- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Sanyo
- 3-WAY ECO-i RCS-TM80BG
- User manual
- 10 Pages
Sanyo 3-WAY ECO-i RCS-TM80BG outdoor unit maintenance remote User manual
The 3-WAY ECO-i RCS-TM80BG is a special remote controller designed for use during service and test runs of the outdoor unit. It provides access to various settings and monitoring functions, including EEPROM data, alarm history, temperatures, and unit connection status. This manual provides detailed instructions on using the controller's functions.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
1. Overview
3-WAY ECO-i SYSTEM
Outdoor Unit Maintenance Remote Controller
3
OUTDOOR UNIT MAINTENANCE REMOTE
CONTROLLER (RCS-TM80BG) for 3-WAY ECO-i
■
About the outdoor unit maintenance remote controller
The outdoor unit utilizes nonvolatile memory (EEPROM) on its PCB. This allows EEPROM data to replace the setting switches that were present on previous PCBs. The outdoor unit maintenance remote controller is used to set and change these EEPROM data.
In addition to setting and checking the outdoor unit EEPROM data, this remote controller can also be used to monitor the outdoor unit alarm history, monitor the various indoor and outdoor temperatures, and check the indoor unit connection status (number of units, operating mode, etc.).
NOTE
Outdoor unit maintenance remote controller does not function as an ordinary remote controller. It is therefore only used for test runs and during servicing.
System diagram
Outdoor unit maintenance remote controller
Special service checker wiring
Outdoor unit
(Servicing No.: 6231785082)
[Service Checker Section]
RCS-TM80BG
Inter-unit control wiring
Outdoor unit control PCB
Indoor unit
Indoor unit
Remote controller Ass’y
Operation manual included in package.
Remote controller
Remote controller
●
The special service checker wiring is required in order to connect the outdoor unit maintenance remote controller
● to the outdoor unit PCB.
Ordinary remote controllers or other controller are still required for the indoor units, even when the outdoor unit maintenance remote controller is connected.
3 - 2
2. Functions
3-WAY ECO-i SYSTEM
Outdoor Unit Maintenance Remote Controller
■
Functions on the ordinary display
(1) Functions: Button operations can be used to perform the following functions.
• Start/stop of all indoor units
• Switching between cooling and heating
• Test run of all indoor units
• Double-speed operation of indoor units (Do not use for actual operation. Doing so may damage the devices.)
(2) Display: The following can be displayed.
• Alarm details display
• No. of indoor/outdoor units
• Unit Nos. of connected indoor/outdoor units
• Indoor/outdoor unit operating status (blinks when an alarm occurs)
• Indoor unit thermostat ON
• Display of individual outdoor unit alarms
• Total operating time of outdoor unit compressors
• Oil level of the outdoor unit oil sensor
• Total outdoor unit power ON time
• Outdoor unit microcomputer version, other information
■
Temperature monitor
• Displays the indoor/outdoor unit sensor temperatures.
■
Outdoor unit alarm history monitor
• Displays the outdoor unit alarm history.
■
Mode settings
• Setting mode 1 and setting mode 2 are used to make the outdoor EEPROM setting.
3
3 - 3
3. Ordinary Display Controls and Functions
3-WAY ECO-i SYSTEM
Outdoor Unit Maintenance Remote Controller
■
Functions on the ordinary display
•
Connect the special service checker wiring to the outdoor unit PCB.
The connection is shown in the figure below.
Outdoor unit PCB
RC (3P, BLU)
PCB connector (3P, BLU)
Special service checker wiring
Relay connector (2P, WHT)
Remote controller Ass’y
3
●
If the communications line in the inter-unit control wiring is connected, it can be left as-is.
●
In case of an independent outdoor unit (1 maintenance remote controller connected to 1 outdoor unit, automatic address setting for indoor units not completed), both setting mode 1 and setting mode 2 can be used.
●
The overall system status for that refrigerant system is displayed.
3 - 4
3. Ordinary Display Controls and Functions
3-WAY ECO-i SYSTEM
Outdoor Unit Maintenance Remote Controller
●
All units start/stop (Fig. 1)
<Operation>
The (ON/OFF operation) button can be used to start and stop all the indoor units.
• The LED turns ON when 1 or more indoor units is operating.
• The LED blinks when an alarm has occurred at 1 or more indoor units during operation.
LED
●
Switching between cooling/heating (Fig. 1)
<Operation>
The (MODE) button switches between heating and cooling modes.
• The specifications are equivalent to the heating/cooling inputs on the previous outdoor unit PCBs.
• The display shows the operating mode of the indoor unit with the lowest unit No.
●
All units test run (Fig. 2)
<Operation>
The (CHECK) button switches test run ON/OFF for all indoor units.
• Press and hold for 4 seconds to turn ON.
“TEST” is displayed while the test run is in progress.
• The status of test runs that are started from the indoor unit remote controller are not displayed on the outdoor unit maintenance remote controller.
Fig. 1
3
Fig. 2
●
Double-speed
• Do not use for actual operation.
(Doing so may damage the devices.)
<Operation>
The timer button is used to switch between doublespeed and normal operation.
• During double-speed operation, the SLEEPING MODE
mark is displayed.
3 - 5
3
3. Ordinary Display Controls and Functions
3-WAY ECO-i SYSTEM
Outdoor Unit Maintenance Remote Controller
•
■
Display (functions)
Use the temperature setting and buttons to change the item code.
Item code
➀ Outdoor unit alarm ➁
Item
No. of connected indoor units
Unit Nos. of connected indoor unit
Operating status of indoor unit
Thermostat ON status of indoor unit
No. of connected outdoor units
Unit Nos. of connected outdoor units
Operating status of outdoor unit compressor
Remarks
Alarm code display
Quantity
7-segment display
7-segment display
7-segment display
1 – 8
7-segment display
7-segment display
Compressor 1 operating time
Compressor 2 operating time
Compressor 3 operating time
Compressor 1 oil level
Compressor 2 oil level
Compressor 3 oil level
Outdoor unit power ON time
Compressor 1 operation count
Compressor 2 operation count
Compressor 3 operation count
Alarm history 1 (most recent)
Alarm history 2
Alarm history 3
Alarm history 4
Alarm history 5
Alarm history 6
Alarm history 7
Alarm history 8 (oldest)
Firmware version
Program version
0 – 99999999 hrs
0 – 99999999 hrs
0 – 99999999 hrs
0 = Empty 1 = Insuffi cient 2 = Suffi cient
0 = Empty 1 = Insuffi cient 2 = Suffi cient
0 = Empty 1 = Insuffi cient 2 = Suffi cient
0 – 99999999 hrs
0 – 65535 times
0 – 65535 times
0 – 65535 times
Display only. Alarm code and unit No. of unit where alarm occurred are displayed alternately.
0 = CCU
1 – 4 = Outdoor unit
Display the version No. × 100.
Display the version No. × 100.
3 - 6
3. Ordinary Display Controls and Functions
3-WAY ECO-i SYSTEM
Outdoor Unit Maintenance Remote Controller
(3) XX-YY R.C.
Displays the outdoor unit sub-bus address which is currently selected.
XX = Outdoor system address on main bus line (1 – 30)
YY = Outdoor unit sub-bus address (1 – 8).
“1” appears when there is only 1 outdoor unit.
Locations where ➀ as shown in Fig. 3.
, ➁ , and ➂ are displayed
2 1
3
Fig. 3
LED
3
<Sample displays>
01: <No. of connected indoor units>
4 units connected
Fig. 4
02: <Unit Nos. 1, 2, 3, and 4 are connected>
Fig. 5
3 - 7
3. Ordinary Display Controls and Functions
3-WAY ECO-i SYSTEM
Outdoor Unit Maintenance Remote Controller
3
■
Concerning the 7-segment, 4-digit display remote controller timer display
The connected unit Nos. are displayed as shown below, using the 7-segment 4-digit ( the colon.
●
Display for unit Nos. 1 − 20
2
1
OFF
3
4
5
ON
7
6
OFF
8
9
10
ON
12
11
OFF
13
14
15
ON
16
OFF
18
17
19
20
ON
Meaning of display colon
) display and
1 ~ 20 21 ~ 40 41 ~ 60 61 ~ 80 is not displayed.
●
Display for unit Nos. 21 − 40
21
OFF
22
23
24
27
26
OFF
28
29
32
31
OFF
33
34
25 30 35
ON ON ON
36
OFF
38
37
39
40
ON
Meaning of display colon
1 ~ 20 21 ~ 40 41 ~ 60 61 ~ 80
●
The meaning of the colon display changes in the same way, allowing unit Nos. up to 80 to be displayed.
●
Sample displays of the unit Nos. of connected indoor units
• Display of unit No. 1
•
Display of unit Nos. 1 and 2
• Display of unit Nos. 1, 2, and 3
• Display of unit Nos. 1, 2, 3, and 4
NOTE
The colon display (Unit Nos. 1 – 20, 21 – 40) changes automatically every 10 seconds.
(The display does not change if higher unit numbers do not exist.)
Pressing the button switches the display immediately to the next higher level, even if 10 seconds have not passed.
■
The total compressor operating time is displayed
(in 1-hour units) using 8 digits.
• When the fi rst 4 digits are displayed, the bottom
(A) (B) dot of the colon is lit. (Figure (A))
• When the last 4 digits are displayed, the colon points are not lit. (Figure (B))
• The display of the fi rst 4 and last 4 digits changes automatically every 10 seconds. It can also be changed by pressing the button.
10: <Total compressor operating time>
(A) and (B) are displayed alternately.
(The example here (0000, 0062) indicates 62 hours.)
NOTE
With the outdoor unit maintenance remote controller (when connected to the outdoor unit), the unit remote controller check functions will not operate.
3 - 8
4. Monitoring Operations
Display the indoor unit and outdoor unit sensor temperatures.
<Operating procedure>
➀
Press and hold the (CHECK) button and buttons simultaneously for 4 seconds or longer to switch to temperature monitor mode.
During temperature monitoring, is lit.
(The display and operations are the same as when monitor mode is started from the unit remote controller.)
➁
Press the to monitor.
button and select the indoor unit
➂
Use the temperature setting and buttons to select the item code of the temperature to monitor.
The selected indoor unit No. and the temperature data are displayed.
➃
To end monitoring, press the (CHECK) button.
The display returns to the normal display.
NOTE
The display does not blink.
4
3-WAY ECO-i SYSTEM
Outdoor Unit Maintenance Remote Controller
1
2
3
3
3 - 9
4. Monitoring Operations
3
■
Display of unit No. 1 (main unit)
DN Description
Intake temp.
E1
E2
E3
Discharge temp.
°C
°C
°C
°C
°C
Discharge temp. setting °C
Indoor unit electronic control valve position STEP
Discharge temp. 1
Discharge temp. 2
°C
°C
High-pressure sensor temp.
Heat exchanger gas 1
Heat exchanger liquid 1
Heat exchanger gas 2
°C
°C
°C
°C
°C
°C
Heat exchanger liquid 2
Outdoor air temp.
Not used
Inverter primary current
CT2
MOV1 pulse
MOV2 pulse
Discharge temp. 3
A
A
STEP
STEP
°C
CT3
MOV3 pulse
MOV4 pulse
Heat exchanger gas 3
Heat exchanger liquid 3
Low-pressure sensor temp.
Receiver temp.
Oil 1
Oil 2
Oil 3
Actual operating frequency
°C
°C
°C
Hz
°C
°C
°C
A
STEP
STEP
°C
3-WAY ECO-i SYSTEM
Outdoor Unit Maintenance Remote Controller
NOTE
0A and subsequent items are outdoor unit data. 0A – 22 are for unit No. 1.
2A – 42 are for unit No. 2. 4A – 62 are for unit No. 3.
Remarks
Indoor unit
Outdoor unit
3 - 10
5. Outdoor Unit Alarm History Monitor
• Displays outdoor unit alarms only. Does not display indoor unit alarms.
• Check the indoor unit alarm histories separately using the indoor unit remote controllers or other control device.
<Operating procedure>
➀
Press and hold the (CHECK) button and button simultaneously for 4 seconds or longer to change to outdoor unit alarm history mode.
During temperature monitoring, displays.
The display and operations are the same as the monitoring of the alarm device history that is performed using the unit remote controller. However, the outdoor unit address appears instead of the unit No.
➁
Press the button and select the outdoor unit for alarm history monitoring.
➂ Use the temperature setting and to select the item code for the alarm history.
buttons
The display shows the address of the selected outdoor unit, the item code, and the alarm history (alarm data).
The outdoor unit address is displayed as R.C. XX-YY.
System XX = Outdoor unit system address
R.C. XX = Outdoor unit system address
YY = Outdoor unit sub-bus address (always “1” for
3-WAY ECO-i units)
Unit code is displayed as 01 – 08. 01 indicates the most recent alarm.
The alarm history is indicated by the alarm code. (If there have been no alarm codes, “-- --” is displayed.)
➃ To clear the alarm history, press the button. (The outdoor unit alarm history will be cleared.)
➄
To exit, press the (CHECK) button. The display returns to the normal remote controller display.
3-WAY ECO-i SYSTEM
Outdoor Unit Maintenance Remote Controller
5
1
4 2
3
3
3 - 11
advertisement
Key Features
- EEPROM data setting and checking
- Outdoor unit alarm history monitoring
- Indoor/outdoor unit temperature monitoring
- Indoor unit connection status
- Test run for all indoor units
- Double-speed operation for indoor units
- Outdoor unit alarm history monitor
- Setting Mode 1 and Mode 2
- 7-segment display for connected unit numbers
- Special service checker wiring