Below you will find brief information for Supervised Power Supply/Charger SMP5PM-CTX. This is a power limited supply/charger that provides a 12VDC or 24VDC output with 4 amps of continuous supply current. The unit includes a built-in charger for sealed lead acid or gel type batteries, and automatically switches to stand-by battery when AC power fails. The SMP5PM-CTX features LED indicators for power supply status, as well as AC fail and low battery supervision.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Supervised Power Supply/Charger SMP5PM-CTX User Manual | Manualzz
SMP5PM-CTX
Supervised Power Supply/Charger
Overview:
The SMP5PM-CTX is a power limited supply/chargers that will convert a 115 VAC / 60Hz input, into a 12VDC or
24VDC power limited output, with 4 amps of continuous supply current (see specifications).
Specifications:
•
•
•
•
•
•
•
•
•
•
•
•
•
Switch selectable 12VDC or 24VDC.
Input 115VAC / 60Hz, .95 amp.
Maximum charge current .5 amp.
4 amps continuous supply current at 12VDC or 24VDC.
Filtered and electronically regulated outputs.
Built-in charger for sealed lead acid or gel type batteries.
Automatic switch over to stand-by battery when AC fails
(zero voltage drop).
AC input and DC output LED indicators.
AC fail supervision (form "C" contacts).
Low battery supervision (form "C" contact).
Short circuit and thermal overload protection.
Unit is complete with power supply, enclosure and cam lock.
Includes battery leads.
Specified at 25˚ C ambient.
SMP5PM-CTX Enclosure Dimensions: 15.5”H x 12”W x 4.5”D (cam lock included)
Note: Enclosure accommodates up to two (2) 12AH batteries
Power Supply Voltage Output Specifications: *
Output VDC
Switch Position
Max. Load DC
12VDC
SW 1 - Closed
4 amps
24VDC
SW1 - Open
4 amps
Installation Instructions:
The SMP5PM-CTX should be installed in accordance with The National Electrical Code
and all applicable Local Regulations.
1. Mount the SMP5PM-CTX in desired location.
2. Set the SMP5PM-CTX to desired DC output voltage via SW1 (see power supply voltage output selection chart).
3. Connect AC power to terminals marked [L & N], connect ground to terminal marked [G].
Use 18 AWG or larger for all power connections (Battery, DC output).
Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).
Keep power limited wiring separate from non-power limited wiring
(115VAC / 60Hz Input, Battery Wires). Minimum .25” spacing must be provided.
4. Connect devices to be powered to terminals marked [+ DC --].
Note: It is good operating practice to measure and verify output voltage before
connecting devices to ensure proper operation of equipment.
*Note: Power switch is used to turn off DC output voltage. It disconnects the L (HOT) terminal
from the rest of the board. When servicing the unit, AC mains should be removed.
5. When the use of stand-by batteries are desired, they must be lead acid or gel type.
Connect battery to terminals marked [- BAT +] (battery leads included).
Use two (2) 12VDC batteries connected in series for 24VDC operation.
Note: When batteries are not used a loss of AC will result in the loss of output voltage.
6. Connect appropriate signaling notification devices to AC Fail & Low battery supervisory
relay outputs marked [N.C., C, N.O.].
IISMP5PM-CTX-Rev. 052400
LED Diagnostics:
Red (DC)
ON
ON
OFF
OFF
Green (AC)
ON
OFF
ON
OFF
Power Supply Status
Normal operating condition.
Loss of AC, Stand-by battery supplying power.
No DC output
Loss of AC. Discharge or no stand-by battery. No DC output.
Terminal Identification:
Terminal
Legend
Function/Description
L, G, N
Connect 115 VAC to these terminals:
L to Hot, N to Neutral, G to ground.
12 / 24VDC - 4 amps continuous power limited output.
Used to notify loss of AC power, e.g. connect to audible device or alarm panel.
Relay normally energized when AC power is present.
Contact rating 1amp @ 120VAC / 28VDC
Used to indicate low battery condition, e.g. connect to alarm panel. N.O., C, N.C.
Relay normally energized when DC power is present.
Contact rating 1 amp @ 120VAC / 28VDC
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC,
24VDC output threshold set @ approximately 21VDC.
Stand-by battery connections. Maximum charge rate .5 amp.
+ DC AC FAIL
N.O., C, N.C.
Low Battery
NO, C, NC
- BAT +
PTC1
RL2
BAT
FAIL
AC FAIL
NO
C NC
NO C
NC
115VAC input
60Hz,
.95 amp
Ground
BAT
12VDC / 24VDC
Selectable Switch
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
Altronix Corp.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
web site: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
MEMBER

advertisement

Key Features

  • Switch Selectable 12VDC or 24VDC
  • 4 Amps continuous supply current
  • Built-in charger for batteries
  • AC Fail supervision
  • Low Battery supervision
  • Short circuit protection
  • Thermal overload protection
  • LED indicators for power supply status

Frequently Answers and Questions

What type of batteries can I use with the SMP5PM-CTX?
The SMP5PM-CTX is designed to work with sealed lead-acid or gel type batteries.
What is the maximum charge current for the built-in charger?
The maximum charge current for the built-in charger is 0.5 amps.
How do I connect the stand-by batteries?
Connect the batteries to the terminals marked -BAT+.