INSTALLATION INSTRUCTIONS FOR EXPOSED GEM•2®
PISTON TYPE WATER CLOSET AND URINAL FLUSHOMETERS
Closet Flushometer for
1½” Top Spud
MODELS 110/111, 115 & 136
Urinal Flushometer for
1¼” Top Spud
MODEL 180
Urinal Flushometer for
¾” Top Spud
MODEL 186
Made in the U.S.A.
Closet Flushometer for
1½” Back Spud
MODELS 120, 121, 122 & 137
LIMITED WARRANTY
Sloan Valve Company warrants its Gem•2® Flushometers to be made of first class materials, free from defects of material or workmanship under normal use and to
perform the service for which they are intended in a thoroughly reliable and efficient manner when properly installed and serviced, for a period of three years (1 year
for special finishes) from date of purchase. During this period, Sloan Valve Company will, at its option, repair or replace any part or parts which prove to be thus
defective if returned to Sloan Valve Company, at customer’s cost, and this shall be the sole remedy available under this warranty. No claims will be allowed for labor,
transportation or other incidental costs. This warranty extends only to persons or organizations who purchase Sloan Valve Company’s products directly from Sloan Valve
Company for purpose of resale.
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. IN NO EVENT IS SLOAN VALVE COMPANY
RESPONSIBLE FOR ANY CONSEQUENTIAL DAMAGES OF ANY MEASURE WHATSOEVER.
VALVE ROUGH-IN
MODELS 110/111, 115
MODELS 120, 121, 122
MODEL 137
MODEL 136
MODEL 180
MODEL 186
NOTE: Requires 1” I.P.S.
(DN 25 mm) Supply.
NOTES:
• WHEN MOUNTED ON AN ADA ACCESSIBLE
BOWL, THE ROUGH-IN TO THE SUPPLY
INLET SHOULD BE NO HIGHER THAN 37½”
(953 mm) OR THE HANDLE WILL EXCEED
MAXIMUM HEIGHT ALLOWANCES UNDER
ADA GUIDELINES.
• NEW ADAAG GUIDELINES ALLOW FOR SPLIT
OR OFFSET GRAB BARS, CHECK WITH
LOCAL AUTHORITIES OR REFERENCE
SECTION 604.5.2 OF ADAAG.
† 1” CONTROL STOP IS AVAILABLE WITH
WHITWORTH THREAD.
2
!!! IMPORTANT !!!
With the exception of Control Stop Inlet, DO NOT use pipe sealant
or plumbing grease on any valve component or coupling!
PRIOR TO INSTALLATION
Before you install the GEM•2® Flushometer, be sure the items listed below
are installed. Also, refer to the rough-in diagram on Page 2.
• Closet/urinal fixture
• Drain line
• Water supply line
!!! IMPORTANT !!!
Never open Control Stop to where the flow from the valve
exceeds the flow capability of the fixture. In the event of a
valve failure, the fixture must be able to accommodate a
continuous flow from the valve.
Important:
• ALL PLUMBING SHOULD BE INSTALLED IN ACCORDANCE WITH
APPLICABLE CODES AND REGULATIONS.
• WATER SUPPLY LINES MUST BE SIZED TO PROVIDE AN ADEQUATE
VOLUME OF WATER FOR EACH FIXTURE.
• WHEN INSTALLING A FLUSHOMETER, IT IS IMPORTANT THAT THE
FLUSH MODEL MATCHES THE REQUIREMENTS OF THE PLUMBING
FIXTURE.
• FLUSH ALL WATER LINES PRIOR TO MAKING CONNECTIONS.
!!! IMPORTANT !!!
Protect the chrome or special finish of Gem•2 Flushometers — DO
NOT USE toothed tools to install or service these valves. Use a
Sloan A-50 Super-Wrench™, Sloan A-109 Plier Wrench or smooth
jawed spud wrench to secure all couplings. Also see “Care and
Cleaning” section of this manual.
The Sloan GEM•2® Flushometer is designed to operate with 10 to 100 psi
(69 to 689 kPa) of water pressure. THE MINIMUM PRESSURE REQUIRED
TO THE VALVE IS DETERMINED BY THE TYPE OF FIXTURE SELECTED.
Consult fixture manufacturer for minimum pressure requirements. Most Low
Consumption water closets (1.6 gpf/6.0 Lpf) require a minimum flowing
pressure of 25 psi (172 kPa).
!!! IMPORTANT !!!
This product contains mechanical and/or electrical components
that are subject to normal wear. These components should be
checked on a regular basis and replaced as needed to maintain
the valve’s performance.
TOOLS REQUIRED FOR INSTALLATION
If you have questions about how to install your Gem•2 Flushometer,
consult your local Sloan Representative or call Sloan Installation
Engineering Department at:
• Straight blade screwdriver
• Sloan A-50 Super-Wrench™, Sloan A-109 Plier Wrench or smooth
jawed spud wrench
1
A
B
C
1-888-SLOAN-14 (1-888-756-2614) OR 1-847-233-2016
Install Optional Sweat Solder
Adapter (only if your supply pipe
does not have a male thread)
Measure from finished
wall to C/L of Fixture
Spud. Cut pipe 1¼"
(32 mm) shorter than
this measurement.
Chamfer O.D. and I.D. of
water supply pipe.
2
A
FINISHED WALL
Measure from finished
wall to first thread of
Adapter or threaded
supply pipe (dimension
“X”). Cut Cover Tube to
this length.
WATER
SUPPLY PIPE
SWEAT
SOLDER ADAPTER
COVER TUBE
WATER SUPPLY PIPE
1-1/4”
(32 mm)
B
Slide Threaded Adapter
fully onto pipe.
Sweat solder the Adapter
to pipe.
Install Cover Tube, Wall Flange
and Control Stop to supply pipe
Slide Cover Tube over
pipe. Slide Wall Flange
over Cover Tube until
against wall.
WALL
FLANGE
SWEAT
SOLDER
ADAPTER
C
C/L OF
FIXTURE
SPUD
SET SCREW
Thread Control Stop onto pipe.
Tighten with a wrench.
SET SCREW
!!! IMPORTANT !!!
With the exception of Control Stop Inlet, DO NOT use pipe
sealant or plumbing grease on any valve component or
coupling!
SUPPLY
FLANGE
D
3
Tighten Set Screw with a 1/16” hex
wrench. DO NOT install Vandal
Resistant Stop Cap at this time.
IRON PIPE NIPPLE OR COPPER PIPE
WITH SWEAT SOLDER ADAPTER
COVER TUBE (COVERING
TUBE AND CAST SET SCREW
AVAILABLE IN “YBYC” SWEAT
SOLDER KIT)
BAK-CHEK®
CONTROL STOP
CONTROL
STOP CAP
Install Vacuum Breaker Flush
Connection
3
A
4A
Slide Spud Coupling, Nylon Slip Gasket, Rubber Gasket and Spud
Flange over Vacuum Breaker Tube.
MODELS 120,
121, 122, 137
MODELS 110/111,
115, 136
VACUUM
BREAKER
TUBE
MODEL 180
ELBOW FLUSH
CONNECTION
B
Align Flushometer directly above
the Vacuum Breaker Flush
Connection by sliding the
Flushometer Body IN or OUT as
needed. Tighten Vacuum Breaker
Coupling by hand.
VACUUM
BREAKER
TUBE
SPUD FLANGE
NYLON SLIP
GASKET
RUBBER
GASKET
SPUD FLANGE
NYLON
SLIP
GASKET
RUBBER
GASKET
SPUD COUPLING
NOTE
NYLON SLIP
GASKET
RUBBER
GASKET
Maximum adjustment of the Sloan Adjustable Tailpiece is
1/2" (13 mm) IN or OUT from the standard 4-3/4" (121 mm)
(centerline of Flushometer to centerline of Control Stop).
SPUD FLANGE
B
Insert Tube into Fixture Spud.
C
Hand tighten Spud Coupling onto Fixture Spud.
If roughing-in measurement exceeds 5-1/4” (133 mm),
consult factory for longer tailpiece.
NOTE
On valves furnished less vacuum breaker (XYV Variation) connect flush
tube to the bottom of the valve using the slip gasket supplied.
C
Align Flushometer Body and securely tighten first the Tailpiece
Coupling (1), then the Vacuum Breaker Coupling (2), and finally
the Spud Coupling (3). Use a wrench to tighten these couplings in
the order shown.
D
If not installed, install Handle Assembly with Gasket to handle
opening on Flushometer Body. Tighten Handle Assembly securely.
5
Install Flushometer (Continued)
A
CONTROL
STOP
TAILPIECE COUPLING
1
HANDLE
ASSEMBLY
Lubricate tailpiece O-ring with
water. Insert Adjustable Tailpiece
into Control Stop. Tighten
Tailpiece Coupling by hand.
SPUD COUPLING
SPUD COUPLING
4B
A
MODEL 186
VACUUM
BREAKER
Install Flushometer
Flush Out Supply Line
Make sure Control Stop
is CLOSED and remove
Flushometer Cover.
FLUSHOMETER
BODY
B
O-RING
GASKET
Lift out Piston Assembly.
ADJUSTABLE TAILPIECE
G-44 FRICTION
RING
VACUUM
BREAKER
COUPLING
VACUUM
BREAKER
REPAIR
KIT
2
C
SPUD
COUPLING
VACUUM
BREAKER
FLUSH
CONNECTION
Install Flushometer Cover wrench
tight. Open Control Stop to flush
supply line. Close Control Stop
and remove Flushometer Cover.
3
C/L
FIXTURE
4-3/4”
(121 mm)
±1/2”
(13 mm)
D
C/L
SUPPLY
4
Reinstall Piston Assembly and
Flushometer Cover. Tighten
Flushometer Cover wrench tight.
6
A
Adjust Control Stop and Install
Vandal Resistant Stop Cap
Open Control Stop COUNTERCLOCKWISE 1/2 turn from closed
position.
TURN COUNTERCLOCKWISE TO OPEN
B
C
Activate
Flushometer.
TURN CLOCKWISE
TO CLOSE
Adjust Control Stop after each flush until the rate of flow delivered
properly cleanses the fixture.
!!! IMPORTANT !!!
The Sloan Gem•2 Flushometer is engineered for quiet operation.
Excessive water flow creates noise, while too little water flow may not
satisfy the needs of the fixture. Proper adjustment is made when
plumbing fixture is cleansed after each flush without splashing water out
from the lip AND a quiet flushing cycle is achieved.
Never open Control Stop to where the flow from the valve exceeds the
flow capability of the fixture. In the event of a valve failure, the fixture
must be able to accommodate a continuous flow from the valve.
CONTROL STOP CAP
D
Install Vandal Resistant Control
Stop Cap onto Control Stop.
H-700-A BAK CHEK® CONTROL STOP
TROUBLESHOOTING GUIDE
B. Line pressure has dropped and is not sufficient to force Relief Valve to seat.
Shut off all control stops until pressure has been restored, then open them
again.
C. 3.5 gpf Closet Piston has been used in a 1.0 or 1.5 gpf Urinal or on a 1.6 gpf
Toilet. Replace with proper Piston.
D. G-21 Main Seat is fouled with debris or is worn. Clean or replace G-21 Main
Seat.
1. Valve does not function (no flush).
A. Control Stop or Main Valve is Closed. Open Control Stop or Main Valve.
B. Handle Assembly is worn. Replace Sloan Handle Assembly (G-143-A).
C. Relief Valve is worn and sticking in UP position. Replace Piston.
2. Volume of water is not sufficient to siphon fixture.
A. Control Stop not open enough. Adjust Control Stop for desired delivery of
water.
B. Urinal Piston Parts inside a Closet Flushometer. Replace Piston Parts with
proper Closet Piston.
C. Low Consumption Flushometer installed on a non-Low Consumption fixture.
Replace with proper Piston Kit.
D. Inadequate volume or pressure at supply. Increase water pressure or supply
(flow) to Flushometer. Consult Factory for assistance.
5. Leaking at Handle Assembly.
A. The B-39 Seal is worn or deteriorated. Install new B-39 Seal. NOTE: The B-39
Seal will easily slide onto the Bushing if it is wet.
B. Handle gasket has been omitted. Replace Sloan Handle Assembly (G-143-A).
C. Valve Handle Bushing is worn. Replace Sloan Handle Assembly (G-143-A).
Refer to the GEM•2 Flushometer Maintenance Guide for additional
Troubleshooting and Repair Part information.
3. Length of flush is too short (Short Flushing) or Flushometer
closes off immediately.
A. Piston Assembly is not hand-tight. Screw the assembly hand-tight.
B. Enlarged Bypass orifice from corrosion or damage. Install NEW Inside Piston
Kit to correct problem and update Flushometer.
C. Urinal Piston in Closet Flushometer. Replace Piston with proper Closet Piston.
D. Low Consumption Piston installed in non-Low Consumption fixture. Replace
Piston with proper Closet Piston.
E. Handle Assembly is worn. Replace Sloan Handle Assembly (G-143-A).
When assistance is required, please contact Sloan Valve Company
Installation Engineering Department at:
1-888-SLOAN-14 (1-888-756-2614) OR 1-847-233-2016
CARE AND CLEANING OF CHROME AND SPECIAL
FINISHES
4. Length of flush is too long (Long Flushing) or fails to close off.
DO NOT use abrasive or chemical cleaners (including chlorine bleach) to
clean Flushometers that may dull the luster and attack the chrome or special
decorative finishes. Use ONLY mild soap and water, then wipe dry with clean
cloth or towel.
While cleaning the bathroom tile, protect the Flushometer from any
splattering of cleaner. Acids and cleaning fluids will discolor or remove
chrome plating.
A. Piston is not seating properly or Bypass orifice is clogged because of foreign
material, or Bypass orifice is closed by an invisible gelatinous film from
“over-treated” water.
Disassemble the working parts and wash thoroughly. NOTE: SIZE OF THE
ORIFICE IN THE BYPASS IS OF UTMOST IMPORTANCE FOR THE PROPER
METERING OF WATER INTO THE UPPER CHAMBER OF THE FLUSHOMETER.
DO NOT ENLARGE OR DAMAGE THIS ORIFICE. REPLACE PISTON IF
CLEANING DOES NOT CORRECT PROBLEM.
5
PARTS LIST
8§
3
7
1
2
4D ‡
4A ‡
4B ‡
4C ‡
6B
6C
5
6A
6A
Item
No.
1
2
3
4A
Part
No.
†
G-143-A
H-700-A
V-500-AA
V-500-AA
4B
V-500-AA
4C
V-500-AA
4D
V-500-A
Description
Valve Assembly
Handle Assembly
Bak-Chek ® Control Stop
1-1/2" (38 mm) x 9" (229 mm) Vacuum Breaker
Assembly CP (Model 110/111) ‡
1-1/2" (38 mm) x 21-1/2" (546 mm) Vacuum Breaker
Assembly CP (Model 115) ‡
1-1/4" (32 mm) x 9" (229 mm) Vacuum Breaker
Assembly CP (Model 180) ‡
3/4" (19 mm) x 9" (229 mm) Vacuum Breaker
Assembly CP (Model 186) ‡
1-1/2" (38 mm) Vacuum Breaker Assembly CP ‡
Item
No.
5
6A
6B
6C
7
8
Part
Description
No.
F-109
1-1/2" (38 mm) Elbow Flush Connection
CR-1010-A 1-1/2" (38 mm) Spud Coupling Assembly
(Models 110/111, 115, 120, 121 & 122)
CR-1009-A 1-1/4" (32 mm) Spud Coupling Assembly
(Model 180)
CR-1008-A 3/4" (19 mm) Spud Coupling Assembly (Model 186)
F-7
Supply Flange (Supplied when Valve is Not Ordered
with Sweat Solder Kit)
H-633-AA 1" (25 mm) Sweat Solder Kit with Cast Set Screw
Flange (YBYC Variation) §
H-636-AA 3/4" (19 mm) Sweat Solder Kit with Cast Set Screw
Flange (YBYC Variation) §
† Part number varies with valve model variation; consult factory.
‡ If valve was specified less vacuum breaker (XYV variation), a straight flush tube is supplied in place of the vacuum breaker assembly. Consult Factory for part
number.
§ Furnished only when ordered with YBYC variation.
For a complete listing of GEM•2 Flushometer Valve Components and Repair Kits, refer to the Maintenance Guide or consult your nearest plumbing wholesaler.
For optimum water conservation and Flushometer performance, use only Genuine Sloan Parts.
NOTICE: The information contained in this document is subject to change without notice.
11170 SW 5TH STREET, SUITE 100 - BEAVERTON, OR 97005
PHONE: 1-800-440-5556 - FAX: 1-503-643-8224
http://www.airdelights.com - Customer_Service@AirDelights.com
Printed in the U.S.A. 04-07