Alco Controls Thermo -Expansion Valve Series T

Alco Controls Thermo -Expansion Valve Series T
Alco Controls
Thermo®-Expansion Valve Series T
Exchangeable Power Assemblies and Orifices
Features
• Modular design for economical logistics and easy assembly and servicing
• Very good stability is attained because of the large forces generated by the large diaphragm diameter
• High quality materials and processes for high reliability and long lifetime
• Superior partial load performance due to double seat orifice design (TJRE, TERE, TIRE & THRE)
• Biflow capability for applications in heat pumps
• Capillary tube length 1.5 m (TCLE, TJRE) and 3m (TERE, TIRE & THRE)
• PS: 31 bar, TS: -45 ... +65°C
• No CE marking according art. 3.3 PED 97/23 EC
TCLE
Type Code
TCL E 100 H W 100WL10x16
Valve Series
External Equalizer
Capacity Code
Refrigerant Code
Charge Code
MOP Code
Flange Style
WL=Angle Style
DL=Straight through
Connection
Selection Chart for Orifices
Series
R 134a
Type
Nominal
Capacity
kW
25 MW
1,5
R 22
Type
Nominal
Capacity
kW
50 HW
1,9
R 404A/R 507
Type
Nominal
Capacity
kW
25 SW
1,3
R 407C
Type
Nominal
Capacity
kW
50 NW
2,1
TCLE
TJRE
75 MW
150 MW
200 MW
250 MW
350 MW
550 MW
750 MW
900 MW
11 MW
13 MW
2,9
6,1
9,3
13,5
17,3
23,6
32,0
37,2
45
57
100 HW
200 HW
250 HW
300 HW
500 HW
750 HW
1000 HW
1200 HW
14 HW
18 HW
3,7
7,9
11,9
17,3
22,2
30,4
41,1
47,8
58
74
75 SW
150 SW
200 SW
250 SW
400 SW
600 SW
850 SW
1000 SW
12 SW
14 SW
2,6
5,6
8,4
12,2
15,7
21,5
29,0
33,8
40
51
100 NW
200 NW
300 NW
400 NW
550 NW
750 NW
1000 NW
1150 NW
14 NW
17 NW
4,0
8,5
12,9
18,7
24,0
32,9
44,4
51,7
62
80
TERE
TIRE
THRE
16 MW
19 MW
25 MW
31 MW
45 MW
55 MW
68 MW
71
81
112
135
174
197
236
22 HW
26 HW
35 HW
45 HW
55 HW
75 HW
100 HW
91
104
143
174
223
253
302
18 SW
20 SW
27 SW
34 SW
47 SW
61 SW
77 SW
63
72
99
120
154
174
209
21 NW
25 NW
33 NW
42 NW
52 NW
71 NW
94 NW
99
112
155
188
241
273
327
Orifice
X 22440-B1B
X 22440-B2B
X 22440-B3B
X 22440-B3,5B
X 22440-B4B
X 22440-B5B
X 22440-B6B
X 22440-B7B
X 22440-B8B
X 11873-B4B
X 11873-B5B
X 9117-B6B
X 9117-B7B
X 9117-B8B
X 9117-B9B
X 9166-B10B
X 9144-B11B
X 9144-B13B
Nominal capacity (Qn) is based on the following conditions:
MOP
Code
35
40
55
65
75
80
100
72
bar
2,4
2,8
3,8
4,5
5,2
5,5
6,9
Evaporating Temperature Range °C
R 134a
R 22
R 404A
R 407C
R 507
MW
HW
SW
NW
SW
-45 .. 0 -45 .. -15
-45 .. -18
-45 .. -18
-45 .. 11
-45 .. -10
-45 .. -10
-45 .. 0
-45 .. -2
-45 .. -2
-45 .. 0
-45 .. 0
-45 .. 13
-45 .. 14
Refrigerant
R 407C
R 22, R 134a,
R 404A/R 507
Evaporating
temperature
+4°C dew
point
Condensing
temperature
+38°C bubble p.
+43°C dew point
Subcooling
+4°C
+38°C
1K
1K
Valve selection for other operating conditions see page 74
or use the Excel based ALCO Selection Tool (download from
www.emersonclimate.eu).
SGE127-EN-1101
Alco Controls
Available upon special request:
•Power assembly with solder connection for external pressure equalization
•Non-standard MOPs
•Non-standard charges
•Non-standard connection sizes, see page 86
Type Code
XB 1019H W100 - 1 B
Power Assembly
Refrigerant Code
Charge Code
MOP Code
Capillary Tube Length
1=1,5m; 2=3m
External Equalization
Selection Chart for Power Assemblies and Recommended Flanges
Orifice
X 22440-B1B
X 22440-B2B
X 22440-B3B
X 22440-B3,5B
X 22440-B4B
X 22440-B5B
X 22440-B6B
X 22440-B7B
X 22440-B8B
X 11873-B4B
X 11873-B5B
X 9117-B6B
X 9117-B7B
X 9117-B8B
X 9117-B9B
X 9166-B10B
X 9144-B11B
X 9144-B13B
Connection
Standard-Flange, Angle (see page 86)
Solder/ODF
mm
inch
C 501 - 5 mm
10 x 16
C 501 - 5
3/8 x 5/8
C 501 - 7 mm
12 x 16
A 576 mm
16 x 22 (22 x 28 ODM)
10331
22 x 22
C 501 - 7
1/2 x 5/8
A 576
5/8 x 7/8 (7/8 x 1 1/8 ODM)
10331
7/8 x 7/8 (1 1/8 x 1 1/8 ODM)
9153 mm
22 x 22
9153
7/8 x 7/8
(1 1/8 x 1 1/8 ODM)
9149
22 x 22
9149
7/8 x 7/8 (1 1/8 x 1 1/8 ODM)
Power
Assembly
XB1019…1B
XC726…2B
Spare Parts
Gasket Set for T Series Valves
Service Tool for T Series
Steel screws for following flange types:
C501 , 9761 , 6346 , A576
9148 , 9149, 9152, 9153, 10331 , 10332
SGE127-EN-1101
Type
X 13455 -1
X 99999
Screw ST 32
Screw ST 48
Part No.
027 579
800 005
803 573
803 574
73
Alco Controls
Correction Tables for Thermo®-Expansion Valves
Series TI, TX3, TX6, T and L
Alternatively download the Excel based ALCO
Selection Tool from www.emersonclimate.eu.
Valve selection for operating conditions
other than nominal conditions:
Qn = Qo x Kt x K∆p
Qn: Nominal valve capacity
Qo: Required cooling capacity
Liquid
R 410A
Kt : Correction factor for evaporating and liquid temperature
K∆p: Correction factor for pressure drop at valve
Correction Factor Kt
(TX3/6 only)
Temperature
entering Valve
°C
+20
+15
+10
+5
+65
1,75
1,76
1,78
1,80
+60
1,49
1,50
1,51
+55
1,31
1,32
+50
1,19
1,20
+45
1,09
+40
Evaporating Temperature
°C
0
-5
-10
-15
-20
-25
-30
-35
-40
-45
1,83 1,86
1,89
2,18 2,55
3,05
3,69 4,49
5,46
6,62
1,53
1,54 1,57
1,59
1,83 2,14
2,55
3,08 3,73
4,52
5,45
1,33
1,35
1,36 1,38
1,40
1,61 1,87
2,23
2,68 3,25
3,92
4,72
1,20
1,21
1,23 1,24
1,26
1,44 1,68
2,00
2,40 2,90
3,49
4,20
1,09
1,10
1,11
1,12 1,13
1,15
1,32 1,53
1,82
2,18 2,63
3,17
3,80
1,01
1,01
1,02
1,03
1,04 1,05
1,06
1,21 1,41
1,67
2,01 2,41
2,90
3,48
+35
0,94
0,94
0,95
0,96
0,97 0,98
0,99
1,13 1,31
1,55
1,86 2,24
2,69
3,21
+30
0,88
0,89
0,89
0,90
0,91 0,91
0,92
1,06 1,22
1,45
1,74 2,09
2,50
2,99
+25
0,83
0,84
0,84
0,85
0,85 0,86
0,87
0,99 1,15
1,36
1,63 1,96
2,35
2,80
+20
0,79
0,80
0,80
0,81 0,81
0,82
0,94 1,09
1,29
1,54 1,84
2,21
2,64
2
3
4
13
14
15
16
1,04
1
0,97
0,94
30
31
Correction Factor K∆p
∆p (bar)
1
K∆p
3,74
∆p (bar)
17
K∆p
0,91
2,65 2,16
18
19
0,88 0,86
1,87
5
6
1,67 1,53
7
1,41
20
21
22
23
0,84
0,82
0,8
0,78
8
9
1,32 1,25
24
25
0,76 0,75
10
1,18
26
0,73
11
12
1,13 1,08
27
28
0,72 0,71
29
0,69
Liquid
Temperature
entering Valve
°C
-10
-15
-20
-25
-30
+60
1,22 1,25
1,27 1,30
1,33 1,36
1,40
1,44 1,48
1,75
2,08 2,46
2,94
+55
1,14 1,16
1,18 1,21
1,23 1,26
1,29
1,33 1,36
1,60
1,90 2,25
2,68
+50
1,07 1,08
1,10 1,13
1,15 1,17
1,20
1,23 1,26
1,48
1,76 2,07
2,46
+45
1,00 1,02
1,04 1,06
1,08 1,10
1,12
1,15 1,17
1,38
1,63 1,92
2,28
+40
0,93 0,96
0,98 0,99
1,01 1,03
1,05
1,08 1,10
1,29
1,52 1,79
2,12
+35
0,90 0,91
0,92 0,94
0,96 0,97
0,99
1,01 1,03
1,21
1,43 1,68
1,99
+30
0,85 0,86
0,88 0,89
0,91 0,92
0,94
0,96 0,98
1,14
1,35 1,58
1,87
+25
0,82
0,83 0,85
0,86 0,87
0,89
0,91 0,92
1,08
1,27 1,49
1,76
+20
0,80 0,81
0,82 0,83
0,85
0,89 0,88
1,02
1,21 1,41
1,67
+15
0,77
0,78 0,79
0,81
0,82 0,84
0,97
1,15 1,34
1,58
+10
0,75 0,76
0,77
0,78 0,80
0,93
1,09 1,28
1,51
+5
0,73
0,74
0,75 0,76
0,89
1,04 1,22
1,44
0
0,71
0,72 0,73
0,85
1,00 1,17
1,37
-5
0,69 0,70
0,82
0,96 1,12
1,31
-10
0,79
0,92 1,07
1,26
1,0
1,5
2,0
2,5
R 134a
Evaporating Temperature
+25
32
0,66
Correction Factor Kt
+30
0,68 0,67
°C
+20
+15
+10
+5
0
-5
0,68
Correction Factor K∆p
∆p (bar)
0,5
K∆p
3,50
∆p (bar)
8,5
K∆p
0,85
2,48 2,02
9,0
9,5
0,83 0,80
3,0
3,5
4,0
4,5
5,0
5,5
6,0
6,5
7,0
7,5
8,0
1,75
1,57 1,43
1,32
1,24 1,17
1,11
1,06 1,01
0,97
0,94 0,90
0,88
10,0
10,5 11,0
11,5
12,0 13,0
14,0
15,0 16,0
17,0
18,0 19,0
20,0
0,78
0,76 0,75
0,73
0,72 0,69
0,66
0,64 0,62
0,60
0,58 0,57
0,55
In cases of subcooling of more than 15K please use additionally
the correction factors on page 60 of this brochure.
74
SGE127-EN-1101
Alco Controls
Liquid
Temperature
entering Valve
°C
Correction Factor Kt
R 22
Evaporating Temperature
+30
°C
+25
+20
+15
+10
+5
0
+60
1,22 1,23
1,24
1,25
1,26 1,28
1,30
+55
1,14 1,15
1,16
1,17
1,19 1,20
1,22
+50
1,08 1,09
1,10
1,11
1,12 1,13
+45
1,02 1,03
1,04
1,05
+40
0,97 0,98
0,99
+35
0,92 0,93
+30
0,88 0,89
+25
+20
+15
-5
-20
-25
-30
-35
-40
-45
1,31 1,38
1,58 1,84
2,16
2,56 3,04
3,55
4,23
1,23 1,29
1,42 1,72
2,02
2,39 2,83
3,30
3,94
1,15
1,16 1,21
1,39 1,62
1,89
2,24 2,66
3,10
3,68
1,06 1,07
1,08
1,10 1,15
1,31 1,52
1,79
2,11 2,50
2,91
3,46
1,00
1,01 1,02
1,03
1,04 1,09
1,24 1,45
1,69
2,00 2,37
2,75
3,27
0,94
0,95
0,96 0,97
0,98
0,99 1,03
1,18 1,37
1,61
1,89 2,24
2,60
3,09
0,90
0,91
0,92 0,93
0,94
0,95 0,99
1,13 1,31
1,55
1,83 2,13
2,47
2,93
0,85
0,86
0,87
0,88 0,89
0,89
0,90 0,94
1,08 1,25
1,46
1,72 2,03
2,36
2,80
0,83
0,83
0,84 0,85
0,86
0,87 0,90
1,03 1,19
1,40
1,64 1,94
2,25
2,66
0,80
0,81 0,81
0,82
0,83 0,87
0,99 1,14
1,34
1,57 1,86
2,15
2,55
+10
0,78 0,78
0,79
0,80 0,83
0,95 1,10
1,28
1,51 1,78
2,06
2,44
+5
0,75
0,76
0,77 0,80
0,91 1,06
1,23
1,45 1,71
1,98
2,34
0
0,73
0,74 0,77
0,88 1,02
1,19
1,39 1,65
1,90
2,25
-5
0,71 0,74
0,85 0,98
1,14
1,34 1,58
1,83
2,17
-10
0,82 0,95
1,10
1,30 1,53
1,77
2,09
∆p (bar)
0,5
1,0
1,5
2,0
2,5
8,0
9,0
K∆p
4,25 3,00
2,46
2,13
1,90 1,74
1,61
1,50 1,42
1,35 1,28
1,23
1,18 1,14
1,06
1,00
∆p (bar)
10,0 11,0
12,0
13,0
14,0 15,0
16,0
17,0 18,0
19,0 20,0
21,0
22,0 23,0
24,0
25,0
K∆p
0,95 0,91
0,87
0,83
0,80 0,78
0,75
0,73 0,71
0,69 0,67
0,66
0,64 0,63
0,61
0,60
Liquid
-15
-40
-45
-10
0,72
-15
Correction Factor K∆p
R 404A
Temperature
3,5
4,0
4,5
5,0
5,5
6,0
6,5
7,0
Correction Factor Kt
entering Valve
3,0
Evaporating Temperature
°C
+25
+20
+15
-25
-30
-35
+60
1,56 1,59
+30
1,64
1,69 1,74
+10
1,81
+5
1,88 1,96
0
-5
2,06 2,43
-10
2,95 3,56
-20
4,37
5,38 6,71 8,47
+55
1,32 1,35
1,38
1,42 1,46
1,50
1,55 1,61
1,68 1,96
2,36 2,83
3,43
4,16 5,12 6,34
+50
1,16 1,18
1,20
1,23 1,26
1,30
1,34 1,38
1,43 1,67
1,99 2,37
2,85
3,43 4,18 5,14
+45
1,04 1,05
1,07
1,10 1,12
1,15
1,18 1,22
1,26 1,46
1,74 2,05
2,46
2,95 3,57 4,35
+40
0,94 0,96
0,97
0,99 1,02
1,04
1,07 1,09
1,13 1,30
1,55 1,82
2,17
2,59 3,13 3,80
+35
0,87 0,88
0,90
0,91 0,93
0,95
0,97 1,00
1,02 1,18
1,40 1,64
1,96
2,33 2,80 3,38
+30
0,81 0,82
0,83
0,84 0,86
0,88
0,90 0,92
0,94 1,08
1,28 1,50
1,78
2,11 2,53 3,05
+25
0,76
0,77
0,79 0,80
0,82
0,83 0,85
0,87 1,00
1,18 1,39
1,64
1,94 2,32 2,79
+20
0,73
0,74 0,75
0,77
0,78 0,80
0,81 0,94
1,10 1,29
1,52
1,80 2,15 2,58
+15
0,70 0,71
0,72
0,73 0,75
0,76 0,88
1,03 1,21
1,42
1,68 2,00 2,40
+10
0,67
0,68
0,69 0,71
0,72 0,83
0,97 1,13
1,34
1,58 1,88 2,25
+5
0,65
0,66 0,67
0,68 0,78
0,92 1,07
1,26
1,49 1,77 2,11
0
0,63 0,64
0,65 0,75
0,88 1,02
1,20
1,41 1,67 2,00
-5
0,61
0,62 0,71
0,83 0,97
1,14
1,34 1,59 1,90
-10
0,60 0,68
0,80 0,93
1,09
1,28 1,52 1,81
Correction Factor K∆p
∆p (bar)
K∆p
4,55 3,21
2,62
2,27 2,03
1,86
1,72 1,61
1,52 1,44
1,37 1,31
1,26
1,21 1,14 1,07
∆p (bar)
10,0 11,0
12,0
13,0 14,0
15,0
16,0 17,0
18,0 19,0
20,0 21,0
22,0
23,0 24,0 25,0
K∆p
1,02 0,97
0,93
0,89 0,86
0,83
0,80 0,78
0,76 0,74
0,72 0,70
0,69
0,67 0,66 0,64
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
5,5
6,0
6,5
7,0
8,0
9,0
In cases of subcooling of more than 15K please use additionally
the correction factors on page 60 of this brochure.
SGE127-EN-1101
75
Alco Controls
Liquid
Correction Factor Kt
R 407C
Temperature
entering Valve
Evaporating Temperature
°C
+30
+25
+20
+15
+10
+5
0
-5
-10
-15
-20
-25
+55
1,20
1,21
1,23
1,26
1,28
1,31
1,34
1,37
1,40
1,63
1,98
2,42
+50
1,10
1,11
1,13
1,15
1,17
1,19
1,22
1,24
1,27
1,48
1,79
2,18
+45
1,02
1,03
1,05
1,06
1,08
1,10
1,12
1,14
1,17
1,35
1,64
2,00
+40
0,95
0,96
0,98
0,99
1,01
1,02
1,04
1,06
1,08
1,25
1,52
1,84
+35
0,89
0,90
0,92
0,93
0,94
0,96
0,98
0,99
1,01
1,17
1,41
1,71
+30
0,85
0,85
0,87
0,88
0,89
0,90
0,92
0,93
0,95
1,10
1,32
1,60
+25
0,81
0,82
0,83
0,84
0,85
0,87
0,88
0,90
1,03
1,25
1,51
+20
0,78
0,79
0,80
0,81
0,82
0,84
0,85
0,98
1,18
1,43
+15
0,75
0,76
0,77
0,78
0,80
0,81
0,93
1,12
1,35
+10
0,73
0,74
0,75
0,76
0,77
0,89
1,07
1,29
+5
0,71
0,72
0,73
0,74
0,85
1,02
1,23
0
0,69
0,70
0,71
0,81
0,98
1,18
-5
0,67
0,68
0,78
0,94
1,13
-10
0,65
0,75
0,90
1,08
Correction Factor K∆p
∆p (bar)
3,0
3,5
6,0
6,5
7,0
K∆p
4,78 3,33 2,72
2,36 2,11
1,92
1,78
1,67 1,57
1,49 1,42
1,36
1,31
1,26
1,18 1,11
∆p (bar)
10,0 11,0 12,0
13,0 14,0
15,0
16,0
17,0 18,0
19,0 20,0
21,0
22,0
23,0
24,0 25,0
K∆p
1,05 1,01 0,96
0,92 0,89
0,86
0,83
0,81 0,79
0,76 0,75
0,73
0,71
0,70
0,68 0,67
-15
-20
-25
-30
-35
-40
-45
0,5
1,0
1,5
Liquid
Temperature
entering Valve
°C
+30
+25
+20
+60
1,54
1,57
+55
1,30
1,33
+50
1,15
+45
2,0
2,5
4,0
4,5
5,0
5,5
8,0
9,0
Correction Factor Kt
R 507
Evaporating Temperature
+15
+10
+5
0
1,61 1,65 1,71
1,76
1,83
1,90 1,98 2,36
2,84
3,44
4,23 5,25
6,61
8,45
1,36 1,39 1,43
1,47
1,52
1,57 1,62 1,92
2,29
2,75
3,35 4,11
5,11
6,44
1,17
1,19 1,22 1,24
1,28
1,31
1,35 1,40 1,64
1,95
2,33
2,81 3,43
4,23
5,29
1,03
1,05
1,07 1,09 1,11
1,14
1,17
1,20 1,23 1,45
1,71
2,04
2,45 2,97
3,64
4,53
+40
0,94
0,96
0,97 0,99 1,01
1,03
1,06
1,08 1,11 1,30
1,53
1,82
2,18 2,63
3,22
3,98
+35
0,87
0,88
0,90 0,91 0,93
0,95
0,97
0,99 1,01 1,18
1,39
1,65
1,97 2,37
2,89
3,56
+30
0,81
0,82
0,83 0,85 0,86
0,88
0,89
0,91 0,93 1,09
1,28
1,51
1,80 2,17
2,63
3,23
+25
0,77
0,78 0,79 0,80
0,82
0,83
0,85 0,87 1,01
1,18
1,40
1,66 1,99
2,42
2,97
+20
0,73 0,74 0,75
0,77
0,78
0,79 0,81 0,94
1,10
1,30
1,54 1,85
2,24
2,74
+15
0,72
0,73
0,75 0,76 0,88
1,03
1,21
1,44 1,73
2,09
2,55
+10
0,67
0,68
0,69
0,70 0,72 0,83
0,97
1,14
1,35 1,62
1,95
2,38
+5
0,64
0,65
0,67 0,68 0,78
0,92
1,07
1,27 1,52
1,83
2,23
0
0,62
0,63 0,64 0,74
0,87
1,02
1,20 1,43
1,73
2,10
-5
0,60 0,61 0,70
0,82
0,96
1,14 1,35
1,63
1,98
-10
0,78
0,91
1,08 1,28
1,54
1,87
∆p (bar)
0,5
1,0
1,5
2,0
2,5
3,0
3,5
5,5
6,0
8,0
9,0
K∆p
4,63
3,27
2,67 2,31 2,07
1,89
1,75
1,64 1,54 1,46
1,40
1,34
1,28 1,24
1,16
1,09
∆p (bar)
10,0
11,0
12,0 13,0 14,0
15,0
16,0
17,0 18,0 19,0
20,0
21,0
22,0 23,0
24,0
25,0
K∆p
1,03 0,99 0,94 0,91 0,87 0,85 0,82 0,79 0,77 0,75
In cases of subcooling of more than 15K please use additionally
the correction factors on page 60 of this brochure.
0,73
0,71
0,70 0,68
0,67
0,65
0,70 0,71
-5
-10
0,58 0,67
Correction Faktor K∆p
76
4,0
4,5
5,0
6,5
7,0
SGE127-EN-1101
Flanges for Valves
Angle Style Flange
Angle Style
Type
Order
No.
C
C
C
C
C
C
501
501
501
501
501
501
-4
- 4 MM
-5
- 5 MM
-7
- 7 MM
—
A 576
A 576 - MM
10331
803 230
803 231
803 232
803 233
803 234
803 235
—
803 238
803 239
803 338
Straight Through
Type
Order
No.
9761
9761
9761
9761
6346
-3
- 3 MM
-4
- 4 MM
- 17
—
—
10332
803 240
803 241
803 350
803 243
803 330
—
—
803 324
Straight Through Flange
Connections
mm
inch
Solder ODF
Solder ODM
Solder ODF
Solder ODM
—
10 x 12
—
10 x 16
—
12 x 16
16 x 22
—
16 x 22
22 x 22
—
—
—
—
—
—
—
—
22 x 28
—
3/8 x 1/2
—
3/8 x 5/8
—
1/2 x 5/8
—
5/8 x 7/8
5/8 x 7/8
—
7/8 x 7/8
9153
803 244
9152
803 286
—
—
7/8 x 7/8
9153 MM
803 245
9152 MM
803 287
22 x 22
28 x 28
—
—
—
—
—
—
—
—
7/8 x 1-1/8
—
1-1/8 x 1-1/8
1-1/8 x 1-1/8
for
Valve
Series
TCLE
ZZCE
LCLE
935 A-G
CPHE 1
CPHE 2
TJRE
ZZJRE
LJRE
935 K
CPHE 3
TERE
TIRE
ZZERE
ZZIRE
LERE
LIRE
CPHE 3,5
CPHE 4
CPHE 5
9149
68
803 284
9148
803 283
22 x 22
—
7/8 x 7/8
1-1/8 x 1-1/8
THRE
CPHE 6
A2.5.1/0501/E
Dimensions TCLE
Angle Style Flanges TCLE
Connections
Lay-in length
Inlet
Outlet
3/8 1/2 SAE
3/8 5/8 SAE
1/2 5/8 SAE
10
12 ODF
14
17
10
16 ODF
14
21
12
16 ODF
18
21
16
22 ODF
21
25
3/8 1/2 ODF
14
17
3/8 5/8 ODF
14
21
1/2 5/8 ODF
18
21
5/8 7/8 ODF
21
25
Straight Through Flanges TCLE
3/8 1/2 SAE
3/8 5/8 SAE
1/2 5/8 SAE
10
12 ODF
8
10
10
16 ODF
8
13
12
16 ODF
10
13
3/8 1/2 ODF
8
10
3/8 1/2 ODF
8
13
1/2 1/2 ODF
10
1/2 5/8 ODF
10
13
1/2 7/8 ODF
19
5/8 5/8 ODF
13
5/8 7/8 ODF
13
19
5/8 1-18 ODF
13
5/8 1-18 ODF 19
13
A
106
106
113
105
105
108
124
105
105
108
124
95
B
78
C
39
77
80
80
90
77
80
80
90
37
40
40
51
37
40
40
51
45
45
50
50
55
55
40
41
41
40
41
40
41
49
41
49
60
60
36
95
97
95
41
98
49
D
30
34
E
29
29
35
27
43
27
27
30
43
F
G
H
Weight
kg
1,1
27
29
1,1
27
10
29
1,2
1,2
31
17
9
31
33
1,1
10
1,15
Dimensions TJRE
Angle Style Flanges TJRE
Connections
Lay-in length
Inlet
Outlet
22
22 ODF
19
19
Straight Through Flanges TJRE
7/8 7/8 ODF
19
19
A
140
B
85
C
51
D
93
E
59
F
G
29
Weight
kg
1,3
137
51
45
75
15
56
29
1,4
Dimensions TERE, TIRE, THRE
Angle Style Flanges Type 9153, 9153-MM for TERE, TIRE
Connections
Lay-in length
Inlet
Outlet
A
B
C
22
22 ODF
19
19
140
7/8 7/8 ODF
19
19
140
Angle Style Flanges Type 9149 for THRE
87
51
22,2 22,2 ODF 19
19
154
7/8 7/8 ODF
19
19
154
Straight Through Flanges Type 9152 for TERE, TIRE
22,2 22,2 ODF 19
19
139
7/8 7/8 ODF
19
19
139
Straight Through Flanges Type 9148 for THRE51
45
22,2 22,2 ODF 19
19
139
7/8 7/8 ODF
19
19
139
25,4
D
92
92
E
59
59
106
106
73
73
F
G
23
25
Weight
kg
1,4
1,4
25
25
1,45
1,45
1,5
1,5
74
16,5
58
25
1,45
1,45