Daikin | DCM601A72 | Sales Bulletin #CT016a

Sales Bulletin #CT016a
Date:
June 5, 2014
To:
Daikin Sales, Service, and Distribution
Subject:
The intelligent Touch Manager (iTM) Version 2.0
Daikin is pleased to announce the release of its new software update for the intelligent Touch
Manager (DCM601A71) with version 2.0.
The new iTM software version 2.0 will be released in late August 2013.
intelligent Touch Manager (iTM)
(DCM601A71)
iTM Plus Adaptor
(DCM601A72)
The iTM has a 10.4” LCD touch screen, USB port, 100Mbps Ethernet port, and is capable of
managing up to 512 indoor unit groups which can cover your project requirements. It is more
powerful than the hardware capabilities of the intelligent Touch Controller (iTC) and the iTM
comes with web access as a standard feature.
Monitor and control of campus environments made
simple with a facility network connected PC
Operation, navigation, and commissioning of the iTM are very intuitive and can be done on or
off site by touch screen, web access, and/or preset tool. Up to 60 floor layout views can be
Published by Daikin Product Marketing Department
Page 2 of 11
created to monitor and control each management point (indoor unit, digital input/output, and
analog input/output groups).
Icon View
List View
Layout View
Easy navigation through menu functions with the new tab/icon display feature
Automatic Ctrl
System Settings
Operation Mgmt
The iTM v2.0 will have enhanced features such as: Auto-changeover (Fixed, Individual,
Averaging, and Vote), Independent Cool and Heat Setpoints, Independent Setback Setpoints,
Scheduling with Optimum Start, and Room Temperature display with 0.1oF resolution.
The iTM is the successor of the intelligent Manager III, and now it will be the successor of the
intelligent Touch Controller (iTC).
The iTC will continue to be sold without the Web/Email option as a lower cost alternative
Centralized Controller and for projects requiring the HTTP option.
The iTM v2.0 can be used as a backup controller to the BMS integration prior to and after the
BMS system fully (or partially) monitors and/or controls the VRV system.
Published by Daikin Product Marketing Department
Page 3 of 11
Advanced Multi-zone Controller Comparison Table
Functions
Basic Items
Hardware
New Feature
Indoor Unit Capacity
DIII-Net Adapter
Total Mangement Points
Dimensions (inches)
Display Size (inches)
Screen Saver
Installation
External Memory
Di / Pi Inputs
Ethernet
Menu Navigation
Area / Zone / Indoor Unit
12
Settings
13 Room Temp Resolution
1
2
3
4
5
6
7
8
9
10
11
14
15
16
17
18
19
20
21
22
Setpoint Resolution
Setpoint
Setpoint Tracking
Setpoint Range Limitation
Setback
Recovery Temperature
Remote Control Pemit/Prohibit
Schedule
Events per day
23
Optimal Start
24
Timed Override
25 Layout View
26
Floor Plan Sections
27
28
29 Auto-changeover
Options
iTC V6.04
Up to 64 – 512 Groups
up to 7 (64 indoor unit groups each)
650
11.42 x 9.57 x 1.97
10.4
3 Types
Wall / Flush mount (0.98 in.)
USB 2.0 (up to 32GB)
1 Di and 3 Di / Pi
100 Mbps
Tab / Icon
Up to 64 – 128 Groups
1 (64 indoor unit groups)
128
9.063 x 5.781 x 4.22
5.7
N/A
Wall / Flush mount (1.97 in.)
PCMCIA
1 Di and 3 Pi
10 Mbps
Menu List
Area / Indoor Unit
Zone / Indoor Unit
o
o
0.1 F / 0.1 C
o
o
o
o
o
1 F / 0.1 C
o
1 F / 0.1 C
Single / Dual
1 F / 0.1 C
Single
o
 (Setpoint Tracking Mode for 0-7 F Differential)

Absolute
Relative
o
o
0 - 10 F
0 - 10 F

7, 5+2, 5+1+1, 1
7
20
Available as pre-cool/heat
doesn’t work with Setback

Timer Extension (adj. 30 - 180 minutes)

60
Fixed
Individual
Averaging
(Weighted Demand)
Vote
(Weighted Demand)
Fixed / Operating
o
o
o
o
1 F / 0.1 C
1 F / 0.1 C
Single / Dual
o
(0 F only)

Absolute
o
0 - 10 F

7, 5+2, 5+1+1
8
N/A
2 Hour Override (fixed)
N/A
N/A
Fixed
Individual
Averaging
Averaging
o

1 Default w/31 optional program settings
Standard

Option
N/A

5.4 F
Adjustable
(15 / 30 / 60 / 90 min)

1 Default
Option
N/A
Option
Option


N/A
Not Needed




N/A

N/A
45 History
500,000
300
46 D-NET


30
Commissioning /
Maintenance
Improved Feature
iTM V2.0
iTM V1.04
31
Changeover Deadband
32
Guard Timer
33
34
35
36
37
38
39
Interlock
Emergency Stop
Web / Error Email Access
System Configuration via Web
PPD Option (tenant billing)
HTTP Option
Di/Dio Unit Compatible
40 WAGO I/O (Di/Do/Ai/Ao)
Software ID Required for Startup
41
(or activation key)
Automatic Adjustment for
42
Daylight Savings Time (DST)
43 Auto Registration
44 Presetting Tool
o
2 F (Minimum)
Adjustable
(15 / 30 / 60 min)
6F
Adjustable
(15 / 30 / 60 / 90 min)
Published by Daikin Product Marketing Department
o
Page 4 of 11
Products
Model
Description
DCM601A71 intelligent Touch Manager
DCM601A72 iTM Plus Adapter
DCM002A71 iTM PPD
Note
Controller with 10.4" LCD / Web Standard
Up to 7 adapter per ITM
Tenant billing software option
*The iTM Integrator (DCM601A73) and iTM Energy Navigator (DCM008A71) options are not currently available
for the North American market.
Published by Daikin Product Marketing Department
Page 5 of 11
Auto-changeover
 Auto-changeover for Heat Recovery and Heat Pump systems with Dual/Single setpoints
Improved
o Primary Changeover deadbands (PCd)
 Adjustable between 1 – 4oF (default of 2oF)
 Guard timer
o Secondary Changeover deadband (SCd)
 Adjustable between 1 – 4oF (default of 1oF)
 Ignores guard timer
o
Enhanced Auto-changeover methods Improved
 Individual, Fixed (default), Average, and Vote
 Weighted Demand configuration for Average and Vote methods
 The Vote Method allows users to configure the system changeover based
upon Heat Override New
 Ideal for Heat Pump or Heat Recovery systems where rooms may have
varying loads
Published by Daikin Product Marketing Department
Page 6 of 11
Vote Method
New

Changeover is evaluated based upon total cooling demand and total heating demand. If
the total cooling demand is greater than the heating (like the figure below), the iTM v2.0
changes the indoor units in the changeover groups to cooling mode.

When the changeover group is in cool mode the total cooling demand will decreased, at
that point the total heating demand may become greater than the cooling demand and
change the mode to heating. (A guard timer applies.)

The setpoints can be different in each indoor unit within the changeover group. The
demand is calculated based on the setpoints in comparison to room temperature for
each indoor unit. The demand within the Primary Changeover deadband (PCd) is
considered as no demand.
o A weight (0 to 3) can be configured for each indoor unit and is multiplied by the
degree difference between the room temperature and setpoint to calculate the
weighted demand

Good for the Heat Pump systems (or under the BS Box with multiple indoor units
connected to the same port in Heat Recovery system) as pseudo simultaneous cooling
and heating operation.
Setpoint
74
PCd
CSP
73
72
HSP
71
70
PCd
69
68
* Option available for heating override if there is an indoor unit which the
heating demand exceeds (H_SP – (PCd + SCd))
Published by Daikin Product Marketing Department
Page 7 of 11
Building facilities management
 WAGO I/O system for management and controls of ancillary equipment by schedule, manual
control, web access, or interlock
o I/O configuration for Digital Input, Digital Output, Analog Input, and Analog Output
o Up to 512 management points can be created
Connect
24 VCD
Power Supply
Unit
Bus Coupler
Item
Required Daikin iTM Basic Kit
Di
Do
Ai
Di, Do, Ai,
End Module
Note
Model
Power Supply Unit 24 VDC,
Connector Module, Bus
Coupler, End Module
51291052
2 Channel Di Module
750-400
4 Channel Di Module
750-432
2 Channel Do Module
750-513/000-001
750-454
750-479
750-461/020-000
2 Channel Ai Module
4-20 mA
±10 VDC
20k Thermistor
Training
The following training classes are offered at Daikin training centers. Check the Daikin training schedule
for class locations and times at www.daikinuniversity.com.


Control Product and Application training class (with ITM) (Course Code: CPA008)
iTM Commission training class (Course Code: ITM008)
o Onsite training can be requested through the Daikin Training Department

iTM Sales Training Webinar (Course Code: OITM01) is also available
o Can be viewed on the Daikin training website at www.daikinuniversity.com.
Published by Daikin Product Marketing Department
Page 8 of 11
Documentation
Located on TRL/FTP site at: ftp.daikinac.com/trl/ControlsDocuments
 iTM User manual
 Installation manual for the iTM
 Installation manual for the iTM Plus Adapter
 Submittal Data Sheet
 iTM Guide Spec
 Sales presentation
 Introduction video
 FAQ
Tools
 TRL - iTM available in the product quotation design/commissioning package

Xpress – The iTM is available under Controls tab for system design
Commissioning
The Commissioning of the iTM may only be performed by a technician who has been qualified to
perform iTM commissioning. The qualification process will require that the candidate for qualification
attend a formal iTM commissioning class. Upon completion of the class participants will be evaluated
by the classroom instructor and based this evaluation may become qualified to commission the iTM. If
prior approval is given from the Daikin Technical Service Department, qualification status may be
granted during onsite iTM commissioning/training. Upon receiving qualification status, the Technical
Service Department will provide the iTM Versionup Tool (software upgrade tool needed to upgrade the
iTM to later software versions), iTM Presetting tool, and iTM commissioning manuals to the qualified
personnel.
Individuals who do not attend a formal iTM commissioning qualification class or receive onsite training
to gain qualification status to commission the iTM will not be provided the opportunity for Daikin
Technical Service support during startup and commissioning of the iTM. Daikin Technical Service
personnel will be available for travel onsite to commission the iTM (iTM commissioning fees will apply).
The iTM Versionup Tool, iTM Presetting Tool, and iTM commissioning manuals will not be provided to
those without the qualification status.
The Power Proportional Distribution (PPD) option commissioning will be carried out by Daikin Technical
Service Personnel only. The iTM PPD Commissioning fees will apply.
Published by Daikin Product Marketing Department
Page 9 of 11
Commissioning Fee Schedule
intelligent Touch Manager Setup & Commissioning Fee
#
Description
1 Basic
Floor Layout Screen
2
Option
3 PPD Option
4 System integration
5
Actual travel
expenses
Part Number
DACA-ITMComm
DACA-ITMLSComm
DACA-ITMPPDComm
DACA-T&H
List Price
$1,210 list + ($50 list x # of indoor unit groups)
$500 list x # of Floor layout screens (up to 20 indoor
units per layout screen)
$1,100 list + ($30 list x # of indoor unit groups)
Charged by project requirement
Default fee $1,000 Continental US and default fee
$2,500 outside Continental US) and actual hotel
expenses (default fee $250/day Continental US and
$350/day outside Continental US) apply.
Upgrading
Upgrades on existing projects from version 1.0x to 2.0 will require a complete recommissioning. Version 1.0x and 2.0 are not compatible, so no data created in the earlier
version will be save when the version upgrade is completed.
Published by Daikin Product Marketing Department
Page 10 of 11
System Overview
Specifications
Published by Daikin Product Marketing Department
Page 11 of 11
Dimensions
iTM
iTM Plus Adapter
Published by Daikin Product Marketing Department
Download PDF