MCSet 24kV(brochure)

MCSet 24kV(brochure)
Bringing enhanced reliability
and simplicity to MV networks
MCset up to 24 kV
air-insulated MV switchgear
SF6 withdrawable circuit breakers
Energy
& Infrastructure
Industry
Safety
2
Simplicity
Reliability
MCset switchgear: Designed for quality,
reliability, and ease-of-use
MCset switchgear are made up of several interconnected functional units:
> The power connections are made
between the functional units within
a switchboard via a single busbar.
> Low voltage wiring trays are provided
in the switchboard above the low
voltage control cabinets.
> The electrical continuity of all the metal
frames is provided by the connection
of each functional unit’s earthing
busbar to the switchgear’s main
earthing circuit.
> Low voltage cables can enter the
switchboard through the top or bottom
of each functional unit.
Busbar compartment
This section connects
the switchgear cubicles
via busbars.
Low voltage cabinet
This section includes:
• the Sepam or MiCOM protection
relay and control unit,
• the low voltage components, and
• the thermal diagnosis module.
Switchgear compartment
This section contains the medium
voltage protection devices, including:
• SF6 breaking devices (circuit
breakers, fuse-contactors),
• lever-type propulsion mechanism
for racking in-out, and
• interlocks to anchor the
withdrawable part.
Cable compartment
This compartment, located in the lower
part of the cubicle, includes:
• the earthing switch,
• the current sensors (LV type CTs, magnetic
or non-magnetic transformers) and
voltage transformers.
3
Why should you choose MCset
air-insulated MV switchgear?
MCset provides exceptional performance
and outstanding reliability, helping
to ensure service continuity for your
networks with proven technology
that’s both easy to use and to maintain.
And, with an industry reputation for
both quality and reliability, MCset
brings added peace of mind to the
operator of any installation.
Safety
> Operations and indications are concentrated on the front
of the switchgear
> Racking in and out is only possible with the door closed
> The earthing switch has making capacity
> Internal arc withstand developed for most of the functional units
> Designed with environmental protection in mind
4
>L
SC 2B (Loss of Service Continuity category) cubicle.
Metal barriers: class PM
Simplicity
> A clear user interface which is easily understood
> Interlocks and padlocks preventing operator errors
> Easy on-site control & monitoring
> Limited and simple maintenance for years
> Easy installation thanks to compactness
> Sepam or MiCOM protection units enabling on-site information
retrieval without any additional devices
Reliability
> The design, manufacturing, and testing are carried out according
to ISO 9001 and 9002 standards
> Design is ensured by advanced computer modeling techniques
> Compliant with main IEC standards as 62271-200 as well as
standards specific to individual countries and applications
> Type testing is also carried out in accordance with main
IEC standards
Exceptional performance,
outstanding reliability
ISO 9001 and 9002 certified quality
Each Schneider Electric site has a functional department whose main mission is to check
quality and ensure compliance with the standards.This system gives you the guarantee
achieved by the system is recognised by a large number of customers and officially approved
organisations.The strict, measured implementation of the system has been acknowledged
by an independant organisation:
> the AFAQ (French Quality Assurance Association) certification.
> The MCset switchgear’s quality system for design and manufacturing is certified
according to the requirements of the ISO quality assurance standards.
Certified
quality under
ISO 9001 and
ISO 9002
Performance through systematic testing
During manufacturing, each cubicle undergoes systematic routine testing aimed
at checking quality and conformity:
> testing of circuit breaker and contactor tightness,
>m
easurement of closing and opening speeds,
> measurement of operating torque,
> dielectric testing,
> testing of safety systems and interlocks,
> testing of low voltage components,
> conformity of drawing and diagrams
The results are recorded and initialed by the quality control department
on the test certificate for each device.
A COMMITMENT TO HIGH STANDARDS
> Type testing is carried out for each performance level
> Design is ensured by advanced computer modeling techniques
> Environmental management system of industrial sites, in compliance with the requirements
of ISO 14001 standard
5
Experience you can depend on
As the result of our extensive worldwide
experience, MCset also provides you
with a high level of reliability, simplicity,
and safety. It is particularly suitable for
infrastructure and large industrial sites,
and is intended for use in MV sections
of HV/MV substations and high-power
MV/MV substations.
Our references
With its strong reputation, MCset has become the switchgear trusted by those who supply
the most critical installations and need to ensure uninterrupted service:
6
Oil & Gas
Marine
Power
generation
Girassol Mpg-Elf
Angola
ONAL
Gabon
Alya Co
Kazakhstan
Tengizchevroil
Kazakhstan
Occidental Mukhaizna LLC
Oman
Qatar Petroleum
Qatar
Repsol, Santander
Spain
Syrian Gas Company
Syria
Turkmengaz
Turkmenistan
Abu Dhabi Oil Refining Company
United Arab Emirates
Yemen LNG Company
Yemen
Yemgas – Technip
Yemen
Jan De Nul
Zhenhua Port Machinery
FREMM
Conti Reederei
MSC
M.O.L.
STX Shipyard
CPOC
Sovcomflot
TMT
British Gas
Norwegian Cruise Line
Belgium
China
France
Germany
Italy
Japan
Korea
Malaysia
Russia
Taiwan
United Kingdom
USA
Sonelgaz
Moranbah Generation Facility
China Nuclear Power programmes
CEA Cadarache
Enertherm
Wind Turbines
La Termica
Al Fanar Electrical System
Skagerak Nett AS
EVN thermal power station
Algeria
Australia
China
France
France
France
Italy
Saudi Arabia
Norway
Vietnam
Transport
infrastructure
Italian Railways
Alicante airport
Port of Laem Chabang
Italy
Spain
Thailand
New Islands Project
Hamilton Island
Al Bustan Palace Hotel
Abu Dhabi
Australia
Oman
Algérienne des eaux
Water treatment, Degremont
Alcoa Aluminium
Croesus Mining
Rolleston Coal Pty LTD
Garadagh Cement
Volvo
Cement Lafarge
Cement Lafarge
Ford
Iraq water treatment
Arab Union Contracting Company
Arcelor
Opel
Bastas Cement
Algeria
Argentina
Australia
Australia
Australia
Azerbaijan
Belgium
Equator - Turkey
France
Germany
Iraq
Libya
Luxemburg
Russia
Turkey
Buildings
Industry
SF6
The dielectric rigidity and the remarkable cut-off characteristics of this gas have made SF6
devices valuable worldwide since the middle of the 1950s. Since then, design refinements in
terms of waterproofing and SF6 end-of-life processing have further reinforced their credibility.
MCset is an indoor switchgear assembly that provides maximum
user safety. It is intended to meet all electrical distribution needs
from 1 to 24 kV and incorporates a set of innovative solutions
designed using proven techniques:
> high-performance breaking devices (SF6),
> digital protection and control system,
> a range of cubicles designed and tested for internal arc resistance.
7
MCset main characteristics
Rated voltage
Ur
(kV)
7.2
12
17.5
24
Ud
(r ms kV)
20
28
38
50
(kV peak)
60
75
95
125
Rated insulation level
Power frequency withstand voltage
50 Hz - 1 min
Lightning impulse withstand voltage Up
1.2/50 µs
Rated normal current and maximum short time withstand current (1)
Functional unit with circuit breaker
Short time withstand Ik max.
current
8
Ik/tk
(kA/3 s)
25
25
25
16
31.5
31.5
31.5
25
40
40
40
31.5
50 (6)
50 (6)
Rated current
Ir max. busbar Ir
(A)
4000
4000
4000
2500 (7)
Rated current
Ir CB
Ir
(A)
1250
1250
1250
630
2500
2500
2500
1250
3150
3150
3150
2500
4000 (2)
4000 (2)
4000 (2)
(kA)
50 (4)
50 (4) (5)
(A)
250
200 (5)
Functional unit with fuse-contactor (3)
Short time withstand Ik max.
current
(prospective value) (9)
Rated current
Ir max.
Functional unit with switch-fuse combination (DI cubicle) (8)
Rated current according to the fuses installed, see documentation
Rated current
Ir max. y
(A)
200
200
200
200
50
50
25
Internal arc classification (maximum value IA and tA)
(kA/1 s)
50
(kA/0.15 s)
31.5
Degree of protection
IP3X
IP4X (7)
IPX2
IP3X
IP4X
IPX1 (7)
The values above are given for the normal operating conditions as defined in IEC 62271-200 and 62271-1
1). For functional units equipped with circuit breakers or fuse-contactors, the breaking capacity is equal to the short time withstand
current. In all cases, the device peak making capacity is equal to 2.5 times the short time withstand current. 2). With fan.
3). Lightning impulse dielectric withstand voltage = 60 kV peak 4). Limited by fuses (prospective value) 5). With Rollarc contactor
6). Limited to 1 s for in-circuit breaker: 1250 A. 7). For higher performance, consult us. 8). According to IEC 62271-105, combinations
do not have a rated short time withstand current. 9). In accordance with IEC 62271-106.
Please consult us for more information on technical characteristics.
Enhanced safety for your staff
and operations
High-level protection of people
MCset is designed to protect users through
its resistance to faults due to internal
arcing. MCset offers several options for
switchboard layouts:
> Three-sided internal arc protection:
installation of a switchboard against a wall,
> Four-sided internal arc protection:
installation of a switchboard requiring rear
access in the middle of a room.
Built for ease of servicing
Each section is isolated from the others
by earthed, metal partitions. This means
that servicing can be carried out in one
of the compartments while the others are
still energised. The earthing switch has full
making capacity and provides total user
protection in the event of closing on a dead
short-circuit.
9
Safe operation
The risks of operating errors are rigorously
ruled out with MCset. In fact, the range offers
an unprecedented level of user protection
against risks that might otherwise occur
during operation. To summarise, the MCset
design prioritizes to four points:
> simple use,
> clear, reliable status information,
> safety interlocking,
> safety systems that prevent all
unauthorised operations.
Simplicity of design
The user interface is easy to understand.
The user is guided through icon-diagrams on
each front panel making it easy to understand
the operating sequence and devices status.
Easy installation thanks to compactness.
Reduced maintenance and reduced probability of failure with
thermal diagnosis system
Specially designed for Schneider Electric MV
equipment, our thermal diagnosis system
continuously monitors the switchgear
temperature, using optical fibres and sensors
installed at the heart of the sensitive areas.
Thermal diagnosis is based on the principle
of temperature measurement of energised
circuits. By using optical fibres, the system
does not introduce any risks in terms of
insulation. It provides:
> permanent monitoring of the temperature
rise in power circuits at the connections
> tripping of a pre-alarm, then an alarm by
activating dry contact outputs
> indication of the zone and circuit involved
An adaptable range to meet your needs
With five functions available in
13 functional units*, MCset has a
comprehensive range of functions
to suit all requirements of a variety
of applications.
The tables below can be used to link
the requirements to functional units
and provide basic information on
the general composition of each unit.
Incomer/feeder
• line (LI-B, LF-B)
• transformer
(TI-B, TF-B, TF-S)
• generator (GI-B)
busbar
LV cabinet
withdrawable part
current sensors
earthing switch
voltage transformers
MV connections
• motor (MF-B, MF-C)
• capacitor (CB-B, CB-C)
busbar
LV cabinet
withdrawable
fuse-contactor
current sensors
earthing switch
voltage transformers
MV connections
Feeder (motor, capacitor)
10
Bus-sectioning
• switchboard (BS-B)
• substation (SS-B)
busbar
LV cabinet
withdrawable part
current sensors
voltage transformers
Metering and busbar earthing
• switchboard (BB-V)
* possibility of Transition cubicle for MCC application (Motorpact)
busbar
LV cabinet
earthing switch
voltage transformers
11
Delivering
innovative
products,
services,
and solutions
worldwide
©2013 Schneider Electric. All Rights Reserved.
Make the most of your energySM
Schneider Electric Industries SAS
Head Office
35, rue Joseph Monier
CS 30323
92506 Rueil-Malmaison Cedex
France
www.schneider-electric.com
998-1209735_GMA-GB
Date: 06/2013