JSP 80
SURGE SUPPRESSION SYSTEM
PRODUCT SPECIFICATIONS
SYSTEM FEATURES AND BENEFITS
• Fail- Safe Design with individually fused MOV’s that eliminate single
point failure protecting against both over-current and over-voltage
events.
• 200 KAIC Short Circuit Rating permits direct buss connection to most
electrical services.
• Proven Performance and Tested at its full rated surge capacity by
a nationally recognized third-party laboratory using NEMA-LS1 test
procedure with a fully configured standard unit.
• Low Let Through Voltage ensured by the lowest possible impedance
path to ground and equal current sharing during surge events.
• Extended Durability and proven to exceed 3,250 surges of 10,000
amps/mode using the ANSI/IEEE C62.41.1 2000 and IEC 61643
test procedures.
• Compact Design provides superior surge protection in a
6”H x 6”H x 4”D housing.
• All Weather sealed, powder-coated NEMA 4/IP65 housing is designed
for any orientation and indoor/outdoor applications.
• 10-Year Standard Warranty with optional 15-year extended warranty.
MODEL NUMBER SCHEME
PRODUCT SPECIFICATIONS
Available Configurations
General Specifications
Model Number
Voltage
Configuration
JSP080-1P120
120V
Single Phase 2-wire + grd
JSP080-1P240*
240V
Single Phase 2-wire + grd
JSP080-1S240
120/240V
Split-Phase 3-wire + grd
JSP080-3Y208
120/208V
Three-Phase 4-wire + grd
JSP080-3Y380*
220/380V
Three-Phase 4-wire + grd
JSP080-3Y415*
240/415V
Three-Phase 4-wire + grd
JSP080-3Y480
277/480V
Three-Phase 4-wire + grd
JSP080-3H240
120/240V
Three-Phase High-Leg
4-wire + grd
*Denotes units that are CE listed
Units suitable for TT and IT grounded power systems available upon request.
Consult factory for model number.
Available Options
Transient Filter that meets UL 1283*:
add suffix “-F”
Stainless Steel Enclosure:
add suffix “-S”
Maximum Surge Current Rating:
Repetitive Surge Current Rating:
Product Design:
Regulatory Listing:
80kA per phase; 40kA per mode
3,250 impulses 10,000 amps/mode using the
ANSI/IEEE C62.41.1 2000 and IEC 61643 test
procedures
Parallel design with individual fused MOVs and
optional UL 1283 EMI/RFI filter
UL 1449 2nd Edition 2005 Revision
(effective 2/9/2007), UL 1283,
CE on 220, 230, and 240V units
Warranty:
10-Year Standard, 15-Year Extended
Electrical Specifications
Operating Frequency:
47-63 Hz
Connection Method:
Parallel to electrical distribution system
Modes of Protection:
L-N, L-G, N-G, & L-L
Fault Rating (SCCR):
200kAIC – no upstream over-current
protection device (breaker or fuse) required
Response Time:
Less than 0.5 nanoseconds
Standard Monitoring:
Status indicator lights (one per phase)
*Not recommended when using telecommunication rectifiers
Stand-Alone Options (To Be Ordered As A Separate Item)
JSP-FMP
Flush-Mount Plate Kit
EMI/RFI Filter Attenuation – Mil Standard 220B
Max. Attenuation Freq.
41 dB @ 106kHz
Made in U.S.A.
Page 1 of 2
ventas@siesamx.com
SURGE SUPPRESSION SYSTEM
JSP 80
Dimensional Specifications Typical 3-Phase Installation
Dim
H1
H2
H3
W1
W2
D1
D2
JSP 80
6.00
6.75
7.50
6.00
4.00
4.16
2.50
4-Wire WYE
(152.4)
(171.5)
(190.5)
(152.4)
(101.6)
(105.7)
(63.5)
JSP
RED
ORN
All measurements in inches (mm)
2
JSP
Mechancial Specifications
Enclosure Type:
Altitude
Powder coated, impact-resistance steel,
weather-proof NEMA 4
Indoor or outdoor
6"H x 6"W x 4”D (152.4 x 152.4 x 105.2)
Pre-wired with 36 inches(910mm) of #10AWG(5.27mm2)
conductor
Dual mounting flanges
-40° C to +70° C (-40° F to +158° F)
5% - 95% non-condensing humidity
Up to 13,000 ft. (4000m)
Weight:
10 lbs. (4.5 kg)
Installation Location:
Dimensions:
Connection Method:
Mounting Method:
Operating Environment:
JSP 80 Performance Data
ANSI/IEEE C62.41.1-2002, C62.41.2-2002, & C62.45-2002
Measured Limiting Voltage
Model
Number
Voltage
Configuration
JSP080-1P120
1P120
JSP080-1P240
1P240
JSP080-1S240
1S240
JSP080-3Y208
3Y208
JSP080-3Y380
3Y380
JSP080-3Y415
3Y415
JSP080-3Y480
3Y480
JSP080-3H240
3H240
Protection
Mode
L-N
L-G
N-G
L-N
L-G
N-G
L-N
L-G
L-L
N-G
L-N
L-G
L-L
N-G
L-N
L-G
L-L
N-G
L-N
L-G
L-L
N-G
L-N
L-G
L-L
N-G
L-N
H-N
L-G
H-G
L-L
H-L
N-G
MCOV
B3 Ring Wave
6kV, 500A
B3/C1 Combo
Wave 6kV, 3kA
C3 Combo
Wave 20kV, 10kA
UL 1449 2nd
2005 Revision
6kV, 500A SVR
150V
150V
150V
320V
320V
320V
150V
150V
300V
150V
150V
150V
300V
150V
320V
320V
640V
320V
320V
320V
640V
320V
320V
320V
640V
320V
150V
320V
150V
320V
320V
470V
150V
202V
529V
548V
180V
855V
840V
202V
529V
290V
548V
202V
529V
290V
548V
180V
855V
261V
840V
180V
855V
261V
840V
180V
855V
261V
840V
202V
180V
529V
855V
290V
840V
548V
587V
564V
594V
1036V
989V
989V
587V
564V
1029V
594V
587V
564V
1029V
594V
1036V
989V
1847V
989V
1036V
989V
1847V
989V
1036V
989V
1847V
989V
587V
1036V
564V
989V
1029V
1250V
594V
1078V
1157V
1180V
1553V
1483V
1470V
1078V
1157V
1667V
1180V
1078V
1157V
1667V
1180V
1553V
1483V
2520V
1470V
1553V
1483V
2520V
1470V
1553V
1483V
2520V
1470V
1078V
1553V
1157V
1483V
1667V
1640V
1180V
400V
400V
400V
800V
800V
800V
400V
400V
800V
400V
400V
400V
800V
400V
800V
800V
1500V
800V
800V
800V
1500V
800V
800V
800V
1500V
800V
400V
800V
400V
800V
800V
1500V
400V
All JSP ™ systems measured limited voltages are peak values (±10%) measured from the zero reference point and are in compliance with test and evaluation procedures
outlined in NEMA LS1-1992 (R2000), paragraphs 2.210 and 3.10.
Specifications subject to change without notice, refer to www.joslynsurge.com for latest revision.
ventas@siesamx.com
©2007 Joslyn® and JSP.™ Made in U.S.A.
1M/9.6.07/JSP80
Page 2 of 2
5900 Eastport Boulevard Richmond, VA 23231-4453 USA
TEL: 804.236.3300 800.238.5000 FAX: 804.236.4047
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising