120 Volt AC, 16-Point Input Module
120 Volt AC, 16-Point Input Module (IC697MDL251)
datasheet GFK-0718C
Features
a45225
D 16 Points - Four isolated groups of 4 points each
D 20 ms input filter
D Proximity switch compatible
Functions
This 120 volt AC Input module provides 16 input
points in four isolated groups of four points each.
This allows each group of four points to be used on a
different phase of the AC supply.
A1
A2
A3
A4
A5
A6
A7
A8
B1
B2
B3
B4
B5
B6
B7
B8
FUSE
INPUT
120 VAC
A1
A2
A3
The input is reactive (resistor/capacitor input) with
current-voltage characteristics which meet IEC standard (type 2). The input characteristics are compatible
with a large range of available proximity switches.
LED indicators which give the ON-OFF status of each
point on the logic (PLC) side of the circuit are included at the top of the module.
A4
A5
A6
A7
A8
B1
B2
B3
B4
B5
The module is mechanically keyed to ensure correct
replacement with a similar type in the field. I/O references are user configurable without the use of jumpers or DIP switches on the module.
Configuration is done using the configuration function of the MS-DOSr or Windowsr programming
software running on Windowsr 95 or Windows NTr
over Ethernet TCP/IP or through the SNP port. The
Programming Software configuration function is
installed on the programming device. The programming device can be an IBM XT, AT,PS/2 or compatible Personal Computer.
B6
B7
B8
C1
C2
C3
C4
C5
C6
C7
C8
D1
D2
D3
D4
D5
D6
D7
D8
SLOT
r
C1
C2
C3
C4
C5
C6
C7
C8
D1
D2
D3
D4
D5
D6
D7
D8
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î Î
Î
A1
A2
A3
A4
A5
A6
A7
A8
B1
B2
B3
B4
B5
B6
B7
B8
C1
C2
C3
C4
C5
C6
C7
C8
D1
D2
D3
D4
D5
D6
D7
D8
FUSE
10MA/PT
50/60 HZ
1
2
3
4
5
A1
A2
A3
A4
6
H
~
N
7
8
9
10
11
12
13
14
15
B1
B2
B3
B4
16
H
~
N
17
18
19
20
21
22
23
24
25
C1
C2
C3
C4
26
H
~
N
27
28
29
30
31
32
33
34
35
36
37
D1
D2
D3
D4
H
~
N
38
39
40
MODULE IC697MDL251
LABEL 44A726758–025R01
IBM and PS/2 are registered trademarks of International Business Machines Corporation.
r MS-DOS, Windows, Windows 95, and Windows NT are registered trademarks of Microsoft Corporation.
t
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F
41-1
Discrete Input Modules
2
GFK-0718C
August 1997
120 Volt AC, 16-Point Input Module
Operation of the 120 VOLT AC16 Point Input Module
LED
a45226
H
OPTO
ISOLATOR
VOLTAGE
ATTENUATOR
FILTER
SYSTEM
INTERFACE
BACKPLANE
Y
N
USER COMMON (4 CIRCUITS)
FIELD
CONNECTIONS
MODULE
Figure 1. Block Diagram for IC697MDL251
This module is compatible with a wide range of both
2-wire and 3-wire proximity switches. To determine
compatibility with a specific proximity switch, find the
ON state characteristics of the switch in the illustration below.
Input Characteristics
The 120 Volt AC 16 Point Input Module is compatible
with a wide variety of input devices, such as:
D Pushbuttons, limit switches, selector switches
D Electronic proximity switches, both 2-wire and
If that point falls to the left of the input load line, the
ON state characteristics are compatible. As an example, the ON state requirements of a compatible proximity switch of 5mA at 20 volts drop is shown.
3-wire
The input circuitry is capacitive to give low heat dissipation and associated high reliability and long life.
In addition, the OFF-state current must be less than
2.2mA.
Input current characteristics provide 10mA typically
in the ON state, and can sink up to 2.2mA of leakage
current in the OFF state to the input device.
a42232
120 VOLTS
45
NON-OPERATIONAL
ON-STATE
VOLTAGE 25
ACROSS
PROXIMITY
SWITCH
100 VOLTS
OPERATIONAL
0
2
4
6
8
10
I LOAD (mA)
Figure 2. Proximity Switch Compatibility
41-2
t
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F
Discrete Input Modules
3
GFK-0718C
August 1997
120 Volt AC, 16-Point Input Module
Module Power
The 120 Volt AC 16 Point Input Module requires 0.35
amps from the 5 volt bus on the backplane.
a45224
TERMINALS
1
Module Mechanical Keying
This module includes a mechanical key that prevents
inadvertent substitution of one module type for
another in a given slot. The key fits a uniquely
shaped area on the board below the connector. The
key is included with each module.
When the module is first installed, the key latches
onto the backplane center rail. When the module is
extracted, the key remains in the center rail, configuring the slot to accept only identical module types.
If it is necessary to change the module location in the
rack after the key has been latched onto the center rail
of the rack, the key can be removed by pushing it upward to unhook the latch while pulling it off the rail.
It may then be reinserted onto the module and the
module inserted into the rack in the desired location.
Note that only the power supply can be placed in the
leftmost rack position.
FIELD WIRING
ÎÎÎ
ÎÎÎ
ÎÎÎ
ÎÎÎ
Î
Î
Î
Î
Î
ÎÎÎ
ÎÎ
ÎÎÎ
ÎÎÎ
ÎÎÎ
Î
Î
Î
Î
ÎÎ
ÎÎÎ
ÎÎÎ
ÎÎÎ
Î
ÎÎÎ
Î
Î
Î
ÎÎÎ
ÎÎÎ
ÎÎÎ
ÎÎÎ
ÎÎÎ
Î
Î
Î
A1
2
3
A2
A3
4
5
6
7
8
9
10
11
A4
H
~
N
B1
12
B2
13
B3
14
15
16
17
18
19
20
21
B4
H
~
N
C1
22
C2
Field Wiring
The module is wired as shown in the illustration on
the right of this page. Since each group of four inputs
is isolated from the others, a wire from the power
source to the power input terminal for each group
(terminal number 10, 20, 30, or 40) is required (power
input terminals for each group are not connected inside the module).
23
C3
24
25
26
27
28
29
30
31
The wire bundle can be secured to the terminal board
by passing a cable tie through a cleat located at the
lower corner of the terminal board.
t
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F
33
~
N
D2
D3
34
35
36
37
38
39
40
H
D1
32
The detachable field wiring terminal board will accept
wire sizes from #22 (0.36 mm2) through #14 (2.10
mm2). Two wires may be terminated on a given lug if
both wires are the same size. There is room for a
bundle of forty #14 (2.10 mm2) wires to be routed out
through the terminal board cavity.
C4
D4
H
~
N
41-3
Discrete Input Modules
4
GFK-0718C
August 1997
120 Volt AC, 16-Point Input Module
Recommended Field Wiring Procedures
The following procedures are recommended when connecting field wiring to the detachable terminal board on this input
module. Module features referenced in the following procedures which are common to all I/O modules for the IC697
PLC are illustrated in the following figure.
a43855
JACKSCREW
HINGED
DOOR
JACKSCREW
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎ
ÎÎÎÎ
ÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
Î
Î
ÎÎÎÎ
Î
Î
ÎÎ
ÎÎ
Î
TERMINAL
BOARD
CORD
TIE
CORD
TIE
CLEAT
CORD
TIE
CLEAT
CORD
TIE
STRAP
CLEAT
Î
Î
Î
Î
Î
STRAP
STRAP
Figure 3. I/O Module Features
1. Turn off power before removing or installing terminals boards. Open the hinged door on the module to access a jackscrew which holds the terminal
board securely in place. The Detachable field wiring terminal board can now be removed from the
module by turning the jackscrew counter-clockwise until it is fully disengaged.
2. To remove the terminal board, grasp the top of the
terminal board and swing it outward as shown in
Figure 2.
Caution
Do not use the hinged door to remove the
terminal board. The hinged door could
be damaged if this is done.
41-4
3. The terminal board is designed to accept wire sizes
from AWG #22 (0.36 mm2) through AWG #14
(2.10 mm2). It is important that when using AWG
#14 (2.10 mm2) wire for wiring all points, that a
maximum insulation diameter of .135 inch (3.43
mm) not be exceeded. To ensure proper connection, two wires may be terminated on any one terminal only if both wires are the same size.
4. The terminal board is designed to accept a maximum of (40) AWG #14 (2.10 mm2) wires. If AWG
#14 (2.10 mm2) wires are to be used, then wire
markers should be placed at least 8 inches (203
mm) from termination end to provide sufficient
space for the hinged door to close.
t
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F
Discrete Input Modules
5
GFK-0718C
August 1997
120 Volt AC, 16-Point Input Module
Î
Î
ÎÎ
ÎÎÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎÎ
ÎÎ
Î
Î
ÎÎ
Î
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
Î
Î
Î
ÎÎ
ÎÎ
JACKSCREW
a43747
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎÎÎ
ÎÎ
ÎÎÎÎÎ
ÎÎÎÎÎ
DO NOT
PULL
ON DOOR
WIRE BUNDLE CABLE TIE CLEAT
Figure 4. Removal of I/O Terminal Board
5. After completing connections to all modules in a
rack, the wire bundle must be secured. To ensure
that the wire bundle is secured properly, it is recommended that a cable tie be wrapped around the
wire bundle and tightly secured through the cable
tie cleat located at the lower right corner of the
terminal board. For extremely large wire bundles,
additional cable ties should be used.
6. A door label insert is included with each module to
indicate circuit wiring information and provide
space to record user circuit wiring identification.
A slot is provided on the hinged door to allow for
insertion of this label. If the label is difficult to insert, crease the scored edge before insertion. The
outside label has a color coded stripe to allow
quick identification of the module voltage type
(blue: low voltage; red: high voltage).
7. After field wiring is completed, the terminal board
should be securely fastened to the rack by inserting the terminal board strap (attached to each
module) into the small rectangular slots in the bottom card guide grill on the rack. This strap not
t
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F
only secures the terminal board to the rack, it also
provides a way of identifying the wired terminal
board with its correct mating rack slot location.
8. For adequate module ventilation, it is recommended that at least a 6 inch (152 mm) clearance
be allowed above and below the rack grill. Wire
bundles should not obstruct the rack grill work.
Removing an I/O Module
The instructions below should be followed when removing an I/O module from its slot in a rack.
D Grasp the board firmly at the top and bottom of
the board cover with your thumbs on the front of
the cover and your fingers on the plastic clips on
the back of the cover.
D Squeeze the rack clips on the back of the cover
with your fingers to disengage the clip from the
rack rail and pull the board firmly to remove it
from the backplane connector.
D Slide the board along the card guide and remove it
from the rack.
41-5
Discrete Input Modules
6
GFK-0718C
August 1997
120 Volt AC, 16-Point Input Module
Table 1. Specifications for IC697MDL251 [
Rated Voltage:
120 VAC, 47 to 63 Hz Sinusoidal
Inputs per Module:
16 (four groups of four inputs each)
Isolation:
1500 volts RMS - any input to backplane
500 volts RMS between input groups
10mA (typical) at rated voltage (reactive)
Input Current:
Input Characteristics On–state Voltage:
75 to 132 volts AC, 47 to 63 Hz Sinusoidal
Off–state Voltage:
0 to 25 volts AC, 47 to 63 Hz Sinusoidal
On–state Current:
6mA to 15mA
Off–state Current:
0 to 3mA (2.2 minimum at 25V input)
Filter Delay Time:
20mstypical
Current Required from 5VDC backplane bus:
0.35 amps
VME
System designed to support the VME standard C.1
[ Refer to GFK-0867B, or later for product standards and general specifications. For installations requiring compliance to more
stringent requirements (for example, FCC or European Union Directives), refer to Installation Requirements for Conformance to
Standards.
Table 2. Ordering Information
Description
Catalog Number
Input Module: 120 Volt AC, 16 Points
IC697MDL251
Note: For Conformal Coat option, or Low Temperature Testing option please consult the factory for price and availability.
41-6
t
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement