We have designed the Amana

®

brand Packaged

Terminal Air Conditioner for customer comfort and owner piece of mind. No other unit in the industry offers so many energy management features as standard. With the ability of the

DigiSmart™ PTAC to reduce operating costs by

35%, there is no need to settle for anything less than an Amana

®

brand PTAC.

Features

Energy Effi ciency — Amana

®

brand PTACs have an EER of up to 12.8 (on heat pumps, a COP of up to 3.6) to keep energy consumption to a minimum

On-board Energy Management System —

Amana

®

brand units are equipped with EMS technology to better control room temperature and save energy dollars

DigiSmart™ Control Board — ready for wireless or wired operation

Programmable Set-back Program — ownercontrolled settings allows automatic temperature setback when unit is idle

Network Ready — Amana

®

brand Dig iSmart™ units connected to a Tridium JACE controller automatically build their own wireless network

DigiSmart™ Suite of Peripherals — remote occupancy sensor, remote thermostat,

RF antennas, and RF platform controller provide everything you need to reduce energy costs by 35%

F

ULL

W

ARRANTY

• 1

ST

Y

EAR

• 2

ND THROUGH

5

TH

Y

EAR

— S

EALED

S

YSTEM

L

IMITED

W

ARRANTY

• 2

ND THROUGH

5

TH

Y

EAR

— P

ARTS www.amana-ptac.com

5/06 SS-DPTAC

S

PECIFICATION

S

HEET

F

EATURES

D

IGI

S

MART

The Amana® DigiSmart™ suite of products work together to let you control and monitor each air conditioning unit.

In-Room Products

PTAC — The PTAC itself contains all the processing power and software to manage energy consumption, unit status, and comfort performance.

Occupancy Control — The remote sensor above the door determines if the room is occupied or not. If occupied, normal routines run, but if unoccupied the PTAC can change temperature settings based upon owner settings.

Remote Thermostat — The DigiSmart™ remote thermostat works just like the one at home but unlike other

PTACs does not disable the unit controls. Remote and PTAC control panels work at the same time and show the same information.

Set-up — Best of all, no wiring. All of the peripheral devices can be installed by your handy man without called an expensive electrician. A touch of a button connects the peripherals to the air conditioner in that room.

Property-Wide Network

The Tridium Jace™ controller connects all Amana® DidgSmart™ PATCs in a property automatically through a self-detection routine.

Once connected to your PC, the status and operating condition of each unit can be viewed remotely and settings changed centrally.

The Tridium Jace™ controller through its NiagaraAX protocol has already built connections to more than

100 commercially available building management systems. So once the network is up and running, Amana®

PTACS can be integrated with your existing building management system or if desired, controlled remotely through the internet.

P

RODUCT

F

EATURES

On-Board Energy Management System (EMS)

Set-Back Mode — the owner can determine amount of time unit left

‘untouched’ (buttons not pushed) before the PTAC begins a set-back routine and new thermostat temperature takes effect, also selected by owner.

Maintenance Status — Separate green LED indicator light to show if unit requires maintenance

Electronic Temperature Limits – owner can set separate cooling and heating temperature ranges and limit operation to one-degree increments, saving energy by preventing guests from over-cooling or over-heating.

Maintenance

Indicator Light

Enhanced Dehumidifi cation Cooling Mode — the unit can be set to lengthen cooling cycles while the room is occupied or unoccupied. This passes more air through the unit while the coil is below the dew point, increasing the amount of moisture removed.

Unit Diagnostics — when switched to diagnostics mode, the unit shows ten different self-diagnosis codes to help keep the unit running most effi ciently.

Freeze Protection — when the unit senses temperature of 40ºF or below, the unit automatically activates the fan motor and the electric or hydronic heat to help prevent burst water pipes or broken fi xtures caused by freezing temperatures.

Extended Heating with the Heat-Pump — heat pump models will operate in heat-pump mode with external temperatures as low 24ºF to provide additional energy savings.

30-Second Fan-Off Delay — the fan continues to run for 30 seconds after the compressor has stopped or after electric heat has been turned off. This improves effi ciency by dispersing the cooled or heated air still on the coil into the room.

2 www.amana-ptac.com

SS-DPTAC

S

PECIFICATION

S

HEET

EMS A

CCESSORIES

DD01A — D

IGI

D

OOR

: W

IRELESS

RF O

CCUPANCY

S

ENSOR

The DigiDoor is a combination door switch and room motion sensor powered by 2 AAA batteries that are included in the kit.

Once wirelessly linked to an Amana ® brand DigiSmart™ PTAC, the DigiDoor monitors room occupancy and automatically activates the

Energy Management System (EMS) temperature set-back function.

You can further refi ne your EMS programming by confi guring the DigiSmart with up to 100,000 EMS set-back combinations, either through the DigiSmart touch-pad or wirelessly through the optional DigiTenna DT01A and DP01A Gateway.

The DigiTenna (DT01A) is required for the DigiDoor to communicate to the DigiSmart PTAC

DP01A — D

IGI

P

LATFORM

: WEB-E

NABLED

P

LATFORM

C

ONTROLLER

The DigiPlatform uses standard 115-volt power and communicates by antennae to each Amana ® brand DigiSmart ™ PTAC with a DigiTenna (DT01A) on an encrypted 2.4 GHz signal using the 802.15 Zigbee standard.

All DigiSmart™ suite of peripherals linked to a DigiSmart™ PTAC can be monitored, controlled, and upgraded easily through the Digi-

Platform wireless RF network.

Because it is Web-enabled, all DigiPlatform functions can be accessed through the Amana ® brand Hotel Link software contained in the

DigiPlatform.

The DigiPlatform has several other software applications embedded in the device that allow optional connectivity to a property management system to monitor room rental status. Optional drivers and/or software are required.

Being BACnet- and LAN-compliant allows the DigiPlatform to integrate with almost every property controller available in the industry today. The DigiPlatform allows operational monitoring of each PTAC and peripheral device. Additional optional software may be required.

DS01A — D

IGI

S

TAT

” RF W

IRELESS

R

EMOTE

-M

OUNTED

T

HERMOSTAT

The DigiStat is a remote wall-mounted thermostat that can control the Amana ® brand DigiSmart™ PTAC from anywhere in the room. It is powered by 2 AAA batteries that are included in the kit.

The DigiStat communicates on a two-way RF encrypted signal. Settings can be changed either at the DigiStat or on the PTAC at the

DigiSmart touch-pad. Settings are automatically relayed to the other device within moments.

A DigiTenna (DT01A) is required for the DigiStat to communicate with the DigiSmart PTAC.

DSUK01B — D

IGI

S

MART

C

ONTROL

B

OARD

U

PGRADE

K

IT

Any Amana ® brand Series A or Series B PTAC produced since 1996 can be upgraded with a DigiSmart™ control board.

The DSUK01B is a fi eld-installation kit to convert an older ‘knob control’ Amana ® brand PTAC to the new DigiSmart™ LED control.

The converted Amana ® brand PTAC has the same energy management system as a DigiSmart™ PTAC and can connect to the DigiSmart™ suite of peripheral devices.

DT01A — D

IGI

T

ENNA

: W

IRELESS

RF G

ATEWAY

T

RANSCEIVER

A

NTENNA

The DigiTenna mounts inside the Amana ® brand DigiSmart PTAC, hidden from sight. It is powered through PTAC and requires no batteries. It is required for any of the DigiSuite RF wireless devices to communicate with the Amana ® brand DigiSmart PTAC.

The DigiTenna communicates to any of the Amana DigiSmart suite of devices via an encrypted 2.4 Ghz signal using the 802.15 Zigbee standard. Some Amana ® brand DigiSmart PTACs may require upgrades to the latest DigiSmart software to allow RF devices to be linked to the control.

For use with: DD01A and DS01A, both required parts of package

R

EMOTE

E

NERGY

M

ANAGEMENT

S

YSTEMS

(EMS) R

EADY

An 18-pin low-voltage connector links the unit to many wired energy management systems (EMS). The control board has low-voltage terminals for a wired room motion sensor, a door switch, or a remote-mounted thermostat. Two serial communication ports also allow for future communications capability to many other types of Amana-approved wireless RF peripheral devices.

R

EMOTE

T

HERMOSTAT

R

EADY

The unit has an 18-pin connector with seven dedicated low-voltage terminals for easy connection to a wide variety of remote wired thermostats. The unit’s off-board 20-va transformer has enough power to supply energy to most commercially available thermostats.

Also, the unit can be confi gured to be used with either a “B” or an “O” terminal, further increasing the types of thermostats that can be connected to the unit.

SS-DPTAC www.amana-ptac.com

3

S

PECIFICATION

S

HEET

PTAC A

CCESSORIES

W

ALL

S

LEEVE

14⅛”

(D)

X

42” (W)

X

161/16” (H)

Our insulated, Stonewood Beige metal sleeves with industry-standard dimensions are shipped with a weather board for use during construction. The WS900D is an industry-standard depth of 14⅛”. The extra-deep sleeves can be custom-ordered starting at 16” to 24” (D) in 1” increments. Sleeves may be shipped separately to allow for installation during construction.

O

UTDOOR

G

RILLES

Available in stamped-aluminum or architecturally louvered for application with a WS900D wall sleeve.

AGK—Extruded aluminum architectural grille available with anodized aluminum fi nish and a baked-on paint fi nish for durability. Choose from three stock colors or a custom color:

CB (Clear Anodized), DB (Dark Brown/Bronze), TB

(Stonewood Beige),

WB (White), SB (Special/Custom Colors)

PGK—One-piece injection molded grille using a polymer blend of engineered thermoplastic high-impact strength material with chemical resistance and an exterior UV protective coating.

Choose from three stock colors:

DB (Dark Brown/Bronze), TB (Stonewood Beige), WB

(White)

WS900D Standard

14⅛” Depth

WS9**D1 Extra Deep

(16” to 24”)

** Depth in inches

Standard Outdoor Grille

SGK01B Single Pack

Architectural Grille

AGK01*B

PGK01*B

Single Pack

Single Pack

T

HERMOSTATS

The following thermostats of fer remote con trol ease. Any ther mo stat other than those listed must be submitted to Goodman Company, LP, for approval prior to use.

Model

C5200609 1*

D9945801 2**

1246005/6

1246001

1246003

1246004

1241501

1*

1*

2**

2**

2**

Type Shape & Orientation

1 Mechanical Manual Round

1 Mechanical Manual Rectangular/Horizontal

1

1

1

1

Mechanical Manual

Digital

Digital

Digital

Horizontal

Manual Rectangular/Horizontal

Manual Rectangular/Horizontal

Program Rectangular/Horizontal

1 Digital Rectangular/Vertical

C

ONDENSATE

D

RAIN

K

IT

Attaches to the wall sleeve base pan for con trolled in ter nal or external disposal of condensate.

DK900D: Condensate

Drain Kit

(use with WS900D)

DK9001D: Condensate

Drain Kit

(use with WS900B and extra-deep wall sleeves)

W

IRE

H

ARNESS

K

IT

(

NOT SHOWN

)

For quick connections of the remote thermostat or front desk with jump ers and connectors.

PWHK01C Wire Harness Kit

R

EMOTE

E

SCUTCHEON

K

IT

(

NOT SHOWN

)

Optional kit for use with units controlled via a wired, remote thermostat. Covers control touch-pad for wired thermostat installations.

REK10B Remote Escutcheon Kit (10 pack)

42"

* PTC Models Only

** PTC and PTH Models

DK900D

14⅛

"

Each kit contains 80 wires and wire nuts, enough to attach a thermostat and one additional accessory to 10

PTAC units. Wires come in assorted colors for easy attachment.

4 www.amana-ptac.com

SS-DPTAC

S

PECIFICATION

S

HEET

PTAC A

CCESSORIES

(

CONT

.)

S

UB

-

BASE

K

IT

The fully skirted sub-base con ceals wiring while pro vid ing strong support, if needed. Plug-in re cep ta cle and fi eldwiring access speeds in stal la tion. Electrical ac ces so ries, such as fuse holders, circuit breakers, and dis con nect switches meet NEC re quire ments.

H

ARD

-

WIRE

K

IT

(

NOT SHOWN

)

Used to permanently wire to the chassis when a stan dard sub -base and power cord are not used.

P

OWER

D

ISCONNECT

S

WITCH

(

NOT SHOWN

)

The PSHW**A power-dis con nect switch can be used for

265-volt or 230/208-volt physical dis con nect, where re quired by local codes. The switch is rat ed at a 30-amp ca pac i ty and for use with Amana ® brand standard sub bases or PTPWHWK4 Hard-Wire Kits.

PTSB320E 230/208V 15/20A

PTSB330E 230/208V 30A

PTSB420E 265V 15/20A

PTSB430E 265V 25A

PTSB000E Non-electrical

PTPWHWK4

PSHW03A

PSHW04A

Hard-Wire Kit

230/208V

265V

F

USE

H

OLDER

K

IT

Cartridge-style fuses can be installed in the fuse hold er for use in the sub-base or chassis. Avail able in 15-, 20-, and 30-amp sizes. (included on 265-volt unit).

FHK315C

FHK320C

FHK330C

230/208V 15A

230/208V 20A

230/208V 30A

C

IRCUIT

B

REAKER

K

IT

(230/208V

ONLY

)

The circuit breaker kit, available in 15-, 20-, or 30-amp sizes, can be used with Amana ® brand sub -bases. It gives over cur rent protection, and its location al lows you to turn the unit on or off without tools.

CBK3**C Circuit Breaker Kit

D

UCT

E

XTENSION

K

IT

Extends air distribution to an adjoining room. Con sists of a main duct for the room of or i gin and an ex ten sion duct to reach the ad join ing room and ter mi nal duct.

PTDK01A allows for the new B Series unit to work with the A Series duct kits.

Main Duct Kit

MDK02B

EDK02B

TDK02

PTDK01A

Extension Duct Kit

Main Duct

Extension Duct

Terminal Duct

Transition Duct Only

Skirting

Optional

Fuse Holder

Location

Optional

Power Switch and Circuit Breaker

Location

Power Receptacle

Leveling Legs

Subbase Box Assembly

Skirting

See below.

Terminal Duct Kit

TRANSITION BAFFLES

P

OWER

V

ENT

K

IT

(

NOT SHOWN

)

Installation of Power Vent increases CFM up to ap prox i mate ly 95. Vent door will automatically close when unit fan is off.

P

OWER

D

OOR

K

IT

(

NOT SHOWN

)

Vent door will automatically open when unit fan is on.

C

ONDENSER

B

AFFLE

K

IT

For use on non-baffl ed grilles. These defl ectors di rect the air to ward the cen ter and away from the inlet to pre vent re cir cu la tion of the hot con dens er air.

PVK3A

PVK4A

230/208V

265V

PDK3A

PDK4A

230/208V

265V

DGK1B Condenser Baffl e Kit

Condenser Baffles

Condenser

Basepan

SS-DPTAC www.amana-ptac.com

5

S

PECIFICATION

S

HEET

PTAC A

CCESSORIES

(

CONT

.)

STC 30-R

ATING

A

CCESSORY

K

IT

(

NOT SHOWN

)

Raises sound ratings from 27 to 30 to meet or exceed most sound test requirements.

STC101A 10 Pack

H

EATER

K

IT

—F

OR

H

EATER

-

LESS

U

NITS

O

NLY

(

NOT SHOWN

)

Optional 1.5 kW heater kits are avail able for use only with models orig i nal ly shipped with out elec tric heat. Ask sales per son for details.

S

UB

-

BASE

E

XTENSION

C

OVER

K

IT

Converts older 30-amp sub-bases to allow for installation of the larger 30-amp LCDI power cord and plugs.

C

ONDENSATE

R

EMOVAL

P

UMP

(

NOT SHOWN

)

Can be fi eld-installed. Assists in removing con den sate de vel oped by heat pump operation and trans fers it to in door coil to dis si pate into room while add ing hu mid i ty to the room.

S

ECURITY

K

EY

L

OCKS

(

NOT SHOWN

)

In conjunction with the tamper-resistant front, the in stal la tion of Amana ® brand se cu ri ty key locks pre vents tam per ing of the controls used to set tem per a ture, heat ing and cool ing functions. UL ap proved for in sti tu tion al use only.

R

EPLACEMENT

S

PARE

F

ILTERS

(

NOT SHOWN

)

Helps keep dirt and lint out of the air and off the coil, thus increasing the unit's efficiency. Amana ® brand filters are easy to remove, wash, and replace.

R

EPLACEMENT

C

HARCOAL

F

ILTER

K

IT

(

NOT SHOWN

)

Absorbs airborne odors caused by cigarette, pipe, or cigar smoke and odors caused by mold, mildew, etc. Filters are made of polyester fibers coated with activated charcoal and are individually wrapped. These permanent filters can be washed or cleaned and reused. Call your Amana ® brand PTAC salesperson for details.

H

YDRONIC

H

EAT

K

IT

Add-on kits fi t all units allowing the addition of hy dron ic water or hydronic steam heat to cool ing and heating units.

The kits feature left- or right-hand pip ing. Unit re tains com plete ser vice ac cess with a kit installed. Unit must be connected to and operated by a wall thermostat.

SBEC10A

CDP302

CDP402

10 Pack

230/208V

265V

KL03B Security Key Lock

FK10A Filters (10-pack) - A Series

FK10B Filters (10-pack) - B Series

CFK10A

CFK10B

HWK03

HVK03

Charcoal Filters - A Series

(10-pack)

Charcoal Filters - B Series

(10-pack)

Hydronic Water Kit

Hydronic Steam Kit

5-1/2"

3-1/4"

1-7/8"

Hydronic Heat Kit-Top View

PTAC UNIT WALL SLEEVE

1-7/8"

3-1/4"

Hydronic Heat Kit-Side View

3"

+1/8"

-0"

Top of Wall Sleeve

4-1/8"

Hydronic Front

15/32"

2 places

Rated Watts

Full Load Amps

(incl. fan)

Min. Ampacity

Fuse Size

Model Nominal BTUs 230V 208V 265V

All 1,500 1,200 1,500

7K & 9K 6.9

6.2

6.1

12K & 15K

7K & 9K

12K & 15K

All

7.1

8.6

8.8

15

6.4

8.6

8.8

15

6.3

7.5

7.7

15

Hydronic Heat Kit-Right View

Hot Water Inlet / Outlet Connections Steam/Water

Coil Position

16-3/4"

8-1/4"

Hot Water Inlet / Outlet Connections

20-3/16"

2-1/8"

2-3/4"

2 places

10-13/16"

53"

Hydronic Air

Discharge

Unit Controls

Compartment

Toe Plate

0" - 3.0" Long

Hydronic Air

Inlet

Bottom of Wall Sleeve

6 www.amana-ptac.com

SS-DPTAC

S

PECIFICATION

S

HEET

PTAC A

CCESSORIES

(

CONT

.)

H

YDRONIC

V

ALVES

(

NOT SHOWN

)

Water and steam valves are available for use with the

HWK03 (water) and HVK03 (steam) heat kits. (See

Ar chi tects and Engineers Manual for specifi cations.)

VS2WNCA* Two-Way / 24-V / NC / Steam

VS2WNOA* Two-Way / 24-V / NO / Steam

VW2WNCA* Two-Way / 24-V / NC / End Switch

VW2WNOA* Two-Way / 24-V / NO / End Switch

VW3WNC2B* Three-Way / 24-V / NC / NO / End Switch

* Pop-top Actuator

H

YDRONIC

T

RANSFORMER

R

ELAY

K

IT

(

NOT SHOWN

)

Add-on kit that allows fi eld conversion of a standard

PTC unit to a hydronic unit.

HTK3A

HTK4A

230/208V

265V

Pull-out Easy Access Filter

Maintaining the unit’s ef fi cien cy while saving time and money is easy. The fi lter is easily accessed for cleaning or replacement without removing the unit front.

SS-DPTAC

Step 1: Open the intake grille louver. Step 2: Pull the fi lter up and out.

www.amana-ptac.com

7

S

PECIFICATION

S

HEET

P

RODUCT

S

PECIFICATIONS

PTC M

ODELS

— C

OOLING

/E

LECTRIC

H

EAT

Model 1, 7, 9, 10, 12

Voltage 1, 3, 11

Capacity

(BTU/h)

PTC073B**APTC074B**APTC093B**AM PTC094B**AM PTC123B**AM PTC124B**AM PTC153B**AM PTC154B**AM

230/208 265 230/208 265 230/208 265 230/208 265

M Models M= 7,100/6,900 M = 7,100 9,100/8,900

N Models N= 7,400/7,300 N = 7,300 N/A

9,100

N/A

12,000/11,900

N/A

12,000

N/A

14,000/13,900

N/A

14,000

N/A

Amps 12

Watts 12

EER

2.8/3.0

610/595

2.3

610

M Models M= 11.6/11.6

M = 11.6

N Models N= 12.4/12.8

N = 12.4

3.7/3.8

790/775

11.5

N/A

3.0

790

11.5

N/A

4.6/5.0

1,110/1,100

10.8

N/A

4.3

1,130

10.8

N/A

6.3/6.9

1,470/1,450

9.5

N/A

5.9

1,470

9.5

N/A

Unit without Electric Heater

Min. Circuit Amps 2, 4, 12 4.0

CFM

(Cool/Wet Coil)

High

Low

245/240

220/205

High

CFM (Dry Coil)

Low

Ventilated Air, CFM

(Fan Only)*

Ventilated Air, CFM

(Compressor & Fan)*

Dehumidifi cation

(Pints/Hr.)

Net Weight (lbs.)

Shipping Weight (lbs.)

265/260

230/215

65*

65*

1.6

90

105

3.6

245

220

265

230

65*

65*

1.6

90

105

5.1

245/240

220/205

265/260

230/215

65*

65*

2.6

95

110

4.4

245

220

265

230

65*

65*

2.6

95

110

6.4

325/315

250/229

345/335

265/235

70*

70*

3.5

105

120

5.7

325

250

345

265

70*

70*

3.5

105

120

8.8

325/315

250/220

345/335

265/235

70*

70*

4.4

110

125

7.7

325

250

345

265

70*

70*

4.4

110

125

- Denotes M or N models

* Approximately 95 CFM with optional power vent kit. Actual vent CFM performance will vary due to application and installation conditions.

6–

7–

8–

Notes:

1– All 265-volt models must use an Amana ® brand sub-base (PTSB4**E) or an Amana ® brand hard-wire kit (PTPWHWK4).

2–

3–

Minimum Circuit Ampacity (MCA) ratings conform to the Na tion al Electric Code; however, local codes should apply.

Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.

Minimum voltage on 265-volt models is 238.5 volts; maximum is 291.5 volts.

4–

5–

Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridgestyle time-delay fuses (included and factory-installed on all Amana ® brand 265-volt chassis). See heater performance for total MCA.

Heating capacity and effi ciency based on unit operation without condensate pump; unit automatically switches to electric heat at approximately 24°F outdoor ambient.

Total watts for 12,000 and 15,000 BTU/h models; subtract 70 watts for PT07/09*B**A*

Specify two-digit heater kW size to complete model number.

Total amps for 12,000 and 15,000 BTU/h models; subtract 0.2 amps for PT07/09*B*A*.

9–

10–

11–

R-22 refrigerant used in all systems.

All units meet or exceed ASHRAE 90.1 standards.

All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.

12– Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation refers to compressor only.

8 www.amana-ptac.com

SS-DPTAC

S

PECIFICATION

S

HEET

P

RODUCT

S

PECIFICATIONS

(

CONT

.)

PTC

AND

PTH M

ODELS

— E

LECTRIC

H

EAT

P

ERFORMANCE

(Primary Heating for PTC Models; Auxiliary Heating for PTH Models; See below for Power Cord Confi guration)

Voltage

Electric

Heater

Size (kW)

230/208V 2.5/2.0

230/208V 3.5/2.9

230/208V 5.0/4.1

265V 2.5

265V

265V

3.7

5.0

No. of

Stages

Nominal Heating (BTU/h)

@ 230V @ 208V @ 265V

1*

1

1

1

1

1*

8,500

12,000

17,100

- -

- -

- -

6,800

9,900

14,000

- -

- -

- -

- -

- -

- -

8,500

12,600

17,100

Total

Watts 6

Total

Amps 8

2,650/2,140 11.5/10.2

3,650/3,040 15.8/14.5

5,150/4,240 22.3/20.3

2,650 10.0

3,850

5,150

14.6

19.5

Minimum

Circuit

Ampacity 2

14.2

19.6

27.7

12.4

18.1

24.2

MOD

15

20

30

15

20

25

4

(amps)

Power

Cord

6 - 15 P

6 - 20 P

6 - 30 P

7 - 20 P

7 - 20 P

7 - 30 P

* PTH/PTC09*B50*G/K has the same airfl ow as a PTC/PTH12*B***G (not available on 7,000 BTU/h models).

Notes:

1– All 265-volt models must use an Amana ® brand sub-base (PTSB4**E) or an Amana ® brand hard-wire kit (PTPWHWK4).

2–

3–

Minimum branch circuit ampacity ratings conform to the Na tion al Electric Code; however, local codes should apply.

Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.

Minimum voltage on 265-volt models is 238.5 volts; maximum is 291.5 volts.

4–

5–

6–

7–

8–

Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridgestyle time-delay fuses (included and factory-installed on all Amana ® brand 265-volt chassis).

Heating capacity and effi ciency based on unit operation without condensate pump; unit automatically switches to electric heat at approximately 24°F outdoor ambient.

Total watts for 12,000 and 15,000 BTU/h models; subtract 70 watts for PT07/09*B**A*

Specify two-digit heater kW size to complete model number.

Total amps for 12,000 and 15,000 BTU/h models; subtract 0.2 amps for PT07/09*B*A*.

9–

10–

11–

R-22 refrigerant used in all systems.

All units meet or exceed ASHRAE 90.1 standards.

All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.

P

OWER

C

ORD

C

ONFIGURATION

Power Cord Plugs

250V Rating Power Cord Plugs with LCDI Device

NEMA 6 Confi guration

Power Receptacle Confi guration

G NEMA6-15R; 250V receptacle, used on 230/208V units

G NEMA6-20R; 250V receptacle, used on 230/208V units

G

NEMA6-30R; 250V receptacle, used on 230/208V units

15 amp

20 amp

277V Rating Power Cord Plugs

NEMA 7 Confi guration

30 amp

20 amp

30 amp

W

G

NEMA7-20R; 277V receptacle, used on 265V units

G

NEMA7-30R; 277V receptacle, used on 265V units

All units come with factory-installed power cords.

All units less than 250 volts come with LCDI device.

SS-DPTAC www.amana-ptac.com

9

S

PECIFICATION

S

HEET

P

RODUCT

S

PECIFICATIONS

(

CONT

.)

PTH M

ODELS

— C

OOLING

/H

EAT

P

UMP

/E

LECTRIC

H

EAT

Model 1, 7, 9, 10, 12 PTH073B**APTH074B**A- PTH093B**AM PTH094B**AM PTH123B**AM PTH124B**AM PTH153B**AM PTH154B**AM

Voltage

(BTU/h)

Amps

Watts

12

12

1, 3, 11

Capacity

M Models

N Models

230/208

M=7,000/6,800

N=7,400/7,300

2.8/3.0

605/585

265

M=7,000

N=7,300

2.3

605

230/208

9,100/

8,900

N/A

3.5/3.8

790/775

265

9,100

N/A

3.0

790

230/208

12,000/

11,800

N/A

4.6/5.0

1,110/

1,090

10.8

N/A

265

12,000

N/A

4.3

1,110

230/208

14,000/

13,900

N/A

6.3/6.9

1,505/

1,495

9.3

N/A

265

14,000

N/A

5.9

1,505

EER

M Models

N Models

Units without Electric Heater

M=11.6/11.6

N=12.4/12.8

MCA 2, 4, 12

CFM

(Cool/Wet Coil)

High

Low

4.0

245/240

220/205

265/260 High

CFM (Dry Coil)

Low

Ventilated Air, CFM

(Fan Only)*

Ventilated Air, CFM

(Compressor and Fan)*

Dehumidifi cation

(Pints/Hr.)

Net Weight (lbs.)

Shipping Weight (lbs.)

230/215

65*

65*

1.6

95

110

M=11.6

N=12.4

3.6

245

220

265

230

65*

65*

1.6

95

110

11.5

N/A

5.1

245/240

220/205

265/260

230/215

65*

65*

2.6

100

115

11.5

N/A

4.4

245

220

265

230

65*

65*

2.6

100

115

6.4

325/315

250/229

345/335

265/235

70*

70*

3.5

110

125

10.8

N/A

5.7

325

250

345

265

70*

70*

3.5

110

125

8.8

325/315

250/220

345/335

265/235

70*

70*

4.4

115

130

9.3

N/A

7.7

325

250

345

265

70*

70*

4.4

115

130

- Denotes M or N models

* Approximately 95 CFM with optional power vent kit; actual vent CFM performance will vary due to application and installation conditions.

** EER = Energy Effi ciency Rating per Air Conditioning & Refrigeration Institute (ARI) and Canadian Standards Association (CSA) EEV Test Pro ce dures.

6–

7–

8–

Notes:

1– All 265-volt models must use an Amana ® brand sub-base (PTSB4**E) or an Amana ® brand hard-wire kit (PTPWHWK4).

2–

3–

Minimum Circuit Ampacity (MCA) ratings conform to the Na tion al Electric Code; however, local codes should apply.

Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.

Minimum voltage on 265-volt models is 238.5 volts; maximum is 291.5 volts.

4–

5–

Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridgestyle time-delay fuses (included and factory-installed on all Amana ® brand 265-volt chassis). See heater performance for total MCA.

Heating capacity and effi ciency based on unit operation without condensate pump; unit automatically switches to electric heat at approximately 24°F outdoor ambient.

Total watts for 12,000 and 15,000 BTU/h models; subtract 70 watts for PT07/09*B**A*

Specify two-digit heater kW size to complete model number.

Total amps for 12,000 and 15,000 BTU/h models; subtract 0.2 amps for PT07/09*B*A*.

9–

10–

11–

R-22 refrigerant used in all systems.

All units meet or exceed ASHRAE 90.1 standards.

All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.

12– Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation refers to compressor only.

10 www.amana-ptac.com

SS-DPTAC

S

PECIFICATION

S

HEET

P

RODUCT

S

PECIFICATIONS

(

CONT

.)

PTH M

ODELS

— R

EVERSE

-C

YCLE

H

EATING

P

ERFORMANCE

Heating

Capacity 1

PTH073B**A- PTH074B**A- PTH093B**AM PTH094B**AM PTH123B**AM PTH124B**AM PTH153B**AM PTH154B**AM

M Models M=6,200/6,000 M = 6,200 8,200/8,000

BTU/h 5

8,200 10,800/10,600 10,800 13,300/13,200 13,300

N Models N=6,400/6,300 N = 6,200 N/A N/A N/A N/A N/A N/A

Amps

12

Watts

12

2.6/3.0

550/530

2.2

550

3.2/3.6

750/730

2.6

750

4.5/5.1

1,020/1,000

3.9

1,020

5.7/6.3

1,340/1,330

5.4

1,340

COP 5

M Models M= 3.3/3.3 M = 3.3

N Models N= 3.5/3.6

N = 3.5

CFM (Dry) 235/230

62 °F 7,200/7,000

235

7,200

3.2

N/A

235/230

9,800/9,600

3.2

N/A

230

9,800

3.1

N/A

310/290

13,000/12,800

3.1

N/A

310

13,000

2.9

N/A

345/335

15,800/15,700

2.9

N/A

345

15,800

Heating

(BTU/h)

Outdoor

Ambient

Rating

Point

5

57 °F 6,900/6,700

52 °F 6,500/6,300

47 °F 6,200/6,000

COP* 3.3/3.3

42 °F 5,900/5,700

37 °F 5,600/5,400

32 °F 5,300/5,100

27 °F 5,000/4,800

6,900

6,500

6,200

3.3

5,900

5,500

5,200

5,000

9,300/9,100

8,700/8,500

8,200/8,000

3.2/3.2

7,700/7,500

7,200/7,000

6,700/6,500

6,200/6,000

9,300

8,700

8,200

3.2

7,700

7,200

6,700

6,200

12,300/12,100

11,600/11,400

10,800/10,600

3.1/3.1

10,100/9,900

9,400/9,200

8,600/8,400

7,900/7,700

12,300

11,600

10,800

3.1

10,100

9,400

8,600

7,900

15,000/14,900

14,200/14,100

13,300/13,200

2.9/2.9

12,500/12,400

11,700/11,600

10,800/10,700

10,000/9,900

15,000

14,200

13,300

2.9

12,500

11,700

10,800

10,000

Watts

Outdoor

Ambient

24 °F 4,800/4,600

62 °F 580/560

57 °F

52 °F

575/555

555/535

47 °F

42 °F

37 °F

32 °F

27 °F

24 °F

550/530

540/525

530/515

515/500

505/490

500/485

550

560

545

535

4,800

580

575

555

525

520

5,900/5,700

810/790

800/780

775/755

750/730

730/710

705/685

690/670

660/640

640/620

750

730

705

690

5,900

810

800

775

660

640

7,500/7,300

1,120/1,100

1,090/1,075

1,060/1,045

1,020/1,005

985/970

950/935

900/885

855/840

830/815

7,500

1,120

1,090

1,060

1,020

985

950

900

855

830

9,500/9,400

1,465/1,455

1,440/1,430

1,405/1,395

1,340/1,330

1,325/1,315

1,285/1,275

1,240/1,230

1,190/1,180

1,180/1,170

9,500

1,465

1,440

1,405

1,340

1,325

1,285

1,240

1,190

1,180

- Denotes M or N models

See Page 10 for Notes and Auxiliary Electric Heater Performance.

COP = Coeffi ciency of Performance; per ARI Test Procedures, units are rated for capacities and effi ciencies.

SS-DPTAC www.amana-ptac.com

11

S

PECIFICATION

S

HEET

C

ONTRACT

B

ID

S

PECIFICATIONS

Ratings

Each unit must meet the following specifi cations:

ARI rating of _________BTU/h cool ing (and _________

BTU/h reverse cycle heating with a COP of _________ at 47° F O.D.)

Electric resistance heat of _________ BTU/h. Total

Amp draw must be of _________ and _________ Watts at _________ volts.

The unit must remove a minimum of _________ pints of mois ture per hour when operated at rating con di tions.

The EER must be a minimum of _________ EER.

Unit Chassis

Each unit must be of slide-out design shipped with room cabinet front-installed. Unit chassis must have the ability to be installed with 0 clearance from fi nished fl oor. An electrical power cord must be included with chassis and installed by the manufacturer to assure proper NEMA 6 or

7 confi guration and UL-approved length. Units less than

250 volts must also have a LCDI power cord. Unit must be tested for conformance to ASTME water infi ltration specifi cation ASTME 331-86, which ensures no water infi ltration when tested at 8" rain per hour at 63 mph wind for 15 minutes.

Room Cabinet

The monochromatic front of the room cabinet must be able to be fi eld-secured to chassis to inhibit tampering. Filter must be accessible without removing room front. Cabinet depth must not exceed 7⅜” to minimize unit’s impact on room space.

Coils

Unit coils must have rifl ed copper tubing expanded into rippled-edge louvered aluminum fi ns. Exterior coil must be of a two-row bent coil design with removable shroud top to allow easy-access for cleaning of the exterior coil.

Heat Pumps

Each unit must include a change-over thermistor that sens es an outside ambient switch-over temperature as low as 24°F, lock-open refrigerant reversing valve dur ing heat pump op er a tion, temperature-activated de frost drain, and au to mat ic emergency heat operation to over ride the heat pump’s change-over thermostat and bring on elec tric re sis tance heat ers in the event of a sealed system failure. Unit must not operate com pres sor and electric heaters si mul ta neous ly.

Com pres sor

The compressor must be hermetically sealed, internally isolated, rotary-type, and permanently mounted on rubber isolators. No removal or adjustment of compressor hold-down bolts is to be required during installation.

Warranty

The warranty is for Full One Year on the entire unit;

Full Second through Fifth Year on the entire sealed re frig er ant system com po nents; Limited Second through

Fifth Year on functional parts only.

12

Unit Digital Controls

Unit control must be completely wired and accessible from the top of the chassis. Controls shall be an LED touch-pad design with six large, easy-to-read and use buttons: Heat – Cool – Off – Fan – Temp+ (plus) – Temp-

(minus) and two red seven-segment LED temperature displays. Unit shall have a green status LED to advise owner of dirty fi lter, dirty coil, or operational diagnostic messages. Unit shall have one-button activation via membrane touch-pad. Unit control board shall have an 18-pin low-voltage connector to allow for easy connection to remote wired devices. Unit shall have two serial-port connectors for easy connection to wired or future wireless EMS (Energy Management Systems).

Unit must have the ability to easily confi gure ownerselectable and programmable functions:

• Fan-cycle operation

• Electronic temperature limiting for cooling

• Electronic temperature limiting for heating

• Enhanced dehumidifi cation cooling operation

• Temperature set-back when inactive

• Un-rented temperature set-back

• Load-shedding operation

• Front-desk on-off or temperature set-back

Unit must have the ability to connect to approved remote devices:

• Wireless or wired thermostat

• Wireless or wired door switch

• Wireless or wired room occupancy sensor

• Wireless or wired room-to-room transfer fan

• Front Desk Control

• RF wireless communications devices

Unit must be able to acquire and display operational temperature data from up to six installed thermistors to include:

• IAT—Indoor air temperature (black)

• ICT—Indoor coil temperature (red )

• IDT—Indoor discharge temperature (yellow)

• OCT—Outdoor coil temperature (blue) (heat pumps)

• Green—Miscellaneous temperature (ex. Outdoor ambient) (optional)

• Orange—Miscellaneous thermistor or analog device

(optional)

Evaporator/Condenser Fans

Direct drive with a permanent, split-capacitor, twospeed motor. Condensate must be directed onto the back and sides of the bent coil to aid in evaporation and removal.

Air Discharge

Must be a sloped surface so that obstructions cannot be placed on the unit. Discharge conditioned air can be directed into the room at an angle of 15 or 40 degrees from the vertical position. The discharge grille must be of polycarbonate material to resist bend ing, cracking, rust ing and corrosion.

www.amana-ptac.com

SS-DPTAC

S

PECIFICATION

S

HEET

N

EW INSTALLATIONS TYPICALLY REQUIRE A MINIMUM OF

WS900D

WALL SLEEVE

AND AN OUTDOOR GRILLE

.

Wall Sleeves (WS900D)

The wall sleeve must be industry-accepted dimensions:

14⅛” depth x 42” width x 16 1 / 16 ” height and con struct ed of G90 HDG galvanized steel with a baked corrosioninhibiting urethane primer and baked-polyester topcoat enamel. Sleeve must be insulated and shipped with a weather resistant rear closure panel installed.

Outdoor Grilles

Outdoor grille must be architecturally extruded, louvered aluminum (AGK01*B), one-piece polymerblend injection molded louver (PGK01*B) or standard stamped aluminum (SGK**B). All other grilles must be submitted to the PTAC manufacturer for feasibility, airflow characteristics and compliance with UL regulations, where necessary.

T

HE OPTIONAL ACCESSORIES LISTED BELOW PERFORM SPECIFIC FUNCTIONS REQUIRED

IN SOME INSTALLATIONS

.

Condensate Drain Kit (DK900D)

Attaches to the bottom of the wall sleeve for di rec tion alcon trolled internal or external dis pos al of condensate, defrost or rain water.

Duct Kits (MDK02B, EDK02B, TDK02)

Three kits must be supplied to provide ducted, con di tioned air into a second room: a main duct kit, an ex ten sion duct kit and a terminal duct kit.

Sub-base Kit (PTSB***E)

Necessary for UL listing requirements for 265V units

(Hard Wire Kit may be substituted for Sub-base kit).

Op tion al for 230/208V units. Must be pre-wired to facilitate fi eld-electrical con nec tions and include a

NEMA 6 or 7 con fi g u ra tion electrical re cep ta cle. It must have 2 leveling screws for sleeve support and ac cu rate unit lev el ing during installation. Lo ca tions for fi eld in stal la tion of physical disconnect switches, cartridgestyle fuse hold ers and circuit break ers must be pro vid ed.

Side-skirts must be provided with sub-bases. (PTSB000E

Non-Elec tri cal Sub-base available.)

Hydronic Heat Kit

Is required for heating functions instead of elec tric re sis tance heaters. Unit must retain complete service access with the kit installed. Proper water or steam valves must be used.

Condensate Removal Pump (Heat Pumps only)

Must be installed to assist in removing the condensate de vel oped by the heat pump operation and transfer it to the indoor coil to dissipate into the room, adding hu mid i ty to the room.

Power Vent & Damper

Must be provided to maximize ventilation air intake to up to approximately 95 CFM. Power vent must be off and damper door closed when unit fan is de-energized.

Circuit Breaker Kit

Must be installed in sub-base to provide overcurrent pro tec tion for proper 230/208V amperage. Can also be used as a physical disconnect where local codes permit for 230/208 voltage.

Fuse Holder (included in 265V chassis)

Must be installed either in the unit or the sub-base and must match the electrical re quire ments of the chas sis.

Hard Wire Kit

Must be used to permanently wire chassis for hard wire purposes. (For 265V units, Hard Wire Kit may be sub sti tut ed with Sub-base Kit.)

Security Key Locks (KL03B)

Must be installed to prevent tampering of the unit con trols. Unit room cabinet must also be secured to the chassis with fi eld supplied screws. UL-ap proved for institutional use only.

Disconnect Switch

Power disconnect switch must be installed in sub-base for use as a physical disconnect, where required by local codes.

Charcoal Filter Kit -- Optional (CFK10B)

Amana® brand Activated Charcoal fi lters absorb odors caused by cigarette, pipe or cigar smoke and airborne odors caused by mold, mildew, etc. These replacement fi lters are polyester fi bers coated with activated charcoal. Each fi lter is in di vid u al ly wrapped to assure maximum ab sorp tion and durability when installed. (10 fi lters per kit.)

Thermostats

A manufacturer-approved manual, auto changeover or pro gram ma ble traditional-wired ther mo stat must be in stalled to pro vide full remote op er a tion of the chassis.

A Remote Es cutch eon Kit must be used to indicate remote operation.

SS-DPTAC www.amana-ptac.com

13

S

PECIFICATION

S

HEET

I

NSTALLATION

:

U

NIT WITH

A

CCESSORY

W

ALL

S

LEEVE AND

S

UB

-

BASE

A

CCESSORY

T

OP

V

IEW

1"

6 - 1 / 8"

42"

40"

24 - 5 / 16"

Location of external drain holes

on bottom flange of Wall Sleeve

9 - 9 / 16"

Air

Flow

Air

Flow

Air

Flow

1"

Air Discharge Grille

3 "

7/8"

STAMPED GRILLE

1-3/8"

ARCH GRILLE

R

IGHT

V

IEW

Control

Door

3" Clearance to side walls

AIR DISCHARGE GRILLE IS

REVERSIBLE TO PROVIDE EITHER

15° OR 40° DISCHARGE ANGLE

21-1/2"

7-3/8"

14-1/8"

WALL SLEEVE

15°

40°

16-1/16"

HINGED

CONTROL

DOOR

OPTIONAL

SUBBASE 4"

13/16"

11-3/8"

2-3/4"

1 - 3 /8"

13/16"

1/2" O.D.

COPPER

DRAIN TUBE

F

RONT

V

IEW

58” LCDI CORD SET

230V/208V UNIT*

LEFT

2-5/8"

14

42"

R I GHT

16-1/16"

3-1/4"

MIN

2"

MAX

1" AND 3/4" CONCENTRIC KNOCKOUTS BACK

& BOTTOM OF SUBBASE (ELECTRICAL ONLY)

Power cord usable length www.amana-ptac.com

SS-DPTAC

F

RAMING FOR

A

CCESSORY

W

ALL

S

LEEVE

(WS900D)

S

PECIFICATION

S

HEET

Alternative

Fastening Method

(Field Supplied)

Wood Screw

Toggle Bolt

Expansion

Anchor Bolt

FASTENING WALL SLEEVE

When installed in an opening, the

Wall Sleeve must be hor i zon tal ly level

(side-to-side) and pitched ¼ bubble to the outside. (NOTE: To ensure unit’s maximum effi ciency, DO NOT over- or under-pitch.)

Mounting

Holes

(Drilled by

Installer)

Plastic

Anchor

Screws

JACK STUDS

HEADER - 4" x 4" OR

DOUBLE 2"x 4" ON EDGE

Wall Sleeve Opening Height should be squared with

Wall Sleeve Opening Width

MAIN STUD

H = 16¼"

W = 42¼"

16 1/4"

MIN

42 1/4"

JACK STUD

CRIPPLE

FINISHED FLOOR

SUB-FLOOR

ADJUST FRAMING TO

SECURE THIS DIMENSION

Wall Sleeve must extend a minimum of ¼” beyond outside wall to allow for proper caulking.

Installation Notes

1.

If Sub-base (PTSB***E) is installed, allow minimum 3¼” height clearance and maximum 5” height clearance between wall sleeve and fl oor; allow minimum 2¾” protrusion from a fi nished wall. See Note 4 if using hydronic units.

2.

3.

4.

5.

Drain Kit (DK900D) shipped separately. Can be mounted either right side, left side, or bottom of sleeve. If mounted to bottom of sleeve, allow 2” height clearance from fl oor to bottom of sleeve.

For UL approval, 265V units must use Amana ® brand Sub-base (PTSB***E) or Amana ® brand Hard-Wire Kit (PTPWHWK4).

Overcurrent protection on 265V units must be by cartridge-style time-delay fuses, which are included and factory-installed on the Amana ® brand 265V chassis.

If Hydronic Kit (HWK03 or HVK03) is installed, Wall Sleeve must extend exactly 3" into the room from the fi nished interior wall. If using the Amana ® brand Sub-base (PTSB***E), only the minimum 3¼” height clearance between wall sleeve and fl oor is permissible. Unit must also be operated with a remote-mounted thermostat.

If Duct Kit (MDK02B) is installed, allow a minimum of 2⅜” into the room from the fi nished interior wall.

SS-DPTAC www.amana-ptac.com

15

S

PECIFICATION

S

HEET

N

OMENCLATURE

P T C 0 9 3 A 3 5 A M

Package

Terminal

Major Design

Series

Model Type

C = Cooler

H = Heat Pump

Nominal Cooling Capacity

07 = 7,000 BTU/h

09 = 9,000 BTU/h

12 = 12,000 BTU/h

15 = 15,000 BTU/h

Electrical

2 115v, 60 Hz

3 230/208v, 60 Hz, 1 Ph

4 265v, 60 Hz, 1 PH

5 240/220v, 50 Hz, 1 Ph

Heater Sizes

00 = 0.0 kW

15 = 1.5 kW

25 = 2.5 kW

35 = 3.5 kW (230/208v)

3.7 kW (265v)

50 = 5.0 kW

Special Feature Code

A Standard Model

B Power Vent

C Seacoast Model

D Condensate Disposal Pump

F Hydronic w/Power Vent & Door

G Hydronic w/Power Door

H Hydronic w/Manual Door

J Power Door

K Condensate Pump w/ Power Vent

L Condensate Pump w/ Power Door

Y 230/208-volt Fuse Holder

Engineering Design Series

M

N

DigiSmart Unit

(230/208 or 265v only)

Premium DigiSmart w/ LED (230/208 or 265v only)

16

ARI (Air Conditioning & Refrigeration

Institute) Standards 310/380

UL (Un der writ ers Laboratories)

USA and Canada

CSA (Canadian Standards As so ci a tion)

EEV Cer ti fi ca tion Pro grams

Amana ® is a trademark of Maytag Corporation and used under license to Goodman Company, L.P. All rights reserved.

Our continuing commitment to quality products may mean a change in specifi cations without notice.

Copyright © 2006 • Goodman Company, L.P. • Houston, Texas • Printed in the USA.