3 Ton Split System Cooling — 1 Ph
4TTX8036A
NOTE: All dimensions are in mm/inches.
Product Specifications
OUTDOOR UNIT 12
POWER CONNS. — V/PH/HZ 3
MIN. BRCH. CIR. AMPACITY
BR. CIR. PROT. RTG. – MAX. (AMPS)
COMPRESSOR
NO. USED - NO. STAGES
VOLTS/PH/HZ
R.L. AMPS 7 - L.R. AMPS
FACTORY INSTALLED
START COMPONENTS 8
INSULATION/SOUND BLANKET
COMPRESSOR HEAT
OUTDOOR FAN
DIA. (IN.) - NO. USED
TYPE DRIVE - NO. SPEEDS
CFM @ 0.0 IN. W.G. 4
NO. MOTORS - HP
MOTOR SPEED R.P.M.
VOLTS/PH/HZ
F.L. AMPS
OUTDOOR COIL — TYPE
ROWS - F.P.I.
FACE AREA (SQ. FT.)
TUBE SIZE (IN.)
REFRIGERANT
LBS. — R-410A (O.D. UNIT) 5
FACTORY SUPPLIED
LINE SIZE - IN. O.D. GAS 6
LINE SIZE - IN. O.D. LIQ. 6
CHARGING SPECIFICATION
SUBCOOLING
DIMENSIONS
CRATED (IN.)
WEIGHT
SHIPPING (LBS.)
NET (LBS.)
MODELS
BASE
A
B
C
D
E
F
G
H
J
K
4
1369
(53-7/8)
946
(37-1/4)
870
(34-1/4)
3/4
3/8
152 (6)
98
(3-7/8)
219
(8-5/8)
86
(3-3/8)
730
(28-3/4)
NO
NO
NO
PROPELLER
27.6 - 1
DIRECT - 1
3700
1 - 1/8
835
208/230/1/60
0.74
SPINE FIN™
1 - 24
30.79
3/8
R-410A
9 LBS.- 13 OZ.
YES
3/4
3/8
9°F
H X W X D
57.4 X 35.1 X 38.7
316
266
1 Certified in accordance with the Air-Source Unitary Air-conditioner Equipment certification
program, which is based on AHRI standard 210/240. In order to achieve AHRI standard rating,
the indoor fan time delay on the comfort control must be enabled.
2 Rated in accordance with AHRI standard 270.
3 Calculated in accordance with Natl. Elec. Codes. Use only HACR circuit breakers or fuses.
4 Standard Air — Dry Coil — Outdoor
5 This value approximate. For more precise value see unit nameplate.
6 Max. linear length 60 ft.; Max. lift - Suction 25 ft.; Max lift - Liquid 25 ft. For greater length consult
refrigerant piping software Pub. No. 32-3312-0* (* denotes latest revision).
7 This value shown for compressor RLA on the unit nameplate and on this specification sheet
is used to compute minimum branch circuit ampacity and max. fuse size. The value shown is
the branch circuit selection current.
8 No means no start components. Yes means quick start kit components. PTC means positive
temperature coefficient starter.
From Dwg. D152635 Rev. 15
4TTX8036A
4TTX8036A1000A
208/230/1/60
24
35
CLIMATUFF® - SCROLL
1-2
208/230/1/60
17.0 - 82
Sound Power Level
Full Octave Sound Power [dB]
Model
A-Weighted Sound
Power Level [dB(A)]
63 Hz
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
4TTX8036A1
72
64
67
65
64
60
56
54
50
Note: Rated in accordance with AHRI Standard 270-2008
© 2013 Trane
Mechanical
­Specification Options
General
The 4TTX8 is fully charged from the factory for matched indoor section and up
to 15 feet of piping. This unit is designed
to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection
of air handlers and furnace coils that are
AHRI certified. The unit shall be certified to UL 1995. Exterior is designed for
outdoor application.
Condenser Coil
The outdoor coil provides low airflow
resistance and efficient heat transfer.
The coil is protected on all four sides by
louvered panels.
Low Ambient Cooling
As manufactured, this unit has a cooling capability to 55°F. For low ambient
cooling below 55° see Application Guide
APP-APG013-EN.
Casing
Unit casing is constructed of heavy
gauge, G60 galvanized steel and
painted with a weather-resistant powder
paint on all louvers and panels. Corrosion and weatherproof CMBP-G30
DuraTuff™ base.
Refrigerant Controls
Refrigeration system controls include
condenser fan, compressor contactor
and high pressure switch. High and low
pressure controls are inherent to the
compressor. A factory installed liquid line
drier is standard.
Compressor
The Climatuff® 2-stage compressor
features internal over temperature and
pressure protection and hermetic motor.
Other features include centrifugal oil
pump and modular plugs for electrical
connections.
Trane
www.trane.com
05/13
Trane has a policy of continuous product and product data improvement and it reserves the right to change
design and specifications without notice.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising