DL305 Base Specifications
1.6’
0.5 M
5-slot I/O base
(local or expansion)
1.115”
29.9mm
I/O Expansion Cable (D3-EXCBL)
8-slot I/O base
(local or expansion)
94--240V
RUN
10-slot I/O base
(local or expansion)
94-240 VAC
Terminal Strip
24V OUT
LG
G
(Bases provide built-in power supplies)
D3-05B-1 <--->
D3-05BDC <--->
D3-08B-1 <--->
D3-10B-1 <--->
D3-10BDC <--->
Number of Slots
5
5
8
10
10
Local CPU Base
Yes
Yes
Yes
Yes
Yes
Expansion Base
Yes
CPU base and two expansion
bases. If CPU base is 5-slot,
then the expansion bases must
be 5-slot also.
Yes
CPU base and two expansion
bases. If CPU base is 5-slot,
then the expansion bases must
be 5-slot also.
Yes (D3-350 only)
CPU base and two expansion
bases. If CPU base is 8-slot,
then the expansion bases must
be 8-slot or 5-slot
Yes
CPU base and one expansion
bases. If CPU base is 10-slot,
then the expansion bases must
be 10-slot or 5-slot
Yes
CPU base and one expansion
bases. If CPU base is 10-slot,
then the expansion bases must
be 10-slot or 5-slot.
Input Voltage Range
85-264VAC
47-63Hz
20.5-30VDC
<10% ripple
85-264VAC
47-63Hz
85-264VAC
47-63Hz
20.5-30VDC
<10% ripple
Base Power Consumption 85 VA Max
48 Watts
85VA Max
85VA Max
65 Watts
Inrush Current Max.
30A 1ms
30A
30A 1ms
30A 1ms
30A
Dielectric Strength
1500VAC for one minute
1500VAC for one minute
between terminals of AC P/S, between 24VDC input termirun output, common, 24VDC nals and run output
1500VAC for one minute
2000VAC for one minute
1500VAC for one minute
between terminals of AC P/S, between terminals of AC P/S, between 24VDC input termirun output, common, 24VDC run output, common, 24VDC nals and run output
Insulation Resistance
>10Mohm at 500VDC
>10Mohm at 500VDC
>10Mohm at 500VDC
>10Mohm at 500VDC
>10Mohm at 500VDC
Power Supply Output
(Voltage Ranges and
Ripple)
(5VDC) 4.75-5.25V
5% ripple
(9VDC) 8.5-10V
5% ripple
(24VDC) 20-28V
5% ripple
(5VDC) 4.75-5.25V
5% ripple
(9VDC) 8.5-10V
5% ripple
(24VDC) 20-28V
5% ripple
(5VDC) 4.75-5.25V
5% ripple
(9VDC) 8.5-10V
5% ripple
(24VDC) 20-28V
5% ripple
(5VDC) 4.75-5.25V
5% ripple
(9VDC) 8.5-10V
5% ripple
(24VDC) 20-28V
5% ripple
(5VDC) 4.75-5.25V
5% ripple
(9VDC) 8.5-10V
5% ripple
(24VDC) 20-28V
5% ripple
5 VDC Current Supplied
.7A
1.4A
1.0A
1.0A
1.4A
9 VDC Current Supplied
2.0A
0.8A
2.0A
2.0A
1.7A
24 VDC Current Supplied 0.5A
0.5A
0.5A
0.5A
0.5A
Auxiliary 24 VDC Output
100mA max
None
100mA max
100mA max
None
Run Relay
250VAC
4A (resistive load)
250VAC
4A (resistive load)
250VAC
4A (resistive load)
250VAC
4A (resistive load)
250VAC,
4A (resistive load)
Fuses
2A (250V) Non-replaceable
4A (250V)
User-replaceable
D3-FUSE-3 <--->
2A (250V) Non-replaceable
2A (250V) Non-replaceable
4A (250V)
User-replaceable
D3-FUSE-3 <--->
Dimensions W/H/D
11.42x4.85x4.41 in.
(290x123x112 mm)
11.42x4.85x4.41 in.
(290x123x112 mm
15.55x4.85x4.41 in.
(395x123x112 mm)
18.3x4.85x4.41 in.
(465x123x112 mm)
18.34x4.85x4.41 in.
(465x123x112 mm)
Weight
37oz. (1050g)
34oz. (964g)
44oz. (1250g)
51.1oz. (1450g)
50.5oz. (1432g)
5–22
PLC Products
1 - 80 0 - 633 - 0405
DL305 Power Requirements
This section shows the amount of
power supplied by the base
power supplies and the amount of
power used by each DL305
device. Note the base power
supplies provide three internal
voltages (5V, 9V, 24V). The chart
shows how much power from
each of these power sources is
required for each DL305 device.
Use this information when calculating the power budget for your
system.
In addition to the three internal
power sources, the DL305 bases
provide an external power
connection. There is 24 VDC
available from the 24 VDC output
terminals on the bases (except
D3-05BDC and D3-10BDC).
The 24 VDC can be used to
power external devices or DL305
modules that require external 24
VDC. The power used from this
external 24 VDC output reduces
the internal system 24 VDC that is
available to the modules by an
equal amount. When using the
24 VDC output at the base
terminal, it is recommended that
100 mA not be exceeded.
Power Consumed
Device
Power Supplied
5V(mA) 9V(mA) 24V(mA) Ext
req.
CPUs
D3-330
D3-340
D3-350
300
300
500
50
20
0
0
0
0
0
0
0
10
25
25
148
112
224
224
68
0
0
0
0
10
10
100
0
0
0
0
0
0
0
0
0
0
DC Input Modules
D3-08ND2
D3-16ND2-1
D3-16ND2F
F3-16ND3F
0
0
0
0
Device
5V(mA) 9V(mA) 24V(mA) 24 V (mA)
D3-05B-1
D3-08B-1
D3-10B-1
D3-05BDC
D3-10BDC
D3-05B-NR
D3-08B-NR
D3-10B-NR
D3-05BDC-NR
D3-10BDC-NR
900
900
900
900
900
900
900
900
900
900
0
0
0
AC/DC Input Modules
D3-08NE3
D3-16NE3
0
0
10
130
DC Output Modules
D3-04TD1
D3-08TD1
D3-08TD2
D3-16TD1-1
D3-16TD2
0
0
0
0
0
12
20
30
40
180
5
24
0
96
0
0
0
0
0
0
12
200
160
160
250
400
0
0
0
0
0
0
0
0
0
0
0
0
AC Output Modules
D3-04TAS
F3-08TAS-1
D3-08TA-1
D3-08TA-2
F3-16TA-2
D3-16TA-2
0
0
0
0
0
0
500
500
500
500
500
500
500
500
500
500
100
100
100
None
None
100
100
100
None
None
Power Consumed
Device
AC Input Modules
D3-08NA-1
D3-08NA-2
D3-16NA
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
5V(mA) 9V(mA) 24V(mA) External
required
Relay Output Modules
D3-08TR
F3-08TRS-1
F3-08TRS-2
D3-16TR
0
0
0
0
360
296
296
480
0
0
0
0
0
0
0
0
Analog Temperature and Thermocouple Modules
F3-04ADS
F3-08AD-1
F3-08THM-n
F3-16AD
F3-04DA-1
F3-04DAS
0
0
0
0
0
0
183
45
50
55
144
154
50
55
34
65
108
145
0
0
0
0
0
0
Communications and Networking
D3-232 DCU
D3-422 DCU
FA-UNICON
D3- DCM
500
500
0
0
0
0
0
300
0
0
0
0
Optional [email protected]
Optional [email protected]
24V or [email protected] 100mA
0
10
70
5
112
0
0
0
0
0
50
50
0
0
0
0
0
0
0
0
0
0
0
0
150
0
0
0
0
0
0
0
0
0
0
0
0
Specialty Modules
D3-08SIM
D3-HSC
D3-TCSU
0
0
40
Programming
D3-HP
D3-HPP
D2-HP
50
50
200
Specialty CPUs
F3-OMUX-1
F3-OMUX-2
F3-PMUX
F3-RTU
409
262
455
416
Operator Interface
DV-1000
150
210
C-more
Micro-Graphic
5–24
PLC Products
1 - 80 0 - 633 - 0405
Dimensions and Installation
It is important to understand the installation requirements for your DL305 system.
This will help ensure that the DL305 products operate within their environmental
and electrical limits.
Plan for safety
This catalog should never be used as a
replacement for the user manual. The user
manuals, D3-USER-M and D3-350-M
(available for download from our web
site), contain important safety information
that must be followed. The system installation should comply with all appropriate
electrical codes and standards.
PLC
Overview
Specification
DL05/06
PLC
Rating
Storage Temperature
Ambient Operating Temperature
Ambient Humidity
Vibration Resistance
Shock Resistance
Noise Immunity
-4°F - 158°F (-20°C to 70°C)
DL105
PLC
32°F - 131°F (0° to 55°C)
30% - 95% relative humidity (non-condensing)
MIL STD 810C, Method 514.2
MIL STD810, Method 516.2
DL205
PLC
DL305
PLC
NEMA (ICS3-304)
DL305 mounting depths
DL405
PLC
OK
Field I/O
Software
4.41”
112mm
Base dimensions and
mounting orientation
5”
127mm
Use the diagrams to the right to make
sure the DL305 system can be installed in
your application. DL305 bases must be
mounted horizontally to ensure proper
airflow for cooling purposes. It is important to check these dimensions against the
conditions required for your application.
For example, it is recommended that you
leave 1.5" depth for ease of access and
cable clearance. However, your distance
may be greater or less. Also, check the
installation guidelines for the recommended cabinet clearances.
C-more
HMIs
Base and CPU
Airflow
Other HMI
With 8-pt., 16-pt. I/O, or
handheld
AC Drives
Motors
Steppers/
Servos
5.94”
151mm
6.75”
171mm
Motor
Controls
Base and CPU with DCU, or
Thumbwheel interface
Proximity
Sensors
With PROM Writer Unit (-lines)
9.0”
229mm
With DCU and D3-DSCBL-2 connected
Photo
Sensors
See
the Enclosures section in
this catalog for an enclosure
that may be suitable for your
application
Limit
Switches
Encoders
Current
Sensors
Pushbuttons/
Lights
Process
2"
50mm
min
A
B
Relays/
Timers
Comm.
C
2"
50mm
min
D
TB’s &
Wiring
Base
Price
D3-05B-1 <--->
D3-08B-1 <--->
D3-10B-1 <--->
A
B
C
11.41" 290mm 10.63" 270mm 4.84” 123mm 3.54”
90mm
15.55" 395mm 14.76" 375mm 4.84” 123mm 3.54”
90mm
18.30" 465mm 17.51" 445mm 4.84” 123mm 3.54”
2"
50mm
min
D
90mm
P anel
Component
Chas s is
Power
Circuit
Protection
Ground Braid
Copper Lugs
Enclosures
P anel or
S tar Was hers
S tar Was hers
Ground
Appendix
Part Index
w w w. a u to m at i o n d i re c t . c o m / d l 305
PLC Products
5–25
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement