cPos - GEMÜ
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Positioner GEMÜ 1436 cPos
Profibus-DP
GB
OPERATING INSTRUCTIONS
th
Status 24 February 2014
from version 2.0.0.0
1/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
TABLE OF CONTENT
1.
2.
TECHNICAL DATA GEMÜ 1436 CPOS PROFIBUS DP
ELECTRICAL CONNECTIONS
3
3
2.1.
GEMÜ 1436 cPos
3
2.2.
RS-485
4
2.3.
Profibus DP status LED
4
2.4.
Supply voltage
4
3.
4.
5.
6.
7.
WIRING IN THE PROFIBUS SYSTEM
SERIAL WIRING IN THE BUS SYSTEM
BUS WIRING VIA STUB
DIFFERENT CONFIGURATION MENU
CYCLIC PROFIBUS DATA
5
5
6
6
7
7.1.
Set value
7
7.2.
Actual value
7
7.3.
Digital input
8
7.4.
Valve position
8
7.5.
Digital output
8
7.6.
Parameter data: Parameters / Actions / Errors
7.6.1. No action
7.6.2. Change parameters
7.6.3. Request parameters
7.6.4. Read error list
7.6.5. Amount of active errors and readout of the active error
7.6.6. Amount of active warnings and readout of the active warning
7.6.7. Error list
7.6.8. Trigger action in the cPos
7.6.9. Quit Feldbus Event
7.6.10.
NoInit
7.6.11.
Clear Error List
7.6.12.
Set Default
7.6.13.
Init valve
7.6.14.
GoClose
7.6.15.
GoOpen
7.6.16.
Find function
7.6.17.
Adjust time
7.6.18.
Find Coefficient
7.6.19.
Init Pilot
8
9
9
10
10
11
12
12
13
13
14
15
15
16
17
17
18
18
19
20
8. EXTERNAL DIAGNOSTIC ERRORS
9. PARAMETER NUMBERS
10. CONFIGURATION EXAMPLE USING SIEMENS S7
21
22
26
2/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
1. Technical Data GEMÜ 1436 cPos Profibus DP
Protocol flow
GSD data file
G1436a.GSD
PNO ID
0x2079
Baud rate
9.6
19.2
45.45
93.75
187.5
500
1.5
3
6
12
Profibus address
(Default setting)
26
kbaud
kbaud
kbaud
kbaud
kbaud
kbaud
Mbaud
Mbaud
Mbaud
Mbaud
2. Electrical connections
2.1.
GEMÜ 1436 cPos
X1
X2
1
3 2
5
4 1
B-codiert
43
5 2
Connection
X1
M12 plug
B coding
Pin
1
2
3
4
5
Signal name
n.c.
RxD/TxD-N
n.c.
RxD/TxD-P
Shield
Connection
X2
M12 plug
A coding
Pin
1
2
3
4
5
Signal name
Uv, 24VDC supply voltage
n.c.
GND
n.c.
n.c.
Connection
X3
M12 socket
B coding
Pin
1
2
3
4
5
Signal name
BUS-VDC, +5V DC
RxD/TxD-N
DGND
RxD/TxD-P
Shield
X3
2 3
5
4
1
B-codiert
X4 is only available in versions with external travel sensor!
Connection
X4
M12 socket
A coding
Pin
1
2
3
4
5
Signal name
U+, Potentiometer signal voltage plus
U , Potentiometer signal output
U -, Potentiometer signal voltage minus
n.c.
n.c.
3/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
2.2.
RS-485
DGND
5
9
4
8
3
RxD/Txd-P
RxD/TxD-N
7
2
6
1
2.3.
VP+5
Profibus DP status LED
Profibus DP status LED
Red light – no bus connection
No light – bus connection ok
No function at Profibus DP design
2.4.
Plug
Supply voltage
Pin Signal name
Wiring
Internal
X2
1
24V DC supply voltage
X2
3
GND
external
24V DC voltage
supply
4/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
3. Wiring in the Profibus system











VP +5
VP +5
390
390
220
220
390
390
Shield
Protection
ground
Protection
ground
DGND
DGND
Slave
With transmission rates
≥ 1.5 Mbaud no wiring with
stubs
4. Serial wiring in the bus system
With a transmission rate ≥ 1.5 Mbaud.
X1
X2
1
3 2
5
4 1
B-codiert
43
5 2
X3
X1
X2
1
2 3
5
4
1
B-codiert
3 2
5
4 1
B-codiert
43
5 2
X3
Profibus
terminating
resistor
2 3
5
4
1
B-codiert
5/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
5. Bus wiring via stub
With a transmission rate ≤ 1.5Mbaud.
Profibus
terminating
resistor
X2
X1
1
43
5 2
3 2
5
4 1
X3
X1
2 3
5
4
43
5 2
3 2
5
4 1
1
B-codiert
X2
1
B-codiert
X3
2 3
5
4
1
B-codiert
B-codiert
6. Different configuration menu
The GEMÜ 1436 cPos with Profibus DP has the following expanded configuration menu
compared to the standard 1436 cPos:
SETUP
1
Service
2
SetBasics
SetFunction
3
SetCalibration
4
Communication
Return
5
5.1
6
Fieldbus
DP adrr
26
PwrOnT.Out
Return
DP Adr
Enter the Profibus adress of the positioner.
PwrOnT.Out
Time delay between error detection and error message during switch on
6/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
7. Cyclic Profibus data
Input data: (Profibus  cPos)
Addr. 0
Addr. 2
2
bytes
1
byte
Dig.
Out
Position
Addr. 3
8 bytes
Parameters / Actions / Errors (see page 9)
Output data: (Profibus  cPos)
Addr. 0
Addr. 2
Addr. 4
2
bytes
Set value
2
bytes
Actual value
1
byte
Dig. In
Addr. 5
8 bytes
Parameters / Action / Errors (see page 9)
7.1.
Set value
Profibus  cPos
The set value is transmitted from the master to the cPos in per mille.
Excessive set values (0x11) trigger an external diagnostic error.
0..1000
2 bytes
7.2.
Actual value
Profibus  cPos
The actual value is transmitted from the master to the cPos in per mille.
Excessive actual values (0x13) trigger an external diagnostic error.
0..1000
2 bytes
7/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
7.3.
Digital input
Profibus  cPos
The digital inputs are transmitted from the master to the cPos. There are 4 inputs
available.
0..0x0F
1 byte
CPos parameter
In W
In X
In 1
In 2
Addr. 4.0
Addr. 4.1
Addr. 4.2
Addr. 4.3
7.4.
Valve position
Profibus  cPos
The valve position is transmitted from the cPos to the master in per mille.
In the NoInit state, the position corresponds to the potentiometer range. After the initialisation (InitValve), the position corresponds to the valve area.
0..1000
2 bytes
7.5.
Digital output
Profibus  cPos
The digital outputs are transmitted from the cPos to the master. There are 3 outputs
available.
cPos Parameter
K1
K2
Ext. Diagnose
7.6.
Adr. 2.0
Adr. 2.1
Adr. 2.7
Parameter data: Parameters / Actions / Errors
cPos Profibus
Parameters / Actions / Errors:
Para
Para
Toggel
code
ID
1
1
2
byte
byte
bytes
8 bytes
Para
value
4
bytes
If the same information is sent more than once, the data record needs to be changed via
the toggle byte.
The instructions 0x45, 0x44 and 0x57 to the query should be sent the instruction „N“ (NOP) , so that the query is processed only once.
8/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
7.6.1.
No action
When using the “N” (NOP) instruction, no action is carried out. The response is another
NOP instruction.
Inquiry from the master:
0xYY
0x4E (“N“)
0x00, 0x00
1 byte
1 byte
2 bytes
0x00, 0x00, 0x00, 0x00
4 bytes
Response of the cPos:
0xYY
0x4E (“N“)
1 byte
1 byte
0x00, 0x00, 0x00, 0x00
4 bytes
7.6.2.
0x00, 0x00
2 bytes
Change parameters
The “S“ (SET) instruction enables the change of a parameter in the cPos via the Profibus.
As a response, the cPos returns the SET instruction with the changed parameter value. If
the value is higher than the valid range, an external diagnostic error with code 0x21 is
generated; if below, the error generated has code 0x20.
Where the parameter does not exist, the diagnostic error triggered has code 0x22, and the
value returned is 0.
In case of a parameter change, the new value of the parameter is returned to the master
together with a SET instruction.
Where the parameter does not exist, the value returned is 0.
Inquiry from the master:
0xYY
0x53 (“S“)
ID
1 byte
1 byte
2 bytes
Value of the parameter
4 bytes
Response of the cPos:
0xYY
0x53 (“S“)
1 byte
1 byte
Value of the parameter
4 bytes
ID
2 bytes
The individual parameters of the GEMÜ 1436 cPos are found on page 22.
Ex:
The Mode parameter needs to be changed to Manual.
0xYY
0xYY
0x53 (“S“)
0x53
ID
Mode
0x64
Value of the parameter
Manual
0x00, 0x00, 0x00, 0x02
9/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
7.6.3.
Request parameters
The “G“ (GET) instruction is used to request from the cPos the value of a parameter via
the Profibus. The cPos responds with a GET instruction containing the parameter value.
Where the parameter does not exist, an external diagnostic error with code 0x22 is triggered.
Inquiry from the master:
0xYY
0x47 (“G“)
ID
1 byte
1 byte
2 bytes
0x00 0x00 0x00 0x00
4 bytes
Response of the cPos:
0xYY
0x47 (“G“)
1 byte
1 byte
Value of the parameter
4 bytes
ID
2 bytes
When the parameter value in the GEMÜ 1436cPos changes, it is
immediately sent to the Profibus master. There is no need to
continuously request the parameter.
7.6.4.
Read error list
The error list is requested using the “E“ (Error List) instruction.
Inquiry from the master:
0xYY
0x45 (“E“)
Serial number of error
in the list
1 byte
1 byte
2 bytes
0x00, 0x00, 0x00, 0x00
4 bytes
The last error is requested with 0x00 0x00
Response of the cPos:
0xYY
0x45 (“E“)
1 byte
1 byte
Serial number of error
in the list
2 bytes
Error information
4 bytes
10/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Attention:
 When a new error occurs, the serial numbering of the listed errors changes.
Error 0 then becomes Error 1, Error 1 becomes Error 2, etc.
 Once the error list is full, the oldest error in the list is deleted.
 If no entry on the required number is found in the error list, the response value is 0xFF 0xFF 0xFF 0xFF
 With number 0 the current error can be monitored
 If there is no error in the error list, error 0x00 0x00 0x00 0x00 is displayed
7.6.5.
Amount of active errors and readout of the active error
The “D“ instruction is used to request the amount of active errors and the active error selected using the ID.
Inquiry from the master:
0xYY
0x44 (“D“)
Number of
active error
1 byte
1 byte
2 bytes
0x00, 0x00, 0x00, 0x00
4 bytes
The first error are demanded with the number 0x00 0x01
Response of the cPos:
0xYY
0x44 (“D“)
1 byte
1 byte
Number of
active error
Amount of active errors
2 bytes
4 bytes
Value of active
error (selected
via ID)
Example:
The potentiometer of the cPos moves in the wrong direction,
i.e. error code “020: Pot Wrong Dir“ is active.
Inquiry from the master:
0x00
0x44
0x00, 0x01
0x00, 0x00, 0x00, 0x00
Response of the cPos:
0x00
0x44
0x00, 0x01
0x00, 0x01, 0x00, 0x14
11/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
7.6.6.
Amount of active warnings and readout of the active warning
The “W“ instruction is used to request the amount of active warnings and the active warning selected using the ID.
Inquiry from the master:
0xYY
0x57 (“W“) Number of
active error
1 byte
1 byte
2 bytes
0x00, 0x00, 0x00, 0x00
4 bytes
The first warning are demanded with the number 0x00 0x01
Response of the cPos:
0xYY
0x57 (“W“)
1 byte
1 byte
Number of
active error
Amount of active errors
2 bytes
4 bytes
Value of active
error (selected
via ID)
Example:
It is a failure of the compressed air has been discovered, i.e. the error "030: Missing Air" is
active.
Inquiry from the master:
0x00
0x57
0x00, 0x01
0x00, 0x00, 0x00, 0x00
Response of the cPos:
0x00
0x57
0x00, 0x01
0x00, 0x01, 0x00, 0x1E
7.6.7.
Error list
NO ERROR
PotWrongDir
Parameter
ID
Hex
0x00 0x00
0x00 0x14
Parameter
ID
Dec
0
20
Wrong Func.
0x00 0x15
21
Pneumatic
0x00 0x16
22
Leckage
Air missing
Bus Fault
TrvlSensErr
0x00 0x17
0x00 0x1E
0x00 0x28
0x00 0x3C
23
30
40
60
Error name
Description
There are no errors
The potentiometer has recognised the wrong control function
during initialisation
An incorrect control function was recognised during automatic initialisation
A failure in the pneumatic was recognised during automatic
initialisation
A leakage was recognised during automatic initialisation
A failure of the compressed air was discovered
Bus fault are detected
A cable break, short-circuit or exceeded range in the travel
sensor connection or in the travel sensor was detected
12/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
7.6.8.
Trigger action in the cPos
The ”A“ (Action) instruction is used to trigger an action in the cPos. Depending on the action to be triggered, additional parameters may be required.
As long as an action is active, no other action may be triggered. Where this is attempted,
the cPos will ignore the new action and generate an external diagnostic error with code
0x40.
Inquiry from the master:
0xYY
0x41 (“A“)
ID
1 byte
1 byte
2 bytes
Parameter
4 bytes
Only one action may be active at a time. If no action is active, the cPos
responds as described in the individual actions.
If an action is active, the field bus will create the following response:
Response of the cPos:
0xYY
0x41 (“A“)
1 byte
1 byte
ID
2 bytes
0xFF
1 byte
Source
1 byte
Number
2 bytes
Source:
Active action was started via the GEMÜ 1436 cPos keypad.
 Acknowledge (quit) at the GEMÜ 1436 cPos
Active action was started via the e.sy-com interface of the GEMÜ 1436
cPos.
 Close active browser window
Active action was started via the field bus.
 Quit with instruction "Q" or
 Select action again and quit
0x01
0x02
0x03
Number:
If the Profibus knows the action, the number is displayed here ( see 7.6.7 ... 7.6.16).
If an action which is unknown to the Profibus is active, "0" is displayed here.
7.6.9.
Quit Feldbus Event
The instruction "Q" (Quit) is used to stop an active event.
This event acknowledges all active events activated via the field bus.
Inquiry from the master:
0xYY
0x51 („Q“) 0x00 0x00
1 Byte
1 Byte
2 Byte
0x00 0x00 0x00 0x00
4 Byte
Response of the cPos:
0xYY
0x51 („Q“)
1 Byte
1 Byte
0x00 0x00 0x00 0x00
4 Byte
0x00 0x00
2 Byte
13/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
7.6.10.
NoInit
With “NoInit“, the valve can be opened and closed manually if not yet initialised.
Where this action is activated once the valve has been initialised, the cPos will generate
an external diagnostic error with code 0x42.
Instruction from the master:
0xYY
0x41 (“A“)
0x00, 0x01
1 byte
1 byte
2 bytes
Function:
Stop valve
Open slowly
Open quickly
Close slowly
Close quickly
Open with PWM [0..1000]
Close with PWM [0..1000]
End event
Function
4 bytes
0x00, 0x00, 0x00, 0x00
0x01, 0x00, 0x00, 0x00
0x02, 0x00, 0x00, 0x00
0x03, 0x00, 0x00, 0x00
0x04, 0x00, 0x00, 0x00
0x05, 0x00, PWM High, PWM Low
0x06, 0x00, PWM High, PWM Low
0x07, 0x00, 0x00, 0x00
Attention: The direction relates to a control function 1 valve. If the cPos is set
up on a control function 2 valve, the valve will move in the opposite direction.
The status reported is the current valve function selected.
Response of the cPos:
0xYY
0x41 (“A“)
1 byte
1 byte
Status:
Stop valve
Open slowly
Open quickly
Close slowly
Close quickly
Open with PWM [0..1000]
Close with PWM [0..1000]
End event
0x00, 0x01
2 bytes
Status
4 bytes
0x00, 0x00, 0x00, 0x00
0x01, 0x00, 0x00, 0x00
0x02, 0x00, 0x00, 0x00
0x03, 0x00, 0x00, 0x00
0x04, 0x00, 0x00, 0x00
0x05, 0x00, PWM High, PWM Low
0x06, 0x00, PWM High, PWM Low
0x07, 0x00, 0x00, 0x00
14/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
7.6.11.
Clear Error List
This action clears the entries from the error list.
Instruction from the master:
0xYY
0x41 (“A“)
0x00, 0x02
1 byte
1 byte
2 bytes
0x00, 0x00, 0x00, 0x00
4 bytes
Response of the cPos:
0xYY
0x41 (“A“)
1byte
1 byte
Status
4 bytes
0x00, 0x02
2 bytes
Status:
Error list cleared (action is ended)
Error list not cleared (action remains active)
7.6.12.
0x00, 0x00, 0x00, 0x01
0x00, 0x00, 0x00, 0x02
Set Default
This action sets the cPos to the default state.
Instruction from the master:
0xYY
0x41 (“A“)
0x00, 0x03
1 byte
1 byte
2 bytes
0x00, 0x00, 0x00, 0x00
4 byte
Response of the cPos:
0xYY
0x41 (“A“)
1 byte
1 byte
Status
4 bytes
0x00, 0x03
2 bytes
Status:
Default setting loaded (action is ended)
Default setting not loaded (action remains active)
0x00, 0x00, 0x00, 0x01
0x00, 0x00, 0x00, 0x02
15/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
7.6.13.
Init valve
This action initialises the valve. The cPos here determines the open and closed position. It
then checks the current control function and subsequently measures the opening and closing times and the valve characteristics.
Then the internal pilot valves are measured
Instruction from the master:
0xYY
0x41 (“A“)
0x00, 0x04
1 byte
1 byte
2 bytes
Function:
Start initialisation
Cancel initialisation
Quit Error
Response of the cPos:
0xYY
0x41 (“A“)
1 byte
1 byte
Function
4 bytes
0x00, 0x00, 0x00, 0x01
0x00, 0x00, 0x00, 0x02
0x00, 0x00, 0xFF, 0x00
0x00, 0x04
2 bytes
Status
4 bytes
In the status, the cPos reports the action currently taken.
Status:
Initialisation inactive
0x00, 0x00, 0x00, 0x00
Close position determined
0x00, 0x00, 0x00, 0x01
Open position determined
0x00, 0x00, 0x00, 0x02
Valve control function determined
0x00, 0x00, 0x00, 0x03
Opening and closing times measured
0x00, 0x00, 0x00, 0x04
Valve characteristics charted
0x00, 0x00, 0x00, 0x05
Pilot valves are measured
0x00, 0x00, 0x00, 0x06
Init Error 22 active
0x00, 0x00, 0x16, 0xFE
Init Error 22 receipt
0x00, 0x00, 0x16, 0xFF
Init Error 20 active
0x00, 0x00, 0x14, 0xFE
Init Error 20 receipt
0x00, 0x00, 0x14, 0xFF
Init Error 23 active
0x00, 0x00, 0x17, 0xFE
Init Error 23 receipt
0x00, 0x00, 0x17, 0xFF
Action can not be started
0x01, 0x00, 0x00, 0x00
16/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
7.6.14.
GoClose
Control function 1 moves the valve to the closed position.
Control function 2 moves the valve to the open position.
Once the valve is in the required position, this needs to be communicated to the cPos.
This then takes the position as “closed“.
Instruction from the master:
0xYY
0x41 (“A“)
0x00, 0x05
1 byte
1 byte
2 bytes
Function
4 bytes
Function
Go to closed position
In closed position
Cancel Close function
0x00,0x00,0x00,0x01
0x00,0x00,0x00,0x02
0x00,0x00,0x00,0x03
Response of the cPos:
0xYY
0x41 (“A“)
1 byte
1 byte
0x00, 0x05
2 bytes
Status:
Go to closed position
In closed position
Cancel Close function
Action can not be started
7.6.15.
Status
4 bytes
0x00,0x00,0x00,0x01
0x00,0x00,0x00,0x02
0x00,0x00,0x00,0x03
0x01, 0x00, 0x00, 0x00
GoOpen
Control function 1 moves the valve to the open position.
Control function 2 moves the valve to the closed position.
Once the valve is in the required position, this needs to be communicated to the cPos.
This then takes the position as “open”.
Instruction from the master:
0xYY
0x41 (“A“)
0x00, 0x06
1 byte
1 byte
2 bytes
Function:
Go to open position
In open position
Cancel Open function
Function
4 bytes
0x00,0x00,0x00,0x01
0x00,0x00,0x00,0x02
0x00,0x00,0x00,0x03
17/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Response of the cPos:
0xYY
0x41 (“A“)
1 byte
1 byte
Status:
Go to open position
In open position
Cancel Open function
Action can not be started
7.6.16.
0x00, 0x06
2 bytes
Status
4 bytes
0x00,0x00,0x00,0x01
0x00,0x00,0x00,0x02
0x00,0x00,0x00,0x03
0x01, 0x00, 0x00, 0x00
Find function
This action determines the control function of the valve and the air flow of the inner pilot
valves. When control function 2 is determined, the cPos swaps the open and closed positions so that the 0% displayed corresponds to the Closed position and 100% to the Open
position.
Instruction from the master:
0xYY
0x41 (“A“)
0x00, 0x07
1 byte
1 byte
2 bytes
Function:
Activate Find function
Cancel Find function
Response of the cPos:
0xYY
0x41 (“A“)
1 byte
1 byte
Function
4 bytes
0x00,0x00,0x00,0x01
0x00,0x00,0x00,0x02
0x00, 0x07
2 bytes
Status
4 bytes
In the status, the cPos reports the current action taken.
Status:
Find Function inactive
0x00,0x00,0x00,0x01
Go to Start position
0x00,0x00,0x00,0x02
Output test pattern
0x00,0x00,0x00,0x03
Action can not be started
0x01, 0x00, 0x00, 0x00
7.6.17.
Adjust time
This action moves the valve to the Closed and the Open positions while determining the
opening and closing times.
Instruction from the master:
0xYY
0x41 (“A“)
0x00, 0x08
1 byte
1 byte
2 bytes
Function
4 bytes
18/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Function:
Activate Adjust Time
Cancel Adjust Time
Quit error
Response of the cPos:
0xYY
0x41 (“A“)
1 byte
1 byte
0x00,0x00,0x00,0x01
0x00,0x00,0x00,0x02
0x00,0x00,0xFF,0x00
0x00, 0x08
2 bytes
Status
4 bytes
In the status, the cPos reports the current action taken.
Status:
Adjust Time inactive
0x00,0x00,0x00,0x01
Go to Start position
0x00,0x00,0x00,0x02
cPos times “go Close“
0x00,0x00,0x00,0x03
cPos times “go Open“
0x00,0x00,0x00,0x04
Error 22 active
0x00, 0x00, 0x16, 0xFE
Error 22 receipt
0x00, 0x00, 0x16, 0xFF
Action can not be started
0x01, 0x00, 0x00, 0x00
7.6.18.
Find Coefficient
This action determines the valve characteristics at the specified calibration points. For this,
the valve approaches these points several times.
Instruction from the master:
0xYY
0x41 (“A“)
0x00, 0x09
1 byte
1 byte
2 bytes
Function:
Activate Find Coefficient
Cancel Find Coefficient
Error receipt
Response of the cPos:
0xYY
0x41 (“A“)
1 byte
1 byte
Function
4 bytes
0x00,0x00,0x00,0x01
0x00,0x00,0x00,0x02
0x00,0x00,0xFF,0x00
0x00, 0x09
2 bytes
Status
4 bytes
In the status, the cPos reports the current action taken.
Status:
Find Coefficient inactive
0x00, 0x00, 0x00, 0x01
Go to calibration point
0x00, 0x00, calibration point, 0x02
Error 22 active
0x00, 0x00, 0x16, 0xFE
Error 22 receipt
0x00, 0x00, 0x16, 0xFF
Action can not be started
0x01, 0x00, 0x00, 0x00
19/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
7.6.19.
Init Pilot
The action measures the internal pilot valves. For this, the minimum travel of the process
valve is determined.
Instruction from the master:
0xYY
0x41 („A“)
0x00, 0x0A
1 byte
1 byte
2 bytes
Function:
Activate Init Pilot
Cancel Init Pilot
Response of the cPos:
0xYY
0x41 („A“)
1 byte
1 byte
Function
4 bytes
0x00,0x00,0x00,0x01
0x00,0x00,0x00,0x02
0x00, 0x09
2 bytes
Status
4 bytes
In the status, the cPos reports the current action taken.
Status:
Init Pilot not active
0x00, 0x00, 0x00, 0x01
Init Pilot active
0x00, 0x00, 0x00, 0x02
Error 22 active
0x00, 0x00, 0x16, 0xFE
Error 22 receipt
0x00, 0x00, 0x16, 0xFF
Error 23 active
0x00, 0x00, 0x17, 0xFE
Error 23 receipt
0x00, 0x00, 0x17, 0xFF
Action can not be started
0x01, 0x00, 0x00, 0x00
20/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
8. External diagnostic errors
Defined error messages:
0x01
0x02
0x03
0x04
0x05
0x07
0x08
0x09
0x0A
0x0B
0x0D
0x0E
0x10
0x11
0x12
0x13
0x20
0x21
0x22
0x30
0x31
0x32
0x33
0x34
0x40
0x42
0x43
Data length service data from master to slave incorrect or
hardware error
Data length service data from slave to master incorrect or
EEROM error
Internal memory error
Fieldbus hardware error or wrong fieldbus ID
Script error
RS transmitter buffer overflow
RS receiver buffer overflow
RS Timeout
General fieldbus error
Parity- or frame check error
Fieldbus configuration error
Fieldbus data buffer overflow
Specified set value too low
Specified set value too high
Specified actual value too low
Specified actual value too high
Specified parameter value too low
Specified parameter value too high
Parameter does not exist
Error in cPos
Error in cPos acknowledged
Warning in cPos
Warning in cPos acknowledged
No error list entry on the requested number available
In the 1436 an action is active which was activated by the fieldbus.
Therefore no new action can be triggered
This action is currently not available
Action doesn‘t exist
21/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
9. Parameter Numbers
Parameter
Parameter
ID
Hex
0x00, 0x64
Parameter
ID
Dec
100
Access
Write
0:
1:
2:
3:
4:
03E8
1000
Read
Pot Min
Pot Max
Proc W *
Proc X *
Pos W
Pos X
Pot Abs
Pos Ctrl Out
Proc Ctrl Out
Diagnosis
Operating hour
Operating minute
Operating second
Warnings
03E9
03EA
03EB
03EC
03ED
03EE
03EF
03F0
03F1
1001
1002
1003
1004
1005
1006
1007
1008
1009
Read
Read
Read
Read
Read
Read
Read
Read
Read
0:
P1
1:
P2
2:
P3
3:
P4
[0..1000] *0,1 %
[0..1000] *0,1 %
[0..1000] *0,1 %
[0..1000] *0,1 %
[0..1000] *0,1 %
[0..1000] *0,1 %
[0..1000] *0,1 %
[-1000..1000] *0,1 %
[0..1000] *0,1 %
044C
044D
044E
044F
1100
1101
1102
1103
Read
Read
Read
Write
Errors
0450
1104
Write
SensTest
0451
1105
Write
SetBasics
CalPointQty
D.Refresh
Dlight
07D0
07D1
07D2
2000
2001
2002
Write
Write
Write
AutoReturn
HelpLanguage
07D3
07D4
2003
2004
Write
Write
Helptext
07D5
2005
Write
PwrOnMode
07D6
2006
Write
Mode
Value range
OFF
Auto
Manual
Manual-Flex
Test
SETUP
Service
I/O Status
ActiveParaSet
[0..99 999] h
[0..59] min
[0..59] s
0:
ON
1:
OFF
0:
ON
1:
OFF
0:
Disable
1:
Enable1
[1..19]
[1..10] *0,1s
0:
ON
1:
ON Key
[1..60] min
0:
D
1:
GB
0:
ON
1:
OFF
0:
Fast
1:
Safe
* only available with version with integrated process controller
22/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
SetBasics
Init Valve
CtrlFn
0834
2100
Write
adjtTimeClose
adjTimeOpen
0835
0836
2101
2102
Read
Read
SetFunction
ProcCtrlMode *
0BB8
3000
Write
DeadBand
CpyParaSet
0BB9
0BBA
3001
3002
Write
Write
ProcCtrl
Proc-P *
Proc-I *
Proc-D *
Proc-T *
IxType
0C1C
0C1D
0C1E
0C1F
0C20
3100
3101
3102
3103
3104
Write
Write
Write
Write
Write
0C21
3105
Write
[0..1000]*0,1
[0..9999]*0,1s
[0..1000]*0,1
[1..10 000] ms
0:
OFF
1:
RC
2:
avr
[10...2000] *0,01s
0:
NC
1:
NO
2:
DA
3:
Boost NC
4:
Boost NO
5:
Auto
6:
Auto NC
7:
Auto NO
8:
Auto DA
9:
Auto NC B
10:
Auto NO B
[0..999] *0,1s
[0..999] *0,1s
0:
OFF
1:
ON
[1..250] *0,1%
0:
OFF
1:
P1<=W
2:
P1=>P2
3:
P1<=P2
4:
P1=>P3
5:
P1<=P3
6:
P1=>P4
7:
P1<=P4
IxFilter
PosCtrl
Pos P
Pos D
Pos T
MinPos
MaxPos
closeTight
openTight
Digital Input
In W
0C80
0C81
0C82
0C83
0C84
0C85
0C86
3200
3201
3202
3203
3204
3205
3206
Write
Write
Write
Write
Write
Write
Write
[0..1000] *0,1
[0..1000] *0,1
[1..5000] ms
[0..1000] *0,1 %
[0..1000] *0,1 %
[0..200] *0,1 %
[800..1000] *0,1 %
0CE4
3300
Write
In X
0CE5
3301
Write
0:
1:
2:
3:
4:
5:
0:
1:
2:
3:
4:
5:
OFF
OFF/ON
Save/ON
ParamSetB0
ParamSetB1
Poti/Ix
OFF
OFF/ON
Save/ON
ParamSetB0
ParamSetB1
Poti/Ix
* only available with version with integrated process controller
23/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
SetFunction
Digital Input
In 1
0CE6
3302
Write
In 2
0CE6
3303
Write
Digital Output
K1 Switch
0D48
3400
Write
K1 Fn
0D49
3401
Write
AlarmMinK1
AlarmMaxK1
SSE1Time
K2 Switch
0D4A
0D4B
0D52
0D4C
3402
3403
3410
3404
Write
Write
Write
Write
K2 Fn
0D4D
3405
Write
AlarmMinK2
AlarmMaxK2
SSE1Time
ErrorTime
ErrorAction
0D4E
0D4F
0D53
0D50
0D51
3406
3407
3411
3408
3409
Write
Write
Write
Write
Write
0:
1:
2:
3:
4:
5:
0:
1:
2:
3:
4:
5:
OFF
OFF/ON
Save/ON
ParamSetB0
ParamSetB1
Poti/Ix
OFF
OFF/ON
Save/ON
ParamSetB0
ParamSetB1
Poti/Ix
0:
NO
1:
NC
0:
No
1:
P min
2:
P max
3:
P min/max
4:
W min
5:
W max
6:
W min/max
7:
X min
8:
X max
9:
X min/max
10:
Active
11:
Error
12:
Warning
13:
SSE min
14:
SSE max
15:
SSE min/max
[2..998] *0,1%
[2..998] *0,1%
[1..1000] *0,1s
0:
NO
1:
NC
0:
No
1:
P min
2:
P max
3:
P min/max
4:
W min
5:
W max
6:
W min/max
7:
X min
8:
X max
9:
X min/max
10:
Active
11:
Error
12:
Warning
13:
SSE min
14:
SSE max
15:
SSE min/max
[2..998] *0,1%
[2..998] *0,1%
[1..1000] *0,1s
[2..1000] *0,1s
0:
Close
1:
Open
2:
Hold
24/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
SetCalibration
X-Direction *
0FA0
4000
Write
W-Direction
0FA1
4001
Write
W-Function
0FA2
4002
Write
Y-Direction*
0FA3
4003
Write
Pot Dir
0FA4
4004
Write
OutMinPos
OutMaxPos
Set W free
W 0%
W 10%
W 20%
W 30%
W 40%
W 50%
W 60%
W 70%
W 80%
W 90%
W 100%
Scaling
Scaling
0FA5
0FA6
4005
4006
Write
Write
0:
rise
1:
fall
0:
rise
1:
fall
0:
lin.
1:
1:25
2:
1:50
3:
free
0:
rise
1:
fall
0:
rise
1:
fall
[0..1000] *0,1 %
[0..1000] *0,1 %
1004
1005
1006
1007
1008
1009
100A
100B
100C
100D
100E
4100
4101
4102
4103
4104
4105
4106
4107
4108
4109
4110
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
[0..1000] *0,1 %
[0..1000] *0,1 %
[0..1000] *0,1 %
[0..1000] *0,1 %
[0..1000] *0,1 %
[0..1000] *0,1 %
[0..1000] *0,1 %
[0..1000] *0,1 %
[0..1000] *0,1 %
[0..1000] *0,1 %
[0..1000] *0,1 %
1068
4200
Write
Decimal point
4mA≙
1069
106A
4201
4202
Write
Write
0:
OFF
1:
ON
[0..2]
[-999..9999]
20mA≙
106B
4203
Write
[-999..9999]
Communication
Field bus\DP Adr
PwrOnT.Out
13EC
13ED
5100
5101
Write
Write
[1..126]
0...300 s
* only available with version with integrated process controller
25/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
10.
Configuration example using SIEMENS S7
Start SIMATIC Manager and click on “Next“ to continue
Select SPS type and click on “ Next“ to continue
26/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Insert new module and click on “ Next“ to continue
Enter project name and create project by clicking on “Finish“
27/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Open new project
Open folder
28/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Configure project (double-click)
Activate window with double-click
29/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Install new GSD file (G1436a.GSD)
30/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
The GSD file is on the CD Rom supplied with every controller
31/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Select “DP“ line
Select “New“
32/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Select transmission speed and confirm with “OK“
Click on “OK“
33/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Drag selection into window
34/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Set Profibus address of the GEMÜ 1436 cPos (default setting 26)
Set Profibus address (26)
35/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Select outputs (click and drag into table)
ATTENTION! Only 1 configuration
Select inputs (click and drag into table)
ATTENTION! Only 1 configuration
The GEMÜ 1436 cPos identifies the configuration on the basis of the block length. No settings required.
36/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Save settings
Input addresses (no action)
Output addresses (no action)
Load configuration in SPS.
37/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
38/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Program OB1
39/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Ex. Input valve position and output to outputs.
ATTENTION! Addresses above 127 must be accessed using PEW, PEB, PAW, PAB....
40/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Confirm by clicking on “Yes“
41/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Create new organisation module
42/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Errors are trapped in organisation module OB82.
ATTENTION! This operation module must be generated.
43/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
No storage of function required
44/45
Operating instructions Profibus DP
Intelligent positioner 1436 cPos
Manufacturer’s declaration
According to the EC Machine Directive 98/37/EC, Appendix II B
We hereby declare that the device described in this specification is intended for installation
in a machine or application whose commissioning is prohibited until it has been determined that this machine/application conforms to EC Directive 98/37/EC.
Subject to technical alterations · 02/2014 · 88306078
Handling, assembly and commissioning, in addition to setting and adjustment of the machine must be performed only by authorized specialist staff.
45/45