2 LOGO! logic module
2
© Siemens AG 2011
LOGO! logic module
2/2
2/2
Introduction
LOGO! logic module
2/3
2/3
2/6
2/8
2/11
2/13
2/18
2/22
LOGO! modular
LOGO! modular basic versions
SIPLUS LOGO! modular basic versions
LOGO! modular pure versions
SIPLUS LOGO! modular pure versions
LOGO! modular expansion modules
SIPLUS LOGO! modular expansion
modules
LOGO! CM EIB/KNX communication
module
AS-Interface connection for LOGO!
2/23
2/23
2/33
LOGO!Power
LOGO!Power
SIPLUS LOGO!Power
2/35
LOGO!Contact
2/36
LOGO! software
2/21
Brochures
For brochures serving as selection
guides for SIMATIC products refer to:
http://www.siemens.com/simatic/
printmaterial
Siemens ST 70 · 2011
© Siemens AG 2011
LOGO! logic module
Introduction
LOGO! logic module
■ Overview
■ General technical data of the SIPLUS LOGO
2
Ambient temperature range
-40/-25 ... +70 °C
Conformal coating
Coating of the printed circuit
boards and the electronic components
Technical data
The technical data of the
standard product applies except
for the ambient conditions.
Ambient conditions
LOGO! logic module
• The compact, easy-to-use and low-cost solution for simple
control tasks
• Compact, easy to operate, universally applicable without
accessories
• "All in one": Integrated display and operator panel
• 36 different functions can be connected at the click of a button
or by means of PC software; up to 130 times over
• Functions are easily changed at the press of a key. No more
time-consuming rewiring
SIPLUS LOGO!
• The controller for use in the toughest ambient conditions
• With extended temperature range from -40/-25 °C to +70 °C
• Suitable for medial exposure (harmful gas atmosphere)
• Condensation permissible
• With the proven PLC technology of LOGO!
• Easy to handle, program, maintain, and service
• Ideal for use in automotive engineering, environmental
engineering, mining, chemical plants, conveying technology,
food industry, etc.
Accessories:
• The front plate mounting set also allows simple and reliable
installation of the logic modules in front plates; IP65 protection
is thus possible.
• In order to ensure dependable operation of SIPLUS devices
supplied by the battery in conjunction with combustion
engines, it is necessary to put in a SIPLUS upmiter upstream
device between the battery and the SIPLUS LOGO!.
For further information, please go to:
www.siemens.com/siplus-extreme
For brochures serving as selection guides for SIMATIC products
refer to:
www.siemens.com/simatic/printmaterial
2/2
Siemens ST 70 · 2011
Relative humidity
5 ... 100%, condensation allowed
Biologically active substances
Conformity with EN 60721-3-3,
Class 3B2 mold and fungal
spores (except fauna)
Chemically active substances
Conformity with EN 60721-3-3,
Class 3C4 incl. salt mist and ISA–
S71.04 severity level G1; G2; G3;
GX 1)2)
Mechanically active substances
Conformity with EN 60721-3-3,
Class 3S4 including conductive
sand, dust 2)
Air pressure (depending on the
highest positive temperature range
specified)
1080 ... 795 hPa
(-1000 ... +2000 m)
see ambient temperature range
795 ... 658 hPa (+2000 ... 3500 m)
derating 10 K
658 ... 540 hPa
(+3500 ... +5000 m)
derating 20 K
1)
2)
ISA-S71.04 severity level GX:
Long-term load:
SO2 < 4.8 ppm; H2S < 9.9 ppm; Cl < 0.2 ppm; HCl < 0.66 ppm;
HF < 0.12 ppm; NH < 49 ppm; O3 < 0.1 ppm; NOX < 5.2 ppm
Limit value (max. 30 min/d):
SO2 < 17.8 ppm; H2S < 49.7 ppm; Cl < 1.0 ppm; HCl < 3.3 ppm;
HF < 2.4 ppm; NH < 247 ppm; O3 < 1.0 ppm; NOX < 10.4 ppm
The supplied plug covers must remain in place over the unused
interface when operated in atmospheres containing corrosive gases!
© Siemens AG 2011
LOGO! logic module
LOGO! modular
LOGO! modular basic versions
■ Overview
• The space-saving basic versions
• Interface for the connection of expansion modules, up to
24 digital inputs, 16 digital outputs, 8 analog inputs and
2 analog outputs can be addressed
• With connection option for LOGO! TD text display (can be
connected to all LOGO! 0BA6 basic versions)
■ Technical specifications
Supply voltages
Rated value
• 12 V DC
• 24 V DC
• 115 V DC
• 230 V DC
• Permissible range, lower
limit (DC)
• Permissible range, upper
limit (DC)
• 24 V AC
• 115 V AC
• 230 V AC
• Permissible range, lower
limit (AC)
• Permissible range, upper
limit (AC)
Time
Time switching clocks
• Power reserve
6ED1 052-1CC01-0BA6
6ED1 052-1MD00-0BA6
6ED1 052-1HB00-0BA6
Yes
Yes
Yes
Yes
6ED1 052-1FB00-0BA6
20.4 V
10.8 V
20.4 V
Yes
Yes
100 V
28.8 V
28.8 V
28.8 V
253 V
Yes
20.4 V
Yes
Yes
85 V
26.4 V
265 V
80 h
80 h
80 h
80 h
8; of which 4 can be used
in analog mode (0 to 10 V)
8; of which 4 can be used
in analog mode (0 to 10 V)
8
8
Digital outputs
Number of digital outputs
4; Transistor
4; Relay
4; Relay
4; Relay
Short-circuit protection
Yes; electrical (1 A)
No; external fusing
necessary
No; external fusing
necessary
No; external fusing
necessary
Output current
• for signal "1" permissible
range for 0 to 55 °C, max.
0.3 A
3A
10 A
3A
10 A
3A
10 A
Yes
Yes
Yes
Digital inputs
Number of digital inputs
Relay outputs
Switching capacity of
contacts
• with inductive load, max.
• with resistive load, max.
EMC
Emission of radio interference
acc. to EN 55 011
• Emission of radio interference acc. to EN 55 011
(limit value class B)
Yes; Radio interference
suppression according to
EN55011, limit value
class B
Siemens ST 70 · 2011
2/3
2
© Siemens AG 2011
LOGO! logic module
LOGO! modular
LOGO! modular basic versions
■ Technical specifications (continued)
2
6ED1 052-1CC01-0BA6
6ED1 052-1MD00-0BA6
6ED1 052-1HB00-0BA6
6ED1 052-1FB00-0BA6
Environmental
requirements
Operating temperature
• Min.
• Max.
0 °C
55 °C
0 °C
55 °C
0 °C
55 °C
0 °C
55 °C
Degree of protection
IP20
Yes
Yes
Yes
Yes
Standards, approvals,
certificates
CSA approval
Yes
Yes
Yes
Yes
Developed according to
IEC1131
Yes
Yes
Yes
Yes
FM approval
Yes
Yes
Yes
Yes
According to VDE 0631
Yes
Yes
Yes
Yes
Marine approval
Yes
Yes
Yes
Yes
UL approval
Yes
Yes
Yes
Yes
on 35 mm DIN rail,
4 spacing units wide
72 mm
90 mm
55 mm
on 35 mm DIN rail,
4 spacing units wide
72 mm
90 mm
55 mm
on 35 mm DIN rail,
4 spacing units wide
72 mm
90 mm
55 mm
on 35 mm DIN rail,
4 spacing units wide
72 mm
90 mm
55 mm
Dimensions and weight
Dimensions
• Mounting
• Width
• Height
• Depth
■ Ordering data
LOGO! logic module 24C
Order No.
I
6ED1 052-1CC01-0BA6
SIPLUS LOGO! TD text display
6ED1 052-1MD00-0BA6
6AG1 055-4MH00-2BA0
(extended temperature range
-10 ... +60 °C and medial
exposure)
4-line text display, can be
connected to all LOGO! 0BA6
Basic and Pure versions,
including connecting cable
LOGO! manual
6ED1 052-1HB00-0BA6
24 V AC/DC power supply,
8x 24 V AC/DC digital inputs,
4x 10 A relay outputs,
integral time switch;
200 function blocks can be
interlinked,
modular expansion capability
LOGO! logic module 230RC
6ED1 055-4MH00-0BA0
4-line text display, can be
connected to all LOGO! 0BA6
Basic and Pure versions,
including connecting cable
12/24 V DC power supply,
8 x 12/24 V DC digital inputs, of
which 4 can be used in analog
mode (0 to 10 V),
4 x 10 A relay outputs,
integrated time switch;
200 function blocks can be
interlinked,
modular expansion capability
LOGO! logic module 24RC
Accessories
LOGO! TD text display
12/24 V DC power supply,
8x 12/24 V DC digital inputs, of
which 4 can be used in analog
mode (0 to 10 V),
4x 10 A relay outputs,
integral time switch;
200 function blocks can be
interlinked,
modular expansion capability
LOGO! logic module 12/24RC
Order No.
German
6ED1 050-1AA00-0AE7
English
6ED1 050-1AA00-0BE7
French
6ED1 050-1AA00-0CE7
Spanish
6ED1 050-1AA00-0DE7
Italian
6ED1 050-1AA00-0EE7
Chinese
6ED1 050-1AA00-0KE7
6ED1 052-1FB00-0BA6
115/230 V AC/DC power supply,
8x 115/230 V AC/DC digital
inputs,
4x 10 A relay outputs,
integral time switch;
200 function blocks can be
interlinked,
modular expansion capability
I: Subject to export regulations AL: N and ECCN: EAR99H
2/4
Siemens ST 70 · 2011
© Siemens AG 2011
LOGO! logic module
LOGO! modular
LOGO! modular basic versions
■ Ordering data
Order No.
LOGO! Memory Card
6ED1 056-1DA00-0BA0
Program module for copying, with
know-how protection
6ED1 056-6XA00-0BA0
Battery module for backing up the
integral real-time clock (not
LOGO! 24)
LOGO! memory/battery card
6ED1 056-7DA00-0BA0
Combined program and battery
module, with know-how protection
and for backing up the integral
real-time clock (not LOGO! 24)
6AG1 057-1AA01-0BA6
J
6ED1 058-0BA02-0YA0
For programming on the PC in
LAD/FBD; executes on Windows
98 SE and higher, Linux, MAC
OSX; on CD-ROM
LOGO!Soft Comfort V6.0
upgrade
J
LOGO! PC cable
6ED1 058-0CA02-0YE0
6ED1 057-1AA00-0BA0
For program transfer between
LOGO! and the PC
For transferring the program
between LOGO! and PC,
including driver on CD-ROM
Width 4 modular spacings
6AG1 057-1AA00-0AA0
Width 4 modular spacings,
with keys
6AG1 057-1AA00-0AA3
Width 8 modular spacings
6AG1 057-1AA00-0AA1
Width 8 modular spacings,
with keys
6AG1 057-1AA00-0AA2
Contains LOGO! 12/24RC,
LOGO! USB PC cable,
LOGO!Soft Comfort V6.0, manual,
screwdriver, information material
German
J
6ED1 057-3BA00-0AA5
English
J
6ED1 057-3BA00-0BA5
German
J
6ED1 057-3AA02-0AA0
English
J
6ED1 057-3AA02-0BA0
German
J
6ED1 057-3BA10-0AA0
English
J
6ED1 057-3BA10-0BA0
LOGO! News Box, 230 V
Upgrade from V1.0 to V6.0
LOGO! USB PC cable
2
Front plate mounting set
LOGO! News Box, 12/24 V
L
Programming device used to
simultaneously reproduce
program module contents on up
to 8 program modules
LOGO!Soft Comfort V6.0
6ED1 057-1CA00-0BA0
Adapter cable for analog modem
communication
LOGO! battery card
LOGO! PROM
Order No.
LOGO! modem cable
J
6ED1 057-1AA01-0BA0
Contains LOGO! 230RC, LOGO!
USB PC cable, LOGO!Soft
Comfort V6.0, manual, screwdriver, information material
LOGO! TD News Box, 12/24 V
Contains LOGO! 12/24RCo,
LOGO! TD, LOGO! USB PC
cable, LOGO! Soft Comfort V6.0,
manual, screwdriver, information
material
J: Subject to export regulations AL: N and ECCN: EAR99S
L: Subject to export regulations AL: 9I999 and ECCN: N
Siemens ST 70 · 2011
2/5
© Siemens AG 2011
LOGO! logic module
LOGO! modular
SIPLUS LOGO! modular basic versions
■ Overview
• The space-saving basic versions
• Interface for the connection of expansion modules, up to
24 digital inputs, 16 digital outputs, 8 analog inputs and
2 analog outputs can be addressed
• With connection option for LOGO! text display TD (can be
connected to all LOGO! 0BA6 basic versions)
2
Note:
SIPLUS extreme products are based on Siemens Industry
standard products. The contents listed here were taken from the
respective standard products. SIPLUS extreme-specific information was added.
SIPLUS LOGO! 24
SIPLUS LOGO! 12/24RC
SIPLUS LOGO! 24RC
SIPLUS LOGO! 230RC
Order number
6AG1 052-1CC01-2BA6
6AG1 052-1FB00-2BA6
6AG1 052-1HB00-2BA6
6AG1 052-1MD00-2BA6
Order No. based on
6ED1 052-1CC01-0BA6
6ED1 052-1FB00-0BA6
6ED1 052-1HB00-0BA6
6ED1 052-1MD00-0BA6
Ambient temperature range
-25°C to +70 °C
Conformal coating
Coating of the printed circuit boards and the electronic components
Technical data
The technical data of the standard product applies except for the ambient conditions.
Ambient conditions
Relative humidity
5 ... 100 %
Condensation permissible
Biologically active
substances
Conformity with EN 60721-3-3, Class 3B2 mold and fungal spores (except fauna)
Chemically active
substances
Conformity with EN 60721-3-3, Class 3C4 incl. salt mist and ISA–S71.04 severity level G1; G2; G3; GX 1) 2)
Mechanically active
substances
Conformity with EN 60721-3-3, Class 3S4 including conductive sand, dust 2)
Air pressure (depending on 1080 ... 795 hPa (-1000 ... +2000 m)
the highest positive temper- see ambient temperature range
ature range specified)
795 ... 658 hPa (+2000 ... +3500 m)
derating 10 K
658 ... 540 hPa (+3500 ... +5000 m)
derating 20 K
1)
2)
ISA-S71.04 severity level GX: Long-term load:
SO2 < 4.8 ppm; H2S < 9.9 ppm; Cl < 0.2 ppm; HCl < 0.66 ppm; HF < 0.12 ppm; NH < 49 ppm; O3 < 0.1 ppm; NOX < 5.2 ppm
Limit value (max. 30 min/d):
SO2 < 17.8 ppm; H2S < 49.7 ppm; Cl < 1.0 ppm; HCl < 3.3 ppm; HF < 2.4 ppm; NH < 247 ppm; O3 < 1.0 ppm; NOX < 10.4 ppm
The supplied plug covers must remain in place over the unused interface when operated in atmospheres containing corrosive gases!
The technical documentation on SIPLUS can be found here:
www.siemens.com/siplus-extreme
2/6
Siemens ST 70 · 2011
© Siemens AG 2011
LOGO! logic module
LOGO! modular
SIPLUS LOGO! modular basic versions
■ Ordering data
SIPLUS LOGO! 24
Order No.
I
6AG1 052-1CC01-2BA6
Order No.
Accessories
(extended temperature range and
medial exposure)
SIPLUS Upmiter upstream
device
24 V DC power supply,
8x 24 V DC digital inputs, of
which 4 can be used in analog
mode (0 to 10 V),
4x 24 V DC digital outputs, 0.3 A;
integrated time switch;
200 function blocks can be
interlinked,
modular expansion capability
for reliable operation at the
battery of combustion engines
SIPLUS LOGO! 12/24RC
Additional accessories
L
L
2
6AG1 053-1AA00-2AA0
See LOGO! modular basic
versions
6AG1 052-1MD00-2BA6
(extended temperature range and
medial exposure)
12/24 V DC power supply,
8x 12/24 V DC digital inputs, of
which 4 can be used in analog
mode (0 to 10 V),
4x 10 A relay outputs,
integral time switch;
200 function blocks can be
interlinked,
modular expansion capability
SIPLUS LOGO! 24RC
6AG1 052-1HB00-2BA6
(extended temperature range and
medial exposure)
24 V AC/DC power supply,
8x 24 V AC/DC digital inputs,
4x 10 A relay outputs,
integral time switch;
200 function blocks can be
interlinked,
modular expansion capability
SIPLUS LOGO! 230RC
6AG1 052-1FB00-2BA6
(extended temperature range and
medial exposure)
115/230 V AC/DC power supply,
8x 115/230 V AC/DC digital
inputs,
4x 10 A relay outputs,
integral time switch;
200 function blocks can be
interlinked,
modular expansion capability
I: Subject to export regulations AL: N and ECCN: EAR99H
L: Subject to export regulations AL: 9I999 and ECCN: N
Siemens ST 70 · 2011
2/7
© Siemens AG 2011
LOGO! logic module
LOGO! modular
LOGO! modular pure versions
■ Overview
• The cost-optimized basic versions
• Interface for the connection of expansion modules, up to
24 digital inputs, 16 digital outputs, 8 analog inputs and
2 analog outputs can be addressed
• With connection option for LOGO! TD text display (can be
connected to all LOGO! 0BA6 basic versions)
2
■ Technical specifications
Supply voltages
Rated value
• 12 V DC
• 24 V DC
• 115 V DC
• 230 V DC
• permissible range, lower
limit (DC)
• permissible range, upper
limit (DC)
• 24 V AC
• 115 V AC
• 230 V AC
• permissible range, lower
limit (AC)
• permissible range, upper
limit (AC)
Time of day
Time switching clocks
• Number
• Power reserve
6ED1 052-2CC01-0BA6
6ED1 052-2MD00-0BA6
6ED1 052-2HB00-0BA6
Yes
Yes
Yes
Yes
6ED1 052-2FB00-0BA6
20.4 V
10.8 V
20.4 V
Yes
Yes
100 V
28.8 V
28.8 V
28.8 V
253 V
Yes
20.4 V
Yes
Yes
85 V
26.4 V
265 V
190
80 h
8
80 h
8
80 h
8
80 h
8; of which 4 can be used
in analog mode (0 to 10 V)
8; of which 4 can be used
in analog mode (0 to 10 V)
8
8
Digital outputs
Number of digital outputs
4; Transistor
4; Relay
4; Relay
4; Relay
Short-circuit protection
Yes; electrical (1 A)
No; external fusing
necessary
No; external fusing
necessary
No; external fusing
necessary
Output current
• for signal "1" permissible
range for 0 to 55 °C, max.
0.3 A
3A
10 A
3A
10 A
3A
10 A
Digital inputs
Number of digital inputs
Relay outputs
Switching capacity of
contacts
• with inductive load, max.
• with resistive load, max.
2/8
Siemens ST 70 · 2011
© Siemens AG 2011
LOGO! logic module
LOGO! modular
LOGO! modular pure versions
■ Technical specifications (continued)
6ED1 052-2CC01-0BA6
EMC
Emission of radio interference
acc. to EN 55 011
• Emission of radio interference acc. to EN 55 011
(limit value class B)
6ED1 052-2MD00-0BA6
6ED1 052-2HB00-0BA6
6ED1 052-2FB00-0BA6
2
Yes; Radio interference
suppression according to
EN55011, limit value
class B
Yes
Yes
Yes
Environmental
requirements
Operating temperature
• Min.
• Max.
0 °C
55 °C
0 °C
55 °C
0 °C
55 °C
0 °C
55 °C
Degree of protection
IP20
Yes
Yes
Yes
Yes
Standards, approvals,
certificates
CSA approval
Yes
Yes
Yes
Yes
Developed according to
IEC1131
Yes
Yes
Yes
Yes
FM approval
Yes
Yes
Yes
Yes
According to VDE 0631
Yes
Yes
Yes
Yes
Marine approval
Yes
Yes
Yes
Yes
UL approval
Yes
Yes
Yes
Yes
on 35 mm DIN rail,
4 spacing units wide
72 mm
90 mm
55 mm
on 35 mm DIN rail,
4 spacing units wide
72 mm
90 mm
55 mm
on 35 mm DIN rail,
4 spacing units wide
72 mm
90 mm
55 mm
on 35 mm DIN rail,
4 spacing units wide
72 mm
90 mm
55 mm
Dimensions and weight
Dimensions
• Mounting
• Width
• Height
• Depth
■ Ordering data
LOGO! logic module 24Co
Order No.
I
6ED1 052-2CC01-0BA6
Order No.
LOGO! logic module 24RCo
24 V DC power supply,
8 digital inputs 24 V DC, of which
4 can be used in analog mode
(0 to 10 V), 4 digital outputs
24 V DC, 0.3 A, integrated time
switch; without display and
keyboard; 200 function blocks
can be interlinked, modular
expansion capability
24 V AC/DC power supply,
8 digital inputs 24 V AC/DC,
4 relay outputs 10 A, integral time
switch; without display and
keyboard; 200 function blocks
can be interlinked, modular
expansion capability
LOGO! logic module 12/24RCo
115/230 V AC/DC power supply,
8 digital inputs 115/230 V AC/DC,
4 relay outputs 10 A,
integral time clock;
without display and keyboard;
200 function blocks can be interlinked,
modular expansion capability
12/24 V DC power supply,
8 digital inputs 12/24 V DC, of
which 4 can be used in analog
mode (0 to 10 V),
4 relay outputs 10 A,
integral time switch;
without display and keyboard;
200 function blocks can be interlinked,
modular expansion capability
LOGO! logic module 230RCo
6ED1 052-2MD00-0BA6
6ED1 052-2HB00-0BA6
6ED1 052-2FB00-0BA6
I: Subject to export regulations AL: N and ECCN: EAR99H
Siemens ST 70 · 2011
2/9
© Siemens AG 2011
LOGO! logic module
LOGO! modular
LOGO! modular pure versions
■ Ordering data
Order No.
Accessories
2
Order No.
LOGO! memory/battery card
LOGO! TD text display
6ED1 055-4MH00-0BA0
4-line text display, can be
connected to all LOGO! 0BA6
Basic and Pure versions,
including connecting cable
SIPLUS LOGO! TD text display
Combined program and battery
module, with know-how protection
and for backing up the integral
real-time clock (not LOGO! 24o)
LOGO! PROM
6AG1 055-4MH00-2BA0
(extended temperature range
-10 ... +60 °C and medial
exposure)
German
6ED1 050-1AA00-0AE7
LOGO!Soft Comfort V6.0
upgrade
English
6ED1 050-1AA00-0BE7
Upgrade from V1.0 to V6.0
French
6ED1 050-1AA00-0CE7
LOGO! PC cable
Spanish
6ED1 050-1AA00-0DE7
Italian
6ED1 050-1AA00-0EE7
For program transfer between
LOGO! and the PC
Chinese
6ED1 050-1AA00-0KE7
LOGO! USB PC cable
LOGO! Memory Card
6ED1 056-1DA00-0BA0
For transferring the program
between LOGO! and PC,
including driver on CD-ROM
Program module for copying, with
know-how protection
Battery module for backing up the
integral real-time clock (not
LOGO! 24)
6AG1 057-1AA01-0BA6
J
6ED1 058-0BA02-0YA0
J
6ED1 058-0CA02-0YE0
For programming on the PC in
LAD/FBD; executes on Windows
98 SE and higher, Linux, MAC
OSX; on CD-ROM
LOGO! manual
LOGO! battery card
L
Programming device used to
simultaneously reproduce
program module contents on up
to 8 program modules
LOGO!Soft Comfort V6.0
4-line text display, can be
connected to all LOGO! 0BA6
Basic and Pure versions,
including connecting cable
6ED1 056-7DA00-0BA0
6ED1 056-6XA00-0BA0
LOGO! modem cable
6ED1 057-1AA00-0BA0
J
6ED1 057-1AA01-0BA0
6ED1 057-1CA00-0BA0
Adapter cable for analog modem
communication
J: Subject to export regulations AL: N and ECCN: EAR99S
L: Subject to export regulations AL: 9I999 and ECCN: N
2/10
Siemens ST 70 · 2011
© Siemens AG 2011
LOGO! logic module
LOGO! modular
SIPLUS LOGO! modular pure versions
■ Overview
• Basic versions optimized for costs
• Interface for the connection of expansion modules, up to
24 digital inputs, 16 digital outputs, 8 analog inputs and
2 analog outputs can be addressed
• With connection option for LOGO! text display TD (can be
connected to all LOGO! 0BA6 basic versions)
Note:
SIPLUS extreme products are based on Siemens Industry
standard products. The contents listed here were taken from the
respective standard products. SIPLUS extreme-specific information was added.
SIPLUS LOGO! 24o
SIPLUS LOGO! 12/24RCo
SIPLUS LOGO! 24RCo
SIPLUS LOGO! 230RCo
Order number
6AG1 052-2CC01-2BA6
6AG1 052-2MD00-2BA6
6AG1 052-2HB00-2BA6
6AG1 052-2FB00-2BA6
Order No. based on
6ED1 052-2CC01-0BA6
6ED1 052-2MD00-0BA6
6ED1 052-2HB00-0BA6
6ED1 052-2FB00-0BA6
Ambient temperature range
-40 °C to +70 °C
Conformal coating
Coating of the printed circuit boards and the electronic components
Technical data
The technical data of the standard product applies except for the ambient conditions.
Ambient conditions
Relative humidity
5 ... 100 %
Condensation permissible
Biologically active
substances
Conformity with EN 60721-3-3, Class 3B2 mold and fungal spores (except fauna)
Chemically active
substances
Conformity with EN 60721-3-3, Class 3C4 incl. salt mist and ISA–S71.04 severity level G1; G2; G3; GX 1) 2)
Mechanically active
substances
Conformity with EN 60721-3-3, Class 3S4 including conductive sand, dust 2)
Air pressure (depending on
the highest positive temperature range specified)
1080 ... 795 hPa (-1000 ... +2000 m)
see ambient temperature range
795 ... 658 hPa (+2000 ... +3500 m)
derating 10 K
658 ... 540 hPa (+3500 ... +5000 m)
derating 20 K
1)
2)
ISA-S71.04 severity level GX: Long-term load:
SO2 < 4.8 ppm; H2S < 9.9 ppm; Cl < 0.2 ppm; HCl < 0.66 ppm; HF < 0.12 ppm; NH < 49 ppm; O3 < 0.1 ppm; NOX < 5.2 ppm
Limit value (max. 30 min/d):
SO2 < 17.8 ppm; H2S < 49.7 ppm; Cl < 1.0 ppm; HCl < 3.3 ppm; HF < 2.4 ppm; NH < 247 ppm; O3 < 1.0 ppm; NOX < 10.4 ppm
The supplied plug covers must remain in place over the unused interface when operated in atmospheres containing corrosive gases!
The technical documentation on SIPLUS can be found here:
www.siemens.com/siplus-extreme
Siemens ST 70 · 2011
2/11
2
© Siemens AG 2011
LOGO! logic module
LOGO! modular
SIPLUS LOGO! modular pure versions
■ Ordering data
2
Order No.
Order No.
SIPLUS LOGO! 24o
Accessories
(extended temperature range and
medial exposure)
SIPLUS Upmiter upstream
device
I
24 V DC power supply,
8 digital inputs 24 V DC, of which
4 can be used in analog mode
(0 to 10 V),
4 digital outputs 24 V DC, 0.3 A,
integrated time switch;
without display and keyboard;
200 function blocks can be
interlinked,
modular expansion capability
6AG1 052-2CC01-2BA6
L
6AG1 053-1AA00-2AA0
for reliable operation at the
battery of combustion engines
Additional accessories
See LOGO! modular pure
versions, page 2/10
SIPLUS LOGO! 12/24RCo
(extended temperature range and
medial exposure)
12/24 V DC power supply,
8 digital inputs 12/24 V DC, of
which 4 can be used in analog
mode (0 to 10 V),
4 relay outputs 10 A,
integral time switch;
without display and keyboard;
200 function blocks can be
interlinked,
modular expansion capability
6AG1 052-2MD00-2BA6
SIPLUS LOGO! 24RCo
(extended temperature range and
medial exposure)
24 V AC/DC power supply,
8 digital inputs 24 V AC/DC,
4 relay outputs 10 A,
integral time switch;
without display and keyboard;
200 function blocks can be
interlinked,
modular expansion capability
6AG1 052-2HB00-2BA6
SIPLUS LOGO! 230RCo
(extended temperature range and
medial exposure)
115/230 V AC/DC power supply,
8 digital inputs 115/230 V AC/DC,
4 relay outputs 10 A,
integral time clock;
without display and keyboard;
200 function blocks can be
interlinked,
modular expansion capability
6AG1 052-2FB00-2BA6
I: Subject to export regulations AL: N and ECCN: EAR99H
L: Subject to export regulations AL: 9I999 and ECCN: N
2/12
Siemens ST 70 · 2011
© Siemens AG 2011
LOGO! logic module
LOGO! modular
LOGO! modular expansion modules
■ Overview
• Expansion modules for the connection to LOGO! Modular
• With digital inputs and outputs, analog inputs or analog
outputs
■ Technical specifications
Supply voltages
Rated value
• 12 V DC
• 24 V DC
• 115 V DC
• 230 V DC
• Permissible range,
lower limit (DC)
• Permissible range,
upper limit (DC)
• 24 V AC
• 115 V AC
• 230 V AC
• Permissible range,
lower limit (AC)
• Permissible range,
upper limit (AC)
6ED1 055-1CB00-0BA0
6ED1 055-1HB00-0BA0
6ED1 055-1MB00-0BA1
Yes
Yes
Yes
Yes
6ED1 055-1FB00-0BA1
20.4 V
20.4 V
10.8 V
Yes
Yes
100 V
28.8 V
28.8 V
28.8 V
253 V
Yes
20.4 V
Yes
Yes
85 V
26.4 V
265 V
Digital inputs
Number of digital inputs
4
4
4
4
Digital outputs
Number of digital outputs
4
4; Relay
4; Relay
4; Relay
Short-circuit protection
Yes; electrical (1 A)
No; external fusing
necessary
No; external fusing
necessary
No; external fusing
necessary
3A
5A
3A
5A
3A
5A
Yes
Yes
Yes
Relay outputs
Switching capacity of
contacts
• with inductive load, max.
• with resistive load, max.
• thermal continuous current,
max.
EMC
Emission of radio interference
acc. to EN 55 011
• Emission of radio interference acc. to EN 55 011
(limit value class B)
0.3 A
Yes
Siemens ST 70 · 2011
2/13
2
© Siemens AG 2011
LOGO! logic module
LOGO! modular
LOGO! modular expansion modules
■ Technical specifications (continued)
2
6ED1 055-1CB00-0BA0
6ED1 055-1HB00-0BA0
6ED1 055-1MB00-0BA1
6ED1 055-1FB00-0BA1
Environmental
requirements
Operating temperature
• Min.
• Max.
0 °C
55 °C
0 °C
55 °C
0 °C
55 °C
0 °C
55 °C
Degree of protection
IP20
Yes
Yes
Yes
Yes
Standards, approvals,
certificates
CSA approval
Yes
Yes
Yes
Yes
Developed according to
IEC1131
Yes
Yes
Yes
Yes
FM approval
Yes
Yes
Yes
Yes
According to VDE 0631
Yes
Yes
Yes
Yes
Marine approval
Yes
Yes
Yes
Yes
UL approval
Yes
Yes
Yes
Yes
on 35 mm DIN rail,
2 spacing units wide
36 mm; 2 DU
90 mm
55 mm
on 35 mm DIN rail,
2 spacing units wide
36 mm; 2 DU
90 mm
55 mm
on 35 mm DIN rail,
2 spacing units wide
36 mm; 2 DU
90 mm
55 mm
on 35 mm DIN rail,
2 spacing units wide
36 mm; 2 DU
90 mm
55 mm
Dimensions and weight
Dimensions
• Mounting
• Width
• Height
• Depth
Supply voltages
Rated value
• 24 V DC
• 115 V DC
• 230 V DC
• Permissible range, lower limit (DC)
• Permissible range, upper limit (DC)
• 115 V AC
• 230 V AC
• Permissible range, lower limit (AC)
• Permissible range, upper limit (AC)
• Permissible frequency range,
lower limit
• Permissible frequency range,
upper limit
6ED1 055-1CB10-0BA0
6ED1 055-1NB10-0BA0
Yes
Yes
20.4 V
28.8 V
20.4 V
28.8 V
6ED1 055-1FB10-0BA0
Yes
Yes
100 V
253 V
Yes
Yes
85 V
265 V
47 Hz
63 Hz
Digital inputs
Number of digital inputs
8
8
8
Input voltage
• for signal "0"
• for signal "1"
< 5 V DC
> 12 V DC
< 5 V DC
> 12 V DC
< 40 V AC; < 30 V DC
> 79 V AC; > 79 V DC
1 mA
1 mA
0.03 mA
2 mA
2 mA
0.08 mA
1.5 ms
1.5 ms
1.5 ms
1.5 ms
50 ms
50 ms
Input current
• for signal "0", max. (permissible
quiescent current)
• for signal "1", typ.
Input delay (for rated value of input
voltage)
• for standard inputs
- at "0" to "1", max.
- at "1" to "0", max.
2/14
Siemens ST 70 · 2011
© Siemens AG 2011
LOGO! logic module
LOGO! modular
LOGO! modular expansion modules
■ Technical specifications (continued)
6ED1 055-1CB10-0BA0
6ED1 055-1NB10-0BA0
6ED1 055-1FB10-0BA0
Digital outputs
Number of digital outputs
8
8; Relay
8; Relay
Short-circuit protection
Yes; electrical (1 A)
No; external fusing necessary
external fusing necessary
Lamp load, max.
2
1 000 W; 500 W at 115 V AC
1 000 W; 500 W at 115 V AC
Controlling a digital input
Yes
Yes
Yes
Parallel switching of 2 outputs
• for increased power
No
No
No
10 Hz
0.5 Hz
2 Hz
0.5 Hz
10 Hz
2 Hz
0.5 Hz
10 Hz
3A
5A
3A
5A
Yes
Yes
Yes
Environmental requirements
Operating temperature
• Min.
• Max.
0 °C
55 °C
0 °C
55 °C
0 °C
55 °C
Degree of protection
IP20
Yes
Yes
Yes
Standards, approvals, certificates
CSA approval
Yes
Yes
Yes
Developed according to IEC1131
Yes
Yes
Yes
FM approval
Yes
Yes
Yes
According to VDE 0631
Yes
Yes
Yes
Marine approval
Yes
Yes
Yes
UL approval
Yes
Yes
Yes
on 35 mm DIN rail, 4 spacing units
wide
72 mm; 4 DU
90 mm
53 mm
on 35 mm DIN rail, 4 spacing units
wide
72 mm; 4 DU
90 mm
53 mm
on DIN rail 25 mm, 4 module
spaces wide
72 mm; 4 DU
90 mm
53 mm
Switching frequency
• with resistive load, max.
• with inductive load, max.
• mechanical, max.
Relay outputs
Switching capacity of contacts
• with inductive load, max.
• with resistive load, max.
• thermal continuous current, max.
EMC
Emission of radio interference acc. to
EN 55 011
• Emission of radio interference acc.
to EN 55 011 (limit value class B)
Dimensions and weight
Dimensions
• Mounting
• Width
• Height
• Depth
0.3 A
6ED1 055-1MA00-0BA0
Supply voltages
Rated value
• 12 V DC
• 24 V DC
6ED1 055-1MD00-0BA1
LOGO! AM2 RTD
Product type designation
Yes
Yes
Yes; 10,8 ... 28.8 V DC
Yes; 10.8 ... 28.8 V DC
Siemens ST 70 · 2011
2/15
© Siemens AG 2011
LOGO! logic module
LOGO! modular
LOGO! modular expansion modules
■ Technical specifications (continued)
2
Analog inputs
Number of analog inputs
Input ranges
• Voltage
• Current
• Resistance thermometer
6ED1 055-1MA00-0BA0
6ED1 055-1MD00-0BA1
2
2; 2 or 3 wire connection
Yes
Yes
Yes; for PT100/PT1000 sensors
Input ranges (rated values), voltages
• 0 to +10 V
Yes
Input ranges (rated values), currents
• 0 to 20 mA
Yes
EMC
Emission of radio interference acc. to
EN 55 011
• Emission of radio interference acc.
to EN 55 011 (limit value class B)
Yes
Yes; Radio interference suppression according to
EN55011, limit value class B
Environmental requirements
Operating temperature
• Min.
• Max.
0 °C
55 °C
0 °C
55 °C
Degree of protection
IP20
Yes
Yes
Standards, approvals, certificates
CSA approval
Yes
Yes; C22.2 Number 142
Developed according to IEC1131
Yes
Yes; EN 61131-2 (IEC 1131-2)
FM approval
Yes
Yes; FM-Standards No. 3611, 3600,
3810 Class I, Division 2, Group A, B, C, D
According to VDE 0631
Yes
Marine approval
Yes
Yes; ABS, BV, DNV, GL, LRS, Class NK
UL approval
Yes
Yes; UL 508
Dimensions and weight
Dimensions
• Mounting
• Width
• Height
• Depth
on 35 mm DIN rail, 2 spacing units wide
36 mm
90 mm
55 mm
36 mm
90 mm
53 mm
6ED1 055-1MM00-0BA1
6ED1 055-1MM00-0BA1
Supply voltages
Rated value
• 12 V DC
• 24 V DC
No
Yes
Analog outputs
Number of analog outputs
2
Output ranges, voltage
• 0 to 10 V
Yes
EMC
Emission of radio interference acc.
to EN 55 011
• Emission of radio interference acc.
to EN 55 011 (limit value class B)
Environmental requirements
Operating temperature
• Min.
• Max.
2/16
Siemens ST 70 · 2011
Yes; Radio interference
suppression according to
EN55011, limit value class B
0 °C
55 °C
Degree of protection
IP20
Yes
Standards, approvals, certificates
CSA approval
Yes
Developed according to IEC1131
Yes
FM approval
Yes
According to VDE 0631
Yes
Marine approval
Yes
UL approval
Yes
Dimensions and weight
Dimensions
• Mounting
• Width
• Height
• Depth
on 35 mm DIN rail, 2 spacing
units wide
36 mm
90 mm
55 mm
© Siemens AG 2011
LOGO! logic module
LOGO! modular
LOGO! modular expansion modules
■ Ordering data
Order No.
6ED1 055-1CB00-0BA0
LOGO! DM8 24
Supply voltage 24 V DC,
4 digital inputs 24 V DC,
4 digital outputs 24 V DC, 0.3 A
Order No.
Accessories
2
LOGO! Manual
LOGO! DM16 24
6ED1 055-1CB10-0BA0
Supply voltage 24 V DC,
8 digital inputs 24 V DC,
8 digital outputs 24 V DC, 0.3 A
LOGO! DM8 12/24R
6ED1 055-1MB00-0BA1
Supply voltage 12/24 V DC,
4 digital inputs 12/24 V DC,
4 relay outputs 5 A
LOGO! DM8 24R
6ED1 055-1HB00-0BA0
German
6ED1 050-1AA00-0AE7
English
6ED1 050-1AA00-0BE7
French
6ED1 050-1AA00-0CE7
Spanish
6ED1 050-1AA00-0DE7
Italian
6ED1 050-1AA00-0EE7
Chinese
6ED1 050-1AA00-0KE7
LOGO! memory card
6ED1 056-1DA00-0BA0
for copying, with know-how
protection
LOGO!Soft Comfort V6.0
Supply voltage24 V AC/DC,
4 digital inputs 24 V AC/DC,
4 relay outputs 5 A
LOGO! DM16 24R
6ED1 055-1NB10-0BA0
Supply voltage 24 V DC,
8 digital inputs 24 V DC,
8 relay outputs 5 A
LOGO!Soft Comfort V6.0
upgrade
LOGO! DM8 230R
6ED1 055-1FB00-0BA1
6ED1 058-0BA02-0YA0
J
6ED1 058-0CA02-0YE0
Upgrade from V1.0 to V6.0
LOGO! PC cable
Supply voltage 115/230 V AC/DC,
4 digital inputs 115/230 V AC/DC,
4 relay outputs 5 A
J
For programming on the PC in
LAD/FBD; executes on Windows
98 SE and higher, Linux, MAC
OSX; on CD-ROM
6ED1 057-1AA00-0BA0
For program transfer between
LOGO! and PC
LOGO! DM16 230R
6ED1 055-1FB10-0BA0
Supply voltage 115/230 V AC/DC,
8 digital inputs 115/230 V AC/DC,
8 relay outputs 5 A
LOGO! AM2
6ED1 055-1MA00-0BA0
Supply voltage 12/24 V DC, two
analog inputs 0 ... 10 V or
0 ... 20 mA, 10-bit resolution
LOGO! AM2 PT 100
I
6ED1 055-1MD00-0BA1
I
6ED1 055-1MM00-0BA1
Supply voltage 12/24 V DC,
2 analog inputs Pt100, temperature range -50 °C ... 200 °C
LOGO! AM2 AQ
Supply voltage 24 V DC, 2 analog
outputs 0 to 10 V, 0/4 to 20 mA
I: Subject to export regulations AL: N and ECCN: EAR99H
J: Subject to export regulations AL: N and ECCN: EAR99S
Siemens ST 70 · 2011
2/17
© Siemens AG 2011
LOGO! logic module
LOGO! modular
SIPLUS LOGO! modular expansion modules
■ Overview
• Expansion modules for connection to LOGO! Modular
• With digital inputs and outputs, analog inputs, or analog
outputs
2
Note:
SIPLUS extreme products are based on Siemens Industry
standard products. The contents listed here were taken from the
respective standard products. SIPLUS extreme-specific information was added.
SIPLUS LOGO! DM8 24
Order No.
6AG1 055-1CB00-2BY0
Order No. based on
6ED1 055-1CB00-0BA0
6AG1 055-1CB00-2XB0
Ambient temperature range
-40 ... +70 °C
Conformal coating
Coating of the printed circuit boards and the electronic components
Technical data
The technical data of the standard product applies except for the ambient conditions.
-25 ... +70 °C
SIPLUS LOGO! DM8 24
Order No.
6AG1 055-1PB00-2BY0
Order No. based on
6ED1 055-1CB00-0BA0
6AG1 055-1PB00-2XB0
Ambient temperature range
-40 ... +70 °C
Conformal coating
Coating of the printed circuit boards and the electronic components
-25 ... +70 °C
Technical data
The technical data of the standard product applies except for the ambient conditions.
SIPLUS LOGO! DM8 24 R
Order Nor
6AG1 055-1HB00-2BY0
Order No. based on
6ED1 055-1HB00-0BA0
6AG1 055-1HB00-2XB0
Ambient temperature range
-40 ... +70 °C
Conformal coating
Coating of the printed circuit boards and the electronic components
Technical data
The technical data of the standard product applies except for the ambient conditions.
-25 ... +70 °C
SIPLUS LOGO! DM8 12/24R
Order No.
6AG1 055-1MB00-2BY1
Order No. based on
6ED1 055-1MB00-0BA1
Ambient temperature range
-40 ... +70 °C
Conformal coating
Coating of the printed circuit boards and the electronic components
Technical data
The technical data of the standard product applies except for the ambient conditions.
2/18
Siemens ST 70 · 2011
6AG1 055-1MB00-2XB1
-25 ... +70 °C
© Siemens AG 2011
LOGO! logic module
LOGO! modular
SIPLUS LOGO! modular expansion modules
■ Overview (continued)
SIPLUS LOGO! DM8 230R
Order No.
6AG1 055-1FB00-2BY1
Order No. based on
6ED1 055-1FB00-0BA1
Ambient temperature range
-40 ... +70 °C
Conformal coating
Coating of the printed circuit boards and the electronic components
Technical data
The technical data of the standard product applies except for the ambient conditions.
2
6AG1 055-1FB00-2XB1
-25 ... +70 °C
SIPLUS LOGO! AM2
Order number
6AG1 055-1MA00-2BY0
Order No. based on
6ED1 055-1MA00-0BA0
6AG1055-1MA00-2XB0
Ambient temperature range
-40 ... +70 °C
Conformal coating
Coating of the printed circuit boards and the electronic components
Technical data
The technical data of the standard product applies except for the ambient conditions.
-25 ... +70 °C
SIPLUS LOGO! AM2 AQ
SIPLUS LOGO! DM16 24R
Order number
6AG1 055-1MM00-2BY1
6AG1 055-1NB10-2BA0
Order No. based on
6ED1 055-1MM00-0BA1
6ED1 055-1CB10-0BA0
Ambient temperature range
-40 ... +70 °C
-25 ... +70 °C
Conformal coating
Coating of the printed circuit boards and the electronic components
Technical data
The technical data of the standard product applies except for the ambient conditions.
Ambient conditions
Ambient conditions
Relative humidity
5 ... 100 %
Condensation permissible
Biologically active substances
Conformity with EN 60721-3-3,
Class 3B2 mold and fungal
spores (except fauna)
Chemically active substances
Conformity with EN 60721-3-3,
Class 3C4 incl. salt mist and ISA–
S71.04 severity level G1; G2; G3;
GX 1 )2)
Mechanically active substances
Conformity with EN 60721-3-3,
Class 3S4 including conductive
sand, dust 2)
Air pressure (depending on the
highest positive temperature range
specified)
1)
2)
1080 ... 795 hPa
(-1000 ... +2000 m)
see ambient temperature range
795 ... 658 hPa
(+2000 ... +3500 m)
derating 10 K
658 ... 540 hPa
(+3500 ... +5000 m)
derating 20 K
ISA-S71.04 severity level GX: Long-term load: SO2 < 4.8 ppm;
H2S < 9.9 ppm; Cl < 0.2 ppm; HCl < 0.66 ppm; HF < 0.12 ppm;
NH < 49 ppm; O3 < 0.1 ppm; NOX < 5.2 ppm
Limit value (max. 30 min/d): SO2 < 17.8 ppm; H2S < 49.7 ppm;
Cl < 1.0 ppm; HCl < 3.3 ppm; HF < 2.4 ppm; NH < 247 ppm;
O3 < 1.0 ppm; NOX < 10.4 ppm
The supplied plug covers must remain in place over the unused
interface when operated in atmospheres containing corrosive gases!
The technical documentation on SIPLUS can be found here:
www.siemens.com/siplus-extreme
Siemens ST 70 · 2011
2/19
© Siemens AG 2011
LOGO! logic module
LOGO! modular
SIPLUS LOGO! modular expansion modules
■ Ordering data
2
Order No.
Order No.
SIPLUS LOGO! DM8 24
SIPLUS LOGO! AM2
(extended temperature range and
medial exposure)
(extended temperature range and
medial exposure)
24 V DC power supply,
four 24 V DC digital inputs,
four 24 V DC digital outputs, 0.3 A
12/24 V DC power supply,
two analog inputs 0 ... 10 V or
0 ... 20 mA, 10 bit resolution
Temperature range -25 ... +70 °C H 6AG1 055-1CB00-2XB0
Temperature range -25 ... +70 °C H 6AG1 055-1MA00-2XB0
Temperature range -40 ... +70 °C L 6AG1 055-1CB00-2BY0
Temperature range -40 ... +70 °C L 6AG1 055-1MA00-2BY0
SIPLUS LOGO! DM8 12/24
SIPLUS LOGO! AM2 AQ
(extended temperature range and
medial exposure)
(extended temperature range and
medial exposure)
12/24 V DC power supply,
four 12/24 V DC digital inputs,
four 24 V DC digital outputs, 0.3 A
24 V DC power supply, 2x analog
inputs 0 ... 10 V, 0/4 ... 20 mA,
10-bit resolution
Temperature range -25 ... +70 °C L 6AG1 055-1PB00-2XB0
Temperature range -40 ... +70 °C L 6AG1 055-1MM00-2BY1
Temperature range -40 ... +70 °C L 6AG1 055-1PB00-2BY0
SIPLUS LOGO! DM16 24R
SIPLUS LOGO! DM8 24R
(extended temperature range and
medial exposure)
(extended temperature range and
medial exposure)
24 V AC/DC power supply,
four 24 V AC/DC digital inputs,
four 5 A relay outputs
Supply voltage 24 V DC,
8x digital outputs 24 V DC,
8x relay outputs 5 A
Temperature range -25 ... +70 °C L 6AG1 055-1NB10-2BA0
Temperature range -25 ... +70 °C A 6AG1 055-1HB00-2XB0
Accessories
Temperature range -40 ... +70 °C L 6AG1 055-1HB00-2BY0
SIPLUS Upmiter upstream
device
SIPLUS LOGO! DM8 12/24R
(extended temperature range and
medial exposure)
12/24 V DC power supply,
four 12/24 V DC digital inputs,
four 5 A relay outputs
L
6AG1 053-1AA00-2AA0
for reliable operation at the
battery of combustion engines
Additional accessories
See LOGO! modular pure
versions, page 2/17
Temperature range -25 ... +70 °C H 6AG1 055-1MB00-2XB1
Temperature range -40 ... +70 °C L 6AG1 055-1MB00-2BY1
SIPLUS LOGO! DM8 230R
(extended temperature range and
medial exposure)
115/230 V AC/DC power supply,
four 115/230 V AC/DC digital
inputs, four 5 A relay outputs
Temperature range -25 ... +70 °C A 6AG1 055-1FB00-2XB1
Temperature range -40 ... +70 °C L 6AG1 055-1FB00-2BY1
A: Subject to export regulations AL: 9I999 and ECCN: 4A994X
H: Subject to export regulations AL: 9I999 and ECCN: EAR99H
L: Subject to export regulations AL: 9I999 and ECCN: N
2/20
Siemens ST 70 · 2011
© Siemens AG 2011
LOGO! logic module
LOGO! modular
LOGO! CM EIB/KNX communication module
■ Overview
■ Technical specifications
CM EIB/KNX
• Expansion module for LOGO! basic versions
• For communication between the LOGO! master and external
EIB components through EIB
2
Supply voltage
24 V AC/DC
Inputs, max.
16 DI/12 DO/8 AI/2 AO
Outputs, max.
16 digital
Continuous current
25 mA
Short-circuit protection
External fuse protection is
required
Integrated time switches/power
reserve
-
Ambient temperature
0 … +55°C
RI specification
To EN 55 011 (limit value class B)
Degree of protection
IP20
Certification
to VDE 0631, IEC61131-2, cULus,
FM
Mounting
On DIN rail 35 mm,
2 module widths wide
Dimensions (W x H x D) in mm
36 (2 MW) × 90 × 55
■ Ordering data
LOGO! CM EIB KNX communi- I
cation module
Order No.
6BK1 700-0BA00-0AA1
for connection to EIB, supply
voltage 24 V DC
Accessories
LOGO! manual
German
6ED1 050-1AA00-0AE7
English
6ED1 050-1AA00-0BE7
French
6ED1 050-1AA00-0CE7
Spanish
6ED1 050-1AA00-0DE7
Italian
6ED1 050-1AA00-0EE7
Chinese
6ED1 050-1AA00-0KE7
I: Subject to export regulations AL: N and ECCN: EAR99H
Siemens ST 70 · 2011
2/21
© Siemens AG 2011
LOGO! logic module
LOGO! modular
AS-Interface connection for LOGO!
■ Overview
2
■ Technical specifications
Each LOGO! can now be connected to the AS-Interface
system
Supply oltage
24 V DC
nputs outputs
4/4
(virtual inputs / outputs)
AS-Interface according to specification
us connection
Ambient temperature
0 ... +55 °C
egree of protection
IP20
ounting
Onto standard mounting rail
imensions
x
x
36 x 90 x 58 mm
ndications of the E s
E
• Green
• Red
• Flashes red/yellow
Status
No data traffic
Zero address
■ Ordering data
An intelligent slave can be integrated into the AS-Interface
system with the AS-Interface for LOGO!. The modular interface
allows the different basic units to be integrated into the system
depending on the required functionality. In addition, the functionality can be quickly and simply adapted to changed requirements by replacing the basic unit.
The interface provides four inputs and four outputs for the
system. These I/Os, however, are not implemented in hardware,
but are only virtually available via the interface.
2/22
Siemens ST 70 · 2011
AS-Interface connection for
LOGO!
Order No.
F
3RK1 400-0CE10-0AA2
F: Subject to export regulations AL: N and ECCN: EAR99
© Siemens AG 2011
LOGO! logic module
LOGO!Power
LOGO!Power
■ Overview
performance range are made possible by: wide-range input,
radio interference class B, the extensive temperature range as
well as numerous certificates.
The LOGO!Power miniature power supply units from Siemens
are the perfect solution for many applications – their flat, stepshaped profile makes them perfectly suited for distribution
boards, for example. Even more fields of application in the lower
Main product features:
• 2 performance classes with 5 V, 12 V, and 15 V each
• 3 performance classes with 24 V
• Flat LOGO! design with an installation depth of only 55 mm
• High efficiency across the entire load range
• Low no-load loss
• Wide-range input from 85 V to 264 V AC
• Operation on DC voltage of 110 V to 300 V
• Constant current for connection of loads with high inrush
current
• Adjustable output voltage
• Green LED for "Output voltage OK"
• Temperature range from -20 °C to +70 °C
• Numerous certificates, such as CE, cULus, FM, GL and ATEX
■ Technical specifications LOGO!Power 5 V
Power supply, type
Order No.
5 V/3 A
6EP1 311-1SH03
5 V/6.3 A
6EP1 311-1SH13
Input
1-phase AC or DC
1-phase AC or DC
Rated voltage Uin rated
100-240 V AC
Wide-range input
100-240 V AC
Wide-range input
Voltage range
85 ... 264 V AC
110 … 300 V DC
85 ... 264 V AC
110 … 300 V DC
Overvoltage strength
2.3 x Uin rated, 1.3 ms
2.3 x Uin rated, 1.3 ms
Mains buffering at Iout rated
> 40 ms at Uin = 187 V
> 40 ms at Uin = 187 V
Rated line frequency, rated line frequency range
50/60 Hz; 47 ... 63 Hz
50/60 Hz; 47 ... 63 Hz
Rated current Iin rated
0.36-0.22 A
0.71-0.37 A
Switch-on current limitation (+25 °C)
< 26 A
< 50 A
I2 t
< 0.8 A2s
< 3 A2s
Built-in incoming fuse
Internal
Internal
Recommended miniature circuit breaker
(IEC 898) in the mains power input
16 A or higher, Characteristic B or 10 A or
higher, Characteristic C
16 A or higher, Characteristic B or 10 A or
higher, Characteristic C
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Uout rated
5 V DC
5 V DC
Total tolerance, static
• Static line compensation
• Static load compensation
±3 %
Approx. 0.2%
Approx. 1.5%
±3 %
Approx. 0.1%
Approx. 2%
Residual ripple
< 100 mVpp (typ. 10 mVpp)
< 100 mVpp (typ. 15 mVpp)
Spikes (bandwidth approx. 20 MHz)
< 100 mVpp (typ. 20 mVpp)
< 100 mVpp (typ. 70 mVpp)
Adjustment range
4.6 ... 5.4 V
4.6 ... 5.4 V
Status indicator
5 V OK = green LED
5 V OK = green LED
On/Off behavior
No overshoot of Uout (soft start)
No overshoot of Uout (soft start)
Startup delay /
voltage rise
< 0.5 s/typ. 15 ms
< 0.5 s/typ. 10 ms
Rated current Iout rated
3A
6.3 A
Current range up to +55 °C
• Derating
0 ... 3 A
0 ... 2.1 A (up to +70 °C)
0 ... 6.3 A
0 ... 4.4 A (up to +70 °C)
Parallel switching for enhanced performance
Yes, 2 units
Yes, 2 units
Siemens ST 70 · 2011
2/23
2
© Siemens AG 2011
LOGO! logic module
LOGO!Power
LOGO!Power
■ Technical specifications LOGO!Power 5 V (continued)
2
Power supply, type
Order No.
5 V/3 A
6EP1 311-1SH03
5 V/6.3 A
6EP1 311-1SH13
Efficiency at Uout rated, Iout rated
Approx. 77%
Approx. 83%
Power loss at Uout rated, Iout rated
Approx. 4 W
Approx. 6 W
Dyn. line compensation
(Uin rated ±15%)
< 0.2 % Uout
< 0.2 % Uout
Dynamic load compensation
(Iout: 10/90/10 %)
Typ. ±3% Uout
Typ. ±3% Uout
Typ. 2 ms
Typ. 2 ms
Typ. 2 ms
Typ. 2 ms
Current limitation
Typ. 3.8 A
Typ. 8.2 A
Short-circuit protection
Constant current characteristic
Constant current characteristic
Sustained short-circuit current rms value
<5A
< 10 A
Primary/secondary isolation
Yes, safety extra low output voltage Uout
according to EN 60950 and EN 50178
Yes, safety extra low output voltage Uout
according to EN 60950 and EN 50178
Efficiency
Closed-loop control
Load step settling time
• 10 to 90%
• 90 to 10%
Protection and monitoring
Safety
Safety class
Class II (without protective conductor)
Class II (without protective conductor)
Safety test
Yes; CB scheme
Yes; CB scheme
CE marking
Yes
Yes
UL/cUL (CSA) approval
cULus-listed (UL 508, CSA C22.2 No. 107.1),
cURus-recognized (UL 60950, CSA C22.2
No. 60950)
cULus-listed (UL 508, CSA C22.2 No. 107.1),
cURus-recognized (UL 60950, CSA C22.2
No. 60950)
Protection against explosion
ATEX (available soon)
ATEX (available soon)
FM approval
Class I Div. 2, Group A, B, C, D T4
Class I Div. 2, Group A, B, C, D T4
Marine approval
GL (available soon)
GL (available soon)
Degree of protection (EN 60529)
IP20
IP20
EMC
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
Not applicable
Not applicable
Noise immunity
EN 61000-6-2
EN 61000-6-2
Operating data
Ambient temperature range
-20 ... +70 °C with natural convection
-20 ... +70 °C with natural convection
Transport and storage temperature range
-40 ... +85 °C
-40 ... +85 °C
Humidity class
Climate class 3K3 according to EN 60721,
no condensation
Climate class 3K3 according to EN 60721,
no condensation
Solid/finely-stranded per screw-type terminal
for 0.5 mm ... 2.5 mm2
2 screw terminals each for 0.5 ... 2.5 mm2
Solid/finely-stranded per screw-type terminal
for 0.5 mm ... 2.5 mm2
2 screw terminals each for 0.5 ... 2.5 mm2
Mechanics
Supply-input connections L1, N
Connections
• Output +
• Output Dimensions (W x H x D) in mm
54 x 90 x 55
72 x 90 x 55
Weight, approx.
0.17 kg
0.25 kg
Mounting
Can be snapped onto standard mounting rail
EN 60715 35x7.5/15
Can be snapped onto standard mounting rail
EN 60715 35x7.5/15
2/24
Siemens ST 70 · 2011
© Siemens AG 2011
LOGO! logic module
LOGO!Power
LOGO!Power
■ Technical specifications LOGO!Power 12 V
Power supply, type
Order No.
12 V/1.9 A
6EP1 321-1SH03
12 V/4.5 A
6EP1 322-1SH03
Input
1-phase AC or DC
1-phase AC or DC
Rated voltage value Uin rated
100-240 V AC
Wide-range input
100-240 V AC
Wide-range input
Voltage range
85 ... 264 V AC
110 … 300 V DC
85 ... 264 V AC
110 … 300 V DC
Overvoltage resistance
2.3 x Uin rated, 1.3 ms
2.3 x Uin rated, 1.3 ms
Mains buffering at Iout rated
> 40 ms at Uin = 187 V
> 40 ms at Uin = 187 V
Rated line frequency, rated line-frequency range
50/60 Hz; 47 ... 63 Hz
50/60 Hz; 47 ... 63 Hz
Rated current value Iin rated
0.53-0.3 A
1.13-0.61 A
Switch-on current limitation (+25 °C)
< 26 A
< 54 A
I2 t
< 0.8 A2s
< 3 A2s
2
Built-in incoming fuse
Internal
Internal
Recommended miniature circuit breaker (IEC 898)
in the mains power input
16 A or higher, Characteristic B or 10 A or
higher, Characteristic C
16 A or higher, Characteristic B or 10 A or
higher, Characteristic C
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage value Uout rated
12 V DC
12 V DC
Total tolerance, static
• Static mains compensation
• Static load smoothing
±3 %
Approx. 0.2 %
Approx. 1.5 %
±3 %
Approx. 0.1 %
Approx. 1.5 %
Residual ripple
< 200 mVpp (typ. 10 mVpp)
< 200 mVpp (typ. 10 mVpp)
Spikes (bandwidth approx. 20 MHz)
< 300 mVpp (typ. 20 mVpp)
< 300 mVpp (typ. 70 mVpp)
Adjustment range
10.5 ... 16.1 V
10.5 ... 16.1 V
Status indicator
Green LED for 12 V OK
Green LED for 12 V OK
On/Off behavior
No overshoot of Uout (soft start)
No overshoot of Uout (soft start)
Startup delay /
voltage rise
< 0.5 s/typ. 15 ms
< 0.5 s/typ. 15 ms
Rated current value Iout rated
1.9 A
4.5 A
Current range up to +55 °C
• Derating
0 ... 1.9 A
0 ... 1.3 A (up to +70 °C)
0 ... 4.5 A
0 ... 3.1 A (up to +70 °C)
Parallel switching for enhanced performance
Yes, 2 units
Yes, 2 units
Efficiency at Uout rated, Iout rated
Typ. 80 %
Typ. 85 %
Heat loss at Uout rated, Iout rated
Typ. 5 W
Typ. 10 W
Dyn. mains compensation
(Uin rated ±15 %)
< 0.2 % Uout
< 0.2 % Uout
Dynamic load smoothing (Iout: 10/90/10%)
Typ. ±3 % Uout
Typ. ±4 % Uout
Load step settling time
• 10 to 90 %
• 90 to 10 %
Approx. 1 ms
Approx. 1 ms
Approx. 1 ms
Approx. 1 ms
Efficiency
Closed-loop control
Protection and monitoring
Current limitation
Typ. 2.8 A
Typ. 5.8 A
Short-circuit protection
Constant current characteristic
Constant current characteristic
Sustained short-circuit current rms value
<4A
<8A
Primary/secondary isolation
Yes, safety extra low output voltage Uout
according to EN 60950 and EN 50178
Yes, safety extra low output voltage Uout
according to EN 60950 and EN 50178
Safety
Protection class
Class II (without protective conductor)
Class II (without protective conductor)
German Technical Inspectorate approval
Yes; CB scheme
Yes; CB scheme
CE mark
Yes
Yes
Siemens ST 70 · 2011
2/25
© Siemens AG 2011
LOGO! logic module
LOGO!Power
LOGO!Power
■ Technical specifications LOGO!Power 12 V (continued)
2
Power supply, type
Order No.
12 V/1.9 A
6EP1 321-1SH03
12 V/4.5 A
6EP1 322-1SH03
UL/cUL (CSA) approval
cULus-listed (UL 508, CSA C22.2 No. 107.1);
cURus-recognized (UL 60950, CSA C22.2
No. 60950)
cULus-listed (UL 508, CSA C22.2 No. 107.1);
cURus-recognized (UL 60950, CSA C22.2
No. 60950)
Explosion protection
ATEX (available soon)
ATEX (available soon)
FM approval
Class I Div. 2, Group A, B, C, D T4
Class I Div. 2, Group A, B, C, D T4
Marine approval
GL, ABS (available soon)
GL, ABS (available soon)
Degree of protection (EN 60529)
IP20
IP20
EMC
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
Not applicable
Not applicable
Noise immunity
EN 61000-6-2
EN 61000-6-2
Operating data
Ambient temperature range
-20 ... +70 °C with natural convection
-20 ... +70 °C with natural convection
Transport and storage temperature range
-40 ... +85 °C
-40 ... +85 °C
Humidity class
Climate class 3K3 according to EN 60721,
no condensation
Climate class 3K3 according to EN 60721,
no condensation
1 screw terminal each for 0.5 mm ... 2.5 mm2
single-core/finely stranded
2 screw terminals each for 0.5 ... 2.5 mm2
1 screw terminal each for 0.5 mm ... 2.5 mm2
single-core/finely stranded
2 screw terminals each for 0.5 ... 2.5 mm2
Mechanics
Supply-input connections L1, N
Connections
• Output +
• Output Dimensions (W x H x D) in mm
54 x 90 x 55
72 x 90 x 55
Weight, approx.
Approx. 0.17 kg
Approx. 0.25 kg
Installation
Snaps onto standard mounting rail EN 60715
35x7.5/15
Snaps onto standard mounting rail EN 60715
35x7.5/15
Power supply, type
Order No.
15 V/1.9 A
6EP1 351-1SH03
15 V/4 A
6EP1 352-1SH03
Input
1-phase AC or DC
1-phase AC or DC
Rated voltage value Uin rated
100-240 V AC
Wide-range input
100-240 V AC
Wide-range input
Voltage range
85 ... 264 V AC
110 … 300 V DC
85 ... 264 V AC
110 … 300 V DC
Overvoltage resistance
2.3 x Uin rated, 1.3 ms
2.3 x Uin rated, 1.3 ms
Mains buffering at Iout rated
> 40 ms at Uin = 187 V
> 40 ms at Uin = 187 V
■ Technical specifications LOGO!Power 15 V
Rated line frequency, rated line-frequency range
50/60 Hz; 47 ... 63 Hz
50/60 Hz; 47 ... 63 Hz
Rated current value Iin rated
0.63-0.33 A
1.24-0.68 A
Switch-on current limit (+25 °C)
< 26 A
< 54 A
I2 t
< 0.8 A2s
< 3 A2s
Built-in incoming fuse
Internal
Internal
Recommended miniature circuit breaker (IEC 898)
in the mains power input
16 A or higher, Characteristic B or 10 A or
higher, Characteristic C
16 A or higher, Characteristic B or 10 A or
higher, Characteristic C
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage Uout rated
15 V DC
15 V DC
Total tolerance, static
• Static mains compensation
• Static load smoothing
±3 %
Approx. 0.1 %
Approx. 1.5 %
±3 %
Approx. 0.1 %
Approx. 1.5 %
Residual ripple
< 200 mVpp (typ. 10 mVpp)
< 200 mVpp (typ. 10 mVpp)
2/26
Siemens ST 70 · 2011
© Siemens AG 2011
LOGO! logic module
LOGO!Power
LOGO!Power
■ Technical specifications LOGO!Power 15 V (continued)
Power supply, type
Order No.
15 V/1.9 A
6EP1 351-1SH03
15 V/4 A
6EP1 352-1SH03
Spikes (bandwidth approx. 20 MHz)
< 300 mVpp (typ. 30 mVpp)
< 300 mVpp (typ. 70 mVpp)
Adjustment range
10.5 ... 16.1 V
10.5 ... 16.1 V
Status indicator
Green LED for 15 V OK
Green LED for 15 V OK
On/Off behavior
No overshoot of Uout (soft start)
No overshoot of Uout (soft start)
Startup delay /
voltage rise
< 0.5 s/typ. 15 ms
< 0.5 s/typ. 15 ms
Rated current value Iin rated
1.9 A
4A
Current range up to +55 °C
• Derating
0 ... 1.9 A
0 ... 1.3 A (up to +70 °C)
0 ... 4 A
0 ... 2.8 A (up to +70 °C)
Parallel switching for enhanced performance
Yes, 2 units
Yes, 2 units
Efficiency at Uout rated, Iout rated
Approx. 81 %
Approx. 85 %
Heat loss at Uout rated, Iout rated
Approx. 7 W
Approx. 11 W
Dyn. mains compensation
(Uin rated ±15%)
< 0.2 % Uout
< 0,2 % Uout
Dynamic load smoothing
(Iout: 10/90/10%)
Typ. ±2.8 % Uout
Typ. ±3 % Uout
Typ. 1 ms
Typ. 1 ms
Typ. 1 ms
Typ. 1 ms
2
Efficiency
Closed-loop control
Load step settling time
• 10 to 90 %
• 90 to 10 %
Protection and monitoring
Current limitation
Typ. 2.7 A
Typ. 5.7 A
Short-circuit protection
Constant current characteristic
Constant current characteristic
Sustained short-circuit current rms value
<4A
<8A
Primary/secondary isolation
Yes, safety extra low output voltage Uout
according to EN 60950 and EN 50178
Yes, safety extra low output voltage Uout
according to EN 60950 and EN 50178
Safety
Protection class
Class II (without protective conductor)
Class II (without protective conductor)
Safety test
Yes; CB scheme
Yes; CB scheme
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-listed (UL 508, CSA C22.2 No. 107.1);
cURus-recognized (UL 60950, CSA C22.2
No. 60950)
cULus-listed (UL 508, CSA C22.2 No. 107.1);
cURus-recognized (UL 60950, CSA C22.2
No. 60950)
Explosion protection
ATEX (available soon)
ATEX (available soon)
FM approval
Class I Div. 2, Group A, B, C, D T4
Class I Div. 2, Group A, B, C, D T4
Marine approval
GL (available soon)
GL (available soon)
Degree of protection (EN 60529)
IP20
IP20
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
Not applicable
Not applicable
Noise immunity
EN 61000-6-2
EN 61000-6-2
EMC
Operating data
Ambient temperature range
-20 ... +70 °C with natural convection
-20 ... +70 °C with natural convection
Transport and storage temperature range
-40 ... +85 °C
-40 ... +85 °C
Humidity class
Climate class 3K3 according to EN 60721,
no condensation
Climate class 3K3 according to EN 60721,
no condensation
Siemens ST 70 · 2011
2/27
© Siemens AG 2011
LOGO! logic module
LOGO!Power
LOGO!Power
■ Technical specifications LOGO!Power 15 V (continued)
2
Power supply, type
Order No.
15 V/1.9 A
6EP1 351-1SH03
15 V/4 A
6EP1 352-1SH03
1 screw terminal each for 0.5 mm ... 2.5 mm2
single-core/finely stranded
2 screw terminals each for 0.5 ... 2.5 mm2
1 screw terminal each for 0.5 mm ... 2.5 mm2
single-core/finely stranded
2 screw terminals each for 0.5 ... 2.5 mm2
Mechanics
Supply-input connections L1, N
Connections
• Output +
• Output Dimensions (W x H x D) in mm
54 x 90 x 55
72 x 90 x 55
Weight, approx.
Approx. 0.17 kg
Approx. 0.25 kg
Installation
Snaps onto standard mounting rail EN 60715
35x7.5/15
Snaps onto standard mounting rail EN 60715
35x7.5/15
■ Technical specifications LOGO!Power 24 V/1.3 A
Power supply, type
Order No.
24 V/1.3 A
6EP1 331-1SH03
Power supply, type
Order No.
24 V/1.3 A
6EP1 331-1SH03
Input
1-phase AC or DC
Closed-loop control
Rated voltage Uin rated
100-240 V AC
Wide-range input
Dyn. mains compensation
(Uin rated ±15%)
< 0,2 % Uout
Voltage range
85 ... 264 V AC
110 … 300 V DC
Dynamic load smoothing
(Iout: 50/100/50 %)
Typ. ±1% Uout
(Iout: 10/90/10 %)
Overvoltage strength
2.3 x Uin rated, 1.3 ms
Mains buffering at Iout rated
> 40 ms at Uin = 187 V
Load step settling time
• 50 to 100%
• 100 to 50%
Typ. 1 ms (10 to 90%)
Typ. 1 ms (90 to 10%)
Rated line frequency, rated line-frequency
range
50/60 Hz; 47 ... 63 Hz
Rated current Iin rated
0.7-0.35 A
Switch-on current limitation (+25 °C)
I2 t
Built-in incoming fuse
Internal
Recommended miniature circuit breaker
(IEC 898) in the mains power input
16 A or higher, Characteristic B or 10 A or higher,
Characteristic C
Protection and monitoring
Output overvoltage protection
Yes, according to
EN 60950
< 30 A
Current limitation
Typ. 1.7 A
< 0.8 A2s
Short-circuit protection
Constant current characteristic
Sustained short-circuit current rms value
<4A
Overload/short-circuit indicator
-
Output
Controlled, isolated DC
voltage
Rated voltage Uout rated
24 V DC
Total tolerance
• Static mains compensation
• Static load smoothing
±3 %
Approx. 0.1%
Approx. 1.5%
Residual ripple
< 200 mVpp (typ. 10 mVpp)
Spikes (bandwidth approx. 20 MHz)
Safety
Primary/secondary isolation
Yes, safety extra low output
voltage Uout according to
EN 60950-1 and EN 50178
Safety class
Class II (without protective
conductor)
Leakage current
-
Safety test
Yes; CB scheme
< 300 mVpp (typ. 20 mVpp)
CE marking
Yes
Adjustment range
22.2 ... 26.4 V
UL/cUL (CSA) approval
Status indicator
24 V OK = green LED
On/Off behavior
No overshoot of Uout (soft
start)
cULus-listed (UL 508, CSA
C22.2 No. 107.1), cURusrecognized (UL 60950,
CSA C22.2 No. 60950)
Startup delay /
voltage rise
< 0.5 s/typ. 15 ms
Protection against explosion
ATEX EX II 3G Ex nA IIC T3
FM approval
Rated current Iout rated
1.3 A
Class I Div. 2, Group A, B,
C, D T4
Marine approval
GL, ABS
0 ... 1.3 A (up to +55°C)
0 ... 0.9 A (up to +70°C)
Degree of protection (EN 60529)
IP20
Yes, 2 units
Emitted interference
EN 55022 Class B
Supply harmonics limitation
Not applicable
Noise immunity
EN 61000-6-2
Current range
• Current range up to +60 °C
• Derating
Parallel switching for enhanced performance
Efficiency
Efficiency at Uout rated, Iout rated
Approx. 83%
Power loss at Uout rated, Iout rated
Approx. 6.3 W
2/28
Siemens ST 70 · 2011
EMC
© Siemens AG 2011
LOGO! logic module
LOGO!Power
LOGO!Power
■ Technical specifications LOGO!Power 24 V/1.3 A (continued)
Power supply, type
Order No.
24 V/1.3 A
6EP1 331-1SH03
Operating data
Ambient temperature range
-20 ... +70 °C with natural
convection
Transport and storage temperature range
-40 ... +85 °C
Humidity class
Climate class 3K3
according to EN 60721,
no condensation
Power supply, type
Order No.
24 V/1.3 A
6EP1 331-1SH03
Dimensions (W x H x D) in mm
54 x 90 x 55
Weight, approx.
Approx. 0.17 kg
Mounting
Can be snapped onto
standard mounting rail
EN 60715 35x7.5/15
Accessories
-
24 V/2.5 A
6EP1 332-1SH43
2
Mechanics
Connections
• Supply input L, N, PE
DC input: L+1, M1, PE
• Output +
• Output -
Solid/finely-stranded per
screw-type terminal (L, N)
for 0.5 mm ... 2.5 mm2
2 screw-type terminals for
0.5 ... 2.5 mm2
2 screw-type terminals for
0.5 ... 2.5 mm2
■ Technical specifications LOGO!Power 24 V/2.5 A
Power supply, type
Order No
24 V/2.5 A
6EP1 332-1SH43
Power supply, type
Order No
Input
1-phase AC or DC
Efficiency
Rated voltage Uin rated
100-240 V AC
Wide-range input
Efficiency at Uout rated, Iout rated
Approx. 88%
Power loss at Uout rated, Iout rated
Approx. 8 W
Voltage range
85 ... 264 V AC
110 … 300 V DC
Closed-loop control
Overvoltage strength
2.3 x Uin rated, 1.3 ms
Mains buffering at Iout rated
> 40 ms at Uin = 187 V
Rated line frequency, rated line-frequency
range
50/60 Hz; 47 ... 63 Hz
Rated current Iin rated
1.22-0.66 A
Switch-on current limitation (+25 °C)
< 46 A
I2 t
< 3 A 2s
Built-in incoming fuse
Internal
Recommended miniature circuit breaker
(IEC 898) in the mains power input
16 A or higher, Characteristic B or 10 A or higher,
Characteristic C
Output
Dyn. mains compensation
(Uin rated ±15%)
< 0,2 % Uout
Dynamic load smoothing
(Iout: 50/100/50 %)
Typ. ±2% Uout
(Iout: 10/90/10 %)
Load step settling time
• 50 to 100%
• 100 to 50%
Typ. 1 ms (10 to 90%)
Typ. 1 ms (90 to 10%)
Protection and monitoring
Output overvoltage protection
Yes, according to EN
60950
Current limitation
Typ. 3.3 A
Short-circuit protection
Controlled, isolated DC
voltage
Constant current characteristic
Sustained short-circuit current rms value
Approx. 3.5 A
Rated voltage Uout rated
24 V DC
Safety
Total tolerance
• Static mains compensation
• Static load smoothing
±3 %
Approx. 0.1%
Approx. 1.5%
Primary/secondary isolation
Yes, safety extra low output
voltage Uout according to
EN 60950-1 and EN 50178
Residual ripple
< 200 mVpp (typ. 10 mVpp)
Safety class
Class II (without protective
conductor)
Spikes (bandwidth approx. 20 MHz)
< 300 mVpp (typ. 50 mVpp)
Leakage current
-
Adjustment range
22.2 ... 26.4 V
Safety test
Yes; CB scheme
Status indicator
24 V OK = green LED
CE marking
Yes
On/Off behavior
No overshoot of Uout
(soft start)
UL/cUL (CSA) approval
Startup delay /
voltage rise
< 0.5 s/typ. 10 ms
cULus-listed (UL 508, CSA
C22.2 No. 107.1), cURusrecognized (UL 60950,
CSA C22.2 No. 60950)
Rated current Iout rated
2.5 A
Protection against explosion
ATEX EX II 3G Ex nA IIC T3
FM approval
0 ... 2.5 A (up to +55°C)
0 ... 1.75 A (up to +70°C)
Class I Div. 2, Group A, B,
C, D T4
Marine approval
GL, ABS
Yes, 2 units
Degree of protection (EN 60529)
IP20
Current range
• Current range up to +60 °C
• Derating
Parallel switching for enhanced
performance
Siemens ST 70 · 2011
2/29
© Siemens AG 2011
LOGO! logic module
LOGO!Power
LOGO!Power
■ Technical specifications LOGO!Power 24 V/2.5 A (continued)
2
Power supply, type
Order No
24 V/2.5 A
6EP1 332-1SH43
EMC
Power supply, type
Order No
24 V/2.5 A
6EP1 332-1SH43
Mechanics
Emitted interference
EN 55022 Class B
Supply harmonics limitation
Not applicable
Noise immunity
EN 61000-6-2
Connections
• Supply input L, N, PE
DC input: L+1, M1, PE
• Output +
Operating data
Solid/finely-stranded per
screw-type terminal (L, N)
for 0.5 mm ... 2.5 mm2
2 screw-type terminals for
0.5 ... 2.5 mm2
2 screw-type terminals for
0.5 ... 2.5 mm2
Ambient temperature range
-20 ... +55 °C with natural
convection
• Output -
Transport and storage temperature range
-40 ... +70 °C
Dimensions (W x H x D) in mm
72 x 90 x 55
Humidity class
Climate class 3K3
according to EN 60721,
no condensation
Weight, approx.
Approx. 0.25 kg
Mounting
Can be snapped onto
standard mounting rail
EN 60715 35x7.5/15
Accessories
-
■ Technical specifications LOGO!Power 24 V/4 A
Power supply, type
Order No.
24 V/4 A
6EP1 332-1SH52
Power supply, type
Order No.
24 V/4 A
6EP1 332-1SH52
Input
1-phase AC or DC
Rated current Iout rated
4A
Rated voltage Uin rated
100-240 V AC
Wide-range input
Voltage range
85 ... 264 V AC
110 … 300 V DC
Current range
• Current range up to +60 °C
• Derating
0 ... 4 A (up to +55°C)
0 ... 2.8 A (up to +70°C)
Overvoltage strength
2.3 x Uin rated, 1.3 ms
Mains buffering at Iout rated
> 40 ms at Uin = 187 V
Rated line frequency, rated line-frequency
range
50/60 Hz; 47 ... 63 Hz
Parallel switching for enhanced performance
Yes, 2 units
Efficiency
Efficiency at Uout rated, Iout rated
Approx. 89%
Power loss at Uout rated, Iout rated
Approx. 12 W
Rated current Iin rated
1.95 to 0.97 A
Closed-loop control
Switch-on current limitation (+25 °C)
< 30 A
Dyn. mains compensation
(Uin rated ±15%)
< 0,2 % Uout
I
2t
< 2.5
A 2s
Built-in incoming fuse
Internal
Dynamic load smoothing
(Iout: 50/100/50 %)
Typ. ±1.5% Uout
(Iout: 10/90/10 %)
Recommended miniature circuit breaker
(IEC 898) in the mains power input
16 A or higher, Characteristic B or 10 A or higher,
Characteristic C
Load step settling time
• 50 to 100%
• 100 to 50%
Typ. 1 ms (10 to 90%)
Typ. 1 ms (90 to 10%)
Output
Controlled, isolated DC
voltage
Protection and monitoring
Rated voltage Uout rated
24 V DC
Output overvoltage protection
Yes, according to
EN 60950
Total tolerance
• Static mains compensation
• Static load smoothing
±3 %
Approx. 0.1%
Approx. 1.5%
Current limitation
Typ. 5.2 A
Short-circuit protection
Constant current characteristic
Sustained short-circuit current rms value
< 10 A
Overload/short-circuit indicator
-
Residual ripple
< 200 mVpp (typ. 30 mVpp)
Spikes (bandwidth approx. 20 MHz)
< 300 mVpp (typ. 60 mVpp)
Adjustment range
22.2 ... 26.4 V
Status indicator
24 V OK = green LED
On/Off behavior
No overshoot of Uout
(soft start)
Startup delay /
voltage rise
< 0.5 s/typ. 15 ms
2/30
Siemens ST 70 · 2011
Safety
Primary/secondary isolation
Yes, safety extra low output
voltage Uout according to
EN 60950-1 and EN 50178
Safety class
Class II (without protective
conductor)
© Siemens AG 2011
LOGO! logic module
LOGO!Power
LOGO!Power
■ Technical specifications LOGO!Power 24 V/4 A (continued)
Power supply, type
Order No.
24 V/4 A
6EP1 332-1SH52
Power supply, type
Order No.
Leakage current
-
Operating data
Safety test
Yes; CB scheme
Ambient temperature range
CE marking
Yes
-20 ... +70 °C with natural
convection
UL/cUL (CSA) approval
cULus-listed (UL 508,
CSA C22.2 No. 107.1),
cURus-recognized
(UL 60950, CSA C22.2
No. 60950)
Transport and storage temperature range
-40 ... +85 °C
Humidity class
Climate class 3K3
according to EN 60721,
no condensation
Protection against explosion
ATEX EX II 3G Ex nA IIC T3
FM approval
Class I Div. 2, Group A, B,
C, D T4
Marine approval
GL, ABS
Degree of protection (EN 60529)
IP20
Emitted interference
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
Noise immunity
EN 61000-6-2
2
Mechanics
Connections
• Supply input L, N, PE
DC input: L+1, M1, PE
• Output +
• Output -
EMC
24 V/4 A
6EP1 332-1SH52
Solid/finely-stranded per
screw-type terminal (L, N)
for 0.5 mm ... 2.5 mm2
2 screw terminals each for
0.5 ... 2.5 mm2
2 screw terminals each for
0.5 ... 2.5 mm2
Dimensions (W x H x D) in mm
90 x 90 x 55
Weight, approx.
Approx. 0.34 kg
Mounting
Can be snapped onto
standard mounting rail
EN 60715 35x7.5/15
Accessories
-
Siemens ST 70 · 2011
2/31
© Siemens AG 2011
LOGO! logic module
LOGO!Power
LOGO!Power
■ Ordering data
2
Order No.
Order No.
LOGO!Power 5 V
LOGO!Power 24 V/1.3 A
Stabilized power supply;
Output: 5 V DC/3 A
• Input: 110 … 300 V AC;
extended operating temperature
range: up to +70°C
Stabilized power supply;
Output: 24 V DC/1.3 A
• Input: 110 … 300 V AC;
extended operating temperature
range: up to +70°C
Stabilized power supply;
Output: 5 V DC/6.3 A
• Input: 110 … 300 V AC;
extended operating temperature
range: up to +70°C
6EP1 311-1SH03
LOGO!Power 24 V/2.5 A
6EP1 311-1SH13
LOGO!Power 12 V
6EP1 321-1SH03
Stabilized power supply;
Output: 12 V DC/4.5 A
• Input: 110 … 300 V AC;
extended operating temperature
range: up to +70°C
6EP1 322-1SH03
LOGO!Power 15 V
Stabilized power supply;
Output: 15 V DC/1.9 A
• Input: 110 … 300 V AC;
extended operating temperature
range: up to +70°C
6EP1 351-1SH03
Stabilized power supply;
Output: 15 V DC/4 A
• Input: 110 … 300 V AC;
extended operating temperature
range: up to +70°C
6EP1 352-1SH03
■ More information
In addition to various power supply product lines, the perfectly
coordinated complete SITOP range offers a unique range of
add-on modules with which the 24 V power supply can be
additionally protected against interference on the primary and
secondary side – right up to all-round protection:
• Redundancy module for setting up a redundant power supply
• Uninterruptible 24 V power supplies with batteries or maintenance-free capacitors for continued operation in the event of
a power failure
• Selectivity modules for electronic protection of 24 V branches
from overload and short-circuit
You can find more information in Catalog KT 10.1 and in the
Internet at
www.siemens.com/sitop
Siemens ST 70 · 2011
Stabilized power supply;
Output: 24 V DC/2.5 A
• Input: 110 … 300 V AC;
extended operating temperature
range: up to +70°C
6EP1 332-1SH43
LOGO!Power 24 V/4 A
Stabilized power supply;
Output: 12 V DC/1.9 A
• Input: 110 … 300 V AC;
extended operating temperature
range: up to +70°C
2/32
6EP1 331-1SH03
Stabilized power supply;
Output: 24 V DC/4 A
• Input: 110 … 300 V AC;
extended operating temperature
range: up to +70°C
6EP1 332-1SH52
© Siemens AG 2011
LOGO! logic module
LOGO!Power
SIPLUS LOGO!Power
■ Overview
■ Technical specifications
Note:
Power supply, type
24 V/1.3 A
SIPLUS extreme products are based on Siemens Industry
standard products. The contents listed here were taken from the
respective standard products. SIPLUS extreme-specific information was added.
Order number
6EP1 331-1SH02
Input
1-phase AC
Rated voltage Uin rated
100 ... 240 V AC
Wide-range input
Voltage range
85 ... 264 V AC
Overvoltage strength
2.3 x Uin rated, 1.3 ms
SIPLUS LOGO!Power 1.3 A
Order number
6AG1 931-1SH02-2AA0
Mains buffering at Iout rated
> 40 ms at Uin = 187 V
Order No. based on
6EP1 331-1SH02
50/60 Hz; 47 ... 63 Hz
Ambient temperature range
-25 °C to +70 °C
Rated line frequency, rated line
frequency range
Conformal coating
Coating of the printed circuit
boards and the electronic components
Rated current Iin rated
0.7-0.35 A
Technical data
The technical data of the
standard product applies except
for the ambient conditions.
Ambient conditions
Relative humidity
5 ... 100 %
Condensation permissible
Biologically active substances
Conformity with EN 60721-3-3,
Class 3B2 mold and fungal
spores (except fauna)
Chemically active substances
Mechanically active substances
Air pressure (depending on the
highest positive temperature range
specified)
1)
2)
Conformity with EN 60721-3-3,
Class 3C4 incl. salt mist and ISA–
S71.04 severity level G1; G2; G3;
GX 1) 2)
Conformity with EN 60721-3-3,
Class 3S4 including conductive
sand, dust 2)
1080 ... 795 hPa
(-1000 ... +2000 m)
see ambient temperature range
795 ... 658 hPa
(+2000 ... +3500 m)
derating 10 K
658 ... 540 hPa
(+3500 ... +5000 m)
derating 20 K
ISA-S71.04 severity level GX: Long-term load: SO2 < 4.8 ppm;
H2S < 9.9 ppm; Cl < 0.2 ppm; HCl < 0.66 ppm; HF < 0.12 ppm;
NH < 49 ppm; O3 < 0.1 ppm; NOX < 5.2 ppm
Threshold / limit value (max. 30 min/d): SO2 < 17.8 ppm;
H2S < 49.7 ppm; Cl < 1.0 ppm; HCl < 3.3 ppm; HF < 2.4 ppm;
NH < 247 ppm; O3 < 1.0 ppm; NOX < 10.4 ppm
The supplied plug covers must remain in place over the unused
interface when operated in atmospheres containing corrosive gases!
2
Switch-on current limitation (+25 °C) < 35 A
I2t
< 0.8 A2s
Built-in incoming fuse
Internal
Recommended miniature circuit
breaker (IEC 898) in the mains
power input
16 A or higher, Characteristic B or
10 A or higher, Characteristic C
Output
Controlled, isolated DC voltage
Rated voltage Uout rated
24 V DC
Total tolerance
• Static mains compensation
• Static load smoothing
±3 %
Approx. 0.1%
Approx. 1.5%
Residual ripple
< 200 mVpp (typ. 10 mVpp)
Spikes (bandwidth approx. 20 MHz) < 300 mVpp (typ. 20 mVpp)
Setting range
22.2 ... 26.4 V
Status indicator
24 V OK = green LED
On/Off behavior
No overshoot of Uout (soft start)
Startup delay /
voltage rise
< 0.5 s/typ. 15 ms
Rated current Iout rated
1.3 A
Current range
• Current range up to +60 °C
• Derating
0 ... 1.3 A (up to 55 °C)
-
Parallel switching for enhanced
performance
Yes, 2 units
Efficiency
Efficiency at Uout rated, Iout rated
Approx. 82%
Heat loss at Uout rated, Iout rated
Approx. 7 W
Closed-loop control
The technical documentation on SIPLUS can be found here:
Dyn. mains compensation
(Uin rated ±15%)
< 0,2 % Uout
www.siemens.com/siplus-extreme
Dynamic load smoothing
(Iout: 50/100/50 %)
Typ. ±1.5 % Uout
(Iout: 10/90/10 %)
Load step settling time
• 50 to 100%
• 100 to 50%
Typ. 20 ms (10 to 90%)
Typ. 20 ms (90 to 10%)
Protection and monitoring
Output overvoltage protection
Yes, according to EN 60950
Current limitation
Typ. 2 A
Short-circuit protection
Constant current characteristic
Sustained short-circuit current rms
value
<4A
Overload/short-circuit indicator
-
Siemens ST 70 · 2011
2/33
© Siemens AG 2011
LOGO! logic module
LOGO!Power
SIPLUS LOGO!Power
■ Technical specifications (continued)
Power supply, type
2
24 V/1.3 A
Safety
Primary/secondary isolation
■ Ordering data
SIPLUS LOGO!Power 24 V 1.3 A L
Order No.
6AG1 931-1SH02-2AA0
(extended temperature range and
medial exposure)
Yes, safety extra low output
voltage Uout according to
EN 60950 and EN 50178
Input 100 ... 240 V AC
Output 24 V DC, 1.3 A
Protection class
Class II (without protective
conductor)
L: Subject to export regulations AL: 9I999 and ECCN: N
Leakage current
-
Safety test
Yes; CB scheme
CE marking
Yes
UL/cUL (CSA) approval
cULus-listed (UL 508, CSA C22.2
No. 107.1), File E197259; cURusrecognized (UL 60950, CSA
C22.2 No. 60950), File E151273
Explosion protection
ATEX EX II 3G Ex nA IIC T3
FM approval
Class I Div. 2, Group A, B, C, D T4
Marine approval
GL, ABS
Degree of protection (EN 60529)
IP20
EMC
Emitted interference
EN 55022 Class B
Supply harmonics limitation
Not applicable
Noise immunity
EN 61000-6-2
Operating data
Range of ambient temperature
-20 ... +55 °C with natural
convection
Transport and storage temperature
range
-40 ... +70 °C
Humidity class
Climate class 3K3 according to
EN 60721, no condensation
Mechanics
Connections
• Supply input L, N, PE
DC input: L+1, M1, PE
• Output +
• Output -
One solid/finely-stranded screwtype terminal each (L, N) for
0.5 mm ... 2.5 mm2
2 screw-type terminals for
0.5 ... 2.5 mm2
2 screw-type terminals for
0.5 ... 2.5 mm2
Dimensions (W x H x D) in mm
54 x 90 x 55
Weight, approx.
Approx. 0.17 kg
Installation
Can be snapped onto standard
mounting rail EN 60715 35x7.5/15
Accessories
-
2/34
Siemens ST 70 · 2011
© Siemens AG 2011
LOGO! logic module
LOGO!Contact
LOGO!Contact
■ Overview
■ Technical specifications
Dimensions and
weight
Weight
• Weight, approx.
6ED1 057-4CA000AA0
6ED1 057-4EA000AA0
160 g
160 g
■ Ordering data
Order No.
LOGO!Contact
Switching module for direct
switching of resistive loads up to
20 A and motors up to 4 kW
Switching voltage 24 V
6ED1 057-4CA00-0AA0
Switching voltage 230 V
6ED1 057-4EA00-0AA0
• Switching module for the direct switching of resistive loads
and motors
Siemens ST 70 · 2011
2/35
2
© Siemens AG 2011
LOGO! logic module
LOGO! software
LOGO! software
■ Overview
■ Ordering data
LOGO!Soft Comfort V6.0
2
Order No.
J
6ED1 058-0BA02-0YA0
J
6ED1 058-0CA02-0YE0
For programming on the PC in
LAD/FBD;
executes under Windows 98 SE
and higher, Linux, MAC OSX;
on CD-ROM
LOGO!Soft Comfort V6.0
upgrade
Upgrade from V1.0 to V6.0
J: Subject to export regulations AL: N and ECCN: EAR99S
• The user-friendly software for creating control programs on a
PC
• Creation of control programs in Function Block Diagram (FBD)
or Ladder Diagram (LAD)
• Plus testing, simulation, online testing and archiving of control
programs
• Professional documentation via numerous comment and print
functions
The connection between LOGO! and the PC is made using the
LOGO! PC cable (serial interface) or the LOGO! USB PC cable
(USB interface).
Minimum system requirements
Windows 98 SE, NT 4.0, ME, 2000, XP or Vista (not 64 bit)
• PC Pentium.
• 90 MB free disk capacity.
• 64 MB RAM.
• SVGA graphics card with minimum resolution 800x600
(256 colors).
Mac OS X
• PowerMac G3, G4, G4 Cube, IMac, PowerBook G3, G4 or
iBook.
Linux (tested with Caldera OpenLinux 2.4)
• Runs on all Linux distributions on which the Java 2 SDK
Version 1.3.1 runs.
• Please refer to your relevant Linux distribution for the
necessary hardware requirements.
■
2/36
Siemens ST 70 · 2011
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement