Below you will find brief information for PTO Generator 12PTOC 3, PTO Generator 25PTOC 3. This manual outlines the installation and operation procedures for using the generator. It covers topics such as connecting the PTO to the generator, starting the generator, and understanding the electrical connections. The document also includes information on troubleshooting common issues and performing routine maintenance.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
OWNERS MANUAL
INSTALLATION AND OPERATION INSTRUCTIONS
Tractor Drive
PTO Generators
12PTOC-3
25PTOC-3
SAFETY FIRST
READ THIS MANUAL BEFORE OPERATING YOUR GENERATOR.
60706-133
Read and understand all instructions in this manual before starting and operating the generator set.
USING THIS MANUAL
Congratulations on your choice of a Winco generator set.
You have selected a high-quality, precision-engineered generator set designed and tested to give you years of satisfactory standby service.
To get the best performance from your new generator set, it is important that you carefully read and follow the operating instructions in this manual.
COPY YOUR MODEL AND SERIAL NUMBER HERE No other
WINCO generator has the same serial number as yours. It is important that you record the number and other vital information here, if you should ever need to contact us on this unit it will help us to respond to your needs faster.
MODEL____________________________________
SERIAL NUMBER____________________________
PURCHASE DATE____________________________
TABLE OF CONTENTS
INTRODUCTION
36 MONTH WARRANTY
GUIDE TO PRODUCT SAFETY
BASIC INFORMATION
PREPARING THE UNIT
Unpacking the unit
Assembly
INSTALLATION
Foundation Mounting
Trailer Mounting
ELECTRICAL CONNECTIONS
OPERATION
Pre-Start Checks
Starting Procedure
Stopping
MAINTENANCE
Lubrication
Cleaning and Inspection
Storage
Generator Testing
Trouble Shooting Table
DEALER___________________________________
WINCO PTO GENERATORS
36 MONTH LIMITED WARRANTY
WINCO, Inc., warrants for thirty-six months from date of shipment, that it will repair or replace at its option, for the original user, the whole or any part of the product found upon examination, by WINCO at its factory at 225 South Cordova Avenue,
Le Center, Minnesota, or by any factory-authorized service station, to be defective in material or workmanship under normal standby use (average less than 50 hours per month) and service.
For warranty service, return the product within 36 months from the date of purchase, transportation charges prepaid, to your nearest factory-authorized service station or the WINCO factory.
There is no other express warranty. To the extent permitted by law, any and all warranties, including those of merchantability and fitness for a particular purpose, are limited to 36 months from date of shipment, and liability for incidental or consequential damages or expenses is excluded. Some states do not allow limitations on the duration of an implied warranty, and some states do not allow the exclusion or limitation of incidental or consequential damages, so that above limitation or exclusion may not apply to you. This warranty gives you specific legal rights; you may have other rights which vary from state to state.
This warranty is limited to bench labor and parts only, no allowance will be made for travel time, or removal and reinstallation of the PTO unit.
WINCO does not warrant drive lines, trailer tires, receptacles, or certain other component parts of the product installed by others, since such items are warranted by their manufacturers.
WINCO does not warrant modifications or alterations which were not made or authorized by the WINCO factory and which affect the stability or reliability of the product.
WINCO does not warrant products which have been exposed to misuse and/or negligence or have been involved in an accident.
WINCO does not warrant products which have been installed in such a manner as not to protect them from the adverse environmental conditions (water, mud, insects, etc.) or have not been kept clean.
WINCO reserves the right to change or improve its products without incurring any obligations to make such changes or improvements on products purchased previously.
8
10
7
7
8
6
6
7
2
3
2
2
1
2 i i
4
5
5
3
3
SAFETY INFORMATION
This generator set has been designed and manufactured to allow safe, reliable performance. Poor maintenance, improper or careless use can result in potential deadly hazards; from electrical shock, exhaust gas asphyxiation, or fire. Please read all safety instructions carefully before installation or use. Keep these instructions handy for future reference. Take special note and follow all warnings on the unit labels and in the manuals.
ANSI SAFETY DEFINITIONS
______________________________________________________
DANGER:
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. This signal word is to be limited to the most extreme situations.
______________________________________________________
______________________________________________________
WARNING:
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
______________________________________________________
______________________________________________________
CAUTION:
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
______________________________________________________
NOTE:
CAUTION is also used on the unit labels and in this manual to indicate a situation that could result in serious damage or destruction of the equipment and possible personal injury.
______________________________________________________
3.
DEADLY EXHAUST GAS - Exhaust fumes from any engine contain carbon monoxide, an invisible, odorless and deadly gas that must be mixed with fresh air.
a.
Operate only in well ventilated areas.
b.
Never operate indoors.
4.
NOISE HAZARD - Excessive noise is not only tiring, but continual exposure can lead to loss of hearing.
a.
Use hearing protection equipment when working around this equipment for long periods of time.
b.
Keep your neighbors in mind when permanently installing this equipment.
5.
CLEANLINESS- Keep the generator and surrounding area clean.
a.
Remove all grease, ice, snow or materials that create slippery conditions around the unit.
b.
Remove any rags or other material that could create potential fire hazards.
6.
SERVICING EQUIPMENT- All service, including the installation or replacement of service parts, should be performed only by a qualified technician.
a.
Use only factory approved repair parts.
b.
Do not work on this equipment when fatigued.
c.
Use extreme caution when working on electrical components. High output voltages from this equipment can cause serious injury or death.
d.
Always avoid hot mufflers, exhaust manifolds, and engine parts. They all can cause severe burns instantly.
1.
ELECTRIC SHOCK- The output voltage present in this equipment can cause a fatal electric shock. This equipment must be operated by a responsible person.
a.
Do not allow anyone to operate the generator without proper instruction.
b.
Guard against electric shock.
c.
Avoid contact with live terminals or receptacles.
d.
Use extreme care if operating this unit in rain or snow.
e.
Use only three-prong grounded plugs and extension cords.
f.
Be sure the unit is properly grounded to an external ground rod driven into the earth.
g.
Do not make or break electrical connection under load.
7.
INSTALLATION- Installing a PTO generator is not a “do-ityourself” project. Consult a qualified, licensed electrician or contractor. The installation must comply with all national, state, and local codes.
a.
Never operate the PTO drive generator without having it properly mounted to a concrete base or approved trailer.
b.
Never connect the PTO generator to an existing electrical system without installing an isolation transfer switch.
c.
Always insure the drive shaft is straight and level before operating the generator.
2.
FIRE HAZARD- Gasoline, diesel and other fuels always present a hazard of possible explosion and/or fire.
a.
Keep a fire extinguisher nearby and know its proper use. Fire extinguishers rated ABC by
NFPA are appropriate.
8.
OPERATION - PTO drive shafts (Tumbling Bars) have many inherent dangers, extreme caution must be exercised when using them.
a.
NEVER allow children around a drive shaft when it is in operation.
b.
Keep all safety guards and shields in place and securely tightened.
c.
Never operate a drive shaft that has been damaged or had the safety shield removed.
d.
Never step over a drive shaft while it is running.
e.
Never wear a necktie, loose articles of clothing, or anything else that can be caught in moving parts.
f.
Never try to stop a turndrive shaft with your hand or your foot.
60706-133
Page 1
8290-01
Description
The WINCO rotating armature power take-off generators are designed primarily for farm use as a standby electrical power supply, utilizing the power take-off of a tractor or truck as the prime mover. This PTO drive generator will provide, 120/240V single phase, 60Hz electrical service when properly driven.
NOTE: The prime mover which drives the generator must be capable of delivering approximately 2 HP per 1000 watts output from the generator. Observe input RPM specifications.
This generator includes a color coded voltmeter to warn against high or low voltage, three output power receptacles, an overload protection circuit, and an electronic excitation circuit. To reduce maintenance problems, the coupling between the generator input shaft and rotor consists of precision helical gearing rather than a chain link drive. The input shaft is a 1 1/8 in. diameter smooth shaft with a keyway and center drilled for a roll pin. Both must be used at all times.
The factory thoroughly tests each generator before shipment.
All are continuous duty rated.
If loss or damage is noted at time of delivery, require that the person making the delivery make note of the loss or damage on the freight bill, or sign the consigner’s memo of the loss or damage. Contact the carrier for claim procedures.
When loss or damage is noted after delivery, segregate the damaged material, and contact the carrier for claim procedures.
The generator may be foundation mounted for use as standby power source, or trailer mounted, and used as portable electrical power sources for areas where commercial power is not readily available, such as out buildings.
“Concealed damage” means damage to the contents of a package which is not evident when the package is delivered by the carrier, but which is discovered later. The carrier or carriers are responsible for merchandise lost or damaged in transit. The title to the goods rests with the consignee when the goods are shipped FOB factory, and only the consignee can legally file claims. Two years are allowed in which to file suit after a claim is disallowed in writing by the carrier.
Assembly
25PTOC-3
The only assembly work required after unpacking the generator is to assemble and wire the load disconnect plug, which is contained in a bag in the subpack carton packed in the generator crate. The bag contains an instruction sheet, a plug body, three or four brass pins (large pin for neutral line), and a small envelope. The small envelope contains an allen wrench, retainer pins, and set screws.
IMPORTANT: THE MANUFACTURER STRONGLY RECOM-
MENDS RUNNING THE GENERATOR UNDER LOAD AT
LEAST ONCE A MONTH IN ORDER TO EVAPORATE ANY
ACCUMULATED MOISTURE CONDENSATION.
To wire the load disconnect plug, use the following type of cable:
Generator
Model
25PTOC-3
Insulation
600V, Neoprene
UNPACKING
Size,
AWG
4
CAUTION: Equipment Damage
DO NOT invert generator during unpacking. The Gearcase contains oil which will leak out if inverted during unpacking.
Unpack the generator as follows:
1. Remove the carton.
To assemble and wire the load disconnect plug, proceed as follows (see Figure 1):
1. Cut cables to the required length.
2. Strip off insulation 7/8" back from one end of each of the cut-to-length cables.
3. Start threading a set screw into each pin.
4. Insert the stripped end of one cable fully into one of the brass pins, and tighten the set screw firmly to secure the cable end in the pin.
2. Examine the unit for damage.
3. Find the small subpack carton packed in the large carton.
Be careful not to throw away the subpack carton with the large carton.
DANGER: Equipment Damage
If cable-to-pin connections are loose, arcing and heat damage to equipment can result.
4. Open the subpack carton and make sure it contains: a.
Generator instruction manual b.
Load disconnect plug (disassembled, in bag)
5. Remove the four bolts which hold down the generator feet to the pallet.
6. Lift the generator from the pallet by means of the lifting eye on the top of the generator.
7. Inspect the generator carefully for freight loss or damage.
8290-01
Figure 1
Page 2
Octopus Plug Assembly
60706-133
5. Insert the brass pin (with cable) into the plug body, and line up the retainer pin holes in the brass pin with those in the plug body.
6. Insert the retainer pin, and tap it firmly into place. The retainer pin will protrude approximately 3/8" when fully seated. (See Figure 1.)
7. Repeat steps 4 through 6 for each brass pin. Make sure to connect the neutral lead (cable), identified and color coded in conformance with the applicable local electrical codes, to the large diameter pin (“N”) on the plug.
C. The foundation surface should be flat.
D. Space is required around the generator for mounting switching devices, making connections, and for servicing.
E. The generator mounting backet must rest evenly and firmly on the foundation. Install shims if necessary to even out the foundation under the mounting pads then bolt the generator firmly in place.
WARNING: Electrical Shock
DURING THE NEXT STEP, THE LOAD DISCONNECT PLUG
SHOULD NOT BE PLUGGED INTO ITS RECEPTACLE.
ALSO, MAKE SURE THAT THE EQUIPMENT TO WHICH
THE PLUG LEADS (CABLES) ARE BEING CONNECTED IS
NOT ENERGIZED (LIVE).
TRAILER MOUNTING
Mount the generator on a trailer if you plan to use it as a portable power source. See Figure 4. When selecting or building a trailer to mount the generator, consider the following points:
8.
Strip the insulation off the free end of each of the plug leads (cables), and connect them to the load transfer switch
(or directly to the load).
A. The trailer construction must be strong enough to support the generator.
12PTOC-3
B. The design of the trailer must enable the trailer to remain stable during operation, and to resist tipping caused by generator starting and reflected load torque.
The only assembly work required after unpacking the generator is to assemble and wire the load disconnect plug, which is contained in the subpack carton packed in the generator crate. This load disconnect plug is a Alpha type 4 wire locking plug. The instruction for wiring the plug are in the box with the plug. The gauge wire required will depend on the type of wire you buy. You will need wire of sufficient size to carry 50 amps at 240 volt. Consult with your local wire supplier for the proper gauge and type.
WARNING: Personal Injury & Equipment Damage
TRAILER MAY TIP OVER AND CAUSE INJURIES IF
WHEELS ARE NOT SPACED FAR ENOUGH APART.
C. The trailer height and mounting position of the generator on the trailer should enable aligning the drive shaft (tumbling bar) in a straight or nearly straight line between the power take-off and generator input shafts. Misalignment must be less than 15 degrees during generator operation, even though the mechanical design of the tumbling bar would allow greater misalignment.
Installation
FOUNDATION MOUNTING
Mount the generator on a foundation if it is to be used as a permanent or standby power source (see Figure 2). See
“TRAILER MOUNTING” if generator will be used as a portable power source (see Figure 3). When planning a foundation consider the following points:
D. The generator mounting area of the trailer bed should be flat.
E. The generator mounting bracket must rest evenly and firmly on the trailer bed. Install shims if necessary to even out the bed under the mounting pads, then bolt the generator firmly in place.
A. The foundation location should enable aligning the drive shaft (tumbling bar) in a straight or nearly straight line between the power take-off and the generator input shaft.
Misalignment must be less than 15 degrees during generator operation, even though the mechanical design of the tumbling bar would allow greater misalignment.
Trailer, for Portable Operation
B. The foundation must be solid enough to absorb generator starting and reflected load torque during operation.
Figure 3
60706-133
Figure 2
Page 3
8290-01
ELECTRICAL CONNECTIONS
CAUTION:
Only qualified electricians should install electrical wiring.
Wiring must conform to all applicable national, state, and local codes. (Reference: National Fire Protection Association
Manual No. 70, National Electrical Code.)
DANGER: PERSONAL INJURY
IF THE GENERATOR IS TO BE USED AS A STANDBY
POWER SOURCE, A SPECIAL DISCONNECT SWITCH
MUST BE INSTALLED TO SEPARATE THE GENERATOR
AND THE COMMERCIAL POWER LINES. THE
DISCONNECT MUST ISOLATE THE GENERATOR FROM
THE COMMERCIAL POWER LINES AND THE LOAD WHEN
THE GENERATOR IS ON STANDBY, AND MUST ISOLATE
THE COMMERCIAL POWER LINES FROM THE LOAD AND
THE GENERATOR WHEN THE GENERATOR IS SUPPLYING
POWER. SEE FIGURE 5.
Figure 5
8290-01
Typical Connection Methods for Generator Power Service
Page 4
60706-133
Operation
OUTPUT POWER AVAILABLE AND LOAD DETERMINATION
Before using the generator, read and understand the following information.
Generator output current (amperage) is internally limited by circuit breakers. If too much demand is placed on a generator output (if you try to drive too many motors with it, for example), one of the circuit breakers will trip, cutting off the output in order to protect the generator.
A 15 amp push-to-reset circuit breaker protects the 120V duplex receptacle output circuit. 15 amps is the total limit for both outputs of the duplex receptacle.
A 50 amp two pole switch type circuit breaker protects the
240V receptacle output circuit.
A large two pole switch type main circuit breaker protects the generator windings and output circuits, including the load disconnect receptacle outputs. The load disconnect receptacle on the 25PTOC is the large round black rubber receptacle on the generator output panel. The mating plug is a
WINCO part number 91357-000. On the 12PTOC it is the 50 amp 4 wire twistlock receptacle on the output panel. The mating plug is a Hubbell CS6365.
To aid in determining how much load can be applied to the generator, and how it should be distributed among the generator output receptacles, the following formulas may be useful. Get load voltage, current, and wattage from the nameplates on the equipment in the load.
(Load Current, in amps) x (Load Voltage) = (Load Wattage)
AMPS X VOLTS = WATTS
WATT/1000 = kW
(Load Current in amps) = (Load Wattage)/(Load Voltage)
Example:
250W, 120V floodlight load = 250W/120V= 2 amps (approx.)
NOTE:
Electric motors require much more current to start than to run.
Commonly, the current rating given on a motor nameplate is the full load (running) current required by the motor, not its starting current, which is a lot higher. Motor starting current requirements vary greatly, by motor size and type. Repulsioninduction type motors are the easiest to start, typically using 1
1/2 to 2 1/2 times as much current to start as to run; capacitor type motors usually require 2 to 4 times as much current to start as to run; split-phase type motors are the hardest to start, normally using 5 to 7 times as much current to start as to run.
MOTOR LOAD
Motor
Amps
Horsepower
1/4
1/3
1/2
3/4
1
1-1/2
2
3
5
7-1/2
SINGLE PHASE
115V
(Running Amps)
5.8
7.2
9.8
13.8
16
20
Amps
230V
2.9
3.6
4.9
6.9
8
10
24
34
56
80
12
17
28
40
Compiled from N.E.C. manual.
To use the full capacity of the generator without tripping its circuit breaker(s), start the motors in the load one at a time, highest starting current motor first, next highest second, etc.
Use the preceding table as a source of general information about motor running current requirements. For more specific information, see motor nameplate or motor manufacturer’s catalog.
PRE-START CHECKS
WARNING: Personal Injury
When working on or around these generators, do not wear loose fitting clothing or any articles that may get caught in moving parts.
1. Visually inspect the generator. Check for: a Correct mounting b. Physical damage c. Debris in cooling vents and screens (could cause generator to overheat).
IMPORTANT: The manufacturer recommends that, if the generator has been stored for any length of time, before using it, the operator remove the control box cover and cooling fan screen, then inspect the generator for rodent nests or other objects that could cause generator binding and/or overheating. See “Cleaning” portion of Maintenance section.
2. Check gear case oil level. (See Figure 6.) Case should be filled with oil to plug marked “OIL LEVEL.” Fill or remove oil as required.
NOTE: EITHER TOO LITTLE OR TOO MUCH OIL CAN HARM
THE EQUIPMENT.
See “Lubrication” portion of Maintenance for oil specifications.
60706-133
Page 5
8290-01
Figure 6
3. Make sure the drive shaft (tumbling bar) is assembled with its universal joint knuckles “synchronized,” as illustrated in
Figure 7. If knuckles are not synchronized, the bar will chatter when rotating, which will cause the generator output voltage to flicker.
Figure 7
DANGER: Personal Injury
POWER TAKE-OFF MUST BE DISENGAGED AT THIS TIME.
4. Couple the tractor to the generator with the drive shaft (tumbling bar). Couple the tumbling bar to the generator input shaft first, then to the power take-off shaft. Check alignment, tractor, power take-off shaft (tumbling bar), and generator input shaft should form a straight (or nearly straight) line, with less than 15° misalignment between the shafts.
Misalignment will cause generator output voltage to flicker.
CAUTION:
Make sure that all tumbling bar lock pins are engaged and that all safety shields are in place before operating the PTO generator.
5. Make sure no binding exists in generator or gear box. If binding is found, locate the cause and correct it before proceeding.
6. Make sure that the electrical loads to be driven by the generator will not draw more current than the ratings of the generator receptacle or cord set which will supply the current.
7. Check all electrical connections in the system to be energized by the generator. Make sure the connections are correct and are tight.
8. Make sure all loads are turned off. Do not start the generator under load.
GENERATOR STARTING PROCEDURE
1. With the power take-off drive disengaged, start the engine which will drive the generator. Run the engine long enough to warm it up before proceeding, so that it will run smoothly and achieve full power under generator load.
2. With engine idling, engage the power take-off drive.
3. Watch the voltmeter on the generator and slowly increase engine speed until the output reaches approximately 260 volts, in green portion of voltmeter scale.
4. With engine and generator running smoothly, switch on the electrical load while watching the voltmeter.
NOTE: Equipment Damage
If the load includes motors turn them on one at a time, highest starting current motor first, next highest second, etc.
Readjust engine throttle to keep generator output under load at 240V (in green portion of voltmeter scale). If engine is equipped with speed governor, it may automatically readjust the throttle as the load changes and keep the generator output at the proper level. However, some governors are not sensitive enough to maintain proper output under changing load, and in such cases the throttle will have to be manually readjusted .
GENERATOR SHUTDOWN PROCEDURE
1. Switch off electrical load.
2. Reduce speed of engine driving generator to idle.
3. Disengage power take-off drive, and allow generator to coast to a stop.
WARNING: Personal Injury
Never try to manually stop the generator. Always let it coast until it stops.
5. Shut off the engine.
4. Disconnect drive shaft (tumbling bar) power take-off end first, then generator end.
8290-01
Page 6
60706-133
MAINTENANCE
General Information
The main components of the generator are: armature, field coils, cooling fan, brushes, brush holder assembly, end brackets, rectifier and voltage regulator. Before performing any maintenance on the generator, isolate and/or disable the drive system so the unit can not be accidentally started while being repaired.
universal joints in the coupling shaft free from grease and dirt buildup.
NOTE:
Do not over lubricate the universal joints.
The troubleshooting chart lists various symptoms of poor generator operation with possible causes and the appropriate corrective action. You will need a volt-ohm meter or test light to check some of the causes. For some of the other causes you will need to check generator speed. To check generator speed you can use a frequency meter, a tachometer, or a 120V-60Hz electric clock and a correctly operating wrist watch. (Run the electric clock on generator power and compare the clock’s second hand movement with that of the wrist watch. They should run at the same speed. If clock runs faster, generator speed is too high, and vice versa.)
Check the generator gear case oil level before each use of the generator. Maintain the oil level at oil level plug height.
(See page 6 for oil level plug location.) The generator is shipped with lubricant in the gear case. Specifications for gear case lubricant are:
API Service: GL-5
Grade: SAE 85W-9O-140
Amount: 2 pints
CAUTION: Equipment Damage
Most electrical equipment in North America operates satisfactorily at frequencies between 58.5 and 62 Hz
(cycles per second.) Operating the generator at frequencies outside that range may cause damage to the generator and/or to electrical equipment driven by the generator.
Periodical Maintenance
Service/maintenance items include periodic external physical inspection for missing hardware or damage to mounting or drive system and checking the oil level in the gear case.
It is recommended that the generator be operated at least monthly under normal loads to familiarize operators with the procedures and controls as well as to dry out any accumulated condensation or other moisture in the generator electrical windings. The maintenance and service attention invested will insure getting the peak performance that was designed into the unit.
The following kinds of oil are recommended for use in the generator gear case: Mobil SAE 85W90-140 API Service GL-
5, Sunoco/DX XL80W90-140 Kendal Three Star 85W-140,
Amoco 85W140 or equivalent.
CAUTION: Equipment Damage
Do not overfill generator gear case. Overfilling causes overheating and oil seal failure.
Change the oil at least once every six months. Change it more often if you use the generator in bad weather. Use the following procedure to change generator gear case oil:
1.
Remove gear case breather. Soak breather in cleaning solvent, then allow it to dry.
2.
Remove oil level check plug.
Routine preventive maintenance minimizes costly repairs and generator down-time. Before each use, inspect the generator: gear case oil level should be correct, cooling vents and screens should be clear, and generator mounting hardware should be tight. Clean and inspect the generator after storing it for long periods, and after using it in extremely dusty conditions or in severe weather, such as rain or blowing snow.
3.
Remove the oil drain plug, drain the oil into a clean oil resistant container, 1 quart or larger. Check the oil for metal. Fine metal dust in the oil does not indicate trouble, but metal chips do. Dismantle the gear case and look for damaged gears if you find metal chips in the oil.
4.
Replace the oil drain plug. Refill the gear case through the breather port with new oil of the recommended type.
Fill the case up to oil level check plug height. (It will take about 1 pint.)
5.
Replace the oil level check plug.
Lubrication
6.
Replace the breather
The generator bearings are factory lubricated and sealed, and require no further lubrication.
Cleaning and Inspection
The generator input shaft should be cleaned and lubricated with a thin film of grease before installing the drive shaft and each time it is removed.
Use a vacuum cleaner or dry low pressure compressed air
(regulated at 25-35 PSI) to clean the generator periodically.
The drive shaft (tumbling bar) requires greasing. Keep the
60706-133
WARNING
DO NOT CLEAN THE GENERATOR WHILE IT IS RUNNING.
Page 7
8290-01
Proceed as follows:
1. Remove control box cover. Vacuum or blow dust or debris from the control box. Inspect all wiring for correct routing, fraying insulation, and secure connections.
2. Remove end cover. Vacuum or blow dust and debris from the inside of the generator. Inspect wiring for loose connections, fraying insulation and correct wire routing.
3. Replace end cover and control box cover.
GENERATOR STORAGE
Before storing the generator, apply a heavy coat of grease to the splined input shaft. Store the generator in a sheltered area, where it is protected against snow, rain, and excessive dust.
Generator Maintenance and Testing
A. Brushes
Under ordinary circumstances, brushes will operate for extremely long periods without requiring replacement. They should be inspected after the first 500 hours of operation, and after every 200 hours of operation thereafter. Remove brushes one at a time and check for length; be sure that each moves freely in the brush holder. Brushes should be replaced when worn down to 3/8”. Replace brushes in complete sets, never singly. When replacing brushes, be careful to reconnect the lead wires properly.
Poor contact (or “skipping”) between brush and slip ring is caused by oil and grit, flint, or other hard substance on the brush, or by the brush not being properly shaped to fit the slip rings. Remedy these defects by fitting the brushes to the slip-ring curvature. Place # 00 sandpaper under the brushes with the abrasive side to the brushes, and work it back and forth until the brushes are the same shape as the slip-rings.
B. Slip rings
The four continuous copper rings located on the end of the armature are the generator output slip rings. For proper generator output, the surface of the slip rings must have a smooth, shiny, highly polished finish. Normal brush seating will transfer a shiny black finish that will seat the copper surface. This finish should not be removed unless it becomes dull or begins to build up.
Under sustained use, it is advisable to check and if necessary, polish the ring surfaces with a crocus cloth to maintain the smooth finish.
C.
Electrical Testing
Testing generator fields for opens and grounds.
1. Disconnect field leads from rectifier.
2. Set multimeter to read resistance, and connect the meter leads to the field leads. If field is open, meter will read infinite resistance (very high ohms). Repair or replace field if it is open. Typical resistance for these fields vary from 20.2 TO 22.4 ohms.
8290-01
Page 8
3. Leaving one meter lead connected to the field, connect the other meter lead to the field shell. If meter indicates continuity, any reading other than infinite resistance, the field is grounded and should be repaired or replaced. To determine which of the fields is grounded, cut the connector between the two coils and retest to determine which coil has the low resistance path.
Testing the Armature for Opens and Grounds
1. Remove all brushes.
2. Ground fault test - set multimeter to read high resistance
(meg-ohms).Holding one meter lead against a clean spot on the armature shaft, touch the other lead to each of the slip rings (one at a time) while observing the meter. If meter indicates continuity (any reading lower than one meg-ohm), the armature is grounded. Dirt between the slip rings and on the insulator surface can cause grounding. If grounding was indicated, carefully clean all dirt off the slip rings and their insulators and then recheck it. Replace the armature if it is grounded and unrepairable.
60706-133
3. Open Test. Set meter to read low resistance (R x ohms).
Holding one meter lead on surface of slip ring No. 1, touch other meter lead to surface of slip ring No. 2 while observing the meter. Meter should indicate continuity (low resistance - less than one ohm is typical). If the meter indicates open circuit (infinite resistance) part of armature winding is open. This may be caused by a repairable defect in the connection at the slip ring, however generally an open armature will have to be replaced. Continue reading the continuity between slip ring No. 2 to No. 3 and
No.2 and No.4. All the slip rings should have continuity to slip ring number 2, the neutral ring.
Testing Rectifiers
The field excitation is supplied through a full wave bridge rectifier. This type of rectifier has four terminals, two AC, a
DC positive and a DC negative.
A rectifier may be tested in the following manner:
1. Tag and disconnect all leads from rectifier.
2. Connect the red ohmmeter lead to the positive DC (+) terminal.
3. Connect the black lead to each of the AC terminals in turn.
Either a high or low resistance reading will be obtained.
4. Reverse the meter leads, black lead to the DC POS (+) and red to the AC terminals, each in turn. An opposite reading should be observed.
5. Connect the red ohmmeter lead to the negative DC (-) terminal.
7. Reverse the meter leads, black lead to the DC NEG (-) and red to the AC terminals, each in turn. An opposite reading should be observed.
8. Check each terminal to the case. An open circuit (very high resistance) reading should be observed. A battery powered test light may be used. Follow the same procedures described above. A good diode element will allow current to pass to the light in the test lamp in only one direction.
9. If the rectifier fails any of the above tests, it should be considered defective and replaced.
Condenser Testing
Condensers are built into the generator circuit to minimize radio interference during operation. If a condenser shorts out, it will also short out the generator output. To determine whether a condenser is shorted, stop the generator and disconnect the condenser lead wire from the brush holder.
Using a multimeter on the R x 100 scale, check the resistance of the condenser. Normal response is a sharp swing of the meter towards low resistance and then a steady rise towards high resistance (open circuit). If the capacitor is shorted it will show as a constant low resistance.
Otherwise, restart the generator without the capacitor connected to recheck the generator for output. If the generator then provides power, the condenser was at fault and should be replaced. (If the generator doesn't provide power, the problem was not caused by that condenser, reconnect the lead wire).
If these tests have not located the trouble, remove the armature and have it tested for opens, shorts, and grounds on a growler.
6. Connect the black lead to each of the AC terminals in turn.
Either a high or low resistance reading will be obtained.
60706-133
Page 9
8290-01
TROUBLE SHOOTING TABLE
SYMPTOM CAUSE(S) CORRECTIVE ACTION
No output voltage.
1.
2.
3.
4.
Circuit breaker open.
Defective voltmeter.
Short circuit in the load.
Defective receptacles.
5.
Loose (or broken) wires or connections in control box.
6.
Defective rectifier.
1.
Reset circuit breakers, replace if defective.
2.
Check output with another meter, replace meter if defective.
3.
Disconnect the load. Check voltage at receptacle cord set.
Check motors, appliances and load leads for short circuit.
Repair short.
4.
Remove panel cover and check for voltage to the receptacles. Replace defective receptacles.
5.
Remove panel cover and check all wiring and connections.
Tighten and/or repair where necessary.
6.
Test rectifier. Replace if defective.
7.
8.
9.
10.
Dirty slip rings.
Brushes binding in holders.
Shorted or open armature.
Shorted or open field coils.
7.
Clean and polish. Use 00 sandpaper or crocus cloth,
never use emery paper.
8.
Check brushes for swelling; replace defective brushes; clean brush holders.
9.
Measure armature resistance. Replace armature if open or shorted.
10.
Measure between leads for open or short. Replace field coils if defective.
Low voltage.
1.
Engine speed too slow.
4.
Incorrect field excitation.
(No-load output low.)
1.
Check engine speed. Increase RPM if necessary.
2.
Generator overloaded.
2.
Reduce load if it is higher than the rated capacity of the generator. (See generator nameplate).
3.
Inadequate engine horsepower.
3.
Generator requires 2.0 HP/1000 watts output. Obtain larger engine if necessary.
4.
Check for worn brushes and weak or broken brush springs; replace as required. Check input AC voltage to rectifier.
Check rectifier output DC voltage to positive DC brush. If no
DC voltage is present at the brush, replace the rectifier.
Check for dirty slip rings. Clean them if they are dirty.
High voltage.
1.
Engine speed too fast.
Excessive vibration.
1.
Check engine speed for correct input RPM.
Output voltage 1.
Tumbling bar (coupling shaft) flickering or misalignment.
fluctuation.
2.
Engine speed not constant.
1.
Reduce tumbling bar misalignment to less than 15 degrees.
4.
Tumbling bar U-joints not synchronized.
2.
Engine governor may be worn or improperly adjusted. Set or repair defective governor.
3.
Loose connection in field circuit.
3.
Check and tighten connections.
4.
Reassemble tumbling bar; see Figure 7.
1.
Correct misalignment. It should be less than 15 degrees.
1.
Power take-off misalignment excessive.
2.
Loose mounting nuts and bolts or hold-down studs.
3.
Universal joints in coupling shaft worn or dry.
4.
Defective bearings.
2.
3.
4.
Tighten mounting nuts and bolts; repair hold-down stud mountings.
Repair or replace defective parts.
Check for possible causes. Replace defective bearings.
Generator 1.
Poor ventilation.
overheating.
2.
Generator overloaded.
Oil leak.
3.
Shorted turns in field or armature windings.
1.
Loose plug in gear case.
2.
Defective seal, gasket, or plug in gear case.
1.
Clean ventilation and cooling fan screens.
2.
Reduce load, then check voltage and current.
3.
Replace defective components.
1.
2.
Tighten plug.
Replace seal(s), gaskets or plugs. Maintain correct oil level.