3 150 RMU7..B Universal Controllers
3
150
Synco™ 700
Universal Controllers
RMU7..B
• With yearly timeswitch
• Each type of controller is supplied with 5 different ventilation / air conditioning plants
preprogrammed
• Freely configurable controller, for optimum adaptation to the relevant type of plant
• Modular expandable with option modules RMZ785, RMZ787 and RMZ788
• Menu-driven operation with separate operator unit (plug-in type or detached)
• Konnex bus connection for operation and process information
Use
For use on basic to complex ventilation, air conditioning and chilled water plants.
The universal controllers are designed to handle the following controlled variables:
Temperature, relative / absolute humidity, pressure / differential pressure, airflow, indoor
air quality and enthalpy.
Functions
Timeswitch and
operating modes
CE1N3150en
30 May 2008
• Yearly timeswitch with automatic summer- / wintertime changeover
• 7-day program (6 switching points per day) and yearly program for holidays / special
days (16 periods)
• Selection of operating mode
with local operator unit: auto, comfort, precomfort, economy and protection or via
status inputs: Comfort, precomfort, economy and protection
• Room controller combination with multiple ventilation controllers or heating controllers
via the Konnex bus. Exchange information such as room temperature, operating
mode and setpoints
• Display of the current operating mode (comfort, precomfort, economy and protection),
including the reason for it
Building Technologies
HVAC Products
Setpoints
• Depending on the sequence controller: Individually adjustable heating and cooling
setpoints (or maximum and minimum setpoints) for comfort and precomfort modes
• Predefined room temperature setpoint with room unit or relative setpoint adjuster
(passive)
• Depending on the sequence controller: Predefined setpoint with absolute remote
setpoint adjuster (active or passive)
• Room temperature setpoint with summer and / or winter compensation
• Depending on the sequence controller: Setpoint shift depending on a sensor,
selectable start and end points
Universal inputs
8 universal inputs for:
• Passive or active analog input signals of the following measured values (°C, %, g / kg,
kJ / kg, W / m2, bar, mbar, m / s, Pa, and ppm, Universal 000.0, Universal 0000, pulse)
• Digital input signals (potential-free contacts)
Additional I/Os
through extension
modules
Additional inputs and outputs to extend functionality.
Total max. 4 extension modules per RMU7..B can be connected.
Selection from:
• max. 1 universal module RMZ785 (8 universal inputs)
• max. 2 universal modules RMZ787 (4 universal inputs and 4 relay outputs)
• max. 2 universal modules RMZ788 (4 universal inputs, 2 relay outputs and 2 analog
outputs)
Data acquisition
Pulse meter (for display only, not for billing purposes).
Two meters available to acquire consumption data.
Processes pulses from gas, hot water, low-temperature hot water, chilled water,
electricity meters.
• Pulse metering (Wh, kWh, MWh, kJ, MJ, GJ, ml, l, m3, heating costs units, BTU, no
unit)
Trend data display
Two independent trend channels available to log measured values for a set period.
KNX bus room temperature and outside air temperatures can be logged in addition to
logical device inputs.
Control functions
• Sequence controller for 3 heating sequences (reverse acting) and 2 cooling
sequences (direct acting), can be used as a controller providing P, PI or PID mode, or
as a differential controller
• Controller can be configured as a room / supply air temperature cascade controller
with limitation of the supply air temperature
• Each sequence can be assigned modulating control (modulating output, step switch,
mixed air damper, heat recovery equipment) and a pump. Up to 3 sequences can act
on the same analog control (e.g. priority cooling / dehumidification)
• General limitation function (minimum / maximum with PI mode per sequence
controller, either as absolute limitation (e.g. for the supply air temperature or supply
air humidity), or as relative temperature limitation (e.g. maximum limitation of the
room / supply air temperature differential). Limitation acts on all sequences.
Minimum limitation for switched on cooling (example: cooling with direct expansion
cooler battery) can be set to a lower setpoint
• Sequence limitation function with PI mode per sequence controller, can be defined as
minimum or maximum limitation. Limitation acts on a single sequence
(e.g. heat recovery anti-icing protection or maximum limitation of the air heating coil’s
return temperature)
• Lock individual sequences by outside air temperature
• Messages about deviations of setpoint / actual value per sequence controller
2/18
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
CE1N3150en
30 May 2008
Switching and
supervisory functions
Fans
Control and monitor supply air and extract air fan with preselected command,
preselected command feedback signal and operating hours meter.
• Single-speed fan (recirculated air operation possible)
• 2-speed fan (lock the second speed per outside air temperature)
• Speed-controlled fan, including pressure or volume flow controller
Pumps
Control and supervise up to 4 simple or twin pumps
• Pump kick
• Permanent ON for low outside air temperatures
• ON after last sequence controller or per operating mode
• Plant stop for pump fault depending on the outside temperature
Heat recovery
Control heat recovery
• Maximum economy changeover
• Efficiency monitoring
• Enabling relay for heat recovery
Mixed air damper
Control mixed air damper
• Maximum economy changeover
• Minimum position
• Startup and maximum position depending on the outside air temperature
• Mixed air damper temperature control at a constant setpoint (economizer)
Linear step switch
Control of up to 3 multistage aggregates, each with 1 linear step switch with a
maximum of 4 relay outputs 1 analog output.
Binary step switch
Control of up to 3 multistage aggregates, each with 1 binary step switch with a
maximum of 4 relay outputs 1 analog output.
Variable step switch
Control of 2 aggregates with a variable step switch with 6 or 4 steps and one analog
output each.
Logic functions
Two freely configurable logic function blocks are available to process multiple logically
linked universal input variables.
• Configurable logic functions
• Adjustable switch-on and switch-off delay and minimum switch-on and switch-off time
• Operating switch (auto, off, on), configurable for manual control
Additional timeswitch
Additional timeswitch with 6 daily switch-on or switch-off times.
• Operating switch (auto, off, on), configurable for manual control
Demand-dependent ventilation (CO2/VOC)
Demand-dependent ventilation (CO2 / VOC), acting on the air dampers or the variable
speed / multispeed fans.
3/18
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
CE1N3150en
30 May 2008
Frost protection
2-stage frost protection function (modulating / 2-position) or frost protection thermostat
(heating sequences delivering 100 % output, fans switched off).
• Frost protection and 3 frost protection monitors
Preheating function
Preheating function is available
Sustained mode
• Sustained heating and cooling mode during occupied or unoccupied periods
Night cooling
Night purging during unoccupied periods in the summer
Heating/cooling demand
• Output of heat and cooling demand signal (relay and DC 0..10 V)
• Collect, evaluate and forward heat and cooling demand from and via the KNX bus
Can also be configured:
• Modeling output (e.g. for demand-dependent setpoint shift of a refrigeration machine)
• Relay output (e.g. to switch-on/switch-off a refrigeration machine)
• Demand-dependent setpoint shift acting on a primary controller
• Adjustable setpoint increase for use with primary controller
Switching heating/cooling
If a 2-pipe system (heating/cooling) is used, you can switch heating/cooling via a digital
or analog input, via an operating mode switch (auto, heating, cooling), by date or via
the KNX bus. The heating/cooling signal can be sent to the KNX bus or issued via a
relay.
Fault messages
Fault indication with red LED, acknowledgement with button.
The following options are available:
• 2 relay outputs as fault message relay
• 10 universal inputs as fault message inputs
• 4 predefined fault inputs (filter supervision, fire shutdown, "supply air smoke
extraction" and "extract air smoke extraction")
4/18
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
CE1N3150en
30 May 2008
Bus functions
•
•
•
•
•
•
•
•
•
•
•
Service and operating
functions
•
•
•
•
Remote operation of Konnex functions with RMZ792 bus operating unit
Room operator unit with the relevant functions
Indication of fault status messages delivered by other devices on the bus
Delivery of a common fault status message from all devices on the bus to a fault relay
Time synchronization
Passing on and adoption of outside temperature signal
Sending or receiving the yearly timeswitch schedule (holidays / special days) from
some other controller
Sending or receiving the 7-day program or the yearly program for the
holidays/ special days of any other controller
Generating and sending a demand signal (hot water, chilled water) to the primary
controller or the hot water / chilled water source
Receiving and evaluating refrigeration demand signals if configured as a primary
controller or hot water / chilled water source
Common control strategy of a ventilation controller with a heating controller or
multiple ventilation controllers to control of the same room
Outside temperature simulation
Wiring test
Data backup
Display of setpoints, actual values and active limitations
5/18
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
CE1N3150en
30 May 2008
Type summary
Controller
Type
RMU710B-1
RMU720B-1
RMU730B-1
RMU710B-2
RMU720B-2
RMU730B-2
RMU710B-3
RMU720B-3
RMU730B-3
RMU710B-4
RMU720B-4
RMU730B-4
RMU710B-5
RMU720B-5
RMU730B-5
Accessories
Operator / service units
Option modules
Universal
inputs
6
8
8
6
8
8
6
8
8
6
8
8
6
8
8
Positioning
outputs
2
3
4
2
3
4
2
3
4
2
3
4
2
3
4
Default languages
Switching
Open
outputs control loop
2
1
de, fr, it, es
4
2
de, fr, it, es
6
3
de, fr, it, es
2
1
de, en, fr, nl
4
2
de, en, fr, nl
6
3
de, en, fr, nl
2
1
sv, fi, no, da
4
2
sv, fi, no, da
6
3
sv, fi, no, da
2
1
pl, cs, sk, hu, ru, bg
4
2
pl, cs, sk, hu, ru, bg
6
3
pl, cs, sk, hu, ru, bg
2
1
ro, sl, sr, hr, el, tr
4
2
ro, sl, sr, hr, el, tr
6
3
ro, sl, sr, hr, el, tr
Name
Operator unit, plug-in type
Operator unit, detached
Service tool
Universal module with 8 universal inputs
Universal module with 4 universal inputs and 4 relay
outputs
Universal module with 4 universal inputs, 2 relay
outputs and 2 analog DC 0...10 V outputs.
Module connector for detached extension modules
Type
RMZ790
RMZ791
OCI700.1
RMZ785
RMZ787
Data sheet
N3111
N3112
N5655
N3146
N3146
RMZ788
N3146
RMZ780
N3138
Ordering and delivery
When ordering, please provide the name and type reference of the controller, for
example, Universal controller RMU730B-2.
The devices listed under “Accessories“ must be ordered as separate items.
Each controller is supplied as follows:
• Complete with 5 standard applications plus one empty application each of basic types
A, P, C and U (configuration must be adapted)
• With operating languages (refer to "Type summary")
Equipment combinations
For equipment combinations, refer to "Product range description: Synco™ 700", or to
the document covering the selected application.
6/18
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
CE1N3150en
30 May 2008
Product documentation
Name
Product range description: Synco™ 700
Basic Documentation: Universal Controllers RMU710B, RMU720B,
RMU730B
Installation Instructions (G3150xx): RMB795, RMS705, RMU7..B
Operating Instructions de, en, fr, nl (B3144x2):
Universal controller RMU7..B.
Data sheet: Konnex bus
Basis documentation: Communication via Konnex bus
CE Declaration of conformity: HVAC Controls Synco™ 700 Range
Environmental product declaration
Ordering number
CE1S3110en
CE1P3150en
74 319 0591 0
74 319 0350 0
CE1N3127en
CE1P3127en
CE1T3110xx
CE1E3110en01
Technical design
Each type of controller has 5 applications of ventilation / air conditioning plants
preprogrammed. Some of them require extension modules.
When commissioning a plant, the relevant plant type must be entered. All associated
functions, terminal assignments, settings and displays will then automatically be
activated, and parameters not required will be deactivated.
In addition, each type of universal controller has 4 empty applications loaded:
• 1 for basic type A (ventilation controller)
• 1 for basic type P (primary air handling)
• 1 for basic type C (demand-dependent chilled water controller)
• 1 for basic type U (universal controller)
Using the operator unit RMZ790 or RMZ791, the controller permits:
• Activation of a preprogrammed application
• Modification of a preprogrammed application
• Free configuration of applications
• Optimization of the controller settings
For operating actions of the functions, refer to the Basic Documentation CE1P3150en.
7/18
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
CE1N3150en
30 May 2008
Version
The universal controller consists of terminal base and controller insert. It has a plastic
housing with the printed circuit boards, 2 terminal levels and accommodates the
connecting elements (electrical and mechanical) for one extension module (refer to
"Accessories").
It can be mounted on a top hat rail conforming to EN 60 715-TH35-7.5, or on a wall.
The controller is operated either with the plug-in type or detached operator unit (refer to
"Accessories").
1
4
Legend
2
11
3
3144Z01
Operating, display
and connecting
elements
1
2
3
4
5
6
7
8
9
10
11
5
6 7
8
9
5
11
10
Connection facility for the service tool (RJ45 connector)
Removable cover with connection facility for the operator unit
LED "RUN" device operating status display; with the following meanings:
LED lit:
Supply voltage, no fault in application and periphery
LED off:
No supply voltage or application fault / periphery
Button " " with LED (red) displays a fault status message and its acknowledgement;
meanings as follows:
LED blinking:
Fault status message, ready to acknowledge
LED lit:
Fault status message still pending but not yet reset
LED off:
No fault status message
Press button:
Acknowledge or reset fault
Openings for plug-in type operator unit RMZ790
Programming button "Prog": Learning button to changeover between the normal mode and the
addressing mode to assume the physical device address (requires tool to operate)
Programming LED "Prog" to display normal mode (LED off) or addressing mode (LED on) to
assume physical device address
Catch for fitting the controller to a top hat rail
Fixing facility for a cable tie (cable strain relief)
Electrical and mechanical connection elements for extension module
Rest for the terminal cover
Engineering notes
• AC 24 V voltage required to power the controller. It must meet requirements for
SELV / PELV (safety extra low-voltage)
• The transformers used must be safety isolating transformers featuring double
insulation to EN 60 742 or EN 61 558-2-6; they must be suited for 100 % duty
• Fuses, switches, wiring and earthing must be in compliance with local regulations
• Sensor wires should not be run parallel to mains carrying wires that power fans,
actuators, pumps, etc.
• It is recommended to use the standard applications provided. Specific plant situations
may require certain adaptations
• Total max. 4 extension modules per RMU7..B can be connected.
Select from 1 RMZ785, 2 RMZ787 or 2 RMZ788
8/18
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
CE1N3150en
30 May 2008
Mounting and installation notes
3144Z03
Low voltage side
Mains voltage side
• Controllers and extension modules are designed for:
– Mounting in a standard cabinet as per DIN 43 880.
– Wall mounting on an existing tophat rail (EN 50 022-35x7.5).
– Wall mounting using two fixing screws.
– Flush panel mounting.
• Not permitted in wet or damp spaces. The permissible environmental conditions must
be observed
• If the controller is not operated inside a control panel, use the detached operator unit
RMZ791 in place of the plug-in type operator unit RMZ790
• Disconnect the system from the power supply prior to mounting and installation the
controller
• The controller insert may not be removed from the terminal base!
• If extension modules are used, they must be attached to the right side of the
controller in the correct order in accordance with the internal configuration
• The extension modules require no wiring between themselves or to the controller; the
electrical connections are made automatically when attaching the modules. If it is not
possible to arrange the extension modules side by side, the first of the detached
modules must be connected to the last previous module or to the controller using the
RMZ780 module connector. In that case, the cumulated cable length may not exceed
10 m
• All connection terminals for protective extra low-voltage (sensors, data bus) are
located in the upper half of the unit, those for mains voltage (actuators and pumps) at
the bottom
• Each terminal (spring cage terminal) can only accommodate one solid wire or one
stranded wire. Cables must be stripped to 7 to 8 mm to connect. To introduce the
cables into the spring cage terminals and to remove them, a screw driver size 0 or 1
required. Cable strain relief can be provided with the help of the fixing facility for cable
ties
• The controller mounted on a top hat rail together with modules can only be removed
from the rail after the module directly attached to the controller has been removed
• The controller is supplied complete with installation instructions and operating
instructions
Commissioning notes
• Using the operator unit RMZ790 or RMZ791, or the service tool, staff trained by
HVAC Products and having the required access rights can change the configuration
and the parameters online or offline at any time
• During the commissioning process, the application is deactivated and the outputs are
in a defined off state. This means that no process and alarm signals will then be
delivered to the bus
• On completion of the configuration, the controller automatically makes a new start
• When leaving the commissioning pages, the peripheral devices connected to the
universal inputs (including the extension modules) are automatically tested and
identified. If a peripheral device is missing, a fault status message will be delivered
• The operator unit can be removed and plugged in or connected while the controller is
operating
• If adaptations to specific plants are required, they must be recorded and the
documentation kept inside the control panel
• For the procedure to be followed when starting up the plant for the first time, refer to
the installation instructions
9/18
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
CE1N3150en
30 May 2008
General notes
Maintenance
The universal controller RMU7..B is maintenance free (no battery changes, no fuses).
The housing may only be cleaned with a dry towel.
Repair
The universal controller cannot be repaired on site.
Disposal
The universal controller is subject to Directive 2002/96/EG (WEEE, Waste of Electrical
and Electronic Equipment).
"The device is considered electronics device for disposal in terms of European Directive
2002/96/EG (WEEE) and may not be disposed of as domestic garbage.
The corresponding national, legal regulations must be observed and the device must
be disposable via the appropriate channels. Observe all local and applicable laws.”
Technical data
Rated voltage
Safety extra low-voltage (SELV) / protective extra low-voltage
(PELV) to
Requirements for external safety isolating transformer (100 %
ED, maximum 320 VA) to
Frequency
Power consumption (excl. modules)
Supply line fusing
AC 24 V ± 20 %
Functional data
Clock reserve
48 hours typical, min. 12 hours.
Universal inputs
Measured value inputs (X…)
Number
Sensors
Passive
refer to "Type summary"
Power supply (G, G0)
Active
Status inputs (X...)
Outputs
Positioning outputs Y
Switching outputs
AC 230 V (Q1x...Q7x)
Contact sensing
Voltage
Current
Requirements for status contacts
Signal coupling
Type of contact
Insulating strength against mains potential
Requirements for pulse contacts
Signal coupling
Type of contact
Mechanical transmitter (reed contract)
Maximum pulse frequency
Minimum pulse length
Electronic transmitter
Maximum pulse frequency
Minimum pulse length
Insulating strength against mains potential
HD 384
EN 60 742 / EN 61 558-2-6
50/60 Hz
12 VA
max. 10 A
LG-Ni 1000, T1, Pt 1000
2x LG-Ni 1000 (averaging)
0…1000 Ω,
DC 0...10 V
DC 15 V
5 mA
potential-free
maintained contact
AC 3750 V to EN 60 730
Screened cable recommended
potential-free
Pulse contact
25 Hz
20 ms (with max. 10 ms bounce
length)
100 Hz
5 ms
AC 3750 V to EN 60 730.
Perm. resistance
Contacts closed
Contacts open
max. 200 Ω
min. 50 kΩ
Number of positioning and switching outputs
Output voltage
Output current
Max. load
refer to "Type summary"
DC 0...10 V
± 1 mA
continuous short-circuit
External supply line fusing
Non-renewable fuse (slow)
Automatic line cutout
Release characteristic
max. 10 A
max. 13 A
B, C, D to EN 60 898
10/18
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
CE1N3150en
30 May 2008
Relay contacts
Switching voltage
AC current
At 250 V
At 19 V
Switch-on current
Contact life at AC 250 V
At 0.1 A res.
At 0.5 A res.
At 4 A res.
Red. factor at ind. (cos φ = 0.6)
Insulating strength
Between relay contacts and system electronics (reinforced
insulation)
Between neighboring relay contacts (operational insulation)
Q1⇔Q2; Q3⇔Q4; Q5⇔Q6⇔Q7
Between relay groups (reinforced insulation)
(Q1, Q2) ⇔ (Q3, Q4) ⇔ (Q5, Q6, Q7).
Power supply external
devices G1
Voltage
Power
Interfaces
Konnex bus
Type of interface
Bus loading number
Bus power supply (decentral., can be switched off)
Power failure of short duration
to EN 50 090-2-2
Extension bus
Connector specification
Number of plug-in cycles
Service tool connection facility
AC 3750 V, to EN 60 730-1
AC 1250 V, to EN 60 730-1
AC 3750 V, to EN 60 730-1
AC 24 V
max. 4 A
Konnex-TP1
2,5
25 mA
100 ms with 1 extension module
4 contacts SELV / PELV
max. 10
RJ45 connector
For switching outputs (Q1x…Q7x)
(measuring errors can be corrected
on the "Settings / Inputs" menu)
max. 300 m
max. 300 m
max. 300 m
max. 300 m.
refer to Data Sheet of the signal
delivering device
max. 700 m
2-core without screening, twisted
pairs.
Max. 300 m.
Electrical connections
Connection terminals
For wires
For stranded wires without ferrules
For stranded wires with ferrules
Konnex bus connection
Spring cage terminals
2
Ø 0,6 mm ... 2.5 mm
2
0.25 ... 2.5 mm
2
0.25 ... 1.5 mm
Non-interchangeable.
Degrees of protection
Degree of protection of housing to IEC 60 529
Safety class to EN 60 730
IP 20 (when mounted)
device suited for use with equipment
of safety class II
Ambient conditions
Operation to
Climatic conditions
Temperature (housing and electronics)
Humidity
Mechanical conditions
Transport to
Climatic conditions
Temperature
Humidity
Mechanical conditions
IEC 60 721-3-3
class 3K5
0 ...50 °C
5...95 % r. h. (non-condensing)
class 3M2
IEC 60 721-3-2
class 2K3
− 25...+ 70 °C
< 95 % r. h.
class 2M2
Classifications to
EN 60 730
Mode of operation, automatic controls
Degree of contamination, controls’ environment
Software class
Rated surge voltage
Temperature for ball-pressure test of housing
type 1B
2
A
4000 V
125 °C
Permissible cable lengths
For passive measuring and positioning signals
Type of signal
LG-Ni 1000, T1
Pt 1000
0…1000 Ω
Contact sensing (status and impulse contacts).
For DC 0...10 V measuring and control signals
max. AC 250 V
min. AC 19 V
max. 4 A res., 3 A ind. (cos φ = 0.6)
min. 5 mA
min. 20 mA
max. 10 A (1 s)
Guide value
7
2 x 10 cycles
6
4 x 10 cycles (N. O.)
6
2 x 10 cycles (changeover)
5
3 x 10 cycles (N.O.)
5
1 x 10 cycles (changeover)
0.85
For Konnex bus
Type of cable
11/18
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
CE1N3150en
30 May 2008
Materials and colors
Terminal base
Controller insert
Packaging
Standards
Product safety
Automatic electrical controls for household and similar use
Applications
Special requirements for energy controllers
Electromagnetic compatibility
For use in industrial and domestic environments
Immunity
Emissions
Home and Building Electronic System (HBES)
Conformity to
EMC directive
Low voltage directive
-conformity to
Australian EMC Framework
Radio Interference Emission Standard
Environmental compatibility
The environmental product declaration CE1E3110en01
contains data on environmentally compatible product design
and assessments (RoHS compliance, materials composition,
packaging, environmental benefit, disposal)
Weight
Excl. packaging
Polycarbonate, RAL 7035 (light-grey)
Polycarbonate, RAL 7035 (light-grey)
Corrugated cardboard
EN 60 730-1
EN 60 730-2-11
EN 60 730-1
EN 60 730-1
EN 50 090-2-2
2004/108/EC
2006/95/EC
Radio communication act 1992
AS/NZS 3548
SO 14001 (Environment)
ISO 9001 (Quality)
SN 36350 (Environmentally
compatible products)
2002/95/EC (RoHS)
0,49 kg
12/18
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
CE1N3150en
30 May 2008
X1 M
X2 M G1 X3 M
G0 G1 Y1 G0 G1 Y2 G0
RMU720B
G1 Y1 G0
G, G0
G1
M
G0
X1...X8
Y1...Y4
Q2x/3x/5x/6x/7x
Q1x/4x
CE+
CE−
Notes
CE
Q11
Q33
Q12
Q14
Q34
G1 Y2 G0
G1 Y3 G0
CE
CE
Q12
G X1 M X2 M G1 X3 M X4 M G1 X5 M X6 M G1 X7 M X8 M
G0 G1 Y1 G0
Legend
CE
X6 M G1
G X1 M X2 M G1 X3 M X4 M G1 X5 M X6 M G1 X7 M X8 M
G0
RMU730B
X4 M G1 X5 M
G1 Y2 G0
G1 Y3 G0
G1 Y4 G0
CE
CE
Q12
Q11
Q23
Q33
Q53
Q14
Q24
Q34
Q54
Q11
Q23
Q33
Q41 Q63 Q73
Q14
Q24
Q34 Q42
Q44 Q64 Q74
Rated voltage AC 24 V
Output voltage AC 24 V for powering external active sensors, signal sources,
monitors or setting units
Measuring neutral for signal input
System neutral for signal output
Universal signal inputs for
LG-Ni 1000, 2x LG-Ni 1000 (averaging), T1, Pt 1000, DC 0...10 V,
0...1000 Ω (setpoint), 1000...1175 Ω (rel. setpoint), pulse, contact sensing
(potential-free)
Control or status outputs, analog DC 0...10 V Q...
Potential-free relay outputs (N.O. contact) for AC 24...230 V
Potential-free relay outputs (changeover) for AC 24...230 V
Konnex bus data line, positive
Konnex bus data line, negative
Each terminal (spring cage terminal) can only accommodate one solid wire or one
stranded wire. Double terminals are internally interconnected.
13/18
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
CE1N3150en
30 May 2008
3150G03
G
3150G02
Internal diagrams
RMU710B
3150G01
Connection diagrams
Connection diagrams
Examples:
Connections on the
measuring side
Connection diagram 1: Measuring section with passive main and auxiliary sensors and
passive signal source
3144A01
G
(3) (1)
AC 24 V
B M
G
B1 B M B5 B2 M R5
X... M
X... M
X... M
G0
N1
G0
Connection diagram 2: Measuring section with active sensor and active signal source
AC 24 V
B M G
G
B3
(1) (2) (3) (4)
GL GN out in
G1 M
X... M G1
3144A02
G
R2
X...
G0
N1
G0
Connection diagrams 3 and 4: Measuring section with CO2 / VOC- and CO2 evaluation.
AC 24 V
M
G
U1 U2
G1 M
G
G
B4
X...
G0
M
G
G1 M
3144A04
(CO2/
(CO2) VOC)
AC 24 V
G
3144A03
G
(CO2/
(CO2) VOC)
U1 U2
B4
X...
G0
N1
N1
G0
Connection diagram 5:
Measuring section with pulse
transmitter
+/-
G
X...
+/-
L
G
Δp
R1
F4
M
G0
N1
G
G0
F31
M X...
M X...
G0 G1 Y1
Q12
G0
Recommendation:
Use shielded wires
N1
B1
B3
B4
B4
B5
Q11
Q33
Q14
Q34
F31
G
Legend to the connection
diagrams 1 through 6
F32
M X...
G0
N1
F32
Y
Y3
K1
K2
G0
3150A02
AC 24 V
3150A01
G
Connection diagram 6:
AC 230 V
AC 24 V
Connections on the
control and monitoring
side
G0
N
Universal controller RMU7..B
Supply air temperature sensor
QAM2120...
B3 Frost sensor QAF63.2/QAF63...
CO2 sensor QPA2000
CO2 / VOC sensor QPA2002/QPA2002D
Room temperature sensor QAA24
F3
F4
K1, K2
R1
R2
R5
Y3
Overcurrent trigger contact
Differential pressure sensor
QBM81...
Motor contactor for fan
Reed pulse transmitter
Setpoint adjuster BSG61
Setpoint shifting unit BSG21.5
Actuating device for heating
14/18
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
CE1N3150en
30 May 2008
Overview of the preprogrammed standard applications
Controller
RMU710B
Plant type Application number / description
A01
Plant diagram
ADA001 U1B HQ
F2
I N.Q1
II N.Q3
Δp
2
Supply air temperature control with hot water air heating
M
coil.
M
Y2
B5
T
N.X2
F3
N.X3
Y1
T
T
Δp
N.X6
Δp
F4
Variant:
M3
N.X5
A7.Q1
M
A7.X1
S01
T
B9
R5
T
2
B1
N.X1
F1
N.X4
Y3
Room (extract) / supply air temperature cascade control
N.Y1
with minimum and maximum limitation of the supply air
N1
A10
A7
temperature.
A02
ADB001 U1B HQ
F2
I N.Q1
II N.Q3
Supply air temperature control with chilled water air
M
Y2
cooling coil.
M
Y1
Δp
2
T
T
2
T
R5
N.X5
Δp
F4
B1
N.X1
F1
N.X4
S01
T
Δp
B9
Variant:
B5
N.X2
N.X6
N.X3
M
Y4
Room (extract) / supply air temperature cascade control
N.Y1
with minimum and maximum limitation of the supply air
N1
A10
A7
temperature.
A03
ADC001 U1B HQ
F2
I N.Q1
II N.Q3
Supply air temperature control with hot water heating
M
Y2
coil and cold water cooling coil.
M
Y1
Δp
2
T
T
Δp
N.X6
Δp
M3
F4
N.X5
Room (extract) / supply air temperature cascade control
with minimum and maximum limitation of the supply air
N.X1
N.X4
M
Y4
N.Y1
N1
B1
F1
A7.Q1
M
Y3
R5
A7.X1
S01
T
B9
N.X2
T
2
Variant:
B5
T
F3
N.X3
N.Y2
A10
A7
temperature.
AEA001 U1B HQ
Supply air temperature control with mixing air dampers
and hot water heating coil in sequence.
F2
I N.Q1
II N.Q3
Δp
2
Y2
M
Y1
M
T
F3
Y6
N.X3
N.Y2
T
2
T
T
T
Δp
B9
Variant:
AQ
M
N.X6
Δp
F4
M3
N.X5
A7.Q1
M
Room (extract) / supply air temperature cascade control
B4
A7.X1
B5
N.X2
R5
A7.X2
S01
A04
B1
N.X1
F1
N.X4
Y3
N.Y1
with minimum and maximum limitation of the supply air
N1
A7
A10
temperature.
ADAE01 U1B HQ
Supply air temperature control with plate heat recovery
system and hot water air heating coil in sequence.
F5
I N.Q1
II N.Q3
Δp
B10
A7.X1
2
Y2
M
Y1
M
T
Δp
T
F2
F3
N.X3
T
2
T
B9
Variant:
N.X6
Δp
F4
M3
M
N.X5
Y6
N.Y2
Room (extract) / supply air temperature cascade control
with minimum and maximum limitation of the supply air
T
T
Δp
A7.Q1
M
F1
B1
B5
N.X2
R5
A7.X2
S01
A05
N.X1
N.X4
Y3
N.Y1
N1
A10
A7
temperature.
15/18
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
CE1N3150en
30 May 2008
RMU720B
Plant type Application number / description
A01
Plant diagram
AEC001 U2B HQ
Supply air temperature control with mixing air dampers
and cold water cooling coil in sequence.
F2
I N.Q1
II N.Q2
Δp
2
Y2
M
Y1
M
Y6
N.X3
N.Y2
T
N.X6
Δp
F4
M3
N.X5
N.X1
N.X4
M
N.Y3
N.Y1
N1
B1
Y4
Y3
Room (extract) / supply air temperature cascade control
F1
N.Q3
M
R5
N.X8
T
T
Δp
with minimum and maximum limitation of the supply air
N.X2
T
2
B4
N.X7
B5
T
F3
B9
Variant:
AQ
M
S01
Controller
A7
A10
temperature.
ADCE01 U2B HQ
Supply air temperature control with plate-type heat
recovering, hot water heating coil and cold water
cooling coil in sequence.
F5
I N.Q1
II N.Q2
Δp
B10
N.X7
2
Y2
M
Y1
M
T
Δp
T
F2
F3
N.X3
T
2
T
T
T
Δp
B9
N.X6
Δp
M
F4
N.X5
M3
Y6
Y3
Variant:
N1
R5
N.X8
B1
N.X1
N.X4
M
Y4
N.Y1
Room (extract) / supply air temperature cascade control
F1
N.Q3
M
N.Y2
B5
N.X2
S01
A02
N.Y3
A7
A10
with minimum and maximum limitation of the supply air
temperature.
ADFB01 U2B HQ
Supply air temperature control with hot water heating
coil and cold water cooling coil.
Room humidity control with steam humidifier.
F2
I N.Q1
II N.Q2
Δp
2
Y2
Y1
T
ϕ
T
M
B16
N.X2, N.X3
F3
M
N.X4
T
2
T
T
N.X8
Y12
M3
N.X7
N.Q3
M
B17
F1
N.Y3
N.Q5
M
Y3
Variant:
N.X1
N.X5
N.X6
Y4
N.Y1
N1
A7.X1
Δp
F4
Room (extract) / supply air temperature cascade control
R5
ϕ
T
T
Δp
B9
S01
A03
N.Y2
A7
A10
with minimum and maximum limitation of the supply air
temperature.
AEDB01 U2B HQ
Supply air temperature control with mixing air dampers
and hot water heating coil in sequence.
Room humidity control with steam humidifier.
F2
I N.Q1
II N.Q2
Δp
2
Y2
ϕ
T
T
M
Y1
M
B16
N.X2, N.X3
M
Y6
B4
AQ
F3
A7.X1
N.X4
N.Y2
2
T
T
N.X8
R5
T
A7.X2
ϕ
T
T
Δp
Δp
B9
S01
A04
F4
Y12
M3
N.X7
M
N.Y3
N.Q5
N.Q3
F1
N.X6
B17
N.X1
N.X5
Y3
Variant:
N.Y1
Room (extract) / supply air temperature cascade control
N1
A7
A10
with minimum and maximum limitation of the supply air
temperature.
ADDP01 U2B HQ
Supply air temperature control with thermal wheel heat
recovery system and hot water air heating coil in
sequence.
Room humidity control with steam humidifier.
F5
I N.Q1
II N.Q2
Δp
B10
A7.X1
2
Y2
M
Y1
N.X2, N.X3
F3
M
N.X4
T
2
T
B9
N.X8
T
T
Δp
ϕ
T
Δp
F4
M3
Y11
N.X7
ϕ
T
B16
F2
N.Y2
N.Q3
M
Y12
N.Y3
N.Q5
F1
N.X6
R5
A7.X2
B17
N.X1
N.X5
Y3
Variant:
Room (extract) / supply air temperature cascade control
T
T
Δp
S01
A05
N.Y1
N1
A10
A7
with minimum and maximum limitation of the supply air
temperature.
16/18
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
CE1N3150en
30 May 2008
RMU730B
Plant type Application number / description
A01
Plant diagram
AEFB01 U3B HQ
Supply air temperature control with mixing air dampers
and cold water cooling coil in sequence.
Room humidity control with steam humidifier.
F2
I N.Q1
II N.Q2
Δp
2
Y2
ϕ
T
T
M
Y1
M
B16
N.X2, N.X3
M
AQ
F3
Y6
N.X4
N.Y2
2
T
N.X8
F4
Y12
M3
N.Q3
M
Y3
Variant:
N1
N.X1
N.X5
N.X6
Y4
N.Y3
N.Y1
Room (extract) / supply air temperature cascade control
B17
F1
N.Y4
N.Q4
M
A7.X2
ϕ
T
T
Δp
N.X7
R5
T
T
Δp
B9
B4
A7.X1
S01
Controller
A7
A10
with minimum and maximum limitation of the supply air
temperature.
ADFP01 U3B HQ
Supply air temperature control with rotating heat
recovery device, hot water heating coil and cold water
cooling coil in sequence.
Room humidity control with steam humidifier.
F5
I N.Q1
II N.Q2
Δp
B10
A7.X1
2
Y2
Δp
B16
F2
Y1
N.X2, N.X3
F3
M
N.X4
T
T
Δp
N.X8
F4
Y12
M3
Y11
N.Y2
N.Q3
M
Y3
N.Y4
N.Q4
M
B17
F1
N.X1
N.X5
N.X6
Y4
N.Y1
N1
A7.X2
ϕ
T
Δp
N.X7
Variant:
R5
T
2
T
B9
ϕ
T
T
T
M
S01
A02
N.Y3
A7
A10
Room (extract) / supply air temperature cascade control
with minimum and maximum limitation of the supply air
temperature.
ADZA01 U3B HQ
Room (extract air) / supply air temperature cascade
control with minimum and maximum limitation of the
supply air temperature, with hot water air reheater and
chilled water air cooling coil in sequence.
F2
I N.Q1
II N.Q2
Δp
2
Y2
Y1
ϕ
T
T
M
B16
N.X2, N.X3
F3
M
N.X5
T
2
T
T
T
Δp
B9
A7.X1
F4
Room humidity control with spray humidifier (release).
M3
N1
M9
M
B17
F1
N.X7
M
N.Q4
Y4
N.Y1
Dewpoint temperature control (supply air humidity
N.X4
N.Q3
M
Y3
A7.X2
Δp
B27
N.X8
R5
ϕ
T
T
S01
A03
N.X1, N.X6
Y10
N.Y3
N.Y2
A10
A7
constant) with hot water air preheating and cold water
air cooler in sequence.
AEZH01 U3B HQ
Room (extract air) / supply air temperature cascade
control with minimum and maximum limitation of the
supply air temperature, with hot water air reheater and
chilled water air cooling coil in sequence.
F2
I N.Q1
II N.Q2
Δp
2
Y2
T
M
N.Y2
M
ϕ
T
B16
N.X2, N.X3
M
Y1
AQ
F3
Y6
N.X5
2
T
A7.X1
B27
F4
N.X8
M
N.Q3
Y3
Room humidity control with spray humidifier (release).
Dewpoint temperature control (constant supply air
N1
N.X4
M3
M9
M
N.Q4
Y4
M
Δp
F1
N.X7
T
A7.X2
R5
A7.X3
ϕ
T
B17
N.X1
N.X6
Y10
N.Y4
N.Y1
T
T
T
Δp
B9
B4
S01
A04
N.Y3
A7
A10
humidity) with mixed air dampers, hot water air
preheater and chilled water air cooling coil in sequence.
AEZH02 U3B HQ
Room (extract air) / supply air temperature cascade
F2
I N.Q1
II N.Q2
Δp
2
Y2
T
M
control with minimum and maximum limitation of the
N.Y2
supply air temperature, with mixed air dampers, hot
B9
Y1
M
AQ
F3
Y6
N.X5
2
water air reheater and chilled water air cooling coil in
T
T
T
Δp
A7.X1
N.X8
N.X4
M3
M
N.Q3
Y3
A10
M9
N.Q4
F1
M
M
Y4
Y10
N.Y4
N.Y1
N1
Δp
B27
F4
sequence.
Room humidity control with spray humidifier (release)
ϕ
T
B16
N.X2, N.X3
M
N.X7
T
T
ϕ
T
B4
A7.X2
R5
A7.X3
S01
A05
B17
N.X1
N.X6
N.Y3
A7
and cold water air cooling.
Dewpoint temperature control (constant supply air
humidity) with hot water air preheater.
17/18
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
CE1N3150en
30 May 2008
Dimensions
80
5
173
3
44
RMZ790
66,4
=
EN 60 715-TH 35-7.5
=
3144M01
3
=
35
90
45
=
ø 5,2
3
2
5
ø 10,5
18
153
Dimensions in mm
18/18
©2007 - 2008 Siemens Switzerland Ltd
Building Technologies
HVAC Products
Universal controllers RMU710B, RMU720B, RMU730B
Subject to change
CE1N3150en
30 May 2008