Zehnder Rittling | FV-08 | Rittling Fanvector Installation, Operation and

Rittling Fanvector Installation, Operation and
Rittling
Fanvector
Installation, Operation and Maintenance
Heating
Cooling
Fresh Air
Clean Air
i
Arrangements1
General information
1
Dimensions and data
2
Installation6
Wiring diagram
9
Operation10
Maintenance11
Service parts
11
Warranty12
IMPORTANT: Submittal documentation, specific to
each project, supersedes the general guidelines
contained within this manual.
Arrangements
Arrangements
Unlike natural convective
products, the Rittling Fanvector
has an increased air capacity due
to the addition of a tangential
blower that pushes a higher
volume of air across the heat
transfer surface. The benefit of
this technology is that less linear
footage of heating products is
required.
The variety of mounting styles
and the slim line design provide
flexibility to the installing
contractor as well as options for
an aesthetically pleasing solution
for the architect.
Ceiling
Wall
Free standing floor
Floor
Recessed floor
General data
Table 1: General data
Size
FV-04
FV-06
FV-08
19,600
General
8,900
13,900
Flow rate (GPM)*
Heating capacity (BTUH)*
0.9
1.4
2.0
Operating pressure (psi)
300
300
300
120V/60Hz/1 Ph
120V/60Hz/1 Ph
120V/60Hz/1 Ph
2
3
4
Shaded pole
Shaded pole
Shaded pole
1/100
Electrical
Supply voltage
Number of motor/blowers
Fan motor type
Motor HP (per motor)
1/100
1/100
Motor FLA (A per motor)
0.9
0.9
0.9
Minimum circuit ampacity (A)
2.3
3.4
4.5
15
15
15
(3) - 2.6" x 11.8"
Tangential
(4) - 2.6" x 11.8"
Tangential
Maximum fuse size (A)
Blower
Blower wheel size (D x W) (in.)
Air flow (CFM)
RPM
(2) - 2.6" x 11.8"
Tangential
160
260
330
0-1,500
0-1,500
0-1,500
4-1/2
Cabinet
Depth (in.)
4-1/2
4-1/2
Height (in.)
8
8
8
Width (in.)
47-15/16
71-15/16
89-7/16
22
44
66
Weight (lbs.)
Recessed floor
FV-04-T
FV-06-T
FV-08-T
Depth (in.)
Model
12-1/8
12-1/8
12-1/8
Height (in.)
6
6
6
Width (in.)
46
64
82
Weight (lbs.)
20
40
60
* 65 °F EAT, 200 °F EWT, 180 °F LWT, cabinet enclosure, same end connection
1
Dimensions and data
Model FV-04
16-gauge powder
coated finish enclosure
4-1/2"
4-25/32"
Iso view
Electrical access
door with 1/4 turn
fastener 5" x 5"
8"
Louvered
outlet
Side view
Less end panel
Louvered inlet
2-7/8"
R 3/16"
1-3/8"
R 3/8"
Back view
Mounting location
9-17/32"
33-11/16"
2-1/2"
Front view
7-1/2"
With front panel
47-15/16"
7/8"
Fan speed switch
Front view
Less front panel
2-5/16"
1-31/32"
44"
Bottom view
1/2" copper
connection
2-25/32"
Bottom view
Alternate view, same end connection
2
Dimensions and data
Model FV-06
16-gauge powder
coated finish enclosure
Iso view
4-1/2"
8"
4-25/32"
Electrical access
door with 1/4 turn
fastener 5" x 5"
Side view
Louvered
outlet
Louvered inlet
Less end panel
2-7/8"
R 3/16"
1-3/8"
R 3/8"
Back view
Mounting location
49-11/16"
11-1/32"
2-1/2"
Front view
7-1/2"
With front panel
71-15/16"
7/8"
Fan speed switch
Front view
Less front panel
2-5/16"
3-23/32"
64-1/2"
Bottom view
1/2" copper
connection
4-15/32"
Bottom view
Alternate view, same end connection
Dimensions and data
3
Dimensions and data
Model FV-08
16-gauge powder
coated finish enclosure
Iso view
4-1/2"
4-25/32"
Electrical access
door with 1/4 turn
fastener 5" x 5"
8"
1/4-20 PPH
fastener
Side view
Less end panel
Louvered
outlet
Louvered inlet
2-7/8"
R 3/16"
1-3/8"
R 3/8"
Back view
Mounting location
67-11/16"
11-1/32"
2-1/2"
Front view
7-1/2"
With front panel
89-7/16"
7/8"
Fan speed switch
Front view
Less front panel
2-5/16"
4-7/32"
81-1/2"
Bottom view
1/2" copper
connection
4-1/2"
4
Bottom view
Alternate view, same end connection
Dimensions and data
Recessed floor
Iso view
Recessed floor
box length
# of
blowers
FV-04-T
46"
2
FV-06-T
64"
3
FV-08-T
82"
4
Model
Recessed floor box
Length is determined by number of
blowers (see chart)
Blower removable
for maintenance
Debris screen to be
placed over blowers
Top view
(Shown less grille)
12.140
Heavy-duty grille (by others)
1.125"
5.688
5.500
Trench vector coil
Adjustable leveling legs (6)
(2" range of adjustability)
4.368
Sectional view
Notes:
 Left hand electrical control shown. Right hand
electrical control is a mirror image.
 The grille should have a minimum of 60% free
surface area to maintain catalog airflow
and capacity.
Dimensions and data
5
Installation
Inspection
Upon receipt of the equipment, carefully check the shipment against
the bill of lading. Make sure all units have been received. Inspect the
packaging of each unit, and inspect each unit for damage. Ensure that
the carrier makes proper notation of any shortages or damage on all
copies of the freight bill and completes a common carrier inspection
report. Concealed damage not discovered during unloading must be
reported to the carrier within 15 days of receipt of shipment. If not
filed within 15 days, the freight company can deny the claim without
recourse.
Storage
Equipment should be stored in its original packaging in a clean,
dry area.
Unit protection
Cover units on the job site with either the original packaging or an
equivalent protective covering. Cap the open ends of pipes stored on
the job site. In areas where painting, plastering, and/or spraying has not
been completed, all due precautions must be taken to avoid physical
damage to the units and contamination by foreign material. Physical
damage and contamination may prevent proper start-up and may result
in costly equipment clean-up.
Examine all pipes, fittings, and valves before installing any of the
system components. Remove any dirt or debris found in or on these
components.
Pre-installation
Before unit start-up, read all manuals and become familiar with the unit
and its operation. Thoroughly check the system before operation.
It is the responsibility of the purchaser to file all
necessary claims with the carrier. Notify your
equipment supplier of all damage within fifteen
(15) days of shipment.
6
Installation
Preparation
■■
Verify that electrical power is disconnected prior to installation and
service.
■■
Ensure that field plumbing and electrical meets applicable national
and local codes and requirements.
■■
The Rittling Fanvector cabinet has keyhole slots included in the
back panel for use in mounting. Proper wall supports and screws to
support the Rittling Fanvector weight should be used when mounting.
The table below shows model weights for each unit size.
Model
Weight (lbs.)
FV-04
22
FV-06
44
FV-08
66
■■
Access to the keyhole slots may require removal of the end panels
and the front cabinet panel. Check if keyhole slots are accessible
through access doors or end panels, and that access is not
obstructed by field barriers.
ŠŠ The end caps are attached by a tongue and groove joint and are
removed by simply pulling them away from the ends of the unit.
ŠŠ The front panel is disassembled by removing the screws in the
front panel and lifting the panel vertically.
■■
Prior to fastening the Rittling Fanvector in place, verify that all wiring
and plumbing is accessible to complete the installation.
■■
Securely fasten unit into place.
Installation
7
Installation
Plumbing
■■
The Rittling Fanvector is supplied with either opposite end, same end
or recessed floor connections.
ŠŠ Opposite end connections have brass headers with a 3/4" FPT
connection. The headers have a 1/4" FPT hole that can be
plugged or fitted with a vent (by others).
ŠŠ Same end connections are supplied with 1/2" straight copper
tubing. Standard 1/2" female copper fittings (sweat) can be used
for connection purposes (by others).
ŠŠ Recessed floor connections are 3/4" straight copper. Standard
1/2" female copper fittings (sweat) can be used for connection
purposes (by others).
■■
Plumbing access openings are cut into the unit cabinet. Openings
can be used as necessary and determined by field plumbing.
■■
Connect inlet and outlet plumbing per building specifications.
■■
All connections should be leak tested prior to electrical connection
and operation.
Electrical
■■
Remove electrical box connection cover to expose unit wiring.
■■
Connect power and thermostat (if used) to unit per the wiring
diagram on page 9.
■■
Replace electrical box connection cover.
If applicable, front panel and end panels should be re-installed at this
time if they were removed for installation purposes.
8
Wiring diagram
White
Black
White
Black
Blower
motor
White
Black
Blower
motor
White
Black
Blower
motor
White
Black
Blower
motor
White
Variable speed control
On/off switch
Black
L1 hot (black)
White
Size
# of Blowers
FV-04
2
FV-06
3
FV-08
4
Field wired
Factory wired 18AWG
L2 neutral (white)
120 VAC
Notes:
 Thermostat shipped loose if wall mounted
 Control valve and changeover switch are
shipped loose
 Complete the wiring in accordance with national
and local codes
 If remote temperature sensor is used, wire to
thermostat tb1, terminals 1 and 2.
Factory wired 16AWG
Wire connection
Factory wire, not connected
Wire termination
Wiring diagram
9
Operation
Initial start-up
■■
Verify that all isolation valves are open and control valves (if any) are
wired.
■■
Verify that all air has been removed from the hot water system and
there is no air trapped in the coil.
■■
Verify that voltage is within an acceptable range and that fuses and
breakers are properly sized.
■■
If unit is controlled by a thermostat, verify that the control system is
calling for heat.
■■
Verify that the unit switch is in “off” position.
■■
Turn on line power to unit. Move unit switch to “on” position.
■■
Adjust blower speed to maximum setting.
■■
Verify that blowers are moving air through the discharge louvers (top)
of the unit.
■■
Adjust blower speed to minimum setting.
■■
Verify that blowers are moving air through the discharge louvers (top)
of the unit.
■■
If unit is controlled by a thermostat, verify that the control system is
working by adjusting temperature setting to turn system on and off.
Continued operation
■■
Set unit switch to “on” position.
■■
If unit is controlled by thermostat, set thermostat to desired control
temperature.
■■
Set fan control to desired speed.
■■
Maintain unit according to the instructions listed in the maintenance
section of this document.
10
Maintenance
Motor blower assembly
■■
The blower motor assembly is assembled with long-life,
maintenance-free bearings. There is no need for lubrication of the
assembly.
■■
Periodic cleaning of the fan and motor can be accomplished best
with a vacuum with a soft brush attachment. Cleaning intervals will
be dependent on operating environment, but is recommended at
lease once a year.
■■
Verify that the power is disconnected prior to cleaning.
Coil
■■
Internal coil maintenance is generally not needed for water systems
that are clean and maintained. If it is known that the water system
contains high levels of dirt or debris, use standard coil cleaning tools
and procedures compatible with copper water lines.
■■
Periodic cleaning of the coil fins can be accomplished best with
a vacuum with a soft brush attachment. Cleaning intervals will be
dependent on operating environment, but is recommended at lease
once a year.
■■
Verify that the power is disconnected prior to cleaning.
Cabinet
■■
Clean with a mild soap and warm water as necessary.
Service parts
Description
FV-04
FV-06
FV-08
Same end
connection coil
11723000005A
11723000006A
11723000007A
Opposite end
connection coil
11723000016A
11723000017A
11723000018A
Motor/blower
assembly (1 pc.)
11723000019A
Fan speed/power
switch assembly
11723000020A
Installation
11
Warranty
Zehnder Rittling guarantees its products to be free from defects in
material and workmanship for a period of two years from date of
shipment from our factory.
Should there be any defects in the good(s), the purchaser should
promptly notify Zehnder Rittlng. Upon receipt of written consent from
Zehnder Rittling, the purchaser shall return the defective good(s) to
the factory for inspection with freight prepaid. If inspection shows the
goods to be defective, Zehnder Rittling will at its discretion repair or
replace the said item(s).
Defects arising from damage due to shipment, improper installation,
negligence or misuse by others are not covered by this warranty.
This warranty is extended only to the original purchaser from
Zehnder Rittling.
12
© Zehnder Rittling August 2014, English, subject to change without notice
Zehnder Rittling · 100 Rittling Boulevard · Buffalo, NY USA 14220
T 716-827-6510 · F 716-827-6523 · sales@zehnder-rittling.com
www.zehnder-rittling.com