensors will be
de-activated, allowing free movement throughout
the premises.
AWAY Button - Press to arm system in AWAY
mode when no one is to remain home. System
will be fully armed with perimeter and interior
protection.
BYPASS Button - This button has multiple func6
tions, depending on the state of the panel.
BYPASS - If you are attempting to arm the system with open zones that cannot be immediately repaired, press BYPASS to temporarily
remove these zones from the system. The FTP Touchpad will beep and TBL will light
steady. Press STAY or AWAY to arm the system as usual.
TEST - Hold Down BYPASS for 4 seconds (and
release) to generate a test report to the central
station and chirp the siren. Hold down BYPASS for 8 seconds to perform a “system walk
test” of the protective devices.
• Walk through the areas protected by motion
sensors. The F-TP Touchpad will beep
when the zone is violated and again when
the zone is restored.
• Open and close all protected doors and windows and listen for the corresponding Touchpad beeps.
• To test transmitter signal strength, see
“Testing the System” on the next page.
After testing the protective devices, the F-TP
Touchpad READY indicator will flash out the
zone number of all zones which have been
activated. Press SILENCE to clear the display
and end the test.
SILENCE Button - Press to silence a Fire Alarm,
silence system troubles and view system troubles.
• Remove F-IFOBs from system: Insert Master
F-IFOB (until beep), then hold SILENCE button for 4 seconds (until beep). Note: Master
F-IFOB will not be removed.
• Test Local F-TP Touchpad PIR Motion Detector: Hold SILENCE button for 8 seconds, until
second beep. Test the F-TP Touchpad’s PIR
Motion Detector by walking in front of it. Press
SILENCE to reset. The F-TP Touchpad
sounder will beep when the internal PIR is
tripped.
Arming when Leaving (AWAY mode)
If you are leaving (and no one is left at home)
and you want to arm the entire system:
1. Check the F-TP Touchpad indicators. The
green READY light must be ON-STEADY,
indicating that the system is ready to arm.
• If the green READY light is BLINKING, this
indicates that a zone is faulted. The
READY light is “blinking out” the zone number of the open zone. Count the flashes
and look at your zone list to see which zone
is open and secure it.
• If the green READY light is OFF, the optional second deadbolt is not locked. If
there are two deadbolts in the system, they
both must be locked before the system can
be armed.
2. Press the AWAY button. The ARMED
indicator will begin to flash, indicating the 60
second exit delay period.
3. Open the door and exit.
4. Lock the deadbolt from the outside to arm
the system. If the deadbolt has not been
locked within 60 seconds of pressing AWAY,
the system will revert back to a disarmed
state.
NOTE: For 60 seconds from the point of arming Away (deadbolt engaged), the system
will check for activity within the premises. If
the system F-TP Touchpad motion sensor
(or any other system motion sensor programmed as an E/E Follower zone) detects
movement within 60 seconds of arming, it
will automatically revert to Stay mode, providing perimeter protection with the interior
protection off. Any activity detected after 60
seconds will result in an alarm. (Requires
[27-2] be enabled.
Arming when Staying (STAY mode)
Arming in the Stay Mode allows you to remain
home with the perimeter protection active and
the interior protection off so that you may move
freely within the premises.
1. Check the F-TP Touchpad indicators. The
green READY light should be ON-STEADY,
indicating that the system is ready to arm.
2. Press the STAY button. The STAY and
ARMED indicators will begin to flash, indicating the 60 second exit delay period.
3. Lock the deadbolt from the intside to arm
the system. If the deadbolt has not been
locked within 60 seconds of pressing STAY,
the system will revert back to a disarmed
state.
Arming when Leaving Others Home
(STAY mode)
If you are leaving and other family members are
remaining home:
1. Check the F-TP Touchpad indicators.
The green READY light should be ONSTEADY, indicating that the system is
ready to arm.
2. Press the STAY button. The STAY indicator will begin to flash, indicating the 60
second exit delay period.
3. Open the door and exit.
4. Lock the deadbolt from the outside to
arm the system. If the deadbolt has not
been locked within 60 seconds of pressing
STAY, the system will revert back to a disarmed state.
Exiting with System Armed (Others Home)
If the system is Armed STAY and you are leaving
other family members home:
1. Press the STAY button. The STAY indicator will begin to flash, indicating the 60
second exit delay period.
2. Unlock the deadbolt from the inside.
3. Open the door and exit.
4. Lock the deadbolt from the outside to
arm the system. If the deadbolt has not
been locked within 60 seconds of pressing
STAY, the system will revert back to a disarmed state.
Exiting with System Armed (No one else
Home)
If the system is armed Stay (with perimeter protection), and you wish to leave (with perimeter
and interior protection), with no one else at
home:
1. Press the AWAY button. The AWAY
indicator will begin to flash, indicating the 60
second exit delay period.
2. Unlock the deadbolt from the inside.
3. Open the door and exit.
4. Lock the deadbolt from the outside to
arm the system. You should hear a siren
chirp confirming Arm AWAY. If the deadbolt has not been locked within 60 seconds
of pressing AWAY, the system will revert
back to a disarmed state.
Bypassing faulted zones
If you are trying to arm the system with faulted
zone(s), the green READY light will be blinking out the number of the faulted zone. If you
cannot locate or repair the zone, it can be
removed from the system, or bypassed.
Bypass the zone(s) by pressing the BYPASS
button (you will hear a beep). The yellow TBL
indicator will light STEADY to indicate that the
zone has been bypassed. The system may
now be armed as usual.
1. Press the BYPASS button. The F-TP
Touchpad will beep and the yellow TBL
indicator will light ON STEADY.
2. Either Press the STAY or AWAY button.
3. If arming AWAY, open the door and exit.
4. Lock the deadbolt.
Disarming when returning home:
When returning home, simply unlock the
deadbolt from the outside to automatically disarm
the system. The red ARMED light will go out and
the green READY light will come on.
Disarming when Home (Armed Stay):
When home with the system armed in the Stay
mode, unlocking the deadbolt from the inside will
disarm the system. The red ARMED light and
yellow STAY will go out and the green READY
light will come on.
Silencing an Alarm
If an alarm occurs while you are at home:
The red ARMED light will be flashing and the
F-TP Touchpad siren will be sounding. To
silence the alarm, insert the F-IFOB key into
the F-IFOB slot on the F-TP Touchpad.
The red ARMED light will continue to flash the
number of the zone (or zones) on which the
alarm occurred.
If an alarm occurs while you are away:
When you unlock the deadbolt to enter, the FTP Touchpad sounder will activate to warn
you that an alarm had occurred while you
were away and the system must be disarmed
manually. To disarm the system, insert the FIFOB key into the F-IFOB slot on the F-TP
Touchpad.
The red ARMED light will continue to flash the
number of the zone (or zones) on which the
alarm occurred. Press SILENCE to clear the
display.
Fire Protection
Fire Alarm (optional)
If a fire is detected, the siren will sound a distinct
pulsating tone and the FIRE indicator on the FTP Touchpad will be flashing.
Fire-Zone Trouble
The system is constantly monitoring the Fire
Zone to insure the connections to the protective
devices are in good working order.
• If the system detects an open on the Fire
Zone, a system trouble will display. The
sounder will activate and the TBL light will
blink 7 times.
Press the SILENCE button to silence the
sounder.
Emergency Buttons (Programmable)
The Emergency Buttons, if programmed, are
always active, whether the system is armed or
disarmed. The emergency signal will only be
transmitted when the Emergency Button is Held
Down for 3 seconds.
• Police Emergency Hold down the Police
Emergency button to alert the central station
of a police emergency.
• Fire Emergency Hold down the Fire I button to alert the central station of a fire
emergency.
• Auxiliary Emergency Hold down the Aux
button to alert the central station of an
Auxiliary emergency.
Note: The Aux button may be programmed to
function as either an Auxiliary Emergency button
or a “service report” button. For Auxiliary Emergency reporting, enable [20-2] (Contact ID Code
140-00).
Testing the System
The following one-step test will test the system’s
siren and central station communicator:
Hold Down the BYPASS button for 4 seconds
(until the F-TP Touchpad beeps). The system will
generate a test report to central station (Contact ID
code 602) and momentarily sound the siren.
• If the siren does not sound, or sounds
weak, check the backup battery and the
associated wiring.
• If the system indicates a communication
failure system trouble (TBL flashing 3
times), call for service. (The communication failure system trouble may take a few
minutes to appear).
A subsequent single press of the SILENCE
button will silence the trouble indication.
Zone Test
Hold Down BYPASS for 8 seconds to perform a
“system walk test” of the protective devices.
• Walk through the areas protected by motion sensors. The F-TP Touchpad will
beep when the zone is violated and again
when the zone is restored.
• Open and close all protected doors and
windows and listen for the corresponding
F-TP Touchpad beeps.
Wireless Signal Strength Test
The F-TP Touchpad will provide an audible
indication of each transmitter’s signal strength.
The signal strength metering is based on a scale
of 4 to 10, with 4 being marginal and 10 being
excellent.
The F-TP Touchpad will “beep out” a number, from
1-4, corresponding to the signal strength of the
transmitter (see Table 5). Each beep is 1 second in
length. The Touchpad will sound a short (.25s)
beep for transmitters with signal strengths of 3 or
less.
SIGNAL STRENGTH
F-TP TOUCHPAD SOUNDER
3 or less
4
5
6-7
.25S BEEP
BEEP BEEP BEEP
8-10
BEEP BEEP BEEP BEEP
BEEP
BEEP BEEP
TABLE 5 AUDIBLE SIGNAL STRENGTH INDICATION
Simultaneously, the F-PROG keypad will provide
both an audible (Table 5) and visual (Figure 6)
indication of transmitter signal strength:
1
Signal Strength = 4
1 2
Signal Strength = 5
1 2 3
Signal Strength = 6-7
1 2 3 4
Signal Strength = 8-10
FIGURE 6 VISUAL SIGNAL STRENGTH INDICATION
Test PIR
Hold Down SILENCE for 8 seconds. Confirm
that the F-TP Touchpad beeps when walking
through the protected area.
After testing the protective devices, the T-TP
Touchpad READY indicator will flash-out the
zone number of all zones which have been activated. Press SILENCE to clear the display and
end the test.
F-IFOB
Operation
Digital
Key
The F-IFOB is a uniquely coded digital key which
performs the following functions when inserted
into the F-IFOB slot on the F-TP Touchpad:
• Disarm an armed system
• Silence an active alarm
The system supports up to (6) F-IFOBs, 1 Master
and 5 additional F-IFOBs. The Master F-IFOB
supports the 3 functions listed above, plus the
ability to enroll additional F-IFOBs into the system.
All F-IFOB activity is logged in the F-8 Panel’s
event buffer. F-IFOBs are identified by User,
with User 1 representing the Master F-IFOB and
the additional F-IFOBs identified as Users 2
through 6, as determined by the order in which
the F-IFOBs were enrolled.
Enrolling the Master F IFOB
The first F-IFOB enrolled into a new system will
automatically be designated as the Master. The
following procedure is used to enroll the master
into a new system (a system which has not yet
had any F-IFOBs enrolled):
1. With the system disarmed, insert the Master
F-IFOB into the F-IFOB slot on the F-TP
Touchpad for approximately 3 seconds and
then remove.
2. Re-insert the Master F-IFOB and then remove.
3. The F-TP Touchpad will beep to indicate that
the F-IFOB has been properly enrolled.
4. Test the Master F-IFOB by arming the system
in the STAY mode and using it to disarm system (insert into the F-IFOB slot and then remove).
Enrolling Additional F-IFOBs
After the Master F-IFOB has been enrolled, additional F-IFOBs may be enrolled using the following procedure:
1. With the system disarmed, insert the Master
F-IFOB into the F-IFOB slot on the F-TP
Touchpad.
2. Remove the Master F-IFOB.
3. Within 8 seconds, insert the new F-IFOB into
the F-IFOB slot on the F-TP Touchpad.
4. Remove the new F-IFOB.
5. Test the new F-IFOB by arming the system in
the STAY mode and using F-IFOB to disarm
system.
Repeat the above steps for each F-IFOB to be
enrolled.
Replacing a lost Master F IFOB
Should the Master F-IFOB be lost, the F-IFOB's
digital code must be cleared from the F-8 Panel
program before a replacement Master F-IFOB
can be enrolled. This may be accomplished
either remotely or locally.
7
Remotely:
1. Establish a connection to the F-8 Panel using
the PCD-Windows downloader software.
2. Upload the existing User Program.
3. Go to the User Code screen and reset the
User 1 code to the default value of 1234.
4. Download the User Program to the control
panel.
Locally:
1. Using a F-PROG keypad programming tool,
enter the Installer program mode.
2. Go to the User 1 Code field (address [95])
and reset it to the default code of 1234.
(press [RESET] [9] [5] [1] [2] [3] [4]).
3. Exit the Installer Program Mode.
Once the User 1 code has been restored to default, a new Master F-IFOB may be learned using the Enrolling the Master F IFOB procedure
above.
Lost Key Mode
In the event that the keys to your deadbolt are
lost or stolen, the system may still be used by
arming in the Lost Key mode. In Lost Key mode,
the system may be armed as usual, however
unlocking the deadbolt will not disarm the system. The system may only be disarmed with the
F-IFOB digital key.
Simultaneously press the STAY and AWAY buttons for 4 seconds to put the system in the lost key
mode. The TBL (Trouble) light will begin to pulse.
The system may be armed as usual, however, it
may only be disarmed with your F-IFOB. To confirm system is in Lost Key mode, press SILENCE.
The TBL light will pulse 6 times. Press SILENCE
again to return to normal operation.
When arriving home to an armed system, open
your Entry door and enter the premises. The FTP Touchpad sounder will sound to remind you
to disarm the system. You must insert the FIFOB into the F-IFOB slot to disarm the system
within 30 seconds, or the alarm will sound.
NOTE: If your deadbolt key is lost, it is important
that you have your locksmith re-key the deadbolt,
or have the deadbolt replaced as soon as possible. In addition, we strongly recommend keeping
your F-IFOB on a different key ring as your deadbolt key.
To exit Lost Key mode and return to normal operation, simultaneously hold down the STAY and
AWAY buttons for 4 seconds. The TBL light will
stop flashing, thus exiting Lost Key mode.
If the user wishes to use the F-IFOB(s) to Silence/Disarm in addition to the keypad Arm/
Disarm code, the Master F-IFOB must be programmed as the User 1 code and the keypad
Arm/Disarm codes must be entered using the
Master F-IFOB ID number to enter User Program
Mode. Once the Master F-IFOB is enrolled in the
system, its ID number can be determined in Installer Program Mode. The User Program Code
is the Master F-IFOB ID number. Although FIFOBs do not have their ID numbers printed on
them, the Master F-IFOB, once enrolled, will
display its number in Installer Program Mode
(address 95...press E to view all 4 numbers).
Use this number in place of the default (1,2,3,4)
User Program Code to enter the user Arm/
Disarm codes.
Entering User Program Mode
1. Enter A8
2. Enter User 1 Code (1234)
3. Press D
(Default)
While in User Program Mode, the "Armed",
"Status" and H System Trouble LEDs will
continue to flash, follow the example below to
program User 2’s code to 1923.
User Mode Programming Example:
1.Press 2, Zone 2 LED will Flash.
2.Enter 1923, Zone 2 LED
will continue to flash until the 4th digit is
entered. The keypad will beep 4 times
confirming a valid entry (Zone LED steady).
Deleting a User Code
Press the number of the User to be deleted, the
zone LED will be flashing indicating that the user
has been selected. Press the F key, the
LED associated with the user will now be OFF.
Exiting User Program Mode
To exit User Program Mode, press C.
Zone Features
[00]Exit/Entry Zones
Delay allows exit and entry through an Exit/
Entry Zone--after the system is armed-without setting off an immediate alarm. Exit
Delay allows the user to leave the premises
after arming. Entry Delay allows the user
time to enter and disarm. The entry delay
may be canceled by pressing F.
[02]Exit/Entry Follower Zones
F-PROG Programmer Operation
(Optional)
User Program Mode
To prevent the loss of the User 1 Code, the panel
default program includes User 1 Code Lockout
[96-2].
To change the User 1 Code from its default value
of 1234, program the 4-digit User 1 Code
through Installer Programming [95]. User 1 Arm/
Disarm code is used to program User Codes 2-8.
By default, the User 1 code cannot be reprogrammed by the user.
If it is necessary to allow the user to re-program
the User 1 code, it can be changed through
downloading or Installer keypad programming.
From Installer Program Mode, change the User 1
Code Lockout ([96-2] LED=OFF) to disabled.
8
Entry Delay allows the user time to enter and
disarm. Allows exit after the panel is armed
without setting off an immediate alarm and
allows entry only if an Exit/Entry Zone [00]
has been violated first.
Group Bypassing - Zones programmed as
Exit/Entry Follower Zones will be Group
bypassed if E is pressed while disarmed
or within the Exit Delay.
[04]24-Hour Protection
A zone that provides protection at all times,
whether or not the system is armed.
[05]40 ms Loop Response
Normally loop response is 750 ms, select this
option to change the loop response to 40 ms.
The slower the loop response, the less
sensitive the system will be to intermittents
(swingers). The programming option is not
permitted for UL installations on zones 3-6.
[06]Disable EOL Resistor
Program this zone type if an End Of Line
Resistor is not required on the zone(s). If
programmed, a direct short across the zone
will be the normal condition (open = fault).
This programming option is not permitted for
UL installations.
[07]Sounder Output
Enables the Bell Output / F-TP Touchpad
siren on a zone alarm for each zone
selected. The Bell Output will remain ON for
the length of time programmed for Burg
(Steady) Output [07]; 0 means output will
stay ON until reset.
[08]PGM Output
The PGM output (terminal 19) is a negative
trigger output which may be used to drive an
LED, low current (<50 mA) relay or to trigger
an input to a long range radio. [08] enables
the PGM Output to activate on a zone alarm
for each zone selected. The PGM Output
will remain ON until reset.
[09]Selective Bypass
If programmed, selected zones will be able
to be bypassed by the User. By default, all
zones are permitted to be bypassed.
System Times
[10]Exit Delay
The delay time which permits exit through an
Exit/Entry Zone [00] after the system is
armed, allows a user to leave the premises
without setting off an immediate alarm. Exit
Delay may be programmed for up to 255
seconds (4¼ minutes); a value of 0 defaults
to 45 seconds for SIA CP-01 (and 15 seconds otherwise). SIA CP-01 Required Default = 60 seconds.
[11]Entry Delay
Delay time permits entry through Exit/Entry
Zone(s) after the system is armed without
setting off an immediate alarm. Entry Delay
allows the user time to enter and disarm the
system.
Upon entering, the Touchpad
sounder will sound a steady tone (Entry
Sound) to remind the user to disarm the
system. Entry Delay Time [11] may be
programmed for up to 255 seconds (4¼
minutes); a value of 0 defaults to 30 seconds
(therefore, any time period programmed will
be added to 30 seconds). Entry Delay may
be canceled by pressing F before or
after arming. SIA CP-01 Required Default =
30 seconds.
[12]Burg (Steady) Output Time-out
Can be programmed from 1 to 255 min (4¼
hours); 0 means output will stay ON until
turned off by entering an Arm/Disarm Code.
[13]Fire (Pulsed/Temporal) Output T/O
Can be programmed from 1 to 255 min (4¼
hours); program 0 for output active until silenced by IFOB or keypad Arm/Disarm
Code. For temporal pattern sounder, enable
[96-3] UL Household Fire.
[14]Test Timer Interval
If Test Timer [36-4] is enabled, program the
interval, in days, between Test Timer
reports. Valid entries are from 1 to 255 days.
[15]Line Cut Time-to-Fail
Enable this feature by programming the delay
time required to declare a line cut failure.
Programming 000 will disable line cut
detection.
[16]Wireless Supervisory Timer
A transmitter will send a transmission every
time it is tripped; when there is no activity, the
transmitter sends a supervisory transmission
about once an hour. If the receiver does not
receive any signal (either a trip or a status)
from a transmitter in the time specified, a
system trouble "RF Supervisory Failure" will
be indicated at the keypad.
Timer is
programmable from 1-26 hours; 0 means NO
supervision. Note: 10 hours must be programmed for UL installations.
[17]Wireless Smoke Sprvsry Timer
A wireless smoke detector will send a
transmission every time it is tripped; when
there is NO activity, the smoke detector
sends a supervisory transmission about
once an hour. If the receiver does not
receive a signal (either a trip or a status)
from a transmitter in the time specified, a
system trouble "RF Supervisory Failure" will
be indicated at the keypad. The Supervisory
timer is programmable from 1-8 hours; 0
means NO supervision. Note: 4 hours must
be programmed in UL installations.
[18]Test Timer Offset
Enter the time, in hours, that a Test Timer will
be used once to report after Installer Mode
has been exited. With the default value of 12,
the test timer will be sent 12 hours after exiting
Installer Mode. The test timer can also be
offset using PCD-Windows Downloading
Software. On power up the test timer is sent
immediately. Follow the commands below to
offset the test timer using Quickloader
Software:
1. From the Status Screen, select
Miscellaneous
2. Enter the number of hours for Test Timer
Offset
3. Select Set Test Timer Offset
4. Select OK
System Features
[20]F-TP Features 1
(1) Enable F-TP Touchpad Fire
Program to send a Fire alarm report (Contact
ID Code 110-00) to central station upon press
of Touchpad Fire button.
Additional Programming required:
Select reporting to Telco 1 [36-1] or Pager
[56-1].
In UL installations, [27-4] must be programmed if this feature is enabled.
(2) Enable F-TP Touchpad AUX
Program to send an Auxiliary alarm report
(Contact ID Code 140-00) to central station
upon press of F-TP Touchpad AUX #3.
Additional Programming required:
Select reporting to Telco 1 [36-2] or Pager
[56-2].
(3) Enable F-TP Touchpad Panic
Program to send a Police Emergency alarm
report (Contact ID Code 123-00) to central
station upon press of F-TP Touchpad police
shield button.
Additional Programming required:
Select reporting to Telco 1 [36-3] or Pager [56-3].
(4) Enable Touchpad Ambush - If enabled,
a 2 second hold-down of the F-Touchpad’s
Silence button within 15 seconds of disarming,
and/or the 8th User Code when entered to
disarm the system will send an Ambush report. Additional Programming required:
• Program User 8 Arm/Disarm Code.
• Select reporting to Telco 1 [36-2] or Pager
[56-2].
UL Installations: If F-TP Touchpad / Keypad
Fire [20-1] is enabled, the keypad must be
mounted within (3) three feet from the F-8
Panel. If [20-4] is enabled, [36-2] must be enabled.
[21]F-TP Features 2
(1) Audible Panic - Enable this option to
change F-TP Touchpad Panic from silent to
audible.
(2) Exit/Entry with Urgency - select to give
an audible indication of Exit and Entry times.
During the last 10 seconds of entry and exit
time, the Touchpad sounds a distinct sound to
indicate the premises must be left or the F-8
Panel must be disarmed.
(3) Display Bypassed (Armed) - Select to
display bypassed zones while the F-8 Panel is
armed.
(4) Service Enable
The F-8 Touchpad Aux button may be programmed for either Auxiliary Emergency reporting [20-2] (Contact ID Code 140-00) or as
an Service Report [21-4] (Contact ID Code
616-00). Test Timer [36-4] also must also be
activated for Service report.
[22]Miscellaneous Features 1
(1) Dialer (Abort) Delay - Program to allow
a 30 second Delay (except 24 Hour Zones)
after a zone alarm and before reporting.
Disarm the system within 30 seconds to
prevent reporting if [79] is not programmed.
(2) Reserved
(3) Swinger Shutdown - Automatically
disables armed zones with excessive alarm/
restores (swingers) while armed. If enabled,
Swinger Shutdown applies to all non-24-Hour
protection zones. A maximum of 3 alarms and
2 restores are allowed per zone while armed
before the zone is disabled.
This
programming option is not permitted for UL
installations.
(4) Bell On Line Cut (Armed) - Activated
(ON) by default. Activates the Sounder Output
if the telephone line has been cut while the F-8
Panel is armed. Note: A time period must be
entered in location [15] Line Cut Time-to-Fail,
in order for [22-4] Bell On Line Cut to function. This programming option is not permitted
for UL installations if [80] is not programmed.
[23]PGM-Prog. Output (T 19) Features 1
(1) PGM on Audio Verification - Enabled
by default to activate the PGM during
reporting. Select specific zones for audio
verification by programming the desired audio
verification zones & events in PGM Output
[08], PGM Features 2 [24] and PGM Features
3 [25]. Connect the PGM to the VeriphoneTM
trigger low input. When location [23-1] is enabled, PGM locations [08], [24], [25] are overridden and location [61] is used instead. If
location [23-1] is NOT selected, then locations [08], [24] and [25] are used to control the
PGM.
(2) Reserved
(3) Follow Keypad Sounder - The following
keypad sounds will activate the PGM output:
Entry Sounder, Keypad Pulsing Sounder,
Keypad Output on Alarm, Chime, Fault Find.
(4) Chirp Bell on Remote (Keyfob) Arm Enabled by default. (SIA CP-01 Requirement).
[24]PGM-Prog. Output (T19) Features 2
(1) Fire - Program to activate the PGM on a
Fire alarm.
(2) AUX - Program to activate the PGM on a
AUX alarm.
(3) Panic - Program to activate the PGM on
a Panic alarm.
(4) Test Timer - Program to activate the
PGM during a Test Timer report.
[25]PGM-Prog. Output (T19) Features 3
(1) AC Fail - Program to activate the PGM
on the loss of AC. (15 minute delay)
(2) Low Battery - Program to activate the
PGM on a Low Battery condition.
(3) *Trouble - Program to activate the PGM
on a Trouble condition.
(4) Armed - Program to activate the PGM
when the panel is Armed. The PGM output
will flash when the panel has gone into alarm.
*Includes Bell Cut, Fire Trouble, Receiver Failto-Respond, Receiver Tamper, Receiver JAM,
Wireless Low Battery, Wireless Supervisory
Fail, Stuck PIR Failure, Zone Trouble.
[26]Miscellaneous Features 2
(1) Momentary Keyswitch Arming - For
Keyswitch Arm/Disarm, connect a normallyopen momentary Keyswitch across Zone 6
zone AND its 2.2K EOLR.
(2) Enable GEM-OUT8. Allows the GEMOUT8 to function with the F-8 Panel, providing
8 outputs that allow the combination of CSVM
voice verification, 7845CZ cell back-up and 2
outputs following the KEYFOB A1 and A2
buttons functioning simultaneously with the F8 Panel. Refer to [61].
(3) Inhibit Fail-to-Communicate Display This option prevents the keypad from either
indicating or sounding when a Fail to
Communicate has occurred.
This
programming option is not permitted for UL
installations.
(4) Inhibit Low Battery Display - Program
to inhibit the Low Battery Display at the F-TP
Touchpad / keypad. Low Battery Reporting is
not inhibited. This programming option is not
permitted for UL installations.
[27]Miscellaneous Features 3
(1) Keyswitch Polarity - Works in conjunction with the momentary keyswitch
function [26-1]. When [27-1] is NOT enabled, the switch type is a momentary N/O
switch wired in parallel with the EOLR (see
the description [26-1] above). To convert
keyswitch operation from Normally Open
style to Normally Closed, enable [27-1]
Keyswitch Polarity, with the momentary N/C
switch wired in series with the EOLR.
Note: Both types of switches must be momentary.
(2) Away to Stay PIR zones
When selected, if the system is armed in the
AWAY mode and interior zone activity is detected within 60 seconds of the system arming, the arming profile will be automatically
changed from AWAY to STAY.
This
programming option is not permitted for UL
9
installations.
(3) Stuck PIR Supervised
When selected, any interior zone which is
faulted at the point of arming and remains
faulted (with no restore) for 4 hours will be
considered a “stuck” PIR and automatically
bypassed from the system. A trouble report
will be sent to central station indicating Interior Zone Trouble (Contact ID code 38900X).
This programming option is not
permitted for UL installations.
(4) F-TP Touchpad Audible Supervision
When selected, an open circuit to the F-TP
Touchpad will sound an audible trouble indication (siren chirp).
[28]Number of Re-Dials if using GEM-OUT8
The number of re-dial attempts made by the
panel if using a GEM-OUT8, with [26-2] enabled. During a Line Cut or Fail-to-Comm
trouble, location [28] will control the number
of dial attempts.
[69]Miscellaneous Features 4
(1) Priority on all zones:
When disarmed, a non-bypassed faulted
zone will flash the zone number. A faulted
non-bypassed zone will prevent arming
when the deadbolt is engaged. This option
must be programmed for UL installations.
(2) Reserved
(3) Disable CHIME on Power Up
All perimeter zones will chime on fault. Keypad, if used, will allow toggling chime on/off.
(4) Fire Alarm Verification - Default is
disabled. If this feature is enabled, the first
trip of a smoke detector will not generate an
alarm. The panel will remove power from
the smoke detector for 14 seconds, allow the
smoke detector to reset for 6 seconds then
wait for another trip for 60 seconds. Only if
another trip is sensed within the 60 seconds
will the system generate a fire alarm.
Central Station Programming
[30]Subscriber ID Number
For 4/2 format, enter a 4 digit number. If 3/1
format is required, enter a 3 digit number,
then press F to blank the last digit.
[31]Telephone Number 1
Program the telephone number to be dialed
for Telephone Number 1. Program the
number directly, just as it is entered on a
TouchTone telephone. A fixed Dial Tone
Detection (E) is included in the Dialing Prefix
(address number 44). Programming an E is
not required for Telco 1, Backup and Pager.
Use F to blank out remaining digits in
the telephone number.
[32]Receiver Format
Select the receiver format (enter number
listed below) to be used to report for
Telephone Number 1. Must be set to 6 for
Contact ID/Point ID.
[0] Disabled
[1] Ademco Slow
[2] Radionics Slow
[3] Silent Knight Fast
[4] Universal High Speed
[5] Reserved
[6] Ademco Point ID
[7] Pager
[33]Receiver Options
(1) 2300 Hz HS/Kissoff - Enable for 2300
10
Hz Handshake and Kissoff (pulse format).
(2) Sumcheck - See address [32]. Only
used for the following Receiver Formats:
Ademco Slow, Radionics Fast, Silent Knight
Fast and Universal High Speed. This is a
sophisticated data format used to enhance
the speed and check the accuracy of the
received transmission. This format should
be used whenever the central station has
sumcheck capability. Instead of sending a
second round to verify correct data, the
panel sends a Sumcheck digit after sending
the Subscriber ID and Alarm Code.
(3) Single Digit - 3/1 receiver format. 3-digit
Subscriber ID number and a 1-digit Alarm
Code will be transmitted.
(4) No Handshake - See address [32]. If
programmed, no Handshake/Kissoff will be
required by the panel.
[34]Zone Report, Telco 1
Select zone(s) required to send an alarm
report to Telephone Number 1.
[35]Zone Restore Report, Telco 1
Select zone(s) required to send a restore
report to Telephone Number 1. The zones
will send a restore after Bell time-out, unless
programmed as silent zones.
[36]System Reporting, Telco 1
(1) F-TP Touchpad Fire - Program to
activate a Touchpad Fire report (I).
(2) F-TP Touchpad AUX AMBUSH Program to activate an AUX or AMBUSH
report (A button on Touchpad). Note: If [362] is enabled, [20-4] must also be enabled.
(3) F-TP Touchpad Panic - Program to
activate a Panic report (Touchpad Aux button
#3).
(4) Test Timer / Comm. Test - Program to
activate a Test Timer report. Test Timer
Interval [14] must also be programmed for
periodic Test Timer Report. Test Timer [364] also must be activated for Test report.
• To enable the Communicator Test, enter
Program Mode, go to address 36 and press
4. For Comm. Test only, do not program
[14].
[37]System Reporting, Telco 1
(1) AC Fail Report - Program to activate
an AC Fail report (15 minute fixed report
delay).
(2) Low Battery Report - Program to
activate a Low Battery report.
(3) Trouble Report - Program to activate a
Trouble report. (See Note A, below).
(4) Fire Report - Program to activate a
Fire report.
[38]System Restore Report, Telco 1
(1) AC Restore - Program to activate an
AC Restore report.
(2) Battery Restore - Program to activate
a Battery Restore report.
(3) Trouble Restore - Program to activate a
Trouble Restore report. (See Note A, below).
(4) Fire Restore - Program to activate a
Fire Restore report.
Note A: (Applies to [37-3] and [38-3]): Includes Bell Cut, Fire Trouble, Receiver/F-TP
Touchpad Fail-to-Respond, Receiver Tamper, Receiver JAM, Wireless Smoke Low
Battery, Wireless Smoke Supervisory Failure,
Wireless Low Battery, Wireless Supervisory
Fail, Wireless Tamper, Stuck PIR Failure,
Zone Trouble. Contact ID format will report
trouble(s) by device and ID number.
[39]Opening/Closing Report, Telco 1
Select users required to send opening and
closing reports to Telephone Number 1. Do
not program for users that are intended to
send a Cancel Code or Conditional Closing
reports.
Backup Telco Programming
[40]Backup Subscriber ID Number
For 4/2 format, enter a 4 digit number. If 3/1
format is required, enter a 3 digit number
then press the F key.
[41]Backup Telephone Number 2
Program the telephone number to be dialed
for Telephone Number 2. A fixed dial tone
detection (E) is included prior to the Dialing
Prefix [44]. To program any additional delay
enter a "D" where required in the telephone
number.
[42]Backup Receiver Format
Refer to section [32] Receiver Options.
[44]Dialing Prefix
Dialing prefix for Telco 1, Backup, and
Pager. Program if using an Outside access
number. A pre-dial delay of 4 seconds is
included by default in the Dialing Prefix
(Address 44). For a delay of 4 seconds,
program “D” in first location. If a fixed dial
tone detection is desired, program “E” in the
first location.
[45]Communicator Features 1
(1) Communicator Enabled - Program to
enable the communicator.
(2) DTMF with Rotary Backup - The first
attempt to communicate is dialed using the
TouchTone method of dialing, subsequent
attempts are dialed using the pulse method
of dialing. Disable this feature to dial using
only rotary dialing.
(3) DTMF only - All attempts to
communicate dial using the TouchTone
method of dialing.
(4) Backup Reporting - After 2 attempts
are made to communicate to Telco 1, the
backup phone number is dialed [41]Backup.
[46]Communicator Features 2
(1) Disable Call Waiting - Default is disabled. If this feature is enabled, the first
attempt will dial " *70" prior to the telephone
number (disabling the call waiting tone during the alarm transmission). If the first call
does not get through, subsequent attempts
will dial as programmed.
(2) 2:1 Rotary Dialing - Changes the
make break ratio when rotary dialing from
1.5:1 to 2:1.
(3) Backup if <4 attempts - If Backup
Reporting [45-4] has been enabled, the
communicator will use Telephone Number 2
[41] for the remaining retries when there are
less than 4 retries remaining.
(4) Reserved
Pager Programming
If Pager Format is enabled, pager data will
be displayed as shown in Figure 8. If Pager
Format is selected, 4/2 format must be
programmed and Sumcheck is not
permitted. If a PIN number is required, refer
to Leading Digits [47].
000033-3456
Leading Digits
Report Code
Subscriber ID Number
FIGURE 8
DEFAULT PAGER DISPLAY
Pager Alarm data is the same as 4/2 format
with the exception that the 2 digit Report
Code is transmitted before the 4 digit
Subscriber ID.
NOTE:
Digits in Report Codes and subscriber IDs that are
programmed with "B" through "F" will be converted to "0"s.
[47]Pager Leading Digits
Pager PIN Number - If a PIN number is
required by the paging system, program the
PIN number in the Leading Digits location.
See sample program below.
If a 7-digit PIN number is required, program
the panel as follows:
[31]/[41]/[51] - Telephone number
[32]/[42]/[52] - Select Format
[47] - X X X X X X X C
Burglary for zones 1 through 8. Optionally,
Contact ID codes for zones 1 through 8 can
be programmed as follows:
[1] Fire
[9] Reserved
[2] Panic
[A] Auxiliary
[3] Burglary
[B] 24 Hour Aux.
[4] Holdup
[C] Reserved
[5] General Alarm
[D] Burg Perimeter
[6] Reserved
[E] Burg Interior
[7] Gas Alarm
[F] Tamper
[8] Heat Alarm
[62]Pager Format Zone Codes
[62-1] Restore Code - Zones 1 through 8.
The second digit of the restore code is the
zone number of the restored zone. For
example, if the Zone Restore Code [62] is
programmed to E, the restore code for that
zone would be E4 (4/2 format).
[62-2] Zone Trouble (Status) Code - Modifies Conditional Closing Reports. If zones
are bypassed at the time of arming, the Conditional Closing report is sent along with the
zone number of the bypassed zone(s)
(Contact ID code 570-00X). For example, a
conditional closing by User 2, with zones 2
and 3 bypassed would be as follows:
1234
C2
1234
F2
1234
F3
[63]Pager Format System Report Codes
7-digit PIN Number
Terminating Digit (#)
Leading and Trailing digits can be letters B,
C or D. B = the * button on a telephone, C =
the # button on a telephone, D = 2 second
delay.
[48]Pager Trailing Digits
Transmitted after alarm data. Refer to
section [47] for programming information.
[49]Pager Options
(1) Skip Alarm Data - Once pager format is
selected, program this option to skip alarm
data. If this option is selected, all the
programmed Leading and Trailing digits are
sent, but the event code and subscriber ID
are not transmitted.
With this option
selected, a telephone number programmed
in Leading Digits or Trailing Digits would
send the telephone number to the pager
each time a report is sent.
(2) Reserved
(3) Reserved
(4) Reserved
[50] - [59]
Programming is the same as for Telco 1.
Program to split/double report to Pager.
Refer to sections [30] through [39].
Report Codes
[60]Pager Format Zone Report Codes
Report Code for Zones 1 through 8.
4/2 format - The Zone Report Code is the
1st digit of the report code sent, the second
digit is the zone number of the reporting
zone. For example, if zone 2 has a report
code of 3, the report code would be 32.
3/1 format - Sends only the report Code and
does not append it with the zone number.
[61]Contact ID Report Codes
Contact ID Report Codes are defaulted to
Program a 2-digit report code for Touchpad
Fire, Touchpad AUX, Touchpad Panic, Test
Timer, AC Fail, Low Battery, Trouble and
Fire.
[64]Pager Format System Restore Code
The code sent when a system condition
restores. The second digit of the 2-digit
restore code is the second digit of the
System Report Code [63]. For example, if a
Low Battery System Report Code is F8 the
Battery Restore would be E8 (4/2 format).
[65]Pager Format Opening and Closing
Codes
Program Opening and Closing Codes for
Users 1 through 8. The second digit of the
report code is the number of the user that
armed or disarmed the system.
For
example, if the Closing Code [65] is
programmed with a C, the closing code for
User 2 would be C2 (4/2 format).
[66]Pager Format Ambush Report Code
Program a 2-digit report code for Ambush.
To send an ambush report, program a User
Code for User 8, Program report User 8 as
Ambush [20-4] and Select reporting for Telco
1 [36-2] and/or Pager [56-2].
Enhanced Comm. Features
[67]Telephone Number 1
(1) Send Cancel Report - Default is enabled. When enabled, will allow a 5 minute
window during which a Cancel Report
(Contact ID code 406-00X) will be transmitted should the system be disarmed during
this time. This 5 minute cancel window
starts at the end of the abort timeout if the
abort feature is enabled; otherwise the 5
minute timeout starts immediately upon the
alarm. Only non 24-hour zones start the
Abort delay and Cancel report timers.
(2) Conditional Closing Telephone 1 When enabled, all users that are not
selected to report an Opening/Closing ([39],
[59]) will report a Closing only when zones
have been bypassed (Contact ID code 40000X). The Status Report (Contact ID code
570-00X) and [62-2] for Pager format is used
to report zones that have been bypassed at
the time of the closing report.
(3) Enable "GEM-KEYF"
(4) Enable "UL G"
[68]Pager Reporting
(1) Cancel Code - see [67-1].
(2) Conditional Closing Pager - see [672].
(3) Reserved
(4) Enable F-TP Ambush Sounder – If
enabled, when disarmed using a deadbolt,
the F-Touchpad will produce a sounder during the 15 second Ambush window.
[69]Miscellaneous Features 4
(1) Priority on all zones - When disarmed, a non-bypassed faulted zone will
flash the zone number. A faulted nonbypassed zone will prevent arming.
(Required for UL installations).
(2) Reserved
(3) CHIME disabled on Power Up - All
perimeter zones will not chime on fault. Keypad, if used, will allow toggling chime on/off.
(4) Fire Alarm Verification - Default is
disabled. If this feature is enabled, the first
trip of a smoke detector will not generate an
alarm. The panel will remove power from
the smoke detector for 14 seconds, allow the
smoke detector to reset for 6 seconds then
wait for another trip for 60 seconds. Only if
another trip is sensed within the 60 seconds
will the system generate a fire alarm. (Not
for California State Fire Marshall approved
installations).
SIA CP-01 / Misc. Features
[70] Miscellaneous Features 5
(1) Exit Restart Enabled - Default is enabled. When enabled, exit delay will be restarted if an egress door is opened, closed
then re-opened. This will occur only once
per arming period.
(2) Convert Away to Stay if No Exit Default is enabled. The system arms in the
Stay mode if the exit delay expires and no
exit has been made.
(3) Enable Bypass For Zone 6 Supervisory Zone - Default is disabled. New location enabled for Cellular Backup. Allows
zone 6 to be bypassed, and on an open
reports contact ID code 330. Requires [70-4]
to be enabled. If [70-3] is enabled, the bell
will chirp 8 seconds after arming and it will
chirp a second time after the Central Station
has acknowledged the receipt of the closing
report.
(4) Zone 6 24Hr Suprvisory Zone New location enabled for Cellular Backup.
Default is disabled. If enabled, Zone 6 will
act as follows: 24 Hour zone, short on Zone
causes alarm with pulsing bell, 1 second on,
1 second off. An open on zone 6 will cause
a trouble report and zone 6 will display on
the F-TP Touchpad. Alarm time-out follows
Fire time-out unless feature [70-3] is enabled.
[79]Abort Delay By Zone Mask
All 8 Zones enabled by default.
11
[80]No Auto-Reset
All 8 Zones enabled by default. This feature
only allows one trip per arming period. The
panel must be disarmed then rearmed for a
burglary zone to generate an alarm again.
[89]Cross Zoning
All 8 Zones disabled by default. Requires
two zones in mask to trip within 90 seconds
of each other before an alarm transmission
sequence (alarm report) is set to Central
Station. Note: If No Auto-Reset [80] is enabled, only 1 trip per Group per arming period will occur.
Wireless
Up to two receivers can be wired to the F-8
Panel. Each wireless transmitter can be
mapped to a zone. Only 1 wireless device is
permitted per zone, however, the use of both
hardwired and wireless on a zone is
permitted.
To Map a transmitter to a zone:
1. Enter the Programming address number
to which the transmitter is to be mapped.
2. Enter the 7-digit RF ID number directly,
just as it is shown on the device label.
After the 7th digit is entered the keypad
will beep.
A transmitter will send a transmission every
time it is tripped. The transmitter also sends
a supervisory transmission about once every
hour. If the receiver does not receive a
signal from a transmitter in the time
programmed in Wireless Supervisory Timer,
a system trouble "RF Supervisory Failure"
will be indicated at the keypad.
Program Wireless Supervisory Timer [16] to
change the supervisory time from the default
of 12 hours.
The Signal strength of a transmitter can be
checked at the keypad (see A7
Fault Find Mode).
[71-78] Wireless Transmitters
Enter the RF ID# and the point number that
is to be mapped to the zone.
Programming Example
Map point 1 of a window door transmitter
with an RF ID# of 0012B0:0 to Zone 3.
1. Enter Installer Mode.
2. Enter C(beeps)73(beeps).
3. Enter
12G200.
4. Enter 1 (beeps).
Note: If the RF ID# in step 3 is not entered
correctly, the keypad will emit a 1 second
tone indicating incorrect entry. Repeat steps
2 - 4 above.
[81] - [84] Wireless Keyfobs
The GEM-KF is a hand-held wireless
transmitter capable of Arming and Disarming
the control panel and/or activating 2 Auxiliary
Functions.
To activate the auxiliary
functions, press and hold the [A1] or [A2] key
for 1.5 seconds (see WI752 for more
information).
Enter the RF ID# and AUX 1 and AUX 2
options for each Keyfob.
AUX 1 & AUX 2
Programming Options:
1 Panic
Program a 1 in the AUX 1 and/or AUX 2
12
option to initiate a panic alarm when the [A1]
or [A2] buttons on the Keyfob are pressed.
Additional programming required:
• Touchpad Panic [20-3]
• Panic Report to Telco 1[36-2] and/or
Pager [56-3]
• Audible Panic (Optional) [21-1]
2 AUX
Program a 2 in the AUX 1 and/or AUX 2
option to initiate a AUX alarm when the [A1]
or [A2] buttons on the Keyfob are pressed.
Additional programming required:
• Touchpad AUX [20-2]
• AUX Report to Telco 1[36-2] and/or Pager
[56-2].
3 Bell ON
Program a 3 in the AUX 1 and/or AUX 2
option to turn the Bell ON when the [A1] or
[A2] buttons on the Keyfob are pressed.
Press the [OFF] button to turn the Bell OFF.
4 PGM
Program a 4 in the AUX 1 and/or AUX 2
option to activate the PGM Output when the
[A1] or [A2] buttons on the Keyfob are
pressed. Press the [OFF] button to turn the
PGM Output OFF.
5 Instant
Program a 5 in the AUX 1 and/or AUX 2
option to activate Instant Mode when the
[A1] or [A2] buttons on the Keyfob are
pressed.
6 RESERVED
7 Full Set System
Program a 7 in the AUX 1 and/or AUX 2
option to Fully Set the System when the
[ON] and the [A1] or [A2] buttons on the
Keyfob are pressed, or when the [A1] or [A2]
buttons are pressed when the system is
armed with Exit/Entry Follower Zones.
Program an 8 in the AUX 1 and/or AUX 2
option to Bypass Exit/Entry Follower Zones.
[85] - [88] Wireless Smoke Detectors
Enter the RF ID# of the smoke detector.
A wireless smoke detector sends a
supervisory transmission about once every
hour. If the receiver does not receive a
signal from a transmitter in the time
programmed in Wireless Smoke
Supervisory Timer, a system trouble "RF
Smoke Supervisory Failure" will be indicated
on the keypad.
Program Wireless Smoke Supervisory Timer
[17] to change the time from the default time
of 8 hours. Refer to Household Fire [96-3].
Note: Mark Smoke Detectors (Smoke 1
through Smoke 4) in order to identify them in
the event of a supervisory or battery failure.
If Household Fire [96-3] is selected, Wireless
Smoke Supervisory Time is fixed at 4 hours.
Downloading
[90]Callback Telephone Number
Program the phone number of the
downloading computer to be dialed by the
panel during a high security download.
[91]Ring Count
Program the number of rings before the
panel will pick-up. Ring Method [92-1]
(Downloading Features) must also be
selected.
[92]Downloading Features
(1) Ring Method - Enable the ring method
of downloading. The panel will pick-up on
the number of rings programmed in Ring
Count [91].
(2) Answering Machine Override - Select
this method to enable the panel to respond
to a Second Call Download. Using PCDWindows downloading software, the
downloading computer will dial the panel
phone number, wait for the programmed
Second Call Duration, hang up and then redial. When the panel recognizes the second
ring, it will respond to the download. Ensure
that the PCD-Windows account has been
configured for Second Call (see Panel selection, Download to Panel tab).
(4) Reserved.
[93]Auto Download ID Number
Enter the number that is used by PCPreset
when downloading using the Site Initiated
Auto Downloading function (A6).
The requirements for Site Initiated Auto
Downloading are as follows:
1. An F-PROG Keypad must be connected
to the system.
2. Download Computer running PCPreset.
3. Program the telephone number of the
Download Computer in location [90]
Callback Telephone Number.
4. Program location [93] with the number
of the PCPreset account that is to be
downloaded.
PCPreset
1. Create the F-8 Panel account to be
downloaded using PCD-Windows
Quickloader Software.
2. Create a List using PCPreset.
3. Select the account by pressing t.
Select the desired account from the list
of PCD-Windows accounts available.
(The location in the list is the Auto
Download ID Number [93])
4. Tag the list by entering aD
(download)
5. Enter Standby Mode by entering o.
The Computer is now in STANDBY mode
Site
At the site perform the following three steps:
1. Arm the panel.
2. Disarm the panel.
3. Enter A6. The panel will now
call the download computer running
PCPreset. PCPreset will answer the
call, establish a connection, and then
download the account that matches the
Auto Download ID Number [93] with the
account of the same number in the list
that PCPreset is currently running.
Installer Programming
[94]Installer Code
The default Installer Code is 6321. Program a
new 4-digit Installer Code. When the panel is
defaulted, the Installer Code will be changed
back to the default Installer Code of 6321.
[95]Master IFOB / User 1 Code
The 1st User Code is a program code as well
as an Arm/Disarm code. The default User
Code is 1234. If User 1 Code Lockout is
programmed, the User 1 Code cannot be
programmed from User Program Mode.
[96]Installer Options 1
Note: All programming within Programming
addresses [96] & [97] will not change if the
panel is defaulted.
(1)
Reserved
(2)
User 1 Code Lockout - If
programmed, the User 1 Code cannot be reprogrammed from User Program Mode.
(3) UL Household Fire - Activates the
following UL required features:
There is a 4 hour re-sound of wireless Smoke
Low Battery and wireless Smoke Supervisory
system troubles.
• An active System Battery test performed
every 4 hours (instead of 24 hours) and
Wireless Smoke Supervisory Timer is set
to 4 hours.
• Fire Bell converts to Temporal pattern
(March Time).
• Wireless Smoke Supervisory Time is fixed
at 4 hours.
(4) SIA CP-01 Features. Enabled by default. When enabled, the following features
take effect:
1. The minimum allowed programmable exit
time is 45 seconds.
2. Exit urgency enunciation.
3. “Report and Enunciate Exit Error”/ (Exit
Error is door open at end of exit delay)
sends “CF” code for pulse formats and
374 Point ID.
4. “Report Recent Close”. If an alarm occurs
within 2 minutes at the end of exit delay,
Panel reports “FC” code for pulse formats
and 459 Point ID.
5. The minimum allowed Entry time is 30
seconds.
6. Enter Urgency Annunciation is changed
from steady sounder to steady with pulsing off. This ensures that the minisounder on alarm (steady sounder)
sounds different from enter urgency.
7. “Silence Entry Sounder on First Button
Press”. During Entry delay, pressing any
digit on the keypad stops the entry
sounder for 10 seconds.
6 times indicating that the report was
aborted.
Cancel Enunciation after Disarm
Enabled by default. If a Cancel Report Code
(406-00X) was sent upon disarming, the
keypad chirps 6 times indicating the system
is disarmed. The keypad then chirps 3 times
indicating a Cancel Report Code was transmitted.
Cross Zone Audible Alarm on First Trip
Enabled by default. First trip of a Cross
Zone will initiate the bell output.
Suppress Test Timer on any Report
Disabled by default. If enabled, any report
(opening, closing, alarm, etc.) will prevent the
next Test Timer report from being sent.
Test Timer Interval in hours
Disabled by default. If enabled, the test timer
interval changes from days to hours programmed in location [14].
Day Zone on Open by Zone Mask
When selected, a zone will produce a system trouble indication for trouble on a
zone. The event is logged and reported
on the Trouble Report [37-3] channel as
Day-Zone Point ID(370).
(Mercantile
Panel Specification).
Pulse Bell on Alarm by Zone Mask
When selected, a zone will produce a
pulsing bell at 1 second on, 1 second off
rate and timeout based on the fire timeout
selected. This feature is provided principally for the case zone 6 must be used for
key-switch input. (Mercantile Panel Specification).
[97]Installer Options 2
(1) Reserved
(2) Reserved
(3) Enable Wireless on Zone 7
(4) User 1 Code-Program only - If
enabled, User 1 Code will function only as the
User Program Code and will not Arm/Disarm
the panel.
Note: All programming within Programming
addresses [96] & [97] will not change if the
panel is defaulted.
[98] Number of Re-Dials
The number of re-dial attempts made by the
panel before indicating a Fail-to-Communicate
(System Trouble 1-3).
Download-Only Features
The following Features are only changeable
through downloading:
Abort Delay Time
Abort delay time defaults to 30 seconds for
zones programmed in [79].
Abort Enunciation After Disarm
Enabled by default. If the system disarmed
in the abort time window, the keypad chirps 6
times indicating disarm, then chirps another
13
System Troubles
The Freedom System is constantly monitoring its
own components, as well as all critical services,
such as AC power and the telephone line, to ensure that it is always ready to provide the protection
for which it was designed. When a system trouble
occurs, the F-TP Touchpad will caution you with a
Trouble (TBL) light and a beeping sounder.
Viewing System Troubles
To determine the nature of the system trouble,
press SILENCE, count the number of Trouble TBL
and READY flashes and refer to the System Trouble Display Table below. If there is more than one
trouble to view, press SILENCE again to scroll to the
next trouble, and press SILENCE again to exit the
VIEW TROUBLE mode. The TBL light will remain
lit as a reminder if the trouble is still present.
Audible System Trouble Indication
For all system troubles, except when the only
system trouble is the loss of AC, the F-TP Touchpad will beep once every 10 seconds. The F-TP
Touchpad will continue to beep until the reset
button is pressed or the trouble has been
acknowledged by pressing SILENCE.
Contact ID System Trouble Report Codes
The following system troubles, when enabled to report to central station [38-3]
will report the unique trouble code below::
Bell Cut
CODE 1 321 G00 ZN000-BELL 1 TROUBLE
2-Wire Fire Trouble
CODE 1 373 G00 ZN000-FIRE LOOP TRBLE
Rcvr &/or EZT Fail-to-Respond CODE 1 382 G00 ZN000-SENSOR TROUBLE
Receiver Tamper
CODE 1 145 G00 ZN000-EXP. MODL. TAMPER
Receiver JAM
CODE 1 333 G00 ZN000-FIRE LOOP TRBLE
Tx Low Battery
CODE 1 384 G00 ZN00n-RF TRAN LOW BATT
Tx Supervisory Failure
CODE 1 381 G00 ZN00n-SUPERVSN LOSS RF
A 300 (SYSTEM TROUBLE RST) code is sent if a restore is reported after
multiple troubles.
Pager System Trouble Reporting
The following system troubles, when enabled to report to pager [57-3], will
send the report code programmed in Trouble Report [63]:
Bell Cut
2-Wire Fire Trouble
Rcvr Fail-to-Respond
Receiver Tamper
Receiver JAM
F1
F1
F1
F1
F1
Tx Low Battery
Tx Supervisory Failure
Smoke Low Battery
Smoke Sup. Failure
F1
F1
F1
F1
Freedom Touchpad System Trouble Display Table
TBL Flashes / READY
Touchpad
Flashes Trouble Condition
beeps
14
Action
STEADY
NONE
Zones Bypassed
This is an indication that zones have been bypassed (by pressing BYPASS).
1
NONE
AC Power Failure
This trouble will occur if AC power is not present. Make sure the system transformer is plugged into its AC receptacle and check the circuit breaker. Typical
voltage reading at the AC terminal (Term 1 & 2) is 17V AC.
2
NONE
Low Battery
If there has been a recent power failure, the battery may be partially depleted and
must be recharged by the F-8 Panel. If the battery does not re-charge in 24 hours,
replace battery.
3
NONE
Communication
Failure
The system was not able to report to central station. If this is due to a temporary
interruption in the telephone service, the trouble can be cleared when the service
is restored by pressing BYPASS again.
4
NONE
Telephone Line Cut
The telephone line has failed. If telephone service has been temporarily interrupted, the trouble will clear when it is restored. Otherwise, call for service.
5
NONE
Bell/Siren Trouble
The Bell / Siren loop is open. Check the wire running from Terminal 14 of the F-8
Panel to Terminal 4 of the F-TP Touchpad.
6
NONE
Lost Key Mode
If the deadbolt key has been lost or stolen, the system may be placed in “Lost Key
Mode” by pressing and holding STAY and AWAY simultaneously for 4 seconds. In
this mode, the system will not disarm when the deadbolt is disengaged. Upon entry, the F-IFOB must be used to disarm the system or it will go into alarm. To exit
this mode, press and hold STAY and AWAY simultaneously for 4 seconds.
7
NONE
Fire Zone Trouble
The Fire loop is open. Ensure that the 2.2K Ohm supervisory resistor is across
Terminals 12 & 13.
1
1
Wireless Receiver Tbl
The GEM-RECV-XP8 wireless receiver is not responding to polls from the control
panel. Ensure that the receiver connections are correct. The red LED on the receiver should be pulsing to indicate proper communication with the control panel.
2
2
Wireless Receiver Jam The GEM-RECV-XP8 wireless receiver is sensing constant RF carrier, which may
interfere in its operation. Remove the cover of the receiver and check the green
Receive LED. It should only light (blink) while it is receiving a transmission from
one of the transmitters. If it is lit steadily, another source of RF is present.
Freedom Touchpad System Trouble Display Table (continued)
TBL Flashes /
READY
Flashes
Touchpad
Beeps
3
Trouble Condition
1-8
Wireless Transmitter
Low Battery
4
1-8
Wireless Transmitter
Supervisory Failure
5
1-4
Wireless Smoke
Detector Low Battery
6
1-4
Wireless Smoke
Detector Supervisory
Failure
Action
The battery in a wireless transmitter is low and should be replaced. This transmitter
is on the zone corresponding to the number STATUS flashes. The replacement
battery for the GEM-Trans2 door/window transmitter, GEM-PIR motion detector and
GEM-GB glass break detector is the Duracell DL123A 3 Volt Lithium (2 required for
the GEM-PIR and GEM-GB). The GEM-DT Dual Technology Sensor requires 4 C
cell alkaline batteries. Warning: Replace batteries only with the same type as
specified above. Use of another battery may present a risk of fire or explosion. Do
not recharge or disassemble battery, or dispose of in fire.
A wireless transmitter on the zone corresponding to the number STATUS flashes
has failed to “check in” with its hourly supervisory signal. This signal must be received by the receiver at least once in the time period programmed in address [16]
(Supervisory Timer, hours).
The battery in a wireless smoke detector is low and should be replaced. The number of the smoke detector corresponds to the number STATUS flashes. The replacement battery is the Duracell MN1604 9 Volt Alkaline (2 required). Warning:
Replace batteries only with the same type as specified above. Use of another battery may present a risk of fire or explosion. Do not recharge or disassemble battery, or dispose of in fire.
A wireless smoke detector on the zone corresponding to the number STATUS
flashes has failed to “check in” with its hourly supervisory signal. This signal must
be received by the receiver at least once in the time period programmed in address
[17] (Wireless Smoke Detector Supervisory Timer, hours).
Contact ID Report Codes and GEM-OUT8 Outputs
1
2
3
4
5
7
8
A
B
C
D
E
F
Point ID
Fire
Panic
Burglary
Holdup
General Alarm
Gas Alarm
Heat Alarm
Auxiliary
24 Hour Aux.
Reserved
Burg Perimeter
Burg Interior
Tamper
Code
110-000
123-00X
130-00X
122-00X
140-00X
162-00X
158-00X
100-00X
150-00X
131-00X
132-00X
137-00X
A*
Y
Y
GEM-OUT8 Output Activation
DO NOT PROGRAM
Output 3
Output 4
SIA CP-01 Quick Reference Chart
Address
Exit Time 60 Seconds
[11] (enter 30)
Entry Time 30 Seconds
[23-4]
Output 6
Y
Y
Y
*COLUMN A = INDICATES IF PGM (OR GEM-OUT8 OUTPUT 1) ACTIVATES IF [23-1] AUDIO
VERIFICATION IS ENABLED
Disable Call Waiting
[67-1]
Send Cancel Report
Touchpad Codes
F-TP Touchpad Fire
F-TP Touchpad Panic
F-TP Touchpad Aux Alarm
F-TP Touchpad Aux Service
F-TP Touchpad Ambush
110-092
123-093
150-094
616-000
121-000
System Codes
Receiver Tamper
AC Fail
Low Battery
Bell Cut
Receiver Jam
Zone Trouble (Door Kick In)
Fire Zone Trouble
Transmitter Supervisory Fail
Wireless Smoke Sup. Fail
Receiver Fail
Transmitter Tamper
Transmitter Low Battery
Wireless Smoke Low Battery
Interior Zone Trouble (Stuck PIR Bypassed) NOTE2
Conditional Open/Close
Open/Close
Cancel Report
Status Report (Bypassed Zones)
Test Timer
Communication Test
145-000
301-000
302-000
321-000
333-000
370-00X
373-000
381-00X
381-00X
382-000
383-00X
384-00X
384-00X
389-00X
400-00X
401-00X
406-00X
570-00X
602-000
602-000
Fire Alarm Verification
[70-1]
Exit Restart Enabled
[70-2]
Convert Away To Stay If No Exit
[79-1,2,3,4,5,6,7,8]
Abort Delay By Zone Mask
[80-1,2,3,4,5,6,7,8]
Swinger Shutdown
[89-1,2,3,4,5,7,8]
[96-4]
Contact ID Report Codes (Grouped by Type)
Chirp Bell On Remote (Keyfob) Arm Enabled
[46-1] not on
[69-4] not on
Y
Description
[10] (enter 60)
Cross Zoning
CP-01 Features
(Download Only)
Abort Delay Time Default To 30 Seconds
(Download Only)
Abort Enunciation After Disarm
(Download Only)
Cancel Enunciation After Disarm
(Download Only)
Cross Zone Audible Alarm On First Trip
1. There is a Communication Delay of 30 seconds in this control panel. It can be removed, or it can be
increased up to 45 seconds at the option of the end user by consulting with the installer.
2. The F-8 control panel and at least one GEM-RP8LCD must be installed.
3. The following optional accessories support the SIA False Alarm Reduction (FAR) classification, and
may be used if desired: GEM-RECV-XP8, GEM-KEYF.
4. Programming at Installation may be subordinate to other UL requirements for the intended application.
5. Un-vacated premises: When the system/partition is armed with AWAY button, the system will arm
STAY if no exit. There must be a minimum of one Stay/Away or Delay Stay/Away zone enrolled on the
partition.
6. Cross zoning is not recommended for Line security Installations nor is it to be implemented on exit /
entry zones.
7. There is a Communication Delay of 30 seconds in this control panel. It can be removed, or it can be
increased up to 45 seconds at the option of the end user by consulting with the installer.
8. Do not duplicate any reporting codes. This applies for all communication formats (other than SIA)
sending automatic programmed reporting codes.
9. In UL installations, Entry Delay time plus Abort Delay time (total combined times) cannot exceed 60
seconds.
10. Exit Time Restart must be disabled for UL Line Security/Encryption applications.
NOTE 2: Any interior zone which is faulted at the point of arming and remains faulted (with
no restore) for 4 hours will be considered a “stuck” PIR. A trouble report will be sent to
central station indicating Interior Zone Trouble (Contact ID code 389-00X). See page 10,
address [27-3].
15
16
E2
F-8 PANEL WIRING DIAGRAM
+ RED
RECHARGEABLE
BATTERY
12 VDC 4AH OR 7AH
RESIDENTIAL BURG (4 HOUR STANDBY)
COMBINED STANDBY CURRENT = 500 MA
ALARM CURRENT = 2.0 A
BLACK
RESIDENTIAL FIRE (24 HOUR STANDBY) (3)
COMBINED STANDBY CURRENT = 120 MA
ALARM CURRENT = 95 MA BELL CURRENT, 275MA ADDITIONAL
AUX POWER OUTPUT AND ONE F-TP TOUCHPAD SIREN (10)
RECOMMENDED BATTERIES YUASA
NP4-12 AND NP7-12
REPLACE EVERY FIVE YEARS
1
EARTH
GROUND
This equipment should be installed in accordance with Chapter 2 of the National Fire Alarm Code, ANSI/
NFPA 72-1996 (National Fire Protection Association Batterymarch Park, Quincy MA 02269). and local
codes. Information describing proper installation, operation, testing, maintenance, evacuation planning,
and repair service is to be provided with this equipment. UL Listed Energy Cable is required.
(REFER TO INSTALLATION INSTRUCTIONS WI1431)
R
2
16 VAC 20 VA
TRANSFORMER
TRF12
(OR EQUIVALENT
SEE WI1076).
3
4
5
6
7
8
+
-
+
+
-
+
DS1
TEL LINE IN USE
12
+
FIRE
PWR
13 14
-
FIRE
+
BELL
To RJ31X
(Supervised)
TELCO
JACK
15
-
GND
WARNING: TO PREVENT RISK OF
EL EC TR IC
SH O C K
D ISC O NN ECT
TELEPHONE LINES PRIOR TO SERVICING
16
+
17
+PWR
-
GND
FT2200
RED
LOAD
50 mA MAX.
2.2K EOLR
FIRE
ZONE
12.6 - 9.0 VDC
GREEN
2.2K
RED
ZONE 5 ZONE 6
ALL OUTPUTS ARE CURRENT LIMITED
4-Wire
Fire
Wiring
2.2K EOLR IS
REQUIRED ONLY
IF NOT USING
ANY TOUCHPAD
SIRENS. SEE
NOTE 11.
+
BLACK
2.2K
Default:
Perimeter
Default:
Perimeter
Default:
Perimeter
(9)
(10)
(11)
2.2K
Default:
Interior
ZONE 3 ZONE 4
WARNING
This unit includes an alarm verification feature
that will result in a delay of the system alarm
signal from the indicated circuits. The total delay (control unit plus smoke detectors) shall not
exceed 60 seconds. No other smoke detector
shall be connected to these circuits unless approved by the local authority having jurisdiction.
Circuit Control Unit
Smoke Detectors
Zones Delay-Sec.
_______ ________
Model Delay-Sec.
The delay (power-up) (start-up) time marked on the
installation wiring diagram of the smoke detector or
on the installed smoke detector(s) is to be used.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
2.2K
12.5 - 10.7 VDC
AUX PWR OUTPUT 10-12.5 VDC
+
2.2K
-
PGM
+PWR
ADDR
PIR≠
AUX2
RED
BLK
GRN
YEL
F-TAB #1
JP1
5
1
Touch 6
2 Pad # 1
7
3
8
4
9
(+)
(COM)
ZONE 1
(+)
MAGNETIC DOOR
CONTACT
(+)
(COM)
ZONE 2
PIR / GLASSBREAK SENSOR,
ETC...
F-TP or F-TPG
ADDR
PIR≠
AUX2
F-8 Terminals
Power
Out (+)
Power
In (+)
12 Fire Power
Power
In (-)
10 Ground
BROWN
Power
Out (-)
GRN
Fire Loop
Fire
Out
Loop In
12 Fire Power
YEL
BROW
BLACK
16
+
Class 2 Transformer
COLD WATER GROUND
CONNECTION. USE ONLY
COLD-WATER PIPE OR
BURIED GROUND ROD. USE
AT LEAST #16 AWG WIRE.
DATA
REMOTE BUS
+
DO NOT connect
to switched outlet.
18 19
(+)
E1
13 Fire
ALL ZONE RESISTORS MUST BE INSTALLED, EVEN IF ZONE IS NOT USED.
COMBINED STANDBY = KEYPAD CURRENT + AUX POWER CURRENT + FIRE POWER CURRENT + PGM CURRENT + F-TP TOUCHPAD CURRENT.
24 HOUR STANDBY REQUIRES A 7AH BATTERY.
UNIT INTENDED TO BE MOUNTED VERTICALLY ON WALL.
REFER TO WI1431 AND WI1471 FOR COMPATIBLE TWO WIRE SMOKE DETECTORS. DO NOT MIX DIFFERENT MODELS.
THIS PANEL SHALL BE CHECKED BY A QUALIFIED TECHNICIAN AT LEAST ONCE EVERY THREE YEARS.
THIS PANEL SUPPORTS ONLY ONE SMOKE DETECTOR IN ALARM EXCEPT WHEN SS2100AT IS USED WITH RR-2. REFER TO WI1471.
SYSTEM MUST BE TESTED AT LEAST ONCE A WEEK IN THE AC/BATTERY MODE AND IN THE BATTERY-ONLY MODE. (CONTACT CENTRAL
STATION PRIOR TO TESTING) AC MUST BE RESTORED AFTER TEST.
F-TP TOUCHPAD STANDBY CURRENT FOR BURGLARY = 160MA. FOR RESIDENTIAL FIRE = 55MA.
TO DISABLE TOUCHPAD SIREN, DO NOT WIRE TERMINAL 4.
ONLY INSTALL 2.2K BELL SUPERVISION END-OF-LINE RESISTOR IF TOUCHPAD SIREN HAS BEEN DISABLED. INSTALL AT BELL OR OTHER
SOUNDING DEVICE.
RED
BLK
F-TAB #2
JP1
5
1
Touch 6
2 Pad # 2
7
3
8
4
9
(+)
(COM)
ZONE 7
(+)
DOOR
CONTACT
(+)
(COM)
ZONE 8
PIR / GLASSBREAK SENSOR,
ETC...
F-TP or F-TPBR
F-PROG*
*The F-PROG is required for programming purposes only
GEM-RECV-XP8
7167-0085: 201
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement