CARLO GAVAZZI | LDI 35 - CONFIGURATION SOFTWARE | datasheet: pdf

datasheet: pdf
What is and Why use the
Digital Panel Meter
In the manufacturing industry and in the process control
applications, it is of vital importance the monitoring and
the control by means of alarms of several physical
variables. In addition analogue or serial retransmission of
the measured value can be required in order to provide a
feedback to the system which controls the process, or to
log the history of the monitored plant. Whatever are
your needs and requirements in the process you have
to control, Carlo Gavazzi has the right solution.
2
Should you need a simple indicator, a controller for every
kind of variable, or a more complex instrument - able for example to manage four alarms, to be connected in a RS485
network, to linearise the non-linear input signals and to
show different conditions with different display colours - we
have the panel meter that better suits your demands. The
range is completed with a universal signal conditioner,
whose flexible and advantageous modular architecture is
common to the other medium and high-end panel meters.
The charactersitics
Wide range of available inputs for all
the applications: voltage, current,
frequency, resistance, temperature.
Modular architecture available in the
medium and high-end meters, making
them flexible and easy to configure.
Different type of outputs available to
retransmit the measured variable:
analogue signal, alarm contacts or serial port
Easy programmability by means of a handy
keypad. The more complex instruments are
configurable by means of dedicated software tool.
3, 3 1/2 or 4-digit LED display with alarm
and over range indication.
3
USC: 5-slot module holder
A new concept of Modularity
• Maximum in-field flexibility
• Quick assembly and configuration
• Easy future expansion
Measurement inputs
0.2-2-20mA AC/DC
0.2-2-20mA AC/DC + excitation output
0.2, 2, 5A AC/DC; 20, 200, 500V AC/DC
TC: J-K-S-T-E, Pt100-250-500-1000, Ni100
Ω: 0.02, 0.2, 2, 20kΩ
4
UDM35: 3 1/2-digit read-out,
or 3-digit + dummy 0 read-out
Display Base
UDM40: 4-digit
read-out, 3-colour display
Power Supply
90 to 260V AC/DC
18 to 60V AC/DC
Communication Port
Outputs
RS485 and RS232 ports
Analogue outputs:
Max 1 analogue output
0 to 20mA and 0 to 10VDC
Alarm outputs:
1 relay output
2 relay outputs
2 relay + 2 open collector outputs
4 relay outputs.
5
Features and Benefits of the Digital Panel Meters
DI3 DIN, DI3 72, LDI3
• Indicators for DIN-rail and panel mounting
• Multi input capabilities
• Easy product configuration
€
UDM40
MDM40
•
•
•
•
Two-alarm tachometer
Dual input and multifunction capability
Management of all available sensors
Reverse speed control
UDM35
MDM40
LDI35/LDM35
LDI35, LDM35H
• Multi range and multi signal indicator and controller
• Powerful scaling capability
• Universal power supply (LDM35H only)
DI3 LDI3
Features/Functions
UDM35
•
•
•
•
Powerful performance
Plug and play modules
Maximum in-field flexibility
Possibility to expand the inputs/outputs
only when really needed by the application
UDM40
•
•
•
•
State of art performances
Maximum in-field flexibility
Input signal linearization capability
3-colour display
USC
•
•
•
•
Universal signal conditioner
Maximum in-field flexibility
Input signal linearization capability
Programming and network software
DI3 DIN, DI3 72, LDI3
The instruments are easily configurable by dip-switches.
That allow to set the position of the decimal point and
the primary of the current transformer or to connect the
potential transformer.
6
USC
UDM40 Color Display
RED - High priority,
abnormal condition
AMBER - Low priority,
abnormal condition
GREEN - Normal
condition
LDI35, LDM and UDM
In the process control
applications, it is a
mandatory condition to
be able to manage signals such as “mA and
volts” which are proportional to pressure or other
variables being measured.
The LDI35/LDM/UDM series answers to this request
with powerful scaling and filter
in order to show the variable in a stable and reliable way on the display.
The available modules
Type
Channels
UDM35
UDM40
USC
OrderingCode
UDM35 base
BD35
UDM40 base
BD40
USC base
BDXX
AC/DC inputs: 200µA, 2mA, 20mA, 200mV, 2V, 20V
1
BQLSX
AC/DC inputs: 200µA, 2mA, 20mA, 200mV, 2V, 20V + excitation output
1
BQLSE
AC/DC inputs: 200mA, 2A, 5A, 20V, 200V, 500V
1
BQHSX
Inputs: 20Ω, 200Ω, 2kΩ,20kΩ; TC: J-K-S-T-E, Pt100-250-500-1000, Ni100
1
BQTRX
Analogue output: 0 to 20mA, 0 to 10V DC
1
BOAV
Relay output
1
BOR1
Relay output
2
BOR2
Outputs: 2 relays + 2 open collectors
4
BOR4
Relay output
4
BOR5
RS485 communication port
1
BRSX
RS232 communication port
1
BRSY
18 to 60V AC/DC power supply
BPL
90 to 260V AC/DC power supply
BPH
UDM35 / UDM40
USC
Slot
A
B
C
D
A
B
C
D
E
Inputs/Outputs
1
2
3
4
1
2
3
4
5
Measurement inputs: LSX, LSE, HSX, TRX
RS485 communication port: SX
RS232 communication port: SY
Analogue output (*): AV
Relay and open collector outputs: R1, R2, R4, R5
Power supply: H, L
(*) Note: Max one analogue output module
7
DI3 DIN
Page 10
DIN rail mounting
Panel mounting
Modular
Indicator
Controller
3-colour display
Signal conditioner
Linearization capability
Multi input (A-V)
Temperature measurement
Tachometer
Command inputs
Up to 1 alarm
Up to 2 alarms
Up to 4 alarms
Analogue output
Serial communication
Universal power supply
8
DI3 72
Page 10
LDI3
Page 10
LDI35
Page 11
LDM35H
Page 12
MDM40
Page 13
UDM35
Page 14
UDM40
Page 15
USC
Page 16
9
DI3 DIN
DI3 72
LDI3
With just four basic models this product family is the ideal
solution for the panel builders.
The product philosophy meets the panel builder and distributor requests in terms of features and flexibility granting
therefore a consistent stock reduction.
Description
Housing (H x W x D)
Mounting
Display type
Variables on display
Measured signals
Type signals
Engineering units
Accuracy
Temperature drift
Sampling rate
Command inputs
Outputs:
Alarm
Analogue
Serial
Signal/display scaling
Power supply
Approvals
Protection degree
10
DI3 72
LDI3
3-DGT µP-based indicator
89 x 53.5 x 58.8 mm (DIN)
72 x 72 x 75 mm (72)
48 x 96 x 83 mm (LDI3)
DIN rail, panel mounting (72, LDI3)
3 DGT, red LED
YES
1A/60mV/100-500VDC
1A/100VAC, 5A/500VAC
1 to 1000Hz
DC or AC
mA, A, V, Hz
±(0.5%FS, + 1DGT)
±350ppm/°C
1 time/s
NO
NO
NO
NO
YES (CT and PT sel. by dip-switch)
24V, 48V, 115V, 230V AC
CE, DI3 72:c CSA us;
LDI3: c CSA us, UR
IP40 (DIN); IP50 (72), IP50
(LDI3), IP65 (LDI3 on request)
The best to suit your needs!
Performances
DI3 DIN
72, LDI3
DIN
Hardware
Functions
In-Out
LDI35
The family is available in two basic versions:
• LDI35, simply as indicator;
• LDI35, up to 1 alarm relay output.
On each basic model it is possible to have a specific version for:
• process applications with 2-20mA and 0.2-20V-200V
input;
• panel builders with 2-5A and 200-500VAC/DC input.
The range is completed by a multi probe temperature
controller and ohmmeter.
LDI35
Housing (H x W x D)
Mounting
Display type
Variables on display
Measured signals
Type signals
Engineering units
Accuracy
Temperature drift
Sampling rate
Command inputs
Outputs:
Alarm
Analogue
Serial
Other available characteristics
Power supply
Approvals
Protection degree
3 1/2-DGT µP-based indicator
and controller
48 x 96 x 83 mm
Panel mounting
3 1/2-DGT or 3DGT+ dummy 0, red LED
YES
(2-20mA, 20-200V); (2-5A, 200500V); (TC: J-K-S-T-L, Pt100-1000,
Ni100, 200-2000 Ω)
DC and AC
Label set
DC: ±(0.3%FS + 1DGT)
AC: ±(0.5%FS + 1DGT)
±200ppm/°C
4 times/s
NO
Up to 1
NO
NO
Signal/display scaling. Digital
filter, Peak and valley. Burn-out
control on temperature input
24, 48, 115, 230VAC, 9 to 32VDC,
40 to 150VDC
CE, c CSA us, UR
IP65 (on request)
The best to suit your needs!
Performances
Description
Hardware
Functions
In-Out
11
LDM35H
The family is available in two basic versions:
• LDM35H, simply indicator;
• LDM35H, up to 2 alarm relay outputs.
Both of them provided with universal power supply.
On each basic model it is possible to have a specific version for:
• process applications with 0.2-2-20mA and
0.2-2-20V DC/AC input;
Description
Housing (H x W x D)
Mounting
Display type
Variables on display
Measured signals
Type signals
Engineering units
Accuracy
Temperature drift
Sampling rate
Command inputs
Outputs:
Alarm
Analogue
Serial
Other available characteristics
Power supply
Approvals
Protection degree
12
3 1/2-DGT µP-based indicator
and controller
48 x 96 x 83 mm
Panel mounting
3 1/2-DGT or 3-DGT + dummy 0,
red LED
YES
(0.2-2-20mA, 0.2-2-20V); (0.2-2-5A,
20-200-500V)
DC and AC TRMS
Self sticking label set
DC: ±(0.3%RDG + 3DGT)
AC: ±(0.5%RDG + 3DGT)
±150ppm/°C
5 times/s
NO
Up to 2
NO
NO
Signal/display scaling. Digital
filter, Peak and valley.
90 to 260V AC/DC,
18 to 60V AC/DC
CE, c CSA us and UR pending
IP65
• panel builders with 0.2-2-5A and 20-200-500V AC/DC
input.
Furthermore TRMS method improves significantly the
accuracy of the measurement on both distorted current
and voltage.
The best to suit your needs!
Performances
LDM35H
Hardware
Functions
In-Out
MDM40
MDM40 tachometer is an extract of flexibility and performances in only one product.
This instrument is suitable to be used in all applications
thanks to:
• the capability to measure a very slow speed/
frequency (0.001 Hz);
• the management of pulse signals from proximity switches,
MDM40
4-DGT multi-range controller for
pulse signal
Housing (H x W x D)
48 x 96 x 124 mm
Mounting
Panel mounting
Display type
4 DGT, red LED
Variables on display
YES
Measured signals
Speed, frequency, rate, period
Type signals
DC or AC
Engineering units
Label set
Accuracy
±(0.001% RDG + 3DGT)
Temperature drift
±100ppm/°C
Sampling rate
Programmable
Command inputs
1 (display hold, key pad lock)
Outputs:
Alarm
2
Analogue
1 (20 mA, 10 VDC)
Serial
RS485
Other available characteristics Signal/disp. and analogue out. scaling.
Digital filter.
Peak and valley.
24,48,115,120,230,240 VAC
Power supply
9 to 32, 40 to 150 VDC
Approvals
CE, UR
Protection degree
IP65
The two independent inputs, with proper parameter programming are able to measure rate, speed, frequency and
period variables using mathematical formulas like: A, B,
1/A, A/B, A-B, (A-B)/B, B/(A+B) and revers speed control.
The best to suit your needs!
Performances
Description
photo switches, NAMUR proximities, encoders and
magnetic pick-up’s;
• the rate-tacho-frequency-period meter functions.
Hardware
Functions
In-Out
13
UDM35
UDM 35 is a universal high-tech instrument that has been
developed to meet the most advanced application needs.
UDM35 offers to the user many solutions and advantages
that can be summarized in:
• quick assembly and maintenance using
plug and play modules;
• easy and quick parameter programming and
parameter cloning on other UDM’s by means of
UdmSoft or PC Hyperterminal;
Description
3 1/2-DGT µP-based controller
with modular housing
Housing (H x W x D)
48 x 96 x 105 mm
Mounting
Panel mounting
Display type
3 1/2-DGT or 3-DGT + dummmy 0,
red LED
Variables on display
YES
(0.2-2-20mA, 0.2-2-20V); (0.2-2-5A,
Measured signals
20-200-500V); (TC: J-K-S-T-E, RTD, Ω)
Type signals
DC and AC TRMS
Engineering units
Self sticking label set
DC: ±(0.1%RDG + 3DGT)
Accuracy
AC: ±(0.3%RDG + 3DGT)
Temperature drift
±150ppm/°C
Sampling rate
5 times/s
Command inputs
1 (display hold, key pad lock or
latch alarm reset)
Up to 4
Outputs:
Alarm
1 (20mA,10VDC)
Analogue
Serial
RS485, RS232
Other available characteristics Signal/display scaling. Analogue
output scaling. Digital filter, Peak
and Valley. Burn-out control on
temperature inputs only.
90 to 260 AC/DC,
Power supply
18 to 60V AC/DC
Approvals
CE; c CSA us and UR pending
Protection degree
IP65
14
• powerful variable control by means of up to 4 alarms;
• remote control facilities like analogue output and
RS485, RS232 communication ports.
The different type of alarm controls:
• up-down functions with automatic reset;
• up-down functions with manual reset;
• down with disable function at power-on.
These alarms can be
combined so to have
up to 4 abnormal steps
notified as pre-alarms
and alarms.
The best to suit your needs!
Performances
UDM35
Hardware
Functions
In-Out
UDM40
UDM40 has the same basic characteristics of UDM35.
Other benefits can be summarized as follows:
• display colour adaptable to other existing instruments
by means of a 3-colour choice;
• management of non linear signals coming from special
process transmitters using a 16-point linearization capability;
• reliable information to the process, working out a
complex or disturbed signal by a programmable
input integration time and/or a smart digital filter.
Controller UDM40
Housing (H x W x D)
Mounting
Display type
Variables on display
Measured signals
Type signals
Engineering units
Accuracy
Temperature drift
Sampling rate
Command inputs
Outputs:
Alarm
Analogue
Serial
Other available characteristics
Power supply
Approvals
Protection degree
4-DGT µP-based controller with
modular housing
48 x 96 x 105 mm
Panel mounting
4-DGT, coulor LED
YES
(0.2-2-20mA, 0.2-2-20V); (0.2-2-5A,
20-200-500V); (TC: J-K-S-T-E, RTD, Ω)
DC and AC TRMS
Self sticking label set
DC: ±(0.1%RDG + 3DGT)
AC: ±(0.3%RDG + 3DGT)
±150ppm/°C
5 times/s
1 (display hold, key pad lock or
latch alarm reset)
Up to 4
1 (20mA, 10VDC)
RS485, RS232
Signal/display scaling. Analogue
output scaling. Digital filter. Integration time. Peak and valley. Burnout control on temp. inputs only.
Linearization. Traffic lights function.
90 to 260 AC/DC,
18 to 60V AC/DC
CE; c CSA us and UR pending
IP65
Alarm status given at a glance using the easy traffic lights
principle. The instrument may show the alarm status based on
a sequence of colours that can be programmed by the user.
The best to suit your needs!
Performances
Description
Hardware
Functions
In-Out
15
USC
The winning point of the USC “Universal Signal
Conditioner” is its architecture. It is formed by a module
holder on which it is possible to plug in modules with different purposes: power supply-measurement-alarm control-signal retransmission. The different combination of the
modules allows to have a simple signal conditioner or a very
sophisticated controller with communication port.
The main advantages given by USC can be summarized
as follows:
The LEDs on modules show
the power supply and communication status all the
time.
Signals conditioner USC
Housing (H x W x D)
Mounting
Display type
Variables on display
Measured signals
Type signals
Engineering units
Accuracy
Temperature drift
Sampling rate
Command inputs
Outputs:
Alarm
Analogue
Serial
Other available characteristics
Power supply
Approvals
Protection degree
µP-based signal conditioner with
modular housing
44 x 113 x 107 mm
DIN-rail mounting
NO
NO
(0.2-2-20mA, 0.2-2-20V); (0.2-2-5A,
20-200-500V); (TC: J-K-S-T-E, RTD, Ω)
DC and AC TRMS
NO
DC: ±(0.1%RDG + 3DGT)
AC: ±(0.3%RDG + 3DGT)
±150ppm/°C
5 times/s
1 (latch alarm reset)
Up to 4
1 (20mA, 10VDC)
RS485, RS232
Signal/display scaling. Analogue
output scaling. Digital filter.
Integration time. Peak and valley.
Burn-out control on temp. inputs
only. Linearization up to 16 points.
90 to 260 AC/DC,
18 to 60V AC/DC
CE; c CSA us and UR pending
IP20
• easy and quick parameter programming and parameter
cloning on other USC’s by means of UscSoft or PC
Hyperterminal;
• powerful variable control by means of up to 4 alarms;
• remote control facilities like analogue output and
RS485, RS232 communication ports;
• management of non linear signals coming from special
process transmitters using a 16-point linearization capability;
• reliable information to the process, working out a
complex or disturbed signal by a programmable input
integration time and/or smart digital filter.
The best to suit your needs!
Performances
Description
Hardware
16
Functions
In-Out
Accessories
Types
SIU-PC85
SIU-DIN 8585
SIU-DIN.RLY
PSU-DIN (DC/AC)
PSU-DIN (AC/DC)
Serial communication
line adapter
Front: 65x80mm
RS232
2-wire comm.
N.A.
N.A.
9-pole, female
RS422
RS485
Serial communication
line amplifier, driver
Front: 89x71.5mm
RS485, RS422
2 or 4-wire comm.
YES
YES
Screw terminal block
RS422
Serial communication
relay outputs
Front: 89x71.5mm
RS485, RS422
2 or 4-wire comm.
N.A.
YES
Screw terminal block
4 relays
5A, 250V
Working mode
Line Bias
Line termination
Connections
Baud rate
Protection
Indication
(by means of LEDs)
4-wire comm.
YES
YES
Screw terminal block
Max 19200 Baud
All inputs/outputs
Power-on
Data-stream
4-wire comm.
YES
YES
Screw terminal block
Max 19200 Baud
All inputs/outputs
Power-on
Power supply unit
AC to DC
Front: 89x71.5mm
N.A.
N.A.
N.A.
N.A.
Screw terminal block
5VDC (max. 200mA)
12VDC (max. 100mA)
24VDC (max. 50mA)
By transformer
N.A.
N.A.
Screw terminal block
N.A.
Output: electronic
Power-on
Insulation
Input/output: 2kV
input/output and
power supply: 4kV
0 to +50°C (R.H.
≤90% non condensing)
-10 to +60°C (R.H.
≤90% non condensing)
1.8m cable with 9 to
9-pole connectors,
power supply cable
Input/output: N.A.
input/output and
power supply: 4kV
0 to +50°C (R.H.
≤90% non condensing)
-10 to +60°C (R.H.
≤90% non condensing)
N.A.
SPDT contacts
N.A.
N.A.
Screw terminal block
Max 9600 Baud
N.A.
Power-on
Comm. status
Output status
Input/output: 2kV
input/output and
power supply: 4kV
0 to +50°C (R.H.
≤90% non condensing)
-10 to +60°C (R.H.
≤90% non condensing)
N.A.
Power supply unit
DC to AC
Front: 89x71.5mm
N.A.
N.A.
N.A.
N.A.
Screw terminal block
24VDC (max. 250mA)
48VDC (max. 125mA)
115VDC (max. 50mA)
Switching mode
N.A.
N.A.
Screw terminal block
N.A.
Output: by fuse
Power-on
N.A.
Input/output: 4kV
0 to +50°C (R.H.
≤90% non condensing)
-10 to +60°C (R.H.
≤90% non condensing)
N.A.
0 to +50°C (R.H.
≤90% non condensing)
-10 to +60°C (R.H.
≤90% non condensing)
N.A.
Other characteristics
Wrong-line connection and full overvoltage protection.
Reverse conversion
capability.
Dual purpose: distance increase by
1200m per unit; network increase
4 relay outputs to be
driven by an RS485
communication port
Stabilised AC voltage
output.
Stability: ≤4%
Un @ max. current
Power supply input
24VAC, 48VAC
115VAC, 230VAC
24VAC, 48VAC
115VAC, 230VAC
24VAC, 48VAC
115VAC, 230VAC
Protection degree
IP20
IP40
IP40
80 to 240VDC
18 to 60VDC
9 to 16VDC
IP40
Stabilised DC voltage
output.
Stability: ≤0.5%
Un @ max. current
Non-stabilised DC
voltage outputs: 2V20V-30VDC
24VAC, 48VAC
115VAC, 230VAC
Description
Housing
Signal input
Working mode
Line Bias
Line termination
Connections
Output
Operating temperature
Storage temperature
Included set
IP40
17
Current Transformer
Types
Class
Bus–bar size
Dimensions (H x W x D)
Standards
Accuracy class
depending on the
burden output
Primary current at
rated output
current of 1A/5A
Types
Class
Bus–bar size
Dimensions (H x W x D)
Standards
Accuracy class
depending on the
burden output
Primary current at
rated output
current of 1A/5A
TADK
TADK2
TAD 2
TAD 3
TAD 4
0.5
Wounded primary
115.5x75x44 mm
IEC 60185/EN 60185
Class 0.5
Burden
VA
1 A 10
5 A 10
10 A 10
15 A 10
25 A 10
40 A 10
0.5
25x5 mm fixed bar
115.5x75x44 mm
IEC 60185/EN 60185
Class 0.5
Burden
VA
1 A 10
5 A 10
10 A 10
15 A 10
25 A 10
40 A 10
50 A 10
60 A 10
80 A 10
100 A 10
150 A 10
200 A 10
250 A 10
0.5/ 1/ 3
Ø 22 mm
98.5x58x44 mm
IEC 60185/EN 60185
Class 0.5 1
3
Burden
VA
VA VA
40 A
3
50 A
3
60 A
3
80 A
3
100 A
3
4
150 A 3
4
6
200 A 3
4
6
250 A 5
8
10
300 A 5
8
10
0.5/ 1
21x14 or 31x11 mm
98.5x58x44 mm
IEC 60185/EN 60185
Class 0.5 1
Burden
VA
VA
100 A
3
150 A 3
4
200 A 3
4
250 A 5
8
300 A 5
8
400 A 6
10
500 A 6
10
600 A 6
10
0.5/1
32x16, 41x11, Ø 32 mm
75x115.5x44 mm
IEC 60185/EN 60185
Class 0.5 1
Burden
VA
VA
100 A
3
150 A
3
200 A 4
250 A 6
300 A 6
400 A 10
500 A 10
600 A 10
800 A 10
TAD 6
TAD 8
TAD 12
TACO 110
TACO 200
0.5/1
55x22, 65x20, Ø 52 mm
105x145x44 mm
IEC 60185/EN 60185
Class 0.5 1
Burden
VA
VA
400 A 6
12
500 A 6
12
600 A 10
20
800 A 10
20
1000A 20
40
1200A 20
40
1500A 30
60
2000A 30
60
0.5/1/5P10
82x32 or 65x34 mm
140x120x55 mm
IEC 60185/EN 60185
Class 0.5 1 5P10
Burden
VA
VA VA
400 A 4
8
5
500 A 6
12
5
600 A 10
20
5
800 A 15
30
5
1000A 20
40
5
1200A 30
50
5
1500A 40
60
5
2000A 50
80
5
2500A 60
100 5
0.5/1/5P10
127x51 or 102x53 mm
183x170x65 mm
IEC 60185/EN 60185
Class 0.5 1 5P10
Burden
VA VA VA
800 A 15 30 10
1000A 20 40 10
1200A 30 60 10
1500A 40 80 10
2000A 50 100 10
2500A 60 120 10
3000A 80 160 10
4000A 100 200 10
0.5/1/5P10
Max. Ø 110 mm
183x170x 65 mm
IEC 60185/EN 60185
Class 0.5 1 5P10
Burden
VA VA VA
800 A 15 30 10
1000A 20 40 10
1500A 40 80 10
2000A 50 100 10
2500A 60 120 10
3000A 80 160 10
4000A 100 200 10
0.5/1/5P10
Max. Ø 200 mm
295x280x45 mm
IEC 60185/EN 60185
Class 0.5 1 5P10
Burden
VA VA VA
1000A 15 30 10
1500A 15 30 10
2000A 15 30 10
2500A 40 80 10
3000A 40 80 10
4000A 50 100 10
5000A 50 100 10
6000A 50 100 10
Cable/Bus–bar type current transformers. Standard output 5A (1A on request). Rated primary currents from 40A to 6000A. DIN–rail or panel mounting.
Current transformer 1-phase AC; operating frequency: 40 to 60 Hz; max system voltage: 0.72 kV; rated insulation level: 3kV/1min @ 50Hz; security factor: ≤5;
rated secondary current: 5A standard (1A on request).
A full range of split-core current transformers is available from 100A to 6000A
18
Accuracy of the main variables
Front housing protection degree
Display digits and (sampling rate)
3-colour display
Excitation output
“Traffic light” function. Alarm level
connected to the display colour
Pulse measuring input
Peak and valley function
Digital filter with action on the display
and signal outputs
Integration time
Linearization
Instantaneous variables displaying
Analogue output for variable retransmission
Alarm outputs for variable control
Digital inputs for external command
Communication port
OUR SALES NETWORK
Carlo Gavazzi GmbH - AUSTRIA
Ketzergasse 374, A-1230 Wien
Tel: +43 1 888 4112
Fax: +43 1 889 10 53
office@carlogavazzi.at
Carlo Gavazzi OY AB - FINLAND
Petaksentie 2-4, FI-00630 Helsinki
Tel: +358 9 756 2000
Fax: +358 9 756 20010
myynti@carlogavazzi.fi
Carlo Gavazzi SpA - ITALY
Via Milano 13, I-20020 Lainate
Tel: +39 02 931 761
Fax: +39 02 931 763 01
info@gavazziacbu.it
Carlo Gavazzi NV/SA - BELGIUM
Schaarbeeklei 213/3, B-1800 Vilvoorde
Tel: +32 2 257 4120
Fax: +32 2 257 41 25
sales@carlogavazzi.be
Carlo Gavazzi Sarl - FRANCE
Zac de Paris Nord II, 69, rue de la Belle
Etoile, F-95956 Roissy CDG Cedex
Tel: +33 1 48 38 98 60
Fax: +33 1 48 63 27 43
french.team@carlogavazzi.fr
Gavazzi Automation Sdn Bhd
No. 1, Jalan Pendidik U1/31, Sek. U1,
Hicom Glenmarie Industrial Park
40150 Shah Alam, Selangor, - MALAYSIA
Tel: +60 3 5569 4212
Fax: +60 3 5568 0004
sales@gavazzi-asia.com
Carlo Gavazzi Inc. - CANADA
2660 Meadowvale Boulevard,
CDN-Mississauga Ontario L5N 6M6,
Tel: +1 905 542 0979
Fax: +1 905 542 22 48
Carlo Gavazzi LTEE - CANADA
3777 Boulevard du Tricentenaire
Montreal, Quebec H1B 5W3
Tel: +1 514 644 2544
Fax: +1 514 644 2808
gavazzi@carlogavazzi.com
Carlo Gavazzi GmbH - GERMANY
Rudolf-Diesel-Strasse 23,
D-64331 Weiterstadt
Tel: +49 6151 81000
Fax: +49 6151 81 00 40
kontakt@carlogavazzi.de
Carlo Gavazzi Handel A/S - DENMARK
Over Hadstenvej 42, DK-8370 Hadsten
Tel: +45 89 60 6100
Fax: +45 86 98 15 30
handel@gavazzi.dk
Carlo Gavazzi UK Ltd - GREAT BRITAIN
7 Springlakes Industrial Estate,
Deadbrook Lane, Hants GU12 4UH,
GB-Aldershot
Tel: +44 1 252 339600
Fax: +44 1 252 326 799
sales@carlogavazzi.co.uk
Carlo Gavazzi BV - NETHERLANDS
Wijkermeerweg 23,
NL-1948 NT Beverwijk
Tel: +31 251 22 9345
Fax: +31 251 22 60 55
info@carlogavazzi.nl
Carlo Gavazzi AS - NORWAY
Melkeveien 13, N-3919 Porsgrunn
Tel: +47 35 93 0800
Fax: +47 35 93 08 01
gavazzi@carlogavazzi.no
Carlo Gavazzi SA - SPAIN
Avda. Iparraguirre, 80-82,
E-48940 Leioa (Bizkaia)
Tel: +34 94 480 4037
Fax: +34 94 480 10 61
gavazzi@carlogavazzi-sa.es
Carlo Gavazzi AB - SWEDEN
Nattvindsgatan 1, S-65221 Karlstad
Tel: +46 54 85 1125
Fax: +46 54 85 11 77
gavazzi@carlogavazzi.se
Carlo Gavazzi AG - SWITZERLAND
Verkauf Schweiz/Vente Suisse
Sumpfstrasse 32,
CH-6312 Steinhausen
Tel: +41 41 747 4535
Fax: +41 41 740 45 40
verkauf_vente@carlogavazzi.ch
Carlo Gavazzi Inc. - USA
750 Hastings Lane,
USA-Buffalo Grove, IL 60089,
Tel: +1 847 465 6100
Fax: +1 847 465 7373
sales@carlogavazzi.com
Carlo Gavazzi Lda - PORTUGAL
Rua dos Jerónimos 38-B,
P-1400-212 Lisboa
Tel: +351 21 361 7060
Fax: +351 21 362 13 73
carlogavazzi@carlogavazzi.pt
Carlo Gavazzi Industri A/S
Hadsten - DENMARK
Tel: +45 89 60 6100
Carlo Gavazzi Ltd
Zejtun - MALTA
Tel: +356 23601 100
Carlo Gavazzi Controls SpA
Belluno - ITALY
Tel: +39 0437 931 000
SAIET Elettronica SpA
Castel Maggiore (BO) - ITALY
Tel: +39 051 417 8811
Carlo Gavazzi Industri A/S
Hadsten - DENMARK
Tel: +45 89 60 6100
Inductive and Capacitive
Proximity Sensors in full metal
and plastic housings.
Photoelectric Sensors.
Level Sensors: Optical,
Conductive and Capacitive.
Ultrasonic Sensors and
Magnetic Switches.
Limit Switches.
Solid States Relays.
Versions for PCB and
panel mounting.
AC Semiconductor
Motor Controllers
Soft starters.
Industrial and PCB Relays.
Energy Management.
Timers and
Monitoring Relays.
Digital Panel Meters and
Temperature Controllers.
Safety Modules, Safety Magnetic
Sensors, Safety Mats, Safety Light
Curtains, Intrinsic Safety, Electrical
Protections
Dupline Field and
Installation Bus.
Building Automation Systems.
Further information on www.carlogavazzi.com/ac
CARLO GAVAZZI
Automation
Components
8028090 BRO DPM ENG REV.06-2004
OUR PRODUCTION SITES