COUNTIS E63 Active energy meters 3 x single-phase - Direct 100 A

COUNTIS E63 Active energy meters 3 x single-phase - Direct 100 A
COUNTIS E63
Single-circuit metering,
measurement &
analysis
Active energy meters
3 x single-phase - Direct 100 A
The solution for
> Data centres
> Infrastructure
Strong points
COUNTIS E63
Function
> Compact
> Advanced multimeasurement functions
> Detection of connection errors
Principle diagram
The COUNTIS E63 is a modular active
electrical energy meter which provides
metering for three single-phase loads, with
direct connection of up to 100 A. It directly
displays the total and partial energy and
power (kWh and kW) consumed by each
single-phase load.
Conformity to standards
CO
UN
TIS
E 63
COUNTIS E63
Advantages
Compact
Due to the integration of three single-phase
meters in the same case (7 modules wide),
the COUNTIS E63 provides significant
space-saving.
Advanced multi-measurement functions
Advanced multi-measurement functions are
available via RS485 MODBUS communication:
• Instantaneous currents: I1, I2, I3
• Instantaneous voltages: V1, V2, V3
• Instantaneous power: 3P, 3S
• Instantaneous power factors: 3PF
• Load curves for each of the 3 phases:
Viewing of average positive active power
consumption over a programmable period.
50
Catalogue 2015 - 2016
Detection of connection errors
The product is protected against
phase/neutral inversion and detects wiring
errors. This simplifies the installation and
commissioning, thereby reducing associated
costs, and ensures that the device operates
correctly.
count_205_a_1_x_cat
> IEC 62053-21
class 1
> IEC 62053-31
> IEC 62053-11
Management software
> To get the most effective
use from your Socomec
measurement and metering
devices, we offer a range of
dedicated software tools.
See page 142.
COUNTIS E63
Active energy meters
3 x single-phase - Direct 100 A
Front panel
count_201x_a_1_cat
1. Backlit LCD display
2. Navigation key
3. Reset key
4. Metrological LED
2
3
4
1
Electrical characteristics
Current measurement
Type
Input consumption
Startup current (Ist)
Minimum current (Imin)
Transition current (Itr)
Reference current (Iref)
Permanent overload (Imax)
Intermittent overload
Voltage measurement
Range of measurement
Consumption on inrush (VA)
Permanent overload
Energy accuracy
Active (according to IEC 62053-21)
3 x single-phase - direct 100 A
0.5 VA max. per phase
80 mA
0.5 A
2A
20 A
100 A
3000 A max for 10 ms
230 ... 400 V +/- 20 %
2
280 V phase-neutral / 480 V phase-phase
Power supply
Self-supplied
Frequency
Operating conditions
Operating temperature
Storage temperature
Relative humidity
Communication
Link
Type
Protocol
MODBUS® speed
RS485
2 … 3 half duplex wires
MODBUS RTU
4800 … 38400 bauds
Type
Number of modules
Dimensions W x H x D
Case degree of protection
Front degree of protection
Display type
Rigid cable cross-section
Flexible cable cross-section
Weight
modular
7
126 x 90 x 62.5 mm
IP20
IP51
backlit LCD display
2.5 to 35 mm2
2.5 to 35 mm2
490 g
yes
50 / 60 Hz
-10 to 55 °C
-20 to 70 °C
95 %
Class 1
Case
62.5
45
COUNTIS E60
Partial
45
Error
90
count_203_a_1_x_cat
126
RESET / PROG
3X230(400)VAC 50/60Hz 0.5-20(100)A
C=2Wh / imp
3 x phases 100A
count_206_b_1_GB_cat
Connection
N
L1’
L2’
L3’
L1
L2
L3
+
-
0
2
15 17 13
N
RS485
COUNTIS E63
1
3
L - 1 - L’
7
9 11
L - 2 - L’
5
L - 3 - L’
References
Type
3 x single phase - 100 A direct with RS485 MODBUS communication
COUNTIS E63
Reference
4850 3016
Catalogue 2015 - 2016
51