01-2013:0
Product data sheet
Sheet No.: 1.604.02 - Rev: 0 Page 1 of 5
January, 2013
Date:
FieldQ
Smart - Control Modules
QC34: FOUNDATION™ fieldbus
Description:
This FieldQ Control Module offers an integrated concept for
valve automation. Its compact and robust construction incorporates basic control and feedback functionality and communicates through the FOUNDATION™ fieldbus protocol.
Construction
The Control Module is mounted at the side of the Pneumatic
Module in front of the basic actuator housing. Inside are terminals available, for connecting the bus wiring and a button
board. Two cable entries are available for this purpose.
Features
- FOUNDATION™-Fieldbus digital communication.
- Supports PlantWeb Alerts.
- Supports NAMUR NE-107 Alarms
- Supports both single and double acting actuators.
- One entry for all wiring (control and feedback).
- IPT-technology (Intelligent Position Tracking).
- Initialization by FOUNDATION fieldbus or Push-button for
easy setup of the actuator.
Pressing 4 seconds simultaneously the “Open” and
“Closed” reassignment buttons starts auto-initialization procedure and sets automatically the feedback limit switches.
- Readjustable or Reversible position feedback using the
re-reassignment buttons or by
FOUNDATION fieldbus.
- Adjustable switch points can be adjusted from 5% to
30% before the end of the stroke by
FOUNDATION fieldbus.
- Three indication LED’s for “Status”, “Open” and “Closed”
position. Status LED indicates:
- Initialization procedure running
(blinking),
- Successful initialization procedure (LED is on) or
- No or failed initialization
(flashing)
- Control Module can be easily plugged in the Pneumatic
Module.
Closed reassignment button
FieldQ
terminal
compartment
Status LED
Push
4 sec.
on
off
Status LED:
Open reassignment button
LED = Flashing
on
off
Time
LED = Blinking
General specifications
Material housing
:Aluminium alloy
Cable entries
:2x M20x1.5 or 2x 1/2”NPT
Electrical connections :Internal terminal strip.
:Optional quick connectors: 7/8” or
M12 connector (see page 2)
Enclosure
:IP65 / NEMA 4X
Finish
:Polyester non-TGIC based powder
coating.
Operating media
:Air or inert gasses, filtered at 5 micron.
Temperature
:-20° to +50°C / -4° to 122°F
Dimensions
:See 1.603.01 metric
See 1.603.04 imperial/UNC
See 1.603.02 DIN 3337
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be
obtained from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 813 630 2255 (fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 626 24 515 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.02 - Rev: 0 Page 2 of 5
January, 2013
Date:
FieldQ
Communication Protocol:
Hazardous area executions:
Protocol
:FOUNDATION™ fieldbus
Transmission
:H1, IEC 61158-2
Maximum current
:18mA from bus
Required external :Restrict the power supply
protection current to <600mA.
Control Module QC34 with FOUNDATION fieldbus is available
with optional intrinsically safe (IS) or Non-Incendive/Non
Sparking (NI) approvals as listed below:
Function blocks
The Control Module provides the following function blocks:
- Resource Block (RB)
- Transducer Block (TB)
- Analog Input (AI) Function Block
- Discrete Output (DO) Function Block
- 2x Discrete Input (DI) Function Block
- PID Function Block
Diagnostics and Alerts
Standard FOUNDATION fieldbus diagnostics and alerts provided meets Emerson PlantWeb Alerts standard.
Applicable diagnostics include:
- Travel times for the Open stroke, Close stroke and Average
travel times.
- Cycle Counters for Control Module, Pneumatic Module,
Actuator and Valve
- Time in Position
- Various internal electronic health tests.
- Instrument temperature.
For more detailed information on diagnostics see page 3
and 4.
Options:
Manual Control
- Can be added as kit or factory option in 2 versions,
“Push button” or a “Push and lock” button.
Glands, plugs and quick connectors
- FieldQ Control Modules can be shipped with plastic or
metal glands (M20x1.5 or 1/2”NPT) and rated IP65 or
higher or a prewired quick connector.
- IECEx:Certificate : KEM 07.0045X
:Intrinsically safe*
:Ga Ex ia IIC T4
:Ex iaD 20 T80° / IP65
:Certificate : KEM 07.0046X
:Non-Sparking
:Ex nA II T4
:Ex nL IIC T4
:Ex tD A22 T80°C
- ATEX :Certificate : KEMA 02ATEX1242X
:Intrinsically safe*
: II 1 G Ex ia IIC T4
: II 1 D Ex iaD 20 T80° / IP65
:Certificate : KEMA 02ATEX1258X
:Non-Sparking
: II 3 G Ex nA II T4
: II 3 G Ex nL IIC T4
: II 3 D Ex tD A22 T80°C
- FM :Intrinsically safe, Class I, II, III Div.1,
Groups ABCDEFG, T4, Type4X/IP65
:Class I, Zone 0, AEx ia IIC T4
:Non Incendive, Class I, II, III, Division 2,
:Groups ABCDFG, T4, Type 4X/IP65
:Class I, Zone 2, IIC T4, Type 4X/IP65
-CSA :Certificate: 1477696
:Intrinsically safe, Class I, II, III Div.1,
Groups ABCDEFG, T4
:Ex ia IIC T4, IP65, (Class I, Zone 0/1)
:
Non Incendive: Class I, II, III Div.2,
Groups ABCDFG, T4
:Ex nA II T4 (Class I, Zone 2)
:Ex nL II T4 (Class I, Zone 2)
Ambient temperature:
T4 @ Ta = :-20°C...+50°C IP65
Note: * The assembly of a FieldQ Actuator with the intrinsically safe
QC34 Control Module, may be used in (ATEX) classified
Zones 1, 2 (Gasses) and/or 21, 22 (Dust).
FISCO & FNICO systems
The FieldQ QC34 is suitable for use in a FISCO or FNICO
system in accordance with IEC 60079-27 :2005
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be
obtained from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 813 630 2255 (fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 626 24 515 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.02 - Rev: 0 Page 3 of 5
January, 2013
Date:
FieldQ
FOUNDATION™ fieldbus terminal wiring
Standard PI-filter present.
Detailed Intrinsically safe or Non-Incendive/Non-Sparking wiring instructions, will be shipped with the product, see Installation Guide : DOC.IG.QC34.1
Field wiring
Actuator wiring
+
FF
Power
supply
-
1
2
3
Quick connector pinouts:
(male chassis part)
1
2
7/8" UNC
3
4
4
1
3
2
2
4
1
Brown
Green / Yellow
Blue
M12
Quick
connector
1
2
3
Terminal
Diagnostics and PlantWeb Alerts QC34
FOUNDATION fieldbus
The FieldQ Control Module with FOUNDATION fieldbus communication has diagnostic capabilities. These process parameters can give information about communication condition,
valve and/or actuator unit. It enables to predict failures in
advance and makes maintenance easier to schedule. The
following diagnostics are available for the FieldQ:
1 Timer parameters:
1.Open and Closed travel time
2.High and low limits of Open and Closed travel time
3.Average travel times of last 30 strokes of Open and
Closed travel.
4.High and low limits of average Open and Closed travel
time
2 Cycle Counters
1.Control Module - Counts how many times the Control
Module cycles (read only).
2.Pneumatic Module - Counts how many times the Pneumatic Module cycles.
3.Actuator - Counts how many times the actuator cycles.
4.Valve - Counts how many times the valve cycles.
3 Time In Position
4 Various internal electronic health tests.
PlantWeb Alerts
Wiring dimensions
Solid wire :2.5mm2 max.
Stranded wire :0.2-3.3mm2 or 24-12 AWG
PlantWeb Alerts are alerts that have been predefined and
categorized for the user. These device alerts can be used to
help troubleshoot the instrument (see also page 4). There are
three categories:
Quick connector pinouts:
- The FOUNDATION fieldbus Module can optionally be
equipped with prewired quick connectors. Two versions are
available: 7/8” or M12 (male chassis part).
- Quick connectors, as shown below are excluded for nonIncendive or non-sparking use in hazardous area’s classified
as Zone 2 or 22 or Cl I, II, III, Div. 2.
- Maintenance alerts
A maintenance alert indicates that the device, or some
part of the device, needs maintenance soon.
- Failed alerts,
A failed alert indicates a failure within the device that will
make the device, or some part of the device, non-operational.
- Advisory alerts
An advisory alert indicates a condition that does not have
a direct impact on the device’s primary function. If the
condition is ignored, the device will eventually fail.
These alerts, when enabled, can participate in the DeltaV
alarm interface tools such as the alarm banner, alarm list, and
alarm summary.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be
obtained from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 813 630 2255 (fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 626 24 515 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.02 - Rev: 0 Page 4 of 5
January, 2013
Date:
FieldQ
Diagnostics and PlantWeb Alerts
Alerts & recommended actions
Alert default setting
Advisory
Alerts
Recommended actions
bit 0
Reserved
bit 1
Internal alerts, bad position sensor
bit 2
Internal alerts, bad temperature
sensor
bit 4
Internal alerts, Specified system
temperature exceeded
Internal alerts, Software error
bit 5
Internal alert, travel deviation
bit 6
Internal alerts, Shutdown is set
bit 7
Internal alerts, Undefined error
Counter alerts, Control Module life
cycle exceeded
bit 3
enable
Feedback problem, replace control
n
module when possible
Temperature sensor problem,
replace Control Module when
n
possible
Take corrective actions to bring
n
temperature within specified range.
n
Maintenance
mask *
enable
Fail
mask *
enable
n
y
y
n
n
y
y
n
n
y
y
n
mask *
n
n
n
n
y
n
n
n
Lost position, Check air pressure y
Internal communications problem,
check shutdown configuration for n
restart, Replace Control Module.
n
Control Module life cycle exceedn
ed, Replace Control Module
Pneumatic Module life cycle
exceeded, Replace Pneumatic
n
Module.
Actuator life cycle exceeded, Ren
place actuator.
Valve life cycle exceeded, take
n
Valve requires maintenance.
Time in position exceeded, appron
priate action.
Open travel timer exceeded, check
n
valve system.
Close travel timer exceeded, check
n
valve system.
Check air pressure, check actuator
y
sizing, check valve system.
y
n
n
n
n
n
n
n
y
n
y
n
n
n
y
y
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
y
n
n
n
n
n
n
n
n
y
y
n
n
n
bit 22 Reserved RB NV Memory Failure
y
y
n
n
n
n
bit 23 Reserved TB Electronics Failure
y
n
n
n
n
n
bit 24 Reserved RB Electronics Failure
y
y
n
n
n
n
bit 8
bit 9
Counter alerts, Pneumatic Module
life cycle exceeded
Counter alerts, Actuator life cycle
exceeded
Counter alerts, Valve life cycle
bit 11
exceeded
bit 10
bit 12 Timer alerts: time in position limit
Timer alerts: open travel time limit
exceeded
Timer alerts: close travel time limit
bit 14
exceeded
Initialization Failed (reason from
bit 15
AUTO_INITIALIZATION STATUS)
bit 16 Reserved Primary Value Failure
bit 13
bit 18 Reserved HW/SW Incompatibility
bit 19
Reserved IO Failure (FF card lost
IO board)
Internal communications are lost,
device will act according to shutdown configuration.
y
n
n
n
n
n
n
n
n
n
n
n
bit 20 Reserved Mechanical Failure
bit 21 Reserved TB NV Memory Failure
*) Mask “n” indicates masked out (not visible).
For more detailed information about the configuration of the QC34 FOUNDATION™ fieldbus Module see Reference Manual DOC.RM.QC34.E. This manual is
available for download from www.FieldQ.com.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be
obtained from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 813 630 2255 (fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 626 24 515 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.02 - Rev: 0 Page 5 of 5
Date:
January, 2013
FieldQ
Namur NE-107 Alarms
This section describes the parameter interaction to implement
a FieldQ™ QC34 Control module to the NAMUR NE-107
requirements as a parameter group in the Resource Block.
There are four alarm categories defined as per the NE-107
specification, Failed, Off Specification, Maintenance, and
Check function.
Maintenance Although the output signal is valid, the wear
reserve is nearly exhausted or a functions will soon be restricted due to operational conditions e.g. build-up of deposits
Off Specification Off-spec means that the device is operating outside its specified range or an internal diagnostic indicates deviations from measured or set values due to internal
problems in the device or process characteristics (e.g. bubble
formation in flow metering or valve sticking).
Check Function Output signal temporarily invalid (e.g.
frozen) due to on-going work on the device.
Failed Output signal invalid due to malfunction in the field
device or its peripherals.
Parameter
Mnemonic
FD_CHECK_ACTIVE
Obj
Type
S
Data Type/
Structure
Bit String
Use/Model
Store
Each of these categories share 32 conditions that can be
defined by the device manufacturer. Each condition may be
mapped or not mapped for each category. If a condition is
mapped then it is indicated in the* ACTIVE parameter. If the
condition in the * ACTIVE parameter is not masked by the
corresponding bit in the *_MASK parameter then the condition will be queued for broadcast using the corresponding
*ALM parameter at the associated priority indicated by *PRI
parameter. The 4 categories are defined below.
The conditions are not expected to identify explicitly the root
cause of the condition, but rather to identify it in terms of:
• Replace the device
• Replace a part of the device
• Correct a configuration problem
• Fix something outside of the device
The above list is all that the operator needs to know to restore
his process functionality and if there are more than 31 device
conditions they should be grouped by definition into these bit
Size
Valid
Range
Initial
Value
C/FD Active
D
4
FD_CHECK_ALM
R
DS-87
C/Alarm
D
15
FD_CHECK_MAP
S
Bit String
C/Contained
S
4
FD_CHECK_MASK
S
Bit String
C/Contained
S
4
FD_CHECK_PRI
S
Unsigned8
C/Alert Priority
S
1
FD_EXTENDED_ACTIVE_n
S
Bit String
C/Contained
D
4
FD_EXTENDED_MAP_n
S
Bit String
C/Contained
S
4
FD_FAIL_ACTIVE
S
Bit String
C/FD Active
D
4
FD_FAIL_ALM
R
DS-87
C/Alarm
D
15
FD_FAIL_MAP
S
Bit String
C/Contained
S
4
FD_FAIL_MASK
S
Bit String
C/Contained
S
4
FD_FAIL_PRI
S
Unsigned8
C/Alert Priority
S
1
FD_MAINT_ACTIVE
S
Bit String
C/FD Active
D
4
FD_MAINT_ALM
R
DS-87
C/Alarm
D
15
FD_MAINT_MAP
S
Bit String
C/Contained
S
4
FD_MAINT_MASK
S
Bit String
C/Contained
S
4
FD_MAINT_PRI
S
Unsigned8
C/Alert Priority
S
1
FD_OFFSPEC_ACTIVE
S
Bit String
C/FD Active
D
4
FD_OFFSPEC_ALM
R
DS-87
C/Alarm
D
15
FD_OFFSPEC_MAP
S
Bit String
C/Contained
S
4
FD_OFFSPEC_MASK
S
Bit String
C/Contained
S
4
FD_OFFSPEC_PRI
S
Unsigned8
C/Alert Priority
S
1
0 - 15
0
FD_RECOMMEN_ACT
S
Unsigned16
C/Contained
D
2
0
FD_SIMULATE
R
DS-89
C/FD Simulate
D
9
1 – manf
spec
FD_VER
S
Unsigned16
C/Contained
S
2
Permission
Other
Read only
Range
Check
ALARM
ALARM
0 - 15
0
ALARM
Yes
Read only
Read only
ALARM
ALARM
0 - 15
0
ALARM
Yes
Read only
ALARM
ALARM
0 - 15
0
ALARM
Yes
Read only
ALARM
ALARM
ALARM
Yes
Read only
disabled
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be
obtained from our web site www.Fieldq.com or from your nearest Valve Automation Center: