LUNA Indoor Environment Control Equipment Digital control system for waterborne climate systems

LUNA Indoor Environment Control Equipment Digital control system for waterborne climate systems
LUNA
Indoor Environment Control Equipment
Digital control system for waterborne climate systems
LUNA Indoor Environment Control System
►► For sequential control of cooling and/or heating.
►► Flexible controller that can be reconfigured according
to needs.
►► Extended unit life cycle
►► Up to 8 actuator pairs can be connected to a single
controller.
For indoor climate systems with water-based cooling and
heating (or electric heating) in new construction and
refurbishment projects.
LUNA for flexible indoor environment control
LUNA includes: Digital controller, thermoelectric
actuators, valves, prefabricated cables, connection card, transformer and accessories.
Controller function: PI (adjustable via remote configu-
ration unit)
Supply voltage: 24 V AC/DC
1
LUNA
►► Complete system that is easily adapted to changing
needs.
Application
LUNA
Functions
• PI function to ensure an even room temperature
• Regularly exercising the valves prevents them from clogging
• Digital functionality provides reliable operation and long
lifetime
• Condensation sensor connection directly into controller
• Input for remote temperature sensor
• Programmable via plug in remote configuration unit
Functionality
LUNA Advantages
• Sequential control of cooling and heating with PI function. Jumpers to set controller outputs – can be switched between PWM (Pulse Wave Modulation) and 0-10
V function.
• Regularly exercising the valves prevents the valve spindles from jamming which is likely to occur if cooling or
heating is not required during a longer period.
• The controller’s digital processor is easily reconfigured
with a remote configuration unit. This provides great
flexibility for changing functions and parameters during
or at any time after installation.
• With new technology, heat generated in the controller
is kept to a minimum, which provides more accurate
control and an extended component life cycle.
• Condensation sensor connects directly to the controller
without the need for an external junction box.
• A number of condensation sensors can be connected in
parallel to the controller, which is advantageous in larger
premises with several critical areas at risk from high
humidity.
• Up to 8 actuator pairs (8 cooling + 8 heating) can be
connected to a single controller.
• The actuators are equipped with a ”first open” function
that involves allowing the valves to remain open until
voltage is supplied.
• The system uses prominent operation indicators. The
controller displays the current operating status using
LEDs and the operating status of the actuators is shown
mechanically via visible cylinder bodies.
Sequential control of cooling and heating. If the room
temperature is more than 0.5°C above the set target
value, the cooling actuators open the cooling valves. If the
room temperature falls more than 0.5°C below the target
value, the heating actuators open the heating valves. The
controller regulates the environment in accordance with
the PI function. The I component senses both the size and
duration of the environmental deviations and adjusts the
actuator opening times accordingly. This type of regulation is called pulse width modulation (PWM). Compared,
for example, with ON/OFF regulation, PWM regulation
provides a more stable room temperature with increased
comfort as a result.
The controller’s standard setting range is 16°C to 28°C,
although the remote configuration unit can be used to set
the range within the interval 0°C to 31.9°C.
The valves are exercised once a day. On these occasions,
all the valves wired to the controller are fully opened for
3 minutes. The actuator is a normally-closed model but
is equipped with the so-called ”first open” function. This
means that the valves are open on delivery, but close 6
minutes after voltage has been supplied. This facilitates
pressure testing the water system and purging it of air.
The controller has two inputs, which by default are used
for a remote temperature sensor and a condensation
sensor respectively. Using the remote configuration unit
to connect to the controller, or in some cases by using the
jumpers, the inputs (and outputs) can be reconfigured
to other functions, such as motion detectors or circuitbreaking window sensors.
LUNA for electric heating
The LUNA can also be used as a room controller if the climate units are equipped with electric heating elements. A
cable is then, as in normal cases, wired from the cooling
output signal connection on the LUNA to the actuator of
the cooling water valve. The controller’s heating output
signal must be reconfigured for pulse-width modulation
and must be wired to a Triac unit, which in turn will control the electric heating elements of the climate unit.
For particulars on how to reconfigure the heating output
signal to enable it to control the power controller, see the
Wiring Directions.
2
The company reserves the right to make design changes without prior notice.
2012-10-02
www.swegon.com
LUNA
Installation
Installation by means of prefabricated cables with connector and connection card is a simple task (Figure 1).
Some installations require long cable runs where prefabricated cables are not long enough. In such cases, the
installer can of course use cables of his own (Figure 2).
In the installation between the LUNA and a climate unit
with electric heating, the control cable used between the
LUNA and the power controller for the heating elements
is 2 metres long (Figure 3).
230 V AC
Figure 3. Connection to the screw terminal for electric heating
Figure 1. Serial assembly with connection card and prefabricated
cables.
LUNA
Figure 2. Connection to screw terminal block in the controller.
The company reserves the right to make design changes without prior notice.
2012-10-02
www.swegon.com
3
LUNA
LUNA RE Room controller
Designation:
LUNA RE-1: Model with fitted cable for connection to LUNA KK connection card.
LUNA RE-S: Model with screw terminal blocks.
Temperature:
Ambient temperature for storage: 0°C to
+70°C
Operating temperature: +5°C to +40°C
Markings:
Swegon logo on casing. Particulars of the part
number, name of the part and a simple wiring
diagram are provided under the detachable
cover. Item number on card.
Encapsulation:
White Polylac – ABS plastic.
Dimensions:
77 x 77 x 27 mm
Protection class:
IP 20
Supply voltage:
24 V AC/DC + 10%.
Controller outputs:
24 V (cooling and heating). Max.2A
Output signal
function:
Cooling: NC
Heating: NC (can be set to NO with function
button)
IMPORTANT! A maximum of 8 actuators may
be energized at the same time, that is: in
applications where normally open actuators
are used, only a total of 8 actuators are permitted to be wired (for example 4 in the heating
circuit + 4 in the cooling circuit)
Inputs:
Remote temperature sensor and condensation
sensor.
Connection block:
All outputs use screw terminal blocks.
Figure 4. LUNA RE-1/ LUNA RE-S room controller
RE-1 with factory-fitted cable.
Cables:
Prefabricated. If other cables are used, 0.5
mm2, stranded cable is recommended.
Power rating:
1 VA
Controller function:
PI (can be switched between PWM and 0-10 V)
P-band, cooling
steps:
1K
P-band, heating
steps:
1,5 K
Neutral zone:
1K
I time:
20 minutes
Valve exercising:
Once per 24-hour period (fully open for 3
minutes)
Important! For electric heating: Shut off the
exercising function for the heating output.
Temperature
sensor:
Thermistor NTC 10K / 25°C.
Setting range:
16 - 28°C. Temperature setting midpoint 22°C
Operating status:
Light-emitting diode
Cooling: lit, blue indication
Neutral: diode not lit
Heating: lit, red indication
Condensation alarm: flashing blue indication (if
cooling is required)
Mounting:
On wall or standard 70 mm electrical bracket.
Not in direct sunlight.
Trunking:
Trunking must have a minimum diameter of 12
mm in order to run connecting cables to the
controller.
Figure 5. LUNA T-CU remote configuration unit
The product is CE labelled and S labelled and meets the EU
provisions for electromagnetic compatibility (EMC).
4
The company reserves the right to make design changes without prior notice.
2012-10-02
www.swegon.com
LUNA
With the LUNA T-CU remote configuration unit you can
easily reconfigure the controller’s default factory settings.
The adjustable parameters include:
• Target range
• Setting range
• Neutral zone
• Controller function
• P-band (cooling and heating)
• Output signal function
The functionality of the inputs can also be altered. By
default, these are used for a remote temperature sensor
and a condensation sensor. More particulars of the input
functions are available in a separate manual available at
www.swegon.com.
“First open” function
On delivery, the actuator is equipped with a ”first open”
function. This means that the valves are open on delivery,
but close 6 minutes after voltage has been supplied. This
facilitates pressure testing the water system and purging
it of air. The actuator’s ”first open” function is automatically deactivated 6 minutes after it has been energized.
You will hear a clicking sound, after which the actuator
will be switched over to the normally-closed position and
the normal control function will begin.
When a remote temperature sensor is connected to the
controller, it automatically overrides the built-in temperature sensor. Using the remote configuration unit to carry
out simple reprogramming, you can instruct the controller
to regulate according to the average of the internal and
remote temperature sensor readings. This can be especially advantageous in a larger room where temperature
differences can arise.
For more information about configuration, contact
Swegon.
LUNA AT Valve actuator
Designation:
LUNA AT-1 (including connector)
Figure 6. LUNA AT
LUNA AT-2 (pins on cable ends)
Temperature:
Ambient temperature for storage: –25 to +60°C
Operating temperature, air temperature: 0 to 60°C
Operating temperature, energy carrier: 10 to 100°C
Swegon logo on casing
Casing:
Polyamide – grey plastic
Supply voltage:
24 V AC/DC, +10%, 0-60 Hz
Functionality:
NC, two-point, thermoelectric
Cable:
Fixed two-wire cable, L= 1.0 m, 0.75 mm2
Power rating,
start-up:
6 VA for a maximum of 2 minutes
Power rating,
operation:
1.8 VA
Opening/Closing
time:
About 3 minutes
Protection class:
IP 54
Actuator power:
100 N +5%
Stroke:
4 mm
Weight:
100 g
Connection:
As standard, a VA-80 adapter is included which fits
thread size M30 x 1.5 mm.
Mounting:
Horizontal or vertical
LUNA
Markings:
Figure 7. LUNA AT position indicator
The actuator’s cylindrical position indicator clearly shows
the current operating mode – see Figure 6. When the
indicator is recessed and level with the casing, the actuator
is in the closed position. When the indicator is raised above
the casing, the actuator is in the open position.
This product CE-marked and fulfils EU requirements on EMC.
The company reserves the right to make design changes without prior notice.
2012-10-02
www.swegon.com
5
LUNA
SYST VD CLC Valve
Table 1. VD CLC valve dimensions
DN
A
B
C
D
E
F
61
33
46.5
24.5
35
M30 x 1,5
65
40
46.5
24.5
35
M30 x 1,5
The SYST VD CLC (straight) valves fit the system’s LUNA AT
actuator together with the LUNA VA-80 adapter.
VD115
1/2”
Dimensions:
See table 1
VD120
3/4”
Kv values:
See table 2
Max. working pressure:
1000 kPa
Max. pressure drop over open valve:
20 kPa
Max. pressure drop over closed valve:
150 kPa
Maximum flow line temperature:
110 °C
Straight 2-way valves (VD)
Maximum glycol concentration in water
system:
40%
1/2”
VD115CLC
1.90
0.25..1.90
3/4”
VD120CLC
2.60
0.25..2.60
Tabulka 2. Hodnoty kv pro ventil VD CLC
DN (inches)
Type
kv-value preset kv-value (m3 /h)
Adjustable range
Table 3. Presetting VD CLC valve kv values
Setting:
1
2
3
4
5
6
7
VD115CLC
0.25
0.65
0.88
1.12
1.30
1.46
1.57
1.90
VD120CLC
0.25
0.60
0.91
1.18
1.43
1.64
1.85
2.60
Flow tol. ±2
60
30
20
10
10
10
10
10
Settings < 5 are not recommended due to increased tolerances
Figure 8. Presetting the kv value.
1. Turn the screw clockwise until it is well seated.
2. Turn the screw anticlockwise to 0.
3. Turn the screw anticlockwise to the desired preset figure.
Preset values, see table 3.
Figure 9. SYST VD CLC valve
6
0
The company reserves the right to make design changes without prior notice.
2012-10-02
www.swegon.com
LUNA
LUNA KK Connection card
Connection card for connecting actuators, transformer and
slave units to the LUNA RE-1 controller. All connections made
with quick connectors and prefabricated cables.
Designation:
LUNA KK
Dimensions:
See Figure 10
Protection class: IP 20
Markings:
The casing shows actuator (heating and cooling), voltage and control signal connections.
The connection card is fitted with two
actuator outputs. One for cooling and one
for heating. The voltage from the transformer can be connected to any two-wire port
marked "power". Slave cables for supplying
voltages to additional units are connected to
any available two-wire port marked "power". The control signal from the controller
can be connected to any available four-wire
port marked "signal". Slave cables for control
signals to additional units are connected to
any available four-wire port marked "signal".
The connection card has pin connectors.
Prefabricated cables are connected to the
connection card with female connectors.
Figure 10. LUNA KK connection card
See the figure under CONNECTION INSTRUCTIONS.
LUNA TS TRANSFORMER
Double-insulated protective transformer
LUNA TS
Encapsulation:
Fully moulded. Plastic casing.
Protection class:
IP 44
Primary side:
230 V AC, 50-60 Hz. Connection via
wall plug (SE).
Secondary side:
24 V AC. T1,6 A, secondary fuse. Connecting cable, length = 1 m, with 2
branches, quick connector 2L for connecting to connection card.
Mounting:
Mounting holes on outside of casing
or fitted with bracket to wall rack in
perimeter wall system.
Figure 11. LUNA TS transformer
LUNA
Designation:
This product CE-marked and fulfils EU requirements on EMC
and LVD.
The company reserves the right to make design changes without prior notice.
2012-10-02
www.swegon.com
7
LUNA
LUNA KL Cables
LUNA KL-A operating voltage cable
Prefabricated 2-wire cable Ø0.35 mm2 with quick connectors for connecting operating voltage between connection
cards. This cable comes in three standard lengths: 1900,
3200 and 4200 mm.
LUNA KL-B slave control cable
Prefabricated 6-wire cable Ø0.35 mm2 with quick connectors for slave control. This cable carries both the control
signal and the operating voltage between cards. This cable
comes in standard lengths: 1900, 3200 and 4200 mm.
Figure 12. LUNA KL cables
1=LUNA KL-A
2=LUNA KL-B
3=LUNA KL-C
LUNA KL-C controller cable
Prefabricated 6-wire cable Ø0.35 mm2 with pins on cable
ends for connecting to the controller’s screw terminal block
and quick connectors for connecting to connection cards.
This cable comes in standard lengths: 1500 and 3000 mm.
Cable length for Primo perimeter wall system
Calculate the required cable length between two units by
measuring from end to end between the units and adding
600 mm. Select the closest longer standard length. See
Figure 13.
Figure 13. Cable length for perimeter wall system
A=Length (end to end)
Selection – maximum cable length
By using prefabricated cables up to 8 actuator pairs can
be connected to a single regulator. The entire assembly
can then be driven by a SYST TS transformer. The transformer can be connected to any terminal card in the circuit.
If cables other than the prefabricated type are used, the
cable rating must comply with the relevant regulations for
low-voltage installations.
8
The company reserves the right to make design changes without prior notice.
2012-10-02
www.swegon.com
LUNA
Accessories
Motion detector
LUNA T-TG remote temperature sensor
If reconfigured the controller can work with motion detectors. KSO type motion detectors are perfect for this purpose.
See separate documentation.
External temperature sensor, length 2500 mm.
Designation:
LUNA T-TG-2
Temperature:
Ambient temperature 0 to 50°C
Sensor element:
Thermistor
Resistance:
10 kW at 25°C
Cable:
2 x 0.25 mm2 length: 2500 mm
SYST CG condensation sensor
Condensation sensor, cable length 1500 mm.
Designation:
SYST CG
Sensor element:
Copper element
Dimensions:
30 x 15 x 0.4 mm (sensor element)
Fastening:
Adhesive tape and cable ties.
Recommended
location:
On the chilled water supply flow pipe where it
is in contact with the room air.
Cable:
2 x 0.25 mm2 length: 1500 mm
Figure 14. LUNA-T-TG
LUNA T-VA adapters for valves from other manufacturers
The LUNA T-VA-80 adapter is supplied as standard with every
LUNA AT actuator. This adapter fits SYST VD CLC valve types as
well as other manufacturers.
Material:
Plastic
Designation:
LUNA T-VA-32 / Tour & Andersson
LUNA T-VA-39 / Oventrop
LUNA T-VA-50 / Honeywell, Reich, MNG, Böhnisch (H), Cazzaniga
LUNA T-VA-54 / MMA
LUNA T-VA-59 / Danfoss RAV/L
LUNA T-VA-72 / Danfoss RAV
LUNA T-VA-78 / Danfoss RA
LUNA T-VA-80 / Siemens and others
TR Triac unit
Material:
Plastic
Control input:
24 V ss.
Control output:
230 V AC, max 16 A
Degree of protection:
IP 20
Dimensions:
150 x 94 x 41 mm
Cable:
2-wire cable for connection to LUNA
controller, L = 2 m
LUNA
Triac unit for controlling electric heating. 
Figure 15. SYST CG
LUNA T-KT connector
If needed, extra connectors are available.
Designation:
LUNA T-KT-2L-1 / for power cable
LUNA T-KT-2L-2 / for actuator
LUNA T.KT-4-L / for slave cable
Figure 16. TR Triac unit
The company reserves the right to make design changes without prior notice.
2012-10-02
www.swegon.com
9
LUNA
Connection instructions
LUNA is a complete control system for waterborne cooling
and heating. The complete packaged system is ideal for
perimeter wall units, installations with ceiling units, individual components should be selected in order to achieve
the correct cable lengths to suit the installation. Figure 18
shows a wiring diagram wherein the entire LUNA system is
used. In this case, the LUNA RE-1 controller is normally used
and is provided fitted with a cable with quick connectors
for connecting to the LUNA KK connection card. In cases
where prefabricated cables are not used, the LUNA RE-S
controller is available and other cables can be directly connected to the terminal blocks (Figure 17).
Table 4. Inputs/Outputs
Controller
terminal
block
Connection
card
Function
Cable
colour
1
Y20
Output signal,
cooling actuator
Brown
2
G
System potential
Blue
3
G
System potential
Blue
4
Y2
Output signal,
heating actuator
Brown
5
G
System
potential input
Black/
White
6
G0
System ground
Black
7
Y1
Input remote
temp. sensor
*
8
Y10
Input
condensation sensor
*
Figure 17. Connection to screw terminal block in LUNA RE-S
controller
*= the LUNA TG and LUNA CG are fitted with one brown
and one white cable. In terms of functionality, it does
not matter which is connected to the system ground and
function input respectively.
Figure 18. Several LUNA KK cards connected in series with a LUNA RE-1
10
The company reserves the right to make design changes without prior notice.
2012-10-02
www.swegon.com
LUNA
Sensor limitations
Remote temperature sensor: One per controller
Maximum cable length: 15 m
Condensation sensor: 8 per controller
Maximum cable length: 15 m
To relocate the jumper for electric heating
If climate units with electric heating are to be controlled
from the LUNA, wire the leads from the Triac unit to the
heating output signal connection on the LUNA as illustrated in Figure 19. The heating output signal must also be
reconfigurated from 24 V DC to 0-10 V DC. Reconfigure as
follows:
1. Disconnect the power supply to the regulator.
Figure 19. Connection to the screw terminal in the LUNA RE-S
controller for electric heating
2. Fasten an approved earthing bracelet, connected to
earthed object, around your wrist.
3. Unscrew the cover of the controller.
4. Move the jumper on the jumper strip as shown in
Figure 20.
5. Connect the LUNA T-CU hand-held unit to the controller and proceed to Menu 4 OUTPUT*.
6. Select OUTPUT no. A2 and set the following settings:
Type = 0-10 V
MOT = 0
* For more information about how to use the hand-held
unit, see separate manual at our website: www.swegon.
com.
The company reserves the right to make design changes without prior notice.
2012-10-02
www.swegon.com
11
LUNA
Figure 20. To reconnect the jumper of the controller for electric
heating
LUNA
SPECIFICATION
Product
Controller
LUNA
c
RE-
a
Version:
Model:
trafo 24V 60VA
with bracket
(perimeter wall system)
Operating voltage (2-wire)
S = Screw terminal block
LUNA a KL-A- aaaa
Version:
LUNA
a
AT-
a
Version:
Length:
1900, 3200 and 4200 mm
Model:
Slave cable (6-wire)
1 = With quick connector
2 = With pins on cable ends
Valve
SYST
VD
aaaCLC
Model:
LUNA a KL-B- aaaa
Version:
Length:
1900, 3200 and 4200 mm
Controller cable (6-wire)
VD = straight
LUNA a KL-C- aaaa
Version:
Size:
115 and 120
Connection card
LUNA c TS - 2
Cables
1 = With factory-fitted controller cable.
Valve actuator
Transformer
Length:
LUNA
c
KK
1500 and 3000 mm
Version:
12
The company reserves the right to make design changes without prior notice.
2012-10-02
www.swegon.com
LUNA
Accessories
External temperature
sensor
LUNA
a
T-
TG-
SYST
CG
LUNA
2
b
T-
CU
LUNA
a
T-
KT-
2L-
LUNA
a
T-
KT-
4L
LUNA
a
T-
VA-
aa
Version:
Model:
2 = bare wire cable ends
Condensation sensor
bare wire cable ends
Remote control
Version:
Connector, 2-wire
a
Version:
Model:
1 = for power cable
2 = for actuator
Connector, 4-wire
Version:
Adapter, actuator / valve
Version:
Triac unit for electric heating
LUNA
For valve type:
32 = Tour & Andersson
39 = Oventrop
50 = Honeywell, Reich, MNG,
Böhnisch (H), Cazzaniga
54 = MMA
59 = Danfoss RAV/L
72 = Danfoss RAV
78 = Danfoss RA
80 = Siemens and others
TR
The company reserves the right to make design changes without prior notice.
2012-10-02
www.swegon.com
13
LUNA
Descriptive texts
Accessories
Examples of descriptive texts in accordance with Swedish
standard VVS AMA.
- Condensation sensor SYST CG, XX qty
- Remote temperature sensor LUNA T-TG-2, XX qty
- Adapter, actuator / valve LUNA T-VA-aa, XX qty
- Remote configuration unit LUNA T-CU, XX qty
- Connector 2-wire LUNA T-KT-2L-a, XX qty
- Connector 4-wire LUNA T-KT-4L, XX qty
Swegon digital control equipment for waterborne climate
systems, LUNA, with the following functions:
•
•
•
•
•
•
•
•
Adapted to indoor environment control
Reprogrammable digital controller
Individual temperature regulation
Current operating status indication
Selectable regulation function PWM or 0-10 V.
Control heating and cooling sequentially
Automatic valve conditioning
Electrothermic actuators, dual-mode (on / off) with
mode clearly indicated
• “First open” function for simplified top-ups and pressure testing of the water system
• Controller with built-in condensation sensor function
• Input for remote temperature sensor
Delivery:
• Ceiling units, climate beams, radiators and cooling/
heating ceiling.
• Valves delivered to RE for mounting in the system.
• Room controller delivered to EE, SE or other contractor
to be fitted to the unit connector.
• All electrical wiring installed by EE or SE, who also provide unit connectors, connection terminals and cables.
Ceiling units, chilled beams, radiators and cooling/heating
panels:
- Controller LUNA RE-S, XX qty
- Valve SYST VD aaa-CLC, XX qty
- Valve actuator LUNA AT-2, XX qty
- Transformer LUNAc TS-2 trafo 24V 60VA, XX qty
- Triac unit, TR, XX
Perimeter wall units:
- Controller LUNA RE-1, XX qty
- Transformer LUNAc TS-2 trafo 24V 60VA, XX qty
- Prefabricated cables LUNA KL-a-bbbb, XX qty
Numbers specified separately or provided with reference
to plans.
Perimeter wall units:
• Room controller delivered to EE, SE or other contractor
to be fitted to the unit connector.
• All electrical wiring installed by EE or SE or other contractor and fitted to the unit connector.
• EE provides an earthed power outlet for every transformer and a mounted unit connector for every room
controller.
.
14
The company reserves the right to make design changes without prior notice.