QuickServer Start-up Guide
FS-QS-1010/1011/12X0/12X1
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after August 2014
Kernel Version: 6.15
Document Revision: 0
QuickServer Start-up Guide Table of Contents
TABLE OF CONTENTS
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Serial and LonWorks Start-up Guide Table of Contents
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 4 of 43
1 EQUIPMENT SET-UP
1
QuickServer is a high performance, cost effective Building and Industrial Automation multi-protocol gateway providing protocol translation between serial, Ethernet, and LonWorks devices and networks.
2 SUPPLIED EQUIPMENT
QuickServer Gateway.
Preloaded with the two selected drivers (on the FS-QS-1X11 and FS-QS-12X1 one of those drivers is
LonWorks). A sample configuration file is also pre-loaded onto the QuickServer.
All instruction manuals, driver manuals, configuration manuals and support utilities are available on the USB drive provided in the optional accessory kit, or on-line at www.fieldserver.com/QS_Support/
Accessory kit (Optional) (Part # FS-8915-36-QS) including:
7-ft CAT5 cable with RJ45 connectors at both ends
Power Supply -110/220V (p/n 69196)
DIN Rail mounting bracket
Screwdriver for connecting to terminals
USB Flash drive loaded with: o QuickServer Start-up Guide o FieldServer Configuration Manual o FieldServer Utilities Manual o All FieldServer Driver Manuals o Support Utilities o Any additional folders related to special files configured for a specific QuickServer o Additional components as required - See Driver Manual Supplement for details
2.1 BTL Mark – BACnet Testing Laboratory
The BTL Mark on the ProtoNode RER is a symbol that indicates to a consumer that a product has passed a series of rigorous tests conducted by an independent laboratory which verifies that the product correctly implements the BACnet features claimed in the listing. The mark is a symbol of a high-quality BACnet product. For more information about the BACnet Testing Laboratory go to: http://www.bacnetinternational.net/btl/
2.2 LonMark Certification
LonMark International is the recognized authority for certification, education, and promotion of interoperability standards for the benefit of manufacturers, integrators and end users. LonMark International has developed extensive product certification standards and tests to provide the integrator and user with confidence that products from multiple manufacturers utilizing LonMark devices will work together. FieldServer
Technologies, manufacturer of the QuickServer has more LonMark Certified gateways than any other gateway manufacturer.
1 LonWorks is a registered trademark of Echelon Corporation
Metasys is a registered trademark of Johnson Controls Inc.
BACnet is a registered trademark of ASHRAE
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 5 of 43
3 MOUNTING
The following mounting options are available:
Product comes with tabs for wall or surface mount. These can be snapped off if not required.
DIN Rail Mounting Bracket - included in the Accessory Kit or ordered separately (Part # FS-8915-35-QS)
Din Rail
Tab
3.1 Dimensions
3.1.1 Dimension Drawing FS-QS-1X10-XXXX
R1 Port
R2 Port
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 6 of 43
3.1.2 Dimension Drawing FS-QS-1X11-XXXX
LonWorks Port
R2 Port
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 7 of 43
3.1.3 Dimension Drawing FS-QS-12XX models with RS-422
R1 Port
R2 Port
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 8 of 43
3.2 Wiring
Power supply must be connected to the terminal block.
3.2.1 Power jumper settings
Power Jumper Switch in “A” position
The QuickServer Carrier Board power jumper is set to position A by default, but can be changed to position B for other power supply requirements:
A Position : The Carrier makes use of a full-wave rectifying bridge. Can be used for 12-24 VAC input or 9 – 30 VDC input. At 9 VDC this becomes marginal.
B Position : The Carrier makes use of a half-wave rectifying bridge. Best position for Grounded AC Transformers and for using DC voltage down to 9VDC.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 9 of 43
3.3 Specifications
2
Available Ports
Power
Approvals
Requirements
FS-QS-1010-XXXX & FS-QS-12X0-XXXX
3
One 6-pin Phoenix connector, one RS-
485 +/- ground port, power +/- frame ground port
One 3-pin RS-485 Phoenix connector, one RS-485 +/- ground port
One Ethernet-10/100 port
Input Voltage: 9-30VDC or 12-24VAC
Input Power Frequency 50/60 Hz.
Power Rating: 2.5 Watts
Current draw @ 12V, 150 mA
TUV approved to UL 916 Standard
RoHS Compliant
FCC Part 15 Compliant
DNP compliant
OPC self-tested to conformance
CE Mark
BTL Mark
FS-QS-1011-XXXX & FS-QS-12X1-XXXX
One 6-pin Phoenix connector, one RS-485 (or RS-232 or RS-422) +/- ground port, power +/- frame ground port
2-pin FTT-10 LonWorks port
One Ethernet-10/100 port
Input Voltage: 9-30VDC or 12-24VAC
Input Power Frequency 50/60 Hz.
Power Rating: 2.5 Watts
Current draw @ 12V, 279 mA
TUV approved to UL 916 Standard
RoHS Compliant
FCC Part 15 Compliant
DNP compliant
OPC self-tested to conformance
LonMark Certification
SPID: 80:00:95:46:00:84:04:01
Profiles:
0000 - Node object (1)
0001 - Open Loop Sensor Object (5)
0003 - Open Loop Actuator Object (5)
Surge Suppression
EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT
Physical Dimensions(excluding the external power supply)
(WxDxH):
Weight:
5.05 x 2.91 x 1.6 in. (12.82 x 7.39 x 4.06 cm) excluding mounting tabs
0.4 lbs (0.2 Kg)
Environment:
Operating Temperature:
Humidity:
-40°C to 75°C (-40°F to167°F)
5 - 90% RH (non-condensing)
“This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
This device may not cause harmful interference
This device must accept any interference received, including interference that may cause undesired operation.
2
Specifications subject to change without notice
3
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 10 of 43
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his expense.
Modifications not expressly approved by FieldServer could void the user's authority to operate the equipment under FCC rules”
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 11 of 43
4 INSTALLING THE QUICKSERVER
4.1 RS-485
4.1.1 RS-485 Connection R2 port
B+ ASG
Connect to the 3 pins on the left-hand-side of the 6 pin connector as shown.
The following Baud Rates are supported on the R2 Port:
4800, 9600, 19200, 38400, 57600, 115200
Refer to Appendix D.7 for the Dip Switch Settings for these Baud Rates.
For connection to RS-232 or RS-422, please refer to Appendix A.2
4.1.2 RS-485 Connection R1 Port (Only on Non-LonWorks QuickServers)
Connect to the 3-pin connector as shown.
+ -
GND
The following Baud Rates are supported on the R1 Port:
110, 300, 600, 1200, 2400, 4800, 9600, 19200, 20833, 28800, 38400, 57600, 76800, 115200
Refer to Appendix D.7 for the Dip Switch Settings for these Baud Rates.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 12 of 43
4.2 QuickServer LonWorks – (FS-QS-1011-XXXX or FS-QS-12X1-XXX)
Connect the QuickServer to the LonWorks terminal using a twisted pair non-shielded cable.
LonWorks Service Pin
LonWorks Terminal
To commission the QuickServer LonWorks port, insert a small screwdriver in the commissioning hole on the face of the QuickServer’s enclosure to access the Service Pin. See the instructions on the QuickServer as to which way to toggle the screwdriver during commissioning.
4.3 QuickServer KNX – (FS-QS-1011-XXXX or FS-QS-12X1-XXX)
Connect the QuickServer to the KNX bus using the standard KNX twisted pair cable.
KNX Programming Button
To commission the QuickServer as a KNX device in ETS Software, insert a small pin into the KNX commissioning hole on the face of the QuickServer to access the button.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 13 of 43
4.4 RS-232 Connection R2 Port (Only available on the FS-QS-12XX Models)
TX
Refer to Appendix A2 for further hardware connection options.
RX SG
The following Baud Rates are supported on the R2 Port:
4800, 9600, 19200, 38400, 57600, 115200
Refer to Appendix D.7 for the Dip Switch Settings for these Baud Rates
4.5 Configure the DIP Switches
The DIP switches on the QuickServer allow users to set the Baud Rate, Node-ID, and MAC address. If a custom configuration has been purchased, these DIP switches will have been configured at the factory. If doing a selfconfiguration, each of these DIP switches will have to be configured. Although it is technically possible to configure the DIP switches in a variety of ways, it is recommended that the banks are configured as laid out in this manual. It is necessary to restart the QuickServer in order for the DIP switch changes to take effect.
4.5.1 Using A0 – A7 to set Node ID/Device Instance.
Refer to Appendix A.1 for configuration example.
The A bank can set the Node-ID/Device Instance for any protocol which requires one.
DIP switches A0 – A7 can be also be used to set MAC Address for BACnet MS/TP. See the DIP switch settings for
the full range of addresses in Appendix D.6
Address 1 ... 128 ... 255
A0 On . Off . On
A1
A2
A3
A4
A5
A6
Off .
Off .
Off .
Off .
Off .
Off .
Off
Off
Off
Off
Off
Off
.
.
.
.
.
.
On
On
On
On
On
On
A7 Off . On . On
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 14 of 43
4.5.2 Using B0 – B3 to set Baud Rate
Refer to Appendix A.1 for configuration example. The
DIP switches B0 – B3 can be set for standard Baud
Rates between 110 and 115200 Baud. Refer to
Appendix D.6 for DIP switch settings.
4.5.3 DIP Switches S0-S3
Refer to Appendix A.1 and Appendix A.1.3 for configuration example. The S0 - S3 DIP switch selection is read directly into a Data Array. This Data_Array value can be used for customized operations such as configuration selection.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 15 of 43
5 OPERATION
5.1 Power up the device
Apply power to the device. Ensure that the power supply used complies with the specifications provided in.
Ensure that the cable is grounded using the “Frame GND” terminal. The QuickServer is factory set for 9-30VDC or
12-24VAC.
PWR+ PWRFG
5.2 Connect the PC to the QuickServer over the Ethernet port.
Ethernet Port
Disable any wireless Ethernet adapters on the PC/Laptop.
Disable firewall and virus protection software .
Connect an Ethernet cable between the PC and QuickServer or connect the QuickServer and the PC to the
Hub/switch using a straight cat5 cable.
The Default IP Address of the QuickServer is 192.168.2.101, Subnet Mask is 255.255.255.0. If the PC and the QuickServer are on different IP Networks, assign a Static IP Address to the PC on the 192.168.2.X network.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 16 of 43
5.3 Connecting to the QuickServer
5.3.1 Using the Toolbox application to Allocate the IP address:
Install the Toolbox application from the USB drive or get it from our website http://fieldserver.com/techsupport/utility/downloads.php
Use the Toolbox application to find the QuickServer, and launch the Web GUI
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 17 of 43
5.4 Set IP Address of the QuickServer
5.4.1 Using the Toolbox Application to set the IP address:
From the Toolbox main page, click on the setup icon (the gear picture).
Select Network Settings.
Modify the IP address (N1 IP address field) of the QuickServer Ethernet port.
If necessary, change the Netmask (N1 Netmask field).
Type in a new Subnet Mask
If necessary, change the IP Gateway (Default Gateway field)
Type in a new IP Gateway
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 18 of 43
Note: If the FieldServer is connected to a router, the IP Gateway of the FieldServer should be set to the IP address of the router that it is connected to.
Click Update IP Settings, then click on the Change and Restart to restart the Gateway and activate the new IP address. Note that the QuickServer will need to be pointed to the new IP address on the Web
Browser before the GUI will be accesssible again. Unplug Ethernet cable from PC and connect it to the network hub or router
5.4.2 Using the Web GUI to set the IP address:
From the GUI main home page, click on setup and then Network Settings to enter the Edit IP Address
Settings menu.
Modify the IP address (N1 IP address field) of the QuickServer Ethernet port.
If necessary, change the Netmask (N1 Netmask field).
Type in a new Subnet Mask
If necessary, change the IP Gateway (Default Gateway field)
Type in a new IP Gateway
Note: If the FieldServer is connected to a router, the IP Gateway of the FieldServer should be set to the IP address of the router that it is connected to
Click Update IP Settings, then click on the System Restart to restart the Gateway and activate the new
IP address. Note that the QuickServer will need to be pointed to the new IP address on the Web
Browser before the GUI will be accessible again. Unplug Ethernet cable from PC and connect it to the network hub or router
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 19 of 43
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 20 of 43
6 CONFIGURING THE QUICKSERVER
6.1 Retrieve the Sample Configuration File
The configuration of the QuickServer is provided to the QuickServer’s operating system via a comma-delimited file called “CONFIG.CSV”.
If a custom configuration was ordered, the QuickServer will be programmed with the relevant device registers in the Config.csv file for the first time start-up. If not, the product is shipped with a sample config.csv that shows an example of the drivers ordered.
In the main menu of the FS-GUI screen, go to Setup, File Transfer, Retrieve.
Click on config.csv, and open or save the file
6.2 Change the Configuration File to Meet the Application
Refer to the FieldServer Configuration Manual in conjunction with the Driver supplements for information on configuring the QuickServer.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 21 of 43
6.3 Load the Updated Configuration file
6.3.1 Using the Toolbox application to load a configuration file:
From the Toolbox main page, click on the setup icon (the gear picture).
Select File Transfer.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 22 of 43
Browse and select the .csv file, open, then click Update Config
Once download is complete, click the Restart Button (or simply cycle power to the QuickServer) to put the new file into operation. Note that it is possible to do multiple downloads to the QuickServer before resetting it.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 23 of 43
6.3.2 Using the Web GUI to load a configuration file:
In the main menu of the FS-GUI screen, go to Setup, File Transfer, Update
Browse and select the .csv file, open, then click Submit
Once download is complete, click the System Restart Button (or simply cycle power to the QuickServer) to put the new file into operation. Note that it is possible to do multiple downloads to the QuickServer before resetting it.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 24 of 43
6.4 Test and Commission the QuickServer
Connect the QuickServer to the third party device(s), and test the application.
From the main menu of FS-GUI click on View, Connections to see the number of messages on each protocol.
For troubleshooting assistance refer to Appendix B, or any of the troubleshooting Appendices in the related Driver Supplements and Configuration Manual. FieldServer Technologies also offers a
Technical support page on the FieldServer website at www.FieldServer.com, which contains a significant number of resources and documentation that may be of assistance.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 25 of 43
Appendix A Useful Features
Appendix A.1. QuickServer DIP Switch configuration
There are 3 DIP switches available on the QuickServer.
A – Address DIP Switch
B – Baud rate DIP Switch
S – Secondary DIP Switch
The following sections describe how to set up the DIP switches in the configuration file. To configure the use of the DIP switches, buffers need to be declared in the “Data Arrays” section which will enable them.
Data_Arrays
Data_Array_Name , Data_Format , Data_Array_Length , Data_Array_Function , Scan_Interval
DA_A
DA_B
DA_S
, UINT16
, BAUD
, UINT16
, 1
, 1
, 1
, Dip_Switches_A
, Dip_Switches_B
, Dip_Switches_S
, 2s
, 2s
, 2s
Appendix A.1.1. Configure DIP switches A0-A7
To configure DIP switches A0-A7 to adjust the Device Id, BACnet MAC address, or both, the dynamic parameters field needs to be added to the configuration file.
Dynamic_Parameters
Function , Data_Array_Name , Data_Array_Offset , Descriptor_Name , Low_Limit , High_Limit
Change_Node_ID , DA_A
Change_System_MAC_Addr , DA_A
, 0
, 0
, Node_Name_A
, Title_A
, 1
, 1
, 4194303
, 254
Appendix A.1.2. Configure DIP switches B0 – B3
To configure DIP switches B0-B3 to adjust the baud rate, the dynamic parameters field needs to be added to the configuration file.
Dynamic_Parameters
Function , Data_Array_Name , Data_Array_Offset , Descriptor_Name
, 0 , P1
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 26 of 43
Appendix A.1.3. Configure DIP switches S0 – S3
The S0 - S3 DIP switch selection is read directly into a Data Array. This Data Array value can be used for customized operations such as config file selection which allows a FieldServer to be loaded with several configurations / profiles that are selected based on a Data Array value. See the example below where a Config Table and Dynamic
Parameter can be used in conjunction with the DIP Switches to achieve this type of customization. .
In this example, 5 configs will need to be downloaded to the QuickServer: config.csv (base config), profile1.csv, profile2.csv, profile3.csv and profile4.csv. The profile configs will be configured as per FieldServer standard configuration templates. The base config will be used to select the appropriate profile config to load.
Column Title
Table_Index_Value
Table_String
Restart_Method*
Function
Config_Table_Name Provide name for Config Table
A unique value that will be used to identify which table entry needs to be used.
A String value, representing the filename of the profile to be loaded for the corresponding Table_Index_Value.
The specified config or profile is loaded on start-up. If the parameter is configured as On_Change, the QuickServer will restart and reload the specified config every time the Data_Array value changes.
Otherwise the config or profile will remain unchanged even if the
Data_Array value changes.
Legal Values
Up to alphanumeric
32 characters
1-10, 000
On_Change,
Never, _
Data_Arrays
Data_Array_Name , Data_Format , Data_Array_Length , Data_Array_Function , Scan_Interval
DA_LOAD_CSV , UINT16 , 1 , Dip_Switches_S , 2s
Config_Table
Config_Table_Name , Table_String , Table_Index_Value csvfilenames csvfilenames
, profile1.csv , 1 // Profile config 1
, profile2.csv , 2 // Profile config 2 csvfilenames csvfilenames
, profile3.csv , 3 // Profile config 3
, profile4.csv , 4 // Profile config 4
Dynamic_Parameters
Function , Data_Array_Name , Data_Array_Offset , Config_Table_Name , Restart_Method load_csv , DA_LOAD_CSV , 2 , csvfilenames , On_Change
Note: In this example the value 0 has no operation, so if 0 is read on the dip switches no profile will be loaded.
Similarly values larger than 4 will be ignored.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 27 of 43
Appendix A.2. RS-422 Connection R2 Port (Only available on the FS-QS-12XX models)
RS422 is a full duplex multi-drop multi-master differential bus. It can be wired to conform to a RS-485 network when less wiring/cabling is used (due to being less expensive to install), but then it becomes a half-duplex multidrop multi-master differential bus. RS-422 is used for dedicated peer to peer high speed communication when low bus latency is required i.e. very few devices on the bus. Its usage is very specific to client installations/requirements.
Notes:
The RS-232 looks similar to the RS-485 but does not have the blue jumper. The blue jumper is used to enable the termination resistor for the RX signals (120 ohms), while the red jumpers are used to enable the bias resistors for RX signals (510 ohms). In the case of Rockwell/Tetrapak, all jumpers are always required to be in default position i.e. not enabled. For other clients, the bias resistors should always be in the on state.
The Part number on the back of the box will identify the port..
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 28 of 43
Appendix A.2.1. Connection and Operation of the RS-422 QuickServer
RS422 connector:
5-pin RS-422
Connector
3-pin Power
Connector
Pin 1-2: TX +/- (Differential TX outputs: All + signals must be connected to each other, and same applies to - signals; no +/- signals may be crossed)
Pin 3-4: RX +/- (Differential RX inputs: All + signals must be connected to each other, and same applies to - signals, no +/- signals may be crossed)
Pin 5: SHD (Shield connection, must be connected on at least one side of the bus, but not necessarily on both sides)
POWER connector:
Please note that AC voltage is not supported on the RS-422 Carrier, and that DC voltage range is ~20VDC to
~28VDC.
Pin 1: +24V (DC power requires this pin be used for the positive voltage)
Pin 2: 0V (DC power requires this pin is used for ground / return voltage)
Pin 3: FG (This pin needs to be connected to EARTH or noise free reference point i.e. CHASSIS)
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 29 of 43
Appendix A.3. KNX Connection R2 Port
The KNX QuickServer is used to transfer data to and from devices using KNX protocol. The KNX driver enables data access from KNX networks to other FieldServer protocols. Most KNX data-point types are supported, allowing communication to almost any kind of KNX device in an installation, such as temperature sensors, shutters, light switches, actuators, alarms, etc. This allows BMS systems to access a KNX network using direct read and write or with KNX configured groups. This setup does not require the use of ETS4 to configure the QuickServer KNX gateway. The KNX protocol is a connectionless protocol and therefore supports multiple clients and multiple servers. The QuickServer is intended to act as a Passive Client on the KNX bus and makes information available to other protocols.
KNX+ KNX- No Connection
The KNX Connection consist of a KNX + and KNX- terminal. Each terminal corresponds to the red KNX+ and gray
KNX- bus connections on a KNX bus.
The following Baud Rates are supported on the R2 Port:
4800, 9600, 19200, 38400, 57600, 115200
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 30 of 43
Appendix A.4. M-Bus Connection R2 Port
The M-Bus driver allows the FieldServer to transfer data to and from devices using M-Bus protocol. The Fieldbus connection is included with the FieldServer. The M-Bus QuickServer Gateway is configurable to act as both a
Master and a Slave M-Bus device.
The M-Bus Connection consist of a + and – terminal. Most M-Bus Devices are not polarity sensitive, although the polarity of the M-Bus connection is indicated on the device diagram, should it be a requirement. The M-Bus devices communicating with the FieldServer must be configured according to the manufacturer’s instructions (e.g.
Primary address and readout data).
The following Baud Rates are supported on the R2 Port:
300, 600, 1200, 2400, 4800, 9600, 19200, 38400
Appendix A.5. Enhanced Network Security
For enhanced network security, one can disable RuiNet access to a FS-GUI capable FieldServer by use of the
RUI_Enable FieldServer parameter. Adding the following to the configuration file will disable RuiNet Access.
FieldServer
Title , RUI_Enable
FieldServer Name , Disabled // Enabled -- is the default if not specified
Note: In order to take a FieldServer Diagnostics log, RuiNet access has to be enabled again.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 31 of 43
Appendix B Troubleshooting Tips
Appendix B.1. Communicating with the QuickServer over the Network
Confirm that the network cabling is correct.
Confirm that the computer network card is operational and correctly configured.
Confirm that there is an Ethernet adapter installed in the PC’s Device Manager List, and that it is configured to run the TCP/IP protocol.
Check that the IP netmask of the PC matches the QuickServer. The Default IP Address of the QuickServer is
192.168.2.X, Subnet Mask is 255.255.255.0. o Go to Start|Run o Type in “ipconfig” o The account settings should be displayed. o Ensure that the IP address is 102.168.2.X and the netmask 255.255.255.0
Ensure that the PC and QuickServer are on the same IP Network, or assign a Static IP Address to the PC on the
192.168.2.0 network.
If using Windows XP or later, ensure that the firewall is disabled.
Ensure that all other Ethernet cards active on the PC, especially wireless adapters are disabled.
Refer to the FieldServer Troubleshooting Guide which can be found at www.fieldserver.com/QS_Support/ for further information
Appendix B.2. Technical support
Before contacting Technical support to report an issue, go to Start|Programs|FieldServer utilities|Tools and run the FST_Diag program. Take a log (See ENote0058 in the folder called Library on the USB Flash Drive). Send this log together with a detailed description of the problem to [email protected] for evaluation.
Note that while all necessary documentation is shipped with the FieldServer on the USB flash drive, these documents are constantly being updated. Newer versions may be available on the web at www.fieldserver.com/QS_Support/
Appendix B.3. Notes Regarding Subnets and Subnet Masks
Please Note that RFC standards allocate the IP address range of 192.0.0.0 through to 223.255.255.255 to be used in Class-C subnetting (i.e.: Subnets listed as 255.255.255.xxx, where xxx can vary based on filtering required).
Consequently, the IP stack for this product will not allow any IP addresses in this range to be allocated a subnet that does not fall within the Class C range.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 32 of 43
Appendix C Limited 2 year Warranty
FieldServer Technologies warrants its products to be free from defects in workmanship or material under normal use and service for two years after date of shipment. FieldServer Technologies will repair or replace any equipment found to be defective during the warranty period. Final determination of the nature and responsibility for defective or damaged equipment will be made by FieldServer Technologies personnel.
All warranties hereunder are contingent upon proper use in the application for which the product was intended and do not cover products which have been modified or repaired without FieldServer Technologies approval or which have been subjected to accident, improper maintenance, installation or application, or on which original identification marks have been removed or altered. This Limited Warranty also will not apply to interconnecting cables or wires, consumables or to any damage resulting from battery leakage.
In all cases FieldServer Technology’s responsibility and liability under this warranty shall be limited to the cost of the equipment. The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty provision and compliance with such instruction shall be a condition of this warranty.
Except for the express warranty stated above, FieldServer Technologies disclaims all warranties with regard to the products sold hereunder including all implied warranties of merchantability and fitness and the express warranties stated herein are in lieu of all obligations or liabilities on the part of FieldServer Technologies for damages including, but not limited to, consequential damages arising out of/or in connection with the use or performance of the product.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 33 of 43
Appendix D Reference
Appendix D.1. LED Functions
Light Description
SPL LED will be on when a configured node in the QuickServer is detected as being offline. See Node
SPL
overview screen of the FS-GUI for further details.
RUN
RUN LED will flash 20 seconds after power up, signifying normal operation. The QuickServer will be able
20 seconds, the LED should be off
ERR
The ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red light will indicate there is a system error on the FieldServer. If this occurs, immediately report the related
“system error” shown in the error screen of the FS-GUI interface to FieldServer Technologies for evaluation.
RX
TX
On normal operation of FS-QS-10XX, the RX LED will flash when a message is received on the field port of the QuickServer.
On normal operation of FS-QS-10XX, the TX LED will flash when a message is sent on the field port of the
QuickServer
PWR This is the power light and should show steady green at all times when the QuickServer is powered.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 34 of 43
Appendix D.2. FS-QS-1010-XXXX LED’s
RUN
ERROR
NODE OFF-LINE
HEART BEAT
RS-485 RX
RS-485 TX
LED’s
Light Description
HEART BEAT The system indicator LED as indication that the operating system is running
ERROR
The ERROR LED will flash once on power up and flash once 15 seconds after power up. A steady red light will indicate there is a system error on the FS-QS-1010-XXXX. If this occurs, immediately report the related “system error” shown in the error screen of the FS_GUI interface to FieldServer
Technologies for evaluation.
NODE OFF-
LINE
RUN
TX
RX
The Node Offline LED will flash once on power up and flash once 15 seconds after power up. If the
Node Offline LED stays on solid, a Node Offline condition has occurred.
The RUN LED will start flashing 20 seconds after power indicating normal operation. The FS-QS-
1010-XXXX will be able to access FS-GUI once this LED starts flashing.
RS-485 indicator LED when a message is sent through the port
RS-485 indicator LED when a message is received by the port
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 35 of 43
Appendix D.3. FS-QS-1011-XXXX LED’s
Note that the lid on top of the QuickServer has to be removed in order to see the LED’s
LON SERVICE LED
LON SERVICE PIN
TX
RUN
LON RX
PWR
SYS ERR
COM ERR
CONFIG ERR
NODE OFFLINE
Light
PWR
PIC RUN
PIC ERR
UNUSED
UNUSED
SYS ERR
(LED1)
COMM ERR
(LED2)
Config ERR
(LED3)
Node Offline
(LED4)
RUN
(PIO)
PIC RUN
(LED5)
PIC ERR
(LED6)
LON-TX LED
Description
This is the power light and should show steady green at all times when the FS-QS-1011-XXXX is powered.
The SYS ERR LED will flash once on power up and flash once 15 seconds after power up. A steady red light will indicate there is a system error on the FS-QS-1011-XXXX. If this occurs, immediately report the related “system error” shown in the error screen of the FS_GUI interface to FieldServer Technologies for evaluation.
The COMM ERR LED will flash once on power up and flash once 15 seconds after power up.
A steady red light will indicate a communication error has occurred. To establish the cause of the error, go to the error screen of the RUI interface.
The Config ERR LED will flash once on power up and flash once 15 seconds after power up. A steady amber light will indicate a configuration error exists in the active configuration. See the Error Screen in the Remote User Interface for a description of the configuration error.
The Node Offline LED will flash once on power up and flash once 15 seconds after power up.
If the Node Offline LED stays on solid, a Node Offline condition has occurred.
The RUN LED will start flashing 20 seconds after power indicating normal operation. The FS-
QS-1011-XXXX will be able to access FS-GUI once this LED starts flashing.
The PIC RUN LED will flash indicating normal operation.
The PIC ERR LED will go on solid indicating there is a PIC error.
On normal operation of FS-QS-1011-XXXX, the TX LED will flash when a message is sent on the Lon port of the QuickServer.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 36 of 43
Light
LON-RX LED
LON-SRV LED
(next to Lon port)
LED 7
LED 8
Description
On normal operation of FS-QS-1011-XXXX, the RX LED will flash when a message is received on the Lon port of the QuickServer.
The LON-SRV LED will flash if the FS-QS-1011-XXXX is configured for implicit addressing and not commissioned. LED will be off if the FS-QS-1011-XXXX is configured for implicit addressing and commissioned or if it is configured for explicit addressing.
Not used
Not used
Appendix D.4. QuickServer FS-QS-101X DCC
Driver
BACnet/IP – BACnet MS/TP
Code
0285
BACnet/IP – LonWorks
JCI Metasys N2 – LonWorks
0131
0097
JCI Metasys N2– BACnet MS/TP 0309
JCI Metasys N2– BACnet/IP 0122
Modbus RTU – BACnet MS/TP 0367
Modbus RTU – BACnet/IP 0104
Modbus RTU – JCI Metasys N2 0038
Modbus RTU – LonWorks
Modbus TCP – BACnet/IP
0085
0237
Modbus TCP – LonWorks 0154
Modbus TCP – BACnet MS/TP 0419
Modbus TCP – JCI Metasys N2 0117
SNMP – BACnet/IP 0333
SNMP – LonWorks 0337
SNMP – JCI Metasys N2 0150
Add BACnet MS/TP - LonWorks 0345
Appendix D.5. Compliance with UL Regulations
For UL compliance, the following instructions must be met when operating the QuickServer.
The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating temperature range.
The interconnecting power connector and power cable shall:
Comply with local electrical code.
Be suited to the expected operating temperature range.
Meet the current and voltage rating for the QuickServer/Net
Furthermore, the interconnecting power cable shall:
Be of length not exceeding 3.05m (118.3”)
Be constructed of materials rated VW-1 or FT-1 or better.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 37 of 43
If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be installed in a Restricted Access Area requiring a key or a special tool to gain access
This device must not be connected to a LAN segment with outdoor wiring.
Appendix D.6. Address DIP Switch Settings
Address A0 A1 A2 A3 A4 A5 A6 A7
28
29
30
31
32
33
34
35
36
37
17
18
19
20
21
22
23
24
25
26
27
11
12
13
14
15
16
7
8
9
10
2
3
0
1
4
5
6
Off
On
Off
On
Off
Off
Off
On
On
Off
Off
Off
Off
Off
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On Off On Off Off Off Off Off
Off On On Off Off Off Off Off
On On On Off Off Off Off Off
Off Off Off On Off Off Off Off
On Off Off On Off Off Off Off
Off On Off On Off Off Off Off
On On Off On Off Off Off Off
Off Off On On Off Off Off Off
On Off On On Off Off Off Off
Off On On On Off Off Off Off
On On On On Off Off Off Off
Off Off Off Off On Off Off Off
On Off Off Off On Off Off Off
Off On Off Off On Off Off Off
On On Off Off On Off Off Off
Off Off On Off On Off Off Off
On Off On Off On Off Off Off
Off On On Off On Off Off Off
On On On Off On Off Off Off
Off Off Off On On Off Off Off
On Off Off On On Off Off Off
Off On Off On On Off Off Off
On On Off On On Off Off Off
Off Off On On On Off Off Off
On Off On On On Off Off Off
Off On On On On Off Off Off
On On On On On Off Off Off
Off Off Off Off Off On Off Off
On Off Off Off Off On Off Off
Off On Off Off Off On Off Off
On On Off Off Off On Off Off
Off Off On Off Off On Off Off
On Off On Off Off On Off Off
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 38 of 43
Address A0 A1 A2 A3 A4 A5 A6 A7
71
72
73
74
75
65
66
67
68
69
70
61
62
63
64
55
56
57
58
59
60
76
77
78
79
80
81
82
44
45
46
47
48
49
38
39
40
41
42
43
50
51
52
53
54
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On Off On Off On On Off Off
Off On On Off On On Off Off
On On On Off On On Off Off
Off Off Off On On On Off Off
On Off Off On On On Off Off
Off On Off On On On Off Off
On On Off On On On Off Off
Off Off On On On On Off Off
On Off On On On On Off Off
Off On On On On On Off Off
On On On On On On Off Off
Off Off Off Off Off Off On Off
On Off Off Off Off Off On Off
Off On Off Off Off Off On Off
On On Off Off Off Off On Off
Off Off On Off Off Off On Off
On Off On Off Off Off On Off
Off On On Off Off Off On Off
On On On Off Off Off On Off
Off Off Off On Off Off On Off
On Off Off On Off Off On Off
Off On Off On Off Off On Off
On On Off On Off Off On Off
Off Off On On Off Off On Off
On Off On On Off Off On Off
Off On On On Off Off On Off
On On On On Off Off On Off
Off Off Off Off On Off On Off
On Off Off Off On Off On Off
Off On Off Off On Off On Off
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 39 of 43
Address A0 A1 A2 A3 A4 A5 A6 A7
116
117
118
119
120
110
111
112
113
114
115
100
101
102
103
104
105
106
107
108
109
121
122
123
124
125
126
127
89
90
91
92
93
94
83
84
85
86
87
88
95
96
97
98
99
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off On Off Off Off On On Off
On On Off Off Off On On Off
Off Off On Off Off On On Off
On Off On Off Off On On Off
Off On On Off Off On On Off
On On On Off Off On On Off
Off Off Off On Off On On Off
On Off Off On Off On On Off
Off On Off On Off On On Off
On On Off On Off On On Off
Off Off On On Off On On Off
On Off On On Off On On Off
Off On On On Off On On Off
On On On On Off On On Off
Off Off Off Off On On On Off
On Off Off Off On On On Off
Off On Off Off On On On Off
On On Off Off On On On Off
Off Off On Off On On On Off
On Off On Off On On On Off
Off On On Off On On On Off
On On On Off On On On Off
Off Off Off On On On On Off
On Off Off On On On On Off
Off On Off On On On On Off
On On Off On On On On Off
Off Off On On On On On Off
On Off On On On On On Off
Off On On On On On On Off
On On On On On On On Off
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 40 of 43
Address A0 A1 A2 A3 A4 A5 A6 A7
161
162
163
164
165
155
156
157
158
159
160
145
146
147
148
149
150
151
152
153
154
166
167
168
169
170
171
172
134
135
136
137
138
139
128
129
130
131
132
133
140
141
142
143
144
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On On On On Off Off Off On
Off Off Off Off On Off Off On
On Off Off Off On Off Off On
Off On Off Off On Off Off On
On On Off Off On Off Off On
Off Off On Off On Off Off On
On Off On Off On Off Off On
Off On On Off On Off Off On
On On On Off On Off Off On
Off Off Off On On Off Off On
On Off Off On On Off Off On
Off On Off On On Off Off On
On On Off On On Off Off On
Off Off On On On Off Off On
On Off On On On Off Off On
Off On On On On Off Off On
On On On On On Off Off On
Off Off Off Off Off On Off On
On Off Off Off Off On Off On
Off On Off Off Off On Off On
On On Off Off Off On Off On
Off Off On Off Off On Off On
On Off On Off Off On Off On
Off On On Off Off On Off On
On On On Off Off On Off On
Off Off Off On Off On Off On
On Off Off On Off On Off On
Off On Off On Off On Off On
On On Off On Off On Off On
Off Off On On Off On Off On
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 41 of 43
Address A0 A1 A2 A3 A4 A5 A6 A7
206
207
208
209
210
200
201
202
203
204
205
190
191
192
193
194
195
196
197
198
199
211
212
213
214
215
216
217
179
180
181
182
183
184
173
174
175
176
177
178
185
186
187
188
189
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off Off On On On On Off On
On Off On On On On Off On
Off On On On On On Off On
On On On On On On Off On
Off Off Off Off Off Off On On
On Off Off Off Off Off On On
Off On Off Off Off Off On On
On On Off Off Off Off On On
Off Off On Off Off Off On On
On Off On Off Off Off On On
Off On On Off Off Off On On
On On On Off Off Off On On
Off Off Off On Off Off On On
On Off Off On Off Off On On
Off On Off On Off Off On On
On On Off On Off Off On On
Off Off On On Off Off On On
On Off On On Off Off On On
Off On On On Off Off On On
On On On On Off Off On On
Off Off Off Off On Off On On
On Off Off Off On Off On On
Off On Off Off On Off On On
On On Off Off On Off On On
Off Off On Off On Off On On
On Off On Off On Off On On
Off On On Off On Off On On
On On On Off On Off On On
Off Off Off On On Off On On
On Off Off On On Off On On
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 42 of 43
Address A0 A1 A2 A3 A4 A5 A6 A7
251
252
253
254
255
245
246
247
248
249
250
235
236
237
238
239
240
241
242
243
244
224
225
226
227
228
229
218
219
220
221
222
223
230
231
232
233
234
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On Off Off On Off On On On
Off On Off On Off On On On
On On Off On Off On On On
Off Off On On Off On On On
On Off On On Off On On On
Off On On On Off On On On
On On On On Off On On On
Off Off Off Off On On On On
On Off Off Off On On On On
Off On Off Off On On On On
On On Off Off On On On On
Off Off On Off On On On On
On Off On Off On On On On
Off On On Off On On On On
On On On Off On On On On
Off Off Off On On On On On
On Off Off On On On On On
Off On Off On On On On On
On On Off On On On On On
Off Off On On On On On On
On Off On On On On On On
Off On On On On On On On
On On On On On On On On
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
QuickServer Start-up Guide Page 43 of 43
Appendix D.7. Baud DIP Switch Settings
Baud B0 B1 B2 B3
Auto 4 Off Off Off Off
110
300
600
1200
On
Off
On
Off
Off
On
On
Off
Off
Off
Off
On
Off
Off
Off
Off
2400
4800
On Off On Off
Off On On Off
9600 On On On Off
19200 Off Off Off On
20833 On Off Off On
28800 Off On Off On
38400 On On Off On
57600 Off Off On On
76800 On Off On On
115200 Off On On On
Please refer to Section 4.1.1 and Section 4.1.2 for Baud Rate supporting Ports
4 Auto-baud is only supported for BACnet MS/TP
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 4 Equipment Set-up
- 4 Supplied equipment
- 4 BTL Mark – BACnet Testing Laboratory
- 4 LonMark Certification
- 5 Mounting
- 5 Dimensions
- 5 Dimension Drawing FS-QS-1X10-XXXX
- 6 Dimension Drawing FS-QS-1X11-XXXX
- 7 Dimension Drawing FS-QS-12XX models with RS
- 8 Wiring
- 9 Specifications
- 11 Installing the QuickServer
- 11 RS-485 Connection R2 port
- 11 RS-485 Connection R1 Port (Only on Non-LonWorks QuickServers)
- 12 QuickServer LonWorks – (FS-QS-1011-XXXX or FS-QS-12X1-XXX)
- 12 QuickServer KNX – (FS-QS-1011-XXXX or FS-QS-12X1-XXX)
- 13 RS-232 Connection R2 Port (Only available on the FS-QS-12XX Models)
- 13 Configure the DIP Switches
- 13 Using A0 – A7 to set Node ID/Device Instance
- 14 Using B0 – B3 to set Baud Rate
- 14 DIP Switches S0-S
- 15 Operation
- 15 Power up the device
- 15 Connect the PC to the QuickServer over the Ethernet port
- 16 Connecting to the QuickServer
- 16 Using the Toolbox application to Allocate the IP address
- 17 Set IP Address of the QuickServer
- 17 Using the Toolbox Application to set the IP address
- 18 Using the Web GUI to set the IP address
- 20 Configuring the QuickServer
- 20 Retrieve the Sample Configuration File
- 20 Change the Configuration File to Meet the Application
- 21 Load the Updated Configuration file
- 21 Using the Toolbox application to load a configuration file
- 23 Using the Web GUI to load a configuration file
- 24 Test and Commission the QuickServer
- 25 Appendix A Useful Features
- 25 Appendix A.1. QuickServer DIP Switch configuration
- 25 Appendix A.1.1. Configure DIP switches A0-A
- 25 Appendix A.1.2. Configure DIP switches B0 – B
- 26 Appendix A.1.3. Configure DIP switches S0 – S
- 27 Appendix A.2. RS-422 Connection R2 Port (Only available on the FS-QS-12XX models)
- 28 Appendix A.2.1. Connection and Operation of the RS-422 QuickServer
- 29 Appendix A.3. KNX Connection R2 Port
- 30 Appendix A.4. M-Bus Connection R2 Port
- 30 Appendix A.5. Enhanced Network Security
- 31 Appendix B Troubleshooting Tips
- 31 Appendix B.1. Communicating with the QuickServer over the Network
- 31 Appendix B.2. Technical support
- 31 Appendix B.3. Notes Regarding Subnets and Subnet Masks
- 32 Appendix C Limited 2 year Warranty
- 33 Appendix D Reference
- 33 Appendix D.1. LED Functions
- 34 Appendix D.2. FS-QS-1010-XXXX LED’s
- 35 Appendix D.3. FS-QS-1011-XXXX LED’s
- 36 Appendix D.4. QuickServer FS-QS-101X DCC
- 36 Appendix D.5. Compliance with UL Regulations
- 37 Appendix D.6. Address DIP Switch Settings
- 43 Appendix D.7. Baud DIP Switch Settings