INSTALLATION AND MAINTENANCE INSTRUCTIONS
FDM-1 Dual Monitor Module
Specifications
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 5.7 mA (LED on)
Average Operating Current: 750µA (LED flashing)
EOL Resistance: 47K Ohms
Maximum IDC wiring resistance: 1,500 Ohms
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Humidity: 10% to 93% Noncondensing
Dimensions: 4 1 /
2
″ H x 4″ W x 1 1 /
4
″ D (Mounts to a 4″ square by 2 1 /
8
″ deep box.)
Accessories: SMB500 Electrical Box
12 Clintonville Rd
Northford, CT 06472-1653
(203) 484-7161
Before Installing
This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
General Description
The Dual Monitor Module is intended for use in intelligent, two wire systems. It provides two independent 2-wire initiating device circuits (IDC), at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices, or either normally open or normally closed security devices. The module has a single panel controlled red LED.
Compatibility Requirements
To ensure proper operation, this module shall be connected to a compatible Notifier system control panel (list available from Notifier).
avoid duplicate addressing of modules on the system.
3. Secure module to electrical box (supplied by installer), as shown in Figure 2A.
Figure 1. Removing
Rotary Switch Stop:
Figure 2A. Module mounting:
LOOP
9
8
7
6
5
4
5
3
2
1
TENS
8
6
6
0
7 8
15
9
10
11
12
13
14
4
2
ONES
0
0
1
2
3
4
ADDRESS
A78-2318-13
Mounting
Mounts directly to 4” square electrical boxes (see Figure 2A). The box must have a minimum depth of 2 1 /
8
”. Surface mounted electrical boxes (SMB500) are available from Notifier.
Wiring
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. This module is intended for power limited wiring only.
1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams.
2. Set the address on the module per job drawings.
Note: Some panels support extended addressing. In order
to set the module above address 99 on compatible systems,
carefully remove the stop on the upper rotary switch with
thumb in the direction shown in Figure 1.
Note: Monitor module L (using terminals 6 and 7) responds at the address set on the code switches. Monitor module H (using terminals 8 and 9) will automatically respond at the next higher address. For example, if the code switches are set to 76, module L will respond at address 76 and module H will respond at address 77. Use caution to
9
8
0
6
7 8
5
4 3
7
9 10 1112
13
2 1
TENS
6
0
15
14
8
6
4
5
1
2
2
ONES
0
3
4
ADDRESS
A78-2610-14
Figure 2B:
LOOP 5
ONES
6
2
0
4
7
6
TENS
8
8
1
0
3
4
15
9
14
5 6
13
2
7
12
8
9
11
10
1
ADDR
ESS
4
3
0
A78-2611-19
N500-75-00 1 I56-1463-02
www.PDF-Zoo.com
Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B:
(—)
TWO INITIATING DEVICE CIRCUITS (L & H),
EACH POWER LIMITED TO 230 A @ 12VDC MAX.
TO NEXT
DEVICE
(+)
MONITOR
MODULE
47 K EOL
RESISTOR
ELR-47K
47 K EOL
RESISTOR
ELR-47K
H
L
LOOP
9
8
7
6
5
4
5
3
2
1
TENS
8
6
6
0
7 8
15
9
10
11
12
4
2
ONES
0
0
1
2
3
4
ADDRESS
(+)
(—)
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR SECURITY
DEVICES ON THE SAME INITIATING DEVICE CIRCUIT.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER’S INSTALLATION INSTRUCTIONS.
(—)
(+)
FROM PANEL OR
PREVIOUS DEVICE
CONNECT MODULES TO LISTED COMPATIBLE
NOTIFIER CONTROL PANELS ONLY
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
COMMUNICATION LINE
32 VDC MAX.
SHIELDED-TWISTED PAIR
IS RECOMMENDED
MONITOR A (TERMINALS 6 & 7) RESPONDS AT ADDRESS
SET ON CODE SWITCHES. MONITOR B (TERMINALS 8 & 9)
RESPONDS AT NEXT HIGHER ADDRESS.
A78-2280-39
N500-75-00 2 I56-1463-02
www.PDF-Zoo.com
©
2001 Notifier