null  null
036-21058-005-A-0704
®
TECHNICAL
GUIDE
®
DESCRIPTION
STANDARD EFFICIENCY
SINGLE PACKAGE AIR CONDITIONERS AND
SINGLE PACKAGE GAS/ELECTRIC UNITS
DM 078, 090, 102, 120 and 150
6-1/2, 7-1/2, 8-1/2, 10 and 12-1/2 NOMINAL TONS
9.0 EER
YORK® Predator® units are convertible single packages
with a common footprint cabinet and common roof curb for
all 6-1/2 through 12-1/2 ton models. All units have two
compressors with independent refrigeration circuits to provide two stages of cooling. The units were designed for
commercial applications and can be easily installed on a
roof curb, slab, or frame.
All Predator® units are self-contained and assembled on
rigid full perimeter base rails allowing for 3-way forklift
access and overhead rigging. Every unit is completely
charged, wired, piped, and tested at the factory to provide
a quick and easy field installation.
All units are convertible between side and down airflow. A
independent economizer design is used on side and down
discharge applications, as well as all tonnage sizes.
Predator® units are available in the following configurations: cooling only, cooling with electric heat, and cooling
with gas heat. Electric heaters are available as factoryinstalled options or field-installed accessories.
Tested in accordance with:
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21058-005-A-0704
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
LIST OF TABLES (cont.)
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Tbl. #
FACTORY INSTALLED OPTIONS . . . . . . . . . . . . . . 5
10 ELECTRICAL DATA DM078 (6-1/2 TON) STD
EFFICIENCY W/O PWRD CONV. OUTLET . . . . . . . 20
FIELD INSTALLED ACCESSORIES . . . . . . . . . . . . 6
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Pg. #
11 ELECTRICAL DATA DM078 (6-1/2 TON) STD
EFFICIENCY WITH PWRD CONV. OUTLET . . . . . . 20
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 45
12 ELECTRICAL DATA DM090 (7-1/2 TON) STD
EFFICIENCY W/O PWRD CONV. OUTLET . . . . . . . 21
LIST OF FIGURES
13 ELECTRICAL DATA DM090 (7-1/2 TON) STD
EFFICIENCY WITH PWRD CONV. OUTLET . . . . . . 21
Fig. #
Pg. #
1
PREDATOR® COMPONENT LOCATION . . . . . . . . . . 3
14 ELECTRICAL DATA DM102 (8-1/2 TON) STD
EFFICIENCY W/O PWRD CONV. OUTLET . . . . . . . 22
2
POWER EXHAUST ACCESSORY DOWNFLOW
APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
15 ELECTRICAL DATA DM102 (8-1/2 TON) STD
EFFICIENCY WITH PWRD CONV. OUTLET . . . . . . 22
3
POWER EXHAUST ACCESSORY HORIZONTAL
APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
16 ELECTRICAL DATA DM120 (10 TON) STD
EFFICIENCY W/O PWRD CONV. OUTLET . . . . . . . 23
4
UNIT 4 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . . 37
5
UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . 37
17 ELECTRICAL DATA DM120 (10 TON) STD
EFFICIENCY WITH PWRD CONV. OUTLET . . . . . . 23
6
UNIT 6 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . . 37
7
UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 38
8
PREDATOR® ROOF CURB DIMENSIONS . . . . . . . . 39
9
SUNLINE™ TO PREDATOR® TRANSITION ROOF
CURBS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
10 BOTTOM DUCT OPENINGS (FROM ABOVE) . . . . . 40
11 REAR DUCT DIMENSIONS . . . . . . . . . . . . . . . . . . . . 41
12 COOLING UNIT WITH GAS HEAT WIRING 230 VOLT
DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
18 ELECTRICAL DATA DM150 (12-1/2 TON) STD
EFFICIENCY W/O PWRD CONV. OUTLET . . . . . . . 24
19 ELECTRICAL DATA DM150 (12-1/2 TON) STD
EFFICIENCY W/PWRD CONV. OUTLET . . . . . . . . . 24
20 ELECTRIC HEAT MULTIPLIERS . . . . . . . . . . . . . . . 24
21 BLOWER PERF. 6-1/2 TON SIDE DUCT . . . . . . . . . 25
22 BLOWER PERF. 7-1/2 TON SIDE DUCT . . . . . . . . . 26
23 BLOWER PERF. 8-1/2 TON SIDE DUCT . . . . . . . . . 27
24 BLOWER PERF. 10 TON SIDE DUCT . . . . . . . . . . . 28
13 COOLING UNIT WITH/WITHOUT ELECTRIC HEAT
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
25 BLOWER PERF. 12-1/2 TON SIDE DUCT . . . . . . . . 29
14 COOLING UNIT WITH GAS HEAT WIRING 460, 575
VOLT AND 50 HZ DIAGRAM . . . . . . . . . . . . . . . . . . . 44
27 BLOWER PERF. 7-1/2 TON DOWNSHOT . . . . . . . . 31
LIST OF TABLES
29 BLOWER PERF. 10 TON DOWNSHOT . . . . . . . . . . 33
Tbl. #
Pg. #
1
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2
PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3
DM CAPACITY RATINGS . . . . . . . . . . . . . . . . . . . . . 14
4
UNIT VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . 14
5
COOLING CAPACITY 6-1/2 TON UNIT . . . . . . . . . . . 15
6
COOLING CAPACITY 7-1/2 TON UNIT . . . . . . . . . . . 16
7
COOLING CAPACITY 8-1/2 TON UNIT . . . . . . . . . . . 17
8
COOLING CAPACITY 10 TON UNIT . . . . . . . . . . . . . 18
9
COOLING CAPACITY 12-1/2 TON UNIT . . . . . . . . . . 19
2
26 BLOWER PERF. 6-1/2 TON DOWNSHOT . . . . . . . . 30
28 BLOWER PERF. 8-1/2 TON DOWNSHOT . . . . . . . . 32
30 BLOWER PERF. 12-1/2 TON DOWNSHOT . . . . . . . 34
31 ADDITIONAL STATIC RESISTANCE . . . . . . . . . . . . 35
32 ELECTRIC HEAT MINIMUM SUPPLY AIR CFM . . . . 35
33 INDOOR BLOWER SPECIFICATIONS . . . . . . . . . . . 36
34 POWER EXHAUST SPECIFICATIONS . . . . . . . . . . . 36
35 4 POINT LOAD WEIGHT . . . . . . . . . . . . . . . . . . . . . . 37
36 6 POINT LOAD WEIGHT . . . . . . . . . . . . . . . . . . . . . . 38
37 UNIT WEIGHT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
38 UNIT CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . 38
Unitary Products
036-21058-005-A-0704
Terminal Block
for Hi-Voltage
Connection
“[email protected]™” Control Board
w/ Screw Connector for T-stat Disconnect Location
Wiring and Network
(Optional Disconnect Switch)
Connection
Filter Access
(2” Filters)
Filter-Drier (Solid Core)
Condenser
Section
Second model
nameplate inside
hinged access
panel
Belt-Drive
Blower Motor
Dual stage
cooling for
maximum
comfort
Slide-Out Motor
and Blower
Assembly for
easy adjustment
and service.
Compressor
#2 Access
(High-Eff
Compressor
w/ crankcase
heater)
Power Ventor Motor
Base Rails w/ Forklift
Slots (3 Sides) & Lifting
Holes
Roof curbs in eight- and
fourteen-inch heights.
Roof curbs for transitioning from York Sunline footprint to the DM
Series footprint are also
available (field-installed
accessory)
FIGURE 1 -
Slide-Out Drain
Pan w/ Steel 3/4”
FPT Connection
Tool-less
door latch
Side entry power
and control wiring
knockouts
•
Standard Efficiency– All standard efficiency units have
a minimum EER of 9.0. Gas/electric units have electronic spark ignition and power vented combustion with
steady state efficiencies of 80%.
Service Friendly – The Predator® incorporates a number of enhancements which improve serviceability.
The motor and blower slide out of the unit as a common
assembly. This facilitates greater access to all the indoor
airflow components, thus simplifying maintenance and
adjustment.
Service time is reduced through the use of hinged, toolless panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other unauthorized persons. It is recommended that the panels be
secured with screws once service is complete.
Unitary Products
Intelligent control board for
safe and efficient operation
PREDATOR® COMPONENT LOCATION
FEATURES
•
Compressor #1 Access (High-Eff
Compressor w/ crankcase heater)
Two-stage gas heating to maintain
warm, comfortable
temperature
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access
to the condenser coils for cleaning or inspection.
Both the unit control board and ignition control board utilize flash codes to aid in diagnosis of unit malfunctions.
Unique alarm codes quickly identify the source of the
unit alarm.
All units use the same standard filter size. This standardization removes any confusion on which filter sizes
are needed for replacement.
The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing the drain pan cover plate on the rear of the unit.
Once the plate is removed, the drain pan slides out
through the rear of the unit.
All Predator® units have a second model nameplate
located inside the control access door. This is to prevent
deterioration of the nameplate through weathering.
3
036-21058-005-A-0704
•
Environmentally Aware – For improved Indoor Air
Quality, foil faced insulation is used exclusively throughout the units.
•
Balanced Heating – The Predator® offers “Ultimate
Heating Comfort” with a balance between 1st and 2nd
stage gas heating. The 1st stage of a gas heat Predator®
unit provides 60% of the heating capacity. Balanced
heating allows the unit to better maintain desired temperatures.
•
•
•
Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side supply/return is desired, the installer simply removes the two
side duct covers from the outside of the unit and installs
them over the down shot openings. No panel cutting is
required. Convertible airflow design allows maximum
field flexibility and minimum inventory.
System Protection - Suction line freezestats are supplied on all units to protect against loss of charge and coil
frosting when the economizer operates at low outdoor air
temperatures while the compressors are running. Every
unit has solid-core liquid line filter-driers and high and
low-pressure switches. Internal compressor protection is
standard on all compressors. Crankcase heaters are
standard on reciprocating compressors. Scroll compressors do not require crankcase heaters. Phase Monitors
are standard on units with scroll compressors. This
accessory monitors the incoming power to the unit and
protects the unit from phase loss and reversed phase
rotation.
•
•
•
4
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0°F outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti-short cycle delay can be temporarily
overridden with the push of a button.
•
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
Reliable – From the beginning – All units undergo computer automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term –
All Predator® units are painted with a long lasting, powder paint that stands up over the life of the unit. The paint
used has been proven by a 750 hour salt spray test.
•
Flexible Placement – All models and configurations
share the same cabinet/footprint and thus the same roof
curb. You have the flexibility to set one curb and choose
the correct tonnage size and heating option after the
internal loads have been determined.
To further simplify planning and installation, Predator®
cabinets are designed to fit your roof. With the optional
roof curb, the unit ductwork is designed to fit around 24”
on-center joists or between 48” on-center joists.
The drain pan can be rotated to drain to either the front
or the rear of the unit. Additionally, the drain pan can be
piped to drain through the roof curb. As it is sometimes
difficult to have a level installation, the drain pan features
a generous slope to ensure proper drainage.
•
Full Perimeter Base Rails – The permanently attached
base rails provide a solid foundation for the entire unit
and protect the unit during shipment. The rails offer forklift access from 3 sides, and rigging holes are available
so that an overhead crane can be used to place the units
on a roof.
•
Easy Installation – Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the
unit. A clearly identified location is provided to mount a
field supplied electrical disconnect switch. Utility connections can be made quickly and with a minimum
amount of field labor.
Fan Delays - Fan on and fan off delays are fully programmable. Furthermore, the heating and cooling
fan delay times are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas and electric heat units. The unit control board will alarm on ignition failures, compressor
lockouts and repeated limit switch trips.
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a
“three times, you’re out” philosophy. The high and
low-pressure switches and the freezestats must trip
three times within two hours before the unit control
board will lock out the associated compressor.
•
Advanced Controls - [email protected]™ control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
•
•
All units are shipped with 2” filters installed.
•
Wide Range of Indoor Airflows – All indoor fan motors
are belt-drive type providing maximum flexibility to handle most airflow requirements. For high static applications, factory installed alternate indoor fan motors are
available. With the optional indoor fan motor, all units
can supply nominal airflow at a minimum of 1.5” ESP.
Unitary Products
036-21058-005-A-0704
•
Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty. Aluminized steel
and stainless steel tubular heat exchangers carry an
additional 10-year warranty.
With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit provides a second
input used to monitor the return air. With a dual input kit
installed, the economizer control compares the values of
the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
FACTORY INSTALLED OPTIONS
YORK® offers several equipment options factory installed, for
the Predator® line.
•
•
•
•
Downflow Economizer - (With barometric relief) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type, and is shipped
installed and wired. The installer needs only to assemble
and mount the outdoor air hood (Provided). The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air.
As the outdoor air intake dampers open, the return air
dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input
dual dry bulb available. To meet regulated air standards,
the economizer control accepts an optional CO2 input for
demand ventilation. With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit
provides a second input used to monitor the return air.
With a dual input kit installed, the economizer control
compares the values of the two enthalpy or temperature
inputs and positions the dampers to provide the maximum efficiency possible.
Horizontal Economizer - (Without barometric relief) All features of the downflow economizer exist except you
must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a
power exhaust. You can order a 1RD0411 Barometric
Relief for horizontal flow economizers only.
BAS Ready Economizer -(With barometric relief) The economizer is provided with a Belimo actuator that
requires a 0-10V DC input from an external source (i.e.,
field installed building automation system controller).
Power exhaust options are available. The economizer is
2% low leakage type with spring return and fully modulating dampers capable of introducing up to 100% outside air. Also include 2” pleated filters.
Slab Economizer for Energy Recovery Ventilators(With barometric relief and Fresh Air Hood) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type, and is shipped
installed and wired. The economizer has spring return,
fully modulating damper actuators and is capable of
introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to economizer
operation is regulated by the standard single enthalpy
input. There is an optional input dual dry bulb available.
To meet regulated air standards, the economizer control
accepts an optional CO2 input for demand ventilation.
Unitary Products
•
Power Exhaust (Downflow only) - This accessory
installs in the unit with a down flow economizer.
•
Motorized Outdoor Air Damper - The motorized outdoor air damper includes a slide-in/plug-in damper
assembly with an outdoor air hood and filters. The outdoor air dampers open to the preset position when the
indoor fan motor is energized. The damper has a range
of 0% to 100% outdoor air entry. Factory installed option
or field installed accessory.
•
Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
•
Aluminized Steel Gas Heat Exchanger - For applications in non-corrosive environments.
•
Stainless Steel Gas Heat Exchanger - For applications
in corrosive environments, this option provides a full
stainless steel heat exchanger assembly.
•
Stainless Steel Drain Pan - An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.
•
Electric Heaters - The electric heaters range from 9kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. All heaters are
intended for single point power supply.
•
Disconnect Switch - For gas heat units and cooling
units with electric heat, an HACR breaker sized to the
unit is provided. For cooling only units, a switch sized to
the largest electric heat available for the particular unit is
provided. Factory installed option only.
•
Convenience Outlet - (Non-Powered /Powered) - This
option locates a 120V single-phase GFCI outlet with
cover, on the corner of the unit housing adjacent to the
compressors. The “Non-powered” option requires the
installer to provide the 120V single-phase power source
and wiring. The “Powered” option is powered by a stepdown transformer in the unit. Factory installed option
only.
•
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment. Available
for both the supply and/or return air.
•
Phase Monitors - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of
phase condition. (Standard on units with Scroll Compressors.)
5
036-21058-005-A-0704
•
•
•
•
•
Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally,
this kit stops animals and foreign objects from entering
the space between the inner condenser coil and the
main cabinet. This is not a hail guard kit.
Dirty Filter Switch - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
Technicoat Condenser Coils - The condenser coils are
coated with a phenolic coating for protection against corrosion due to harsh environments.
Technicoat Evaporator Coil - The evaporator coils are
coated with a phenolic coating for protection against corrosion due to harsh environments.
BAS - Building Automation System Controls [email protected]
FQV™ INTELLI-Comfort™ Control - The York® [email protected]
FQV™ INTELLI-Comfort™ control is factory installed. It
includes a supply air sensor, a return air sensor, and an
outside air sensor. There are provisions for a field
installed dirty filter indicator switch, an air-proving switch,
an Outside Air Humidity sensor, a Return Air Humidity
sensor, an Inside IAQ sensor, and an Outside Air IAQ
sensor. Construction mode operation, 365-day real time
clock with 7 day programming plus holiday scheduling is
built-in. Two different modes of demand ventilation are
achieved through the INTELLI-Comfort™ using CO2
sensors. It uses an inside CO2 sensor to perform
Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a
Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the equipment when
harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection
for hot gas re-heat system. It uses the INTELLI-Start™
algorithm to maximize energy savings by recovering the
building from the Unoccupied Setpoints to the Occupied
Setpoints just in time for the Occupied Time Period to
begin. The [email protected]™ INTELLI-Comfort™ balances
space temperature, ventilation air temperature, CO2 and
humidity for ultimate comfort.
•
[email protected]™ INTELLI-Comfort™ with ModLINC
Control - The York® [email protected]™ INTELLI-Comfort™
with ModLINC control is factory installed. It includes all
the features of the INTELLI-Comfort™ control with an
additional control to translate communications from
MODBUS to the BACnet MSTP protocol.
•
Novar® BAS Control - The Novar® ETC-3 building
automation system controller is factory installed. Incudes
supply air sensor, return air sensor, dirty filter indicator
switch, and air proving switch.
•
Johnson Controls BAS Control - The Johnson Control
YK-UNT-1126 building automation system controller is
6
factory installed. Includes supply air sensor, return air
sensor, dirty filter indicator switch, and air proving switch.
•
CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
•
Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
FIELD INSTALLED ACCESSORIES
YORK® offers several equipment accessories for field installation, for the Predator® line.
•
Downflow Economizer - (With barometric relief) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the economizer control accepts an optional CO2 input for demand
ventilation. With single enthalpy input, the economizer
control monitors outdoor air. The dual enthalpy kit provides a second input used to monitor the return air. With
a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature
inputs and positions the dampers to provide the maximum efficiency possible
•
Horizontal Economizer - (Without barometric relief) All features of the downflow economizer exist except you
must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a
power exhaust. You can order a 1RD0411 Barometric
Relief for horizontal flow economizer.
•
Slab Economizer for Energy Recovery Ventilator(Without barometric relief or Fresh Air Hood) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the economizer control accepts an optional CO2 input for demand
ventilation. With single enthalpy input, the economizer
control monitors outdoor air. The dual enthalpy kit provides a second input used to monitor the return air. With
a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature
Unitary Products
036-21058-005-A-0704
inputs and positions the dampers to provide the maximum efficiency possible.
section heating kit is available. This kit provides electric
heat in the gas heat controls section to ensure the gas
valve and controls will continue to function properly at
extremely low temperatures.
You can order 1EH0409 Barometric Relief/FA Hood
for field installations without an ERV.
•
Dual Enthalpy Control, Accessory - This kit contains
the required components to convert a single enthalpy
economizer to dual enthalpy.
•
Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed slab economizers.
•
Power Exhaust - This accessory installs in the unit with
a down flow economizer. Power exhaust plugs into the
connector in the unit bulkhead. You must purchase
1EH0408 barometric relief when applying to a horizontal flow application.
•
Manual Outdoor Air Damper - Like the motorized outdoor air damper, each manual outdoor air damper
includes a slide-in damper assembly with an outdoor air
hood and filters. Customers have a choice of dampers
with ranges of 0% to 100% or 0% to 35% outdoor air
entry.
•
Motorized Outdoor Air Damper - The motorized outdoor air damper includes a slide-in/plug-in damper
assembly with an outdoor air hood and filters. The outdoor air dampers open to the preset position when the
indoor fan motor is energized. The damper has a range
of 0% to 100% outdoor air entry. Factory installed option
or field installed accessory.
•
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
•
CO2 Sensor - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
preset limits.
•
Dirty Filter Switch - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high
pressure drop across the filters.
•
Coil Guard - Field installed decorative wire coil guard.
•
•
•
•
Gas Heat High Altitude Kit - This kit converts a gas
heat unit to operate at high altitudes, 2,000 to 6,000 feet.
Conversion kits are available for natural gas and propane.
•
Gas Heat Propane Conversion Kit - This kit converts a
gas-fired heater from natural gas to propane. It contains
the main burner orifices and gas valve replacement
springs.
•
Gas Piping Kit - Contains pipe nipples, fittings and gas
cock required for gas supply connection with external
shut off.
•
Electric Heaters - The electric heaters range from 9 kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. Cooling units
include an adapter panel for easy installation of the electric heaters. Necessary hardware and connectors are
included with the heaters. All heaters are intended for
single point power supply.
•
Low Limit / Compressor Lockout Kit
1.
Compressor Lockout (CLO): To prevent mechanical (compressorized) operation of the unit during
cold outdoor conditions where there is a risk of
returning liquid refrigerant back to the compressors.
2.
Low Limit Control (LLC): To prevent the supply air
from dropping below a specified setpoint by utilizing
the units first stage heating means when there is a
demand for cooling during cold outside conditions.
•
Metal Frame Filter Kit - Metal frame with polyester filter
medium.
•
Permanent Filters - Permanent filters are available.
•
Roof Curbs - The roof curbs have insulated decks and
are shipped disassembled The roof curbs are available
in 8” and 14” heights. For applications with security concerns, burglar bars are available for the duct openings of
the roof curbs.
Hail Guard - This kit includes a sloped hood which
installs over the outside condenser coil and prevents
damage to the coil fins from hail strikes. Field installed
accessory only.
•
Roof Curb Transition - Single Piece Adapter (10” High)
- Roof curbs for transitioning from Sunline™ units to
Predator® units. Fits 7.5 to 12.5 Sunline™ roof curbs
only.
Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can
be installed to prevent the flue exhaust from entering
nearby fresh air intakes.
•
Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
•
Thermostat - The units are designed to operate with 24volt electronic and electro-mechanical thermostats. All
units (with or without an economizer) operate with twostage heat/two-stage cool or two-stage cooling only thermostats, depending upon unit configuration.
-60°F Gas Heat Kit - For installations which require gas
heat units to perform in low ambient temperatures, a gas
Unitary Products
7
036-21058-005-A-0704
TABLE 1: ACCESSORIES
Part Number
1RC0470
1RC0471
1RC0472
1BD0408
2TP04520925
2TP04521825
2TP04522425
2TP04523625
2TP04525425
2TP04520946
2TP04521846
2TP04522446
2TP04523646
2TP04525446
2TP04520958
2TP04521858
2TP04522458
2TP04523658
2TP04525458
1FA0411
1FA0412
2MD04702724
2MD04703324
2EE04705024
2EE04705124
2EE04705224
2PE04703225
2PE04703246
2PE04703258
2EC04700924
1EH0407
1RD0411
1EH0408
1EH0409
2AQ04700424
2AQ04700324
2SD04700424
2MK04700624
1CG0419
1CG0420
1HG0411
1GP0404
1NP0441
1HA0442
1HA0443
1FE0411
2BC04700106
2BC04700151
2BC04700154
1FL0402
2DF0401
1FF0410
8
Description
Roof Curb, 8" Height
Roof Curb, 14" Height
Roof Curb, Transition (7.5 T through 12.5 T)
Burglar Bars, Downflow
Electric Heat 9kW 230V
Electric Heat 18kW 230V
Electric Heat 24kW 230V
Electric Heat 36kW 230V
Electric Heat 54kW 230V
Electric Heat 9kW 460V
Electric Heat 18kW 460V
Electric Heat 24kW 460V
Electric Heat 36kW 460V
Electric Heat 54kW 460V
Electric Heat 9kW 575V
Electric Heat 18kW 575V
Electric Heat 24kW 575V
Electric Heat 36kW 575V
Electric Heat 54kW 575V
Manual Outside Air Damper 0-35%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)
Manual Outside Air Damper 0-100%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)
Motorized Damper, Downflow (Incl. Hood, Damper & Filter, no Barometric Relief)
Motorized Damper, Horizontal (Incl. Hood, Damper & Filter, no Barometric Relief)
Economizer, Downflow (Incl. Barometric Relief & All Hoods)
Economizer, Horizontal (Incl. Dampers & Hoods, no Barometric Relief)
Economizer, Slab, Downflow (Incl. Dampers only no Hoods or Barometric Relief)
Power Exhaust, Downflow, 230V (For Units with Economizer only)
Power Exhaust, Downflow, 460V (For Units with Economizer only)
Power Exhaust, Downflow, 580V (For Units with Economizer only)
Dual Enthalpy Control (Use with Single Enthalpy Economizer)
Hood Kit, Downflow Economizer (Included with all Downflow Economizers)
Barometric Relief Kit, Ductmount for Horizontal Application (Incl. Damper & Hood)
Barometric Relief Kit, Ductmount for Horizontal Application w/ Power Exhaust (Incl. Damper & Hood)
Barometric Relief / Hood Kit, for Field Installed Slab Econ. w/o ERV (Incl. Barometric Relief & FA Hood)
CO2 Detector Unit Mount
CO2 Detector Space Mount
Smoke Detector, Supply or Return (Return Not Available with Horizontal Economizer)
Low Limit / Compressor Lockout Kit
Coil Guard (Electric / Electric & HP models)
Coil Guard (Gas / Electric models)
Hail Guard Kit
Gas Piping Kit
Propane Conversion Kit
High Altitude Kit for Natural Gas
High Altitude Kit for Propane
Flue Exhaust Extension Kit
Gas Heat Kit, -60 deg F, 230V
Gas Heat Kit, -60 deg F, 460V
Gas Heat Kit, -60 deg F, 575V
Permanent Filter Kit
Dirty Filter Switch
Filter Frame Kit, Metal
Weight
124 lbs.
97 lbs.
-
25 lbs.
-
Unitary Products
036-21058-005-A-0704
NOMENCLATURE
6½ - 12½ Ton Predator Model Number Nomenclature
D M 090 N10 A 2 A AA 3
Product Generation
3 = Third Generation
4 = Fourth Generation
Product Category
D = Air Cond., Single Package
Product Identifier
M = R-22 Standard Efficiency
H = R-22 High Efficiency
Nominal Cooling Capacity - MBH
Voltage
2 = 208/230-3-60
3 = 380-3-60
4 = 460-3-60
5 = 575-3-60
078 = 6-½ Ton
090 = 7-½ Ton
102 = 8-½ Ton
120 = 10 Ton
150 = 12-½ Ton
Heat Type & Nominal Heat Capacity
C00 = Cooling Only. Suitable for field installed electric heat
Gas Heat Options
N 10 = 100 MBH Output Aluminized Steel
N 15 = 150 MBH Output Aluminized Steel
N 20 = 200 MBH Output Aluminized Steel
S 10 = 100 MBH Output Stainless Steel
S 15 = 150 MBH Output Stainless Steel
S 20 = 200 MBH Output Stainless Steel
Installation Options
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2 & 4
L = Options 1, 3 & 4
M = Options 1, 2, 3 & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3 & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3 & 5
V = Options 1, 4 & 5
W = Options 1, 3, 4 & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Additional Options
(See Next Page)
Options
Electric Heat Options
1 = Disconnect
2 = Non-Pwr’d Conv Outlet
3 = Smoke Detector S. A.
4 = Smoke Detector R. A.
5 = Pwr’d Conv Outlet
E09 = 9 kW Electric Heat
E18 = 18 kW Electric Heat
E24 = 24 kW Electric Heat
E36 = 36 kW Electric Heat
E54 = 54 kW Electric Heat
Airflow
A = Standard Motor
B = Standard Motor/Economizer/Barometric Relief (Downflow only)
C = Standard Motor/Economizer/Power Exhaust (Downflow only)
D = Standard Motor/Motorized Damper (Downflow only)
E = Standard Motor/Horizontal Economizer (No Barometric Relief)
F = Standard Motor/Slab Economizer/Power Exhaust (Downflow only)
G = Standard Motor/Slab Economizer/Barometric Relief (Downflow only)
L = Standard Motor/BAS Ready Econ (NoBASController)/Barometric Relief w/2" Pleated Filters (Downflow only)
M = Standard Motor/BAS Ready Econ (NoBASController)/Power Exhaust w/2" Pleated Filters (Downflow only)
N = High Static Motor
P = High Static Motor/Economizer/Barometric Relief (Downflow only)
Q = High Static Motor/Economizer/Power Exhaust (Downflow only)
R = High Static Motor/Motorized Damper (Downflow only)
S = High Static Motor/Horizontal Economizer (No Barometric Relief)
T = High Static Motor/Slab Economizer/Power Exhaust (Downflow only)
U =High Static Motor/Slab Economizer/Barometric Relief (Downflow only)
Y = High Static Motor/BAS Ready Econ (NoBASController)/Barometric Relief w/2" Pleated Filters (Downflow only)
Z = High Static Motor/BAS Ready Econ (NoBASController)/Power Exhaust w/2" Pleated Filters (Downflow only)
Unitary Products
9
036-21058-005-A-0704
NOMENCLATURE ADDITIONAL OPTIONS
Additional Options
AA
AB
AC
AD
AE
AF
AG
AH
AJ
AK
AL
AM
AN
CA
CB
CC
CD
CE
CF
CG
CH
CJ
CK
CL
CM
CN
CP
CQ
CR
CS
CT
CU
CV
CW
CX
JA
JB
JC
JD
JE
JF
JG
JH
JJ
JK
JL
JM
JN
JP
JQ
JR
JS
JT
JU
JV
JW
JX
10
None
Phase Monitor
Coil Guard
Dirty Filter Switch
Phase Monitor & Coil Guard
Phase Monitor & Dirty Filter Switch
Coil Guard & Dirty Filter Switch
Phase Monitor, Coil Guard, & Dirty Filter Switch
SS Drain Pan
SS Drain Pan & Phase Monitor
SS Drain Pan & Coil Guard
SS Drain Pan & Dirty Filter Switch
SS Drain Pan, Phase Monitor, Coil Guard & Dirty Filter Switch
CPC Controller with Dirty Filter Switch & Air Proving Switch
CPC Controller, DFS, APS & Phase Monitor
CPC Controller, DFS, APS & Coil Guard
CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS & Technicoat Cond. Coil
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS & Technicoat Evap. Coil
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS, SS Drain Pan
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
Johnson UNT Controller, DFS, APS & Phase Monitor
Johnson UNT Controller, DFS, APS & Coil Guard
Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS, SS Drain Pan
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Unitary Products
036-21058-005-A-0704
Additional Options
HA
HB
HC
HD
HE
HF
HG
HH
HJ
HK
HL
HM
HN
HP
HQ
HR
HS
HT
HU
HV
HW
HX
WA
WB
WC
WD
WE
WF
WG
WH
WJ
WK
WL
WM
WN
WP
WQ
WR
WS
WT
WU
WV
WW
WX
NA
NB
NC
ND
NE
NF
NG
NH
NJ
NK
NL
NM
NN
NP
NQ
Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Intelli-Comfort w/ModLINC Controller
Intelli-Comfort w/ModLINC Controller, & Phase Monitor
Intelli-Comfort w/ModLINC Controller, & Coil Guard
Intelli-Comfort w/ModLINC Controller, Phase Monitor, & Coil Guard
Intelli-Comfort w/ModLINC Controller, & Technicoat Cond. Coil
Intelli-Comfort w/ModLINC Controller, Technicoat Cond. Coil, & Phase Monitor
Intelli-Comfort w/ModLINC Controller, Technicoat Cond. Coil, & Coil Guard
Intelli-Comfort w/ModLINC Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Intelli-Comfort w/ModLINC Controller, & Technicoat Evap. Coil
Intelli-Comfort w/ModLINC Controller, Technicoat Evap. Coil, & Phase Monitor
Intelli-Comfort w/ModLINC Controller, Technicoat Evap. Coil, & Coil Guard
Intelli-Comfort w/ModLINC Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Intelli-Comfort w/ModLINC Controller, & Technicoat Evap. & Cond Coils
Intelli-Comfort w/ModLINC Controller, Technicoat Evap. & Cond Coils, & Phase Monitor
Intelli-Comfort w/ModLINC Controller, Technicoat Evap. & Cond Coils, & Coil Guard
Intelli-Comfort w/ModLINC Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Intelli-Comfort w/ModLINC Controller, SS Drain Pan
Intelli-Comfort w/ModLINC Controller, SS Drain Pan, Phase Monitor, & Coil Guard
Intelli-Comfort w/ModLINC Controller, SS Drain Pan, & Technicoat Cond Coils
Intelli-Comfort w/ModLINC Controller, SS Drain Pan, & Technicoat Evap Coil
Intelli-Comfort w/ModLINC Controller, SS Drain Pan, & Technicoat Evap and Cond Coils
Intelli-Comfort w/ModLINC Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
Novar ETC-3 Controller, DFS, APS & Phase Monitor
Novar ETC-3 Controller, DFS, APS & Coil Guard
Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
Unitary Products
11
036-21058-005-A-0704
Additional Options
NR
NS
NT
NU
NV
NW
NX
LA
LB
LC
LD
LE
LF
LG
LH
LJ
LK
LL
LM
LN
LP
LQ
LR
LS
LT
LU
LV
LW
LX
TA
TB
TC
TD
TE
TF
TG
TH
TJ
TK
TL
TM
TN
TP
TQ
TR
TS
TT
TU
TV
TW
TX
TY
TZ
T1
T3
T4
T6
T7
T9
12
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS, SS Drain Pan
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Simplicity Intelli-Comfort Controller
Simplicity Intelli-Comfort Controller, & Phase Monitor
Simplicity Intelli-Comfort Controller, & Coil Guard
Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, SS Drain Pan
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Technicoat Condenser Coil
Technicoat Condenser Coil & Phase Monitor
Technicoat Condenser Coil & Coil Guard
Technicoat Condenser Coil & Dirty Filter Switch
Technicoat Condenser Coil, Phase Monitor, & Coil Guard
Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator Coil
Technicoat Evaporator Coil & Phase Monitor
Technicoat Evaporator Coil & Coil Guard
Technicoat Evaporator Coil & Dirty Filter Switch
Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils
Technicoat Evaporator & Condenser Coils & Phase Monitor
Technicoat Evaporator & Condenser Coils & Coil Guard
Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Condenser & SS Drain Pan
Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & SS Drain Pan
Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils & SS Drain Pan
Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
Unitary Products
036-21058-005-A-0704
TABLE 2: PHYSICAL DATA
Models
Component
Evaporator
Blower
Evaporator
Coil
078
090
102
120
150
Blower, Centrifugal (Dia. X Wd. in.)
15 x 15
15 x 15
15 x 15
15 x 15
15 x 15
Motor, Standard (HP)
1-1/2
1-1/2
2
2
3
Motor, Optional (HP)
2
2
3
3
5
Rows
2
2
3
2
3
Fins per Inch
15
15
15
15
15
Height (in.)
30
32
24
40
40
Face Area (ft. each)
9.9
10.6
7.9
13.2
13.2
Propeller Dia. (in., each)
24
24
24
24
24
Motor (HP, each)
1/3
1/3
3/4
3/4
3/4
CFM, Nominal (each)
3400
3400
4400
4400
4400
Rows (each)
1
1
1
1
2
Fins per Inch
20
20
20
20
20
Height (in. each)
24
28
36
44
44
Face Area (ft.2 each)
7.9
9.2
11.9
14.5
14.5
System 1 (lb./oz.)
4/6
4/12
5/0
6/12
10/12
System 2 (lb./oz.)
4/0
4/6
5/4
6/12
11/0
Quantity
2
2
2
2
2
Type
Recip
Recip
Recip
Recip
Scroll
Size (Wd. x Ht. x Thickness in.)
25x20x2
25x20x2
25x20x2
25x20x2
25x20x2
Number Per Unit
4
4
4
4
4
2
Condenser
Fan
(2 per Unit)
Condenser
Coil
(2 per unit)
Refrigerant
Charge
Compressors
Air Filters
Unitary Products
13
036-21058-005-A-0704
TABLE 3: DM CAPACITY RATINGS
Cooling Capacities
ARI Ratings*
Size
(Tons)
CFM
Model
MBH
EER
IPLV
Gas Heat Capacity
Nominal
Sound
Gas Line
Electric Heat
Rating
Size
‡
Seasonal Temp.
Capacity
Input Output
(in. OD)
(dB)†
Efficiency Rise
(kW)
(MBH) (MBH)
(%)
(°F)
Cooling
Only
078
(6-1/2)
090
(7-1/2)
102
(8-1/2)
Electric
Heat
150
(12-1/2)
9.0
9.45
2600
84
-
-
-
-
-
9, 18, 24, 34
-
-
-
-
-
Gas Heat
-
120
96
80
20-50
3/4
Gas Heat
-
180
144
80
35-65
3/4
Cooling
Only
-
-
-
-
-
-
9, 18, 24, 34
-
-
-
-
-
Electric
Heat
86
9.0
10.15
3000
84
Gas Heat
-
120
96
80
15-45
3/4
Gas Heat
-
180
144
80
30-60
3/4
Cooling
Only
-
-
-
-
-
-
9, 18, 24, 34
-
-
-
-
-
Gas Heat
-
120
96
80
15-45
3/4
Gas Heat
-
180
144
80
10-40
3/4
Cooling
Only
-
-
-
-
-
-
9, 24, 34 54
-
-
-
-
-
Gas Heat
-
180
144
80
20-50
3/4
Gas Heat
-
240
192
80
35-65
3/4
Cooling
Only
-
-
-
-
-
-
9, 24, 34, 54
-
-
-
-
-
Gas Heat
-
180
144
80
10-40
3/4
Gas Heat
-
240
192
80
25-55
3/4
Electric
Heat
Electric
Heat
120
(10)
77
-
Electric
Heat
98
120
144
9.0
9.0
9.3
9.35
9.10
9.25
3000
90
4000
90
4500
90
* Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.
† Rated in accordance with ARI 270 standard.
‡ See Table 20.
TABLE 4: UNIT VOLTAGE LIMITATIONS
14
POWER RATING
MIN.
MAX.
208/230-3-60
187
252
460-3-60
432
504
575-3-60
540
630
Unitary Products
036-21058-005-A-0704
TABLE 5: COOLING CAPACITY 6-1/2 TON UNIT
Air On
Evap. Coil
CFM
1950
2275
2600
2925
3250
1950
2275
2600
2925
3250
1950
2275
2600
2925
3250
WB
(°F)
Temperature of Air on Condenser Coil 85°F
Tot.
Tot.
Cap.*
(MBH)
Input†
(kW)
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
87
80
71
66
91
83
74
69
94
87
77
72
95
88
77
73
96
89
78
74
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
73
66
64
54
76
68
67
56
78
71
69
58
78
70
69
58
78
70
69
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
62
51
67
42
63
52
68
43
63
52
69
43
64
53
70
44
65
54
71
44
Unitary Products
Temperature of Air on Condenser Coil 95°F
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Tot.
Tot.
Input†
(kW)
71
68
Cap.*
(MBH)
6.8
49
43
37
32
26
6.7
61
55
50
44
38
33
6.4
71
66
61
55
50
44
6.4
66
66
61
56
50
44
6.9
54
47
41
34
28
6.7
67
61
54
47
41
34
6.5
74
72
66
60
53
47
6.5
69
69
67
60
54
47
7.0
59
52
44
37
29
6.8
74
66
58
51
43
36
6.6
77
77
72
64
57
49
6.6
72
72
72
65
57
49
7.0
63
55
46
37
29
6.8
78
70
61
52
44
35
6.6
77
77
75
66
58
49
6.6
73
73
73
64
56
47
7.0
67
58
48
38
29
6.8
83
73
64
54
44
35
6.6
78
78
78
68
59
49
6.6
74
74
74
64
54
45
Temperature of Air on Condenser Coil 105°F
7.8
43
37
31
26
20
7.5
54
48
43
37
32
26
7.4
61
57
52
46
41
35
7.3
54
54
48
43
37
32
7.9
48
41
34
28
21
7.6
60
54
47
40
34
27
7.5
65
62
57
50
44
37
7.4
56
56
53
46
40
33
8.0
53
45
38
30
22
7.7
66
59
51
44
36
28
7.5
69
67
62
54
47
39
7.5
58
58
58
50
42
35
8.0
57
48
40
31
23
7.7
68
62
54
46
37
28
7.6
69
68
64
56
47
38
7.5
58
58
58
49
40
32
8.1
61
52
42
32
23
7.8
70
66
57
48
38
28
7.6
69
69
67
57
48
38
7.6
57
57
57
48
38
28
Temperature of Air on Condenser Coil 125°F
8.8
38
32
27
21
15
8.4
48
42
37
31
25
20
8.4
57
50
44
39
33
27
8.3
42
42
37
31
26
20
8.8
42
35
29
22
16
8.4
52
46
40
33
27
20
8.5
63
56
48
41
35
28
8.3
43
43
40
33
27
20
8.9
46
39
31
23
16
8.5
52
50
43
35
28
20
8.5
69
62
52
44
37
29
8.4
43
43
43
35
28
20
9.0
52
43
34
26
17
8.6
53
53
47
39
30
21
8.6
70
66
58
50
41
32
8.5
44
44
44
35
26
18
9.1
57
47
38
28
18
8.7
54
54
52
42
32
23
8.8
71
71
65
55
45
36
8.6
44
44
44
34
25
15
27
39
39
28
40
40
28
42
42
26
40
38
25
39
35
78
73
63
59
82
76
66
62
86
80
69
65
85
79
69
64
85
78
68
64
21
30
26
21
31
27
21
31
27
20
30
23
19
28
19
67
58
66
48
69
60
67
49
71
61
69
50
71
62
69
51
71
62
70
51
86
83
80
77
74
14
22
15
13
22
14
12
21
13
13
24
9
13
26
5
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
71
68
7.3
45
40
34
28
23
7.1
57
52
46
41
35
29
6.9
63
61
56
50
45
39
6.8
59
59
54
49
43
37
7.4
50
44
37
31
24
7.2
64
57
51
44
38
31
6.9
66
65
61
55
48
42
6.9
62
62
60
53
46
40
7.5
56
48
41
33
26
7.3
70
63
55
48
40
33
7.0
69
69
67
59
52
44
7.0
65
65
65
57
50
42
7.5
60
51
43
34
25
7.3
74
66
58
49
40
32
7.1
69
69
67
59
50
42
7.0
64
64
64
56
47
39
7.5
64
54
44
35
25
7.3
78
70
60
50
41
31
7.1
68
68
68
58
49
39
7.1
64
64
64
54
45
35
Temperature of Air on Condenser Coil 115°F
8.3
40
35
29
23
18
7.9
51
45
40
34
29
23
7.9
59
54
48
42
37
31
7.8
48
48
43
37
31
26
8.4
45
38
32
25
18
8.0
56
50
43
37
30
24
8.0
64
59
52
46
39
33
7.9
49
49
46
40
33
27
8.4
49
42
34
27
19
8.1
61
55
47
39
32
24
8.0
69
64
57
49
42
34
7.9
50
50
50
43
35
28
8.5
54
46
37
28
20
8.2
62
58
51
42
33
25
8.1
69
67
61
53
44
35
8.0
51
51
51
42
33
25
8.6
59
49
40
30
20
8.3
62
62
55
45
35
25
8.2
70
70
66
56
46
37
8.1
51
51
51
41
31
22
86
83
80
77
74
24
33
32
24
35
33
25
37
35
23
33
30
21
29
25
17
26
20
17
26
20
17
26
20
16
27
16
16
27
12
*
These capacities are gross ratings. For net
capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air
blower motor.
† These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
15
036-21058-005-A-0704
TABLE 6: COOLING CAPACITY 7-1/2 TON UNIT
Air On
Evap. Coil
CFM
2250
2625
3000
3375
3750
2250
2625
3000
3375
3750
2250
2625
3000
3375
3750
16
WB
(°F)
Temperature of Air on Condenser Coil 85°F
Tot.
Tot.
Cap.*
(MBH)
Input†
(kW)
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
98
90
83
79
100
92
85
81
102
94
87
83
103
95
88
84
104
96
88
84
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
85
77
70
67
87
79
72
69
90
82
74
72
90
82
74
72
91
82
74
72
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
73
62
57
55
75
64
59
56
78
66
61
58
78
66
61
58
78
66
61
58
Temperature of Air on Condenser Coil 95°F
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Tot.
Tot.
Input†
(kW)
71
68
Cap.*
(MBH)
7.9
58
51
45
39
32
7.7
71
65
59
52
46
39
7.5
83
78
71
65
59
52
7.4
79
79
73
67
61
54
7.9
63
55
48
40
33
7.8
78
70
62
55
47
40
7.6
85
82
76
69
61
53
7.5
81
81
78
71
63
55
8.0
68
60
51
42
33
7.8
84
75
66
57
49
40
7.6
87
87
81
72
63
54
7.6
83
83
83
74
65
57
8.1
73
63
53
43
33
7.9
89
79
69
59
49
39
7.7
88
88
84
74
64
54
7.6
84
84
84
74
64
54
8.1
77
66
55
43
32
8.0
94
82
71
60
49
38
7.7
88
88
87
76
64
53
7.7
84
84
84
73
62
51
Temperature of Air on Condenser Coil 105°F
8.9
52
46
39
33
27
8.7
65
59
52
46
39
33
8.5
70
69
62
56
50
43
8.5
67
67
61
55
49
42
9.0
58
50
43
35
27
8.8
71
64
56
49
41
34
8.5
72
71
68
60
52
45
8.5
69
69
66
59
51
44
9.1
63
55
46
37
28
8.8
78
69
61
52
43
35
8.6
74
74
73
64
55
46
8.6
72
72
72
63
54
45
9.2
68
58
48
38
28
8.9
80
73
63
53
43
33
8.7
74
74
74
64
54
44
8.7
72
72
72
62
52
42
9.3
72
61
50
39
27
9.0
82
77
66
55
44
32
8.8
74
74
74
63
52
41
8.8
72
72
72
61
50
38
Temperature of Air on Condenser Coil 125°F
10.0
47
40
34
27
21
9.6
58
52
45
39
33
26
9.5
57
57
52
45
39
32
9.5
55
55
48
42
36
29
10.1
52
45
37
30
22
9.7
64
58
50
42
35
27
9.6
59
59
57
49
42
34
9.6
56
56
53
46
38
31
10.2
58
49
41
32
23
9.8
66
63
54
46
37
28
9.7
61
61
61
53
45
36
9.7
58
58
58
49
41
32
10.3
63
53
43
33
23
9.9
66
66
57
47
37
27
9.8
61
61
61
52
42
32
9.8
58
58
58
48
38
28
10.4
67
56
45
34
22
10.0
66
66
60
49
38
27
9.9
61
61
61
50
39
27
9.9
58
58
58
47
36
25
33
46
48
32
46
48
31
46
48
29
44
44
26
42
40
91
84
76
73
94
87
78
76
96
89
81
78
97
90
81
78
97
90
81
79
27
37
36
26
37
36
26
38
37
24
34
32
21
30
27
79
69
63
61
81
71
65
63
84
74
67
65
84
74
68
65
84
74
68
65
86
83
80
77
74
20
26
23
20
27
23
19
27
23
17
22
18
15
16
14
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
71
68
8.4
55
49
42
36
29
8.2
68
62
56
49
43
36
8.0
76
74
68
61
55
49
7.9
73
73
68
62
55
49
8.5
60
53
45
38
30
8.3
75
67
60
52
45
37
8.0
78
77
73
65
58
50
8.0
76
76
73
66
58
50
8.6
66
57
48
40
31
8.3
81
73
64
55
46
38
8.1
81
81
78
69
60
52
8.1
78
78
78
69
61
52
8.6
70
60
50
40
30
8.4
86
76
66
56
46
36
8.2
81
81
80
70
60
50
8.2
78
78
78
68
58
49
8.7
75
63
52
41
30
8.5
90
80
69
58
46
35
8.3
81
81
81
70
59
48
8.2
79
79
79
67
56
45
Temperature of Air on Condenser Coil 115°F
9.5
49
43
37
30
24
9.2
62
55
49
42
36
30
9.0
63
63
57
51
44
38
9.0
61
61
55
48
42
36
9.6
55
47
40
32
25
9.2
68
61
53
46
38
30
9.1
65
65
62
55
47
39
9.1
63
63
60
52
45
37
9.7
61
52
43
34
26
9.3
74
66
58
49
40
31
9.1
67
67
67
59
50
41
9.2
65
65
65
56
47
39
9.7
65
55
45
35
25
9.4
74
70
60
50
40
30
9.2
68
68
68
58
48
38
9.2
65
65
65
55
45
35
9.8
70
58
47
36
25
9.5
74
74
63
52
41
30
9.3
68
68
68
57
45
34
9.3
65
65
65
54
43
32
86
83
80
77
74
30
42
42
29
42
43
29
43
43
27
40
39
24
36
34
23
31
29
23
32
30
23
32
30
20
28
25
18
23
20
*
These capacities are gross ratings. For net
capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air
blower motor.
† These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
Unitary Products
036-21058-005-A-0704
TABLE 7: COOLING CAPACITY 8-1/2 TON UNIT
Air On
Evap. Coil
CFM
2550
2975
3400
3825
4250
2550
2975
3400
3825
4250
2550
2975
3400
3825
4250
WB
(°F)
Temperature of Air on Condenser Coil 85°F
Tot.
Tot.
Cap.*
(MBH)
Input†
(kW)
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
113
105
93
90
118
109
96
94
122
113
100
97
123
114
101
98
125
115
102
99
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
98
87
77
76
101
90
80
79
105
93
83
81
107
95
84
83
109
96
86
84
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
84
69
63
62
87
71
65
63
89
73
67
65
90
74
68
66
92
75
69
67
Unitary Products
Temperature of Air on Condenser Coil 95°F
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Tot.
Tot.
Input†
(kW)
71
68
Cap.*
(MBH)
9.4
66
59
52
45
37
9.2
82
75
67
60
53
45
9.0
93
90
83
76
68
61
8.9
90
90
84
77
69
62
9.5
73
65
56
47
39
9.3
90
81
72
64
55
47
9.0
96
95
89
81
72
64
9.0
94
94
91
82
73
65
9.5
80
70
60
50
40
9.3
98
88
78
68
58
48
9.1
100 100
96
86
76
66
9.0
97
97
97
87
77
67
9.6
86
74
63
52
41
9.4
104
93
82
71
59
48
9.1
101 101
99
88
76
65
9.1
98
98
98
87
76
64
9.6
92
79
66
54
41
9.4
111
99
86
73
61
48
9.2
102 102 102
89
77
64
9.1
99
99
99
87
74
61
Temperature of Air on Condenser Coil 105°F
10.6
58
51
44
36
29
10.3
74
66
59
52
44
37
10.1
77
77
70
63
55
48
10.1
76
76
68
61
54
47
10.7
65
56
48
39
31
10.4
81
73
65
56
47
39
10.1
80
80
76
68
59
51
10.2
79
78
75
66
58
49
10.8
72
62
52
42
32
10.5
88
80
70
60
50
40
10.2
83
83
83
73
63
53
10.2
81
81
81
71
62
52
10.9
78
66
55
44
32
10.5
92
85
74
63
52
40
10.3
84
84
84
73
62
50
10.3
83
83
83
71
60
49
10.9
83
71
58
45
33
10.6
96
91
78
66
53
40
10.3
86
86
86
73
60
48
10.3
84
84
84
71
59
46
Temperature of Air on Condenser Coil 125°F
11.9
52
44
37
30
22
11.4
66
58
51
44
36
29
11.2
63
62
54
47
40
33
11.3
62
61
53
46
39
31
12.0
58
50
41
33
24
11.5
71
65
57
48
39
31
11.3
65
64
61
52
43
35
11.4
63
63
59
51
42
33
12.1
65
55
45
35
25
11.6
73
72
62
52
42
33
11.4
67
67
67
57
47
37
11.5
65
65
65
55
45
35
12.2
70
59
48
37
25
11.7
74
74
66
55
43
32
11.5
68
68
68
56
45
34
11.6
66
66
66
55
44
32
12.3
76
63
51
38
25
11.8
75
75
70
57
44
32
11.6
69
69
69
56
43
31
11.7
67
67
67
55
42
29
38
54
55
38
55
56
38
56
57
37
54
53
35
51
49
105
96
85
83
109
100
88
86
113
103
91
89
115
105
93
91
117
107
94
93
30
41
39
30
42
41
30
43
42
29
39
38
28
35
33
91
78
70
69
94
81
72
71
97
83
75
73
99
84
76
74
100
86
77
76
86
83
80
77
74
22
25
24
22
26
25
23
27
26
21
22
21
19
18
17
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
71
68
10.0
62
54
47
40
33
9.8
78
70
63
56
48
41
9.5
85
85
77
70
63
56
9.5
83
83
76
69
61
54
10.1
68
60
51
43
34
9.9
86
77
69
60
51
43
9.6
88
88
84
76
67
59
9.5
86
86
83
74
66
57
10.2
75
65
55
46
36
9.9
94
84
74
64
54
44
9.7
91
91
91
81
71
61
9.6
89
89
89
79
70
60
10.2
81
70
59
47
36
10.0
100
90
78
67
56
44
9.7
93
93
93
81
70
59
9.6
91
91
91
80
68
57
10.2
87
75
62
49
37
10.0
107
95
83
70
57
45
9.7
94
94
94
82
69
56
9.7
93
93
93
80
67
55
Temperature of Air on Condenser Coil 115°F
11.3
55
48
40
33
26
10.9
70
62
55
48
40
33
10.6
70
69
62
55
48
40
10.7
69
68
61
54
46
39
11.4
62
53
45
36
27
11.0
76
69
61
52
43
35
10.7
72
72
68
60
51
43
10.8
71
71
67
58
50
41
11.5
68
59
49
39
29
11.1
83
76
66
56
46
36
10.8
75
75
75
65
55
45
10.9
73
73
73
63
53
44
11.5
74
63
51
40
29
11.1
84
81
70
59
48
36
10.9
76
76
76
65
53
42
10.9
74
74
74
63
52
41
11.6
80
67
54
42
29
11.2
86
86
74
61
49
36
10.9
77
77
77
65
52
39
11.0
76
76
76
63
50
38
86
83
80
77
74
34
48
47
34
50
48
34
51
50
33
48
46
32
44
42
26
33
32
26
34
33
27
35
34
25
31
29
23
27
25
*
These capacities are gross ratings. For net
capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air
blower motor.
† These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
17
036-21058-005-A-0704
TABLE 8: COOLING CAPACITY 10 TON UNIT
Air On
Evap. Coil
CFM
3000
3500
4000
4500
5000
3000
3500
4000
4500
5000
3000
3500
4000
4500
5000
18
WB
(°F)
Temperature of Air on Condenser Coil 85°F
Tot.
Tot.
Cap.*
(MBH)
Input†
(kW)
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
132
124
116
110
135
127
119
112
138
130
121
115
141
132
124
117
144
135
126
119
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
117
107
97
98
121
110
100
102
124
113
103
105
127
116
106
107
130
119
108
110
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
101
87
79
83
105
90
81
86
108
92
84
88
112
96
87
91
115
99
89
94
Temperature of Air on Condenser Coil 95°F
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Tot.
Tot.
Input†
(kW)
71
68
Cap.*
(MBH)
11.0
76
68
59
50
42
10.7
96
87
79
70
62
53
10.5
115 106
98
89
81
72
10.3
110 109 101
92
83
75
11.1
83
73
63
53
43
10.8
104
94
84
74
64
54
10.6
118 114 105
95
84
74
10.4
112 112 108
98
87
77
11.2
91
79
67
56
44
10.9
113 101
90
78
66
55
10.7
121 121 111 100
88
76
10.5
115 115 115 103
91
80
11.3
98
85
71
58
45
11.0
122 108
95
82
69
55
10.7
124 124 118 105
92
78
10.5
117 117 117 104
90
77
11.3
105
90
75
60
45
11.0
130 116 101
86
71
56
10.8
126 126 125 110
95
80
10.6
119 119 119 105
90
75
Temperature of Air on Condenser Coil 105°F
12.4
70
62
53
45
36
12.0
89
80
71
63
54
46
11.6
97
94
85
77
68
60
11.7
98
96
88
79
71
62
12.5
78
68
58
48
38
12.1
98
88
78
68
57
47
11.7
100
99
93
83
73
62
11.8
102 100
95
85
75
65
12.7
86
74
63
51
39
12.2
107
96
84
72
61
49
11.9
103 103 100
89
77
65
11.9
105 105 103
91
80
68
12.8
93
79
66
53
39
12.3
112 102
88
75
62
49
12.0
106 106 104
91
77
64
12.0
107 107 106
93
80
66
12.9
99
84
69
54
40
12.4
117 108
93
78
63
48
12.1
108 108 107
93
78
63
12.1
110 110 110
95
80
65
Temperature of Air on Condenser Coil 125°F
13.8
64
55
46
38
29
13.0
80
72
63
55
46
38
12.7
79
79
74
65
57
48
12.9
83
82
74
65
56
48
14.0
71
61
51
40
30
13.2
89
79
69
59
49
39
12.9
81
81
80
70
60
50
13.0
86
85
80
70
60
50
14.1
78
66
55
43
31
13.3
92
86
75
63
51
40
13.0
84
84
84
75
64
52
13.1
88
88
87
75
63
52
14.2
86
72
59
46
32
13.4
96
94
80
67
54
41
13.1
87
87
87
75
62
49
13.2
91
91
90
77
64
51
14.4
93
78
63
48
33
13.6
99
99
86
71
56
41
13.3
89
89
89
75
60
45
13.4
94
94
94
79
65
50
45
64
66
44
64
67
43
65
68
42
65
64
41
65
60
125
116
106
106
129
120
110
109
133
124
113
113
135
126
115
115
138
128
117
117
37
51
54
37
52
55
37
54
56
35
51
53
33
48
50
109
97
88
91
113
100
91
94
116
103
94
97
119
106
96
99
123
109
99
102
86
83
80
77
74
29
40
39
29
40
40
28
40
40
27
35
37
27
30
35
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
71
68
11.7
74
65
57
48
40
11.4
93
84
75
67
58
50
11.1
106 100
91
82
74
65
11.1
106 103
95
86
78
69
11.8
82
72
62
52
41
11.5
102
92
82
72
62
52
11.2
110 106
99
89
79
69
11.2
109 108 103
93
83
73
12.0
90
78
67
55
43
11.7
112 100
89
77
65
54
11.3
113 113 107
95
84
72
11.3
113 113 111 100
88
76
12.0
96
83
70
56
43
11.7
119 106
92
79
66
53
11.4
115 115 112
98
85
72
11.4
115 115 114 101
88
74
12.1
102
87
72
58
43
11.8
126 111
96
81
67
52
11.5
117 117 116 101
86
71
11.5
117 117 117 102
87
72
Temperature of Air on Condenser Coil 115°F
13.1
67
58
50
41
33
12.5
85
76
67
59
50
42
12.2
88
88
80
71
62
54
12.3
91
89
81
72
64
55
13.2
75
64
54
44
34
12.6
94
83
73
63
53
43
12.3
91
91
87
76
66
56
12.4
94
93
88
78
67
57
13.4
82
70
59
47
35
12.8
103
91
79
68
56
44
12.4
94
94
94
82
70
59
12.5
97
97
95
83
71
60
13.5
89
76
63
49
36
12.9
106
98
84
71
58
45
12.5
96
96
96
83
70
56
12.6
99
99
98
85
72
59
13.6
96
81
66
51
37
13.0
109 104
90
75
60
45
12.7
99
99
99
84
69
54
12.7
102 102 102
87
72
57
86
83
80
77
74
41
57
61
42
58
63
42
60
65
39
58
61
37
57
57
33
45
46
33
46
47
33
47
48
31
43
45
30
39
42
*
These capacities are gross ratings. For net
capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air
blower motor.
† These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
Unitary Products
036-21058-005-A-0704
TABLE 9: COOLING CAPACITY 12-1/2 TON UNIT
Air On
Evap. Coil
CFM
3750
4375
5000
5625
6250
3750
4375
5000
5625
6250
3750
4375
5000
5625
6250
WB
(°F)
Temperature of Air on Condenser Coil 85°F
Tot.
Tot.
Cap.*
(MBH)
Input†
(kW)
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
154
152
145
144
158
156
148
147
161
159
151
150
161
158
151
150
160
158
150
149
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
144
139
130
130
148
143
134
134
152
147
137
137
151
145
136
136
149
144
134
135
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
131
124
114
114
136
128
117
118
140
132
121
121
137
129
119
119
134
127
117
117
Unitary Products
Temperature of Air on Condenser Coil 95°F
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Tot.
Tot.
Input†
(kW)
71
68
Cap.*
(MBH)
12.0
93
82
71
61
50
39
11.8
122 112 101
90
79
69
11.6
145 138 128 117 106
96
11.6
144 143 133 122 111 101
12.0
101
89
76
63
51
38
11.8
133 120 107
95
82
70
11.7
148 145 136 123 111
98
11.7
147 147 141 129 116 104
12.1
110
95
81
66
52
37
11.8
143 129 114
99
85
70
11.7
151 151 144 130 115 101
11.7
150 150 150 136 121 106
12.1
116
99
83
66
49
33
11.9
150 133 117 100
83
67
11.7
151 151 147 131 114
97
11.7
150 150 150 133 116 100
12.1
122 103
84
66
47
28
11.9
156 138 119 100
82
63
11.7
150 150 150 132 113
94
11.7
149 149 149 130 112
93
Temperature of Air on Condenser Coil 105°F
15.1
88
77
66
56
45
34
14.7
117 106
96
85
74
63
14.5
130 126 115 104
94
83
14.5
130 128 117 106
96
85
15.1
98
85
72
60
47
34
14.8
129 117 104
91
79
66
14.6
134 131 125 113 100
87
14.6
134 132 127 114 102
89
15.2
107
93
78
63
49
34
14.9
141 127 112
98
83
68
14.6
137 137 135 121 106
91
14.7
137 137 137 123 108
93
15.3
113
96
80
63
47
30
14.9
142 131 115
98
82
65
14.7
136 136 135 118 102
85
14.7
136 136 136 119 103
86
15.3
119 100
82
63
44
26
14.9
144 136 117
99
80
61
14.7
134 134 134 116
97
79
14.7
135 135 135 116
97
79
Temperature of Air on Condenser Coil 125°F
18.3
81
71
60
49
39
28
17.8
111 100
90
79
68
58
17.5
114 110 100
89
78
68
17.6
114 109
98
87
77
66
18.4
92
80
67
54
42
29
18.0
124 113 100
88
75
62
17.6
117 116 112
99
86
74
17.8
118 115 110
97
85
72
18.6
103
89
74
60
45
30
18.2
132 125 111
96
81
67
17.8
121 121 121 109
94
80
18.0
121 121 121 107
92
78
18.7
108
92
75
58
42
25
18.2
129 129 112
95
79
62
17.9
119 119 119 103
87
70
18.0
119 119 119 102
86
69
18.8
113
95
76
57
39
20
18.3
127 127 113
95
76
58
18.0
117 117 117
98
79
61
18.1
117 117 117
98
79
61
29
58
85
90
26
57
85
91
22
56
86
92
16
50
81
83
10
45
76
74
151
147
138
138
155
150
142
142
158
154
145
145
157
153
144
144
157
152
143
143
24
53
72
74
22
53
75
77
20
54
77
79
13
48
68
69
7
43
60
60
138
131
122
122
142
135
126
126
146
139
129
129
144
137
127
127
142
135
125
126
86
83
80
77
74
17
47
57
55
17
50
61
59
16
52
65
63
9
46
53
53
2
39
42
42
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
71
68
13.4
91
80
70
59
48
38
13.1
120 109
98
88
77
66
13.0
138 134 123 112 101
91
13.0
138 137 126 116 105
94
13.5
100
87
75
62
50
37
13.2
131 118 106
93
80
68
13.0
142 139 132 119 107
94
13.0
142 141 136 123 111
98
13.5
109
95
80
65
51
36
13.2
142 128 113
98
84
69
13.1
145 145 141 126 112
97
13.1
145 145 145 131 116 101
13.5
115
99
82
66
49
32
13.2
147 133 116 100
83
66
13.1
144 144 142 126 109
92
13.1
144 144 144 128 111
94
13.5
122 103
84
66
47
28
13.2
152 138 119 101
82
63
13.1
143 143 143 125 106
88
13.0
143 143 143 125 106
88
Temperature of Air on Condenser Coil 115°F
16.7
85
74
63
53
42
31
16.2
114 103
93
82
71
61
16.0
122 118 107
97
86
75
16.1
122 118 108
97
86
75
16.8
95
82
70
57
44
32
16.4
127 115 102
89
77
64
16.1
126 124 118 106
93
80
16.2
126 124 118 106
93
81
16.9
105
91
76
61
47
32
16.5
139 126 111
97
82
68
16.2
129 129 129 115 100
85
16.3
129 129 129 115 100
86
17.0
111
94
77
61
44
28
16.6
137 130 113
97
80
64
16.3
127 127 127 111
94
78
16.4
127 127 127 111
94
78
17.0
116
97
79
60
42
23
16.6
135 134 115
97
78
59
16.3
125 125 125 107
88
70
16.4
126 126 126 107
88
70
86
83
80
77
74
27
56
80
84
24
55
81
85
22
55
83
87
16
50
76
78
10
45
69
69
21
50
65
65
19
51
68
68
18
53
71
71
11
47
61
61
4
41
51
51
*
These capacities are gross ratings. For net
capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air
blower motor.
† These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
19
036-21058-005-A-0704
TABLE 10: ELECTRICAL DATA DM078 (6-1/2 TON) STD EFFICIENCY W/O PWRD CONVENIENCE OUTLET
MCA
Min. Circuit
Supply
Pwr
Pwr
w/Power
Ampacity
Blower
Exh Conv
Electric Heater Actual Heater
Exhaust
Voltage
(Amps)
Motor FLA Motor Outlet
KW Amps
Model No.
(Amps)
RLA
LRA
FLA
1.5
2
1.5
2
1.5
2
FLA FLA
ea.
ea.
ea.
HP
HP
HP
HP
HP
HP
None
--38.0
40.0 43.5 45.5
2TP04520925
6.8
18.9
38.0
40.0 43.5 45.5
12.8 110.0
1.5
6.2
8.2
5.5
0.0
208
2TP04521825
13.5
37.5
54.6
57.1 61.5 64.0
2TP04522425
18
50.0
70.2
72.7 77.1 79.6
2TP04523625
25.5
70.8
96.2
98.7 103.1 105.6
None
--38.0
40.0 43.5 45.5
2TP04520925
9
21.7
38.0
40.0 43.5 45.5
12.8 110.0
1.5
6.2
8.2
5.5
0.0
230
2TP04521825
18
43.3
61.9
64.4 68.8 71.3
2TP04522425
24
57.7
79.9
82.4 86.8 89.3
2TP04523625
34
81.8 110.0 112.5 116.9 119.4
None
--20.7
21.7 22.9 23.9
2TP04520946
9
11.3
20.7
21.7 22.9 23.9
460
7.1
54.0
0.8
3.1
4.1
2.2
0.0
2TP04521846
18
22.6
30.9
32.2 33.7 34.9
2TP04522446
24
30.1
40
41.2 42.7
44
2TP04523646
34
42.7
55
56.2 57.7
59
None
--15.1
16.3 16.9 18.1
2TP04520958
9
9.0
15.1
16.3 16.9 18.1
575
5.1
44.0
0.6
2.4
3.6
1.8
0.0
2TP04521858
18
18.1
24.7
26.2 26.9 28.4
2TP04522458
24
24.1
31.9
33.4 34.1 35.6
2TP04523658
34
34.1
43.9
45.4 46.1 47.6
*
Maximum HACR breaker of the same AMP size is applicable.
OD Fan
Compressors
Motors
Max
Max Fuse* Size
Fuse*
w/Power
Size
Exhaust
(Amps)
(Amps)
1.5
2
1.5
2
HP HP
HP
HP
50 50
50
50
50 50
50
50
60 60
70
70
80 80
80
80
100 100 110
110
50 50
50
50
50 50
50
50
70 70
70
80
80 90
90
90
110 125 125
125
25 25
25
30
25 25
25
30
35 35
35
35
40 45
45
45
60 60
60
60
20 20
20
20
20 20
20
20
25 30
30
30
35 35
35
40
45 50
50
50
TABLE 11: ELECTRICAL DATA DM078 (6-1/2 TON) STD EFFICIENCY WITH PWRD CONVENIENCE OUTLET
Max
MCA
Max Fuse* Size
Supply
Pwr
Pwr
Min. Circuit
Fuse*
w/Power
w/Power
Blower
Exh Conv
Ampacity
Electric Heater Actual Heater
Size
Exhaust
Exhaust
Voltage
Motor FLA Motor Outlet
(Amps)
KW Amps
Model No.
(Amps)
(Amps)
(Amps)
RLA
LRA
FLA
1.5
2
1.5
2
1.5
2
1.5
2
1.5
2
FLA FLA
ea.
ea.
ea.
HP
HP
HP
HP
HP
HP HP HP
HP
HP
None
--48.0
50.0 53.5 55.5 60 60
60
60
2TP04520925
6.8
18.9
48.0
50.0 53.5 55.5 60 60
60
60
12.8 110.0
208
1.5
6.2
8.2
5.5
10.0
2TP04521825
13.5
37.5
67.1
69.6 74.0 76.5 70 70
80
80
2TP04522425
18
50.0
82.7
85.2 89.6 92.1 90 90
90
100
2TP04523625
25.5
70.8 108.7 111.2 115.6 118.1 110 125 125
125
None
--48.0
50.0 53.5 55.5 60 60
60
60
2TP04520925
9
21.7
48.0
50.0 54.2 56.7 60 60
60
60
230
12.8 110.0
1.5
6.2
8.2
5.5
10.0
2TP04521825
18
43.3
74.4
76.9 81.3 83.8 80 80
90
90
2TP04522425
24
57.7
92.4
94.9 99.3 101.8 100 100 100
110
2TP04523625
34
81.8 122.5 125.0 129.4 131.9 125 125 150
150
None
--25.7
26.7 27.9 28.9 30 30
30
35
2TP04520946
9
11.3
25.7
26.7 27.9 28.9 30 30
30
35
460
7.1
54.0
0.8
3.1
4.1
2.2
5.0
2TP04521846
18
22.6
37.2
38.4 39.9 41.2 40 40
40
45
2TP04522446
24
30.1
46.2
47.5
49
50.2 50 50
50
60
2TP04523646
34
42.7
61.2
62.5
64
65.2 70 70
70
70
None
--19.1
20.3 20.9 22.1 20 25
25
25
2TP04520958
9
9.0
19.1
20.3 21.1 22.6 20 25
25
25
575
5.1
44.0
0.6
2.4
3.6
1.8
4.0
2TP04521858
18
18.1
29.7
31.2 31.9 33.4 30 35
35
35
2TP04522458
24
24.1
36.9
38.4 39.1 40.6 40 40
40
45
2TP04523658
34
34.1
48.9
50.4 51.1 52.6 50 60
60
60
*
Maximum HACR breaker of the same AMP size is applicable.
Compressors
20
OD Fan
Motors
Unitary Products
036-21058-005-A-0704
TABLE 12: ELECTRICAL DATA DM090 (7-1/2 TON) STD EFFICIENCY W/O PWRD CONVENIENCE OUTLET
MCA
Pwr
Min. Circuit
Supply
Pwr
w/Power
Ampacity
Blower
Exh Conv
Electric Heater Actual Heater
Exhaust
(Amps)
Voltage
Motor FLA Motor Outlet
Model No.
KW
Amps
(Amps)
RLA
LRA
FLA
1.5
2
1.5
2
1.5
2
FLA
FLA
ea.
ea.
ea.
HP
HP
HP
HP
HP
HP
None
--39.6
41.6 45.1 47.1
2TP04520925
6.8
18.9
39.6
41.6 45.1 47.1
208
13.5 110.0
1.5
6.2
8.2
5.5
0.0
2TP04521825
13.5
37.5
54.6
57.1 61.5 64.0
2TP04522425
18
50.0
70.2
72.7 77.1 79.6
2TP04523625
25.5
70.8
96.2
98.7 103.1 105.6
None
--39.6
41.6 45.1 47.1
2TP04520925
9
21.7
39.6
41.6 45.1 47.1
230
13.5 110.0
1.5
6.2
8.2
5.5
0.0
2TP04521825
18
43.3
61.9
64.4 68.8 71.3
2TP04522425
24
57.7
79.9
82.4 86.8 89.3
2TP04523625
34
81.8 110.0 112.5 116.9 119.4
None
--20.7
21.7 22.9 23.9
2TP04520946
9
11.3
20.7
21.7 22.9 23.9
460
7.1
54.0
0.8
3.1
4.1
2.2
0.0
2TP04521846
18
22.6
30.9
32.2 33.7 34.9
2TP04522446
24
30.1
40
41.2 42.7
44
2TP04523646
34
42.7
55
56.2 57.7
59
None
--15.8
17
17.6 18.8
2TP04520958
9
9.0
15.8
17
17.6 18.8
5.4
44.0
0.6
2.4
3.6
1.8
0.0
575
2TP04521858
18
18.1
24.7
26.2 26.9 28.4
2TP04522458
24
24.1
31.9
33.4 34.1 35.6
2TP04523658
34
34.1
43.9
45.4 46.1 47.6
*
Maximum HACR breaker of the same AMP size is applicable.
Compressors
OD Fan
Motors
Max
Max Fuse* Size
Fuse*
w/Power
Size
Exhaust
(Amps)
(Amps)
1.5
2
1.5
2
HP HP
HP
HP
50 50
50
60
50 50
50
60
60 60
70
70
80 80
80
80
100 100
110
110
50 50
50
60
50 50
50
60
70 70
70
80
80 90
90
90
110 125
125
125
25 25
25
30
25 25
25
30
35 35
35
35
40 45
45
45
60 60
60
60
20 20
20
20
20 20
20
20
25 30
30
30
35 35
35
40
45 50
50
50
TABLE 13: ELECTRICAL DATA DM090 (7-1/2 TON) STD EFFICIENCY WITH PWRD CONVENIENCE OUTLET
Max
Max Fuse* Size
MCA
Supply
Pwr
Pwr
Min. Circuit
Fuse*
w/Power
w/Power
Ampacity
Blower
Exh Conv
Electric Heater Actual Heater
Size
Exhaust
Exhaust
(Amps)
Voltage
Motor FLA Motor Outlet
KW Amps
Model No.
(Amps)
(Amps)
(Amps)
RLA
LRA
FLA
1.5
2
1.5
2
1.5
2
1.5
2
1.5
2
FLA FLA
ea.
ea.
ea.
HP
HP
HP
HP
HP
HP HP HP
HP
HP
None
--49.6
51.6 55.1 57.1 60 60
60
70
2TP04520925
6.8
18.9
49.6
51.6 55.1 57.1 60 60
60
70
5.5
10.0
208
13.5 110.0
1.5
6.2
8.2
2TP04521825
13.5
37.5
67.1
69.6 74.0 76.5 70 70
80
80
2TP04522425
18
50.0
82.7
85.2 89.6 92.1 90 90
90
100
2TP04523625
25.5
70.8 108.7 111.2 115.6 118.1 110 125 125
125
None
--49.6
51.6 55.1 57.1 60 60
60
70
2TP04520925
9
21.7
49.6
51.6 55.1 57.1 60 60
60
70
8.2
5.5
10.0
13.5 110.0
1.5
6.2
230
2TP04521825
18
43.3
74.4
76.9 81.3 83.8 80 80
90
90
2TP04522425
24
57.7
92.4
94.9 99.3 101.8 100 100 100
110
2TP04523625
34
81.8 122.5 125.0 129.4 131.9 125 125 150
150
None
--25.7
26.7 27.9 28.9 30 30
30
35
2TP04520946
9
11.3
25.7
26.7 27.9 28.9 30 30
30
35
7.1
54.0
0.8
3.1
4.1
2.2
5.0
460
2TP04521846
18
22.6
37.2
38.4 39.9 41.2 40 40
40
45
2TP04522446
24
30.1
46.2
47.5
49
50.2 50 50
50
60
2TP04523646
34
42.7
61.2
62.5
64
65.2 70 70
70
70
None
--19.8
21
21.6 22.8 25 25
25
25
2TP04520958
9
9.0
19.8
21
21.6 22.8 25 25
25
25
5.4
44.0
0.6
2.4
3.6
1.8
4.0
575
2TP04521858
18
18.1
29.7
31.2 31.9 33.4 30 35
35
35
2TP04522458
24
24.1
36.9
38.4 39.1 40.6 40 40
40
45
2TP04523658
34
34.1
48.9
50.4 51.1 52.6 50 60
60
60
*
Maximum HACR breaker of the same AMP size is applicable.
Compressors
Unitary Products
OD Fan
Motors
21
036-21058-005-A-0704
TABLE 14: ELECTRICAL DATA DM102 (8-1/2 TON) STD EFFICIENCY W/O PWRD CONVENIENCE OUTLET
MCA
Max
Max Fuse* Size
Supply
Pwr
Min. Circuit
Pwr
w/Power
Fuse*
w/Power
Blower
Ampacity
Exh Conv
Electric Heater Actual Heater
Exhaust
Size
Exhaust
Voltage
Motor FLA Motor Outlet
(Amps)
Amps
KW
Model No.
(Amps)
(Amps)
(Amps)
RLA
LRA
FLA
2
3
2
3
2
3
2
3
2
3
FLA
FLA
ea.
ea.
ea.
HP
HP
HP
HP
HP
HP
HP HP
HP
HP
None
--51.2
53.9 56.7 59.4 60 60
70
70
2TP04520925
6.8
18.9
51.2
53.9 56.7 59.4 60 60
70
70
16.0 137.0
3.5
8.2 10.9
5.5
0.0
208
2TP04521825
13.5
37.5
57.1
60.5 64.0 67.3 60 70
70
70
2TP04522425
18
50.0
72.7
76.1 79.6 83.0 80 80
80
90
2TP04523625
25.5
70.8
98.7 102.1 105.6 109.0 100 110 110
110
None
--51.2
53.9 56.7 59.4 60 60
70
70
2TP04520925
9
21.7
51.2
53.9 56.7 59.4 60 60
70
70
5.5
0.0
16.0 137.0
3.5
8.2 10.9
230
2TP04521825
18
43.3
64.4
67.8 71.3 74.6 70 70
80
80
2TP04522425
24
57.7
82.4
85.8 89.3 92.7 90 90
90
100
2TP04523625
34
81.8 112.5 115.9 119.4 122.7 125 125 125
125
None
--26
27.2 28.2 29.4 30 35
35
35
2TP04520946
9
11.3
26
27.2 28.2 29.4 30 35
35
35
8.3
69.0
1.6
4.1
5.3
2.2
0.0
460
2TP04521846
18
22.6
32.2
33.7 34.9 36.4 35 35
35
40
2TP04522446
24
30.1
41.2
42.7
44
45.5 45 45
45
50
2TP04523646
34
42.7
56.2
57.7
59
60.5 60 60
60
70
None
--20.6
21.1 22.4 22.9 25 25
25
25
2TP04520958
9
9.0
20.6
21.1 22.4 22.9 25 25
25
25
6.4
58.0
1.3
3.6
4.1
1.8
0.0
575
2TP04521858
18
18.1
26.2
26.8 28.4
29
30 30
30
30
2TP04522458
24
24.1
33.4
34
35.6 36.2 35 35
40
40
2TP04523658
34
34.1
45.4
46
47.6 48.3 50 50
50
50
Maximum HACR breaker of the same AMP size is applicable.
*
Compressors
OD Fan
Motors
TABLE 15: ELECTRICAL DATA DM102 (8-1/2 TON) STD EFFICIENCY WITH PWRD CONVENIENCE OUTLET
MCA
Max
Max Fuse* Size
Supply
Pwr
Pwr
Min. Circuit
w/Power
Fuse*
w/Power
Blower
Exh Conv
Ampacity
Electric Heater Actual Heater
Exhaust
Size
Exhaust
Voltage
Motor FLA Motor Outlet
(Amps)
KW
Model No.
Amps
(Amps)
(Amps)
(Amps)
RLA
LRA
FLA
2
3
2
3
2
3
2
3
2
3
FLA
FLA
ea.
ea.
ea.
HP
HP
HP
HP
HP
HP
HP HP
HP
HP
None
--61.2
63.9 66.7 69.4 70 70
80
80
2TP04520925
6.8
18.9
61.2
63.9 66.7 69.4 70 70
80
80
3.5
8.2 10.9
5.5
10.0
16.0 137.0
208
2TP04521825
13.5
37.5
69.6
73.0 76.5 79.8 70 80
80
80
2TP04522425
18
50.0
85.2
88.6 92.1 95.5 90 90
100
100
2TP04523625
25.5
70.8 111.2 114.6 118.1 121.5 125 125 125
125
None
--61.2
63.9 66.7 69.4 70 70
80
80
2TP04520925
9
21.7
61.2
63.9 66.7 69.4 70 70
80
80
16.0 137.0
3.5
8.2 10.9
5.5
10.0
230
2TP04521825
18
43.3
76.9
80.3 83.8 87.1 80 90
90
90
2TP04522425
24
57.7
94.9
98.3 101.8 105.2 100 100 110
110
2TP04523625
34
81.8 125.0 128.4 131.9 135.2 125 150 150
150
None
--31
32.2 33.2 34.4 35 40
40
40
2TP04520946
9
11.3
31
32.2 33.2 34.4 35 40
40
40
69.0
1.6
4.1
5.3
8.3
2.2
5.0
460
2TP04521846
18
22.6
38.4
39.9 41.2 42.7 40 40
45
45
2TP04522446
24
30.1
47.5
49
50.2 51.7 50 50
60
60
2TP04523646
34
42.7
62.5
64
65.2 66.7 70 70
70
70
None
--24.6
25.1 26.4 26.9 30 30
30
30
2TP04520958
9
9.0
24.6
25.1 26.4 26.9 30 30
30
30
6.4
58.0
1.3
3.6
4.1
1.8
4.0
575
2TP04521858
18
18.1
31.2
31.8 33.4
34
35 35
35
35
2TP04522458
24
24.1
38.4
39
40.6 41.2 40 40
45
45
2TP04523658
34
34.1
50.4
51
52.6 53.3 60 60
60
60
Maximum HACR breaker of the same AMP size is applicable.
*
OD Fan
Compressors
Motors
22
Unitary Products
036-21058-005-A-0704
TABLE 16: ELECTRICAL DATA DM120 (10 TON) STD EFFICIENCY W/O PWRD CONVENIENCE OUTLET
Supply
Pwr
Min. Circuit
Pwr
Blower
Ampacity
Exh Conv
Electric Heater Actual Heater
Voltage
Motor FLA Motor Outlet
(Amps)
KW
Amps
Model No.
RLA
LRA
FLA
2
3
2
3
FLA FLA
ea.
ea.
ea.
HP
HP
HP
HP
None
--51.9
54.6
2TP04521825
13.5
37.5
57.1
60.5
16.3 150.0
3.5
8.2 10.9
5.5
0.0
208
2TP04522425
18
50.0
72.7
76.1
2TP04523625
25.5
70.8
98.7 102.1
2TP04525425
40.6 112.7 151.1 154.5
None
--51.9
54.6
2TP04521825
18
43.3
64.4
67.8
16.3 150.0
3.5
8.2 10.9
5.5
0.0
230
2TP04522425
24
57.7
82.4
85.8
2TP04523625
34
81.8 112.5 115.9
2TP04525425
129.9 140.2 143.5
54
None
--33.2
34.4
2TP04521846
18
22.6
33.2
34.4
11.5
75.0
1.6
4.1
5.3
2.2
0.0
460
2TP04522446
24
30.1
41.2
42.7
2TP04523646
34
42.7
56.2
57.7
2TP04525446
54
67.8
70.1
71.6
None
--22.2
22.7
2TP04521858
18
18.1
26.2
26.8
7.1
62.0
1.3
3.6
4.1
1.8
0.0
575
2TP04522458
24
24.1
33.4
34
2TP04523658
34
34.1
45.4
46
2TP04525458
54
54.2
56.5
57.1
Maximum HACR breaker of the same AMP size is applicable.
*
Compressors
OD Fan
Motors
MCA
w/Power
Exhaust
(Amps)
2
3
HP
HP
57.4 60.1
64.0 67.3
79.6 83.0
105.6 109.0
158.0 161.4
57.4 60.1
71.3 74.6
89.3 92.7
119.4 122.7
147.0 150.4
35.4 36.6
35.4 36.6
44
45.5
59
60.5
72.8 74.3
24
24.5
28.4
29
35.6 36.2
47.6 48.3
58.7 59.3
Max
Max Fuse* Size
Fuse*
w/Power
Size
Exhaust
(Amps)
(Amps)
2
3
2
3
HP HP
HP
HP
60 70
70
70
60 70
70
70
80 80
80
90
100 110 110
110
175 175 175
175
60 70
70
70
70 70
80
80
90 90
90
100
125 125 125
125
150 175 175
175
40 45
45
45
40 45
45
45
45 45
45
50
60 60
60
70
80 80
80
80
25 25
30
30
30 30
30
30
35 35
40
40
50 50
50
50
70 70
70
70
TABLE 17: ELECTRICAL DATA DM120 (10 TON) STD EFFICIENCY WITH PWRD CONVENIENCE OUTLET
Supply
Pwr
Pwr
Blower
Exh Conv
Electric Heater Actual Heater
Voltage
Motor FLA Motor Outlet
KW
Model No.
Amps
RLA
LRA
FLA
2
3
FLA
FLA
ea.
ea.
ea.
HP
HP
None
--2TP04521825
13.5
37.5
3.5
8.2 10.9
5.5
10.0
16.3 150.0
208
2TP04522425
18
50.0
2TP04523625
25.5
70.8
2TP04525425
40.6
112.7
None
--2TP04521825
18
43.3
16.3 150.0
3.5
8.2 10.9
5.5
10.0
230
2TP04522425
24
57.7
2TP04523625
34
81.8
2TP04525425
129.9
54
None
--2TP04521846
18
22.6
75.0
1.6
4.1
5.3
11.5
2.2
5.0
460
2TP04522446
24
30.1
2TP04523646
34
42.7
2TP04525446
54
67.8
None
--2TP04521858
18
18.1
7.1
62.0
1.3
3.6
4.1
1.8
4.0
575
2TP04522458
24
24.1
2TP04523658
34
34.1
2TP04525458
54
54.2
Maximum HACR breaker of the same AMP size is applicable.
*
OD Fan
Compressors
Motors
Unitary Products
Min. Circuit
Ampacity
(Amps)
2
HP
61.9
69.6
85.2
111.2
163.6
61.9
76.9
94.9
125.0
152.7
38.2
38.4
47.5
62.5
76.3
26.2
31.2
38.4
50.4
61.5
3
HP
64.6
73.0
88.6
114.6
167.0
64.6
80.3
98.3
128.4
156.0
39.4
39.9
49
64
77.8
26.7
31.8
39
51
62.1
MCA
w/Power
Exhaust
(Amps)
2
3
HP
HP
67.4 70.1
76.5 79.8
92.1 95.5
118.1 121.5
170.5 173.9
67.4 70.1
83.8 87.1
101.8 105.2
131.9 135.2
159.5 162.9
40.4 41.6
41.2 42.7
50.2 51.7
65.2 66.7
79.1 80.6
28
28.5
33.4
34
40.6 41.2
52.6 53.3
63.7 64.3
Max
Max Fuse* Size
Fuse*
w/Power
Size
Exhaust
(Amps)
(Amps)
2
3
2
3
HP HP
HP
HP
70 80
80
80
70 80
80
80
90 90
100
100
125 125 125
125
175 175 175
175
70 80
80
80
80 90
90
90
100 100 110
110
125 150 150
150
175 175 175
175
45 50
50
50
45 50
50
50
50 50
60
60
70 70
70
70
90 90
90
90
30 30
35
35
35 35
35
35
40 40
45
45
60 60
60
60
70 70
70
70
23
036-21058-005-A-0704
TABLE 18: ELECTRICAL DATA DM150 (12-1/2 TON) STD EFFICIENCY W/O PWRD CONVENIENCE OUTLET
MCA
Max
Min. Circuit
Supply
Pwr
Pwr
w/Power
Fuse*
Ampacity
Blower
Exh Conv
Electric Heater Actual Heater
Exhaust
Size
Voltage
(Amps)
Motor FLA Motor Outlet
Amps
KW
Model No.
(Amps)
(Amps)
RLA
LRA
FLA
3
5
3
5
3
5
3
5
FLA
FLA
ea.
ea.
ea.
HP
HP
HP
HP
HP
HP HP HP
None
--62.9 68.1 68.4 73.6 80 80
2TP04521825
13.5
37.5
62.9 68.1 68.4 73.8 80 80
20.0 146.0
3.5
10.9 16.1
5.5
0.0
208
2TP04522425
18
50.0
76.1 82.6 83.0 89.5 80 90
2TP04523625
25.5
70.8 102.1 108.6 109.0 115.5 110 110
2TP04525425
40.6
112.7 154.5 161.0 161.4 167.9 175 175
None
--62.9 68.1 68.4 73.6 80 80
2TP04521825
18
43.3
67.8 74.3 74.6 81.1 80 80
20.0 146.0
3.5
10.9 16.1
5.5
0.0
230
2TP04522425
24
57.7
85.8 92.3 92.7 99.2 90 100
2TP04523625
34
81.8 115.9 122.4 122.7 129.2 125 125
2TP04525425
129.9 143.5 150.0 150.4 156.9 175 175
54
None
--27.4 30.2 29.6 32.4 35 35
2TP04521846
18
22.6
33.7 37.2 36.4 39.9 35 40
8.4
73.0
1.6
5.3
8.1
2.2
0.0
460
2TP04522446
24
30.1
42.7 46.2 45.5
49
45 50
2TP04523646
34
42.7
57.7 61.2 60.5
64
60 70
2TP04525446
54
67.8
71.6 75.1 74.3 77.8 80 90
None
--21.8 23.7 23.6 25.5 25 30
2TP04521858
18
18.1
26.8 29.2
29
31.4 30 30
6.7
60.0
1.3
4.1
6.0
1.8
0.0
575
2TP04522458
24
24.1
34
36.4 36.2 38.6 35 40
2TP04523658
34
34.1
46
48.4 48.3 50.6 50 50
2TP04525458
54
54.2
57.1 59.5 59.3 61.7 70 70
*
Maximum HACR breaker of the same AMP size is applicable.
OD Fan
Compressors
Motors
Max
Fuse
Size
w/Power
3
5
HP HP
80 90
80 90
90 90
110 125
175 175
80 90
80 90
100 100
125 150
175 175
35 40
40 40
50 50
70 70
80 90
30 30
30 35
40 40
50 60
70 70
TABLE 19: ELECTRICAL DATA DM150 (12-1/2 TON) STD EFFICIENCY W/PWRD CONVENIENCE OUTLET
MCA
Max
Min. Circuit
Supply
Pwr
Pwr
w/Power
Fuse*
Ampacity
Blower
Exh Conv
Electric Heater Actual Heater
Exhaust
Size
Voltage
(Amps)
Motor FLA Motor Outlet
KW
Amps
Model No.
(Amps)
(Amps)
RLA
LRA
FLA
3
5
3
5
3
5
3
5
FLA
FLA
ea.
ea.
ea.
HP
HP
HP
HP
HP
HP HP HP
None
--72.9 78.1 78.4 83.6 90 90
2TP04521825
13.5
37.5
73.0 79.5 79.8 86.3 90 90
20.0
146.0
3.5
10.9 16.1
5.5
10.0
208
2TP04522425
18
50.0
88.6 95.1 95.5 102.0 90 100
2TP04523625
25.5
70.8 114.6 121.1 121.5 128.0 125 125
2TP04525425
40.6
112.7 167.0 173.5 173.9 180.4 175 175
None
--72.9 78.1 78.4 83.6 90 90
2TP04521825
18
43.3
80.3 86.8 87.1 93.6 90 90
20.0
146.0
3.5
10.9 16.1
5.5
10.0
230
2TP04522425
24
57.7
98.3 104.8 105.2 111.7 100 110
2TP04523625
34
81.8 128.4 134.9 135.2 141.7 150 150
2TP04525425
129.9 156.0 162.5 162.9 169.4 175 175
54
None
--32.4 35.2 34.6 37.4 40 40
2TP04521846
18
22.6
39.9 43.4 42.7 46.2 40 45
8.4
73.0
1.6
5.3
8.1
2.2
5.0
460
2TP04522446
24
30.1
49
52.5 51.7 55.2 50 60
2TP04523646
34
42.7
64
67.5 66.7 70.2 70 70
2TP04525446
54
67.8
77.8 81.3 80.6 84.1 90 90
None
--25.8 27.7 27.6 29.5 30 30
2TP04521858
18
18.1
31.8 34.2
34
36.4 35 35
6.7
60.0
1.3
4.1
6.0
1.8
4.0
575
2TP04522458
24
24.1
39
41.4 41.2 43.6 40 45
2TP04523658
34
34.1
51
53.4 53.3 55.6 60 60
2TP04525458
54
54.2
62.1 64.5 64.3 66.7 70 70
*
Maximum HACR breaker of the same AMP size is applicable.
Compressors
OD Fan
Motors
Max
Fuse
Size
w/Power
3
5
HP HP
90 100
90 100
100 110
125 150
175 200
90 100
90 100
110 125
150 150
175 175
40 45
45 50
60 60
70 80
90 90
30 35
35 40
45 45
60 60
70 70
NOTES FOR TABLE 21 THROUGH TABLE 30:
TABLE 20: ELECTRIC HEAT MULTIPLIERS
VOLTAGE
NOMINAL
240
480
600
RATING
208
230
460
0.75
0.92
0.92
575
0.92
NOTE: Electric heaters are rated at nominal voltage. Use
this table to determine the electric heat capacity for
heaters supplied at lower voltages.
24
•
Blower performance includes dry coil and 2” throwaway
filters.
•
Blower performance for gas heat includes the maximum
number of heat tubes available for each tonnage.
•
ESP (External Static Pressure) given is that available for
the supply and return air duct system. All internal resistances have been deducted from the total static pressure
of the blower.
kW Cap. Multiplier
Unitary Products
Unitary Products
0.2
0.4
0.6
0.8
1.0
External Static Pressure
1.2
1.4
1.6
1.8
760 1.18 1100
776 1.25 1166
652
707
764
823
885
949
2900 642 0.82
3000 652 0.88
3100 662 0.95
3200 672 1.02
3300 682 1.09 1016
976
917
860
806
1.11 1037
High Horsepower Option Required
745
730 1.05
715 0.98
699 0.92
684 0.86
755
705
659
614
2800 632 0.76
669 0.81
654 0.76
639 0.71
623 0.66
---572
2700 622 0.70
----
----
600
----
----
608 0.61
-------
550
----
2400
----
----
-------
2600 612 0.64
----
2300
----
----
----
----
2500 602 0.59
----
2200
----
----
----
----
2100
----
----
----
----
----
2000
641
971
923
877
832
790
750
712
676
825 1.40 1305
815 1.33 1244
805 1.27 1185
795 1.21 1129
786 1.15 1074
776 1.10 1022
766 1.04
756 0.99
746 0.94
736 0.89
727 0.85
717 0.80
707 0.76
697 0.72
687 0.69
758
968
922
880
843
810
782
884 1.61 1499
876 1.52 1417
867 1.44 1339
858 1.36 1266
850 1.28 1197
841 1.22 1133
832 1.15 1074
824 1.09 1019
815 1.04
807 0.99
798 0.94
789 0.90
781 0.87
772 0.84
764 0.81
884
997
940
893 1.18 1097
957 1.34 1252 1013 1.42 1324 1062 1.59 1484
996 1.66 1544 1046 1.78 1655 1094 1.96 1827
989 1.60 1493 1041 1.71 1597 1088 1.90 1770
983 1.55 1444 1035 1.65 1541 1083 1.84 1713
976 1.50 1395 1030 1.59 1485 1078 1.78 1656
970 1.44 1346 1024 1.53 1430 1073 1.71 1599
963 1.39 1299 1019 1.48 1377 1067 1.65 1541
974 1.85 1725 1034 2.00 1862
981 1.92 1793 1041 2.06 1918
987 2.00 1862 1047 2.12 1974
936 1.79 1666
944 1.86 1731
----
----
----
----
----
----
----
----
----
967 1.78 1660 1028 1.94 1807 1073 2.10 1956
960 1.71 1597 1021 1.88 1753 1068 2.03 1894
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
954 1.65 1537 1015 1.82 1700 1062 1.97 1833 1109 2.14 1999
940 1.53 1423 1002 1.71 1595 1051 1.84 1713 1099 2.02 1884
947 1.59 1479 1008 1.77 1647 1057 1.90 1773 1104 2.08 1941
934 1.47 1369
927 1.41 1318
920 1.36 1269
913 1.31 1223
907 1.26 1179
900 1.22 1137
929 1.72 1602
921 1.65 1539
914 1.58 1476
906 1.52 1414
899 1.45 1353
891 1.39 1292
884 1.32 1232
876 1.26 1172
869 1.19 1113
861 1.13 1055
854 1.07
846 1.01
839 0.95
RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts
1900
CFM
TABLE 21: BLOWER PERFORMANCE 6-1/2 TON SIDE DUCT
036-21058-005-A-0704
25
26
0.2
0.4
0.6
0.8
1.0
External Static Pressure
1.2
1.4
1.6
1.8
----
----
----
----
638
654
670
686
702
718
734
750
766
782
798
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
----
1.60
1.48
1.37
1.27
1.17
1.08
1.00
0.92
0.84
0.78
0.71
----
----
----
----
----
----
1490
1383
1281
1185
1094
1009
929
855
787
724
666
----
----
----
----
----
----
844
829
814
799
783
768
753
738
722
707
692
677
662
646
----
----
High Horsepower Option Required
----
----
2200
----
987
924
866
813
766
725
689
----
----
1.70 1587
1.59 1485
1.49 1388
1.39 1297
1.30 1211
1.21 1131
1.13 1056
1.06
0.99
0.93
0.87
0.82
0.78
0.74
----
----
----
794
976
932
893
860
832
810
884 1.85 1721
872 1.74 1622
861 1.64 1528
849 1.54 1440
837 1.46 1357
826 1.37 1280
814 1.30 1208
802 1.22 1141
791 1.16 1081
779 1.10 1025
767 1.05
755 1.00
744 0.96
732 0.92
720 0.89
709 0.87
697 0.85
843
996
949
908
873
851 1.04
969
910 1.32 1226
978 1.50 1395 1030 1.59 1485 1078 1.78 1656
996 1.66 1544 1046 1.78 1655 1094 1.96 1827
990 1.60 1494 1041 1.71 1597 1088 1.90 1770
984 1.55 1444 1035 1.65 1541 1083 1.84 1713
935 2.12 1977
984 2.26 2109
976 2.17 2022
----
-------
-------
-------
-------
----
----
----
968 2.08 1937 1012 2.26 2104 1065 2.31 2149
915 1.89 1759
925 2.00 1865
959 1.99 1854 1005 2.17 2022 1058 2.24 2090
998 2.09 1944 1052 2.18 2032
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
990 2.00 1868 1046 2.12 1975 1089 2.30 2148
951 1.90 1773
983 1.93 1795 1040 2.06 1918 1084 2.23 2083
943 1.82 1694
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
976 1.85 1726 1034 2.00 1862 1078 2.17 2019 1125 2.33 2170
968 1.78 1659 1027 1.94 1807 1073 2.10 1956 1120 2.27 2113
961 1.71 1594 1021 1.88 1753 1068 2.03 1894 1115 2.21 2056
954 1.64 1533 1015 1.82 1699 1062 1.97 1833 1109 2.14 1998
946 1.58 1475 1009 1.77 1647 1057 1.90 1773 1104 2.08 1941
939 1.52 1419 1003 1.71 1595 1051 1.84 1713 1099 2.02 1884
932 1.47 1367
924 1.41 1317
917 1.36 1270
934 1.74 1618
926 1.66 1543
918 1.58 1471
909 1.50 1401
901 1.43 1333
893 1.36 1267
884 1.29 1203
876 1.22 1141
868 1.16 1082
859 1.10 1025
905 1.78 1658
895 1.68 1562
885 1.58 1472
875 1.49 1388
866 1.40 1309
856 1.33 1235
846 1.25 1167
836 1.18 1104
826 1.12 1047
816 1.07
807 1.02
797 0.97
787 0.94
777 0.90
RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts
2300
CFM
TABLE 22: BLOWER PERFORMANCE 7-1/2 TON SIDE DUCT
036-21058-005-A-0704
Unitary Products
Unitary Products
0.4
0.6
0.8
1.0
External Static Pressure
1.2
1.4
1.6
1.8
812
828
4300
1.93
1.83
1.73
1.64
1.55
1.46
1.38
1.30
1.23
1.16
1.10
1.04
----
----
----
1802
1706
1614
1526
1443
1363
1287
1215
1148
1084
1024
968
----
----
----
----
----
----
-------
-------
703 1.07 995
758 1.10 1023 831 1.26 1179 887.46 1.40 1302 947.16 1.57 1464 1003.3 1.72 1601 1080 1.89 1758
741 1.16 1083 795 1.27 1181 861 1.42 1320 915.6 1.59 1482 971.19 1.75 1634 1023.4 1.92 1792 1090 2.15 2006
729 1.12 1048 783 1.21 1125 851 1.36 1268 906.22 1.52 1419 963.18 1.69 1574 1016.7 1.85 1726 1086 2.06 1922
716 1.09 1019 771 1.15 1072 841 1.31 1221 896.84 1.46 1359 955.17 1.63 1517 1010 1.78 1662 1083 1.97 1840
877 2.11 1968 920 2.33 2174 967 2.51 2338 1004 2.74 2556 1046.9 2.89 2694 1083.3 3.04 2836 1117
3.22 3001 ----
862 2.01 1870 907 2.21 2059 955 2.40 2233 994 2.61 2436 1037.5 2.78 2587 1075.3 2.93 2728 1110.3 3.11 2897 ----
----
----
----
----
847 1.91 1777 894 2.09 1950 942 2.29 2131 984 2.49 2321 1028.2 2.66 2484 1067.3 2.81 2623 1103.6 3.00 2796 1131 3.35 3122
832 1.81 1687 882 1.98 1846 930 2.18 2032 974 2.37 2211 1018.8 2.56 2383 1059.3 2.71 2522 1096.9 2.89 2698 1127 3.24 3021
818 1.72 1602 869 1.88 1748 918 2.08 1937 963 2.26 2106 1009.4 2.45 2286 1051.3 2.60 2424 1090.3 2.79 2602 1124 3.13 2922
803 1.63 1520 856 1.78 1656 906 1.98 1846 953 2.15 2005 1000 2.35 2191 1043.3 2.50 2330 1083.6 2.69 2509 1121 3.03 2824
788 1.55 1443 843 1.68 1569 893 1.89 1758 943 2.05 1910 990.64 2.25 2100 1035.3 2.40 2239 1076.9 2.59 2419 1117 2.93 2728
773 1.47 1369 831 1.60 1489 881 1.80 1674 933 1.95 1819 981.26 2.16 2012 1027.3 2.31 2152 1070.2 2.50 2331 1114 2.82 2632
758 1.39 1300 818 1.52 1414 869 1.71 1593 922 1.86 1733 971.88 2.07 1927 1019.3 2.22 2068 1063.5 2.41 2246 1110 2.72 2539
743 1.32 1234 805 1.44 1344 856 1.63 1516 912 1.77 1652 962.5 1.98 1845 1011.2 2.13 1987 1056.8 2.32 2164 1107 2.62 2446
728 1.26 1173 792 1.37 1281 844 1.55 1442 902 1.69 1576 953.12 1.89 1766 1003.2 2.05 1910 1050.1 2.24 2084 1104 2.53 2356
713 1.20 1116 780 1.31 1223 832 1.47 1371 892 1.61 1505 943.74 1.81 1691 995.22 1.97 1836 1043.4 2.15 2007 1100 2.43 2266
698 1.14 1063 767 1.26 1170 820 1.40 1305 882 1.54 1438 934.36 1.74 1618 987.21 1.89 1765 1036.7 2.07 1933 1097 2.34 2178
683 1.09 1014 754 1.21 1124 807 1.33 1241 871 1.48 1377 924.98 1.66 1549 979.2 1.82 1698 1030 2.00 1861 1093 2.24 2091
669 1.04 968
654 0.99 927
----
High Horsepower Option Required
796
4200
748
3800
4100
732
3700
764
716
3600
780
700
3500
4000
684
3400
3900
668
3300
----
----
652
----
3000
3100
----
2900
3200
----
----
2800
----
----
----
----
2600
RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts
0.2
2700
CFM
TABLE 23: BLOWER PERFORMANCE 8-1/2 TON SIDE DUCT
036-21058-005-A-0704
27
28
0.4
0.6
0.8
1.0
External Static Pressure
1.2
1.4
1.6
1.8
2.21
2.32
2.44
2.56
2.69
----
----
694
707
720
733
746
759
772
784
797
810
823
836
849
862
875
888
901
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
2503
2387
2274
2166
2061
1960
1863
1770
1680
1595
1513
1435
1361
1290
1224
1161
1102
----
----
----
----
----
----
----
741 1.20 1122 816 1.35 1256 865 1.46 1365 923 1.69 1571 971 1.91 1784 1035 2.04 1906 1092.2 2.26 2110
971 3.03 2823 1021 3.32 3093 ----
----
----
----
957 2.88 2687 1007 3.15 2941 1036 3.33 3100 -------
-------
----
----
----
943 2.74 2556 993 3.00 2795 1024 3.18 2964 1070 3.40 3166 ----
929 2.61 2430 979 2.85 2654 1012 3.04 2832 1058 3.25 3032 ----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
915 2.48 2308 965 2.70 2519 1001 2.90 2705 1047 3.11 2902 1082 3.41 3175 ----
----
----
----
901 2.35 2191 951 2.56 2390 989 2.77 2581 1036 2.98 2776 1072 3.25 3032 1102 3.42 3184 -------
----
887 2.23 2079 937 2.43 2266 978 2.64 2463 1024 2.85 2654 1062 3.11 2895 1093 3.29 3065 1125 3.40 3171
----
-------
----
859 2.01 1869 909 2.18 2035 955 2.40 2238 1001 2.60 2422 1042 2.83 2637 1076 3.04 2838 1112 3.17 2953
873 2.12 1972 923 2.30 2148 966 2.52 2348 1013 2.72 2536 1052 2.96 2763 1084 3.16 2949 1118 3.28 3061
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
845 1.90 1771 895 2.07 1928 943 2.29 2132 990 2.48 2311 1032 2.70 2516 1067 2.93 2729 1106 3.06 2848 1147.2 3.38 3148
831 1.80 1678 881 1.96 1827 932 2.18 2031 979 2.37 2205 1022 2.58 2402 1058 2.82 2625 1099 2.95 2747 1142.2 3.26 3040
817 1.70 1589 867 1.86 1731 920 2.07 1934 967 2.26 2103 1012 2.46 2293 1050 2.71 2524 1093 2.84 2649 1137.2 3.15 2934
803 1.61 1505 853 1.76 1641 909 1.98 1841 956 2.15 2005 1002 2.35 2190 1041 2.60 2427 1086 2.74 2554 1132.2 3.04 2832
789 1.53 1426 839 1.67 1556 897 1.88 1753 944 2.05 1911 992 2.24 2092 1032 2.50 2334 1080 2.64 2462 1127.2 2.93 2732
775 1.45 1351 825 1.59 1477 886 1.79 1669 933 1.95 1821 982 2.15 2001 1023 2.41 2244 1073 2.55 2373 1122.2 2.83 2634
761 1.37 1281 811 1.51 1404 874 1.70 1589 922 1.86 1735 972 2.05 1915 1015 2.31 2158 1067 2.45 2287 1117.2 2.72 2540
747 1.30 1216 797 1.43 1336 863 1.62 1514 910 1.77 1653 962 1.97 1834 1006 2.23 2076 1061 2.37 2205 1112.2 2.63 2448
733 1.24 1156 783 1.37 1274 851 1.55 1443 899 1.69 1575 952 1.89 1760 997 2.14 1997 1054 2.28 2125 1107.2 2.53 2360
719 1.18 1100 769 1.31 1218 840 1.48 1376 887 1.61 1501 943 1.81 1691 988 2.06 1922 1048 2.20 2049 1102.2 2.44 2274
705 1.13 1049 755 1.25 1167 828 1.41 1314 876 1.54 1431 933 1.75 1628 980 1.99 1851 1041 2.12 1976 1097.2 2.35 2190
High Horsepower Option Required
2.10
2.00
1.90
1.80
1.71
1.62
1.54
1.46
1.38
1.31
1.25
1.18
----
----
----
----
----
----
3100
RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts
0.2
3000
CFM
TABLE 24: BLOWER PERFORMANCE 10 TON SIDE DUCT
036-21058-005-A-0704
Unitary Products
Unitary Products
0.4
0.6
0.8
1.0
1.2
External Static Pressure
1.4
1.6
1.8
2.0
----
----
----
----
----
----
----
3900 ----
4000 ----
4100 ----
4200 ----
4300 ----
4400 ----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
874 1.93 1801 927 2.04 1906 984 2.27 2113 1037 2.41 2245 1089 2.57 2399 1138 2.68 2499 1178 2.82 2628
885 2.12 1973 932 2.27 2115 982 2.45 2283 1035 2.68 2494 1083 2.82 2626 1130 2.98 2774 1171 3.10 2887 1212 3.29 3066
870 2.01 1877 917 2.18 2028 968 2.34 2182 1022 2.57 2392 1071 2.71 2524 1120 2.87 2672 1163 2.98 2780 1204 3.16 2947
855 1.92 1786 903 2.09 1947 954 2.24 2085 1009 2.46 2295 1060 2.60 2427 1109 2.76 2576 1155 2.88 2680 1195 3.04 2834
840 1.82 1699 888 2.01 1871 941 2.14 1993 997 2.36 2202 1048 2.50 2334 1099 2.67 2485 1146 2.77 2586 1186 2.93 2728
868 2.28 2121 931 2.45 2283 975 2.58 2409 1023 2.81 2616 1074 3.03 2828 1117 3.18 2960 1160 3.34 3111 1196 3.48 3245 1239 3.71 3462
851 2.19 2042 915 2.33 2175 961 2.47 2305 1009 2.68 2501 1061 2.91 2712 1106 3.05 2844 1150 3.21 2993 1188 3.35 3119 1230 3.57 3324
834 2.11 1970 900 2.22 2072 946 2.37 2207 996 2.56 2390 1048 2.79 2601 1094 2.93 2733 1140 3.09 2881 1179 3.22 3000 1221 3.42 3192
----
----
----
----
----
High Horsepower Option Required
----
----
----
----
6200 1098 4.86 4531 1169 5.09 4744 1204 5.29 4927 1236 5.61 5231 ----
----
----
----
----
----
----
----
----
----
6100 1082 4.64 4326 1152 4.87 4539 1189 5.09 4745 1222 5.39 5027 ----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
-------
----
----
5900 1050 4.22 3936 1119 4.45 4149 1159 4.71 4393 1193 4.97 4635 1229 5.27 4917 1267 5.47 5101 ----
6000 1066 4.43 4127 1136 4.66 4341 1174 4.90 4567 1207 5.18 4828 1243 5.48 5108 ----
----
----
----
5800 1033 4.02 3751 1102 4.25 3965 1143 4.53 4224 1178 4.77 4447 1215 5.07 4731 1254 5.28 4918 1279 5.42 5050 ----
----
----
5700 1017 3.83 3574 1085 4.06 3788 1128 4.35 4058 1164 4.58 4265 1201 4.88 4549 1241 5.08 4740 1267 5.23 4872 1293 5.50 5125 ----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
5600 1001 3.65 3403 1069 3.88 3618 1113 4.18 3897 1149 4.39 4089 1188 4.69 4372 1228 4.90 4566 1256 5.04 4698 1283 5.30 4938 ----
----
----
5500 984 3.48 3240 1052 3.71 3455 1098 4.01 3740 1135 4.20 3918 1174 4.51 4200 1215 4.72 4396 1244 4.86 4528 1273 5.10 4757 1286 5.41 5044 -------
----
5400 968 3.31 3083 1035 3.54 3298 1083 3.85 3587 1120 4.03 3753 1160 4.33 4032 1202 4.54 4231 1233 4.68 4363 1262 4.91 4580 1278 5.20 4848 ----
----
----
----
----
----
----
----
----
----
5300 952 3.15 2934 1018 3.38 3149 1067 3.69 3438 1106 3.85 3593 1147 4.15 3869 1189 4.37 4070 1221 4.51 4202 1252 4.73 4409 1270 5.00 4660 1317 5.36 4996
5200 936 2.99 2791 1002 3.23 3007 1052 3.53 3293 1091 3.69 3439 1133 3.98 3711 1177 4.20 3914 1210 4.34 4046 1242 4.55 4244 1262 4.80 4477 1308 5.15 4800
5100 919 2.85 2656 985 3.08 2872 1037 3.38 3152 1077 3.53 3291 1119 3.82 3558 1164 4.04 3763 1198 4.18 3895 1232 4.38 4083 1254 4.61 4301 1300 4.95 4610
5000 903 2.71 2527 968 2.94 2744 1022 3.24 3016 1062 3.38 3148 1105 3.66 3409 1151 3.88 3616 1187 4.02 3748 1222 4.21 3929 1245 4.43 4131 1291 4.75 4427
4900 887 2.58 2406 952 2.81 2622 1007 3.09 2883 1048 3.23 3011 1092 3.50 3265 1138 3.73 3473 1175 3.87 3605 1211 4.05 3779 1237 4.26 3967 1282 4.56 4250
4800 870 2.46 2291 935 2.69 2508 991 2.96 2755 1033 3.09 2879 1078 3.35 3126 1125 3.58 3335 1164 3.72 3467 1201 3.90 3635 1229 4.09 3810 1273 4.38 4080
4700 854 2.34 2184 918 2.58 2401 976 2.82 2631 1019 2.95 2753 1064 3.21 2991 1112 3.43 3201 1152 3.58 3333 1191 3.75 3496 1221 3.93 3659 1265 4.20 3916
4600 838 2.23 2083 901 2.47 2301 961 2.69 2511 1004 2.82 2633 1051 3.07 2862 1099 3.30 3072 1141 3.44 3204 1181 3.61 3362 1212 3.77 3515 1256 4.03 3758
4500 822 2.13 1990 885 2.37 2208 946 2.57 2395 990 2.70 2518 1037 2.94 2736 1087 3.16 2948 1129 3.30 3080 1171 3.47 3234 1204 3.62 3377 1247 3.87 3607
----
3800 ----
RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts
0.2
3700 ----
CFM
TABLE 25: BLOWER PERFORMANCE 12-1/2 TON SIDE DUCT
036-21058-005-A-0704
29
30
0.2
0.4
0.6
0.8
1.0
External Static Pressure
1.2
1.4
1.6
728
739
750
761
772
784
795
2700
2800
2900
3000
3100
3200
3300
----
1.36
1.26
1.16
1.06
0.96
0.86
0.76
----
----
----
----
----
----
----
----
1269
1175
1080
987
894
801
709
----
----
----
----
----
----
----
----
836
825
813
801
790
778
767
755
743
732
720
----
----
----
Std HP Motor 1.5
Motor Efficiency 0.8
High Horsepower Option Required
----
2400
----
----
2300
2600
----
2200
2500
----
----
2100
----
----
2000
----
964
895
828
763
699
----
----
---0.9
946
891
839
789
742
698
890 1.67 1552
1400
1.52 1417
1.5
879 1.58 1475
868
857 1.42 1327
846 1.35 1257
834 1.28 1190
823 1.21 1125
812 1.14 1063
801 1.08 1003
789 1.01
778 0.96
767
756 0.85
0.8
733 0.75
745
1.43 1336
1.35 1258
1.27 1182
1.19 1107
1.11 1035
1.03
0.96
0.9
0.82
0.75
----
----
----
---0.9
1.1
825
1030
975
922
872
1.3
1211
947 1.85 1721
937 1.76 1640
926 1.68 1562
916 1.59 1487
906 1.52 1414
896 1.44 1344
886 1.37 1276
875
865 1.23 1148
855 1.17 1088
845
824 0.99
835 1.05
814 0.94
804
963
931 1.21 1124
1.4
980 1.37 1279 1019 1.51 1409
1.5
1395 1031 1.63 1521
1301 1000 1.56 1454 1036 1.69 1578
993
987 1.43 1336 1025 1.57 1465
1.6
1491 1019 1.76 1641 1053 1.88 1755
992 1.75 1627 1032 1.9
939 2.05 1908
935 1.96 1827
----
-------
-------
----
931 1.87 1748 1023 2.06 1917
----
----
----
----
----
----
----
----
----
----
----
----
1769 1045 2.04 1906
927 1.79 1671 1015 1.98 1842
923 1.71 1596 1008 1.9
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
1771 1064 2.01 1878
985 1.67 1558 1026 1.83 1705 1059 1.95 1816
977
969 1.53 1426 1013 1.69 1577 1047 1.82 1695
962 1.46 1363 1006 1.63 1515 1042 1.76 1636
954
946 1.33 1240
939 1.27 1181
918 1.63 1523 1000 1.82 1697 1039 1.97 1838
914 1.56 1452
910 1.48 1384
906 1.41 1317
902 1.34 1253
898 1.28 1191
894 1.21 1131
889 1.15 1073
885 1.09 1017
881 1.03
RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts
1900
CFM
TABLE 26: BLOWER PERFORMANCE 6-1/2 TON DOWNSHOT
036-21058-005-A-0704
Unitary Products
Unitary Products
0.4
0.6
0.8
1.0
External Static Pressure
1.2
1.4
1.6
----
----
----
----
0.87 812
1.00 936
1.13 1058
1.26 1177
1.39 1295
1.51 1410
2600 ----
2700 ----
2800 ----
2900 ----
3000 817
3100 822
3200 827
3300 832
3400 837
3500 842
----
1.87 1741
3700 852
3800 857
Std HP Motor 1.5
Motor Efficiency 0.8
----
----
----
----
878
2.01 1874
1.92 1787
1.82 1697
866
872
1.72 1606
1.62 1513
1.52 1418
1.42 1321
1.31 1222
1.20 1121
1.09 1018
0.98 913
0.87 806
0.75 698
----
----
----
----
859
853
846
840
833
827
820
814
808
801
----
----
----
----
High Horsepower Option Required
1.63 1523
1.75 1633
3600 847
----
----
----
----
----
----
----
----
----
2500 ----
----
2400 ----
----
2300 ----
1.87 1742
893
917
909
2.09 1951
2.02 1883
1.95 1813
1.79 1671
885
901
1.71 1598
1.64 1524
1.55 1449
1.47 1373
1.39 1296
1.31 1218
1.22 1139
1.14 1058
1.05 977
0.96 894
0.87 811
0.78 726
877
869
862
854
846
838
830
822
814
806
798
791
1.82 1692
927
971
962
953
944
2.15 2001
2.08 1939
2.01 1877
1.95 1816
1.88 1754
1.75 1631
918
936
1.68 1569
1.62 1508
1.55 1446
1.49 1384
1.42 1323
1.35 1261
1.29 1200
1.22 1138
1.16 1077
1.09 1015
909
900
892
883
874
865
857
848
839
830
2.00 1863
1.93 1798
1029 2.29 2132
1020 2.21 2063
1012 2.14 1995
1003 2.07 1928
994
985
1.86 1734
1.79 1671
968
976
1.73 1609
1.66 1548
1.60 1488
1.53 1429
1.47 1371
1.41 1314
1.35 1258
1.29 1203
1.23 1149
959
950
941
933
924
915
906
897
889
----
----
----
----
----
----
----
----
----
----
----
----
1047 2.21 2059
1039 2.13 1986
1031 2.05 1914
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
1060 2.11 1971
1015 1.90 1774
----
1053 2.04 1899
1007 1.83 1707
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
1076 2.07 1925
----
1070 1.99 1857
1039 1.89 1760
1046 1.96 1829
1064 1.92 1790
1032 1.82 1692
1.76 1640
1058 1.85 1725
1018 1.67 1561
998
1023 1.98 1843
1046 1.71 1597
1052 1.78 1660
1025 1.74 1626
1011 1.61 1497
1004 1.54 1435
1.69 1576
1.62 1512
1.56 1450
1.49 1389
1.43 1330
1.36 1272
990
982
974
966
958
950
RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts
0.2
2200 ----
CFM
TABLE 27: BLOWER PERFORMANCE 7-1/2 TON DOWNSHOT
036-21058-005-A-0704
31
32
0.4
0.6
0.8
1.0
1.2
External Static Pressure
1.4
1.6
1.8
2.0
----
----
----
1.11 1035
1.14 1061
1.18 1096
1.22 1138
1.28 1189
1.34 1248
1.41 1315
1.49 1391
1.58 1474
1.68 1566
1.79 1666
1.90 1774
2.03 1890
2.16 2015
2600 ----
2700 ----
2800 ----
2900 652
3000 671
3100 690
3200 709
3300 729
3400 748
3500 767
3600 786
3700 805
3800 824
3900 843
4000 862
4100 881
4200 900
----
945
928
911
894
877
860
843
826
809
792
775
758
741
724
706
689
672
655
----
Std HP Motor 2
Motor Efficiency 0.8
High Horsepower Option Required
----
----
----
----
----
----
----
2500 ----
----
----
----
-------
756
742
829
814
2.35 2190 988
2.21 2063 974
2.08 1943 959
1.96 1829 945
1.85 1723 930
1.74 1624 916
1.64 1532 901
1.55 1447 887
1.47 1369 872
1.39 1298 858
1.32 1234 843
1.26 1178
1.21 1128
1.16 1085 800
1.13 1050 785
959
868
856
894
996 1.78 1657 1029 1.92 1794 1054 2.03 1894 1074 2.10 1953
989 1.70 1583 1023 1.84 1720 1049 1.95 1822 1070 2.02 1885
981 1.62 1511 1016 1.77 1647 1044 1.88 1752 1065 1.95 1817
1011 1.94 1812 1041 2.09 1947 1065 2.19 2041 1083 2.25 2093
2.38 2218 1027 2.58 2405 1059 2.77 2578 1083 2.92 2722
2.26 2109 1017 2.46 2297 1050 2.65 2473 1076 2.81 2621
2.56 2383 1026 2.76 2571 1058 2.95 2749 1085 3.12 2911
2.42 2257 1014 2.63 2449 1048 2.82 2631 1076 3.00 2797
----
-------
-------
-------
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2.15 2005 1007 2.35 2193 1041 2.54 2370 1069 2.71 2522 1090 2.82 2630
-------
2.14 1995 1024 2.33 2174 1054 2.50 2331 1078 2.63 2449
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2.04 1902 1015 2.23 2080 1047 2.40 2239 1072 2.53 2361
----
----
----
1.94 1812 1007 2.13 1989 1040 2.31 2149 1066 2.44 2275 1086 2.52 2352
1.85 1726 998 2.04 1900 1032 2.21 2061 1060 2.35 2190 1080 2.44 2273
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
1.76 1643 990 1.95 1815 1025 2.12 1976 1053 2.26 2107 1075 2.35 2194 1092 2.40 2237
1.68 1564 981 1.86 1732 1018 2.03 1893 1047 2.17 2026 1070 2.27 2117 1087 2.32 2165
1.60 1488 972 1.77 1653
1.52 1416 964 1.69 1576 1003 1.86 1733 1035 2.01 1870 1060 2.11 1967 1079 2.17 2023
1.45 1347 955 1.61 1501
1.38 1282 946 1.53 1430
1.31 1221 938 1.46 1362
974 1.55 1441 1010 1.69 1577 1039 1.81 1683 1061 1.88 1751
920 1.32 1233 967 1.47 1374 1004 1.62 1508 1034 1.73 1615 1056 1.81 1686
929 1.39 1296
2.24 2092 1033 2.44 2270 1062 2.60 2425 1084 2.72 2538
2.04 1905 997
1.94 1810 986
1.84 1719 976
1.75 1632 966
1.66 1550 956
1.58 1473 945
1.50 1400 935
1.43 1331 925
1.36 1267 915
1.29 1207 904
1.24 1152
884
1.25 1163
2.29 2138 1002 2.50 2331 1038 2.70 2516 1067 2.88 2686 1091 3.03 2825
2.17 2023 990
2.05 1915 977
1.94 1812 965
1.84 1715 953
1.74 1623 941
1.65 1537 929
1.56 1456 916
1.48 1381 904
1.41 1312 892
1.34 1248 880
1.28 1190
1.22 1138
1.17 1091 843
1.13 1049 831
1.18 1101
1.13 1054 874
795 1.09 1012 863 1.19 1108
807
1.09 1014 819
1.06 984
713 1.03
727
1.10 1021 771
1.07 999
1.06 985
----
----
RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts
0.2
2400 ----
2300
CFM
TABLE 28: BLOWER PERFORMANCE 8-1/2 TON DOWNSHOT
036-21058-005-A-0704
Unitary Products
Unitary Products
0.2
0.4
0.6
0.8
1.0
External Static Pressure
1.2
1.4
1.6
2760
2934
3115
3305
2.16
2.30
2.45
2.61
2.78
2.96
767
786
805
824
843
862
881
900
919
938
957
976
995
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800 1015 3.15
4900 1034 3.34
5000 1053 3.55
2595
2437
2288
2148
2015
1890
1774
1666
1566
1474
1391
1315
Std HP Motor 2
Motor Efficiency 0.8
988 2.56 2383 1026 2.76 2571 1058 2.95 2749
2.80 2614 1032 3.00 2792 1063 3.18 2963
1082 3.71 3462
1065 3.52 3278
----
-------
-------
----
1047 3.33 3102 1075 3.49 3253
1030 3.15 2932 1061 3.32 3094
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2.65 2466 1017 2.84 2650 1050 3.03 2828 1079 3.21 2996
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
974 2.42 2257 1014 2.63 2449 1048 2.82 2631 1076 3.00 2797
----
----
959 2.29 2138 1002 2.50 2331 1038 2.70 2516 1067 2.88 2686
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
990 2.38 2218 1027 2.58 2405 1059 2.77 2578
945 2.17 2023
----
----
977 2.26 2109 1017 2.46 2297 1050 2.65 2473 1076 2.81 2621
930 2.05 1915
----
----
965 2.15 2005 1007 2.35 2193 1041 2.54 2370 1069 2.71 2522
916 1.94 1812
953 2.04 1905
941 1.94 1810
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
976 2.04 1902 1015 2.23 2080 1047 2.40 2239 1072 2.53 2361
----
901 1.84 1715
887 1.74 1623
1013 2.97 2770 1046 3.15 2940 1075 3.33 3103
996
979
998 2.04 1900 1032 2.21 2061 1060 2.35 2190
990 1.95 1815 1025 2.12 1976 1053 2.26 2107
981 1.86 1732 1018 2.03 1893 1047 2.17 2026
966 1.94 1812 1007 2.13 1989 1040 2.31 2149 1066 2.44 2275
956 1.85 1726
945 1.76 1643
935 1.68 1564
997 2.24 2092 1033 2.44 2270 1062 2.60 2425
929 1.84 1719
916 1.75 1632
904 1.66 1550
892 1.58 1473
880 1.50 1400
986 2.14 1995 1024 2.33 2174 1054 2.50 2331
872 1.65 1537
858 1.56 1456
843 1.48 1381
829 1.41 1312
814 1.34 1248
2.49 2324 1003 2.70 2514 1038 2.89 2697 1068 3.08 2871
2.35 2190
945
962
2.21 2063
2.08 1943
1.96 1829
1.85 1723
1.74 1624
1.64 1532
1.55 1447
1.47 1369
1.39 1298
1.32 1234
1.26 1178
1.21 1128
928
911
894
877
860
843
826
809
792
775
758
741
High Horsepower Option Required
2.03
1.90
1.79
1.68
1.58
1.49
1.41
----
1248
3500
1.34
----
----
----
----
----
----
748
----
3200
----
----
3400
----
3300
----
3100
RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts
3000
CFM
TABLE 29: BLOWER PERFORMANCE 10 TON DOWNSHOT
036-21058-005-A-0704
33
34
0.2
0.4
0.6
0.8
1.0
1.2
External Static Pressure
1.4
1.6
1.8
2.0
1198 4.69 4369 1235 4.90 4566 1271 5.10 4756 ----
3784
3971
4166
4368
4576
4792
----
5400 1122 4.06
5500 1141 4.26
5600 1160 4.47
5700 1178 4.69
5800 1197 4.91
5900 1216 5.14
----
----
----
6000
6100
6200
----
----
----
----
----
Std HP Motor 3
Motor Efficiency 0.8
----
----
----
----
----
----
----
----
----
----
----
----
1234 5.12 4776 ----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
1216 4.90 4569 1253 5.11 4765 ----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
1162 4.28 3987 1201 4.49 4185 1238 4.70 4378 1275 4.90 4565 1311 5.09 4745 ----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
1144 4.08 3805 1184 4.29 4003 1222 4.50 4196 1259 4.70 4384 1296 4.90 4566 1331 5.09 4742 ----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
1126 3.89 3629 1167 4.11 3827 1205 4.31 4020 1243 4.51 4208 1281 4.71 4391 1317 4.90 4569 1352 5.09 4740 ----
High Horsepower Option Required
----
----
----
1180 4.48 4175 1218 4.69 4373 1255 4.90 4564 1291 5.10 4750 ----
3603
5300 1103 3.87
----
1108 3.71 3460 1149 3.92 3656 1189 4.13 3848 1227 4.33 4037 1265 4.53 4221 1302 4.72 4399 1338 4.91 4572 1372 5.09 4740 ----
3430
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
1072 3.37 3141 1115 3.57 3331 1156 3.78 3520 1196 3.98 3707 1234 4.17 3891 1272 4.37 4071 1309 4.56 4246 1344 4.74 4417 1379 4.92 4585
1054 3.21 2990 1098 3.41 3177 1139 3.61 3364 1180 3.81 3549 1219 4.00 3732 1257 4.20 3912 1294 4.39 4088 1330 4.57 4260 1365 4.75 4429
1036 3.05 2846 1081 3.25 3029 1123 3.45 3212 1164 3.64 3396 1204 3.84 3578 1242 4.03 3758 1280 4.22 3933 1316 4.40 4106 1352 4.59 4275
1019 2.91 2708 1063 3.10 2886 1106 3.29 3066 1148 3.48 3247 1188 3.68 3428 1227 3.87 3606 1266 4.06 3782 1303 4.24 3955 1338 4.43 4125
3263
2536
5100 1066 3.50
2.72
983 2.63 2451 1029 2.81 2617 1073 2.99 2788 1116 3.18 2963 1157 3.37 3139 1198 3.56 3315 1237 3.74 3490 1275 3.93 3662 1311 4.11 3832
1001 2.76 2577 1046 2.95 2749 1090 3.14 2925 1132 3.33 3103 1173 3.52 3281 1212 3.71 3459 1251 3.90 3634 1289 4.08 3807 1325 4.27 3977
5200 1084 3.68
991
4700
2411
965 2.50 2332 1012 2.67 2491 1056 2.85 2657 1100 3.03 2828 1142 3.22 3001 1183 3.41 3175 1223 3.59 3348 1261 3.78 3520 1298 3.96 3690
1090 3.54 3297 1132 3.74 3491 1172 3.95 3682 1211 4.15 3870 1250 4.35 4054 1287 4.54 4233 1323 4.73 4407 1358 4.91 4577 1392 5.09 4744
972
4600
2.59
2294
947 2.38 2219 995 2.54 2371 1040 2.72 2531 1084 2.89 2697 1127 3.08 2867 1168 3.26 3039 1208 3.44 3211 1247 3.63 3381 1285 3.81 3550
3103
953
4500
2.46
2184
2080
2.16 2012 960 2.30 2147 1007 2.46 2294 1052 2.63 2449 1096 2.80 2611 1138 2.98 2777 1179 3.16 2945 1219 3.34 3113 1258 3.52 3280
929 2.27 2113 977 2.42 2256 1023 2.59 2410 1068 2.76 2571 1111 2.94 2737 1153 3.12 2906 1194 3.30 3076 1233 3.48 3245 1271 3.66 3414
911
893 2.06 1918 943 2.19 2044 990 2.34 2183 1036 2.50 2332 1080 2.67 2489 1123 2.84 2652 1165 3.02 2817 1205 3.20 2983 1244 3.38 3149
5000 1047 3.33
934
4400
2.34
2.23
908 1.99 1853 957 2.12 1976 1004 2.27 2112 1050 2.42 2258 1094 2.59 2412 1136 2.76 2571 1177 2.93 2733 1217 3.11 2895
2951
915
4300
1984
----
4900 1028 3.17
897
4200
2.13
----
----
----
2806
878
4100
----
----
---875 1.96 1831 926 2.09 1946 974 2.23 2077 1020 2.38 2220 1065 2.54 2372 1108 2.71 2530 1151 2.89 2693 1191 3.06 2856 1231 3.24 3021
4800 1009 3.01
----
4000
----
----
2667
----
3900
----
----
2.86
----
----
3800
RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts RPM BHP Watts
3700
CFM
TABLE 30: BLOWER PERFORMANCE 12-1/2 TON DOWNSHOT
036-21058-005-A-0704
Unitary Products
036-21058-005-A-0704
TABLE 31: ADDITIONAL STATIC RESISTANCE
Cooling Only*
CFM
Electric Heat KW†
Economizer† ‡
9
18
24
36
54
0.10
1900
0.06
0.02
0.05
0.06
0.07
0.08
2100
0.07
0.02
0.06
0.07
0.08
0.09
0.11
2300
0.08
0.02
0.07
0.08
0.09
0.10
0.13
2500
0.09
0.02
0.08
0.09
0.10
0.11
0.14
2700
0.11
0.03
0.09
0.10
0.12
0.13
0.16
2900
0.12
0.03
0.10
0.11
0.13
0.14
0.18
3100
0.14
0.03
0.12
0.13
0.15
0.16
0.20
3300
0.16
0.03
0.13
0.14
0.17
0.18
0.22
3500
0.18
0.04
0.15
0.16
0.19
0.20
0.24
3700
0.20
0.04
0.17
0.18
0.21
0.22
0.26
3900
0.23
0.04
0.19
0.20
0.23
0.24
0.28
4100
0.25
0.04
0.21
0.22
0.25
0.26
0.31
4300
0.28
0.05
0.23
0.24
0.28
0.29
0.34
4500
0.30
0.05
0.25
0.26
0.30
0.31
0.37
4700
0.33
0.05
0.28
0.29
0.33
0.34
0.40
4900
0.36
0.05
0.30
0.31
0.35
0.37
0.43
5100
0.39
0.06
0.33
0.34
0.38
0.40
0.46
5300
0.42
0.06
0.35
0.37
0.41
0.43
0.49
5500
0.45
0.06
0.38
0.40
0.44
0.46
0.53
5700
0.48
0.06
0.41
0.43
0.47
0.49
0.56
5900
0.52
0.07
0.44
0.46
0.50
0.53
0.59
6100
0.56
0.07
0.47
0.49
0.53
0.56
0.62
6300
0.60
0.07
0.50
0.53
0.56
0.59
0.65
* Add these resistance values to the available static resistance in the respective Blower Performance Tables.
† Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
‡ The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 32: ELECTRIC HEAT MINIMUM SUPPLY AIR CFM
UNIT MODEL SIZE, NOMINAL TONS
HEATER
kW
VOLTAGE
6.5
7.5
8.5
10
12.5
MINIMUM SUPPLY AIR CFM
9
1950
2250
2550
N/A
N/A
18
1950
2250
2550
3000
3750
1950
2250
2550
3000
3750
1950
2250
2550
3000
3750
4000
24
208/230
36
54
N/A
N/A
N/A
3500
9
1950
2250
2550
N/A
N/A
18
1950
2250
2550
3000
3750
1950
2250
2550
3000
3750
36
1950
2250
2550
3000
3750
54
N/A
N/A
N/A
3000
3750
9
1950
2250
2550
N/A
N/A
18
1950
2250
2550
3000
3750
3750
24
480
1950
2250
2550
3000
36
1950
2250
2550
3000
3750
54
N/A
N/A
N/A
3500
3750
24
Unitary Products
600
35
036-21058-005-A-0704
TABLE 33: INDOOR BLOWER SPECIFICATIONS
MODEL
DM078
DM090
DM102
DM120
DM150
MOTOR
HP
RPM
Eff.
MOTOR SHEAVE
SF
Frame
Datum Dia. (in.)
BLOWER SHEAVE
Bore (in.)
Model
Datum Dia. (in.)
Bore (in.)
Model
BELT
1-1/2
1725
80%
1.15
56
3.4 - 4.4
7/8
1VM50
9.5
1
AK99
A58
2
1725
80%
1.15
56
3.4 - 4.4
7/8
1VM50
7.5
1
AK79
A55
1-1/2
1725
80%
1.15
56
3.4 - 4.4
7/8
1VM50
9.0
1
AK94
A57
2
1725
80%
1.15
56
3.4 - 4.4
7/8
1VM50
7.5
1
AK79
A55
2
1725
80%
1.15
56
3.4 - 4.4
7/8
1VM50
9.0
1
AK94
A56
3
1725
80%
1.15
56
3.4 - 4.4
7/8
1VM50
7.0
1
AK74
A54
2
1725
80%
1.15
56
3.4 - 4.4
7/8
1VM50
8.5
1
AK89
A56
3
1725
80%
1.15
56
3.4 - 4.4
7/8
1VM50
7.0
1
AK74
A54
3
1725
80%
1.15
56
3.4 - 4.4
7/8
1VM50
7.0
1
AK74
A54
5
1725
87%
1.15
184T
4.3 - 5.3
1 1/8
1VP56
6.7
1
BK77
BX55
TABLE 34: POWER EXHAUST SPECIFICATIONS
POWER EXHAUST
MODEL
VOLT
PHASE
2PE0473125
2PE0473146
2PE0473158
208/230
460
575
1
1
1
*
MOTOR
HP
RPM
*
ELECTRICAL
QTY
1075
0.75
1
1050
LRA
FLA
MCA
FUSE
SIZE
[email protected]
0.1 ESP
24.9
5.0
2.2
1.5
6.3
2.8
1.9
10
5
4
3,800
N/A
Motors are multi-tapped and factory wired for high speed.
FRESH AIR HOOD
(FROM ECONOMIZER)
SUPPLY DUCT COVER
22 316
RETURN DUCT COVER
26 5 8
POWER CONTROL ACCESS
BAROMETRIC RELIEFHOOD
(FROM ECONOMIZER)
FIGURE 2 -
36
POWER EXHAUST ACCESSORY DOWNFLOW APPLICATION
Unitary Products
036-21058-005-A-0704
FRESH AIR HOOD
(FROM ECONOMIZER)
SUPPLY DUCT
(FIELD SUPPLIED)
RETURN DUCT
(FIELD SUPPLIED)
RETURN DUCT COVER
22 316
26 5 8
POWER CONTROL ACCESS
BAROMETRIC RELIEFHOOD
(FROM ECONOMIZER)
FIGURE 3 -
POWER EXHAUST ACCESSORY HORIZONTAL APPLICATION
25-1/2"
47-1/2"
FRONT
LEFT
FIGURE 5 -
UNIT CENTER OF GRAVITY
F R O N T
L E F T
B
C
A
D
FIGURE 4 -
UNIT 4 POINT LOAD
TABLE 35: 4 POINT LOAD WEIGHT
Location (lbs.)
Model
A
B
C
DM078
228
195
285
333
DM090
230
197
287
336
DM102
238
203
296
347
DM120
245
209
305
357
DM150
262
224
327
382
Unitary Products
F R O N T
D
L E F T
A
D
C
B
E
F
FIGURE 6 -
UNIT 6 POINT LOAD
37
036-21058-005-A-0704
TABLE 36: 6 POINT LOAD WEIGHT
TABLE 37: UNIT WEIGHT
Locations (lbs.)
Model
A
B
C
D
E
F
DM078
156
140
127
185
205
228
DM090
158
142
128
187
207
230
DM102
163
146
132
192
213
237
DM120
168
151
136
198
219
244
DM150
180
161
145
212
235
262
Model
Shipping Weight (lbs.)
Operating Weight (lbs.)
DM078
1046
1041
DM090
1056
1051
DM102
1089
1084
DM120
1121
1116
DM150
1200
1195
30-11/32
50-3/4
See Detail
A
Control
Entry
Ø 7/8
Power
Entry
Ø 2-1/2
Power
Entry
Ø 2-1/2
4-1/4
11-1/2
Convenience
Power
Outlet
Entry
Ø 7/8
30-3/16
FIGURE 7 -
89
27
UNIT DIMENSIONS
TABLE 38: UNIT CLEARANCES
G a s P ip e In le t
DETAIL A
Top*
72”
Right
Front
36”
Left
Rear
5 -1 /4
B a s e
P a n
1 7 -1 3 /1 6
V ie w
38
For Drain
Dimensions
See Detail C
6-3/16
24-3/16
59
FRONT
17-3/16
LEFT
For Baserail
Dimensions
See Detail B
o f W a ll A c r o s s fr o m
C o il
†
36”
Bottom
12”
36”
‡
0”
*
Units must be installed outdoors. Overhanging structure or shrubs should not obstruct condenser air discharge outlet.
† To remove the slide-out drain pan, a rear clearance of
60” is required. If space is unavailable, the drain pan
can be removed through the front by separating the
corner wall.
‡ Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.
Unitary Products
036-21058-005-A-0704
DETAIL B
DETAIL C
2-3/8
5 -3 /8
3-3/4
3-9/16
R IG H T
8 0 -5 /8
IN S U L A T E D D E C K U N D E R
C O N D E N S E R S E C T IO N
2 0
2 0
S U P P L Y
6
R E T U R N
2 T Y P .
3 0
IN S U L A T E D D E C K U N D E R
C O M P R E S S O R S E C T IO N
5 0 -1 /2
8 o r 1 4
FIGURE 8 -
Unitary Products
F R O N T
PREDATOR® ROOF CURB DIMENSIONS
39
036-21058-005-A-0704
2 T Y P
2 3
3 0 -1 /2
5 0 -1 /2
4
8 0 -5 /8
2 6
R E T U R N
S U P P L Y
1 0
7 6 -5 /8
5 9 -1 /4
9 4
F R O N T
FIGURE 9 -
6 4 -1 /4
R IG H T
SUNLINE™ TO PREDATOR® TRANSITION ROOF CURBS
32-11/16
6-13/16
Supply
Air
6-13/16
6-13/16
Return
Air
24
LEFT
27-1/2
21
18
21-3/16
19-3/16
17-3/16
12-5/16
7-1/8
14-23/32
FRONT
16-3/8
18-1/16
19-5/8
Bottom
Condensate
Drain
Bottom
Power, Control and
Convenience Outlet
Wiring Entries
Bottom
Gas Supply Entry
63-1/2
FIGURE 10 - BOTTOM DUCT OPENINGS (FROM ABOVE)
40
Unitary Products
036-21058-005-A-0704
18-1/4
Dot Plugs
Return
Air
28-1/4
Supply
Air
18-1/4
18-1/16
2-31/32
5-5/32
28-1/4
31-11/16
FIGURE 11 - REAR DUCT DIMENSIONS
Unitary Products
41
036-21058-005-A-0704
FIGURE 12 - COOLING UNIT WITH GAS HEAT WIRING 230 VOLT DIAGRAM
42
Unitary Products
036-21058-005-A-0704
FIGURE 13 - COOLING UNIT WITH/WITHOUT ELECTRIC HEAT WIRING DIAGRAM
Unitary Products
43
036-21058-005-A-0704
FIGURE 14 - COOLING UNIT WITH GAS HEAT WIRING 460, 575 VOLT AND 50 HZ DIAGRAM
44
Unitary Products
036-21058-005-A-0704
GUIDE SPECIFICATIONS
PREDATOR®
DM 078, 090, 102, 120 & 150
9.0 EER
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility. YORK® Predator® units are convertible single packages with a common
footprint cabinet and common roof curb for all 6-1/2 through
12-1/2 ton models. All units have two compressors with independent refrigeration circuits to provide 2 stages of cooling.
The units were designed for light commercial applications
and can be easily installed on a roof curb, slab, or frame. All
Predator® units are self-contained and assembled on rigid full
perimeter base rails allowing for 3-way forklift access and
overhead rigging. Every unit is completely charged, wired,
piped, and tested at the factory to provide a quick and easy
field installation. All units are convertible between side and
down airflow. Independent economizer designs are used on
side and down discharge applications, as well as all tonnage
sizes. Predator® units are available in the following configurations: cooling only, cooling with electric heat, and cooling with
gas heat. Electric heaters are available as factory-installed
options and field-installed accessories.
fan performance without removing panels or creating bypass
of the coils. Condensate pan shall be slide out design, constructed of a non corrosive material, internally sloped and
conforming to ASHRAE 62-B9 standards. Condensate connection shall be a minimum of ¾” I.D. female and be rigid
mount connection.
DESCRIPTION
OUTDOOR (CONDENSER) FAN ASSEMBLY
Units shall be factory assembled, single package, (Elec/Elec,
Gas/Elec), designed for outdoor installation. Units shall have
a minimum EER of 9.0. They shall have built in field convertible duct connections for down discharge supply/return or
horizontal discharge supply/return and be available with factory installed options or field installed accessories. The units
shall be factory wired, piped and charged with R-22 refrigerant and factory tested prior to shipment. All unit wiring shall
be both numbered and color coded. The cooling performance
shall be rated in accordance with DOE and ARI test procedures. Units shall be CSA certified to ANSI Z21.47 and UL
1995/CAN/CSA No. 236-M90 standards.
The outdoor fans shall be of the direct drive type, discharge
air vertically, have aluminum blades riveted to corrosion
resistant steel spider brackets and shall be dynamically balanced for smooth operation. The outdoor fan motors shall
have permanently lubricated bearings internally protected
against overload conditions and staged independently. A
cleaning window shall be provided on two sides of the units
for coil cleaning.
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel with
exterior surfaces coated with a non-chalking, powder paint
finish, certified at 750 hours salt spray test per ASTM-B117
standards. Indoor blower sections shall be insulated with up
to 1” thick insulation coated on the airside. Aluminum foil
faced insulation shall be used in the unit’s compartments and
be fastened to prevent insulation from entering the air
stream. Cabinet doors shall be hinged with tool-less access
for easy servicing and maintenance. Full perimeter base rails
shall be provided to assure reliable transit of equipment,
overhead rigging, fork truck access and proper sealing on
roof curb applications. Disposable 2” filters shall be furnished
and be accessible through hinged access door. Fan performance measuring ports shall be provided on the outside of
the cabinet to allow accurate air measurements of evaporator
Unitary Products
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable
pitch motor pulley. Job site selected brake horsepower shall
not exceed the motors nameplate horsepower rating plus the
service factor. Units shall be designed to operate within the
service factor. Fan wheel shall be double inlet type with forward curve blades, dynamically balanced to operate
smoothly throughout the entire range of operation. Airflow
design shall be constant volume. Bearings shall be sealed
and permanently lubricated for longer life and no maintenance. Entire blower assembly and motor shall be slide out
design.
REFRIGERANT COMPONENTS
Compressors:
A. Shall be fully hermetic type, direct drive, internally protected with internal high-pressure relief and over temperature protection. The hermetic motor shall be suction gas
cooled and have a voltage range of + or – 10% of the
unit nameplate voltage.
B. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
Coils:
A. Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless internally
enhanced copper tubes with all joints brazed. Special
Phenolic coating shall be available as a factory option.
B. Evaporator and condenser coils shall be of the direct
expansion, draw-thru design.
45
036-21058-005-A-0704
Refrigerant Circuit and Refrigerant Safety Components shall
include:
A. Independent fixed-orifice or thermally operated expansion devices.
B. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
C. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
D. The unit shall have two independent refrigerant circuits,
equally split in 50% capacity increments.
Unit Controls:
A. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on
the 24-volt transformer side.
B. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit
should any of the following standard safety devices trip
and shut off compressor:
C. Loss-of-charge/Low-pressure switch.
(1) High-pressure switch.
(2) Freeze-protection thermostat, evaporator coil. If any
of the above safety devices trip, an LED (light-emitting
diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped.
D. Unit shall incorporate “AUTO RESET” compressor over
temperature, over current protection.
E. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
F. Unit control board shall have on-board diagnostics and
fault code display.
G. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
0 ºF.
H. Control board shall monitor each refrigerant safety
switch independently.
I.
Control board shall retain last 5 fault codes in non-volatile memory, which will not be lost in the event of a power
loss.
GAS HEATING SECTION (IF EQUIPPED)
Heat exchanger and exhaust system shall be constructed of
aluminized steel and shall be designed with induced draft
combustion with post purge logic, energy saving direct spark
ignition, and redundant main gas valve. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 40 ºF. Burners shall be of the in-
46
shot type, constructed of aluminum-coated steel. All gas piping shall enter the unit cabinet at a single location, through
either the side or bottom, without any field modifications. An
integrated control board shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall
be provided with the following minimum protection:
A. Primary and auxiliary high-temperature limit switches.
B. Induced draft pressure sensor.
C. Flame roll out switch (manual reset).
D. Flame proving controls. Unit shall have two independent
stages of capacity (60% 1st stage, 100% 2nd stage).
ELECTRIC HEATING SECTION (IF EQUIPPED)
An electric heating section, with nickel chromium elements,
shall be provided in a range of 9 thru 54 KW, offering two
states of capacity all sizes. The heating section shall have a
primary limit control(s) (automatic reset) to prevent the heating element system from operating at an excessive temperature. The Heating Section assembly shall slide out of the unit
for easy maintenance and service. Units with Electric Heating
Sections shall be wired for a single point power supply with
branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 ºF outdoor temperature, exceeding maximum load criteria of ARI
Standard 210/240. The compressor, with standard controls,
shall be capable of operation down to 0 ºF outdoor temperature. Unit shall be provided with fan time delay to prevent cold
air delivery before heat exchanger warms up. (Gas heat only)
ELECTRICAL REQUIREMENTS - All unit power wiring shall
enter unit cabinet at a single factory provided location and be
capable of side or bottom entry to minimize roof penetrations
and avoid unit field modifications. Separate side and bottom
openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES - Compressor – 5
Years, Heat Exchanger – 10 Years, Elect. Heat Elem. – 5
Years, Parts – 1 Year
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall
be made available by either/or):
1.
ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER – Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, springreturn damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return
air damper assembly to take in outdoor air to meet the
minimum ventilation requirement of the conditioned
space during normal operation. During economizer operation, a mixed-air temperature control shall modulate the
Unitary Products
036-21058-005-A-0704
outdoor and return air damper assembly to prevent the
supply air temperature from dropping below 55 ºF.
Changeover from compressor to economizer operation
shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor
intake opening shall be covered with a rain hood that
matches the exterior of the unit. Water eliminator/filters
shall be provided. Simultaneous economizer/compressor
operation is also possible. Dampers shall fully close on
power loss. Available with barometric relief or power
exhaust.
2.
MOTORIZED OUTDOOR AIR DAMPERS – Outdoor
and return air dampers that are interlocked and positioned by a 2-position, spring-return damper actuator.
The maximum leakage rate for the outdoor air intake
dampers shall not exceed 2% when dampers are fully
closed and operating against a pressure differential of
0.5 IWG. A unit-mounted potentiometer shall be provided
to adjust the outdoor and return air damper assembly to
take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected positions – regardless of the outdoor air enthalpy. Dampers
return to the fully closed position when the indoor fan
motor is de-energized. Dampers shall fully close on
power loss.
•
COIL GUARD - Designed to prevent condenser coil
damage.
•
BAS CONTROLS - Include supply air sensor, return air
sensor, dirty filter indicator and air proving switch.
•
DIRTY FILTER SWITCH – This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally highpressure drop across the filters.
•
BREAKER – An HACR breaker can be factory installed
on gas heat units or cooling units with electric heat.
•
DISCONNECT SWITCH - A disconnect can be factory
installed on a cooling only units sized for the largest electric heat available.
•
STAINLESS STEEL HEAT EXCHANGER – For applications in a corrosive environment, this option provides a
full stainless steel heat exchanger assembly.
•
STAINLESS STEEL DRAIN PAN – Provides years of
trouble-free operation in corrosive environments.
•
SMOKE DETECTOR – A smoke detector can be factory
mounted and wired in the supply and/or return air compartments.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•
ROOF CURB - 14” and 8” high, full perimeter knockdown
curb, with hinged design for quick assembly.
•
BAROMETRIC RELIEF DAMPER – (Unit mounted –
Downflow, Duct Mounted – Horizontal) – Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.
•
PROPANE CONVERSION KIT – Contains new orifices
and gas valve springs to convert from natural to L.P. gas.
•
–60 ºF GAS HEAT KIT – Provides an electric heat kit for
the gas compartment for use in extreme low ambient
conditions.
•
ECONOMIZER (Downflow and Horizontal flow)
•
POWER EXHAUST – (Unit mount – Downflow, Duct
mount – Horizontal flow)
•
DUAL ENTHALPY KIT - Provides a second input to
economizer to monitor return air.
ADDITIONAL FACTORY INSTALLED OPTIONS
•
ALTERNATE INDOOR BLOWER MOTOR – For applications with high restrictions, units are available with
optional indoor blower motors that provide higher static
output and/or higher airflow.
•
CONVENIENCE OUTLET (POWERED/NON-POWERED) – Unit can be provided with an optional 120VAC
GFCI outlet with cover on the corner of the unit housing
the compressors.
•
•
ELECTRIC HEAT - Electric heaters range from 9 kW to
54 kW and are available in all the voltage options of the
base unit.
PHASE MONITOR - Designed to prevent damage in outof-phase condition.
Unitary Products
47
Subject to change without notice. Printed in U.S.A.
Copyright © 2004 by Unitary Products. All rights reserved.
Unitary
Products
Group
5005
York
Drive
036-21058-005-A-0704
Supersedes: 036-21058-004-C-0504
Norman
OK
73069
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement